KELSEY CENTRIFUGAL JIG (KCJ) PILOT PLANT FUNCTIONAL SPECIFICATION

Size: px
Start display at page:

Download "KELSEY CENTRIFUGAL JIG (KCJ) PILOT PLANT FUNCTIONAL SPECIFICATION"

Transcription

1 KELSEY CENTRIFUGAL JIG (KCJ) PILOT PLANT FUNCTIONAL SPECIFICATION MT Project Number: Revision Date Revision Description BY APPROVED A 04/08/09 Issued for Internal Review TJ AF B 05/03/10 Revised AF AF C 06/04/10 Revised / Updated AF / TJ / SG AF D 10/05/10 Updated with Exxaro Plant Interfaces DE / TJ AF E 17/05/10 Updated with Commissioning Data Tables TJ AF

2 TABLE OF CONTENTS 1 INTRODUCTION Section A: OVERALL PILOT PLANT OPERATION Process Description Overall Process Process Water Sump Level Control Exxaro Feed Preparation Plant Exxaro Product Handling Facility KCJ Pilot Plant Start up and Shutdown Procedures Plant Start-Up Sequence Start Interlocks Plant Start Sequence Jig Feed Start-Up Sequence Start Interlocks Jig Feed Start Sequence Plant Shutdown Sequence KCJ Pilot Plant Alarms Full Pilot Plant Shutdown Alarms Feed Off Alarms Adjustable Pump Minimum and Maximum Speed Set Points Jig Feed Pump (PU-01) Final Tails Pump (PU-02) Jig Tails Pump (PU-03) Interface Signals Between Client Feed and Pilot Plant Pilot Plant Ready for Feed Signal Pilot Plant Faulted Signal Exxaro Feed Preparation Plant Exxaro Final Tails and Final Concentrate Discharge System Fault Shutdowns Operator Controls Section B: MODEL J1800 KELSEY JIG OPERATION Drives Jig Spin Motor Jig Pulse Motor Screen Clean Motor Blast Pump Motor Lube Pump Motor Solenoid Valves Swing Arm Solenoid Valve Blast Rod Solenoid Valves Instruments Vibration Transmitter Jig Feed Flow Transmitter Hutch Water Flow Transmitter Hutch Water Pressure Transmitter Lube Oil Tank Level Switch Lube Oil Supply Pressure Switch Air Pressure Switch Swing Arm Actuator Reed Switches (ZS32 and ZS33) Blast Rod Actuator Reed Switches (ZS25 and ZS31) Sequences Jig Start up Sequence Start Signal Stop Signal Start Interlocks Sequence Jig Shutdown Sequence

3 Start Signal Stop Signal Sequence Jig Flush Sequence Start Signal Stop Signal Start Interlocks Sequence Jig Screen Clean Sequence Start Signal Stop Signal Start Interlocks Sequence Jig Fast Shutdown Sequence Start Signal Stop Signal Start Interlocks Sequence Alarms Fast Trips Process Shutdown Alarms Jig Motor Fault Alarms Jig Spin Motor Jig Pulse Motor Lube Pump Motor Blast Pump Motor Screen Clean Motor Adjustable Control and Alarm Set Points Sequence Control Set Points Control Set Points Alarm Set Points Table of Alarm and Control Commissioning Setpoints PAGE: ENGR DATA ENTRY PUMPS PAGE: ENGRS DATA ENTRY JIG PAGE: SEQUENCES PAGE: SEQUENCES PAGE: ALARM SETPOINTS PAGE: ALARM SETPOINTS PAGE: ALARM SETPOINTS PAGE: EXXARO SETPOINTS PAGE: PLANT SEQUENCES PAGE: JIG CONTROL PAGE: JIG DRIVES PAGE: VFD PUMPS PAGE: PUMPS

4 1 INTRODUCTION This document describes the control and operation of the Kelsey Centrifugal Jig (KCJ) Pilot Plant as configured for Exxaro Namakwa Sands. As the control and sequences of the KCJ are far more complex relative to the overall plant, this document is divided into two sections as outlined below to make referencing easier: Section A covers the overall KCJ Pilot Plant function including the screen, pumps, KCJ, etc. Section B covers in more detail the various KCJ functions that form part of the overall plant. The Control of the KCJ Pilot Plant has two modes of operation: Automatic Mode o In this mode, there will be pre-defined sequences that the Operator will have to manually start. o A sequence cannot start until all the other sequences have stopped Manual Mode o In this mode, each drive can be operated independently from the HMI A process description, start up and shut down sequences, interlocks and other information are provided in this document. 4

5 2 Section A: OVERALL PILOT PLANT OPERATION 2.1 Process Description Referring to: Flow sheets: Exxaro NSL Pilot Plant 2009 PFD - 40tph (Rev G) Exxaro NSL Pilot Plant 2009 PFD - 25tph (Rev G) Exxaro NSL Pilot Plant 2009 PFD - 10tph (Rev G) P+ID Exxaro KCJ Pilot Plant P+ID (Rev D) Overall Process Feed at t/h solids and % solids by mass is pumped by the client (after removal of +1 mm material) from their Feed Preparation Plant (not shown on PFD or P&ID) to the Plant Feed Surge Bin (SB-01) located on the bottom of the screening module. A manual sampler at the entry to SB-01 allows for sampling of the incoming feed to the plant. Feed material from BIN-01 is pumped (by PU-06) via a 3-way gravity distributor (DS-01) which in turn feeds each of the lower 3 feed preparation decks of the Derrick Stack Sizer Screen (SC-01). These feed preparation screen decks have 210 μm apertures designed to cut the feed to a top size of 250 μm, with the undersize reporting to the Jig Feed Sump (SU-01) via a discharge chute (CH-01) and the oversize reporting to the Final Tails Sump (SU-02) via a discharge chute (CH-02). Sampling of the undersize stream requires a portable manual sampler which can be placed under the main flow into SU-01. A manual sampler is installed to enable a sample of the oversize stream to be taken. Undersize material is pumped (by PU-01) to a bank of two (2) dewatering cyclones (CY- 01&02). Overflow from these cyclones reports to the Motive Water Sump (SU-05) via a manual sampler. The cyclone underflow constitutes the KCJ feed at 30-50% solids by mass and is discharged by gravity into the KCJ, with an in-line flow transmitter measuring the feed rate into the KCJ. A bypass facility allows the KCJ feed (cyclone underflow) to discharge directly to the Jig Tails Sump (SU-03) during start up, screen cleaning and minor trip / alarm clearing procedures. The bypass process is performed by two actuated knife gate valves located on the dewatering cyclone underflow tank (TA-02) that operate in opposite tandem when one is open the other is shut and vice versa. A manual sampler is installed above the entry to the Jig Tails Sump (SU-03) which enables a sample of KCJ feed to be taken during feed diversion. KCJ concentrate reports to the Jig Concentrate Sump (SU-04) via a manual sampler and is pumped (by PU-04) to the client Product Handling facility (not shown on PFD or P&ID). KCJ tailings containing ragging report to the Jig Tails Sump (SU-03) via a manual sampler. The KCJ tailings are pumped (by PU-03) to the top ragging recovery deck of the Derrick Stack Sizer Screen (SC-01). The coarse ragging is scalped out of the KCJ tails with a 500 μm screen deck (designed to cut the tailings and maintain a ragging bottom size of 600 μm) and discharged via chutes back to the Jig Feed Sump (SU-01). The underflow from the ragging recovery deck constitutes final tailings and is discharged to the Final Tails Sump (SU-02). A jet pump (JP-02) located at the bottom of the Final Tails Sump pumps the tailings to the suction of the Final Tails Pump (PU-02), which then pumps the tailings to the client Product Handling facility (not shown on PFD or P&ID). Motive water to drive the jet pump (JP-02) is supplied from the Motive Water Sump (SU-05) via the Motive Water Pump (PU-05) and motive pressure is set via a hand operated diaphragm valve and manual pressure gauge. 5

6 2.1.2 Process Water A Process Water Tank (TA-01) located in the bottom section of the screening module is fed by the client via a pilot operated float valve, which will regulate the inflow of process water assuming the water supply comes from a client water supply manifold with other users. If a dedicated water supply pump is used to feed water to the plant then a level sensor linked to either the water supply pump speed or a proportional control valve may be required to control in place of the float valve to avoid dead heading the pump. In the event of oversupply, the water sump overflows into the Final Tails Sump (SU-02) if overfilled. A low level switch in the tank protects the pumps from running dry. A Process Water Pump (PU-07) supplies process water to: Derrick Stack Sizer Screen (SC-01) sprayers KCJ screen cleaner and lubrication system Sump make-up lines KCJ hutch water is supplied by a dedicated Hutch Water Pump (PU-08). Pressure control valves are located in the discharge lines from both PU-07 and PU-08, allowing the system pressure in both these circuits to be adjusted as required. Two sets of 500 µm in-line filters with isolation valves are fitted in parallel in the hutch water delivery line. One filter set at a time is required for operation, allowing the second set to be cleaned without stopping the plant. A flow meter, pressure transducer and pressure gauge are also fitted in the hutch water delivery line to allow the flow rate and pressure to be monitored and interlocked with the operation of the KCJ pulse system via the control system. Two sets of 50 µm in-line filters with isolation valves are fitted in parallel in the process water delivery line prior to the KCJ screen cleaner (blast pump, pre-wash water and scraper head flush) and lubrication system (cooling water). One filter set at a time is required for operation, allowing the second set to be cleaned without stopping the plant Sump Level Control The method of sump level control for each pump and sump is described individually below: PU-01 / SU-01 Jig Feed Sump This pump feeds the dewatering cyclones and requires a constant speed to ensure constant cyclone feed pressure. A VFD (variable frequency drive) is fitted to this pump for initial speed setting only. Sump level control is achieved with a level transmitter and a make up water solenoid valve system driven by a switching controller. PU-02 / SU-02 Final Tails Sump Sump level control is achieved with a level transmitter and VFD on the pump operating in a PID control loop. 6

