Oklahoma Gas & Electric P.O. Box 321 Oklahoma City, OK, Main Street, Suite 900 Cambridge, MA 02142

Size: px
Start display at page:

Download "Oklahoma Gas & Electric P.O. Box 321 Oklahoma City, OK, Main Street, Suite 900 Cambridge, MA 02142"

Transcription

1 Final Report Oklahoma Gas & Electric System Loss Study Submitted to Oklahoma Gas & Electric P.O. Box 321 Oklahoma City, OK, Submitted by Stone & Webster Management Consultants, Inc. 1 Main Street, Suite 900 Cambridge, MA August 14, 2008

2 LEGAL NOTICE This report was prepared by Stone & Webster Management Consultants, Inc. ("Stone & Webster Consultants") expressly for Oklahoma Gas & Electric. ( OG&E ). Neither Stone & Webster Consultants, nor OG&E, nor any person acting in their behalf, (a) makes any warranty, express or implied, with respect to the use of any information or methods disclosed in this report; or (b) assumes any liability with respect to the use of any information or methods disclosed in this report. Any recipient of this report, by their reliance on, acceptance or use of this report, releases Stone & Webster Consultants and its affiliates from any liability for any direct, indirect, consequential or special loss or damage whether arising in contract, tort (including negligence) or otherwise. Nothing expressed in this report should be construed as a legal opinion as to compliance with law or regulation. ELECTRONIC MAIL NOTICE Electronic mail copies of this report are not official unless authenticated and signed by Stone & Webster Consultants and are not to be modified in any manner without Stone & Webster Consultants' express written consent. i

3 Electric System Loss Study Table of Contents Section Description Page 1 EXECUTIVE SUMMARY TECHNICAL LOSSES LOSS ALLOCATION LOSS FACTOR DEVELOPMENT RESULTS INTRODUCTION TRANSMISSION SYSTEM LOSSES TRANSMISSION LINE LOSSES TRANSMISSION TRANSFORMER LOSSES CORONA LOSSES TRANSMISSION SYSTEM LOSS SUMMARY DISTRIBUTION PRIMARY LOSSES TRANSFORMER LOAD LOSSES TRANSFORMER NO- LOAD LOSSES SUMMARY OF DISTRIBUTION PRIMARY TRANSFORMER LOSSES DISTRIBUTION PRIMARY DISTRIBUTION LINES PRIMARY 4-KV LINES PRIMARY 12-KV LINES PRIMARY 24-KV LINES PRIMARY 34.5-KV LINES SUMMARY OF PRIMARY DISTRIBUTION LINE LOSSES DISTRIBUTION SECONDARY SYSTEM DISTRIBUTION SECONDARY TRANSFORMERS DISTRIBUTION SECONDARY LINES AND SERVICE DROPS CUSTOMER METERS NON-TECHNICAL LOSSES HOURLY LOAD ALLOCATION PROCEDURE CONCLUSION HISTORICAL LOSSES LOSS STUDY COMPARISONS METHODOLOGY ATTACHMENTS...30 ii

4 Electric System Loss Study Tables in Report LIST OF TABLES IN OG&E SYSTEM LOSS STUDY Table 1 Calculated Losses and Non-Technical Losses...2 Table 2 Adjusted Calculated Losses...3 Table 3 Losses by Service Level...5 Table 4 Monthly Losses and Loss Factors...6 Table 5 Categories of Load and No-Load Losses...9 Table 6 Corona Losses...13 Table 7 Transmission System Losses...13 Table 8 Distribution Primary Transformer Losses...15 Table 9 Modeled 4-kV Circuits...16 Table 10 Modeled 12-kV Circuits...18 Table 11 Modeled 24-kV Circuits...20 Table 12 Modeled 34-kV Circuit Loads and Losses...21 Table 13 Losses in Primary Distribution Lines...22 Table 14 Secondary Transformer Losses...24 Table 15 Secondary Lines and Service Drops Losses...24 Table 16 Customer Meter Losses...25 Table 17 Comparison of Previous Loss Studies...28 LIST OF FIGURES IN OG&E SYSTEM LOSS STUDY Figure 1 Sales to Ultimate Customers...7 Figure 2 Losses as a Percent of Total System Load...8 Figure 3 Transmission System Line Losses...11 Figure 4 Circuit Loss Results and Exponential Equation for 4-kV Circuits...17 Figure 5 Circuit Loss Results and Exponential Equation for the 12-kV Circuits...19 Figure 6 Circuit Loss Results and Exponential Equation for the 24-kV Circuits...20 Figure 7 Circuit Loss Results and Exponential Equation for 34-kV Circuits...22 Figure 8 Historical Losses as a Percent of System Load...27 iii

5 Electric System Loss Study TABLES IN ATTACHMENT Table A-1 Table A-2 Table A-3 Table A-4 Table A-5 Table A-6 Transmission Transformer No-Load Losses Distribution Primary Transformer Losses (4 kv Class) Distribution Primary Transformer Losses (12kV Class) Distribution Primary Transformer Losses (24.9 kv Class) Distribution Primary Transformer Losses (34 kv Class) Secondary Transformer Losses iv

6 Electric System Loss Study 1 Executive Summary This report documents the results of an Electric System Loss study performed for the Oklahoma Gas & Electric (OG&E) system for the 2006 test year. OG&E, a subsidiary of OG&E Energy Group, is a regulated electric utility company that serves about 755,000 retail customers in Oklahoma and Western Arkansas and a number of wholesale customers throughout the region. OG&E has nine power plants capable of producing about 6,903 MW. The company delivers electricity across an interconnected transmission and distribution system spanning about 30,000 square miles. Electric power system losses are a consequence of doing business for a full service electric utility. The electric system is dynamic and decisions are made every day that affect losses and thus the efficiency of the system. In addition, the losses that do result from the operation of the electric system must be properly charged to the customers that are responsible for those losses. To enhance the operational decision making process and fairly allocate losses to customers, it is necessary to understand the electric losses in detail as a function of where they occur on the system 1.1 Technical Losses The technical losses were investigated and calculated for the following categories: Transmission lines, corona, transmission transformers, sub-transmission lines, distribution transformers, distribution lines, distribution secondary transformers, service drops and meters. Technical losses within the electric system are a function of both currents in the system and voltage. Load losses or copper losses are the normal terms used to describe the current-related losses. Excitation losses in transformers, meters and reactors are called no-load, iron or excitation losses and are a function of the voltage at these different components. Corona losses are also in this category. Coronal losses depend on the voltage level and the length of the transmission circuits. The corona losses are not very significant in the OG&E system. Generator step up (GSU) transformers, depending on meter location, can contribute to the load and no-load losses of the system. The results of the technical calculation of system losses by the voltage levels on the OG&E system are shown in the Table Loss Allocation The total calculated losses for all categories, including the load and no-load components and the nontechnical losses, must be consistent with the FERC Form 1 reported energy losses. When there is a difference between the reported loss and the calculated study loss, as shown in Table 1, an allocation process must be conducted. The difference in losses was allocated to the calculated losses. The resulting adjusted losses are shown in Table 2 on the next page. 1

7 Electric System Loss Study Table 1 Calculated Losses and Non-Technical Losses System Function Calculated Losses for Year 2006 Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Calculated Technical Losses Transmission System Line and Transformer (Load) 161, , ,117,832 Line Corona ,811,152 Transformer No-Load 7, , ,396,512 Distribution Primary System Primary Transformer (No-Load) 4 kv Class ,322, kv Class 6, , ,136, Class ,144, kv Class 1, , ,622,768 Primary Transformer (Load) 4 kv Class 1, , ,945, kv Class 32, , ,801, Class 1, , ,699, kv Class 3, , ,518,719 Primary Lines 4 kv Class 6, , ,857, kv Class 88, , ,584, Class 4, , ,999, kv Class 7, , ,444,218 Distribution Secondary System Secondary Transformer (No-Load) 33, , ,826,995 Secondary Transformer (Load) 31, , ,948,473 Secondary Lines & Service Drops 134, , ,043,758 Customer Meters ,723,066 Non-Technical Losses Energy Diversion Unmetered Company Use 5, , ,523,977 Total Calculated Losses 530, , ,741,469,357 FERC Form 1 Reported Losses 1,957,267,000 2

