GRUNDFOS INSTRUCTIONS. UPE Series 2000 UPE(D) FZ, UPE F. Installation and operating instructions

Size: px
Start display at page:

Download "GRUNDFOS INSTRUCTIONS. UPE Series 2000 UPE(D) FZ, UPE F. Installation and operating instructions"

Transcription

1 GRUNDFOS INSTRUCTIONS UPE Series 2000 UPE(D) FZ, UPE F Installation and operating instructions

2

3 UPE Series 2000 Declaration of Conformity English (GB) Installation and operating instructions Dansk (DK) Monterings- og driftsinstruktion Deutsch (DE) Montage- und Betriebsanleitung Ελληνικά (GR) Οδηγίες εγκατάστασης και λειτουργίας Español (ES) Instrucciones de instalación y funcionamiento Français (FR) Notice d'installation et de fonctionnement Italiano (IT) Istruzioni di installazione e funzionamento Nederlands (NL) Installatie- en bedieningsinstructies Polski (PL) Instrukcja montażu i eksploatacji Português (PT) Instruções de instalação e funcionamento Русский (RU) Руководство по монтажу и эксплуатации Suomi (FI) Asennus- ja käyttöohjeet Svenska (SE) Monterings- och driftsinstruktion Appendix Table of contents 3

4 Declaration of conformity Declaration of Conformity GB: EC declaration of conformity We, Grundfos, declare under our sole responsibility that the products UPE(D) Series 2000, to which this declaration relates, are in conformity with these Council directives on the approximation of the laws of the EC member states: Machinery Directive (2006/42/EC). Standard used: EN 809: Low Voltage Directive (2006/95/EC). Standards used: EN : 2002 and EN : EMC Directive (2004/108/EC). Standard used: EN DE: EG-Konformitätserklärung Wir, Grundfos, erklären in alleiniger Verantwortung, dass die Produkte UPE(D) Series 2000, auf die sich diese Erklärung bezieht, mit den folgenden Richtlinien des Rates zur Angleichung der Rechtsvorschriften der EU-Mitgliedsstaaten übereinstimmen: Maschinenrichtlinie (2006/42/EG). Norm, die verwendet wurde: EN 809: Niederspannungsrichtlinie (2006/95/EG). Normen, die verwendet wurden: EN : 2002 und EN : EMV-Richtlinie (2004/108/EG). Norm, die verwendet wurde: EN ES: Declaración CE de conformidad Nosotros, Grundfos, declaramos bajo nuestra entera responsabilidad que los productos UPE(D) Series 2000, a los cuales se refiere esta declaración, están conformes con las Directivas del Consejo en la aproximación de las leyes de las Estados Miembros del EM: Directiva de Maquinaria (2006/42/CE). Norma aplicada: EN 809: Directiva de Baja Tensión (2006/95/CE). Normas aplicadas: EN : 2002 y EN : Directiva EMC (2004/108/CE). Norma aplicada: EN IT: Dichiarazione di conformità CE Grundfos dichiara sotto la sua esclusiva responsabilità che i prodotti UPE(D) Series 2000, ai quali si riferisce questa dichiarazione, sono conformi alle seguenti direttive del Consiglio riguardanti il riavvicinamento delle legislazioni degli Stati membri CE: Direttiva Macchine (2006/42/CE). Norma applicata: EN 809: Direttiva Bassa Tensione (2006/95/CE). Norme applicate: EN : 2002 e EN : Direttiva EMC (2004/108/CE). Norma applicata: EN PL: Deklaracja zgodności WE My, Grundfos, oświadczamy z pełną odpowiedzialnością, że nasze wyroby UPE(D) Series 2000, których deklaracja niniejsza dotyczy, są zgodne z następującymi wytycznymi Rady d/s ujednolicenia przepisów prawnych krajów członkowskich WE: Dyrektywa Maszynowa (2006/42/WE). Zastosowana norma: EN 809: Dyrektywa Niskonapięciowa (LVD) (2006/95/WE). Zastosowane normy: EN : 2002 oraz EN : Dyrektywa EMC (2004/108/WE). Zastosowana norma: EN DK: EF-overensstemmelseserklæring Vi, Grundfos, erklærer under ansvar at produkterne UPE(D) Series 2000 som denne erklæring omhandler, er i overensstemmelse med disse af Rådets direktiver om indbyrdes tilnærmelse til EF-medlemsstaternes lovgivning: Maskindirektivet (2006/42/EF). Anvendt standard: EN 809: Lavspændingsdirektivet (2006/95/EF). Anvendte standarder: EN : 2002 og EN : EMC-direktivet (2004/108/EF). Anvendt standard: EN GR: Δήλωση συμμόρφωσης EC Εμείς, η Grundfos, δηλώνουμε με αποκλειστικά δική μας ευθύνη ότι τα προϊόντα UPE(D) Series 2000 στα οποία αναφέρεται η παρούσα δήλωση, συμμορφώνονται με τις εξής Οδηγίες του Συμβουλίου περί προσέγγισης των νομοθεσιών των κρατών μελών της ΕΕ: Οδηγία για μηχανήματα (2006/42/EC). Πρότυπο που χρησιμοποιήθηκε: EN 809: Οδηγία χαμηλής τάσης (2006/95/EC). Πρότυπα που χρησιμοποιήθηκαν: EN : 2002 και EN : Οδηγία Ηλεκτρομαγνητικής Συμβατότητας (EMC) (2004/108/EC). Πρότυπο που χρησιμοποιήθηκε: EN FR: Déclaration de conformité CE Nous, Grundfos, déclarons sous notre seule responsabilité, que les produits UPE(D) Series 2000, auxquels se réfère cette déclaration, sont conformes aux Directives du Conseil concernant le rapprochement des législations des Etats membres CE relatives aux normes énoncées ci-dessous : Directive Machines (2006/42/CE). Norme utilisée : EN 809 : Directive Basse Tension (2006/95/CE). Normes utilisées : EN : 2002 et EN : Directive Compatibilité Electromagnétique CEM (2004/108/CE). Norme utilisée : EN NL: EC overeenkomstigheidsverklaring Wij, Grundfos, verklaren geheel onder eigen verantwoordelijkheid dat de producten UPE(D) Series 2000 waarop deze verklaring betrekking heeft, in overeenstemming zijn met de Richtlijnen van de Raad in zake de onderlinge aanpassing van de wetgeving van de EG Lidstaten betreffende: Machine Richtlijn (2006/42/EC). Gebruikte norm: EN 809: Laagspannings Richtlijn (2006/95/EC). Gebruikte normen: EN : 2002 en EN : EMC Richtlijn (2004/108/EC). Gebruikte norm: EN PT: Declaração de conformidade CE A Grundfos declara sob sua única responsabilidade que os produtos UPE(D) Series 2000, aos quais diz respeito esta declaração, estão em conformidade com as seguintes Directivas do Conselho sobre a aproximação das legislações dos Estados Membros da CE: Directiva Máquinas (2006/42/CE). Norma utilizada: EN 809: Directiva Baixa Tensão (2006/95/CE). Normas utilizadas: EN : 2002 e EN : Directiva EMC (compatibilidade electromagnética) (2004/108/CE). Norma utilizada: EN

5 RU: Декларация о соответствии ЕС Мы, компания Grundfos, со всей ответственностью заявляем, что изделия UPE(D) Series 2000, к которым относится настоящая декларация, соответствуют следующим Директивам Совета Евросоюза об унификации законодательных предписаний стран-членов ЕС: Механические устройства (2006/42/ЕС). Применявшийся стандарт: EN 809: Низковольтное оборудование (2006/95/EC). Применявшиеся стандарты: EN : 2002 и EN : Электромагнитная совместимость (2004/108/EC). Применявшийся стандарт: EN SE: EG-försäkran om överensstämmelse Vi, Grundfos, försäkrar under ansvar att produkterna UPE(D) Series 2000, som omfattas av denna försäkran, är i överensstämmelse med rådets direktiv om inbördes närmande till EU-medlemsstaternas lagstiftning, avseende: Maskindirektivet (2006/42/EG). Tillämpad standard: EN 809: Lågspänningsdirektivet (2006/95/EG). Tillämpade standarder: EN : 2002 och EN : EMC-direktivet (2004/108/EG). Tillämpad standard: EN FI: EY-vaatimustenmukaisuusvakuutus Me, Grundfos, vakuutamme omalla vastuullamme, että tuotteet UPE(D) Series 2000, joita tämä vakuutus koskee, ovat EY:n jäsenvaltioiden lainsäädännön yhdenmukaistamiseen tähtäävien Euroopan neuvoston direktiivien vaatimusten mukaisia seuraavasti: Konedirektiivi (2006/42/EY). Sovellettu standardi: EN 809: Pienjännitedirektiivi (2006/95/EY). Sovellettavat standardit: EN : 2002 ja EN : EMC-direktiivi (2004/108/EY). Sovellettu standardi: EN Bjerringbro, 15th March 2011 Svend Aage Kaae Technical Director Grundfos Holding A/S Poul Due Jensens Vej Bjerringbro, Denmark Declaration of conformity Person authorised to compile technical file and empowered to sign the EC declaration of conformity. 5

