Thermodynamic Properties of DuPont ISCEON MO99
|
|
- Eric Waters
- 5 years ago
- Views:
Transcription
1 DuPont ISCEON REFRIGERANTS Technical Information Thermodynamic Properties of DuPont ISCEON MO99 SI Units
2 Thermodynamic Properties of DuPont ISCEON MO99 SI Units Physical Properties Refrigerant Classification Molecular Weight Boiling Point at One Atmosphere HFC 99.1 g/mol C Critical Temperature C Critical Pressure kpa Critical Density kg/m 3 Critical Volume m 3 /kg Ozone Depletion Potential Global Warming Potential (AR4) ASHRAE Standard 34 Safety Rating Temperature Glide (Low-Medium Temp) A1 3-4 C Units and Factors t = temperature in C P = pressure in kilopascals absolute [kpa (abs)] vf = volume of saturated liquid in m 3 /kg vg = volume of saturated vapor in m 3 /kg V = volume of superheated vapor in m 3 /kg df = 1/vf = density of saturated liquid in kg/m 3 dg = 1/vg = density of saturated vapor in kg/m 3 hf = enthalpy of saturated liquid in kj/kg hfg= enthalpy of vaporization in kj/kg hg = enthalpy of saturated vapor in kj/kg H = enthalpy of superheated vapor in kj/kg sf = entropy of saturated liquid in kj/(kg) (K) sg = entropy of saturated vapor in kj/(kg) (K) S = entropy of superheated vapor in kj/(kg) (K) One atmosphere = kpa Reference point for enthalpy and entropy: hf = 200 kj/kg at 0 C sf = 1 kj/kg K at 0 C 1
3 Saturation Properties - Temperature Table Pressure Volume Density Enthalpy Entropy Temp [kpa] [m 3 /kg] [kg/m 3 ] [kj/kg] [kj/k-kg] Temp C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Latent Vapor Liquid Vapor C p f p g v f v g d f d g H f H fg H g S f S g
4 Saturation Properties - Temperature Table Pressure Volume Density Enthalpy Entropy Temp [kpa] [m 3 /kg] [kg/m 3 ] [kj/kg] [kj/k-kg] Temp C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Latent Vapor Liquid Vapor C p f p g v f v g d f d g H f H fg H g S f S g
5 Saturation Properties - Temperature Table Pressure Volume Density Enthalpy Entropy Temp [kpa] [m 3 /kg] [kg/m 3 ] [kj/kg] [kj/k-kg] Temp C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Latent Vapor Liquid Vapor C p f p g v f v g d f d g H f H fg H g S f S g
6 Temp C C C C Temp Temp C C C C Temp
7 Temp C C C C Temp Temp C C C C Temp
8 Temp C C C C Temp Temp C C C C Temp
9 Temp C C C C Temp Temp C C C C Temp
10 Temp C C C C Temp Temp C C C C Temp
11 Temp C C 0.29 C 1.86 C Temp Temp 3.37 C 4.82 C 6.22 C 7.57 C Temp
12 Temp 8.88 C C C C Temp Temp C C C C Temp
Thermodynamic Properties of
DuPont Opteon yf REFRIGERANT Technical Information Thermodynamic Properties of DuPont Opteon yf SI Units Physical Properties Refrigerant Classification Molecular Weight HFO 114.04 g/mol Boiling Point at
More informationBoiling Point at One Atmosphere C Critical Temperature 74.9 C
Opteon XP44 Refrigerant Thermodynamic Properties of Opteon XP44 (R-452A) SI Units Physical Properties Molecular Weight 103.5 g/mole Boiling Point at One Atmosphere -47.0 C Critical Temperature 74.9 C Critical
More informationBoiling Point at One Atmosphere C Critical Temperature 81.5 C
Opteon XP40 Refrigerant Thermodynamic Properties of Opteon XP40 (R-449A) SI Units Physical Properties Molecular Weight 87.2 g/mole Boiling Point at One Atmosphere -46.0 C Critical Temperature 81.5 C Critical
More informationBoiling Point at One Atmosphere C Critical Temperature 96.5 C
Opteon XP10 Refrigerant Thermodynamic Properties of Opteon XP10 (R-513A) SI Units Physical Properties Molecular Weight 108.4 g/mole Boiling Point at One Atmosphere -29.2 C Critical Temperature 96.5 C Critical
More informationBoiling Point at One Atmosphere 29.1 C Critical Temperature C. Critical Density kg/m 3
Opteon XP30 Refrigerant Thermodynamic Properties of Opteon XP30 (R-514A) SI Units Physical Properties Molecular Weight 139.6 lb/lb-mole Boiling Point at One Atmosphere 29.1 C Critical erature 178.1 C Critical
More informationOpteon XP40. Thermodynamic Properties
Thermodynamic Properties This bulletin presents thermodynamic data for (R-449A), a non-flammable, low GWP hydrofluoro-olefin based refrigerant. (R-449A) is a near azeotrope blend of HFC-32/HFC-125/HFO-1234yf/HFC-134a.