8 Electric System Loss Study Table 2 Adjusted Calculated Losses Adjusted Calculated Losses for Year 2006 System Function Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Calculated Technical Losses Transmission System Line and Transformer (Load) 161, , ,117,832 Line Corona ,811,152 Transformer No-Load 7, , ,396,512 Distribution Primary System Primary Transformer (No-Load) 4 kv Class ,273, kv Class 9, , ,381, Class ,015, kv Class 1, , ,869,691 Primary Transformer (Load) 4 kv Class 2, , ,177, kv Class 46, , ,278, Class 1, , ,918, kv Class 5, , ,815,801 Primary Lines 4 kv Class 9, , ,565, kv Class 128, , ,330, Class 5, , ,062, kv Class 10, , ,867,712 Distribution Secondary System Secondary Transformer (No-Load) 33, , ,826,995 Secondary Transformer (Load) 46, , ,268,480 Secondary Lines & Service Drops 134, , ,043,758 Customer Meters ,723,066 Non-Technical Losses Energy Diversion Unmetered Company Use 5, , ,523,977 Total Adjusted Losses 614, , ,957,267,002 FERC Form 1 Reported Losses 1,957,267,000 3

9 Electric System Loss Study 1.3 Loss Factor Development For this study, Stone & Webster Management Consultants Inc. in partnership with Siemens Power Technologies (Siemens PTI), International developed several techniques to provide both the system loss study and the service level loss factors. Using Siemens PTI software and a representative sample of circuits, both transmission and distribution systems were modeled in detail to determine the technical losses. Energy losses were calculated using the load factor / loss factor methodology based on the peak losses and 8,760 hourly load research profiles. 1.4 Results The final work products for this loss study project included the following deliverables to OG&E: Technical loss study using engineering calculations based on OG&E voltage levels and system configuration Hourly demand factors based on 8,760 hourly load research data Monthly typical energy and demand loss factors by service level Seasonal energy and demand loss factors by service level Annual energy and demand factors by service level Final report and results with supporting tables Tables 3 and 4 summarize the results of the loss study by month and by service level, respectively. The remainder of this document describes the methodology utilized to develop losses and loss factors for the Oklahoma Gas and Electric System. 4

10 Electric System Loss Study Table 3 Losses by Service Level OG&E Losses by Service Level Test Year 2006 Energy kwh Losses kwh Loss Percent 1 TOTAL SYSTEM 27,942,194,067 Load No-Load Total 1,953,471, % Service Level 1 3,722,173,097 Load 80,341,184 No-Load 8,581,978 Total 88,923, % Service Level 2 3,867,856,408 Load 106,193,001 No-Load 27,049,148 Total 133,242, % Service Level 3 2,280,896,124 Load 101,155,581 No-Load 15,951,031 Total 117,106, % Service Level 4 716,913,655 Load 35,534,225 No-Load 16,789,041 Total 52,323, % Service Level 5 17,354,354,783 Load 1,149,742,760 No-Load 412,133,198 Total 1,561,875, % 1 Loss percentage is calculated as loss / energy in this table 5

11 Electric System Loss Study Table 4 Monthly Losses and Loss Factors OG&E Monthly Loss Factors Energy (kwh) Energy Losses (kwh) Energy Loss Percent Demand (kwh) Demand Losses (kwh) Demand Losses Percent Months January 2,220,507, ,198, % 3,732, , % February 2,128,846, ,504, % 4,002, , % March 2,157,171, ,860, % 4,892, , % April 2,177,976, ,347, % 4,892, , % May 2,544,458, ,010, % 5,649, , % June 2,876,975, ,147, % 5,500, , % July 3,329,420, ,892, % 6,418, , % August 3,433,204, ,111, % 6,473, , % September 2,410,606, ,054, % 5,168, , % October 2,202,006, ,853, % 4,940, , % November 2,093,776, ,021, % 4,402, , % December 2,372,261, ,272, % 4,257, , % OG&E Seasons Summer Jun-Oct 14,252,211, ,059, % 6,473, , % Winter All Other 15,694,995, ,214, % 5,649, , % Calendar Seasons Summer Jun-Aug 9,639,599, ,151, % 6,473, , % Fall Sept-Nov 6,706,388, ,929, % 5,168, , % Winter Dec-Feb 6,721,614, ,975, % 4,257, , % Spring Mar-May 6,879,605, ,218, % 5,649, , % 6

12 Electric System Loss Study 2 Introduction The OG&E peak demand in August of 2006 was 6,473 MW with an annual energy requirement of 28,492,417,000. Sales to the ultimate customers, excluding requirements and non-requirements sales, have been growing at a rate of about 2 per cent a year, compounded annually, from 1994 to Figure 1 shows this growth. Figure 1 Sales to Ultimate Customers 30,000,000 25,000,000 20,000,000 Energy MWh 15,000,000 10,000,000 5,000, Year Electric system losses as a per cent of the energy through the system have been relatively constant over the same period. In 2006 the energy loss was about 6.9 per cent. Figure 2 shows the energy losses over the same period. 7

13 Electric System Loss Study Figure 2 Losses as a Percent of Total System Load Percent Year Total energy losses are determined by taking the difference between all the known inputs to the system and all the known outputs. Inputs and outputs at the control area boundaries and generator outputs are normally recorded in KW every hour. These values can then be determined on a year-end to year-end basis. Most customer meters are recorded each month by meter reading methods that can only record about a twentieth of the meters each day in the month. Although each customer has an annual energy recorded, it is not based on a true calendar year consumption period. This usually results in meter reading billing cycling errors. The loss factor methodology was used in this study. This is a time proven methodology that should be based on accurately recorded energy. The issue with this is that not all the energy consumption can be measured by the end of the year as some energy used is not metered. Most residential and commercial meters measure continuous energy which must be manually read, usually once a month. The billing cycling errors distort the energy used in the calendar year. When the December and January weather patterns are similar from one year to the next the billing cycle error is minimized. There is another potential difficulty in that every load must be metered and recorded. A large error is introduced when one load is not metered or when there is an error in recording the energy. Capturing all the loads becomes very important. Additionally, energy diversion (stolen energy) and unmetered substation station light and power use must be estimated. 8

14 Electric System Loss Study OG&E rates are based on the voltage level of service to the customer. There are five service levels. Service level 1 (SL-1) is large industrial and full requirement customers. These customers have their own transmission transformers and are connected directly to the transmission system. The OG&E transmission voltages are: 500-kV, 345-kV, 161-kV, 138-kV, and 69-kV. Service level 2 (SL-2) customers are also connected to the transmission system but the connecting transformer is owned by OG&E and the meter is on the low voltage side. Losses become part of the OG&E transmission system in this situation. Service level 3 (SL-3) customers are connected directly to the distribution primary lines and the customer owns the transformer. In this case the customer is responsible for the transformer losses. The distribution primary voltages classes are: 34.5-kV, 24-kV, 12-kV, 4-kV, and 2.4-kV. Service level 4 (SL-3) customers are the same as SL-3 customer except that OG&E owns the transformer and is responsible for the losses in the transformer. These customers are normally small industrial and commercial. Service level 5 (SL-5) customers are residential and commercial. They are connected to the distribution primary lines by a transformer owned by OG&E with secondary lines to a meter. Secondary service voltages are: 480-V, 277-V, 208-V, 240-V, and 120-V The methodology used to allocate electric system losses to the system voltage levels and to the voltage service classes is based on the difference between the meter readings in and out at each voltage level. Total system energy losses are reported on page 401 line 27 of the FERC Form 1. There are eight categories that can be established to define and calculate specific losses that occur on the electric system. Within these categories there may be load and no-load losses. These categories, and the presence of load and/or no-load losses, are provided in Table 5. The demand and energy losses for the OG&E system were calculated for these eight categories and were allocated to the five service levels. Table 5 Categories of Load and No-Load Losses Category Load Losses No-Load Losses Transmission Lines Yes No Corona No Yes Transmission Transformers Yes Yes Distribution Substation Transformers Yes Yes Distribution Lines Yes No Distribution Secondary Transformers Yes Yes Service Drops Yes No Meters No Yes Finally, the non-technical losses were estimated to complete the calculation process. Energy diversion and substation station power and light are the two main non-technical losses. Loss factors for each hour of the year for each of the service levels were also calculated. 9