7 PU-03 / SU-03 Jig Tailings Sump Sump level control is achieved with a level transmitter and VFD on the pump operating in a PID control loop. A float valve is also installed and can be used to assist with sump level control if necessary by opening a manual isolation valve. PU-04 / SU-04 Jig Concentrate Sump This pump is a fixed speed pump. Level control is achieved via a float valve. A pump suction water injection point will also assist with maintaining level. A low level sensor is installed to shut the pump down should the sump run dry. PU-05 / SU-05 Motive Water Sump This pump is a fixed speed pump. Level control is achieved with a float valve. A low level sensor is installed to shut the pump down should the sump run dry. PU-06 / SB-01 Screen Feed Bin Sump level control is achieved with a level transmitter and VFD on the pump operating in a PID control loop. PU-07 and PU-08 / TA-01 Process Water Sump The client feeds water at the correct rate (or just above) into the process water sump via the inlet manifold. The water sump overflows into the Final Tails Sump (SU-02) and the overflow from SU-02 is lower than this level, preventing solids overflowing back into the water sump. A low level sensor is installed to shut the pump down should the sump run dry. In the case of the client supplying water from a manifold with other users, a pilot operated 150NB shut off valve (installed on the inlet flange) will stop flow into the tank should the inflow exceed the outflow. If the client will be using a dedicated water supply pump then a client supplied level sensor and control loop back to the client s water supply pump or alternatively a client supplied proportional control valve in the client water supply line to the plant will be required Exxaro Feed Preparation Plant Concentrate is pumped from the Jig Plant Concentrate sump (SU-04) to an up-current classifier which replaces sea water with fresh water. UCC overflow is directed to the main bunded area floor for removal by a sump pump, while UCC underflow is pumped by a Cons Pump (611) via a dewatering hydrocyclone to final stacking Exxaro Product Handling Facility Tails are pumped from the Jig Plant Final Tails sump (SU-02) via a dewatering hydrocyclone to a Tails sump. Cyclone underflow is directed into a Tails sump, while overflow is split between the Tails sump (to control slurry volume/density for pumping) and the main bunded area floor for removal by a sump pump. Three pumps (Tails Pumps 612A, B & C) in series pump the slurry 1.8km from the Tails sump to disposal at the PCP West Plant. 7

8 2.2 KCJ Pilot Plant Start up and Shutdown Procedures Plant Start-Up Sequence Start Interlocks At start up it is assumed that the water sump (TA-01) is full and all actuated valves and drives are healthy to start subject to interlocks. Start-up interlocks: All Jig drives are in Automatic Mode and Healthy o Jig Spin Motor o Jig Pulse Motor o Jig Lube Pump o Jig Screen Clean Reciprocating Motor o Jig Blast Pump o Hutch Water Isolation Valve in Auto Screen Cleaner Swing Arm retracted, in Auto and Healthy Screen Cleaner Blast Rod up, in Auto and Healthy No other sequence running All E-stops healthy No Category 1 or 2 Alarms Derrick Screen Feed Pump (PU-06) in Auto and Healthy Jig Feed Diverter knife gate valves are in Bypass position Vibrating Screen (SC-01) in Auto and Healthy Jig Feed Pump (PU-01) in Auto and Healthy Jig Tailings Pump (PU-03) in Auto and Healthy Jig Concentrate Pump (PU-04) in Auto and Healthy Final Tails Pump (PU-02) in Auto and Healthy Motive Water Pump (PU-05) in Auto and Healthy Process Water Pump (PU-07) in Auto and Healthy Hutch water pump (PU-08) in Auto and Healthy Compressor power is on and air receiver is fully charged to 600 kpa (this is checked manually) Plant Start Sequence For the Exxaro plant set-up, before a plant start is initiated: Operator starts Exxaro Feed Preparation Plant slurry pump on water Water enters the Jig Plant Surge Bin (SB-01) and, once the Jig Plant start is initiated, when this bin level reaches a pre-set (adjustable) level the Derrick Screen Feed Pump (PU-06) will start 8

9 The Plant Start-up Sequence is then as follows: Start up alarm sounds for 5 sec. Jig feed diverter knife gate valves shift to Bypass position Start Jig Lube Motor Start Vibrating Screen (SC-01) and allow 15 sec of running to settle down Start Process Water Pump (PU-07) - this will fill all sumps via the make up water float valves and the spray/wash water valves Wait 30 seconds to fill sumps Start Sump Pump (PU-09) [Not applicable PU-09 replaced by NSL sump pump] Start Jig Tails Pump (PU-03) Start Jig Feed Pump (PU-01) Start Final Tails Pump (PU-02) As soon as the Jig Plant Final tails Pump (PU-02) starts, the Exxaro Tails Pumps (612A, B & C) are automatically started in a timed sequence (with adjustable delays) and the Exxaro Cons Pump (611) also starts at the same time as Tails Pump 612A Start Motive Water Pump (PU-05) Start Jig Concentrate Pump (PU-04) Wait 60 seconds, then Start Kelsey Jig Drives/Valves as per Section B, o Hutch Water Pump (PU-08) o Open Hutch Water Isolation Valve o Jig Spin Motor o Jig Pulse Motor Jig Feed Start-Up Sequence Start Interlocks The start interlocks for this sequence are: Vibrating Screen (SC-01) running Jig Feed Pump (PU-01) running Jig Tails Pump (PU-03) running Jig Concentrate Pump (PU-04) running Final Tails Pump (PU-02) running Motive Water Pump (PU-05) running Process Water Pump (PU-07) running Jig lube system running Hutch water pump (PU-08) running Hutch water isolation valve open Hutch water pressure healthy Hutch water flow healthy Jig spin motor running Jig pulse motor running No other sequence running Feed Diverter Knife Gate Valves in Automatic Mode Swing Arm is Healthy, commanded to retract, and in Automatic Mode Blast Rod is Healthy, commanded to be up and in Automatic Mode 9

10 Jig Feed Start Sequence When the Jig Plant has run up to the point of becoming ready for feed, a Ready to Receive signal is sent to the Exxaro PCS (as per Section 2.5) and: Operator goes to Feed Preparation Plant and starts feed Conveyor The Feed On signal from the Exxaro Feed Preparation Plant indicates that solids are entering the system and coming to the Jig Plant The Jig Feed knifegate valves are then cycled between Bypass and To Jig for a preset (adjustable) duration and a pre-set (adjustable) number of times before staying in the To Jig position The Jig Process is now operating and will settle to steady state operation with Jig Plant sump levels controlled automatically (as per Section 2.1.3) Exxaro Tails and Cons sump levels are not controlled automatically through the Jig Plant PLC and the Operator is responsible for monitoring and controlling these levels If there is a fault with the Jig which causes the Jig Feed valve to be diverted to Bypass then the Ready to Receive signal will be lost at the Exxaro Feed Preparation Plant and the solids will be stopped. In this case, once the Jig fault is fixed and the Ready to Receive signal is again activated, the Operator must go to the Feed Preparation Plant and restart the solids, so that the sequence above is repeated Plant Shutdown Sequence The plant shutdown sequence is initiated from the HMI by pressing the PLANT STOP button on the PLANT OVERVIEW page. The Plant Shutdown Procedure is as follows: Remove Ready to Receive interface signal to main plant o This should in turn stop the feed conveyor at the Exxaro Feed Preparation Plant and stop solids from entering the plant o The Exxaro Feed Preparation Plant pump will continue on water only until stopped by the Operator o The Derrick Screen Feed Pump (PU-06) will continue running until it trips out on low level or until it is stopped (as below) Shift jig feed diverter knife gate valves to Bypass position wait 5 minutes Shutdown Jig as per Jig Shutdown Sequence in Section Once Jig is shutdown: o Stop Derrick Screen Feed Pump (PU-06) o Stop Jig Concentrate Pump (PU-04) o Stop Jig Feed Pump (PU-01) o Stop Jig Tails Pump (PU-03) o Stop Motive Water Pump (PU-05) o Stop Final Tails Pump (PU-02) o Stop Process Water Pump (PU-07) o Stop Sump Pump (PU-09) o Stop Vibrating Screen (SC-01) 10

11 After the Plant Stop is complete, the Operator must manually stop the Exxaro Feed Preparation Plant pump, so water stops being delivered to the Jig Plant Stopping the Final Tails Pump (PU-02) initiates a Flush Sequence for the Exxaro Product Discharge system, whereby: o The Tails Sump Flush Valve opens for a time (adjustable) sufficient to flush out the entire tails pipeline o Tails and Cons pumps run on while the Tails Sump Flush Valve is open o When the flush time is complete, all pumps stop and the valve closes 11

12 2.3 KCJ Pilot Plant Alarms Full Pilot Plant Shutdown Alarms The following alarms constitute Process Shutdown alarms: Pilot Plant shut down via a Jig Fast Shutdown Shutdown of the following: o Derrick Screen Feed Pump (PU-06) o Jig Concentrate Pump (PU-04) o Jig Feed Pump (PU-01) o Jig Tails Pump (PU-03) o Motive Water Pump (PU-05) o Final Tails Pump (PU-02) o Process Water Pump (PU-07) o Sump Pump (PU-09) o Vibrating Screen (SC-01) Low level alarm in Process Water Tank (TA-01) for 10sec Process Water Pump (PU-07) trip alarm Activation of any of the Plant Emergency Stop Pushbuttons Loss of the 24VDC Control Power Supply Feed Off Alarms The following trip alarms cause the de-activation of the Pilot Plant Ready for Feed interface signal and cause the Jig Feed Diverter knife gate valves to go to the Bypass position: Vibrating Screen (SC-01) Jig Feed Pump (PU-01) Derrick Screen Feed Pump (PU-06) Motive Water Pump (PU-05) Final Tails Pump (PU-02) Jig Concentrate Pump (PU-04) Jig Tails Pump (PU-03) 12

13 2.4 Adjustable Pump Minimum and Maximum Speed Set Points The following set points will be tuned during site commissioning: Jig Feed Pump (PU-01) Set Point is determined by cyclone feed pressure during commissioning and set VFD not used for level control Final Tails Pump (PU-02) Final Tails minimum speed - 90% of steady state speed (settling velocity limit). Final Tails pump maximum speed - 110% of steady state speed Jig Tails Pump (PU-03) Jig Tails minimum speed - 90% of steady state speed (settling velocity limit). Jig Tails pump maximum speed - 110% of steady state speed. 13