6 English (GB) English (GB) Installation and operating instructions Original installation and operating instructions. CONTENTS Page 1. Symbols used in this document 6 2. General description 6 3. Applications Pumped liquids 7 4. Installation Positioning the pump Mounting the pressure sensor Control box positions Twin-head pumps Non-return valve Insulation Frost protection 8 5. Electrical connection Wiring diagram 9 6. Start-up Venting the pump Functions Control modes Control of twin-head pumps Selection of control mode Max. or min. curve duty Constant-curve duty Temperature influence Indicator lights External fault indication External analog 0-10 V controller External forced control Deactivating the control panel Bus communication Remote control Setting the pump Factory settings Control panel R Menu OPERATION Menu STATUS Menu INSTALLATION Priority of settings Fault finding Megging Megging of UPE pumps High-voltage test Service kits Technical data Disposal Symbols used in this document Caution Note Warning Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice. Warning The use of this product requires experience with and knowledge of the product. Persons with reduced physical, sensory or mental capabilities must not use this product, unless they are under supervision or have been instructed in the use of the product by a person responsible for their safety. Children must not use or play with this product. Warning If these safety instructions are not observed, it may result in personal injury! If these safety instructions are not observed, it may result in malfunction or damage to the equipment! Notes or instructions that make the job easier and ensure safe operation. 2. General description The Grundfos UPE(D) FZ is a range of circulator pumps with differential-pressure control enabling adjustment of the pump performance to the actual system requirements. In many systems, this will reduce the power consumption considerably, reduce noise from thermostatic valves and similar fittings, and improve the control of the system. The desired head can be set on the pump control panel. These instructions apply to the pump types UPE(D) FZ and UPE FZ. The pump offers the following functions: Proportional-pressure control (factory setting). The pump head is changed in accordance with the flow demand. The desired head can be set on the pump control panel. Constant-pressure control. A constant head is maintained, irrespective of the flow demand. The desired head can be set on the pump control panel. Constant-curve duty. The pump runs at a constant speed on or between the max. and min. curves. 6

7 Temperature influence. The pump head varies depending on the liquid temperature. External fault signal via a potential-free output. External analog control of head or speed from an external 0-10 V signal transmitter. External forced control via inputs for start/stop min. curve. Bus communication. The UPE(D) FZ circulator pumps incorporate an input for bus communication. The pump can be controlled and monitored by a building management system. Remote control. The pump can be operated with the Grundfos R100 remote control. 3. Applications The UPE(D) FZ circulator pumps are designed for circulating liquids in heating systems. The UPE(D) FZ range is suitable for systems with a constant flow where it is desirable to optimise the setting of the pump duty point. systems with variable flow-pipe temperatures. 3.1 Pumped liquids Thin, clean, non-aggressive and non-explosive liquids, not containing solid particles, fibres or mineral oil. In heating systems, the water should meet the requirements of accepted standards on water quality in heating systems, for example the German standard VDI Mounting the pressure sensor Mount the pressure sensor only after Note the pump has been installed in the system. See fig Place the O-ring in the seat of the pump housing. 2. Place the sensor housing without damaging the O-ring. 3. Fit and tighten the two screws. Fig. 1 Mounting the pressure sensor 4.3 Control box positions Note The control box must only be turned to the positions shown on page 310. The arrows show the allowed/possible flow directions Changing the control box position Warning Before any dismantling of the pump, the system must be drained, or the isolating valves on either side of the pump must be closed, as the pumped liquid may be scalding hot and under high pressure. TM English (GB) Warning The pump must not be used for the transfer of flammable liquids, such as diesel oil, petrol or similar liquids. 4. Installation 4.1 Positioning the pump The arrow on the pump housing indicates the liquid flow direction through the pump. Warning Make sure that persons cannot accidentally come into contact with the hot surfaces of the pump. The pump must be installed with the motor shaft horizontal. See mounting dimensions at the end of these instructions. Fig. 2 Correct control box position Change the control box position as follows: 1. Slacken the cable clamp of the pressure sensor. 2. Remove the four screws holding the pump head. 3. Turn the pump head to the desired position. 4. Refit the four screws and tighten securely. 5. Adapt the pressure sensor cable, and tighten the cable clamp. Warning Make sure that the pressure sensor cable cannot come into contact with the pump head. TM

8 English (GB) 4.4 Twin-head pumps Twin-head pumps offer these operating modes: alternating operation standby operation synchronous operation single-pump operation Master pump and slave pump The master pump will always be the pump to the right when seen from the control box end and the pump is pumping upwards. See fig. 3, pos. 1. Fig. 3 Master pump (1) and slave pump (2) 4.5 Non-return valve If a non-return valve is fitted in the pipe system (fig. 4), it must be ensured that the minimum discharge pressure is always higher than the closing pressure of the valve. This is especially important in proportional-pressure control mode (reduced head at low flows). TM Electrical connection The electrical connection and protection must be carried out according to local regulations. Warning Never make any connections in the pump control box unless the power supply has been switched off for at least 5 minutes. The indicator light must be off. See fig. 6, pos. 21. The earth terminal of the pump must be earthed. The pump must be connected to an external mains switch with a minimum contact gap of 3 mm in all poles. Earthing or neutralisation can be used for protection against indirect contact. Megging must be carried out as described in section 10. Megging. If the pump is connected to an electric installation where an earth leakage circuit breaker (ELCB) is used as an additional protection, this circuit breaker must trip out when earth fault currents with DC content (pulsating DC) and smooth DC earth fault currents occur. The earth leakage circuit breaker must be marked with these symbols: Fig. 4 Non-return valve TM The pump requires no external motor protection. Check that the supply voltage and frequency correspond to the values stated on the pump nameplate. 5.1 Ferrite core Install the ferrite core as shown below. 4.6 Insulation If the pump is insulated without using Grundfos insulating kits, it must be ensured that the differential-pressure and temperature sensor in the pump housing is not covered. 4.7 Frost protection If the pump is not being used during periods of frost, the necessary steps must be taken to prevent frost bursts. TM Fig. 5 Ferrite core installed 8

9 5.2 Wiring diagram TM English (GB) Fig. 6 Internal view of the control box Pos. Description A, Y, B Terminal block for GENIbus T Terminal block for twin-head pump D Terminal block for pressure and temperature sensor on the pump (standard) 1, 2 (START/STOP) 3, 4 (MIN.) Terminals for external start/stop (connect only contacts with no voltage) Terminals for min. curve input (connect only contacts with no voltage) Terminals for external analog input 0-10 VDC 5, 6 (0-10 V) Terminal 5 = +10 V Terminal 6 = 0 V 7, 8 (ALARM) Terminal block for remote alarm contact. Maximum load: 250 VAC, 5 A. 9, 10, 11 Terminals for supply voltage, 1 x 230 V, Hz Terminal 9 = Line (L) Terminal 10 = Earth ( ) Terminal 11 = Neutral (N) Terminals for connection of motor cables 12, 13, 14 Terminal 12 = brown lead Terminal 13 = grey lead Terminal 14 = black lead 15 Motor earthing screw 16, 17 Terminals for connection of motor protector, white lead (T1, T2) 18 Terminal for control panel 9

10 English (GB) 19 Control panel retaining screws 20 Terminal for fan 21 High-voltage indicator 22 Terminal for screened motor cable 23 Fan Note: All cables used must be heat-resistant up to at least +85 C. All cables used must be installed in accordance with EN Warning Wires connected to outputs 7 and 8, inputs 1 to 6, supply terminals and differential-pressure and temperature sensor must be separated from each other and from the supply by reinforced insulation. All wires connected to a terminal block must be tied up at the terminals. Concerning demands on signal wires and signal transmitters, see section 12. Technical data. 6. Start-up Do not start the pump until the system has been filled with liquid and vented. Furthermore, the required minimum inlet pressure must be available at the pump inlet. See section 12. Technical data. Note The system cannot be vented through the pump. 6.1 Venting the pump Vent the pump before start-up. See fig. 7. Warning When the vent screw is slackened, scalding hot liquid under high pressure may escape. Care must be taken to ensure that the escaping liquid does not cause personal injury or damage to other components. Vent screw TM TM Fig. 7 Venting the pump The pump may be noisy, when first switched on, due to air remaining in the pump. This noise should cease after a few minutes running. After start-up, set the desired operating mode and possibly pump head. 10

11 7. Functions Some functions can only be selected with the Grundfos R100 remote control. Where and how the various settings are made appear from section 8. Setting the pump. 7.1 Control modes The UPE(D) FZ pumps can be set to the control mode which is most suitable for the individual system. Two control modes are available: proportional pressure (factory setting) constant pressure. Proportional-pressure control To be set on the control panel or with the R100. The pump head is reduced at falling water demand and increased at rising water demand. See fig. 8. This is the factory setting as, in most cases, this is the optimum control mode, and at the same time it consumes the least energy. Constant-pressure control To be set on the control panel or with the R100. The pump maintains a constant pressure, irrespective of water demand. See fig. 8. H set H H set 2 Fig. 8 Pressure control 7.2 Control of twin-head pumps The factory setting can be changed with the R100. Fig. 9 Proportional pressure Slave pump Q H H set Constant pressure Master pump Master and slave pumps Q TM TM Four operating modes are available. The selection of operating mode depends on whether reliability, lifetime or performance has top priority. Alternating operation (factory setting). Pump operation alternates every 24 hours. If the power supply to the pump has been switched off, any of the pumps may start when the power supply is switched on again. Reaction in case of fault: In case of fault in one pump, the duty pump will operate continuously as a single-head pump. Standby operation. The master pump is operating continuously. Every 25 hours the slave pump will start and run for approx. 10 seconds to prevent it from seizing up. Reaction in case of fault: If the master pump stops due to a fault, the slave pump will operate continuously as a single-head pump. Synchronous operation. The pumps are operating at the same motor frequency. This operating mode is suitable if the flow demand exceeds the flow of one pump. Reaction in case of fault: In case of fault in one pump, the duty pump will operate continuously as a single-head pump. Single-pump operation. The pumps are operating completely independently of each other without internal communication, but the twin-head cable must be connected. All functions of each pump are identical to those of a single-head pump. All the other functions mentioned in sections 7.1 Control modes to 7.13 Remote control are possible in the four operating modes Why select single-pump operation Select single-pump operation when the twin-head pump is to be controlled or monitored by a Grundfos pump management system. in all other situations where the master and slave pumps are to operate independently of each other as two single-head pumps R100 remote control Single-pump operation is to be selected with the R100. See section Twin-head pump Operation in parallel In single-head operation mode, the pumps must never run at the same time, unless the pump is controlled by a Grundfos pump management system Setting the slave pump When single-pump operation mode has been selected, the slave pump settings will correspond to the settings of the last working pump. English (GB) 11