15 Electric System Loss Study 3 Transmission System Losses The OG&E transmission system consists of lines and transformers with voltage levels between 69 KV and 500 KV. Both the high and low voltage sides of transmission transformers must be within this range. The losses of those transformers with voltage levels on the low side below this range are considered part of the distribution system. Power and energy losses within the transmission system are due to the resistive component of the transmission lines, the resistive and admittance components of the transformers, and corona losses. Transmission system losses can be grouped into three types: transmission line losses, transformer losses and corona losses. 3.1 Transmission Line Losses Power flowing through transmission lines results in demand and energy losses. These losses are a function of the resistive component of the transmission line and the square of the current. The current flows through the transmission system from generators to the five service level loads and through tie lines, to and from OG&E s neighboring utilities. There are over 100 tie lines to nine control areas in place or planned in the next few years. The transmission line loss analysis was performed using Siemens PTI s computer program, Power System Simulator for Engineering (PSSTME) Revision 29. PSSTME is an integrated program for simulating, analyzing, and optimizing power system performance that uses the most advanced and proven methods for performing power flow studies, unbalanced fault analysis, and dynamic stability simulation. Five power flow cases representing different power flow conditions of the Eastern Interconnected System, which includes the OG&E control area and all of its neighboring utilities, was provided by OG&E. The five cases were for the year 2006 and represented the summer peak, summer shoulder, winter peak, spring peak, and fall peak load conditions with representative generation and tie flows for each case. The power flow cases represent only the transmission system. The control area hourly load data for the OG&E s transmission system in 2006 was also provided. From the original five cases, twenty-one power flow cases were developed by modeling system loads in increments of about 225 MW from the minimum to the maximum system load. In developing the cases, the original cases that most closely matched the new load were used. From the original cases, the system load was scaled up or down to match the new or desired case load. The generation was also scaled accordingly. Five extra cases were also created using the five power flow cases to create an overlap among the five cases. In total, thirty-two cases were run and the OG&E transmission losses were recorded for each of the cases. The resistances of the transmission transformers and the corresponding no load admittance data of the transformers were already included in the power flow cases. Therefore, the load and no-load losses of the transmission transformers were automatically included in the transmission losses. The power flow simulations performed for the thirty-two cases studied provided the transmission demand losses for each of the corresponding system load levels. A mathematical relationship between the 10

16 Electric System Loss Study transmission system losses and the system demand was found using regression analysis. The resulting relationship was used to calculate the transmission losses corresponding to the system load for each hour of the year. The plot of the transmission loss vs. system demand and the curve for the estimated mathematical relationship are shown in Figure 3. The correlation coefficient R2 was found to be indicating a reasonable curve fit. The data points at the higher end of the demand scale show the variances in the provided power flow cases. These variances correspond to the control area boundary flow differences and the internal generation differences that swing the losses up or down from the regression curve. The curve as plotted shows that, in some instances, the near same load levels produce somewhat different losses. The differences occur as a result of transitioning from one case to another (i.e. winter peak to summer peak). The transition cases have different generation dispatches, different import and export schedules and loop flow differences. Figure 3 Transmission System Line Losses y = x R 2 = Losses (MW) Demand (MW) 3.2 Transmission Transformer Losses Transformers have two main types of losses. The first is the resistive loss (load-losses) which is a function of the transformer resistive component and the current squared. This loss depends on the loading of the transformer. The second is the no-load loss (excitation loss), which is a function of the transformer 11

17 Electric System Loss Study admittance and the operating voltage squared. All transformers on the electric system have these two types of losses. The no-load loss is constant and it is always present as long as the transformer is energized. The loss is in the form of heat energy and noise. Both the load and no-load losses were included in the power flow case, so there was no need to calculate them separately. Generation step-up (GSU) transformers are only included in the transmission category if the metering is located on the generation side of the transformer. The meter location for the OG&E generation step-up transformers are on the high side, which is the industry standard. Therefore, the losses in the GSU transformers are already taken into account in the generation plant efficiency, so they were not calculated. In this case, the GSU transformer losses, both load and no-load losses, are part of the cost associated with the net energy output from each generating unit having this metering arrangement. 3.3 Corona Losses Corona loss is an electric discharge to the air that surrounds a conductor. Under the proper weather conditions, the air surrounding the conductors of high voltage transmission lines becomes ionized and conducts electricity to a limited extent. As a result, a small part of the electric energy flowing in the transmission line leaks into the air resulting in electric loss. The amount of the corona discharge depends on the voltage level, the diameter of the conductor and the weather conditions. Other factors affect the corona discharge, such as, adverse weather conditions, elevation, conductor spacing, and the presence of a shield wire. Rain also increases corona loss substantially. Corona demand losses are calculated separately for the 500-kV, 345-kV, 161-kV, 138-kV, and 69-kV transmission lines using the Bonneville Power Administration computer program, CORONAII, Corona and Field Effects. Corona loss is negligible for voltages that are 69-kV and below in fair weather conditions. OG&E had about 4,576 miles of lines at 69-kV and above within its control area in Table 6 shows the length of the lines of the transmission system and the resulting demand and energy corona losses by voltage level. The losses are based on normal conditions for most of the hours in a year and for an average of one-half inch of rain for the 137 hours per year according to local publicly available sources. The demand is assumed at time of normal conditions. 12

18 Electric System Loss Study Table 6 Corona Losses Lines kv Length of Circuits Miles Loss No Rain kw/mile Loss with Rain kw/mile Hours of Rain Hours Demand Losses kw Energy Losses kwh 69 1, , , , ,536, ,194,386 Total 4, ,811,152 Coincident Demand Transmission System Loss Summary The transmission losses are summarized in Table 7. The calculating techniques used in the calculation of transmission losses are very straight forward and are performed with a high degree of accuracy. Therefore, there is great confidence in the accuracy of these calculations. As a consequence, during the allocation process that was performed to match the reported losses to the calculated losses, the transmission system losses were not modified. System Function Table 7 Transmission System Losses Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Line and Transformer (Load) 161, , ,117,832 Line Corona ,811,152 Transformer No-Load 7, , ,396,512 13

19 Electric System Loss Study 4 Distribution Primary Losses Demand and energy losses have been calculated for the distribution primary system. Included in this category are the load and no-load losses in the distribution primary transformers and the losses in the distribution primary lines. Customers with rates associated with service levels 3 and 4 are connected to the distribution primary system. Distribution primary transformers have low side voltages in the following voltage classes: 34.5-kV, 24-kV, 12-kV, and 4-kV. The actual low side voltage varies within a small range around the class voltages with the exception of the 2.4-kV low side voltages which were also included in the 4-kV class. Distribution primary lines operate at the same voltages mentioned above. The non-coincident peak losses were calculated for transformer load losses and primary line losses. Energy peak losses were calculated form the peak losses using the loss factor methodology. On the other side, transformer no-load losses are voltage dependent and, as a result, are relatively constant. No-load transformer losses were calculated from the nominal voltages and the transformer no-load parameters. OG&E maintains a sophisticated load research program that enables the load and loss factors to be calculated directly from the data without having to use the empirical formula methods. The load factor is calculated by taking the average of the 8,760 hourly loads in the test year. If the loads are in per unit the loss factor is calculated from the square of the per unit loads for the same 8,760 hours. The per unit (pu) load is any individual load divided by the peak load in that study period. For example, at the time of the peak, the per unit load would be 1.00 pu, the highest value in the set. 4.1 Transformer Load Losses Transformer load losses are associated with the current flowing through the transformer. The peak load losses are a function of the square of load current through the transformer at the time of the noncoincident peak. The OG&E SCADA system (System Control and Data Acquisition) provided the peak load for many of these transformers. These peak loads were used to calculate the load losses using typical transformer resistance in per unit values. The average loading for those transformers having recorded load information was also determined. This average loading was then used as the peak load for those transformers with no historical loading information. The calculation of the load transformer losses is a simple per unit calculation that uses the square of the load multiplied by the resistance, thus providing a non-coincident peak loss. Non-coincident peak loss is used with a loss factor and 8,760 hours in year to determine the annual energy loss. It was assumed that a diversity factor at this level was 5 percent. Tables A-1 through A-4 in the Appendix show the non-coincident load losses for each individual transformer. 4.2 Transformer No- Load Losses The no-load losses are associated with the winding excitation and are a function of the square of the applied voltage. The voltage was assumed to be constant for the calculation of the no-load losses. Transformer no-load losses have a relatively small variance when converted to per unit based on the Oil to Air (OA) transformer rating. Therefore, if manufacturer test values were not available, typical values were used. The OA rating is the lowest rating given to a transformer. The OA rating is the most basic cooling rating, as there are no oil pumps to circulate the oil, and cooling fans are offline so only natural convection occurs. 14

