MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For heat loss replacement, floor heating and radiant space heating

Size: px
Start display at page:

Download "MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For heat loss replacement, floor heating and radiant space heating"

Transcription

1 MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE For heat loss replacement, floor heating and radiant space heating MI Configuration Type SUA Design A Heated length lead length PRODUCT OVERVIEW Heat-loss replacement replaces heat in concrete floors built over garages, loading docks, arcades, and other cold spaces. The cable is typically attached to the bottom of concrete floors. Type SUB, HLR and FH Design B lead length Heated length Hot/cold joint NPT threaded connector lead length Comfort floor heating warms concrete, tile, stone and marble floors in lobbies, foyers, bathrooms, kitchens and gymnasiums. The cable is typically embedded in concrete or a thick mortar bed. Radiant space heating provides primary space heating for rooms with concrete floors. The cable is typically embedded in concrete or a thick mortar bed. Hot/cold NPT threaded joint connector Type HLR heating cables are supplied with a copper sheath and are ideally suited for heat loss replacement applications. Types SUA, SUB and FH heating cables have a copper sheath that is covered with an extruded high-density polyethylene (HDPE) jacket and are suitable for applications where the cable is directly embedded in concrete or mortar floors. The heating cables are factory assembled with an HDPE jacketed copper sheath cold lead, pre-terminated and ready to connect to a junction box. The copper sheath provides an ideal ground path and allows for a rugged yet flexible heating cable that is easy to install. The radiant heat provided by the Raychem heating cable allows you to feel comfortable at lower air temperatures, resulting in lower heating costs. Thermal Management representatives can provide design assistance and help you install the product that meets your goals for an efficient, cost-effective floor heating system. CABLE CONSTRUCTION Type HLR heating cable Sheath Seamless copper Insulation Magnesium oxide Conductor type Alloy or copper Number of conductors 1 Insulation voltage rating 600 V (without jacket) 0.10 to 0.05 in (3.0 to 5. mm) Raychem-DS-H5808-MIfloorheatingCOM-EN / 9

2 CABLE CONSTRUCTION Types SUA, SUB and FH heating cable Jacket HDPE Sheath Seamless copper Insulation Magnesium oxide Conductor type Alloy or copper Number of conductors 1 Insulation voltage rating 600 V (with jacket) 0.00 to in (5.1 to 7.7 mm) lead (Type SUA/SUB/HLR/FH cables) Jacket HDPE Sheath Seamless copper Insulation Magnesium oxide Conductor type Copper Number of conductors 1 or Insulation voltage rating 600 V (with jacket) to 0.40 in (7.9 to 10.7 mm) Gland (NPT) 1/ in length 1 in (30 mm) MINIMUM INSTALLATION TEMPERATURE F ( 30 C) MINIMUM BENDING RADIUS 6 times cable TYPE HLR - HEAT LOSS REPLACEMENT CABLE SPECIFICATIONS 10 Volts and 08 Volts, 3-phase Wye HLR1 B 61CD H5A Y HLR B 61CD H5A Y HLR3 B 61CD H5A Y HLR4 B 61CD H5A Y HLR5 B 61CD H5A Y HLR6 B 61CE H5A Y HLR7 B 61CE H5A Y HLR8 B 61CE H5A Y HLR9 B 61CE H5A Y HLR10 B 61CE H5A Y HLR11 B 61CE H5A Y HLR1 B 61CE H30A Y HLR13 B 61CC H40A Y / 9 Raychem-DS-H5808-MIfloorheatingCOM-EN-1707

3 TYPE HLR - HEAT LOSS REPLACEMENT CABLE SPECIFICATIONS 08 Volts HLR14 B 61CD H5A Y HLR15 B 61CD H5A Y HLR16 B 61CD H5A Y HLR17 B 61CD H5A Y HLR18 B 61CE H5A Y HLR19 B 61CE H5A Y HLR0 B 61CE H5A Y HLR1 B 61CE H5A Y HLR B 61CE H5A Y HLR3 B 61CE H5A Y HLR4 B 61CE H30A Y HLR5 B 61CC H40A Y Volts HLR6 B 61CD H5A Y HLR7 B 61CD H5A Y HLR8 B 61CD H5A Y HLR9 B 61CD H5A Y HLR30 B 61CE H5A Y HLR31 B 61CE H5A Y HLR3 B 61CE H5A Y HLR33 B 61CE H5A Y HLR34 B 61CE H5A Y HLR35 B 61CE H5A Y HLR36 B 61CE H30A Y HLR37 B 61CC H40A Y Volts and 480 Volts, 3-phase Wye HLR38 B 61CD H5A Y HLR39 B 61CD H5A Y HLR40 B 61CD H5A Y HLR41 B 61CD H5A Y HLR4 B 61CE H5A Y HLR43 B 61CE H5A Y HLR44 B 61CE H5A Y HLR45 B 61CE H5A Y HLR46 B 61CE H5A Y HLR47 B 61CE H5A Y HLR48 B 61CE H30A Y HLR49 B 61CC H40A Y Raychem-DS-H5808-MIfloorheatingCOM-EN / 9