More informationThermodynamic Properties of DuPont ISCEON MO59 (R-417A)
DuPont ISCEON 9 Series REFRIGERANTS Technical Information Thermodynamic Properties of DuPont ISCEON MO59 (R-417A) SI Units Thermodynamic Properties of DuPont ISCEON MO59 (R-417A) Refrigerant (R-125/R-134a/R-600
More informationThermodynamic Properties of Opteon XP40 (R-449A) Engineering (I/P) Units. Boiling Point at One Atmosphere F Critical Temperature 178.
Opteon XP40 Refrigerant Thermodynamic Properties of Opteon XP40 (R-449A) Engineering (I/P) Units Physical Properties Molecular Weight 87.2 lb/lb-mole Boiling Point at One Atmosphere -50.8 F Critical Temperature
More informationBoiling Point at One Atmosphere F Critical Temperature F
Opteon XP44 Refrigerant Thermodynamic Properties of Opteon XP44 (R-452A) Engineering (I/P) Units Physical Properties Molecular Weight 103.5 lb/lb-mole Boiling Point at One Atmosphere -52.7 F Critical Temperature
More informationThermodynamic Properties of SUVA MP66 Refrigerant (R-401B) Technical Information T-MP66- SI. DuPont Fluorochemicals
DuPont Fluorochemicals Technical Information T-MP66- SI Technical Information Technical Information Thermodynamic Properties of SUVA MP66 Refrigerant (R-401B) Thermodynamic Properties of Suva MP66 Refrigerant
More informationTechnical Information. T-HP62 SI f. Suva refrigerants. Thermodynamic Properties of Suva HP62. Refrigerant [R-404A (44/52/4]
Technical Information T-HP62 SI f Suva refrigerants Thermodynamic Properties of Suva HP62 Refrigerant [R-404A (44/52/4] Thermodynamic Properties of SUVA HP62 Refrigerant SI Units New tables of the thermodynamic
More informationHCFC-123. Thermodynamic Properties of. (2,2 dichloro-1,1,1-trifluoroethane) T-123 ENG. Technical Information
Technical Information D U P O N T T-123 ENG SUVA REFRIGERANTS TM Thermodynamic Properties of HCFC-123 (2,2 dichloro-1,1,1-trifluoroethane) Du Pont Product Names: SUVA 123 Refrigerant f Thermodynamic Properties
More informationForane 427A Refrigerant
Forane 427A Refrigerant A NEW - % HFC - EASIER RETROFIT FOR EXISTING HCFC-22 INSTALLATIONS www.forane 427A.com Forane 427A Refrigerant A New Retrofit for HCFC-22 no equipment change necessary similar performance
More informationHours / 100 Marks Seat No.
17529 14115 3 Hours / 100 Seat No. Instructions (1) All Questions are Compulsory. (2) Answer each next main Question on a new page. (3) Illustrate your answers with neat sketches wherever necessary. (4)
More informationDanfoss Commercial Compressors Towards more eco-friendly commercial refrigeration systems
MAKING MODERN LIVING POSSIBLE Technical product news Towards more eco-friendly commercial refrigeration systems Using R407A, R407F as drop-in of R404A systems Table 1 The refrigeration industry has made
More informationHoneywell Solstice yf Cool for all concerned
Honeywell olstice yf Cool for all concerned HONEYWELL LOW GLOBAL WARMING POTENTIAL REFRIGERANT I THE COOL CHOICE olstice yf A Green olution to a Global Challenge Introduction tarting in 2011, automakers
More informationTEST REPORT #18. Compressor Calorimeter Test of Refrigerants R-134a, N-13a and ARM-42a
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #18 Compressor Calorimeter Test of Refrigerants R-134a, N-13a
More informationTHERMINOL LT. heat transfer fluid. Wide temperature range, liquid/vapor phase fluid to 315 C. (--103 to 600 F)
THERMINOL LT heat transfer fluid Wide temperature range, liquid/vapor phase fluid --75 to 315 C (--103 to 600 F) THERMINOL LT heat transfer fluid Normal boiling pt. temp., 358 Max. bulk use temp., 600
More informationTheoretical and Experimental Study of an Oil-Free Scroll Vapor Expander
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2008 Theoretical and Experimental Study of an Oil-Free Scroll Vapor Expander Bernard Aoun