20 Electric System Loss Study The no-load losses for the distribution primary transformers are shown on Tables A-1 through A-4 in the Appendix. The demand no-loss that is calculated is the coincident peak loss. To calculate the no-load energy losses the coincident peak loss is multiplied by the 8,760 hours in the period. 4.3 Summary of Distribution Primary Transformer Losses The distribution primary transformer losses are summarized in Table 8 below for every voltage class. Table 8 System Function Distribution Primary Transformer Losses Non-Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Primary Transformer (No-Load) 4 kv Class ,322, kv Class 6, , ,136, Class ,144, kv Class 1, , ,622,768 Primary Transformer (Load) 4 kv Class 1, , ,945, kv Class 32, , ,801, Class 1, , ,699, kv Class 3, , ,518, Distribution Primary Distribution Lines The procedure used to calculate the primary distribution line losses is described below. Given the high number of primary lines in the OG&E system, it was not practical to perform detailed loss calculations for each of the primary distribution circuits. Therefore, the detailed loss calculations were performed for a representative sample of circuits. Typical circuits for each of the four voltage classes were selected by OG&E. The following number of circuits was studied: Eight 4-kV circuits, sixteen 12-kV circuits, six 24-kV circuits, and ten 34.5-kV circuits. The circuits selected were modeled using the Siemens PTI computer model PSS/E Adept. The data for these circuits were taken from previously modeled circuits that OG&E had set up on their own distribution program Cyme. The data included: Conductor length, type, phasing (A, B, C, AB, BC, AC, and ABC), loads by phase, and capacitors. Total circuit load was scaled for each circuit to match the SCADA system recorded non-coincident peak loads on that circuit. The circuit losses were calculated by the PSS/E Adept computer program. A regression analysis was performed on the losses as calculated for each distribution voltage classes. The resulting equations were used to estimate the losses for any particular circuit loading. The equations were applied to all circuits in their class to determine each circuit s non-coincident demand loss. Energy losses were calculated from the non-coincident demand using the loss factor. The coincident demand was determined using the calculated loss at the system peak hour. 15

21 Electric System Loss Study 4.5 Primary 4-kV Lines The 4-kV voltage class customers have a population of 125 circuits at 4.16-kV and 4 circuits at 2.4-kV. Eight of these circuits were used and modeled as a representative sample of the total population. Table 9 shows the resulting losses from these 8 circuits and the percentage based on the circuit peak demand. Table 9 Circuit Number Circuit Loading KVA Modeled 4-kV Circuits Circuit Losses KW Percent Losses % , , , The regression analysis was performed using linear, power, and exponential equations. The equation selected from these three choices was the exponential equation even though the calculated correlation coefficient R 2 was relatively low. The low correlation coefficient results from the wide variation in calculated losses as a function of the circuit peak load. Figure 4 shows the graph of the loss results and the exponential equations curve. 16

22 Electric System Loss Study Figure 4 Circuit Loss Results and Exponential Equation for 4-kV Circuits y = e x R 2 = Losses KW ,000 1,200 1,400 Circuit Loading KVA 4.6 Primary 12-kV Lines The 12-kV distribution primary lines are the typical voltage with 742 circuits. Sixteen of these circuits were selected to represent the total population. The selected circuits were modeled and the losses were calculated. Table 10 shows these circuits, the losses and the percent losses. The losses range from 1.00 percent to 2.44 percent. 17

23 Electric System Loss Study Table 10 Modeled 12-kV Circuits Circuit Number Circuit Loading KVA Circuit Losses KW Percent Losses % , , , , , , , , , , , , , , , , A regression analysis of the losses calculated using the computer model was performed to determine an equation that could be used to calculate the losses for the entire population of 742 circuits. Circuit loss as a function of circuit peak load in kva was used. The correlation coefficient was again low (though a better fit than for 4-kV) because of the variation in the calculated losses as a function of circuit load. Figure 5 shows the losses for the sixteen circuits and the equation that represents the 12-kV circuits. 18

24 Electric System Loss Study Figure 5 Circuit Loss Results and Exponential Equation for the 12-kV Circuits y = e x R 2 = Losses KW Circuit Loading KVA 4.7 Primary 24-kV Lines There are 53 distribution circuits at 24-kV on the OG&E system. Six of these circuits were selected for detailed study. Losses were calculated as a function of the circuit peak load. The results of these six circuits are shown in Table 11. Note that circuits and have very similar loads and losses. This similarity results in two data points on top of each other on the graph making it appear to have only five entries. 19

25 Electric System Loss Study Table 11 Circuit Number Modeled 24-kV Circuits Circuit Loading KVA Circuit Losses KW Percent Losses % , , , , , , A regression analysis of the losses calculated using the computer model was performed to determine an equation that could be used to calculate the losses from the 53 circuits. Circuit loss as a function of circuit peak load in kva was used. This correlation coefficient was also affected by the variation in the calculated losses as a function of circuit load. Figure 6 shows the losses for the sixteen circuits and the equation that represents the 24-kV circuits. Figure 6 Circuit Loss Results and Exponential Equation for the 24-kV Circuits Losses KW y = 6.924e x R 2 = Circuit Loading KVA 20

26 Electric System Loss Study 4.8 Primary 34.5-kV Lines The 34.5-kV distribution circuits have the heaviest loads. Ten of these circuits were selected to be modeled to represent the total population of 57 circuits. Table 12 shows the modeled circuits. Table 12 Modeled 34-kV Circuit Loads and Losses Circuit Number Circuit Loading KVA Circuit Losses KW Percent Losses % , , , , , , , , , , The exponential equation was selected to represent the 34.5-kV distribution circuits. The variation of the losses as a function of load was the reason why the correlation coefficient was relatively low. Figure 7 shows the losses for the ten circuits and the equation that represents the 34-kV circuits. 21

27 Electric System Loss Study Figure 7 Circuit Loss Results and Exponential Equation for 34-kV Circuits y = e x R 2 = Losses KW Circuit Loading KVA 4.9 Summary of Primary Distribution Line Losses Table 13 summarizes the losses in the primary distribution lines. Table 13 System Function Losses in Primary Distribution Lines Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Primary Lines 4 kv Class 6, , ,857, kv Class 88, , ,584, Class 4, , ,999, kv Class 7, , ,444,218 22