4 TYPE HLR - HEAT LOSS REPLACEMENT CABLE SPECIFICATIONS 347 Volts and 600 Volts, 3-phase Wye HLR50 B 61CD H5A Y HLR51 B 61CD H5A Y HLR5 B 61CD H5A Y HLR53 B 61CD H5A Y HLR54 B 61CE H5A Y HLR55 B 61CE H5A Y HLR56 B 61CE H5A Y HLR57 B 61CE H5A Y HLR58 B 61CE H5A Y HLR59 B 61CE H5A Y HLR60 B 61CE H30A Y Volts HLR61 B 61CD H5A Y HLR6 B 61CD H5A Y HLR63 B 61CD H5A Y HLR64 B 61CD H5A Y HLR65 B 61CE H5A Y HLR66 B 61CE H5A Y HLR67 B 61CE H5A Y HLR68 B 61CE H5A Y HLR69 B 61CE H5A Y Volts HLR70 B 61CD H5A Y HLR71 B 61CD H5A Y HLR7 B 61CD H5A Y HLR73 B 61CD H5A Y HLR74 B 61CE H5A Y HLR75 B 61CE H5A Y HLR76 B 61CE H5A Y HLR77 B 61CE H5A Y / 9 Raychem-DS-H5808-MIfloorheatingCOM-EN-1707

5 TYPE SUA/SUB - FLOOR HEATING AND RADIANT SPACE HEATING CABLE SPECIFICATIONS 10 Volts and 08 Volts, 3-phase Wye SUA A 61HD HA Y SUA3 A 61HD HA Y SUA4 A 61HD HA Y SUA7 A 61HD HA Y SUA8 A 61HE HA Y SUB1 B 61HE H5A Y SUB B 61HE H5A Y SUB3 B 61HE H30A Y SUB4 B 61HE H30A Y SUB5 B 61HE H40A Y SUB6 B 61HE H40A Y SUB7 B 61HE H40A Y SUB8 B 61HC H60A Y SUB9 B 61HC H60A Y SUB10 B 61HC H80A Y Volts SUA1 A 61HD HA Y SUA6 A 61HE HA Y SUB19 B 61HD H5A Y SUB0 B 61HE H5A Y SUB1 B 61HE H5A Y SUB B 61HE H5A Y Volts SUA1 A 61HD HA Y SUA6 A 61HE HA Y SUB19 B 61HD H5A Y SUB0 B 61HE H5A Y SUB1 B 61HE H5A Y SUB B 61HE H5A Y Volts and 480 Volts, 3-phase Wye SUB19 B 61HD H5A Y SUB0 B 61HE H5A Y SUB1 B 61HE H5A Y SUB B 61HE H5A Y Volts and 600 Volts, 3-phase Wye SUB11 B 61HD H5A Y SUB1 B 61HD H5A Y SUB13 B 61HE H5A Y SUB14 B 61HE H5A Y Raychem-DS-H5808-MIfloorheatingCOM-EN / 9

6 TYPE FH - FLOOR HEATING AND RADIANT SPACE HEATING CABLE SPECIFICATIONS 10 Volts and 08 Volts, 3-phase Wye FH1 B 61HD H5A Y FH B 61HD H5A Y FH3 B 61HD H5A Y FH4 B 61HD H5A Y FH5 B 61HE H5A Y FH6 B 61HE H5A Y FH7 B 61HE H5A Y FH8 B 61HE H5A Y FH9 B 61HE H5A Y FH10 B 61HE H5A Y FH11 B 61HE H5A Y Volts FH1 B 61HD H5A Y FH13 B 61HD H5A Y FH14 B 61HD H5A Y FH15 B 61HD H5A Y FH16 B 61HE H5A Y FH17 B 61HE H5A Y FH18 B 61HE H5A Y FH19 B 61HE H5A Y FH0 B 61HE H5A Y FH1 B 61HE H5A Y FH B 61HE H5A Y Volts FH3 B 61HD H5A Y FH4 B 61HD H5A Y FH5 B 61HD H5A Y FH6 B 61HD H5A Y FH7 B 61HE H5A Y FH8 B 61HE H5A Y FH9 B 61HE H5A Y FH30 B 61HE H5A Y FH31 B 61HE H5A Y FH3 B 61HE H5A Y FH33 B 61HE H5A Y / 9 Raychem-DS-H5808-MIfloorheatingCOM-EN-1707

7 TYPE FH - FLOOR HEATING AND RADIANT SPACE HEATING CABLE SPECIFICATIONS 77 Volts and 480 Volts, 3-phase Wye FH34 B 61HD H5A Y FH35 B 61HD H5A Y FH36 B 61HD H5A Y FH37 B 61HD H5A Y FH38 B 61HE H5A Y FH39 B 61HE H5A Y FH40 B 61HE H5A Y FH41 B 61HE H5A Y FH4 B 61HE H5A Y FH43 B 61HE H5A Y FH44 B 61HE H5A Y Volts and 600 Volts, 3-phase Wye FH45 B 61HD H5A Y FH46 B 61HD H5A Y FH47 B 61HD H5A Y FH48 B 61HD H5A Y FH49 B 61HE H5A Y FH50 B 61HE H5A Y FH51 B 61HE H5A Y FH5 B 61HE H5A Y FH53 B 61HE H5A Y FH54 B 61HE H5A Y Volts FH55 B 61HD H5A Y FH56 B 61HD H5A Y FH57 B 61HD H5A Y FH58 B 61HD H5A Y FH59 B 61HE H5A Y FH60 B 61HE H5A Y FH61 B 61HE H5A Y FH6 B 61HE H5A Y Volts FH63 B 61HD H5A Y FH64 B 61HD H5A Y FH65 B 61HD H5A Y FH66 B 61HD H5A Y FH67 B 61HE H5A Y FH68 B 61HE H5A Y Raychem-DS-H5808-MIfloorheatingCOM-EN / 9