14 2.5 Interface Signals Between Client Feed and Pilot Plant Pilot Plant Ready for Feed Signal The Jig Plant Ready to Receive signal is enabled when all the following conditions are met: Hutch Water Pump (PU-08) is Running with Adequate Flow and Pressure Jig Spin Motor Running at Selected Speed Jig Pulse Motor Running Jig Lube Pump Running Vibrating Screen (SC-01) running Jig Feed Pump (PU-01) running Jig Tails Pump (PU-03) running Jig Cons Pump (PU-04) running Motive Water Pump (PU-05) running Final Tails Pump (PU-02) running Process Water Pump (PU-07) running Feed bypass knife gate valves in bypass position No other sequence is Running Loss of any of these conditions causes the loss of the Pilot Plant Ready for Feed signal Pilot Plant Faulted Signal The Pilot Plant Faulted signal is enabled when any of the following conditions are met: Jig Category 1 Alarm Jig Category 2 Alarm Process Water Tank (TA-01) Low Level Alarm Vibrating Screen (SC-01) Trip Alarm Jig Feed Pump (PU-01) Trip Alarm Derrick Screen Feed Pump (PU-06) Trip Alarm Jig Tails Pump (PU-03) Trip Alarm Jig Cons Pump (PU-04) Trip Alarm Motive Water Pump (PU-05) Trip Alarm Final Tails Pump (PU-02) Trip Alarm Process Water Pump (PU-07) Trip Alarm Hutch Water Pump (PU-08) Trip Alarm Loss of all of these conditions causes loss of the Pilot Plant Faulted Signal. 14

15 2.5.3 Exxaro Feed Preparation Plant The following control signals between the Exxaro Plant Control System (PCS) and the Jig Plant are connected: 1 Jig Plant Ready to Receive DO from Jig Plant to DI in Exxaro PCS Clean contact from Jig Plant, interrogation voltage by Exxaro This signal is active when the Jig Plant has all circulation pumps running, the jig spin and pulse are up to speed and the jig has run with hutch water to spread the bed for 1 minute (adjustable) The signal indicates to the Exxaro Feed Preparation Plant that solids feed can be sent to the Jig Plant 2 Feed On DO from Exxaro PCS to DI in Jig Plant Switched 24V signal powered from Exxaro This signal indicates that the Feed Conveyor is running and that solids are entering the Feed Preparation Plant Exxaro Final Tails and Final Concentrate Discharge System The following control signals between the Exxaro Plant Control System (PCS) and the Jig Plant are connected: 1 Run Concentrate Pump 611 and Tails Pump 612A A 24V powered output to a 24V relay in Exxaro MCC runs both pumps Output is maintained, so that when on the pumps run and when off the pumps stop 2 Run Tails Pump 612B A 24V powered output to a 24V relay in Exxaro MCC runs this pump Output is maintained, so that when on the pump runs and when off the pump stops 3 Run Tails Pump 612C A 24V powered output to a 24V relay in Exxaro MCC runs this pump Output is maintained, so that when on the pump runs and when off the pump stops 4 Run Tails Sump Water Valve A 24V powered output to a 24V relay in Exxaro MCC operates this valve Output is maintained, so that when on the valve is open and when off the valve is closed 5 Pumps Running 4 pump motor MCC contactor auxiliary contacts in series Presents a dry contact to the Jig Plant PLC when all 4 pumps are running 15

16 2.5.5 Fault Shutdowns Whenever the Final Tails pump (PU-02) stops, the Plant Stop Sequence will be followed, if possible (typically, if a problem arises in the Jig Plant, then that will apply) If a fault occurs in the Exxaro Product Discharge system pumps, then all pumps will be shut down immediately and an alarm will be logged on the Jig Plant Control system Failure of the Exxaro Product Discharge system pumps will cause a controlled Jig Plant shutdown and will be immediately passed to the Feed system via the control signals to stop feed While the Jig Plant is flushing out and shutting down, tails and concentrate products will continue to pump to the Exxaro sumps which will overflow to the main sump for removal by the Exxaro sump pump Operator Controls A Pumps Start pushbutton is shown alongside the Exxaro Product Discharge system pumps on the PLANT OVERVIEW and PLANT SEQUENCE pages Pressing this button will start the Exxaro Product Discharge system pumps, if plant conditions require the pumps to continue to run If plant conditions do not require the pumps to continue running, then they will go into a Flush Sequence (as per Section above) THIS BUTTON IS FOR ABNORMAL SITUATIONS ONLY, AND SHOULD NOT BE USED UNDER NORMAL CONDITIONS 16

17 3 Section B: MODEL J1800 KELSEY JIG OPERATION 3.1 Drives Jig Spin Motor The Jig Spin Motor spins the jig, creating a centrifugal force and pushing the feed and ragging material towards the internal screen. The motor has two speeds of operation in Automatic mode: Normal Speed o The Normal speed of the motor is set by the Operator and adjustable from the touch panel o The minimum speed limit is 30Hz and the maximum is 50Hz o The ramp-up and ramp-down time is set in the VSD to be 90 seconds Jog Speed o The Jog speed is preset in the VSD at 0.4 Hz (~10 rpm) o This speed is used during the Screen Clean Cycle In Maintenance mode, the Operator has full control of the spin from 0-60 Hz. The motor can be started by: An internal control signal The operator in Maintenance Mode The motor can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy A Motor Fault Alarm Note: ALL Spin motor braking is via a braking resistor (unless the drive turns off in which case the Jig Bowl will free wheel to a stop). The interlocks for this motor are: Screen Cleaner Arm in retracted position when NOT in Jog Speed Mode Lube System Healthy (Lube Pump Running & Healthy Oil Level and Pressure) Vibration Healthy Jig Pulse Motor The Jig Pulse Motor controls the off-set cam which drives the arms that pulse the diaphragms around the periphery of the internal jig screen. As the jig spins, the diaphragms at the back of the hutches are pushed in and out, thereby pulsing the water in the hutches backwards and forwards through the screen and ragging bed, elutriating the ragging bed and feed material and allowing the heavier concentrate particles to move through to the hutches. 17

18 The speed of the motor is set by the Operator and adjustable from the touch panel. In Automatic mode, the minimum speed limit is 0Hz and the maximum is 50Hz. The ramp-up and ramp-down time is set in the VSD to be 3 seconds. In Maintenance mode, the speed is preset at 10Hz for Operators. When logged in, Engineers can adjust this setpoint but will be reverted to 10Hz on logout. The motor can be started by: An internal control signal The operator in Maintenance Mode The motor can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy A Motor Fault Alarm The interlocks for this motor are: Jig Spin Motor Running (unless in maintenance mode) Lube System Healthy (Lube Pump Running & Healthy Oil Level and Pressure) Vibration Healthy Hutch Water Healthy (Sufficient water flow and pressure) (unless in maintenance mode) Screen Clean Motor The Screen Clean Motor is mounted on the Screen Cleaning Arm and controls the cam shaft that drives the screen cleaning head. In automatic mode, the head operates up and down the screen while the jig bowl is spun at jog speed The motor can be started by: An internal control signal The operator in Maintenance Mode The motor can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy A Motor Fault Alarm The interlocks for this motor are: No start unless jig spin motor is running at jog speed 18

19 3.1.4 Blast Pump Motor The Blast Pump controls the blast water used to remove material dislodged from the screens by the cleaning head. The motor can be started by: An internal control signal The operator in Maintenance Mode The motor can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy A Motor Fault Alarm The interlocks for this motor are: Blast Pump Suction Water Isolation Valve (SV 112) Open Process Water Pump (PU-07) Running Blast Pump water supply pressure healthy Lube Pump Motor The Lube Pump controls the oil used in the Kelsey Jig. The motor can be started by: An internal control signal The operator in Maintenance Mode The motor can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy A Motor Fault Alarm The interlocks for this motor are: Nil 19

20 3.2 Solenoid Valves Swing Arm Solenoid Valve The Swing Arm Valve (SV 201) is a single-acting control valve for the Swing Arm Actuator. When in operation, the Cleaning Swing Arm extends into the Kelsey Jig. In this position the Swing Arm is engaged. When the Jig is in normal operation the Swing Arm is retracted. The valve can be started by: An internal control signal The operator in Maintenance Mode The valve can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy The interlocks for this valve are: Jig Spin Motor Running at Jog Speed Air Pressure Healthy Jig Spin Motor Not Running(when Swing Arm is in Maintenance) Blast Rod Solenoid Valves The Blast Rod Solenoid Valve (SV 202 / SV 203) is a double-acting control valve for the Blast Rod Actuator. When in operation, the Blast Rod directs the blast water up and down the screens. When Solenoid Valve (SV 202) is energized, the Blast Rod extends or travels DOWN. When Solenoid Valve (SV 203) is energized, the Blast Rod retracts or travels UP. The valves can be started by: An internal control signal The operator in Maintenance Mode The valves can be stopped by: An internal control signal The operator in Maintenance Mode Interlock not healthy The interlocks for valve (SV 202 / SV 203) are: Swing Arm ENGAGED (ZS32) when Blast Rod is in Manual Mode. 20

21 3.3 Instruments Vibration Transmitter The Vibration Transmitter provides an analog level of vibration, with alarm and trip of the Kelsey Jig. A Vibration Trip Setpoint is configurable by the Engineer and will trigger a Fast Trip. The Vibration Transmitter is located in Instrument Junction Box near the Jig. The vibration sensor is mounted on the lid. The scaling is: 4-20 ma = 0 100% represents 0-2.6mm displacement Jig Feed Flow Transmitter The Jig Feed Flow Transmitter indicates an analog flow of the slurry feed to the Jig. The minimum and maximum scale for this instrument can be adjusted by the Engineer to ensure that the reading on the PLC panel is close to that on the transmitter. The scaling is: 4-20 ma = 0-75 m 3 /hr Hutch Water Flow Transmitter The Hutch Water Flow Transmitter indicates an analog flow of the hutch water. The Low Flow Alarm Setpoint is configurable by the Engineer will trigger a Fast Trip. The minimum and maximum scale for this instrument can be adjusted by the Engineer to ensure that the reading on the PLC panel is close to that on the transmitter. The scaling is: 4-20 ma = 0-75 m 3 /hr Hutch Water Pressure Transmitter The Hutch Water Pressure Transmitter indicates an analog Pressure of the hutch water. The Low Pressure Alarm Setpoint is configurable by the Engineer and will trigger a Fast Trip. The minimum and maximum scale for this instrument can be adjusted by the Engineer to ensure that the reading on the PLC panel is close to that on the transmitter. The scaling is: 4-20 ma = kpa Lube Oil Tank Level Switch The Lube Oil Tank Float Switch indicates a digital, healthy level in the Oil Tank. Loss of the healthy signal will trigger a Low Level Warning. Continual loss of signal for more than the Tank Oil Level Low Time will trigger a Process Shutdown Alarm. 21