12 English (GB) 7.3 Selection of control mode Systems with specified control mode If the pump control mode (proportional or constant pressure) and head have been specified for the system in which the pump is to be installed, set the pump as specified. See section 8. Setting the pump. If problems should arise, see section 9. Fault finding. Systems with no specified control mode If the pump control mode and head have not been specified for the system (for instance, an uncontrolled standard pump is replaced by the UPE pump), it is advisable to use the settings in the table below and in section Setting in connection with pump replacement. System type 1. Relatively great head losses in the boiler circuit and the distribution pipes. 2. Relatively small head losses in the boiler circuit and the distribution pipes. Description a) Two-pipe heating systems with thermostatic valves and with a dimensioned pump head higher than 4metres, very long distribution pipes, strongly throttled pipe balancing valves, differential pressure regulators, great head losses in those parts of the system through with the total quantity of water flows (for example boiler, heat exchanger and distribution pipe up to the first branching) or low differential temperature. b) Underfloor heating systems and one-pipe heating systems with thermostatic valves and great head losses in the boiler circuit. c) Primary circuit pumps in systems with great head losses in the primary circuit. a) Two-pipe heating systems with thermostatic valves and with a dimensioned pump head lower than 2metres, dimensioned for natural circulation, small head losses in those parts of the system through with the total quantity of water flows (for example boiler, heat exchanger and distribution pipe up to the first branching) or modified to a high differential temperature (for example district heating). b) Underfloor heating systems with thermostatic valves. c) One-pipe heating systems with thermostatic valves or pipe balancing valves. d) Primary circuit pumps in systems with small head losses in the primary circuit. Select this control mode Proportional pressure Constant pressure 12

13 7.3.1 Setting in connection with pump replacement If an uncontrolled pump is to be replaced with a UPE(D) FZ pump, settings can be made according to the tables below. Existing pump Existing pump at maximum speed UPE(D) FZ Existing pump Existing pump at reduced speed UPE(D) FZ English (GB) Maximum head [m] Setting of head [m] Setting of control mode Read the tables as follows: If the maximum head of the existing pump is 6 metres and the pump is running at maximum speed under normal operating conditions, it is recommended to set the pump to 3 metres and to select proportional pressure. If, however, the existing pump is running at a reduced speed, it is recommended to set the pump to 2 metres and to select constant pressure. 7.4 Max. or min. curve duty To be set on the control panel, with the R100 or a building management system via bus. It is not possible to set max. curve duty via the external input. The pump can be set to operate according to the max. or min. curve, like an uncontrolled pump. See fig. 10. Maximum head [m] The max. curve mode can be selected if an uncontrolled pump is required. See section 8.2 Control panel. In this operating mode, the pump will operate independently of an external controller, if installed. The min. curve mode can be used in periods in which a minimum flow is required. This operating mode is for instance suitable for night-time duty. 7.5 Constant-curve duty To be set with the R100. The pump can be set to operate according to a constant curve, like an uncontrolled pump. Select one of the curves between the max. and min. curves. See fig. 11. Fig. 11 Setting of head [m] Constant-curve duty Setting of control mode 3 2 Constant pressure Constant pressure 4 2 Constant pressure Constant pressure Proportional pressure 5 2 Constant pressure 6 3 Proportional pressure 6 2 Constant pressure Proportional pressure Proportional pressure 8 4 Proportional pressure 8 3 Proportional pressure Proportional pressure Proportional pressure 10 5 Proportional pressure Proportional pressure Proportional pressure 11 4 Proportional pressure 12 6 Proportional pressure 12 4 Proportional pressure H Min. Max. Q TM H Min. Max. Q TM Fig. 10 Max. and min. curves 13

14 English (GB) 7.6 Temperature influence To be set with the R100. When temperature influence is activated in proportional- or constant-pressure control mode, the setpoint for head will be reduced according to the liquid temperature. It is possible to set temperature influence to function at liquid temperatures below 80 C or below 50 C. These temperature limits are called T max.. The setpoint is reduced in relation to the head set (= 100 %) according to the characteristics below. H % % H actual 3030% % 20 Fig. 12 Temperature influence In the above example, T max. = 80 C has been selected. The actual liquid temperature T actual causes the setpoint for head to be reduced from 100 % to H actual. The temperature influence function requires: Proportional- or constant-pressure control mode. The pump must be installed in the flow pipe. System with flow-pipe temperature control, for example according to outdoor temperature. Temperature influence is suitable in systems with variable flows (for example twopipe heating systems) in which the activation of the temperature influence function will ensure a further reduction of the pump performance in periods with small heating demands and consequently a reduced flow-pipe temperature. systems with almost constant flows (for example one-pipe heating systems and underfloor heating systems) in which variable heating demands cannot be registered as changes in the head as is the case with two-pipe heating systems. In such systems, the pump performance can only be adjusted by activating the temperature influence function. Selection of T max. In systems with a flow-pipe temperature of up to and including 55 C, select T max. = 50 C. above 55 C, select T max. = 80 C. H t [ C] T actual Q TM Indicator lights The two indicator lights are used for fault and operating indication. For position on pump (fig. 14), see section 8.2 Control panel. Note When the R100 remote control communicates with the pump, the red indicator light will flash rapidly. Functions of indicator lights Indicator lights Fault (red) Off Off Off Permanently on Permanently on Permanently on Operation (green) Off Permanently on Flashing Off Permanently on Flashing See also section 9. Fault finding. Description The power supply has been switched off. The pump is operating. The pump has been set to stop. The pump has stopped due to a fault. Restarting will be attempted. It may be necessary to restart the pump manually by resetting the fault indication. The pump is operating, but it has been stopped due to a fault. Note: If there is no differential-pressure or temperature sensor signal, the pump will continue operating according to the max. curve. The pump has been set to stop, but it has been stopped due to a fault. 14

15 7.8 External fault indication The pump incorporates a signal output for a potential-free fault signal via terminals 7 and 8. Functions of signal output Signal output Description The power supply has been switched off. The pump is operating. The pump has been set to stop. 7.9 External analog 0-10 V controller The pump has an input for an external 0-10 VDC analog signal transmitter (terminals 5 and 6). Via this input, the pump can be controlled by an external controller if the pump has been set to this control mode: Constant curve. The external analog signal will set the pump curve within the range from the min. curve to the constant curve selected according to the characteristic in fig. 13. At an input voltage lower than 0.5 V, the pump will operate according to the min. curve. The setpoint cannot be changed. The setpoint can only be changed when the input voltage is higher than 0.5 V. H m 1 2 English (GB) The pump has stopped due to a fault. Restarting will be attempted. It may be necessary to restart the pump manually by resetting the fault indication. The pump is operating, but it has been stopped due to a fault. Note: If there is no differentialpressure or temperature sensor signal, the pump will continue operating according to the max. curve. The pump has been set to stop, but it has been stopped due to a fault. The fault signal output is activated when the pump registers a fault. The fault signal relay is activated together with the red indicator light on the pump. Resetting of fault indications A fault indication can be reset in one of the following ways: Briefly press or on the pump. This will not influence the pump performance set. Briefly switch off the power supply to the pump. With the R100. See section 8.3 R100. The fault indication cannot be reset until the cause of the fault has disappeared. 0 Fig. 13 Pos. Constant curve Description 1 Maximum head/constant curve 2 Head set/constant curve Note Min. curve The min. curve input, terminals 3 and 4, must be short-circuited. 7 U V TM

16 English (GB) 7.10 External forced control The pump incorporates inputs for external signals for the forced-control functions: start/stop of pump (terminals 1 and 2) min. curve duty (terminals 3 and 4). During forced control, the light fields or indicator lights on the pump will show which function is active. Functional diagram: Start/stop input H H Functional diagram: Min. curve input The min. curve input is only active if the start/stop input is short-circuited. H H Start/stop Q Q Min. curve Q Q Normal duty Stop Normal duty Min. curve (night-time duty) 7.11 Deactivating the control panel To be set with the R100. The buttons on the pump control panel can be deactivated to prevent unauthorised persons from operating the pump Bus communication The pump has a serial communication port which enables communication with the Grundfos Control MPC Series 2000, a CIM/CIU communication interface, a building management system or another type of external control system. If a CIU unit is installed in the system, it is possible to establish communication between the pump and a main network via one of the following protocols: LON Profibus DP Modbus RTU BACnet MS/TP. For further details, see the installation and operating instructions for the CIM and CIU. Via the bus signal, it is possible to remote-set pump operating parameters, such as desired head, temperature influence and operating mode. At the same time, the pump can provide status information about important parameters, such as actual head, actual flow, power input and fault indications. Note When the pump is controlled via a bus signal, the number of settings available on the pump control panel or via the R100 will be reduced. The pump head and control mode can only be set via the bus signal. The pump control panel or the R100 can only set the pump to max. curve and to stop. However, an R100 is required if a number is to be allocated to the pump. See sections Pump number and 8.7 Priority of settings Remote control The pump is designed for wireless communication with the Grundfos R100 remote control. The R100 communicates with the pump via infrared light. During communication, the R100 must be pointed at the pump control panel. When the R100 is communicating with the pump, the red indicator light will flash rapidly. The R100 offers additional setting options and status displays for the pump. See section 8.3 R