8 APPROVALS GROUND-FAULT PROTECTION Note: For heat loss replacement applications where the cable is attached to the bottom of the concrete floor, contact Thermal Management for additional information. To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Thermal Management, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection. Many Raychem control and monitoring systems meet the ground-fault protection requirement. 8 / 9 Raychem-DS-H5808-MIfloorheatingCOM-EN-1707

9 NORTH AMERICA Tel: Fax: Tel: Fax: Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice Pentair. Raychem-DS-H5808-MIfloorheatingCOM-EN / 9

MI Heating Cable. HDPE jacketed, copper sheathed MI cable. For surface snow melting in concrete, asphalt, and pavers. MI Heating Cable Configuration

MI Heating Cable. HDPE jacketed, copper sheathed MI cable. For surface snow melting in concrete, asphalt, and pavers. MI Heating Cable Configuration MI Heating Cable HDPE jacketed, copper sheathed MI cable For surface snow melting in concrete, asphalt, and pavers Pipe Freeze Protection and Flow Maintenance Fire Sprinkler System Freeze Protection MI

More information

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For commercial and industrial applications. Heating cable construction

MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE. For commercial and industrial applications. Heating cable construction MI HEATING CABLE COPPER AND HDPE JACKETED COPPER SHEATHED MI CABLE For commercial and industrial applications Heating cable construction Insulation (magnesium oxide) Heating conductor Copper sheath HDPE

More information

Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket

Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket SELF-REGULATING HEATING CABLE For pipe freeze protection and flow maintenance Heating cable construction Tinned-copper braid Modified polyolefin (-CR) or fluoropolymer (-CT) outer jacket Modified polyolefin

More information

XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES XMI-L STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES cable construction Corrugated stainless steel 316L outer sheath Insulation (magnesium oxide) conductors (dual)

More information

Product Overview. Application

Product Overview. Application Self-Regulating SC, SC/H Series-resistance heating cables for longline systems Electrical freeze protection for long pipelines in both nonhazardous and hazardous locations Power-Limiting Mineral Insulated

More information

STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES

STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES STAINLESS STEEL, LOW TEMPERATURE SHEATH CONSTANT WATTAGE MINERAL INSULATED HEATING CABLES Insulation (magnesium oxide) conductors (dual) Corrugated stainless steel 316L outer sheath Alloy 825 sheath cable

More information

Power-Limiting Cables

Power-Limiting Cables Power-Limiting Cables This section provides general design guidelines for power-limiting heat-tracing systems installed on insulated metal pipes. For other applications or design assistance, contact your

More information

SURFACE SNOW MELTING MI MINERAL INSULATED HEATING CABLE SYSTEM

SURFACE SNOW MELTING MI MINERAL INSULATED HEATING CABLE SYSTEM SURFACE SNOW MELTING MI MINERAL INSULATED HEATING CABLE SYSTEM This step-by-step design guide provides the tools necessary to design a Raychem Mineral Insulated heating cable surface snow melting system.

More information

C A Heating Cable Gland Kit Installation Instructions

C A Heating Cable Gland Kit Installation Instructions C75-100-A Heating Cable Gland Kit Installation Instructions Description The C75-100-A is a NEMA 4X-rated gland kit used to transition heating cables into a junction box when making connections off of a

More information

COPPER SHEATHED, MINERAL INSULATED FIRE-RATED WIRING CABLE

COPPER SHEATHED, MINERAL INSULATED FIRE-RATED WIRING CABLE PYOTENAX SYSTEM 1850 COPPE SHEATHED, MINEAL INSULATED FIE-ATED IING CALE Cable construction Magnesium oxide (MgO) insulation Solid copper conductors HDPE jacket (optional) Seamless copper sheath PODUCT

More information

PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS

PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS PMKG-JS POLYMATRIX SPLICE CONNECTION KIT INSTALLATION INSTRUCTIONS DESCRIPTION The PolyMatrix PMKG-JS is a NEMA 4X rated splice connection kit for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT

More information

JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions

JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions JBS-100-STB Single Entry Power Connection with Junction Box Installation Instructions Description The JBS-100-STB is a NEMA 4X rated power connection kit. It is designed for use with Raychem BTV-CR, BTV-CT,

More information

MI Heating Cable for Surface Snow Melting

MI Heating Cable for Surface Snow Melting MI Cable for Surface Snow Melting. Pipe Freeze Protection and Flow Maintenance Visit www.tycothermal.com for more information on our ten-year extended warranty. Pyrotenax brand copper sheath mineral insulated

More information

Heating Cable. Construction

Heating Cable. Construction MI Mineral Insulated High Temperature A B C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to 1112 F (600 C) Maximum Exposure Temperature 1200 F (648 C) (Power Off)

More information

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions

EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions Description The ElectroMelt EMK-XP Power Connection and End Seal Kit is for use with ElectroMelt EM2-XR and EM3-XR heating

More information

PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions

PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions PMKG-J2LP PolyMatrix Powered Splice Kit Installation Instructions Description The PolyMatrix PMKG-J2LP is a NEMA 4X rated connection kit for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT and