22 3.3.6 Lube Oil Supply Pressure Switch The Lube Oil Supply Pressure Switch indicates a digital, healthy pressure in the Oil Tank. Loss of the healthy signal will trigger a Low Pressure Alarm (Fast Trip) The pressure switch is set at 25psi (rising) and 20psi (falling) Air Pressure Switch The Air Pressure Switch indicates a digital, healthy pressure in the air supply for the solenoid valves. Loss of the healthy signal will trigger a Low Pressure Alarm (Process Shutdown) Swing Arm Actuator Reed Switches (ZS32 and ZS33) There are two reed switches on the Swing Arm Actuator to indicate full extension and retraction. Extension of the actuator indicates the Swing Arm is ENGAGED (ZS32) and retraction indicates the Swing Arm is RETRACTED (ZS33) Blast Rod Actuator Reed Switches (ZS25 and ZS31) There are two reed switches on the Blast Rod Actuator to indicate full extension and retraction. Extension of the actuator indicates the Blast Rod is DOWN (ZS31) and retraction indicates the Blast Rod is UP (ZS25). 22

23 3.4 Sequences There is one Emergency Shutdown sequence and five sequences in Automatic mode: Jig Startup Jig Flush Jig Screen Clean 1 (initiated when the Jig is Stopped) Jig Screen Clean 2 (initiated when the Jig is Running) Jig Shutdown The five sequences in Automatic mode cannot be run concurrently. The Jig Startup, Jig Flush and both Jig Screen Clean sequences need to be manually started by the Operator and can be stopped mid-way. The Jig Shutdown Sequence is initiated if one of the other sequences is stopped mid-way but can also be initiated manually by the Operator Jig Start up Sequence Start Signal The Jig Startup Sequence is initiated by the Operator from either Touch Panel or during the Plant Startup sequence Stop Signal The Jig Startup Sequence can be stopped: Manually by the Operator, if a sequence stop has been initiated or if the sequence has completed successfully; or By a Fast Trip or Category 2 Alarm Start Interlocks The start interlocks for this sequence are: Jig Spin, Pulse and Lube are Stopped, Healthy and in Automatic Mode Swing Arm Healthy, retracted and in Automatic Mode Blast Rod Healthy, up and in Automatic Mode Hutch Water Valve (HV 115) in Automatic Mode Hutch Water Pump (PU-08) Healthy and in Automatic Mode No other sequence running Feed bypassed Air pressure healthy E-stops healthy No Category 1 or 2 Alarms 23

24 Sequence 1. Activate Jig System Start output (siren for 5 seconds) 2. Start Lube Pump 3. Wait S11: Lube System Run Up Timer (Adjustable from the Touch Panel) for correct Lube Pump operation 4. Start Hutch Water Pump (PU-08) and Open Hutch Water Valve (HV 115) 5. Wait S15: Hutch Water Run-Up Time (Adjustable from the Touch Panel) for correct Hutch Water flow and pressure 6. Start Jig Spin Motor at Auto Speed 7. Wait for Spin Motor at Speed Signal to confirm correct Jig Spin Motor Speed 8. Wait S35: Pulse Motor Start Delay Time (Adjustable from the Touch Panel) 9. Start Jig Pulse Motor at Auto Speed Jig Shutdown Sequence Start Signal The Jig Shutdown Sequence is initiated if one of the other sequences has stopped mid-way, manually by the Operator from the HMI, by a Process Shutdown Alarm or during the Plant Shutdown Sequence Stop Signal The Jig Shutdown Sequence can be stopped if the sequence has completed successfully or by a Fast Trip, or by Stop command from the HMI Start Interlocks There are no start interlocks for this sequence Sequence 1. Activate Jig Shutdown Siren for 5sec(Start-Up Warning Siren) 2. Bypass Feed 3. Wait S36: Feed Bypass Wait Time (Adjustable from the Touch Panel); If Feed has already been off for this time then continue. 4. Place Jig Pulse Motor to Automatic mode and initiate stop 5. Place Hutch Water Pump (PU-08) to Automatic mode and initiate stop 6. Place Hutch Water Valve (HV 115) to Automatic mode and initiate close 7. Place Jig Spin Motor to Automatic mode and stop 8. Place Blast Rod Solenoid Valve into Automatic mode and retract up 9. Place Swing Arm Solenoid Valve into Automatic mode and retract 10. Place Blast Pump into Automatic mode and stop 11. Place Screen Clean Motor into Automatic mode and stop 12. Place Screen Pre-Wash Water Valve (SV 116) in Automatic mode and close 13. Place Blast Pump Suction and Scraper Head Flush Water Isolation Valve (SV 112) in Automatic mode and close. 14. Wait for Jig Spin Motor Amps to be below S46: Motor Stopped Current Setpoint 24

25 15. Wait S12: Lube System Stop Time Delay (Adjustable from the Touch Panel) 16. Place Lube Pump into Automatic mode and stop Jig Flush Sequence Start Signal The Jig Flush Sequence is initiated by the Operator from either Touch Panel. The start signal is not issued unless the Operator confirms that the Concentrate Spigots have been removed. The signal is momentary. If there is an unhealthy start interlock, the sequence will not start Stop Signal The Jig Flush Sequence can be stopped: Manually by the Operator, if the sequence has completed successfully; or By a Fast Trip or Category 2 Alarm Start Interlocks The start interlocks for this sequence are: Jig Spin Motor Not Running, Healthy and in Automatic Mode Jig Pulse Motor Not Running, Healthy and in Automatic Mode Lube Pump Motor Not Running, Healthy and in Automatic Mode Swing Arm retracted and in Automatic Mode Blast Rod up and in Automatic Mode No other sequence running Feed bypassed Air pressure healthy E-stops healthy Hutch Water Pump (PU-08) Healthy and in Automatic Mode Hutch Water Valve (HV 115) in Automatic Mode Process Water Pump (PU-07) Healthy and in Automatic Mode No Category 1 or 2 Alarms Sequence 1. Operator confirms that the Concentrate spigots have been removed before a start signal is initiated. 2. Display status Time remaining on touch screen 3. Activate Plant Start-Up Warning Siren for 5seconds 4. Start Lube Pump and Process Water Pump (PU-07) 5. Wait S11: Lube System Run-Up Time (Adjustable from the Touch Panel) for correct Lube Pump operation 6. Start Hutch Water Pump (PU-08) and OPEN Hutch Water Valve (HV-115) 7. Wait S15: Hutch Water Run-Up Time (Adjustable from the Touch Panel) for correct Hutch Water flow and pressure 25

26 8. Start Jig Spin Motor at Auto Speed 9. Wait for Spin Motor At Speed signal to confirm correct Jig Spin Motor speed 10. Cycle Hutch Water Valve (HV 115) on for S40: Hutch On Time and then off for S41:Hutch Off Time (Both adjustable from the Touch Panel), for S39: Flush time (Adjustable from the Touch Panel) 11. Wait for S39:Flush Time (Adjustable from the Touch Panel) 12. Stop Hutch Water Pump (PU-08) and Close Hutch Water Valve (HV 115) 13. Leave Spin Motor running for 30sec to empty any water out of the Jig 14. Stop Jig Spin Motor 15. Wait for Jig Spin Motor Amps to be below Motor Stopped Current Setpoint (Adjustable from the Touch Panel) to confirm stop 16. Wait S12:Lube System Stop Time Delay (Adjustable from the Touch Panel) 17. Stop Lube Pump 18. Prompt Operator of completion of Flush Sequence (Display Jig Flush Sequence Complete on touch screen) Jig Screen Clean Sequence Start Signal The Jig Screen Clean 1 Sequence is initiated by the Operator from either Touch Panel. This screen clean sequence is to be used for performing a screen clean on the JIG when it is initially stopped and returning the JIG to the stopped state upon completion of the screen clean cycle. The signal is momentary. If there is an unhealthy start interlock, the sequence will not start Stop Signal The Jig Screen Clean Sequence can be stopped: Manually by the Operator, if the sequence has completed successfully; or By a Fast Trip or Category 2 Alarm Start Interlocks The start interlocks for this sequence are: Jig Spin Motor Not Running and in Automatic Mode Jig Pulse Motor Not Running and in Automatic Mode Lube Pump Motor Not Running and in Automatic Mode Swing Arm Healthy, retracted and in Automatic Mode Blast Rod Healthy, up and in Automatic Mode No other sequence running JIG Feed bypassed for at least 60seconds Air pressure healthy E-stops healthy Screen Pre-Wash Water Valve (SV 116) in Automatic Mode Blast Pump Healthy and in Automatic Mode 26

27 Blast Pump Suction and Scraper Head Flush Water Isolation Valve (SV112) in Automatic Mode No Category 1 or Category 2 Alarms Process Water Pump PU-07 Running in Auto or Manual. Blast Pump water supply pressure healthy Sequence 1. Display status Time remaining on touch screen 2. Activate Plant Start-Up Warning Siren for 5 seconds 3. Start Lube Pump 4. Wait S11:Lube System Run-Up Time (Adjustable from the Touch Panel) for correct Lube Pump 5. Start Jig Spin Motor at Jog Speed 6. Wait for Spin Motor At Speed signal to confirm correct Jig Spin Motor Jog Speed 7. Open Screen Pre-Wash Water Valve (SV 116) 8. Wait for S42:Pre Wash Time (Adjustable from the Touch Panel) 9. Open Blast Pump Suction Water and Scraper Head Flush Water Isolation Valve (SV 112) 10. Extend Swing Arm into Jig 11. Start Blast Pump Motor 12. Start Screen Clean Motor 13. On first down extension of the Blast Rod, hold position for S44:Screen Bottom Clean Time (Adjustable from the Touch Panel) 14. Start Blast Rod Cycle (Activate Blast Rod Solenoid Actuator continuously up and down between reed limits) 15. Wait for S43: Screen Clean Time (Adjustable from the Touch Panel) 16. Stop Blast Pump Motor 17. Stop Screen Clean Motor 18. Close Screen Pre-Wash Water Valve (SV 116) 19. Stop and retract Blast Rod up 20. Stop and retract Swing Arm 21. Wait 5 seconds 22. Close Blast Pump Suction Water Scraper Head Flush Water Isolation Valve (SV 112). 23. Wait for Jig Spin Motor Amps to be below S46: Motor Stopped Current Setpoint (Adjustable from the Touch Panel) to confirm stop 24. Wait S12: Lube System Stop Time Delay (Adjustable from the Touch Panel) 25. Stop Lube Pump 26. Prompt Operator of completion of Screen Cleaning (Display Jig Screen Clean Sequence 1 (Initiated when JIG Stopped) Complete on touch screen) Jig Fast Shutdown Sequence The Jig Fast Shutdown Sequence is activated when a Fast Trip becomes active. It will automatically stop any sequence and place every motor into Automatic Mode and stop them. 27