28 Electric System Loss Study 5 Distribution Secondary System Distribution secondary transformers, distribution secondary lines, distribution service drops and customer meters comprise the distribution secondary system. Distribution secondary transformers have a load and no-load loss component. The meter losses are considered to be caused by excitation losses and, therefore, are quantified as no-load losses. SL-5 customers are connected to the distribution secondary system. This service class has the most customers and their demand and energy contribution to the system is the most significant. 5.1 Distribution Secondary Transformers Distribution secondary transformers on the OG&E system range in size from 1 kva to 5,000 kva. In 2006 OG&E reported 176,530 installed units on the system with a total capacity of 10,904,204 kva. The average size of secondary transformers was 71 kva in 2006 and the most frequently installed size was the 25 kva unit for the overhead system and the 50 kva unit for the underground system. As with all transformers, there are load loss and no-load loss components. No-load losses were developed using typical loss characteristics for each size of transformer. These typical no-load per unit values are shown in Table A-6 in the Appendix. The no-load demand was calculated by using the typical no-load per unit value for each transformer size and multiplying it by the number of transformers in that size category. The energy no-load losses were found by multiplying the demand no-load losses by 8,760 hours for the year. The coincident demand load loss is a function of the current squared (current is proportional to load) at time of system peak, but this is not necessarily the maximum demand on the transformer. Based on the peak demand from the load research information from service levels SL3, SL4, and SL5, it was found that the average distribution secondary transformer is loaded to 32 percent. This is the loading from which the demand must be calculated. This is an average loading and because the calculation of loss is a square function, it is not correct to simply take the 32 percent loading to calculate the losses. The proper method is to calculate each transformer s demand using the loading of each transformer but this individual loading is not known. An approximation method is to create a frequency distribution that will average to 32 percent loading for each transformer size, but will capture the various loadings above and below the average. This was accomplished by using the average load on 60 percent of the transformers, a loading of 120 percent of average on 20 percent of the transformers and a load of 80 percent on 20 percent of the transformers. The energy load losses were calculated from the non-coincident demand load losses by using a loss factor of and 8,760 hours. The load factor was increased to 0.3 during the allocation process to balance against total energy losses. A coincidence factor of 85 percent was used to calculate the coincident peak loss. The secondary transformers load and no-load losses are summarized in Table

29 Electric System Loss Study Table 14 System Function Secondary Transformer Losses Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Secondary Transformer (No-Load) 33, , ,826,995 Secondary Transformer (Load) 31, , ,948, Distribution Secondary Lines and Service Drops Losses that occur on the secondary lines and service drops are the most difficult to calculate because of the lack of data and the sheer number of secondary lines and service drops. Information as to the configuration, conductor size, and length of each of the services to customers are not kept on a drawing because a large number of drawings would be required and because a distribution standard is used. Each customer s electric service installation is slightly different than a standard. Based on the OG&E standards, 15 different secondary and service drop configurations were used with 5 different loads each. The customer load was assumed to be un-balanced for the 240/120 volt configurations with 50 percent of the load on one leg, 40 percent on the other leg and 10 percent on the neutral. The non-coincident demand losses were calculated based on these 75 different loads and configurations (15 service drops, 5 loadings, with unbalance configurations). It was assumed that the coincident factor was 85 percent. Energy losses were then determined using a loss factor of and 8,760 hours. The loss factor was increased to 0.3 during the allocation process that was performed to match the calculated values to the recorded energy loss. The losses in the secondary lines and service drops are summarized in Table 15. Table 15 System Function Secondary Lines and Service Drops Losses Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Secondary Lines & Service Drops 134, , ,043, Customer Meters Losses can be attributed to each meter on the electric system. The standard residential meter takes just under one watt of energy for each hour of operation. The demand loss for electric meters is calculated by taking the number of meters times the hourly losses. The coincident and non-coincident demands are the same. The energy losses are calculated by multiplying the demand loss by 8,760 hours in a year. The resulting electric meter energy losses are shown in Table

30 Electric System Loss Study System Function Table 16 Customer Meter Losses Non- Coincident Peak Losses KW Coincident Peak Losses KW Energy Losses KWh Customer Meters ,723, Non-Technical Losses There are two main components that make up energy that is unaccounted. These two components are energy diversion and Company unmetered use. Energy diversion is the term used to describe energy that is stolen by customers tampering with the meter or bypassing the meter. Energy diversion in the United States is very small. In discussions with OG&E, it was determined that energy diversion was not a problem in their service territory. The only company unmetered use that is believed not to be in the calculated losses is the substation station, light and power. An estimate of the non-coincident demand for this use is based on a 25 kva transformer at the 362 substation loaded to 60 percent of capacity. This yields a non-coincident peak load of 5,430 kw. The coincident peak is estimated at 90 percent of the non-coincident value and is 4,887.0 kw. Energy is calculated using a 45 percent utilization factor yielding 21,523,977 kwh. 25

31 Electric System Loss Study 6 Hourly Load Allocation Procedure Technical losses were calculated using OG&E data for eight categories including, transmission lines, transmission corona, transmission transformers, distribution substation transformers, distribution lines, distribution secondary transformers, service drops, and meters. Summing the energy on these eight independently calculated systems should approximate the total energy loss determined by taking the difference between the inputs to the system and the sales. The calculating methods use statistical approaches for the calculation of the losses of these eight systems. This usually results in differences between the recorded annual energy losses and the annual calculated values. Therefore, the loss difference needs to be allocated back to the calculated values so that the sum of the eight categories is equal to the recorded difference. After the sum of the annual losses has been allocated to match the recorded annual losses, it is necessary to determine the losses at each hour for each service level. The loss factor at each service level is a function of the entire load that passes through the service level or system element such as the transmission system. This is accomplished by using the load research service level 8,760 load data. Losses at the transmission level are the sum of all five service levels. The combination of these five service level load shapes is determined by adding each specified hour. The sum in any one hour is the load that results in losses on the transmission system. The loss factor is the per unit square of this load data set. If the demand loss, which is a function of the square of the current, is multiplied by each hour, the annual energy loss is determined. No load losses that are constant in each hour are added separately. SL-4 losses are determined using the data sets of SL-2, SL-3, SL-4, and SL-5. This is the load that goes through the distribution transformers. The same process as described above is used to determine the hour by hour losses. Likewise the service level 3, the primary distribution lines follows the same procedure as is that used for service level 4, distribution secondary transformers and service level 5, distribution secondary lines and service drops. 26

32 Electric System Loss Study 7 Conclusion The loss study presented in this document relies on standard industry approaches and the best available data produced by OG&E for use in the analyses. The resulting losses are in line with previous studies for the OG&E system and reflect changes that occur over time: differing service territory characteristics, changes in standard equipment in use by the utility, degradation of equipment not yet ready for replacement and weather conditions. 7.1 Historical Losses A comparison of historical system losses (using percentages) is provided in Figure 8. Figure 8 Historical Losses as a Percent of System Load Percent Year 7.2 Loss Study Comparisons There are two previous studies that calculated losses on the OG&E system, one with a test year of 1992 and the other with a test year of The present study has a test year of The 1992 study used a different methodology to determine losses. The 2001 and 2006 studies used similar methods for the most 27

33 Electric System Loss Study part, but the data was, of course, five years newer and had more advanced collecting and recording techniques. Table 15 shows the comparison of the latest study with previous loss studies. Table 17 Energy Loss Percent Comparison of Previous Loss Studies OG&E System Losses Comparison of Loss Studies 1992 Study 2001 Study 2006 Study Demand Energy Demand Energy Loss Loss Loss Loss Percent Percent 2 Percent Percent Demand Loss Percent Service Level % 1.10% 2.48% 2.47% 2.39% 2.73% Service Level % 2.54% 3.14% 3.30% 3.44% 6.23% Service Level % 3.88% 4.67% 5.81% 5.13% 10.14% Service Level % 5.79% 6.95% 7.25% 7.30% 10.29% Service Level % 7.52% 8.41% 9.29% 9.00% 11.11% The difference in the demand losses has been progressively higher from the first study to the last study as load is attached to the electric system farther away for the generators. This is because the hour by hour method of calculating losses can more accurately determine losses, both peak and energy. 7.3 Methodology For this study, total energy losses are determined by taking the difference between all the known inputs to the system and all the known outputs. Inputs and outputs at the control area boundaries and generator outputs are normally recorded in KW every hour. These values can then be determined on a year-end to year-end basis. Most customer meters are recorded each month by meter reading methods that can only record about a twentieth of the meters each day in the month. Although each customer has an annual energy recorded, it is not based on a true calendar year consumption period. This usually results in meter reading billing cycling errors. The loss factor methodology was used in this study. This is a time proven methodology that should be based on accurately recorded energy. The issue with this is that not all the energy consumption can be measured by the end of the year as some energy used is not metered. Most residential and commercial meters measure continuous energy which must be manually read, usually once a month. The billing 2 Loss factor in this table is calculated as Loss / Energy 28

Residential Load Profiles

Residential Load Profiles Residential Load Profiles TABLE OF CONTENTS PAGE 1 BACKGROUND... 1 2 DATA COLLECTION AND ASSUMPTIONS... 1 3 ANALYSIS AND RESULTS... 2 3.1 Load Profiles... 2 3.2 Calculation of Monthly Electricity Bills...