More informationGYANMANJARI INSTITUTE OF TECHNOLOGY (GMIT) SUBJECT: ELEMENTS OF MECHANICAL ENGINEERING Assignment Ch 1
1. 3. GYANMANJARI INSTITUTE OF TECHNOLOGY (GMIT) Assignment Ch 1 A steel ball having mass of 10 kg and a specific heat of 460 J/kg K is heated from 50 o C to 200 o C. Determine the heat required. In a
More informationAHRI Standard 1371 (SI) 2017 Standard for Performance Rating of Electronic Expansion Valves
AHRI Standard 1371 (SI) 2017 Standard for Performance Rating of Electronic Expansion Valves IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of
More informationME2301 THERMAL ENGINEERING L T P C OBJECTIVE:
ME2301 THERMAL ENGINEERING L T P C 3 1 0 4 OBJECTIVE: To integrate the concepts, laws and methodologies from the first course in thermo dynamics into analysis of cyclic processes To apply the thermodynamic
More informationRetrofit Guidelines for DuPont ISCEON MO79 (R-422A) Refrigerant
DuPont ISCEON 9 Series REFRIGERANTS Technical Information ART- 44 (MO79-EU) Retrofit Guidelines for DuPont ISCEON MO79 (R-422A) Refrigerant Retrofit Guidelines for DuPont ISCEON MO79 Refrigerant Table
More informationNoble Group of Institutions, Junagadh. Faculty of Engineering Department of Mechanical Engineering
Semester:1 st Subject: Elements of Mechanical Engineering (2110006) Faculty: Mr. Ishan Bhatt Year: 2017-18 Class: Comp. & IT Ele TUTORIAL 1 INTRODUCTION Q.1 Define: Force, Work, Pressure, Energy, Heat
More informationScheme - G. Sample Test Paper-I. Course Name : Diploma in Mechanical Engineering Course Code : ME Semester : Fifth Subject Title : Power Engineering
Sample Test Paper-I Marks : 25 Time:1 hour Q1. Attempt any Three 3X3=9 a) Define i) Mean Effective Pressure ii) Piston Speed iii) Swept Volume b) Draw Carnot cycle on P-V and T-S Diagram c) State the need
More informationPHYSICAL BLOWING AGENTS FOR PU / PIR FOAMS A SHORT HISTORY
PHYSICAL BLOWING AGENTS FOR PU / PIR FOAMS A SHORT HISTORY PHYSICAL BLOWING AGENTS More than you wanted to know! Topics Jargon Types of Blowing Agents How they work Requirements Nomenclature History Blowing
More information-5 F to 620 F. High Performance, Low-pressure Heat Transfer Fluid. Heat Transfer Fluid by Solutia. Technical Bulletin A +400 C +700 F +350 C
62 High Performance, Low-pressure Heat Transfer Fluid Heat Transfer Fluid by Solutia Technical Bulletin 7239731A 62-5 F to 620 F +400 C +350 C +300 C +250 C +200 C +150 C +100 C +50 C 0 C +700 F +600 F
More informationAPPENDIX A. Mechanical Equipment Sheets: York Chiller Marley Cooling Towers Calmac IceBank Storage Tanks Low Temp Air Cooling Coils
APPENDIX A Mechanical Equipment Sheets: York Chiller Marley Cooling Towers Calmac IceBank Storage Tanks Low Temp Air Cooling Coils FORM 201.24-EG3 (1201) YCWS WATER COOLED LIQUID CHILLER HFC-407C 89 TONS
More informationRCD Air Cooled Condensing Unit (50/60 Hz)
Environment friendly Easy to access components More efficient air cooled condenser coils Easy to install and maintain The Saudi Factory for Air Conditioning Units RCD Air Cooled Condensing Unit (50/60
More informationMSC 110mm Series Vertical Medium Screw Compressors
MSC 110mm Series Vertical Medium Screw Compressors 10 110 TR (35 385kW) : 118 176 CFM : 65 115 HP Products that perform... By people who care INTRODUCTION Backed by over 40 years of experience, the Dunham-Bush
More informationBangkok Technical Conference Bangkok, Thailand 30 June, 2013
Cost-Effective Alternative In PU Foam Applications Bangkok Technical Conference Bangkok, Thailand 30 June, 2013 ecomate: International Perspective, Trends & Developments Outline ecomate Technology Review
More informationInterstate Chemical Company Hermitage, PA INTERCOOL BIO-GREEN A NEW FULLY INHIBITED HEAT TRANSFER FLUID MADE FROM A RENEWABLE ENERGY SOURCE