28 Start Signal The Jig Fast Shutdown Sequence is initiated if a Fast Trip becomes active Stop Signal The Jig Fast Shutdown Sequence will stop after it has successfully completed Start Interlocks There are no start interlocks for this sequence Sequence 1. Activate Jig System Shutdown output for 5 seconds (Start-Up Warning Siren) 2. Bypass Feed 3. Place Jig Pulse Motor to Automatic mode and initiate stop 4. Place Hutch Water Pump (PU-08) into Automatic mode and initiate stop 5. Place Hutch Water Valve (HV 115) into Automatic mode and Close 6. Place Jig Spin Motor to Automatic mode and stop 7. Place Blast Rod to Automatic and retract up 8. Place Swing Arm to Automatic and retract out 9. Place Blast Pump into Automatic mode and stop 10. Place Screen Clean Motor into Automatic mode and stop 11. Place Screen Pre-Wash Water Valve in Automatic mode and Close 12. Place Blast Pump Suction Water and Scraper Head Flush Water Isolation Valve (SV 112) into Automatic mode and Close. 13. Wait for Jig Spin Motor Amps to be below S46: Motor Stopped Current Setpoint (Adjustable from the Touch Panel) to confirm stop 14. De-activate Jig System Running output 15. Wait S12: Lube System Stop Time Delay (Adjustable from the Touch Panel) 16. Place Lube Pump into Automatic mode and stop 28

29 3.5 Alarms All alarms are latched and will need to be Acknowledged and reset from the Touch Panel. There are two categories of alarms: Fast Trip Alarm Process Shutdown Alarm Each motor has a Motor Fault Alarm which consists of: Isolator Not Healthy Alarm Faulted Alarm (type of fault signal dependant on motor) Failed to Start Alarm. The Jig System Healthy Output will be activated if there is no Fast Trip or Process Shutdown Alarms present Fast Trips Fast Trips will initiate a Fast Shutdown Sequence. The Fast Trips are: Jig Pulse Motor Fault Alarm Jig Spin Motor Fault Alarm Lube Pump Motor Fault Alarm Low Oil Tank Pressure Alarm Triggered if after S11: Lube System Run-Up Time, (Adjustable from the Touch Panel) the pressure is not healthy after the Lube Pump is run Hutch Water Low Pressure Alarm Triggered if after S15:Hutch Water Run-Up Time, the pressure is below the S18:Hutch Water Low Pressure Setpoint (Both adjustable on the Touch Panel) Hutch Water Low Flow Alarm Triggered if after S15: Water Run-Up Time, the pressure is below the S16:Hutch Water Low Flow Setpoint (Both adjustable on the Touch Panel) Vibration Hi Hi Trip Alarm Triggered if after 10 seconds, if the vibration is above the S20: Vibration Hi Hi Setpoint (Adjustable from the Touch Panel) Emergency Stop Not Healthy Alarm Swing Arm Failed To Position Alarm Triggered if after S9: Swing Arm Fail to Retract/S10: Failed to Engage Setpoint, the Swing Arm has not reached the reed switch (Adjustable from the Touch Panel) 24VDC Control Supply Failed Alarm Hutch Water Pump (PU-08) Fault Process Water Pump (PU-07) Fault Process Water Tank (TA-01) Low Level Alarm Exxaro Pumps Fail alarm caused by the failure of any of the 4 Exxaro downstream product pumps Process Shutdown Alarms The Process Shutdown alarms make up the rest of the alarms and will initiate a Shutdown Sequence. These alarms are: 29

30 Tank Oil Level Low Alarm Triggered if after S14:Tank Oil Low Level Time (Adjustable from the Touch Panel), the level is not healthy Screen Clean Motor Fault Alarm Blast Pump Motor Fault Alarm Blast Rod Failed To Position Alarm Triggered if after S7:Blast Rod Fail to Position Up/S8: Blast Rod Fail to Position Down Setpoint, the Blast Rod has not reached the reed switch (Adjustable from the Touch Panel) Solenoid Valve Air Pressure Not Healthy Alarm Jig Motor Fault Alarms Each Motor has a Motor Fault Alarm that will stop the motor from running. This is regardless of whether the motor is being driven by a sequence in automatic mode or by an operator in maintenance mode Jig Spin Motor Motor Fault Alarm consists of: VSD Not Healthy Alarm PLC Input from VSD Failed to Start Alarm S1:Fail to Start Setpoint (Adjustable from the Touch Panel) Failed to Stop Alarm S2:Fail to Stop Setpoint (Adjustable from the Touch Panel) Jig Pulse Motor Motor Fault Alarm consists of: VSD Not Healthy Alarm PLC Input from VSD Failed to Start Alarm S3:Fail to Start Setpoint (Adjustable from the Touch Panel) Lube Pump Motor Motor Fault Alarm consists of: Overload Alarm PLC Input from motor overload contact Failed to Start Alarm S6:Fail to Start Setpoint (Adjustable from the Touch Panel) Blast Pump Motor Motor Fault Alarm consists of: Overload Alarm PLC Input from motor overload contact Failed to Start Alarm S5:Fail to Start Setpoint (Adjustable from the Touch Panel) Screen Clean Motor Motor Fault Alarm consists of: Overload Alarm PLC Input from motor overload contact Failed to Start Alarm S4:Fail to Start Setpoint (Adjustable from the Touch Panel) 30

31 3.6 Adjustable Control and Alarm Set Points Sequence Control Set Points S35: Pulse Motor Start Delay Time Time delay after the Jig Spin Motor is running before starting the Jig Pulse Motor. Min 60 seconds. Operator adjustable. S37: Pre-feed Bypass ON/OFF Cycle Time The time Feed Bypass is on/off in the pre-feed start sequence. Min 0 seconds. Operator adjustable. S38: Pre-feed Bypass ON/OFF Number of Cycles The number of Feed Bypass on/off cycles in the pre-feed start sequence. Min 0 seconds. Operator adjustable. S36: Feed Bypass Wait Time Time delay after the feed has been bypassed before stopping the pulse motor in the shutdown sequence. Min 0 seconds. Operator adjustable. S39: Flush Time Flush sequence time duration. Min 60 seconds. Operator adjustable. S40: Hutch On Time Time the Hutch Water is on in the flush sequence. Min 0 seconds. Operator adjustable. S41: Hutch Off Time Time the Hutch Water is off in the flush sequence. Min 0 seconds. Operator adjustable. S42: Pre Wash Time Time delay after the Jig Spin Motor is running before starting the screen clean sequence. Min 0 seconds. Operator adjustable. S44: Screen Bottom Clean Time Time the Blast Rod is in the extended down position on the first cycle to allow the bottom of the screen to be properly cleaned. Min 0 seconds. Operator adjustable. 31

32 S43: Screen Clean Time Screen Clean sequence time duration. Min 60 seconds. Operator adjustable Control Set Points S45: Jig Spin Motor Auto Speed Setpoint Min 30 Hz. Operator adjustable. S46: Jig Spin Motor Manual Speed Setpoint Min 0 Hz. Operator adjustable. S47: Jig Spin Motor At Speed Debounce Setpoint Time delay after the At Speed signal is off before rechecking the signal state. Min 0 seconds. Engineer adjustable. S48: Motor Stopped Current Setpoint The motor is considered to be stopped if the current is less than this setpoint. Min 0 amps. Engineer adjustable. S49: Jig Pulse Motor Auto Speed Setpoint Min 0 Hz. Operator adjustable. S50: Jig Pulse Motor Manual Speed Setpoint Min 0 Hz. Default 10 Hz. Engineer adjustable. Changes back to default when an Operator logs in. S51: Vibrating Screen (SC-01) Motor Manual Speed Setpoint Min 0 %. Operator Adjustable. S52: Vibrating Screen (SC-01) Motor Auto Speed Setpoint Min 70 %. Operator Adjustable. S72: Ragging Recovery Screen Feed Pump (PU-03) Minimum Speed Control Setpoint Min 0 %. Operator Adjustable 32

33 S73: Ragging Recovery Screen Feed Pump (PU-03) Maximum Speed Control Setpoint Min 0 %. Operator Adjustable S74: Final Cons Pump (PU-04) Minimum Speed Control Setpoint Min 0 %. Operator Adjustable S75: Final Cons Pump (PU-04) Maximum Speed Control Setpoint Min 0 %. Operator Adjustable S76: Jig Plant Feed Pump (PU-06) Minimum Speed Control Setpoint Min 0 %. Operator Adjustable S77: Jig Plant Feed Pump (PU-06) Maximum Speed Control Setpoint Min 0 %. Operator Adjustable S78: Final Tails (PU-02) Minimum Speed Control Setpoint Min 0 %. Operator Adjustable S79: Final Tails (PU-02) Maximum Speed Control Setpoint Min 0 %. Operator Adjustable Alarm Set Points S11: Lube System Run-Up Time Time delay to ensure Lube Pump is running correctly. Also used in the Oil Tank Low Pressure Alarm. Min 30 seconds. Engineer adjustable. S12: Lube System Stop Delay Time Time delay after the Jig Spin Motor has stopped before stopping Lube Pump. Min 0 seconds. Engineer adjustable 33

34 S14: Tank Oil Level Low Time Time delay after the Low Level signal becomes active before initiating an alarm. Min 0 seconds. Engineer adjustable. S15: Hutch Water Run-Up Time Time delay to ensure Hutch Water is running correctly. Also used in the Hutch Water Low Flow Alarm and Hutch Water Low Pressure Alarm. Min 0 seconds. Operator adjustable. S16: Hutch Water Low Flow Setpoint Min 0 m3/hr. Engineer adjustable S18: Hutch Water Low Pressure Setpoint Min 0 kpa. Engineer adjustable S20: Vibration Hi Hi Trip Setpoint Min 0 %. Engineer adjustable. S1: Jig Spin Motor Fail to Start Time Setpoint Min 0 seconds. Engineer Adjustable. S2: Jig Spin Motor Fail to Stop Time Setpoint Min 0 seconds. Engineer Adjustable. S3: Jig Pulse Motor Fail to Start Time Setpoint Min 0 seconds. Engineer Adjustable. S4: Screen Clean Motor Fail to Start Time Setpoint Min 0 seconds. Engineer Adjustable. S5: Blast Pump Motor Fail to Start Time Setpoint Min 0 seconds. Engineer Adjustable. S6: Lube Pump Motor Fail to Start Time Setpoint Min 0 seconds. Engineer Adjustable. S7: Blast Rod Fail to Position Up Time Setpoint Min 0 seconds. Engineer Adjustable. 34