More information

Methodology of Cost Allocation

Methodology of Cost Allocation Methodology of Cost Allocation Robin Kliethermes May 17, 2013 1 Purpose of Cost Allocation Determine whether each class of customers is providing the utility with a reasonable level of revenue necessary

More information

Cost Reflective Tariffs

Cost Reflective Tariffs Cost Reflective Tariffs for Large Government,Commercial and Industrial Customers Customer Guide Introduction On September 2016, the Council of Ministers had approved the introduction Cost of Reflective

More information

NORTHEAST NEBRASKA PUBLIC POWER DISTRICT RATE SCHEDULE LP-2 Large Power Service. Effective: For bills rendered on and after January 1, 2014.

NORTHEAST NEBRASKA PUBLIC POWER DISTRICT RATE SCHEDULE LP-2 Large Power Service. Effective: For bills rendered on and after January 1, 2014. NORTHEAST NEBRASKA PUBLIC POWER DISTRICT RATE SCHEDULE LP-2 Large Power Service Effective: For bills rendered on and after January 1, 2014. SECTION 1. AVAILABILITY AND APPLICABILITY 1.1 This Rate Schedule

More information

NORTHEAST NEBRASKA PUBLIC POWER DISTRICT RATE SCHEDULE LP-2 Large Power Service. Effective: For bills rendered on and after February 1, 2019.

NORTHEAST NEBRASKA PUBLIC POWER DISTRICT RATE SCHEDULE LP-2 Large Power Service. Effective: For bills rendered on and after February 1, 2019. NORTHEAST NEBRASKA PUBLIC POWER DISTRICT RATE SCHEDULE LP-2 Large Power Service Effective: For bills rendered on and after February 1, 2019. SEDC:60/7/8/9 SECTION 1. AVAILABILITY AND APPLICABILITY 1.1

More information

Net Metering & Compensation Seminar

Net Metering & Compensation Seminar Net Metering & Compensation Seminar November 2, 2017 Eversource Energy Hadley, MA Changes Are Here Market Net Metering Credit was introduced: 60% Market equal to 60% of distribution, transition, transmission

More information

Effect of DG Installation on Customer Load Shapes

Effect of DG Installation on Customer Load Shapes Effect of DG Installation on Customer Load Shapes P R E S E N T E D T O Westar Energy P R E S E N T E D B Y The Brattle Group J u n e 2 3, 2017 Copyright 2017 The Brattle Group, Inc. Characteristics of

More information

September 2016 Water Production & Consumption Data

September 2016 Water Production & Consumption Data September 2016 Water Production & Consumption Data September 2016 monthly water production (288.48 AF) was lowest in at least 17 years. Monthly water production has increased slightly each month since

More information

Presented by Eric Englert Puget Sound Energy September 11, 2002

Presented by Eric Englert Puget Sound Energy September 11, 2002 Results from PSE s First Year of Time of Use Program Presented by Eric Englert Puget Sound Energy September 11, 2002 Puget Sound Energy Overview 973,489 Total Electric Customers 908,949 are AMR Capable

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD May 1, 2017 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY. Availability

ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY. Availability ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY GENERAL POWER RATE--SCHEDULE GSB Availability This rate shall apply to the firm electric power requirements where a

More information

Feasibility Study for the Q MW Solar Project

Feasibility Study for the Q MW Solar Project Feasibility Study for the Q171 74.5 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC

More information

Massachusetts Electric Company and Nantucket Electric Company, Docket No. D.T.E

Massachusetts Electric Company and Nantucket Electric Company, Docket No. D.T.E Amy G. Rabinowitz Counsel April 3, 2003 By Hand Mary L. Cottrell, Secretary Department of Telecommunications and Energy One South Station, 2 nd Floor Boston, MA 02110 Re: Massachusetts Electric Company

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD June 1, 2018 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

ELECTRIC SERVICE RATE SCHEDULES. Effective November 1, 2017

ELECTRIC SERVICE RATE SCHEDULES. Effective November 1, 2017 ELECTRIC SERVICE RATE SCHEDULES Effective November 1, 2017 SCHEDULE 100 RESIDENTIAL SERVICE Residential Customers for all domestic uses. CHARACTER OF SERVICE: Alternating current, sixty-hertz 120/240 volts

More information

DRIVER SPEED COMPLIANCE WITHIN SCHOOL ZONES AND EFFECTS OF 40 PAINTED SPEED LIMIT ON DRIVER SPEED BEHAVIOURS Tony Radalj Main Roads Western Australia

DRIVER SPEED COMPLIANCE WITHIN SCHOOL ZONES AND EFFECTS OF 40 PAINTED SPEED LIMIT ON DRIVER SPEED BEHAVIOURS Tony Radalj Main Roads Western Australia DRIVER SPEED COMPLIANCE WITHIN SCHOOL ZONES AND EFFECTS OF 4 PAINTED SPEED LIMIT ON DRIVER SPEED BEHAVIOURS Tony Radalj Main Roads Western Australia ABSTRACT Two speed surveys were conducted on nineteen

More information

Contact person: Pablo Taboada Mobile:

Contact person: Pablo Taboada   Mobile: Contact person: Pablo Taboada e-mail: ptaboada@aenor.es Mobile: 34 609015450 Génova 6 28004 Madrid. Spain Phone: 34 91 4326004 Fax: 34 91 3190581 CDM Executive Board RESPONSE TO REQUEST FOR REVIEW Request

More information

Large General Service Time-of-Use Storage Program

Large General Service Time-of-Use Storage Program Large General Service Time-of-Use Storage Program AVAILABILITY Available throughout the Company s entire electric service area where the facilities of the Company are of adequate capacity and are adjacent

More information

Introduction to Charging: Which Parties Pay Which Charges?

Introduction to Charging: Which Parties Pay Which Charges? Introduction to Charging: Which Parties Pay Which Charges? Information I National Grid Last Updated December 2015 Connection Charging - The cost of sole use assets required to connect to the transmission

More information

THE PUBLIC SERVICE COMMISSION OF WYOMING

THE PUBLIC SERVICE COMMISSION OF WYOMING NAME: Powder River Energy Corporation WY PSC Tariff No. 7 ADDRESS:, Sundance, WY 82729 THE PUBLIC SERVICE COMMISSION OF WYOMING TARIFF RATE RIDER 5th Revised Sheet No. 1 Cancels 4th Revised Sheet No. 1

More information

Rate Schedules. Effective 1/1/2019

Rate Schedules. Effective 1/1/2019 Rate Schedules 2019 Effective 1/1/2019 SUMMARY OF RATE SCHEDULES REVISIONS FOR RATES EFFECTIVE JANUARY 1, 2019 (1) Rate component changes for Residential and Heating Service rate schedules. (2) General

More information

11. Electrical energy tariff rating

11. Electrical energy tariff rating 799 11. Electrical energy tariff rating 800 11. ELECTRICAL ENERGY TARIFF RATING There is no universal system for billing electrical energy. Each country generally adopts its own method, taking into account

More information

Group 3: Pricing from 1 April 2018 and load management

Group 3: Pricing from 1 April 2018 and load management Group 3: Pricing from 1 April 2018 and load management This document is intended to provide background to Network Tasman s Group 3 pricing, in particular the Regional Coincident Peak Demand (RCPD) price,

More information

Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any

Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any Draft Version 1 Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation,

More information

Meter Insights for Downtown Store

Meter Insights for Downtown Store Meter Insights for Downtown Store Commodity: Analysis Period: Prepared for: Report Date: Electricity 1 December 2013-31 December 2014 Arlington Mills 12 February 2015 Electricity use over the analysis

More information

Demand and Time of Use Rates. Marty Blake The Prime Group LLC

Demand and Time of Use Rates. Marty Blake The Prime Group LLC Demand and Time of Use Rates Marty Blake The Prime Group LLC Factors Affecting Electric Rates Generation plant cost increases Fuel price increases and volatility Carbon and environmental regulations Cost