Interstate Chemical Company Hermitage, PA INTERCOOL BIO-GREEN A NEW FULLY INHIBITED HEAT TRANSFER FLUID MADE FROM A RENEWABLE ENERGY SOURCE INTERCOOL BIO-GREEN A A Green Heat Transfer Fluid Intercool Bio-Green
More informationSolubility, Miscibility, and Liquid Viscosity of Lubricants with CO 2 and Propane
Solubility, Miscibility, and Liquid Viscosity of Lubricants with CO and Propane Chris Seeton Seeton C&P University of Illinois at Urbana-Champaign Chicago 03 ASHRAE Winter Meeting 0.67 0.367 0.167-0.03743-0.3743-0.43743
More informationDevelopment Of A Piston-Cylinder Expansion Device For The Transcritical Carbon Dioxide Cycle
urdue University urdue e-ubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Development Of A iston-cylinder Expansion Device For he ranscritical Carbon
More informationTHERMINOL 62. heat transfer fluid. High performance under low-pressure applications. -23 to 325 C. (--9 to 620 F)
THERMINOL 62 heat transfer fluid High performance under low-pressure applications -23 to 325 C (--9 to 620 F) THERMINOL 62 heat transfer fluid Min. use temp., 9 Max. bulk use temp., 620 Physical and chemical
More informationTHERMINOL 55. heat transfer fluid. Efficient, reliable mediumtemperature-range. -28 to 290 C. (--18 to 550 F)
THERMINOL 55 heat transfer fluid Efficient, reliable mediumtemperature-range fluid -28 to 290 C (--18 to 550 F) THERMINOL 55 heat transfer fluid Max. extended use temp, 600 Max. bulk use temp., 550 Physical
More informationTHERMINOL 66. heat transfer fluid. Proven performance for high-temperature, low-pressure applications. -3 to 345 C. (27 to 650 F)
THERMINOL 66 heat transfer fluid Proven performance for high-temperature, low-pressure applications -3 to 345 C (27 to 650 F) THERMINOL 66 heat transfer fluid Min. use temp., 27 Max. bulk use temp., 650
More informationTHERMINOL 75. heat transfer fluid. Ultrahigh temperature at low pressure. 80 to 385 C. (175 to 725 F)
THERMINOL 75 heat transfer fluid Ultrahigh temperature at low pressure 80 to 385 C (175 to 725 F) THERMINOL 75 heat transfer fluid Max. bulk use temp., 725 Physical and chemical characteristics Min. use
More informationLow NOx Combustion of DME by Exhaust Gas Recirculation under the High Pressure
35 7 th Asia DME Conference November 16-18, 011 Niigata Toki Messe Convention Center, Niigata, Japan Low Combustion of DME by Exhaust Gas Recirculation under the High Pressure *Hiroaki TAKEUCHI Mamoru
More informationTHERMINOL 54. heat transfer fluid. Efficient, reliable mediumtemperature-range. 28 to 280 C. (- 18 to 540 F)
THERMINOL 54 heat transfer fluid Efficient, reliable mediumtemperature-range fluid 28 to 280 C (- 18 to 540 F) THERMINOL 54 heat transfer fluid Max. bulk use temp., 540 Physical and chemical characteristics
More informationKINGS COLLEGE OF ENGINEERING DEPARTMENT OF MECHANICAL ENGINEERING. Question Bank. UNIT-I THERMODYNAMIC CYCLES Part-A (2 Marks)
KINGS COLLEGE OF ENGINEERING DEPARTMENT OF MECHANICAL ENGINEERING Question Bank Sub. Code/Name: ME1351 - THERMAL ENGINEERING Year/Sem: III/VI 1. What is a thermodynamic cycle? UNIT-I THERMODYNAMIC CYCLES
More informationHYDROFLUORIC ACID FLUOROCARBONS AND PROCESS ECONOMICS PROGRAM. Report No. 89. November A private report by the MENLO PARK, CALIFORNIA
Report No. 89 HYDROFLUORIC ACID FLUOROCARBONS AND by HAROLD W. SCHEELINE November 1973 A private report by the PROCESS ECONOMICS PROGRAM STANFORD RESEARCH INSTITUTE I I MENLO PARK, CALIFORNIA -. _ CONTENTS
More informationCAMERON HYDRAULIC DATA
CAMERON HYDRAULIC DATA Preface to the Twentieth Edition The Book is a Flowserve Corporation publication and, as in the previous nineteen editions, is published as an aid to engineers involved with the