35 S8: Blast Rod Fail to Position Down Time Setpoint Min 0 seconds. Engineer Adjustable. S9: Swing Arm Fail to Retract Time Setpoint Min 0 seconds. Engineer Adjustable. S10: Swing Arm Fail to Engage Time Setpoint Min 0 seconds. Engineer Adjustable. 35

36 3.6.4 Table of Alarm and Control Commissioning Setpoints PAGE: ENGR DATA ENTRY PUMPS Parameter Commissioning Setpoint PID Execution Time Base 25 Final Tails LIC106 Kc Proportional Gain 65 Final Tails LIC106 Ti Integral Time 260 Final Tails PU02 Minimum Speed (Hz) 20 Jig Tails LIC120 Kc Proportional Gain 40 Jig Tails LIC120 Ti Integral Time 100 Jig Tails PU03 Minimum Speed (Hz) 10 Jig Feed LIC104 Kc Proportional Gain 40 Jig Feed LIC104 Ti Integral Time 80 Jig Feed PU01 Minimum Speed (Hz) 10 Jig Feed PU01 Maximum Speed (Hz) 60 PU01 LIC104 SELECT PID Screen Feed LIC132 Kc Gain 85 Screen Feed LIC132 Ti Integral Time 260 Screen Feed PU06 Minimum Speed (Hz) 15 Jig Feed PU01 Low Level Trip (%) 0 Final Tails PU02 Low Level Trip (%) 5 Jig Tails PU03 Low Level Trip (%) 5 Water Addition Screen Feed PU06 Low Level Trip (%) 2 Alarm Hooter Silence Alarm Available 36

37 PAGE: ENGRS DATA ENTRY JIG Parameter Commissioning Setpoint JIG SPIN MOTOR Pulley Ratio 5.72 At Speed Signal Debounce Setpoint (secs) 20 Motor Stopped Current Setpoint (Amps) 1.0 JIG PULSE MOTOR Pulley Ratio

38 PAGE: SEQUENCES Parameter Commissioning Setpoint START Feed Start Delay Time (secs) 60 Pulse Motor Start Delay Time (secs) 60 Pre-feed Bypass ON/OFF Cycle Time (secs) 5 Number of Cycles 3 SHUTDOWN Feed Bypass Wait Time (secs) 60 Spindry Wait Time (secs) 30 Feed Auto Stop ENABLE/DISABLE DISABLE 38

39 PAGE: SEQUENCES 2 Parameter Commissioning Setpoint FLUSH Flush Time (secs) 180 Hutch On Time (secs) 10 Hutch Off Time (secs) 10 SCREEN CLEAN Pre Wash Time (secs) 10 Screen Clean Time (secs) 150 Screen Bottom Clean Time 10 39

40 PAGE: ALARM SETPOINTS 1 Parameter Commissioning Setpoint Jig Spin Motor Fail To Start Setpoint (secs) 10 Jig Spin Motor Fail To Stop Setpoint (secs) 150 Jig Pulse Motor Fail To Start Setpoint (secs) 10 Screen Clean Motor Fail To Start Setpoint (secs) 10 Blast Pump Fail To Start Setpoint (secs) 10 Lube Pump Fail To Start Setpoint (secs) 10 Blast Rod Fail To Position Up Setpoint (secs) 10 Blast Rod Fail To Position Down Setpoint (secs) 10 Swing Arm Fail To Position In Setpoint (secs) 10 Swing Arm Fail To Position Out Setpoint (secs) 10 40

41 PAGE: ALARM SETPOINTS 2 Parameter Commissioning Setpoint Lube System Start Delay Time Setpoint (secs) 60 Lube System Stop Time Setpoint (secs) 30 Lube Spin Drive Fault Stop Time Setpoint (secs) 600 Lube Low Level Time Setpoint (secs) 120 Lube Return Oil High Temperature Setpoint (degc) 80 Lube Return Oil High Temp Time Setpoint (secs) 3 Hutch Water Start Delay Time Setpoint (secs) 10 Hutch Water Low Flow Setpoint (m3/hr) 24 Hutch Water Low Flow Time Setpoint (secs) 3 Hutch Water Low Pressure Setpoint (kpa) 250 Hutch Water Low Pressure Time Setpoint (secs) 3 41

42 PAGE: ALARM SETPOINTS 3 Parameter Commissioning Setpoint Blast Water Start Delay Time Setpoint (secs) 10 Vibration High TRIP Setpoint (%) 18 Vibration High Trip Time Setpoint (%) 20 Vibration Warning Alarm Setpoint (%) 10 Spin Motor Ramp Time from VSD (secs) 120 Belt Slip Dead-Band (Hz) 7.0 Belt Slip Alarm Time Setpoint (secs) 600 PU01 Jig Feed Sump Low Level Trip Setpoint (%) 0 PU02 Final Tails Sump Low Level Trip Setpoint (%) 5 PU03 Jig Tails Sump Low Level Trip Setpoint (%) 5 PU06 External Feed Delay Time Setpoint (secs) 6 42

43 PAGE: EXXARO SETPOINTS Parameter Commissioning Setpoint Feed Input Transit Time Setpoint (secs) 6 Pump 612A & 611 Start Delay Setpoint (secs) 10 Tails Pump 612B Start Delay Setpoint (secs) 20 Tails Pump 612C Start Delay Setpoint (secs) 30 Tails Flush Time Setpt. From PU02 Stop (secs) 180 PU06 Bin Start Level (%) 0 43

44 PAGE: PLANT SEQUENCES Parameter Commissioning Setpoint Hooter Time (secs) 5 Screen Start Delay Time (secs) 0 Process Water PU07 Start Delay Time (secs) 3 Jig Tails PU03 Start Delay Time (secs) 3 Jig Feed PU01 Start Delay Time (secs) 3 Final Tails PU02 Start Delay Time (secs) 3 Motive Water PU05 Start Delay Time (secs) 3 Jig Cons PU04 Start Delay Time (secs) 30 44

45 PAGE: JIG CONTROL Parameter Commissioning Setpoint JIG SPIN MOTOR Auto Speed Setpoint (rpm) 175 At Speed Signal Debounce Setpoint (secs) 20 Motor Stopped Current Setpoint (Amps) 1.0 JIG PULSE MOTOR Auto Speed Setpoint (rpm)

46 PAGE: JIG DRIVES 1 Parameter Commissioning Setpoint JIG SPIN MOTOR Manual Speed Setpoint (rpm) 175 JIG PULSE MOTOR Manual Speed Setpoint (rpm) 10 46

47 PAGE: VFD PUMPS Parameter Commissioning Setpoint PU01 JIG FEED PUMP High Level Setpoint (%) 80 Low Level Setpoint (%) 70 PU02 FINAL TAILS PUMP Level Setpoint (%) 70 PU03 JIG TAILS PUMP Level Setpoint (%) 70 PU06 SCREEN FEED PUMP Level Setpoint (%) 70 47

48 PAGE: PUMPS Parameter Commissioning Setpoint SC01 RAGGING SCRN Speed Setpoint (Hz) 40 48

Lease Automatic Custody Transfer

Lease Automatic Custody Transfer Lease Automatic Custody Transfer Angus Manufactured LACT Units Updated 19-Dec-01, Slide 2 LACT Unit Requirements Are used for the automatic unattended measurement of crude oil. Accurately measure the quantity

More information

AggreSand SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES

AggreSand SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES WASHING SYSTEMS TECHNICAL SPECIFICATION AggreSand FEATURES 3 Aggregates, 2 Sand, 1 Machine Fully Modular Fully Automated Radio Controlled Containerised Transport Pre Wired & Pre Plumbed 1 Day Set-Up 1

More information

AggreSand SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES

AggreSand SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES WASHING SYSTEMS TECHNICAL SPECIFICATION AggreSand FEATURES 3 Aggregates, 2 Sand, 1 Machine Fully Modular Fully Automated Radio Controlled Containerised Transport Pre Wired & Pre Plumbed 1 Day Set-Up 1

More information

Spartan Controls Millennium Compressor Control Panel Operating Philosophy

Spartan Controls Millennium Compressor Control Panel Operating Philosophy Project: Stock Revision 1 Page 1 Spartan Controls Millennium Compressor Control Panel Operating Philosophy Location: Stock Customer references: Vendor: Vendor document: Spartan Controls Ltd. Operating

More information

AggreSand 165 SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES

AggreSand 165 SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES WASHING SYSTEMS TECHNICAL SPECIFICATION AggreSand 165 FEATURES 3 Aggregates, 2 Sand, 1 Machine Fully Modular Fully Automated Radio Controlled Containerised Transport Pre Wired & Pre Plumbed 1 Electrical

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31 LACT MEASUREMENT Prepared By: Ken A. Steward. P.E. Linco-Electromatic, Inc. 4580 West Wall Street Midland, Texas 79703 The Operation of L.A.C.T. Units The simplest approach to the understanding of the

More information

Hitachi Screw Point List and Startup Sequence

Hitachi Screw Point List and Startup Sequence Micro Control Systems APPLICATION NOTE APP-008 Hitachi Screw Point List and Startup Sequence Revision History Date Author Description 1/16/98 RCT Initial App note (draft copy) 3/12/98 RCT Released 3/13/98

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

CENTRIFEEDER ELECTRONICS

CENTRIFEEDER ELECTRONICS CENTRIFEEDER ELECTRONICS FOR USE WITH CENTRIFEEDER with Integrated Vibratory Control REV 08/13 ADDENDUM VERSION 6.22 SOFTWARE Copyright 2011 Eastern Instrument Laboratories, Inc. All Rights Reserved. TABLE

More information

AggreSand 206 SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES

AggreSand 206 SYSTEMS WASHING TECHNICAL SPECIFICATION FEATURES WASHING SYSTEMS TECHNICAL SPECIFICATION AggreSand 206 FEATURES 3 Aggregates, 2 Sand, 1 Machine Fully Modular Fully Automated Radio Controlled 5 x 40' Containers & 1 40' Flat Rack Pre Wired & Pre Plumbed

More information

DASSAULT AVIATION Proprietary Data

DASSAULT AVIATION Proprietary Data F2000EX EASY 02-49-00 CODDE 1 PAGE 1 / 2 TABLE OF CONTENTS 02-49 02-49-00 TABLE OF CONTENTS 02-49-05 GENERAL Introduction Sources Equipment location 02-49-10 DESCRIPTION Introduction Description Operating

More information

Vission 20/20 micro-controller. Operation and service manual

Vission 20/20 micro-controller. Operation and service manual Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1