17 8. Setting the pump For the setting of the pump, use control panel R100 remote control bus communication (not described in detail in these instructions. Contact Grundfos). The table below shows the application of the individual operating units and in which section the function has been described. Function Control panel R Control panel Warning At high liquid temperatures, the pump may be so hot that only the buttons should be touched to avoid burns. The control panel (fig. 14) incorporates buttons for setting, and. light fields, yellow, for indication of control mode and pump head. indicator lights, green and red, for operating and fault indication. See section 7.7 Indicator lights. Buttons English (GB) Proportional-pressure control Constant-pressure control Setting of pump head Max. curve duty Min. curve duty Constant-curve duty Temperature influence Resetting of fault indications Activation/deactivation of pump buttons Allocation of pump number Reading of various data Start/stop "-" = not available with this operating unit. 8.1 Factory settings Control mode Head Control of twinhead pump UPE(D) FZ Proportional pressure 6 m at max. flow. See fig. 14. Alternating operation UPE FZ Proportional pressure 6 m at max. flow. See fig Light fields Indicator lights Fig. 14 Control panel Control mode setting Description of function, see section 7.1 Control modes. When and are pressed simultaneously, the light fields will indicate the selected control mode: Light fields Top + bottom light fields flashing Middle light fields flashing None of the light fields are on Control mode Proportional pressure Constant pressure Constant curve If the buttons are pressed for more than 5 sec., the control mode will change over to constant pressure and proportional pressure respectively. This means that constant-curve duty is deactivated if selected with the R100. TM

18 English (GB) Setting of pump head The desired pump head is set by pressing or. The light fields on the control panel will indicate the head set. The scaling is set to be approx. 1.2 metres per light field. The table below shows examples of pump head settings indicated by the light fields. Constant-pressure control Proportional-pressure control H m H m UPE FZ UPE(D) FZ 12 0 Light fields 5 and 6 are activated, indicating a desired head of approx. 6.5 metres. Q TM Light fields 5 and 6 are activated, indicating a desired head of approx. 6.5 metres. Q TM

19 8.2.3 Setting to max. curve duty Description of function, see section 7.4 Max. or min. curve duty. Press continuously to change over to the max. curve of the pump (top light field flashes). See fig. 15. To change back, press continuously until the desired head is indicated. H m Fig. 15 Max. curve duty Setting to min. curve duty Description of function, see section 7.4 Max. or min. curve duty. Press continuously to change over to the min. curve of the pump (bottom light field flashes). See fig. 16. To change back, press continuously until the desired head is indicated. H m Fig. 16 Q Min. curve duty Q TM TM Start/stop of pump Stop the pump by continuously pressing until none of the light fields are activated. When the pump is stopped, the green indicator light will be flashing. Start the pump by continuously pressing until the desired head is indicated. If the pump is to be inoperative for a period, it is recommended to use the start/stop input, the R100 or to switch off the power supply. In this way, the pump head setting will remain unchanged when the pump is to be started again Resetting of fault indications To reset fault indications, briefly press or. This will not influence the pump performance set. If the fault has not disappeared, the fault indication will reappear. 8.3 R100 The pump is designed for wireless communication with the Grundfos R100 remote control. The R100 communicates with the pump via infrared light. During communication, the R100 must be pointed at the pump control panel. When the R100 is communicating with the pump, the red indicator light will flash rapidly. The R100 offers additional setting options and status displays for the pump. The R100 displays are divided into four parallel menus. See fig. 17: 0. GENERAL, see operating instructions for the R OPERATION 2. STATUS 3. INSTALLATION The number stated at each individual display in fig. 17 refers to the section in which the display is described. English (GB) 19

20 English (GB) 0. GENERAL 1. OPERATION 2. STATUS 3. INSTALLATION Fig. 17 Menu overview 20

21 8.4 Menu OPERATION When the communication between the R100 and the pump has been established, "Contact with" appears in the display. When the "arrow down" on the R100 is pressed, the OPERATION menu appears. Note The display "Contact with" appears only once, i.e. when the R100 gets contact with the pump Setpoint This display depends on the control mode selected in the display "Control mode" in the INSTALLATION menu. If the pump is remote- or forced-controlled via external signals, the number of possible settings will be reduced. See section 8.7 Priority of settings. Attempts to change the settings will result in an indication in the display saying that the pump is remote-controlled and that changes therefore cannot be made. The following example of display will appear if the pump is in proportional-pressure control mode Fault indications If the pump is faulty, the cause will appear in this display. Possible causes: Phase failure Pump blocked Undervoltage Defective pressure/temperature sensor Internal fault. The fault indication can be reset in this display. If the fault cause has not disappeared when resetting is attempted, this will be indicated in the display. 8.5 Menu STATUS The displays appearing in this menu are status displays only. It is not possible to change or set values. The actual values in these displays are stated as a guide Actual setpoint English (GB) Set the desired head. Furthermore, it is possible to select one of these operating modes: Stop Min. (min. curve) Max. (max. curve). This display will be a little different in the case of constant-pressure control or constant-curve duty. The actual duty point of the pump is indicated by a square in the Q/H field. No indication at low flow Operating mode Field "Actual setpoint": Actual setpoint of pump. Field "corresponding to": Actual setpoint in % of the setpoint set if the pump is connected to an external analog 0-10 V signal transmitter or if temperature influence or proportional-pressure control is activated Operating mode Select an operating mode: Stop Min. (min. curve) Normal (proportional pressure, constant pressure or constant curve) Max. (max. curve). This display shows the actual operating mode (Stop, Min., Normal or Max.) and where this was selected (Pump, R100, Bus or External). 21

22 English (GB) Head and flow 8.6 Menu INSTALLATION In this menu, the settings are chosen that should be considered when installing the pump Control mode Description of function, see section 7.1 Control modes or 7.5 Constant-curve duty. Very low flows cannot be registered, and the R100 will show "<" in front of the lowest possible flow value of the pump in question Speed The actual pump speed Liquid temperature Select a control mode: Prop. pressure (proportional pressure), Const. pressure (constant pressure), Const. curve (constant curve). Setting of setpoint and curve is carried out in display Setpoint in the OPERATION menu Min. curve This display does not apply to UPE(D) FZ and UPE FZ. Description of function, see section 7.4 Max. or min. curve duty. The actual temperature of the pumped liquid Power input and power consumption This display does not apply to UPE(D) FZ and UPE FZ. Actual power input and power consumption of the pump. Power consumption is not calculated in UPE(D) FZ and UPE FZ Operating hours In this display, it is possible to choose between two min. curves. The curve is used when the operating mode "Min. curve" is selected. When controlling UPE(D) FZ and UPE FZ, only one min. curve is available Temperature influence Description of function, see section 7.6 Temperature influence. Number of operating hours of the pump. The value of operating hours is an accumulated value and cannot be set to zero. The temperature influence function can be activated in this display. In the case of temperature influence, the pump must be installed in the flow pipe. It is possible to choose between maximum temperatures of 50 C and 80 C. The temperature influence function will be active only in proportional- or constant-pressure control mode. When the temperature influence is active, a small thermometer is shown in the display "Setpoint" in the OPERATION menu. See section Setpoint. 22

23 Note If the pump is controlled via bus, temperature influence cannot be set with the R Buttons on pump 8.7 Priority of settings The external forced-control signals will influence the settings available on the pump and with the R100. The pump can always be set to max. curve duty or to stop on the pump control panel or with the R100. If two or more functions are activated at the same time, the pump will operate according to the function with the highest priority. The priority of the settings is as shown in the tables below. Without bus signal English (GB) To prevent unauthorised persons from operating the pump, the function of the buttons and can be deactivated in this display. The buttons can be reactivated only with the R100. The buttons can be set to: Active Not active Pump number Possible settings Priority Pump control panel or R100 External signals 1 Stop 2 Max. curve 3 Stop 4 Min. curve Min. curve 5 Setting of head Setting of head With bus signal A number between 1 and 64 can be allocated to a pump or changed so that the R100 or a unit connected to the bus network can distinguish between two or more pumps. The Grundfos Pump Management System 2000 can, however, only accept the numbers 1 to 8. For further details, see the installation and operating instructions for the management system in question Twin-head pump Priority Pump control panel or R100 Possible settings External signals Bus signal 1 Stop 2 Max. curve 3 Stop Stop 4 Max. curve 5 Min. curve Min. curve 6 Setting of head This display can only be used in connection with twin-head pumps. See also the document "Supplement to installation instructions". 23

24 English (GB) 9. Fault finding Warning Before removing the control box cover, make sure that the power supply has been switched off for at least 5 minutes. The pumped liquid may be scalding hot and under high pressure. Before any removal or dismantling of the pump, the system must therefore be drained, or the isolating valves on either side of the pump must be closed. See also section 7.7 Indicator lights. Fault Cause Remedy 1. The pump is not running. None of the indicator lights are on. 2. The pump is not running. The green indicator light is flashing. 3. The pump has stopped due to a fault. The red indicator light is on, and the green indicator light is off. 4. The pump is operating, but has been stopped due to a fault. The red and green indicator lights are on. 5. The pump has been set to stop, but it has been stopped due to a fault. The red indicator light is on, and the green indicator light is flashing. 6. Noise in the system. The green indicator light is on. 7. Noise in the pump. The green indicator light is on. a) One fuse in the installation is blown. b) The current-operated or voltageoperated circuit breaker has tripped out. Replace the fuse. Cut in the circuit breaker. c) The pump is defective. Repair or replace the pump. The pump has been stopped in one of the following ways: 1. With the button. 2. With the R External on/off switch in position off.* 4. Via bus signal.* 1. Start the pump by pressing. 2. Start the pump with the R100 or by pressing. 3. Switch on the on/off switch.* 4. Start the pump via bus signal.* *The fault can be temporarily corrected by selecting max. curve duty on the pump or with the R100 as external forced-control signals will be ignored. a) Power supply failure (for example undervoltage). b) Pump blocked and/or impurities in the pump. Check that the power supply falls within the specified range. Remove the vent screw, turn the rotor with a screwdriver inserted into the slot in the shaft end, and/or dismantle and clean the pump. c) Fault in electronics. Contact Grundfos. a) The pressure and temperature sensor is defective. b) The pump has restarted automatically after a temporary fault. a) The pressure and temperature sensor is defective. b) The pump has restarted automatically after a temporary fault. Check sensor connection. Replace if necessary. Reset the fault indication. Check sensor connection. Replace, if necessary. Reset the fault indication. a) Air in the system. Vent the system. b) The flow is too high. Reduce the head (setpoint), and possibly change over to constant pressure. c) The pressure is too high. Reduce the head (setpoint), and possibly change over to proportional pressure. a) Air in the pump. Vent the pump. b) The inlet pressure is too low. Increase the inlet pressure, and/or check air volume in the expansion tank (if installed). 24