More information

2018 Load & Capacity Data Report

2018 Load & Capacity Data Report Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation, accuracy, completeness

More information

Merger of the generator interconnection processes of Valley Electric and the ISO;

Merger of the generator interconnection processes of Valley Electric and the ISO; California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson Vice President, Policy & Client Services Date: August 18, 2011 Re: Decision on Valley Electric

More information

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan XXXXX Kokish River Hydroelectric Project Interconnection Facilities Study and Project Plan March 16, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All

More information

NEW HAMPSHIRE GAS CORPORATION WINTER PERIOD ORIGINAL FILING CONTENTS 3. CONVERSION OF GAS COSTS - GALLONS TO THERMS SCHEDULE A

NEW HAMPSHIRE GAS CORPORATION WINTER PERIOD ORIGINAL FILING CONTENTS 3. CONVERSION OF GAS COSTS - GALLONS TO THERMS SCHEDULE A NEW HAMPSHIRE GAS CORPORATION COST OF GAS RATE FILING - DG 13- WINTER PERIOD 2013-2014 ORIGINAL FILING CONTENTS 1. TARIFF PAGE - COST OF GAS RATE 2. MARKED TARIFF PAGE - COST OF GAS RATE 3. CONVERSION

More information

FOR IMMEDIATE RELEASE

FOR IMMEDIATE RELEASE Article No. 7433 Available on www.roymorgan.com Roy Morgan Unemployment Profile Friday, 12 January 2018 2.6m Australians unemployed or under-employed in December The latest data for the Roy Morgan employment

More information

FLORENCE ELECTRICITY DEPARTMENT. GENERAL POWER RATE--SCHEDULE GSC (October 2015) Availability

FLORENCE ELECTRICITY DEPARTMENT. GENERAL POWER RATE--SCHEDULE GSC (October 2015) Availability FLORENCE ELECTRICITY DEPARTMENT GENERAL POWER RATE--SCHEDULE GSC () Availability This rate shall apply to the firm electric power requirements where a customer s currently effective onpeak or offpeak contract

More information

PUBLIC UTILITIES COMMISSION

PUBLIC UTILITIES COMMISSION The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location. PUBLIC UTILITIES COMMISSION FINAL DECISION THRESHOLD

More information

August 15, Please contact the undersigned directly with any questions or concerns regarding the foregoing.

August 15, Please contact the undersigned directly with any questions or concerns regarding the foregoing. California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 August 15, 2017 Re: California

More information

Total Production by Month (Acre Feet)

Total Production by Month (Acre Feet) Production by Month (acre-feet) 2008 2009 2010 2011 2012 2013 2014 2015 2016 January 25 339.10 228.90 249.50 297.99 243.06 327.14 247.66 212.37 February 234.00 218.80 212.10 241.52 245.82 279.08 234.16

More information

Decision on Merced Irrigation District Transition Agreement

Decision on Merced Irrigation District Transition Agreement California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson, Vice President Policy & Client Services Date: March 13, 2013 Re: Decision on Merced Irrigation

More information

Abstract. Background and Study Description

Abstract. Background and Study Description OG&E Smart Study TOGETHER: Technology-Enabled Dynamic Pricing Impact Evaluation Craig Williamson, Global Energy Partners, an EnerNOC Company, Denver, CO Katie Chiccarelli, OG&E, Oklahoma City, OK Abstract

More information

FLORENCE ELECTRICITY DEPARTMENT. MANUFACTURING SERVICE RATE--SCHEDULE TDMSA (October 2015) Availability

FLORENCE ELECTRICITY DEPARTMENT. MANUFACTURING SERVICE RATE--SCHEDULE TDMSA (October 2015) Availability FLORENCE ELECTRICITY DEPARTMENT MANUFACTURING SERVICE RATE--SCHEDULE TDMSA () Availability This rate shall apply to the firm electric power requirements where (a) a customer s currently effective onpeak

More information

M A N I T O B A ) Order No. 42/14 ) THE PUBLIC UTILITIES BOARD ACT ) April 23, 2014

M A N I T O B A ) Order No. 42/14 ) THE PUBLIC UTILITIES BOARD ACT ) April 23, 2014 M A N I T O B A ) ) THE PUBLIC UTILITIES BOARD ACT ) BEFORE: Régis Gosselin, B ès Arts, M.B.A., C.G.A., Chair Larry Soldier, Member Marilyn Kapitany, B.Sc. (Hons.), M.Sc., Member Neil Duboff, B.A. (Hons.),

More information

UNITIL ENERGY SYSTEMS. INC. CALCULATION OF THE EXTERNAL DELIVERY CHARGE

UNITIL ENERGY SYSTEMS. INC. CALCULATION OF THE EXTERNAL DELIVERY CHARGE Schedule LSM-DJD-1 Page 1 of 2 UNITIL ENERGY SYSTEMS. INC. CALCULATION OF THE EXTERNAL DELIVERY CHARGE Calculation Calculation of the Calculation of the of the EDC EDC/ Only EDC/Non- 1. (Over)/under Recovery

More information

increase of over four per cent compared to the average of $409,058 reported in January 2010.

increase of over four per cent compared to the average of $409,058 reported in January 2010. SINGLE FAMILY RESIDENTIAL BREAKDOWN uary 211 26.8 % 1.7 % 7.%.4%.1 % Good Start to 211 TORONTO - February 4, 211 Greater Toronto REALTORS reported 4,337 transactions through the TorontoMLS system in uary

More information

ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY. Availability

ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY. Availability ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY MANUFACTURING SERVICE RATE--SCHEDULE MSD Availability This rate shall apply to the firm electric power requirements

More information

Economics of Integrating Renewables DAN HARMS MANAGER OF RATE, TECHNOLOGY & ENERGY POLICY SEPTEMBER 2017

Economics of Integrating Renewables DAN HARMS MANAGER OF RATE, TECHNOLOGY & ENERGY POLICY SEPTEMBER 2017 Economics of Integrating Renewables DAN HARMS MANAGER OF RATE, TECHNOLOGY & ENERGY POLICY SEPTEMBER 2017 Presentation Outline Understanding LPEA s expenses and what drives them Economics of net metering

More information

JBS Energy, Inc. 311 D Street West Sacramento California, USA tel Prepared by William B. Marcus Greg Ruszovan

JBS Energy, Inc. 311 D Street West Sacramento California, USA tel Prepared by William B. Marcus Greg Ruszovan Know Your Customers : A Review of Load Research Data and Economic, Demographic, and Appliance Saturation Characteristics of California Utility Residential Customers Prepared by William B. Marcus Greg Ruszovan

More information

FOR IMMEDIATE RELEASE

FOR IMMEDIATE RELEASE Article No. 7761 Available on www.roymorgan.com Roy Morgan Unemployment Profile Monday, 8 October 2018 Unemployment down to 9.4% in September off two-year high Australian employment has grown solidly over

More information

FOR IMMEDIATE RELEASE

FOR IMMEDIATE RELEASE Article No. 5842 Available on www.roymorgan.com Roy Morgan Unemployment Profile Thursday, 2 October 2014 Unemployment climbs to 9.9% in September as full-time work lowest since October 2011; 2.2 million

More information

February 10, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426

February 10, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 California Independent System Operator Corporation February 10, 2016 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California

More information

Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1

Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1 Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide Version 1.1 October 21, 2016 1 Table of Contents: A. Application Processing Pages 3-4 B. Operational Modes Associated

More information

EC Forum on Model Approaches to Distribution Pricing. June 2009

EC Forum on Model Approaches to Distribution Pricing. June 2009 EC Forum on Model Approaches to Distribution Pricing June 2009 Session Explain Aurora UoS Pricing and fit with the Retail Model Approach Discuss how we transitioned a Demand tariff structure to Aurora

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

Manitoba Hydro Customer Consultation. Industrial Rates Workshop

Manitoba Hydro Customer Consultation. Industrial Rates Workshop Manitoba Hydro Customer Consultation Industrial Rates Workshop Industrial Rates Workshop Engage g Customers in Rate Development Increase understanding of rate-setting process Solicit feedback and input

More information

Flexible Capacity Needs and Availability Assessment Hours Technical Study for 2020

Flexible Capacity Needs and Availability Assessment Hours Technical Study for 2020 Flexible Capacity Needs and Availability Assessment Hours Technical Study for 2020 Clyde Loutan Principal, Renewable Energy Integration Hong Zhou Market Development Analyst, Lead Amber Motley Manager,

More information

NPCC Natural Gas Disruption Risk Assessment Background. Summer 2017

NPCC Natural Gas Disruption Risk Assessment Background. Summer 2017 Background Reliance on natural gas to produce electricity in Northeast Power Coordinating Council (NPCC) Region has been increasing since 2000. The disruption of natural gas pipeline transportation capability

More information

Thank you for your time and attention to this matter. Please feel free to contact me if you have any questions regarding the filing.