More information

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No. Application Guide 575-012 Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1 Carlyle Controller Part No. 2BSB000928 1 General Description The PCM is part of Paragon Compressor

More information

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS INTRODUCTION The two most common methods of measuring the volume of petroleum liquids are tank gauging and liquid metering. The problems associated with

More information

Section 3 Technical Information

Section 3 Technical Information Section 3 Technical Information In this Module: Engine identification Modes of operation Battery charging and heat manage operation Service and repair procedures Maintenance requirements Engine Identification

More information

ATA 49 AUXILIARY POWER UNIT

ATA 49 AUXILIARY POWER UNIT F900EX EASY 02-49-00 CODDE 1 PAGE 1 / 2 TABLE OF CONTENTS 02-49 02-49-00 TABLE OF CONTENTS 02-49-05 GENERAL Introduction Sources APU location 02-49-10 DESCRIPTION Introduction Description Operating principle

More information

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F Starting System DS-102 Series 200 Elmatik AS P.O.Box 309 NO-3471, Slemmestad T - +47 31 28 37 83 F - +47 31 28 37 93 www.elmatik.no post@elmatik.no CONTENT 1. INTRODUCTION 3 2. TECHNICAL SPECIFICATIONS

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS PLC DSE704 AUTOSTART CONTROL MODULE OPERATING MANUAL 057-042 704 Operating Instructions Issue 2.1 18/06/2007 11:27:00 JR - 1 - Deep Sea Electronics Plc

More information

Reciprocating Equipment Manager Operations Manual AIR / FUEL RATIO AND GOVERNOR CONTROL

Reciprocating Equipment Manager Operations Manual AIR / FUEL RATIO AND GOVERNOR CONTROL REMVue Reciprocating Equipment Manager Operations Manual AIR / FUEL RATIO AND GOVERNOR CONTROL REMVue 500/AS OPERATIONS MANUAL Version 3 April 16, 2007 DISCLAIMER This document is designed to provide information

More information

4.2 Component Identification

4.2 Component Identification Digital Control Panels Deep Sea Electronics 5220 4.1 General 4.2 Component Identification 4.3 The YML5220 Controller 4.4 Description of Controls 4.5 Navigation 4.5.1 General Navigation 4.5.2 The Event

More information

VSPS PACKAGE BOOSTER SYSTEM (END SUCTION PUMP DESIGN) FEATURES T Y P E

VSPS PACKAGE BOOSTER SYSTEM (END SUCTION PUMP DESIGN) FEATURES T Y P E PACKAGE BOOSTER SYSTEM (END SUCTION PUMP DESIGN) PACKAGED PUMP SYSTEM WITH CAPACITIES TO 300GPM, PRESSURE BOOST TO 100PSI* WITH UP TO 25HP ON EACH PUMP AVAILABLE IN DUPLEX, AND TRIPLEX CONFIGURATION, AND

More information

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL 1. INTRODUCTION VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down DC-DC Converter has a digitally adjustable output in 0.2V increments. This

More information

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...

More information

Flight Systems. Replacement for KASSEC DESCRIPTION

Flight Systems.   Replacement for KASSEC DESCRIPTION DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most

More information

GLM SERIES CONTROL Users Manual Rev:

GLM SERIES CONTROL Users Manual Rev: GLM SERIES CONTROL Users Manual Rev: 808062 Connecting Power Page 2 Motor Terminal Wiring Diagrams Page 3 Getting Started / Setup Page 4 1. Obstruction Detection Devices Page 4 2. Checking Power and Direction

More information

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

MATRIX LLC LEVEL CONTROL PANEL

MATRIX LLC LEVEL CONTROL PANEL MATRIX LLC LEVEL CONTROL PANEL Installation Operation Maintenance Manual 1-26-09 REV-0.3 1 INDEX Introduction. 3 Product Configurations..... 4 I/O Descriptions. 8 Operation o Intercooler, Accumulator,

More information

AP1000 European 7. Instrumentation and Controls Design Control Document

AP1000 European 7. Instrumentation and Controls Design Control Document 7.3 Engineered Safety Features AP1000 provides instrumentation and controls to sense accident situations and initiate engineered safety features (ESF). The occurrence of a limiting fault, such as a loss

More information

ICL Three Pump Controller

ICL Three Pump Controller ICL Three Pump Controller Pump Operation The number of pumps that the program controls can be selected by enabling only the ones that are currently installed and in service. The enable/disable setting

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE USER MANUAL IMI vibration switch INSTALLATION - OPERATION - MAINTENANCE Z0929039_A ISSUED 03/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. contents Overview General

More information

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL AUTOMATIC FILTERS, INC. 67 S. LA CIENEGA BLVD. LOS ANGELES, CA 90034 30 839 88 800 336 94 FAX 30 839 6878 www.tekleen.com info@tekleen.com Tekleen GB6 & GB7 USERS MANUAL GB6 & GB7 USERS MANUAL AUTOMATIC

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 2 Float Switch EXERCISE OBJECTIVE Learn the working principle of float switches and how to use the float switch, Model 46935. DISCUSSION OUTLINE The Discussion of this exercise covers the following

More information

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION... CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...6 4.1. DISPLAY PANEL...6 4.2. LCD ICON INSTRUCTION...7 4.3. DISPLAY INSTRUCTIONS...7 4.4. DISPLAY DESCRIPTION...8

More information

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis.

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis. CENTRIFUGAL CHILLER Annual Inspection Refrigerant Circuit Check and record refrigerant level Inspect for leak results Calculate refrigerant lass and report to the customer. Repair minor leaks as required

More information

R & D SPECIALTIES ROTROL I USER'S MANUAL

R & D SPECIALTIES ROTROL I USER'S MANUAL R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL

More information

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Instruction Manual. Q Series 2 Motor Control Modules - OEM A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230

More information

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION

More information

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 4 3. SPECIFICATIONS... 5 4. OPERATION... 6 5. PROTECTION...

More information

NECO Pumping Systems

NECO Pumping Systems INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems PACKAGED CIRCULATING SYSTEM THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED CIRCULATING SYSTEM IS OF THE HIGHEST QUALITY AND

More information

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

Control Panel. Operation and Service Manual

Control Panel. Operation and Service Manual Control Panel Operation and Service Manual 1 2 Important Note Before applying power to the control panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral

More information

CENTRIFLOW METER and ELECTRONICS WIRING and INSTALLATION MANUAL REV 01/16 ORIGINAL LANGUAGE Copyright 2016 Eastern Instrument Laboratories, Inc. All Rights Reserved. TABLE OF CONTENTS SAFETY Safe Operation...

More information

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No Document No. 155-521 (For Use with 2-1/2-Inch to 6-Inch Pressure Independent Control Valves) Features Operating voltage: AC/DC 24V Application Control signals: 3-position, DC 0 to 10V, DC 4 to 20 ma Fail-safe

More information

ELECTRICAL SYSTEM RP-7

ELECTRICAL SYSTEM RP-7 ELECTRICAL SYSTEM RP-7 This section of the manual does not include integral electrical components of the engine. Refer to section Engine RP-1 for details. This section of the manual is divided into three

More information

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. General information Actuator controls AC 01.2 for controlling multi-turn actuators of the SA/SAR type range and part-turn actuators of the SQ/SQR.2 type range. Features and functions Power supply Standard

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Exercise 3-1. Basic Hydraulic Circuit EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Complete hydraulic circuit

Exercise 3-1. Basic Hydraulic Circuit EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Complete hydraulic circuit Exercise 3-1 Basic Hydraulic Circuit EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the hydraulic schematic and components of the nacelle trainer. You will identify

More information

REVISION HISTORY REVISION HISTORY

REVISION HISTORY REVISION HISTORY FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim

More information

Fincor Series 2230 MKII/2240

Fincor Series 2230 MKII/2240 Fincor Series 2230 MKII/ Fincor Series 2200 regenerative drives are ideal for your more demanding applications. They feature flexibility with ratings up to 5 horsepower. The Series 2230 MKII offers new

More information

Vission 20/20 micro-controller. Operation and service manual Version 2.6

Vission 20/20 micro-controller. Operation and service manual Version 2.6 Vission 20/20 micro-controller Operation and service manual Version 2.6 Important Message READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR. The following instructions have been prepared to assist in operation

More information

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units Universal and Multi Split Units If there is a fault on any LG Universal or Multi unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller

More information

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL 5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL > Section DSE Model 5220 Automatic Mains Failure & Instrumentation System Operators Manual TABLE OF CONTENTS

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC DEEP SEA ELECTRONICS PLC 703 AUTOMATIC START MODULE OPERATING INSTRUCTIONS Author:- John Ruddock 703 Operating Instructions Issue Beta1 25/08/2003 2:45 PM JR - 1 - >

More information

Model H30 Operation Manual

Model H30 Operation Manual Model H30 Operation Manual Model H30 Version 1.0 August 1, 2007 2 135 West Davenport Street Rhinelander WI 54501 Phone: 866.441.7997 Fax: 866.278.0036 info@houstonst.com www.houstonst.com 3 Table of Contents

More information

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951

More information

PRESSURE GOVERNOR, ENGINE MONITORING, AND MASTER PRESSURE DISPLAY MODEL: TCA100

PRESSURE GOVERNOR, ENGINE MONITORING, AND MASTER PRESSURE DISPLAY MODEL: TCA100 Document Number: XE-TCA1PM-R0A TCA100 Rev0511 PRESSURE GOVERNOR, ENGINE MONITORING, AND MASTER PRESSURE DISPLAY MODEL: TCA100 FIRE RESEARCH CORPORATION www.fireresearch.com 26 Southern Blvd., Nesconset,

More information

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start)

AQUASTAR C6. (Comfort 6000) Next Generation Auto Backwash Valve System. (selectable time-pressure or remote cycle start) AQUASTAR C6 (Comfort 6000) Next Generation Auto Backwash Valve System (selectable time-pressure or remote cycle start) SIDE MOUNTED AND TOP MOUNTED VALVES WITH QUICK INSTALL ELECTRIC ACTUATORS FOR PIPE

More information

DRIVE THE WATER CYCLE. January 10 TH 2013

DRIVE THE WATER CYCLE. January 10 TH 2013 DRIVE THE WATER CYCLE January 10 TH 2013 DRIVE THE WATER CYCLE EXTENDED FLOW CONTROLS Throttling control Bypass control Parallel Pump control VSD control THROTTLING CONTROL The operation point is modified