25 Fault Cause Remedy 8. Insufficient heat in some places in the heating system. Note a) The flow is too low. Increase the head (setpoint) and/or change over to constant pressure. The R100 can also be used for fault finding. English (GB) 10. Megging Megging of an installation incorporating an UPE pump is not allowed, as the built-in electronics may be damaged. If megging of the pump is necessary, the pump should be electrically separated from the installation. Twin head pumps: The master and slave pumps must be megged separately. Megging of the pump can be carried out as described below Megging of UPE pumps See also section 5.2 Wiring diagram. 1. Switch off the power supply. 2. Remove the conductors from terminals L, N and earth (terminals 9, 10 and 11). 3. Short-circuit terminals L and N using a short wire. 4. Test between terminals L/N and earth. Maximum test voltage: 1000 VAC or 1500 VDC. Note: Never test between supply terminals (L and N). Maximum permissible leakage current: <20mA. 5. Remove the short wire between terminals L and N. 6. Fit the supply wires to terminals L and N and the earth terminal. 7. Switch on the power supply High-voltage test If it is necessary to high-voltage test the UPE pump, the megging instructions must be followed. See section 10. Megging. 25

26 English (GB) 11. Service kits Warning Before starting work on the pump, make sure that the mains switch has been switched off. It must be ensured that the power supply cannot be accidentally switched on. The service kits can be ordered as required: Service kit Pump type Product number Pump head UPE(D) 80/ FZ Control box, complete UPE(D) 80/ FZ Sensor, complete UPE(D) 80/ FZ Connection cable UPED FZ Gasket kit UPE(D) 80/ FZ Fan UPE(D) 80/ FZ Air vent plug UPE(D) 80/ FZ Flap valve kit UPED FZ

27 12. Technical data Supply voltage 1 x 230 V - 10 %/+ 6 %, 50/60 Hz. Motor protection The pump requires no external motor protection. Enclosure class IPX4D. Relative air humidity Maximum 95 %. Ambient temperature 0 C to +40 C. Temperature class TF110 to EN Liquid temperature Maximum: +110 C. Continuously: +2 C to +95 C. Ambient temperature [ C] System pressure The system pressure is indicated on the nameplate. Pump type UPE(D) FZ UPE FZ Maximum liquid temperature [ C] 0 to System pressure PN 6 PN 10 PN 16 [MPa] [MPa] [MPa] Number of bolt holes Inlet pressure The following minimum pressures must be available at the pump inlet during operation: Liquid temperature EMC (electromagnetic compatibility) EN Electromagnetic disturbance, first environment (residential areas). Immunity to electromagnetic disturbance, second environment (industrial areas). Sound pressure level The sound pressure level of the pump is lower than 38 db(a). Leakage current The pump mains filter will cause a discharge current to earth during operation. I leakage < 3.5 ma. Inputs and outputs Start/stop input Min. curve input Input for analog 0-10 V signal Signal output Bus input 13. Disposal External potential-free switch. Contact load: 5 V, 0.5 ma. Screened cable. Loop resistance: Maximum 130 Ω/km. Logical levels: Logical zero: U < 1.5 V. Logical one: U > 4.0 V. External signal: 0-10 VDC. Maximum load: 1 ma. Screened cable. Internal potential-free changeover contact. Maximum load: 250 V, 2 A, AC1. Minimum load: 5 V, 1 ma. Screened cable. Grundfos bus protocol, GENIbus protocol, RS-485. Screened cable. Lead cross section: mm 2. Cable length: Maximum 1200 m. This product or parts of it must be disposed of in an environmentally sound way: 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. English (GB) Pump type UPE(D) FZ UPE FZ 75 C 90 C 110 C [bar]/ [MPa] 0.6/ / 0.06 [bar]/ [MPa] 1.0/ / 0.1 [bar]/ [MPa] 1.7/ / 0.17 Subject to alterations. 27

GRUNDFOS MAGNA Series 2000

GRUNDFOS MAGNA Series 2000 GRUNDFOS INSTRUCTIONS GRUNDFOS MAGNA Series 2000 MAGNA 32-120, 40-120, 50-120, 65-120, 50-60, 65-60 Installation and operating instructions Declaration of Conformity We, Grundfos, declare under our sole

More information

N CX 5500 DAT Operating and Instruction manual

N CX 5500 DAT Operating and Instruction manual N0. 148258 00 DAT.1998-10-26 CX 5500 Operating and Instruction manual ENGLISH CX 5500 Technical data m = 8.6 kg = 43 db(a) U = 120/230 V f = 50/60 Hz T = 0-30 C Must only be used for * Spot suction of

More information

GRUNDFOS MAGNA Series 2000 MAGNA , , 65-60

GRUNDFOS MAGNA Series 2000 MAGNA , , 65-60 GRUNDFOS INSTRUCTIONS GRUNDFOS MAGNA Series 2000 MAGNA 40-120, 65-120, 65-60 Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are

More information

User Manual. PBA428 Weighing platform

User Manual. PBA428 Weighing platform User Manual PBA428 Weighing platform Service XXL Congratulations on choosing the quality and precision of METTLER TOLEDO. Proper use according to these instructions and regular calibration and maintenance

More information

INSTRUCTIONS & MAINTENANCE SHEET HYDROTEST PUMPS

INSTRUCTIONS & MAINTENANCE SHEET HYDROTEST PUMPS INSTRUCTIONS & MAINTENANCE SHEET HYDROTEST PUMPS HAP0070, HAP0130, HAP0180, HAP0250, HAP0400, HAP0740, HAP1300, HAP1900, HAP2900 V03.2013 DECLARATION OF CONFORMITY DECLARACION DE CONFORMIDAD LARZEP, S.A.

More information

SAUTER TVO Version /2014 GB

SAUTER TVO Version /2014 GB Sauter GmbH Tel.: +49-[0]7433-9933-199 Fax: +49-[0]7433-9933-149 Internet: www.sauter.eu Instruction Manual Motorized Vertical Test Stand SAUTER TVO Version 1.3 11/2014 GB PROFESSIONAL MEASURING TVO-BA-e-1413

More information

Lenntech BME, BMET. Installation and operating instructions. Tel Fax.

Lenntech BME, BMET. Installation and operating instructions. Tel Fax. GRUNDFOS INSTRUCTIONS BME, BMET Installation and operating instructions Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 English (GB) English (GB) Installation and

More information

GRUNDFOS INSTRUCTIONS. UPE Series 2000 UPE(D) FZ, UPE FZ. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. UPE Series 2000 UPE(D) FZ, UPE FZ. Installation and operating instructions GRUNDFOS INSTRUCTIONS UPE Series 2000 UPE(D) 80-120 FZ, UPE 100-120 FZ Installation and operating instructions UPE Series 2000 Declaration of Conformity.......................................... 4 English

More information

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE 1 & 3 phase

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE 1 & 3 phase GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE CRKE, SPKE, MTRE, CIE 1 & 3 phase Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted

More information

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions Declaration of Conformity We, Grundfos, declare under our sole responsibility that the products Hydro MPC, to which this declaration

More information

TriScroll TM 300 Series Dry Scroll Vacuum Pump

TriScroll TM 300 Series Dry Scroll Vacuum Pump vacuum technologies TriScroll TM 300 Series Dry Scroll Vacuum Pump MODULE REPLACEMENT MANUAL idealvac.com Manual No. 699904285 Revision E May 2003 (505)872-0037 idealvac.com Varian TriScroll 300 Dry Scroll

More information

Service instructions. MAGNA Series 2000

Service instructions. MAGNA Series 2000 Service instructions MAGNA Series 2000 Magna 32-120, 40-120, 50-60, 50-120, 65-60, 65-120 1 phase 50/60 Hz The pump must be serviced by a qualified person. Service must be carried out in accordance with

More information

PRE-SWEEP / DUST CONTROL KIT. For Advance Hydro-Retriever 3800 / Nilfisk BR 1000 CONTENTS OF KIT

PRE-SWEEP / DUST CONTROL KIT. For Advance Hydro-Retriever 3800 / Nilfisk BR 1000 CONTENTS OF KIT 56409786 PRE-SWEEP / DUST CONTROL KIT For Advance Hydro-Retriever 3800 / Nilfisk BR 1000 CONTENTS OF KIT ITEM PART NO. QTY DESCRIPTION 56040587 1 Instruction Sheet * N/A 1 Pre-sweep Assembly A 56409558

More information

GRUNDFOS INSTRUCTIONS. Hydro Multi-E. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro Multi-E. Installation and operating instructions GRUNDFOS INSTRUCTIONS ydro Multi-E Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions. CONTENTS Page

More information

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME

CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE CRKE, SPKE, MTRE, CHIE, CME 1 & 3 phase Installation and operating instructions 2 English (US) Installation and operating instructions Original installation and operating

More information

Operating manual FP-2. Index

Operating manual FP-2. Index Operating manual FP-2 Index 1 Introduction... 2 2 Technical data... 2 3 Maintenance... 2 4 Directions of safety... 2 5 Starting... 3 6 Exhaustion... 4 7 Searching for an error... 4 8 Spare parts... 5 9

More information

Operating Instructions Precision balance

Operating Instructions Precision balance KERN & Sohn GmbH Ziegelei 1 D-72336 Balingen E-Mail: info@kern-sohn.com Tel: +49-[0]7433-9933-0 Fax: +49-[0]7433-9933-149 Internet: www.kern-sohn.com Operating Instructions Precision balance KERN Version

More information

Instrucciones de instalación y funcionamiento Installation and operating instructions

Instrucciones de instalación y funcionamiento Installation and operating instructions Wilo-ElectronicControl D Einbau- und Betriebsanleitung E Instrucciones de instalación y funcionamiento GB Installation and operating instructions I Istruzioni di montaggio, uso e manutenzione F Notice

More information

Operating Instructions

Operating Instructions Operating Instructions Conversion box Model No. WV-TC312/WV-TC312E (The stand is removed from the conversion box in this illustration.) Before attempting to connect or operate this product, please read

More information

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Hydro MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions These installation

More information

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/ GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/98800750 English (GB) English (GB) Installation and operating instructions Original installation

More information

GRUNDFOS INSTRUCTIONS. Grundfos ALPHA Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Grundfos ALPHA Installation and operating instructions GRUNDFOS INSTRUCTIONS Grundfos ALPHA Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be

More information

RoboSterz. Automatic Management of Steering Without Operator ITA. Mod. V.