More informationPERFORMANCE AND EMISSION CHARACTERISTICS OF A VARIABLE COMPRESSION SI ENGINE USING ETHANOL- GASOLINE BLENDS AS FUEL
Proceedings of the International Conference on Mechanical Engineering 2011 (ICME2011) 18-20 December 2011, Dhaka, Bangladesh ICME11-TH-001 PERFORMANCE AND EMISSION CHARACTERISTICS OF A VARIABLE COMPRESSION
More informationSeries Low Pressure Steam Boiler Safety Valves
14-200 Series Low Pressure Steam Boiler Safety Valves ASME Section IV Set pressures from 5 to 15. Sizes 2", 2-1/2" and 3". Section IV Heating Boilers Applications: The 14 Series is an ASME Section IV high
More informationUSO4CICV01/US04CICH02:
Natubhai V. Patel College of Pure & Applied Sciences S. Y. B.Sc. Semester-4 Industrial chemistry/ IC (Vocational) USO4CICV0/US04CICH02: Chemical Plant Utilities UNIT 5 Internal combustion engine In an
More informationGEOlube RFL Range Product Data
GElube RFL Range Product Data GElube RFL Range TECHNICAL DATA SHEET North America 340 Mathers Road Ambler PA 19002 USA Tel: +1 215 773 9280 (Toll Free 888 519 3883) Fax:+1 215 773 9424 Europe Charleston
More informationEvaluation of methods to decrease the discharge temperature of R32 scroll compressor
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Evaluation of methods to decrease the discharge temperature of R32 scroll compressor
More informationTHERMINOL VP-3. heat transfer fluid. High-temperature, low-odor, vapor/liquid phase fluid. 2 to 330 C. (36 to 625 F)
THERMINOL VP-3 heat transfer fluid High-temperature, low-odor, vapor/liquid phase fluid 2 to 330 C (36 to 625 F) THERMINOL VP-3 heat transfer fluid Physical and chemical characteristics Therminol VP-3
More informationElements of Mechanical Engineering (EME) QUESTIONS
QUESTIONS 1) In First angle projection method (a) Plan comes above elevation (b) Plan comes below elevation (c) Plan comes besides elevation (d) Plan is on the left hand side. (2) Where LHSV in third angle
More informationSeries Low Pressure Steam Heating Boiler Safety Valves
12-200 Series Low Pressure Steam Heating Boiler Safety Valves Section IV Heating Boilers Medium capacity safety valves protect ASME Section IV low pressure steam heating boilers. Cast bronze, full nozzle
More informationDensity Baume (% m/m) (kg/m 3 ) (lb/ft 3 ) (lb/ga) (degree) % (m/m) (kg/m 3 ) (lb/ft 3 ) (lb/ga) (degree)
Appendix 779 List of Tables Table A.1 Density and Baume of Pure Sucrose Solutions Table A.2 Sucrose Solubility in Pure Sucrose Solutions Table A.3 Sucrose Solubility in Impure Sucrose Solutions Table A.4
More informationEngineers Tables SI Units
Engineers Tables SI Units 1. Introduction The following tables provide practical information to help you design or set up refrigeration systems using KLEA 407C. We've tried to make the layout as easy as
More informationVETRI VINAYAHA COLLEGE OF ENGINEERING AND TECHNOLOGY DEPARTMENT OF MECHANICAL ENGINEERING ME6404 THERMAL ENGINEERING
VETRI VINAYAHA COLLEGE OF ENGINEERING AND TECHNOLOGY DEPARTMENT OF MECHANICAL ENGINEERING ME6404 THERMAL ENGINEERING UNIT I - GAS POWER CYCLES 1. What is a thermodynamic cycle? Thermodynamic cycle is defined
More informationSection 1: Principle of Operation... 2
Table of Contents Section 1: Principle of Operation... 2 Model FC 125... 3 Model FC 150... 4 Model FC 200... 5 Model FC 300... 6 Model FC 400... 7 Model FC 600... 8 Section 3: Options... 9 Port Orientation...
More informationRefrigerating Engineers & Technicians Association. Industrial Refrigeration 1 Final Examination for Course Credit Supplemental Materials Package
Refrigerating Engineers & Technicians Association Industrial Refrigeration 1 Final Examination for Course Credit Supplemental Materials Package - June 1, 2007-1 Commonly Used Refrigerants Refrigerant Number
More information05 Marks (c) Sketch and explain Lancashire Boiler.