More information

LIQUID MEASUREMENT STATION DESIGN Class No

LIQUID MEASUREMENT STATION DESIGN Class No LIQUID MEASUREMENT STATION DESIGN Class No. 2230.1 Michael Frey Systems Sales Manager Daniel Measurement & Control, Inc. 5650 Brittmoore Rd. Houston, Texas 77041 INTRODUCTION The industry continues to

More information

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL 1. INTRODUCTION VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down 24V to 12V DC-DC Converter has a programmable 12.0 to 15.0V output in

More information

Electrical Control System Components Basics of Magnetic Control :

Electrical Control System Components Basics of Magnetic Control : Electrical Control System Components Basics of Magnetic Control : Dr.M.S.Narkhede, LEE, GP Mumbai 1 Contact Types : Contacts are classified into different ways as follows. According to applications contacts

More information

GENCORE 5 FUEL CELL SYSTEM System Fundamentals

GENCORE 5 FUEL CELL SYSTEM System Fundamentals GENCORE 5 FUEL CELL SYSTEM System Fundamentals GenCore 5T48 GenCore 5B48 GenCore 5U48 GenCore 5T24 GenCore 5U120 Revision 1 December 1, 2004 GENCORE DESCRIPTION GenCore fuel cell systems are direct hydrogen

More information

Terminal Assembly Machine

Terminal Assembly Machine 1996 Instruction/Service Manual Terminal Assembly Machine Acme Manufacturing Inc. #J9876 Built by: For: The Wiley Company ACME Manufacturing, Inc. 2000 Coyote Lane Roadrunner, MN 55122 (612) 555-1234 (612)

More information

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER I. REFERENCE: 1 30 [1] Snow Engineering Co. Drawing 80504 Sheet 21, Hydraulic Schematic [2] Snow Engineering Co. Drawing 60445, Sheet 21 Control Logic Flow Chart [3] Snow Engineering Co. Drawing 80577,

More information

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014

HS Refrigeration Screw Compressor Troubleshooting Guidelines. SG March 2014 HS Refrigeration Screw Compressor Troubleshooting Guidelines SG-0003-01 March 2014 Refrigeration Screw Compressor Troubleshooting Guidelines SG-0003-01 March 2014 BITZER Screw Compressors CS High Temp

More information

GENSET CONTROL MODULE A121A / A241A

GENSET CONTROL MODULE A121A / A241A Technical Data Sheet GENSET CONTROL MODULE A121A / A241A Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 4-alarm light outputs with lamp-test provisions.

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only GENERAL These split-system condensing units are designed to

More information

UD SERIES COMPRESSORS

UD SERIES COMPRESSORS UD SERIES COMPRESSORS INDUSTRIAL AIR COMPRESSOR 40-400 HP UPDRAFT MODELS Electric Motor - 460/575/3/60 standard (208/230/3/60 optional on most models) Motor Starter - 460 volt, full voltage magnetic starter

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS GENERAL Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA 00, HB 60 / 80 / 600, HF-25, HL-0 / -0 / -50 Models These split-system condensing units

More information

The Vario motor-driven pump series from ProMinent Adaptable to a wide range of applications VARIO METERING PUMP

The Vario motor-driven pump series from ProMinent Adaptable to a wide range of applications VARIO METERING PUMP The Vario motor-driven pump series from ProMinent Adaptable to a wide range of applications VARIO METERING PUMP ProMinent Modular design allows selection of the features you need Three diaphragm sizes

More information

MODEL 233P/111P/233P-1.5

MODEL 233P/111P/233P-1.5 II-111-233-15P-B INSTALLATION INSTRUCTIONS Revision C Rapid City, SD, USA, 07/2015 MODEL 233P/111P/233P-1.5 BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA 00, HB 60 / 80 / 600, HF-25, HL-0 / -0 / -50 Models GENERAL These split-system condensing units

More information

A system of lubricant dispensing devices (oil or grease) connected by piping to a central pumping unit that is operated automatically or manually.

A system of lubricant dispensing devices (oil or grease) connected by piping to a central pumping unit that is operated automatically or manually. Air/Oil Systems: A lubrication system in which small measured quantities of oil are introduced into an air/oil mixing device which is connected to a lube line that terminates at a bearing, or other lubrication

More information

"INTEGRAL +" CONTROLS HANDBOOK WITH POSITIONER POSIGAM+ OR MODUGAM+

INTEGRAL + CONTROLS HANDBOOK WITH POSITIONER POSIGAM+ OR MODUGAM+ "INTEGRAL +" CONTROLS HANDBOOK WITH POSITIONER POSIGAM+ OR MODUGAM+ Page 2/36 SUMMARY 1. INTRODUCTION... 3 2. CONFIGURATION... 4 3. POWER SUPPLY... 5 3.1 ACTUATOR POWER SUPPLY... 5 3.2 OUTPUT POWER SUPPLY....

More information

Operator s Series 300 Generator Paralleling System

Operator s Series 300 Generator Paralleling System Operator s Series 300 Manual Generator Paralleling System +Before reading please note the following: DANGER is used in this manual to warn of a hazardous situation which, if not avoided, will result in

More information

Discrete Control Logic. 1. Pneumatic circuits. - Low forces - Discrete, fixed travel distances - Rotational or reciprocating motion

Discrete Control Logic. 1. Pneumatic circuits. - Low forces - Discrete, fixed travel distances - Rotational or reciprocating motion Discrete Control Logic 1. Pneumatic circuits - Low forces - Discrete, fixed travel distances - Rotational or reciprocating motion Main components: compressor, valves, cylinders Pneumatic components: cylinders

More information

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down). Technical Data Sheet GENSET CONTROL MODULE A121H / A241H Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 4-alarm light outputs with lamp-test provisions.

More information

2 WAY REMOTE STARTER & ALARM SYSTEM INSTALLATION GUIDE FCC ID NOTICE

2 WAY REMOTE STARTER & ALARM SYSTEM INSTALLATION GUIDE FCC ID NOTICE REV. ARS. WAY REMOTE STARTER & ALARM SYSTEM INSTALLATION GUIDE FCC ID NOTICE This device complies with Part 5 of the FCC rules. Operation is subject to the following conditions:. This device may not cause

More information

MODEL 235P INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 08/2009 II_235P_B1

MODEL 235P INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 08/2009 II_235P_B1 INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 08/2009 MODEL 235P II_235P_B1 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605) 348-5685 BE SURE

More information

Servo and Proportional Valves

Servo and Proportional Valves Servo and Proportional Valves Servo and proportional valves are used to precisely control the position or speed of an actuator. The valves are different internally but perform the same function. A servo

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE5220 AUTO MAINS FAILURE MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel:

More information

Deep Sea Electronics Plc

Deep Sea Electronics Plc Deep Sea Electronics Plc 5120 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL Author: Anthony Manton Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH England Tel: +44 (0) 1723

More information

Induction Power Supplies

Induction Power Supplies Induction Power Supplies 7.5kW; 135 400kHz 480V version (Integral Heat Station) User s Guide Model 7.5-135/400-3-480 SMD Control Brds Rev. D 5/08 Table of Contents 1. Specifications and features...3 2.

More information

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE

100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE 100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE Start-up must be performed by a trained, experienced service person. The following general start-up

More information

Product Information Page

Product Information Page PROGRAMMING GC31 PRESSURE TRANSMITTER TO MONITOR AND CONTROL A HYDRAULIC PRESS PIP #: TR-PI-104 The GC31 differential pressure transmitter is compact, flexible and supports numerous pressure applications

More information

Setup Tabs. Basic Setup: Advanced Setup:

Setup Tabs. Basic Setup: Advanced Setup: Setup Tabs Basic Setup: Password This option sets a password that MUST be entered to re-enter the system. Note: ProEFI can NOT get you into the calibration if you lose this password. You will have to reflash

More information

fm 120 2g c SYSTEMS WASHING

fm 120 2g c SYSTEMS WASHING WASHING SYSTEMS TECHNICAL SPECIFICATION fm 120 2g c features Static sand recovery unit One chassis Two centrifugal slurry pumps Two hydrocyclones Collection tank Split 12 x 5 dewatering screen Produce

More information

CTi Automation - Phone: Fax: Web:

CTi Automation - Phone: Fax: Web: CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net The control & protection you expect in an innovative soft starter design... Flexibility

More information

FINE-SEPARATION FOR AGGREGATES

FINE-SEPARATION FOR AGGREGATES FINE-SEPARATION FOR AGGREGATES LETTER FROM THE FAMILY Founded by H. William Derrick Jr. in 1951, Derrick Corporation was created to solve some of the most challenging mechanical separation needs of the

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE4120 AUTO MAINS FAILURE MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel:

More information

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO: YMC 2 - MOD A STARTUP CHECKLIST Supersedes 160.78-CL2 (512) Form 160.78-CL2 (615) STARTUP CHECKLIST CUSTOMER: JOB NAME: ADDRESS: LOCATION: PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT

More information

GE Energy. The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline

GE Energy. The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline GE Energy The Becker * DNGP: Fail-Safe Protection for Your Gas Pipeline DNGP with Modbus Communication protocol features ZERO Bleed * technology and control logic designed for natural gas control valves

More information

System Background and Operation

System Background and Operation Pty Limited 1/48 Racecourse Road RUTHERFORD NSW 2320 Telephone: (02) 4932 0111 Facsimile: (02) 4932 0222 E-mail:hyden@hydeneng.com.au ABN: 17 129 010 902 ENVIROSPRAY Manual Manual Number: 06500976A Manual

More information

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start. Technical Data Sheet GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 5-alarm light outputs with lamp-test

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 13 Pumps and Accessory Equipment Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 13 Pumps and Accessory Equipment Revised DRIVER OPERATOR Page 1 of 13 PUMPS AND ACCESSORY EQUIPMENT Pumps are designed for many different purposes. In order to understand the proper application and operation of a pump in a given situation, firefighters

More information

CONTROL PTY LTD Phone: (02) UNIT 14/62 OWEN ST Fax: (02) GLENDENNING NSW 2761 INCA MODEL PV2

CONTROL PTY LTD Phone: (02) UNIT 14/62 OWEN ST Fax: (02) GLENDENNING NSW 2761 INCA MODEL PV2 1 INCA CONTROL PTY LTD Phone: (02) 9675 3815 UNIT 14/62 OWEN ST Fax: (02) 9675 1381 GLENDENNING NSW 2761 ELECTRICAL ENGINEERS Email: sales@incacontrol.com.au Design & Manufacture of: Custom-built switchboards

More information

J1 Plug Pin Identification

J1 Plug Pin Identification D D8 D D D D ART_8 J 8 D D0 R R R R TB 80 D D D D D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 8 INPUT Steer Left

More information