RoboSterz. Automatic Management of Steering Without Operator ITA. Mod. V. RoboSterz Automatic Management of Steering Without Operator ITA Mod. V. INDEX 1. What is it "RoboSterz"... 6 1.1. Benefits... 6 1.2. Installation... 6 2. Use of RoboSterz... 7 2.1. Use of the Robosterz

More information

Adam Equipment. TBB - TRIPLE BEAM Mechanical Balance Manual. 8141, RevD Nov2015 (ENG)

Adam Equipment. TBB - TRIPLE BEAM Mechanical Balance Manual. 8141, RevD Nov2015 (ENG) Adam Equipment TBB - TRIPLE BEAM Mechanical Balance Manual 8141, RevD Nov2015 (ENG) @Adam Equipment Company 2015 P.N. 8141, RevD Nov2015) CONTENTS / INHALT / TABLE DES MATIERES / CONTENIDO / CONTENUTO

More information

GRUNDFOS INSTRUCTIONS. Hydro Multi-B. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Hydro Multi-B. Installation and operating instructions GRUNDFOS INSTRUCTIONS Hydro Multi-B Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

User manual / 230 V. Electronically controlled motor, constant torque with intermediate reverse

User manual / 230 V. Electronically controlled motor, constant torque with intermediate reverse User manual 16800-115 / 230 V Electronically controlled motor, constant torque with intermediate reverse TABLE OF CONTENTS Chap. Description Page 1 GENERALITY 1 2 Recommendations and percautions before

More information

Communicating Electronic Control for Fan Coil Units Régulation électronique communicante pour ventilo-convecteurs

Communicating Electronic Control for Fan Coil Units Régulation électronique communicante pour ventilo-convecteurs Installation and maintenance manual Manuel d installation et de maintenance R English Français Communicating Electronic Control for Fan Coil Units Régulation électronique communicante pour ventilo-convecteurs

More information

GRUNDFOS INSTRUCTIONS. DME, Variant B. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. DME, Variant B. Installation and operating instructions GRUNDFOS INSTRUCTIONS DME, Variant B Installation and operating instructions GB Declaration of Conformity We, Grundfos Alldos, declare under our sole responsibility that the products DME, to which this

More information

MagnaRail. MagnaRail. For emergency vehicles, trucks and buses EXHAUST RAIL INSTRUCTION MANUAL GB. No (00)

MagnaRail. MagnaRail. For emergency vehicles, trucks and buses EXHAUST RAIL INSTRUCTION MANUAL GB. No (00) For emergency vehicles, trucks and buses EXHAUST RAIL INSTRUCTION MANUAL GB No. 144249(00) 2009-12-04 2 GB LIST OF CONTENTS Technical data... Pre-installation... Mounting instructions... Setting the code...

More information

Beton Trowel nv INSTRUCTION MANUAL SLAB SAW BTCS500 - GEBABEBB BBRUBEBB BNP FORTIS: ING: BE BE

Beton Trowel nv INSTRUCTION MANUAL SLAB SAW BTCS500 - GEBABEBB BBRUBEBB BNP FORTIS: ING: BE BE INSTRUCTION MANUAL SLAB SAW BTCS500 BBRUBB 1/20 Use this guide along with the parts lists attached to locate and identify components of your saw. When ordering replacement parts, be sure to provide the

More information

Company name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact:

Company name: GSI Created by: Xiao Ying Wong Phone: Date: 10/03/2017 Client: Client Number: Contact: Position Qty. Description 2 NBG 125-8-16/156 A-F2-A-BAQE Product No.: On request Non-self-priming, single-stage, centrifugal volute pump designed according to ISO 5199 with dimensions and rated performance

More information

BoosterpaQ - Hydro MPC

BoosterpaQ - Hydro MPC GRUNDFOS INSTRUCTIONS BoosterpaQ - Hydro MPC Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only

More information

GRUNDFOS INSTRUCTIONS MTH. Installation and operating instructions

GRUNDFOS INSTRUCTIONS MTH. Installation and operating instructions GRUNDFOS INSTRUCTIONS MTH Installation and operating instructions Declaration of Conformity We, Grundfos, declare under our sole responsibility that the products MTH, to which this declaration relates,

More information

POWER SUPPLY UNIT FOR 3 KW MAGNETRON TECHNICAL NOTE

POWER SUPPLY UNIT FOR 3 KW MAGNETRON TECHNICAL NOTE POWER SUPPLY UNIT FOR 3 KW MAGNETRON TECHNICAL NOTE (Issue April 2004) CE Declaration of Conformity Dichiarazione di Conformità CE Manufacturer s Name: Nome del Costruttore: Manufacturer s Address: Indirizzo

More information

Wilo-Control SC-Fire Jockey

Wilo-Control SC-Fire Jockey Pioneering for You Wilo-Control SC-Fire Jockey de en fr Einbau- und Betriebsanleitung Installation and operating instructions Notice de montage et de mise en service nl Inbouw- en bedieningsvoorschriften

More information

1. General description CONTENTS. 1.1 Applications. The Buerkert 7800 dosing pump is a self-priming diaphragm

1. General description CONTENTS. 1.1 Applications. The Buerkert 7800 dosing pump is a self-priming diaphragm CONTENTS Page 1. General description 4 1.1 Applications 4 1.2 Type key 5 2. Technical data 6 2.1 Mechanical data 6 2.2 Electrical data 6 2.3 Input/output data 6 2.4 Dimensions 7 3. Installation 7 3.1 Safety

More information

RI.15KI. L Rev. 04/03/02 MIKROCONTROLLER-STEUERUNG FÜR. Betriebsanleitung

RI.15KI. L Rev. 04/03/02 MIKROCONTROLLER-STEUERUNG FÜR. Betriebsanleitung L8542624 Rev. 04/03/02 CENTRALINA A MICROPROCESSORE PER CTROL UNIT WITH MICROCTROLLER FOR MIKROCTROLLER-STEUERUNG FÜR CENTRALE A MICROCTRÔLEUR POUR CENTRALITA A MICROPROCESADOR POR RI.15KI UNI EN ISO 9001

More information

3 Specification Magneta Smedegaard

3 Specification Magneta Smedegaard 3 Specification Magneta Smedegaard 3.1 Variable Speed Circulator Pumps Main applications Heating, ventilation, air-conditioning, refrigerating and circulation systems - One-pipe and two-pipe systems -

More information

Grundfos MAGNA, Relay Module

Grundfos MAGNA, Relay Module GRUNDFOS INSTRUCTIONS Grundfos MAGNA, Relay Module Installation and operating instructions 2 Grundfos MAGNA, Relay Module Installation and operating instructions 4 3 LIMITED WARRANTY Products manufactured

More information

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Quick guide. Plug-in fans GPPM with FC101_106 August 2014 Quick guide Plug-in fans GPPM with FC101_106 August 2014 Fläkt Woods permanent magnet motors and speed controllers for plug fans GPPM 1. General Fläkt Woods offers a wide range of permanent magnet motors

More information

GRUNDFOS INSTRUCTIONS. CUE, Hp. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. CUE, Hp. Installation and operating instructions GRUNDFOS INSTRUCTIONS CUE, 0.75-125 Hp Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

GRUNDFOS INSTRUCTIONS MAGNA3. Installation and operating instructions

GRUNDFOS INSTRUCTIONS MAGNA3. Installation and operating instructions GRUNDFOS INSTRUCTIONS MAGNA3 Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS Page 1.

More information

GRUNDFOS INSTRUCTIONS MAGNA3. Installation and operating instructions

GRUNDFOS INSTRUCTIONS MAGNA3. Installation and operating instructions GRUNDFOS INSTRUCTIONS MAGNA3 Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS Page 1.

More information

Operating Instructions School Balance

Operating Instructions School Balance KERN & Sohn GmbH Ziegelei 1 D-72336 Balingen E-Mail: info@kern-sohn.com Tel: +49-[0]7433-9933-0 Fax: +49-[0]7433-9933-149 Internet: www.kern-sohn.com Operating Instructions School Balance KERN Version

More information

Adam Equipment. User Manual (EN) Pricing Retail RAV Series Adam Equipment Co. Ltd.