More information

JBM-100-STB NEMA 4X-rated connection kit Installation Instructions

JBM-100-STB NEMA 4X-rated connection kit Installation Instructions JBM-100-STB NEMA 4X-rated connection kit Installation Instructions Power Connection, Powered Splice, Powered Tee, Dual Power Connection, Splice or Tee with Junction Box Approvals Hazardous Locations CLI,

More information

SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions

SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions SPC-P Smart Power Connection with Temperature Monitoring Transmitter Pipe Mounted Installation Instructions SPC-P with Pyrotenax MI heating cable using required MI cable grounding kit SPC-P with Raychem

More information

C A HEATING CABLE GLAND KIT INSTALLATION INSTRUCTIONS

C A HEATING CABLE GLAND KIT INSTALLATION INSTRUCTIONS C75-100-A HEATING CABLE GLAND KIT INSTALLATION INSTRUCTIONS DESCRIPTION The C75-100-A is a NEMA 4X-rated gland kit used to transition heating cables into a junction box when making connections off of a

More information

Heating Cable. Construction

Heating Cable. Construction Mineral Insulated High Temperature A C Constant Wattage Series Resistance Heating Cable Sets Process Temperature Maintenance to F (593 C) Maximum Exposure Temperature 4 F (76 C) (Power Off) Corrosion Resistant

More information

JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS

JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS JBS-100-A, A6 SINGLE ENTRY POWER CONNECTION WITH JUNCTION BOX INSTALLATION INSTRUCTIONS DESCRIPTION The JBS-100-A and JBS-100-A6 are NEMA 4X-rated power connection kit. It is designed for use with Raychem

More information

ALLOY 825 SHEATHED, MINERAL INSULATED, FIRE-RATED WIRING CABLE

ALLOY 825 SHEATHED, MINERAL INSULATED, FIRE-RATED WIRING CABLE PYOTENAX SYSTEM 2000 ALLOY 825 SHEATHED, MINEAL INSULATED, FIE-ATED IING CALE Cable construction Seamless Alloy 825 metal sheath Magnesium oxide (MgO) insulation Solid nickel-clad copper conductors PODUCT

More information

SELF-REGULATING CABLES

SELF-REGULATING CABLES Self-Regulating SELF-REGULATING CABLES This step-by-step design guide provides the tools necessary to design a selfregulating heat-tracing system for insulated pipes and tubing. For other applications

More information

Self-regulating cables

Self-regulating cables Self-Regulating Self-regulating cables This step-by-step design guide provides the tools necessary to design a selfregulating heat-tracing system for insulated pipes and tubing. For other applications

More information

PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM

PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM PIPE FREEZE PROTECTION AND FLOW MAINTENANCE XL-TRACE SYSTEM This step-by-step design guide provides the tools necessary to design a Raychem XL-Trace pipe freeze protection or flow maintenance system. For

More information

XMI Mineral Insulated Heating Cables

XMI Mineral Insulated Heating Cables XMI Mineral Insulated Heating Cables This section provides an overview and general design guidelines for mineral insulated heat-tracing systems. For complete design assistance, contact your Pentair Industrial

More information

QUICKTERM TERMINATION KIT

QUICKTERM TERMINATION KIT PYROTENAX QUICKTERM TERMINATION KIT INSTALLATION INSTRUCTIONS FOR TERMINATING SINGLE CONDUCTOR COPPER SHEATHED MINERAL INSULATED CABLE DESCRIPTION This termination kit is used to terminate #6 AWG and larger

More information

MIQ MINERAL INSULATED HEATING CABLE INSTALLATION INSTRUCTIONS

MIQ MINERAL INSULATED HEATING CABLE INSTALLATION INSTRUCTIONS MIQ INSTALLATION INSTRUCTIONS MIQ CATALOGUE REF. NO. Example: D / MIQ-50E3H-2S / 200 / 1404 / 120 / 4 / 12 / 6 Design (A,B,D,E) Cable Reference Length (Feet or Meters) Watts Volts Cold Lead Length (Feet

More information

V (For 120, 208, 277, 600 V, please call.) Output: 37 W/ft 2 and 50W/ft 2 Cold lead:

V (For 120, 208, 277, 600 V, please call.) Output: 37 W/ft 2 and 50W/ft 2 Cold lead: Snow Melting Mats Data Sheet GENERAL PRODUCT INFORMATION ProLine snow melting mats feature pre-spaced heat cable (3 and 4-inch spacing) in mats that can be rolled out for quick, easy installation. To make

More information

Type LT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations

Type LT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations A, I, A, Operating Principle The parallel bus wires apply voltage along the entire length of the heater cable. The conductive core provides an infinite number of parallel conductive paths permitting the

More information

Type LT Self-Regulating Heater Cable For use in Ordinary (Unclassified) and Hazardous (Classified) Locations

Type LT Self-Regulating Heater Cable For use in Ordinary (Unclassified) and Hazardous (Classified) Locations F, G ;, Class I, Class Groups F, G; Operating Principle The parallel bus wires apply voltage along the entire length of the heater cable. The conductive core provides an infinite number of parallel conductive

More information

Type HLT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations

Type HLT Self-Regulating Heater Cable For use in Ordinary and Hazardous (Classified) Locations E, I, E, Description Nelson s Type HLT self-regulating heater cable is a parallel circuit electric heater strip. A conductive fluoropolymer core material is extruded over the multi-stranded, nickel-plated,