Model question paper No.1 1. Answer any FIVE full questions choosing at least two questions from part A & two questions from part B 2. Use of steam tables is permitted 1. (a) Discuss briefly the different
More informationPerformance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2011 Standard for Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does
More information30 F to 650 F. Unique. High-temperature, Low-pressure Heat Transfer Fluid. Technical Bulletin D (Supersedes 9146C) +400 C +700 F +350 C +600 F
66 Unique Technical Bulletin 7239146D (Supersedes 9146C) High-temperature, Low-pressure Heat Transfer Fluid 30 F to 650 F +400 C +350 C +300 C +250 C +200 C +150 C +100 C +50 C +700 F +600 F +500 F +400
More informationCalculation of Kv value Medium Saturated Liquids steam RECOMMENDED FLOW VELOCITIES AT THE INLET OF VALVE, FOR THE SIZING OF NOMINAL PIPE SIZE :
DT SHEET FOR CONTROL VLVES VLVE SIZING The valve sizing is based on the calculation of the Kv coefficient. The Kv represents the quantity of water, expressed in cubic meters (m3) at 15ºC, that flows through
More informationVXF53.. VVF53.. Acvatix Valves VVF..,VXF.. Basic Documentation. CE1P4030en Building Technologies
VVF53.. VXF53.. Acvatix Valves VVF..,VXF.. Basic Documentation CE1P4030en 12.09.2011 Building Technologies Siemens Switzerland Ltd. Industry Sector Building Technologies Division Gubelstrasse 22 6301 Zug
More informationAir Cylinders Drive System Full Stroke Time & Stroke End Velocity. How to Read the Graph
1-1 Best Pneumatics Air Cylinders Drive System Full Time & End Velocity How to Read the Graph This graph shows the full stroke time and stroke end velocity when a cylinder drive system is composed of the
More informationMohammad Faisal Haider. Department of Mechanical Engineering Bangladesh University of Engineering and Technology
Mohammad Faisal Haider Lecturer Department of Mechanical Engineering Bangladesh University of Engineering and Technology Steam Turbine 2 Vapor Power Cycle 4 5 Steam Turbine A steam turbine is prime mover
More informationDetermination of the Performance, Leak Scenario, Flammability and Oil Return Characteristics of a Novel R22 Replacement
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Determination of the Performance, Leak Scenario, Flammability and Oil Return
More informationProperties of Polyvinylether (PVE) as a Lubricant for Air Conditioning systems with HFC Refrigerants?Data Update?
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Properties of Polyvinylether (PVE) as a Lubricant for Air Conditioning systems
More informationPower Rating Minimum Power 218 bkw 292 bhp Maximum Power 359 bkw 482 bhp mm (5.4 in) mm (6.5 in)
The Cat 3406C Diesel Fire Pump Engine is offered in ratings ranging from 218-359 bkw (292-482 bhp) @ 1750-2300 rpm. These ratings are non-certified and available for global non-regulated areas. They are
More informationTHERMINOL RD. heat transfer fluid. Low-viscosity, medium-temperature fluid. -36 to 270 C. (--33 to 520 F)
THERMINOL RD heat transfer fluid Low-viscosity, medium-temperature fluid -36 to 270 C (--33 to 520 F) THERMINOL RD heat transfer fluid Max. bulk use temp., 520 Physical and chemical characteristics Min.