Adam Equipment. User Manual (EN) Pricing Retail RAV Series Adam Equipment Co. Ltd. Adam Equipment Pricing Retail RAV Series User Manual (EN) (P.N. 3.02.6.6.12923, Revision 1.00, Effective Feb2016 ENG/FR/DE/ES) 2016 Adam Equipment Co. Ltd. ENGLISH: P 1-4 FRANÇAIS: P 5-9 DEUTSCH: P 10-16

More information

KERN HFB Version /2012 GB

KERN HFB Version /2012 GB PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 info@pce-americas.com PCE Instruments UK Ltd. Units 12/13 Southpoint Business

More information

Submersible Tank Pump

Submersible Tank Pump Submersible Tank Pump Applications: Silent household pressure systems, garden irrigation, or water transfer. Performance Outline Pump Features High efficiency moulded impellers Stainless steel construction,

More information

TOTAL AIRTOOL SERVICES (UK) Ltd

TOTAL AIRTOOL SERVICES (UK) Ltd TOTAL AIRTOOL SERVICES (UK) Ltd BALANCER OPERATING MANUAL Reproduced from Tecna manual Translation of the Original Instructions Install the balancer before using it. This operation is to be carried out

More information

Unilift KP 150, KP 250, KP 350

Unilift KP 150, KP 250, KP 350 GRUNDFOS INSTRUCTIONS Unilift KP 150, KP 250, KP 350 Installation and operating instructions DRAINAGE PUMP 1Z28 LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted

More information

INSTRUCTION MANUAL ABIS-06 Premium airmotor

INSTRUCTION MANUAL ABIS-06 Premium airmotor INSTRUCTION MANUAL ABIS-06 Premium airmotor www.beveltools.com 01-2015 For your safety, please read manual thoroughly before operating. After reading this manual, keep it in a place that the user always

More information

User manual Humdinger concrete vibrator

User manual Humdinger concrete vibrator www.betontrowel.com 1590130051 BETONTROWEL.COM User manual Humdinger concrete vibrator 2015 IP44 I 2 Introduction Legal note This user manual contains the original instructions, written in the English

More information

BoosterpaQ - Hydro MPC

BoosterpaQ - Hydro MPC GRUNDFOS INSTRUCTIONS BoosterpaQ - Hydro MPC Installation and operating instructions LIMITED WARRANTY Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION en OPERATING INSTRUCTION 86152-13EN G 09/11 Halogen Light Arrow HLPK13 ( flashing arrow / flashing cross ) part no. 21023 Halogen Light Arrow HLPK13 ( flashing arrow / flashing cross ) with electric motor

More information

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when

More information

Datalogic Scanning, Inc. 959 Terry Street Eugene, Oregon Telephone: (541) Fax: (541)

Datalogic Scanning, Inc. 959 Terry Street Eugene, Oregon Telephone: (541) Fax: (541) Datalogic Scanning, Inc. 959 Terry Street Eugene, Oregon 97402 Telephone: (541) 683-5700 Fax: (541) 345-7140 An Unpublished Work - All rights reserved. No part of the contents of this documentation or

More information

4 Specification Magneta Smedegaard twin pumps

4 Specification Magneta Smedegaard twin pumps 4 Specification Magneta Smedegaard twin pumps 4.1 Variable Speed Circulator Pumps Designation: Example Magneta Smedegaard 30-60D Key to the designation Main applications Heating, ventilation, air-conditioning,

More information

Sandfiltration kit + Swimmey pump

Sandfiltration kit + Swimmey pump Sandfiltration kit + Swimmey pump INSTALLATION ENGLISH INSTRUCTIONS The manufacturer has the right to modify the products without previous notice for as far as their characteristics are not really changed

More information

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete booster systems 50/60 Hz

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete booster systems 50/60 Hz GRUNDFOS DT BOOKET ydro Solo-E Complete booster systems 50/60 z ydro Solo-E Table of contents 1. Product introduction 3 Introduction..................................................................................

More information

TOTAL AIRTOOL SERVICES (UK) Ltd

TOTAL AIRTOOL SERVICES (UK) Ltd TOTAL AIRTOOL SERVICES (UK) Ltd BALANCER OPERATING MANUAL Reproduced from Tecna manual Translation of the Original Instructions Install the balancer before using it. This operation is to be carried out

More information

MKT Series AUDIPACK. AUDIPACK Industriestraat GT Moerkapelle The Netherlands

MKT Series AUDIPACK. AUDIPACK Industriestraat GT Moerkapelle The Netherlands UDIPCK UDIPCK Industriestraat 2 2751 GT Moerkapelle The Netherlands Tel: +31(0)795931671 Fax: +31(0)795933115 Email: audipack@audipack.com www.audipack.com MKT Series MKT Series-01-2010-02 MKT Series CHECKLIST

More information

Instruction Manual. Dosing Pump type /150l/h

Instruction Manual. Dosing Pump type /150l/h Instruction Manual Dosing Pump type 7800 60/150l/h CONTENTS Page 1. General description 4 1.1 Applications 4 1.2 Type key 5 2. Technical data 6 2.1 Mechanical data 6 2.2 Electrical data 6 2.3 Input/output

More information

GRUNDFOS DATA BOOKLET. Grundfos UPBasic. Circulator pumps 50 Hz

GRUNDFOS DATA BOOKLET. Grundfos UPBasic. Circulator pumps 50 Hz GRUNDFOS DATA BOOKLET Grundfos UPBasic Circulator pumps 50 Hz Contents General data Performance ranges Page Product range, 1 x 0 V, 50 Hz Page 4 Type key Page 4 Construction Page 4 Material specification

More information

GRUNDFOS DATA BOOKLET. Self-priming multistage pumps 50 Hz

GRUNDFOS DATA BOOKLET. Self-priming multistage pumps 50 Hz GRUNDFOS DATA BOOKLET Self-priming multistage pumps 50 Hz Contents General data Applications 3 Type key 3 Pumped liquids 3 Operating conditions 3 Technical data 3 Features and benefits 3 Control panel

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

GRUNDFOS INSTRUCTIONS BMEX. Installation and operating instructions

GRUNDFOS INSTRUCTIONS BMEX. Installation and operating instructions GRUNDFOS INSTRUCTIONS BMEX Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions. CONTENTS Page 1. Symbols

More information

SINCE Circulating Pumps. Series 500. available in both the single and twin version.

SINCE Circulating Pumps. Series 500. available in both the single and twin version. SINCE 1981 Circulating Pumps Series 500 available in both the single and twin version. www.flofab.com GB ENGLISH 2. GENERAL Read this documentation carefully before installation. INPUT POWER CABLE INSTALL

More information

ISTRUZIONI PER L'INSTALLAZIONE E LA MANUTENZIONE INSTRUCTIONS DE MISE EN SERVICE ET D'ENTRETIEN INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE

ISTRUZIONI PER L'INSTALLAZIONE E LA MANUTENZIONE INSTRUCTIONS DE MISE EN SERVICE ET D'ENTRETIEN INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE ISTRUZIONI PER L'INSTALLAZIONE E LA MANUTENZIONE INSTRUCTIONS DE MISE EN SERVICE ET D'ENTRETIEN INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE INSTALLATIONSANWEISUNG UND WARTUNG INSTRUCTIES VOOR INGEBRUIKNAME

More information

Japanese Technology since Ego Circulators. Databook

Japanese Technology since Ego Circulators. Databook Japanese Technology since 1912 Ego Circulators Databook Japanese Technology since 1912 www.ebaraeurope.com INDEX Ego Range GENERAL INTRODUCTION THREADED CIRCULATORS THREADED/FLANGED CIRCULATORS FLANGED

More information

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting

More information

DUNE DCT SERIES Manual

DUNE DCT SERIES Manual Adam Equipment DUNE DCT SERIES Manual (P.N. 9384, Revision B3, March 2016) Adam Equipment Company 2016 Easy Reference: Model name of the scale: Serial number of the unit: Software revision number (Displayed

More information

POWER SUPPLY UNIT FOR 2 KW MAGNETRON TECHNICAL NOTE

POWER SUPPLY UNIT FOR 2 KW MAGNETRON TECHNICAL NOTE POWER SUPPLY UNIT FOR 2 KW MAGNETRON TECHNICAL NOTE (Issue October 2004) CE Declaration of Conformity Dichiarazione di Conformità CE Manufacturer s Name: Nome del Costruttore: Manufacturer s Address: Indirizzo

More information

TOTAL AIRTOOL SERVICES (UK) Ltd

TOTAL AIRTOOL SERVICES (UK) Ltd TOTAL AIRTOOL SERVICES (UK) Ltd BALANCER OPERATING MANUAL Reproduced from Tecna manual Translation of the Original Instructions Install the balancer before using it. This operation is to be carried out

More information

GRUNDFOS DATA BOOKLET. Hydro Multi-B. Booster systems with 2 or 3 pumps. 50/60 Hz

GRUNDFOS DATA BOOKLET. Hydro Multi-B. Booster systems with 2 or 3 pumps. 50/60 Hz GRUNDFOS DATA BOOKLET Hydro Multi-B Booster systems with 2 or 3 pumps 50/60 Hz Hydro Multi-B Table of contents 1. Product introduction 3 Applications..................................................................................

More information

GRUNDFOS DATA BOOKLET. Control HVAC. For variable-primary-flow systems

GRUNDFOS DATA BOOKLET. Control HVAC. For variable-primary-flow systems GRUNDFOS DATA BOOKLET Control HVAC For variable-primary-flow systems Control HVAC Table of contents 1. Product description 3 Introduction..................................................................................

More information

LHS/LHSa SERIES Manual

LHS/LHSa SERIES Manual Adam Equipment LHS/LHSa SERIES Manual (P.N. 7.00.6.6.0200, Revision B November 2012) Software version L1.1/LA1.1 Adam Equipment Company 2012 1.0 CONTENTS 1.0 CONTENTS... 1 2.0 INTRODUCTION... 2 2.1 FEATURES...