More information

Self-Regulating Cables

Self-Regulating Cables Self-Regulating 1. Self- Regulating 2. Power- Limiting This step-by-step design guide provides the tools necessary to design a self-regulating heat-tracing system for insulated pipes and tubing. For other

More information

HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES

HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES HWAT System INSTALLATION AND OPERATION MANUAL FOR HOT WATER TEMPERATURE MAINTENANCE SYSTEMS FOR THERMALLY INSULATED PIPES THERMAL MANAGEMENT SOLUTIONS WWW.THERMAL.PENTAIR.COM Important Safeguards and Warnings

More information

Warm Tiles Troubleshooting. Al & Jed

Warm Tiles Troubleshooting. Al & Jed Warm Tiles Troubleshooting Al & Jed C O N T E N T S DFT Cable Construction (p.1) An overview of how the cable is built and what comprises the cable. Types of Cable Faults (p.4) Discusses the different

More information

C Power Connection Kit

C Power Connection Kit 1548-4000C Power Connection Kit For use with Dekoron 2700 Family of Heating Cables Installation Instructions Kit Description The Dekoron 1548-4000C electrical connection kit distirbuted by Heat-Line is

More information

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance XL-Trace System Installation and Operation manual for pipe freeze protection and flow maintenance Thermal building solutions WWW.PENTAIRTHERMAL.COM Important Safeguards and Warnings WARNING: FIRE AND SHOCK

More information

HTSB system System overview

HTSB system System overview HTSB system System overview Easy planning of heating circuits Simple installation on site Wide operating temperature range The BARTEC HTSB heating system covers a wide range of applications in trace heating.

More information

THERMAL MANAGEMENT

THERMAL MANAGEMENT DESIGN GUIDELINES XL-TRACE LSZH SELF-REGULATING HEATING CABLES FOR PIPE FREEZE PROTECTION SYSTEMS THERMAL MANAGEMENT WWW.PENTAIRTHERMAL.COM PIPE FREEZE PROTECTION SYSTEM OVERVIEW SBS Control Panel T-Connection

More information

High Voltage Copper, Smooth Aluminum Shield/Sheath

High Voltage Copper, Smooth Aluminum Shield/Sheath High Voltage Copper, Smooth Aluminum Shield/Sheath XLPE Insulation, HDPE Jacket, 69 kv - 138 kv Features True triple vertical extrusion system for optimum insulation concentricity, and excellent electric

More information

Any inquiries, please feel free to contact or Caledonian

Any inquiries, please feel free to contact or Caledonian Caledonian Low Voltage cables to IEC 60502 Standard www.caledonian-cables.co.uk www.caledonian-cables.net 1 Addison Company Profile Caledonian. established in 1978.offers one of the most complete lines

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other

More information

Primary, Secondary, Post-Secondary Education Facilities

Primary, Secondary, Post-Secondary Education Facilities STABILOY Feeder Solutions Primary, Secondary, Post-Secondary Education Facilities Introduction At Alcan Cable your children s safety is our top concern. That is why our STABILOY aluminum alloy feeder cables

More information

Industrial, Heavy Insulated Mono-Tape. and Duo-Tape

Industrial, Heavy Insulated Mono-Tape. and Duo-Tape Industrial, Heavy Insulated Mono-Tape and Duo-Tape Description: HTS/Amptek AWD and AWM Heating Tapes are Single and Double Duo-Tapes designed for use in high temperature applications. AWD and AWM Heating

More information

Ecoflex potable PEX plus pre-insulated pipe system Installation guide

Ecoflex potable PEX plus pre-insulated pipe system Installation guide Ecoflex potable PEX plus pre-insulated pipe system Installation guide Ecoflex potable PEX plus pre-insulated pipe system installation guide l 1 Uponor Ecoflex potable PEX plus pre-insulated pipe system

More information

SIGNATURE WiFi-Enabled. WiFi-enabled. ELEMENT Non-Programmable. Dual-voltage (120 V & 240 V)

SIGNATURE WiFi-Enabled. WiFi-enabled. ELEMENT Non-Programmable. Dual-voltage (120 V & 240 V) THERMOSTATS SIGNATURE WiFi-Enabled Floor Heating Thermostat WiFi-enabled 3.5 Color touchscreen Energy usage monitor 7-day programmability Dual-voltage (120 V & 240 V) HOME Programmable Floor Heating Thermostat

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

NYY-J Cable. Dungannon Electrical Wholesale Tel: Page 1 of 10

NYY-J Cable. Dungannon Electrical Wholesale Tel: Page 1 of 10 NYY-J Cable Application: A VDE approved, solid conductor, black PVC jacketed, 600/1kV power and control cable. These power cables are designed for energy supply cable ducts, power station, industry and

More information

ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS

ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS ElectroMelt System INSTALLATION AND OPERATION MANUAL FOR SURFACE SNOW MELTING AND ANTI-ICING SYSTEMS THERMAl MANAGEMENT WWW.PENTAIRTHERMAl.COM Important Safeguards and Warnings WARNING: FIRE AND SHOCK

More information

Mineral-Insulated RTD Temperature Probe According to DIN EN 60751

Mineral-Insulated RTD Temperature Probe According to DIN EN 60751 ata Sheet 902210 Page 1/12 Mineral-Insulated RT Temperature Probe According to IN EN 60751 For temperatures from -50 (-200) to +600 C Flexible sheath cable with vibration-resistant measuring insert As

More information

HOSPITAL AND HEALTHCARE

HOSPITAL AND HEALTHCARE STABILOY Brand Feeder Solutions HOSPITAL AND HEALTHCARE Introduction General Cable understands that hospitals require complex buiding designs that must address a wide range of systems and applications.