More informationTHERMINOL 68. heat transfer fluid. High-temperature, low-viscosity fluid. -26 to 360 C. ( 14 to 680 F)
THERMINOL 68 heat transfer fluid High-temperature, low-viscosity fluid -26 to 360 C ( 14 to 680 F) THERMINOL 68 heat transfer fluid Physical and chemical characteristics Therminol 68 fluid is designed
More informationTHERMINOL D-12. heat transfer fluid. Low-odor, FDA-grade, NSF-registered cooling/heating fluid. -94 to 230 C. (--137 to 450 F)
THERMINOL D-12 heat transfer fluid Low-odor, FDA-grade, NSF-registered cooling/heating fluid -94 to 230 C (--137 to 450 F) THERMINOL D-12 heat transfer fluid Min. use temp., 137 225 Max. bulk use temp.,
More informationTHERMINOL 72. heat transfer fluid. High temperature, excellent stability at medium pressure. -14 to 380 C. (7 to 715 F)
THERMINOL 72 heat transfer fluid High temperature, excellent stability at medium pressure -14 to 380 C (7 to 715 F) THERMINOL 72 heat transfer fluid 225 Min. use temp., 7 800 Max. bulk use temp., 715 F
More informationREFRIGERATION LUBRICANTS
REFRIGERATION LUBRICANTS 1 Matrix Specialty Lubricants Matrix Specialty Lubricants is a company based in The Netherlands, producing and marketing specialty lubricants and greases. Matrix Specialty Lubricants
More informationTemperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25)
Data sheet Temperature controller AVT with safety temperature monitor STM / VGS for steam (PN 25) Description Controller closes on rising temperature. The controllers are: - Type-tested acc. to EN 14597
More informationKlea 410A Engineers Tables SI Units
Klea 410A Engineers Tables SI Units 1. Introduction The following tables provide practical information to help you design or set up refrigeration systems using Klea 410A. We've tried to make the layout
More informationDEPARTMENT OF MECHANICAL ENGINEERING Question Bank ME THERMAL ENGINEERING. Part-A (2 Marks)
DEPARTMENT OF MECHANICAL ENGINEERING Question Bank ME1351 - THERMAL ENGINEERING UNIT I GAS POWER CYCLES Part-A (2 Marks) 1. What is a thermodynamic cycle? 2. What is meant by air standard cycle? 3.. Name
More informationFloat valve Type HFI. Data sheet
Data sheet Float valve ype is a high pressure float valve with internal liquid measuring device. he float valve is designed for direct flange mounting or welding on to plate heat exchanger type condensers,
More informationGEA Bock HC Compressors. Semi-hermetic Compressors for Hydrocarbons. engineering for a better world. GEA Refrigeration Technologies
GEA Bock HC Compressors Semi-hermetic Compressors for Hydrocarbons engineering for a better world GEA Refrigeration Technologies At a Glance Differences to a standard compressor Electronic motor protection
More informationRetrofit Guidelines for HFC-23. Table 1 HFC-23 Physical Properties and Operating Performance. Physical Property Units HFC-23 R-503 R-13
Technical Information DuPont Suva refrigerants Retrofit Guidelines for HFC-23 ART-25 Introduction HFC-23 refrigerant (also known as Freon 23) is a commercially available, CFC-free alternative to R-503
More informationABSTRACT 1. INTRODUCTION
1260, Page 1 Patrice BONNEFOI 1, Philippe DUGAST 2, Jean de BERNARDI 3 1 Danfoss CC, Advanced Technology, Trévoux, France 33 (0)4 74 00 28 29, p.bonnefoi@danfoss.com 2 Danfoss CC, Advanced Technology,
More informationPrepared By : Checked By : Approved By : Page 1 out of 6
Software Name Carrier AHU - Version 1.0, Patch R1.1X UNIT MODEL GENERAL SPECIFICATIONS GENERAL LOCATION / WEIGHT UNIT DIMENSION Configuration : Quick Selection Wizard Unit Orientation : Horizontal Box
More informationThe performance of diesel engine using diesel oil and dme mixture fuels
International Research Journal on Engineering Vol. 2(2), pp. 019-027, February, 2014 Available online at http://www.apexjournal.org 2014 Apex Journal International Full Length Research The performance
More informationCapacity regulators (hot gas bypass) PMC and CVC
MAKING MODERN LIVING POSSIBLE Technical brochure Capacity regulators (hot gas bypass) PMC and CVC The PMC and CVC is used for capacity regulation in refrigeration, freezing and air conditioning plant for
More informationLive Crude Oil Volatility
Live Crude Oil Volatility Dan Wispinski : Alberta Innovates Technology Futures Bob Falkiner : Imperial Oil Engineering Services CCQTA/COQA October 31, 2014 Food-Agriculture Environment Health Pipeline
More informationTEST REPORT #29. Compressor Calorimeter Test of R- 404A Alternative Refrigerant DR-7 in Reciprocating Compressors
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #29 Compressor Calorimeter Test of R- 4A Alternative Refrigerant
More informationCapacity Charts. Direct Spring Acting Safety Relief Valves for Air, Gas, Liquid, and Steam Service