More information

TYPE NO. AS APPROPRIATE

TYPE NO. AS APPROPRIATE Victor Products Ltd New York Way New York Industrial Park Newcastle upon Tyne NE27 0QF ENGLAND Tel : +44(0)191 2808000 Fax : +44(0)191 2808080 0518 Making Hazardous Environments Work A42 RANGE OF 250AMP

More information

Delta HE 35-XX, 55-XX

Delta HE 35-XX, 55-XX Installation and Operating Instructions Delta HE 35-XX, 55-XX 10.2009 Table of contents Table of contents EC Conformity Declaration Technical Data Delta HE 35 Technical Data Delta HE 55 Mounting Instructions

More information

GEIGER GJ56.. AIR (GJ56.. F03) for Venetian blinds

GEIGER GJ56.. AIR (GJ56.. F03) for Venetian blinds Motor for Venetian blinds: GEIGER GJ56.. AIR (GJ56.. F03) for Venetian blinds DE FR ES IT Original-Montage- und Betriebsanleitung Original assembly and operating instructions Notice originale de montage

More information

Operating instructions

Operating instructions Operating instructions BB www.bron.ch Operating instructions Powerbox 900 by bron Before use We are pleased you have chosen a Powerbox 900 by bron which is a high-quality product in every respect. If used

More information

TECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00

TECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00 TECHNICAL MANUAL EN Inverter / Charger Combi Combi SW 12V 1600VA Réf : PF.16088 Combi SW 24V 3800VA Réf : PF.16089 SAFETY PRECAUTIONS TO PREVENT ANY RISK OF ELECTRIC SHOCK OR FIRE, READ THIS MANUAL CAREFULLY

More information

grundfos INSTRUCTIONS BMS/ BMST/ BMSX High pressure and reverse osmosis systems

grundfos INSTRUCTIONS BMS/ BMST/ BMSX High pressure and reverse osmosis systems grundfos INSTRUCTIONS BMS/ BMST/ BMSX High pressure and reverse osmosis systems A BMS hp 9 0 Pos. Description Raw-water feed pump Pressure gauge (raw water) Filter Low-pressure switch Flowmeter BMS hp

More information

NBE40-125/139 AS-F2-A-BAQE

NBE40-125/139 AS-F2-A-BAQE GRUNDFOS DATA BOOKLET NBE-125/139 AS-F2-A-BAQE Grundfos pump 999983 Thank you for your interest in our products. Please contact us for more information, or visit our website https://www.lenntech.com/grundfos/nbe/999983/nbe--125-139-as-f2-a-e-baqe.html

More information

KSEV97X. IT Libretto Istruzioni GB Instruction Manual. 11 FR Manuel d Instructions 20 DE Bedienungsanleitung 29 NL Gebruiksaanwijzing

KSEV97X. IT Libretto Istruzioni GB Instruction Manual. 11 FR Manuel d Instructions 20 DE Bedienungsanleitung 29 NL Gebruiksaanwijzing IT Libretto Istruzioni 2 Instruction Manual 11 FR Manuel d Instructions 20 DE Bedienungsanleitung 29 NL Gebruiksaanwijzing 38 ES Manual de Instrucciones 47 KSEV97X Dear Customer, If you follow the recommendations

More information

Operating and maintenance instructions

Operating and maintenance instructions Operating and maintenance instructions Fleece disc Klünder disc Hermann Klünder GmbH Brückenstraße 1 D-31628 Landesbergen Tel: +49(0)5025/94073, Fax: 49 (0) 5025/94074 www.mietenpflege.de Table of Contents

More information

TOTAL AIRTOOL SERVICES (UK) Ltd

TOTAL AIRTOOL SERVICES (UK) Ltd TOTAL AIRTOOL SERVICES (UK) Ltd BALANCER OPERATING MANUAL Reproduced from Tecna manual Translation of the Original Instructions Install the balancer before using it. This operation is to be carried out

More information

How to Order. Nil. W Water-cooled refrigerator type. Temperature: 5 to 40 C, Humidity: 30 to 70%RH Clean water 5 to /1.

How to Order. Nil. W Water-cooled refrigerator type. Temperature: 5 to 40 C, Humidity: 30 to 70%RH Clean water 5 to /1. Thermo-cooler Series HRGC Specifications HRGC//5 Cooling method Refrigerant Control method Ambient temperature/humidity Circulating fluid Note ) Temperature range setting Note ) C Cooling capacity Note

More information

c-go 24V/6A 24V/8A 24V/12A

c-go 24V/6A 24V/8A 24V/12A c-go 24V/6A 24V/8A 24V/12A Battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Quick start guide... 4 4. Operation... 4 5. Problem solving... 6 6. Specifications...

More information

Instruction Manual Electronic Crane Scales. Logbook Regular maintenance and care KERN HUS/HUM Version /2011 GB

Instruction Manual Electronic Crane Scales. Logbook Regular maintenance and care KERN HUS/HUM Version /2011 GB KERN & Sohn GmbH Ziegelei 1 D-72336 Balingen E-Mail: info@kern-sohn.com Tel: +49-[0]7433-9933-0 Fax: +49-[0]7433-9933-149 Internet: www.kern-sohn.com Instruction Manual Electronic Crane Scales Logbook

More information

NKE80-160/175A2F2AE-SBQQE

NKE80-160/175A2F2AE-SBQQE GRUNDFOS DATA BOOKLET NKE8-1/17AFAE-SBQQE Grundfos Pump 99187 Thank you for your interest in our products Please contact us for more information, or visit our website https://www.lenntech.com/grundfos/nkebasis/99187/nke-8-1-17-a-f-a-e-bqqe.html

More information

Multi-Mover Charger for model L25

Multi-Mover Charger for model L25 Multi-Mover Charger for model L25 Important safety instruction. Keep these instructions. This manual contains important instructions for the safety of the user and the operation of the device. 1. SYMBOLS

More information

Lenntech. Lenntech SQ, SQ-N, SQE, SQE-N. Submersible pumps 50/60 Hz GRUNDFOS DATA BOOKLET. Tel.

Lenntech. Lenntech SQ, SQ-N, SQE, SQE-N. Submersible pumps 50/60 Hz GRUNDFOS DATA BOOKLET.  Tel. Lenntech GRUNDFOS DATA BOOKLET SQ, SQ-N, SQE, SQE-N Submersible pumps 50/60 Hz Lenntech info@lenntech.com info@lenntech.com Tel. Tel. +31-152-610-900 +31-152-610-900 www.lenntech.com www.lenntech.com Fax.

More information

Originalbetriebsanleitung - Akku-Schlagbohrschrauber 6. Original operating manual - Cordless percussion drill 10

Originalbetriebsanleitung - Akku-Schlagbohrschrauber 6. Original operating manual - Cordless percussion drill 10 Festool GmbH Wertstraße 0 D-730 Wendlingen Tel.: +9 (0)70/80-0 Telefax: +9 (0)70/80-0608 www.festool.com Originalbetriebsanleitung - Akku-Schlagbohrschrauber 6 Original operating manual - Cordless percussion

More information

HD-X2. Operating Instructions. Ref. No H /1232

HD-X2. Operating Instructions. Ref. No H /1232 english HD-X2 Operating Instructions IRO AB Box 54 SE-523 22 Ulricehamn SWEDEN Tel: (+46) 32 297 00 Fax: (+46) 32 298 00 info@iro.se www.iroab.com Contents HD-X2 Contents... Safety...2 Technical specifications...3

More information

LK Manifold Shunt VS2

LK Manifold Shunt VS2 LK Manifold Shunt VS2 Design LK Manifold Shunt VS2 is a shunt unit with a two way control valve used in systems with a primary pump. The shunt unit is mountable from both the left and right of LK Manifolds.

More information

Service instructions. MS6 3.7 kw - 30 kw. 50/60 Hz 3~

Service instructions. MS6 3.7 kw - 30 kw. 50/60 Hz 3~ Service instructions MS6 3.7 kw - 30 kw 50/60 Hz 3~ 1. Symbols used in this document... 2 2. Identification... 2 2.1 Nameplate... 2 2.2 Frequency converter operation... 2 2.3 Product number key... 3 2.4

More information

VOLUMETRIC PUMPS. BOMBA ELIAS has developed the volumetric for clean water suitable for small flow rates and average height.

VOLUMETRIC PUMPS. BOMBA ELIAS has developed the volumetric for clean water suitable for small flow rates and average height. VOLUMETRIC PUMPS NIZA PISCIS Introduction: BOMBA ELIAS has developed the volumetric for clean water suitable for small flow rates and average height. NIZA series are technopolymers volumetric pumps, and

More information

Operation instructions Platform/floor scales

Operation instructions Platform/floor scales KERN & Sohn GmbH Ziegelei 1 D-72336 Balingen E-Mail: info@kern-sohn.com Tel: +49-[0]7433-9933-0 Fax: +49-[0]7433-9933-149 Internet: www.kern-sohn.com Operation instructions Platform/floor scales KERN EOB/EOE/EOS/BOBP

More information

GEIGER-GJ56.. with mechanical end stop For Venetian blinds and exterior blinds

GEIGER-GJ56.. with mechanical end stop For Venetian blinds and exterior blinds Venetian blind motor: GEIGER-GJ56.. with mechanical end stop For Venetian blinds and exterior blinds DE FR ES IT Original-Montage- und Betriebsanleitung Original assembly and operating instructions Notice

More information

BARTELL MORRISON INC. 375 Annagem Blvd., Mississauga, ON L5T 3A7 Telephone: Fax: CONCRETE MIXER

BARTELL MORRISON INC. 375 Annagem Blvd., Mississauga, ON L5T 3A7 Telephone: Fax: CONCRETE MIXER BARTELL MORRISON INC. 375 Annagem Blvd., Mississauga, ON L5T 3A7 Telephone: 1-647-953-4100 Fax: 1-647-953-4101 CONCRETE MIXER MC6PH160, MC6PE150, MC75SH160, MC75SE200, MC95PH240, MC95PE200, MC95SH240,

More information

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage.

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage. INSTALLATI Speed-controlled drive system manufacturer EMS Model Units included S for rotary heat exchanger EURA, size 20 60. Page Content 1 Technical data 1 Units included............motor, Control unit

More information