More information

High Voltage Aluminum, Smooth Aluminum Shield/Sheath

High Voltage Aluminum, Smooth Aluminum Shield/Sheath High Voltage Aluminum, Smooth Aluminum Shield/Sheath XLPE Insulation, HDPE Jacket, 69 kv - 138 kv Features True triple vertical extrusion system for optimum insulation concentricity, and excellent electric

More information

NABTEB Past Questions and Answers - Uploaded online

NABTEB Past Questions and Answers - Uploaded online NATIONAL BUSINESS AND TECHNICAL EXAMINATIONS BOARD (NABTEB) ELECTRICAL INSTALLATION AND MAINTENANCE WORKS (041) MAY/JUNE, 2005 Question: 1(a) 1(b) What is Stroboscopic effect? With the aid of a diagram,

More information

Troubleshooting Checklist

Troubleshooting Checklist Troubleshooting Checklist Fax Number US & Canada: 1-877-270-1738 Easyheat.Technicalservices@Emerson.com Return this completed document to your contact at Easy Heat Warm Tiles along with photographs or

More information

Cable resistance thermometer Model TR40

Cable resistance thermometer Model TR40 Electrical temperature measurement Cable resistance thermometer Model TR40 WIKA data sheet TE 60.40 for further approvals see page 11 Applications For direct installation into the process Machine building

More information

H900 WinterGard Power Connection Kit with End Seal Installation Instructions

H900 WinterGard Power Connection Kit with End Seal Installation Instructions H900 WinterGard Power Connection Kit with End Seal Installation Instructions Power connection for H311, H611, and H621 Power connection for H612 and H622 Description The WinterGard power connection kit

More information

ATHLETIC STADIUMS AND SPORTS ARENAS

ATHLETIC STADIUMS AND SPORTS ARENAS STABILOY Brand Feeder Solutions ATHLETIC STADIUMS AND SPORTS ARENAS Introduction Stadiums of all shapes and sizes require a consistent source of power to keep their fans happy. At General Cable, dependability

More information

FTG10OM1-0,6/1KV. 50 N/mm 2 of copper section max for fixed layings

FTG10OM1-0,6/1KV. 50 N/mm 2 of copper section max for fixed layings HEPR insulated flexible with braided shield of red copper wires and plastic sheath of halogen-free flame retardant and without emission of corrosive gases. The keeps the electrical characteristics for

More information

VALSIR SUPPLY SYSTEMS MIXAL

VALSIR SUPPLY SYSTEMS MIXAL TECHNICAL DATA SHEET VALSIR SUPPLY SYSTEMS MIXAL The product Mixal is an extremely flexible multilayer pipe and is therefore ideal for the creation of floor, wall and ceiling radiant heating and cooling

More information

Section 4 ASTM Ecoflex Thermal Single Submittal Information Revision H: Dec. 20, 2010 Project Information Job Name: Location: Engineer: Contractor: Manufacturer s Representative: Technical Data Part No.

More information

Troubleshooting Checklist

Troubleshooting Checklist Troubleshooting Checklist Fax Number US & Canada: 1-877-270-1738 Easyheat.Technicalservices@Emerson.com Return this completed document to your contact at Easy Heat Warm Tiles along with photographs or

More information

In-Pipe Retro 240 V In-pipe freeze protection heating cable Installation Instructions

In-Pipe Retro 240 V In-pipe freeze protection heating cable Installation Instructions all In-Pipe Retro 240 V In-pipe freeze protection heating cable Installation Instructions Approvals Type PS, X Made in Canada Kit Contents Item Qty Note: This product is suitable for use in potable water.

More information

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 Product HVS Series Cable Splice Shim Kit for 1/C Extruded Dielectric (Poly/EPR) Power Cables: Metallic Tape, Wire Shield, UniShield, LC Shield, Lead Sheath or Concentric Neutral URD Cables UniShield is

More information

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS

HAK-C-100 CONNECTION KIT FOR DIVISION 1 HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS HAK-C-100 CONNCTION KIT FO DIVISION 1 HAZADOUS LOCATIONS INSTALLATION INSTUCTIONS APPOVALS Hazardous Locations (1) (1) xcept VPL. KIT CONTNTS Class I, Div. 1, Groups B, C, D Class II, Div. 1, Groups, F,

More information

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1).

AutoMatrix Power Connection Kit. (1) This type 4X enclosure is intended for indoor or outdoor use primarily to. (2) May be required (see step 1). R AMG-BC-III AutoMatrix Power Connection Kit Description The AMG-BC-III is a copper free aluminum (maximum 4/10 of 1% copper) NEMA 4X (1) rated power connection kit for single or dual heating cable entry.