Direct Spring Acting Safety Relief Valves for Air, Gas, Liquid, and Steam Service About Reyco Valve Division The Reyco line of direct spring acting pressure relief valves utilizes sound engineering principles
More informationTable I.1. The energy use and its relationship to GDP of some selected countries Share of world total (%) 2007 GDP
Appendix I Energy Versus GDP for Various Countries Table I.1. The energy use and its relationship to GDP of some selected countries. Primary energy consumption Mtoe 2007 2007 Share of world total (%) 2007
More informationTEST REPORT #50. Compressor Calorimeter Test of Refrigerant Blend DR-3 in a R-404A Reciprocating Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT # Compressor Calorimeter Test of Refrigerant Blend DR-3 in a
More informationEffect of Lubricant-Refrigerant Mixture Properties on Compressor Efficiencies
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Effect of Lubricant-Refrigerant Mixture Properties on Compressor Efficiencies Scott
More informationLSC Series. Open Drive Large Screw Compressors. Fifteen Displacements. 50-2,500 TR (176-8,785 kw) 278-3,336 CFM 100-2,200 HP
Open Drive Large Screw Compressors Fifteen Displacements 50-2,500 TR (176-8,785 kw) 278-3,336 CFM 100-2,200 HP Designed for Refrigeration, Air- Conditioning, and Process Applications Field Serviceable
More informationTable 1. Table 2. Table 3: Toxicology/Environmental FM-200 (UL/FM) 14A-07H SECTION 1 - INTRODUCTION. Agent Physical Properties FM-200
02 2010-03 SECTION 1 - INTRODUCTION Agent Physical Properties Table 1. Agent Physical Properties HFC-227ea Chemical structure CF 3 CHFCF 3 Chemical name Heptafluoropropane Molecular weight 170 Boiling
More informationPlease welcome for any correction or misprint in the entire manuscript and your valuable suggestions kindly mail us
Problems of Practices Of Basic and Applied Thermodynamics I. C. Engine Prepared By Brij Bhooshan Asst. Professor B. S. A. College of Engg. And Technology Mathura, Uttar Pradesh, (India) Supported By: Purvi
More informationSpecifications for Refrigerants
AHRI Standard 700 with Addendum 1 2016 Standard for Specifications for Refrigerants WITH ADDENDUM 1, SPECIFICATIONS FOR REFRIGERANTS September 2016 Addendum 1 (dated September 2016) of AHRI Standard 700-2016,
More informationHUDSON TECHNOLOGIES REFRIGERANTSIDE SOLUTIONS OTHER SERVICES PRODUCTS
HUDSON TECHNOLOGIES S Chiller dehydration & decontamination (online & offline) Refrigerant moisture reduction (online & offline) Rust and particulate reduction Hermetic burnout decontamination Residue
More informationScientific Journal Impact Factor: (ISRA), Impact Factor: 2.114
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Exhaust Gas Heat Recovery for C.I Engine-A Review Baleshwar Kumar Singh, Dr. Nitin Shrivastava * Department of Mechanical Engineering,
More informationfor Pressure Vessels,Steam Boiler etc. (2.0MPa)
( FULL BORE TYPE ) for Pressure Vessels,Steam Boiler etc. (.0MPa) SPECIFICATIONS Model name Code name Cap type Applicable fluid Set pressure range Applicable temperature End connection Materials Valve
More informationDelfield Undercounters/Worktops
NSF and UL certified DOE 2017, Energy Star and EPA SNAP compliant Built in Covington, TN Covington Facility = ~200K Sq. Ft. 2 EnergyStar (EPA) Voluntary compliance Energy usage guidelines Effective October
More informationHCFCs Refrigeration Retrofit Guidelines
Honeywell Genetron Refrigerants HCFCs Refrigeration Retrofit Guidelines R-12 to: MP39/R-401A MP66/R-401B R-409A R-502 to: HP80/R-402A R-408A Table of Contents HCFC Retrofit Guidelines........................1
More informationProyecto fin de carrera: Sustitución de central térmica en una fábrica de refinado de aceite y envasado. Paraffinic Hydrocarbon (Single Cut)
A.4. CARACTERISTICAS DEL ACEITE TERMICO Paratherm HE High Flash & Fire Points, Thermally Stable HEAT TRANSFER FLUID TYPICAL PROPERTIES* Physical Properties Feedstock Paraffinic Hydrocarbon (Single Cut)
More informationEVAPORATOR PRESSURE REGULATORS
PARKER (S)PORT, (S)PORT II FEATURES AND BENEFITS Highest capacity commercial regulator in the industry. Sweat-in-place without disassembly. Interchangeable capacity cartridges. Low pressure drop. Manual
More informationFlame Arrestor Design and Application Data
Flame Arrestor Design and Application Data Please print it, fill it out and fax it to 1-352-493-2111 or scan & email to info@paradoxintellectual.com Items marked with an asterisk (*) are required fields.
More informationProduct Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil
FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil A13303 Fig. 1 - FPM(A,B)NU Uncased Horizontal Fan Coil (FPMANU model shown) Fig. 2 - FPM(A,B)NC Cased Horizontal Fan Coil
More information