More information

THIS MATERIAL IS MEANT TO BE USED ALONG WITH OUR CATALOG IT IS NOT A SUBSTITUTE FOR THE CATALOG

THIS MATERIAL IS MEANT TO BE USED ALONG WITH OUR CATALOG IT IS NOT A SUBSTITUTE FOR THE CATALOG THIS MATERIAL IS MEANT TO BE USED ALONG WITH OUR CATALOG IT IS NOT A SUBSTITUTE FOR THE CATALOG COMPANY OVERVIEW Since 1970, we have been pioneering new developments in heater technology and providing

More information

UNDERGROUND TRANSMISSION SOLUTIONS PRODUCT CATALOG

UNDERGROUND TRANSMISSION SOLUTIONS PRODUCT CATALOG UNDERGROUND TRANSMISSION SOLUTIONS PRODUCT CATALOG SOUTHWIRE SOLUTIONS FOR UNDERGROUND TRANSMISSION CABLES SERVICES XLPE Cables 69 through 400 kv with Copper and Aluminum conductors through 6,800 kcmil

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

2011 NEC Code Updates Part 3

2011 NEC Code Updates Part 3 www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Kompensator External Low Voltage Heating Cable System

Kompensator External Low Voltage Heating Cable System External Low Voltage Heating Cable System LOW VOLTAGE Installation Instructions General Information Kit Contents Qty Description 1 heating cable at pre-determined length Table of Contents General Information........................

More information

MgO ORDER CODES. 1-1 Thermocouple Types CODE

MgO ORDER CODES. 1-1 Thermocouple Types CODE MgO Insulated Thermocouples with Extension Leadwire MgO Insulated Thermocouples with Sheath Terminations A Pyromation MgO thermocouple assembly consists of a thermocouple element swaged in hardpacked standard

More information

Electrical Protection

Electrical Protection Electrical Protection Excessive current in any electrical circuit is hazardous and not desired, and these maybe caused by the following; 1. Overloads, and 2. Short-circuits. Overload Currents: These are

More information

Electrical Safety. Recognizing & Controlling Hazards

Electrical Safety. Recognizing & Controlling Hazards Electrical Safety Recognizing & Controlling Hazards Introduction Healthcare facilities, including hospitals, physician offices, laboratoratories, dental offices and beyond are vulnerable to a variety of

More information

P High Voltage Catalogue Cables Australia Powering your Project

P High Voltage Catalogue Cables Australia Powering your Project P +61 8 9367 8978 www.cablesaustralia.com.au High Catalogue Cables Australia Powering your Project CABLES AUSTRALIA PTY LTD HIGH VOLTAGE CATALOGUE ABOUT US Cables Australia is a locally owned and operated

More information

Aermotor 4 Submersible Pumps - 5, 8, 12, 16, 20, 22 & 25 GPM

Aermotor 4 Submersible Pumps - 5, 8, 12, 16, 20, 22 & 25 GPM A+ SUPER SUB series stainless steel Precision engineered stainless steel 4 submersible pumps that deliver dependable performance and efficiency in all applications. Heads to 000 feet and capabilities to

More information

Cable thermocouple Model TC40

Cable thermocouple Model TC40 Electrical temperature measurement Cable thermocouple Model TC40 WIKA data sheet TE 65.40 for further approvals see page 11 Applications For direct installation into the process Machine building Motors

More information

Page 2. Pitot tube anti-ice. Windshield Anti-ice Components. Propeller Anti-ice Components. Wing boot anti-ice pneumatic components

Page 2. Pitot tube anti-ice. Windshield Anti-ice Components. Propeller Anti-ice Components. Wing boot anti-ice pneumatic components Ice & Rain Trainer Component Location Page 2 Pitot tube anti-ice Propeller Anti-ice Components Windshield Anti-ice Components Wing boot anti-ice pneumatic components Control and Indicating Components 110

More information

INSTALLATION PRODUCTION TESTS

INSTALLATION PRODUCTION TESTS Deadbreak Apparatus Connectors 600 A 15/25 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-10 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class Bol-T Deadbreak Connector is used to terminate

More information

STABILOY BRAND FEEDER SOLUTIONS INDUSTRIAL FACILITIES AND FACTORIES

STABILOY BRAND FEEDER SOLUTIONS INDUSTRIAL FACILITIES AND FACTORIES STABILOY BRAND FEEDER SOLUTIONS INDUSTRIAL FACILITIES AND FACTORIES Introduction When it comes to feeder cables, General Cable keeps industries of all types humming with cost savings on total installation,

More information

Thermocouples W A T L O W

Thermocouples W A T L O W W A T O W Watlow s mineral insulated thermocouples are fast-responding, durable, and capable of handling high temperatures. These thermocouples are manufactured with best-in-class XACTPAK, Watlow s trademark

More information

Cable thermocouple Model TC40

Cable thermocouple Model TC40 Electrical temperature measurement Cable thermocouple Model TC40 WIKA data sheet TE 65.40 Applications For direct installation into the process Machine building Motors Bearings Pipelines and vessels Special

More information

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions Segurança TC RU C-DE.ГБ06.B.00230 OCP 0004 Compulsório INMETRO Operation Manual and Installation Instructions Segurança PSB Heating System Cold applied connection technology Compulsório Type 27-1680-...0/...

More information

FR-N1X1G1. Low voltage - Energy, cabling, signalling and control

FR-N1X1G1. Low voltage - Energy, cabling, signalling and control Low voltage - Energy, cabling, signalling and control FR-N1X1G1 Construction: NF C 32-323 NF C 32-323/1 Fire propagation: NF EN 60332-3-24 NF C 32-070 C1 IEC 60332-3-24 C Flame propagation: NF EN 60332-1-2

More information

Ecoflex Pre-insulated Pipe Systems

Ecoflex Pre-insulated Pipe Systems ECOFLEX PRE-ISULATED PIPE SSTEMS PRODUCT GUIDE Ecoflex Pre-insulated Pipe Systems A Flexible, Sustainable and Durable Solution Designed for fluid transfer in a variety of hydronic heating, cooling and

More information

STABILOY BRAND FeeDeR SOLuTIONS

STABILOY BRAND FeeDeR SOLuTIONS STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum

More information

Technical Data Sheet Unshielded (YY) PVC Control Cable

Technical Data Sheet Unshielded (YY) PVC Control Cable Technical Data Sheet Unshielded (YY) PVC Control Cable MachFlex 350 YY VDE Registered Flexible PVC Control Cables Applications Designed for applications which are installed in occasional flexing and fixed

More information

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets OFFSHORE WIND FEASIBILITY STUDY APPENDICES 10-7 10.3.2 Appendix C.2 Subsea Cable Data Sheets Design data for TFVA 36 kv 3x1x240 mm 2 KQ Metallic Laying up Inner sheath Bedding Armor Diameter of conductor

More information

MGO Thermocouples. Controls. Connection Head. Connection Head. Thermowells. Junction Fittings. Connectors Connection Heads.

MGO Thermocouples. Controls. Connection Head. Connection Head. Thermowells. Junction Fittings. Connectors Connection Heads. Connection Head Type J, K, T and E Grounded Ungrounded Exposed Sheath Materials 304 Stainless Steel 316 Stainless Steel Inconel 600 Standard Aluminum Aluminum Flip Top Cast Iron/Aluminum 316 Stainless

More information

Pow-R-Flex low ampere busway

Pow-R-Flex low ampere busway Pow-R-Flex low ampere busway Commercial Industrial Telecommunications Data centers Research Light manufacturing Pow-R-Flex low ampere busway Pow-R-Flex low ampere busway Pow-R-Flex low ampere busway provides

More information

BS6724 SWA/LSZH Cable IEC /1000V

BS6724 SWA/LSZH Cable IEC /1000V BS6724 SWA/LSZH Cable IEC 60502 600/1000V Applications: Power cable suitable for power networks, where fire emission of smoke and toxic fumes creates a serious potential threat. Suitable for direct burial.

More information

Hot runner thermocouple Model TC46

Hot runner thermocouple Model TC46 Electrical temperature measurement Hot runner thermocouple Model TC46 WIKA data sheet TE 65.46 for further approvals see page 7 Applications Plastics and rubber industry Hot runner bushings, drops and

More information

Aim higher. Soil & Waste System

Aim higher. Soil & Waste System Aim higher Soil & Waste System Driven by durability FACT Trend towards prefabrication In most countries the labour costs are becoming an increasing part of the total installed cost of a project. To keep

More information

Thermocouple Model TC10-H without thermowell

Thermocouple Model TC10-H without thermowell Electrical temperature measurement Thermocouple Model TC10-H without thermowell WIKA data sheet TE 65.08 for further approvals see page 7 Applications For direct installation in the process Machine building

More information

ITS-50R TRANSFER SWITCH OWNER S MANUAL

ITS-50R TRANSFER SWITCH OWNER S MANUAL ITS-50R OWNER S MANUAL IOTA Engineering Transfer Switches provide automatic power switching between two or three separate 120/240 volt AC input sources, including powercords, onboard generators, onboard

More information

PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual (PT-Series)

PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual (PT-Series) PRO-Tect Pipe Freeze Protection Self-Regulating Heating Cable Install Manual () Free Design Service 24/7 Installation Support (800) 875-5285 www.warmlyyours.com Assembly Tools Needed Utility knife Wire

More information

ORDER CODES CODE. Special limits of error High-Purity MgO Insulation (99.4% Pure) Use this table only if options are desired.

ORDER CODES CODE. Special limits of error High-Purity MgO Insulation (99.4% Pure) Use this table only if options are desired. MgO Insulated Thermocouples with Extension Leadwire MgO Insulated Thermocouples with Sheath Terminations Pyromation MgO thermocouple assembly consists of a thermocouple element swaged in hard-packed, standard-purity

More information

Spring Test 7 due 05/03/2013

Spring Test 7 due 05/03/2013 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous

More information

GFCI-AFCI FAQ. Where are AFCIs and GFCIs required?

GFCI-AFCI FAQ. Where are AFCIs and GFCIs required? GFCI-AFCI FAQ What does an AFCI do? o An AFCI will shut down, or trip, a branch circuit when certain conditions are met. AFCIs monitor the circuit for arc faults, an unintentional electrical discharge

More information

Elegance Electrician s Installation Guide

Elegance Electrician s Installation Guide Elegance Electrician s Installation Guide CentraLite Systems, Inc. 6420 Wall St. Mobile, AL 36695 Phone: 877-466-5483 Fax: 251-607-9119 2003-2005 CentraLite Systems, Inc. Revised 10/20/2005 ELECTRICIAN

More information

Limit Switch - Safety Type with pull button reset Plastic Body IP65 and Metal Body IP66

Limit Switch - Safety Type with pull button reset Plastic Body IP65 and Metal Body IP66 Limit Switch - Safety Type with pull button reset Plastic Body IP65 and Metal Body IP66 Double Insulation (for thermoplastic type) High mechanical resistant Degree of protection IP65 (thermoplastic) IP66

More information