Thank you for your time and attention to this matter. Please feel free to contact me if you have any questions regarding the filing. Mary L. Cottrell, Secretary March 27, 2009 Page 1 Stacey M. Donnelly Counsel September 23, 2009 Mark D. Marini, Secretary Department of Public Utilities One South Station Boston, MA 02110 Re: D.P.U. 09-03

More information

FUEL ADJUSTMENT CLAUSE

FUEL ADJUSTMENT CLAUSE Page 26.1 ENTERGY NEW ORLEANS, INC. ELECTRIC SERVICE Supersedes: FAC effective 6/1/09 RIDER SCHEDULE FAC-5 Schedule Consists of: One Sheet Plus Schedule A and Attachments A and B FUEL ADJUSTMENT CLAUSE

More information

Reforming the TAC and Retail Transmission Rates. Robert Levin California Public Utilities Commission Energy Division August 29, 2017

Reforming the TAC and Retail Transmission Rates. Robert Levin California Public Utilities Commission Energy Division August 29, 2017 Reforming the TAC and Retail Transmission Rates. Robert Levin California Public Utilities Commission Energy Division August 29, 2017 1 CPUC Staff Rate Design Proposals Restructure the High-Voltage TAC

More information

Douglas Electric Cooperative Roseburg, Oregon

Douglas Electric Cooperative Roseburg, Oregon Douglas Electric Cooperative Roseburg, Oregon Policy Bulletin 30-8 Net Metering Services Policy: Net metering service is available, on an equal basis, to Customers who own and operate a net metering generating

More information

ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY. LARGE MANUFACTURING SERVICE RATE SCHEDULES (November 2018)

ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY. LARGE MANUFACTURING SERVICE RATE SCHEDULES (November 2018) ELECTRIC POWER BOARD OF THE METROPOLITAN GOVERNMENT OF NASHVILLE AND DAVIDSON COUNTY LARGE MANUFACTURING SERVICE RATE SCHEDULES () Availability These rates shall apply to the firm electric power requirements

More information

Net Consumption (GWh)

Net Consumption (GWh) GEORGIAN ENERGY MARKET Over the last 20 years Georgia s power market has evolved from a vertically integrated single buyer utility, to a competitive regional power market model. The Georgian wholesale

More information

EXHIBIT A-2 Amending Chapter TMC (all additions and amendments effective April 1, 2018) Chapter ELECTRIC ENERGY REGULATIONS AND RATES 1

EXHIBIT A-2 Amending Chapter TMC (all additions and amendments effective April 1, 2018) Chapter ELECTRIC ENERGY REGULATIONS AND RATES 1 EXHIBIT A-2 Amending Chapter 12.06 TMC (all additions and amendments effective April 1, 2018) Chapter 12.06 ELECTRIC ENERGY REGULATIONS AND RATES 1 Amended and Added Sections: 12.06.140 Tampering and injury

More information

SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-27 CUSTOMER GENERATION PRICE PLAN FOR RESIDENTIAL SERVICE

SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-27 CUSTOMER GENERATION PRICE PLAN FOR RESIDENTIAL SERVICE SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-27 CUSTOMER GENERATION PRICE PLAN FOR RESIDENTIAL SERVICE Effective: April 2015 Billing Cycle AVAILABILITY: The E-27 Price Plan is subject

More information

ENERGY MANAGEMENT 4/22/2014. What are your approximate yearly energy costs? (Electricity, natural gas, etc.)

ENERGY MANAGEMENT 4/22/2014. What are your approximate yearly energy costs? (Electricity, natural gas, etc.) MICHIGAN CHAMBER OF COMMERCE ENERGY MANAGEMENT Webinar Electricity - Natural Gas April 23, 2014 10:00 A.M. - 11:00 A.M. EDT Presented by John M. Studebaker, Ph.D. www.studebakerenergy.net JStudebaker 4/23/14

More information

Delaware Electric Cooperative

Delaware Electric Cooperative Delaware Electric Cooperative Approved Rates Rate Leaf No. Residential 48 Residential Load Management 51 Residential Space Heating 54 General Service 56 Irrigation 58 Irrigation Demand Off-Peak 61 Irrigation-Demand

More information

P. SUMMARY: The Southeastern Power Administration (SEPA) establishes Rate Schedules JW-

P. SUMMARY: The Southeastern Power Administration (SEPA) establishes Rate Schedules JW- This document is scheduled to be published in the Federal Register on 08/29/2016 and available online at http://federalregister.gov/a/2016-20620, and on FDsys.gov 6450-01-P DEPARTMENT OF ENERGY Southeastern

More information

PURCHASED GAS ADJUSTMENT RIDER SCHEDULE

PURCHASED GAS ADJUSTMENT RIDER SCHEDULE Page 22 GAS SERVICE Effective: October 27, 2005 Filed: August 25, 2005 Supersedes: PGA-2 filed 8/25/05 RIDER SCHEDULE PGA-3 Schedule Consists of: Three Sheets Plus PURCHASED GAS ADJUSTMENT RIDER SCHEDULE

More information

Oregon DOT Slow-Speed Weigh-in-Motion (SWIM) Project: Analysis of Initial Weight Data

Oregon DOT Slow-Speed Weigh-in-Motion (SWIM) Project: Analysis of Initial Weight Data Portland State University PDXScholar Center for Urban Studies Publications and Reports Center for Urban Studies 7-1997 Oregon DOT Slow-Speed Weigh-in-Motion (SWIM) Project: Analysis of Initial Weight Data

More information

ESTIMATING THE LIVES SAVED BY SAFETY BELTS AND AIR BAGS

ESTIMATING THE LIVES SAVED BY SAFETY BELTS AND AIR BAGS ESTIMATING THE LIVES SAVED BY SAFETY BELTS AND AIR BAGS Donna Glassbrenner National Center for Statistics and Analysis National Highway Traffic Safety Administration Washington DC 20590 Paper No. 500 ABSTRACT

More information

U.S. Classes 3-8 Used Trucks

U.S. Classes 3-8 Used Trucks Americas Commercial Transportation Research Co., LLC www.actresearch.net COMMERCIAL VEHICLES State of the Industry U.S. Classes 3-8 Used Trucks May 215 Data Published June 24, 215 Contributor to Blue Chip

More information

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li

More information

SPRINGFIELD UTILITY BOARD ELECTRIC RATE SCHEDULES

SPRINGFIELD UTILITY BOARD ELECTRIC RATE SCHEDULES AVAILABLE RESIDENTIAL SCHEDULE R-1 Available to residential services in all territory served by the Springfield Utility Board (SUB) except where special rates are in effect. CHARACTER OF SERVICE 60 Hertz

More information

Consumer Guidelines for Electric Power Generator Installation and Interconnection

Consumer Guidelines for Electric Power Generator Installation and Interconnection Consumer Guidelines for Electric Power Generator Installation and Interconnection Habersham EMC seeks to provide its members and patrons with the best electric service possible, and at the lowest cost

More information

Analysis of Impact of Mass Implementation of DER. Richard Fowler Adam Toth, PE Jeff Mueller, PE

Analysis of Impact of Mass Implementation of DER. Richard Fowler Adam Toth, PE Jeff Mueller, PE Analysis of Impact of Mass Implementation of DER Richard Fowler Adam Toth, PE Jeff Mueller, PE Topics of Discussion Engineering Considerations Results of Study of High Penetration of Solar DG on Various

More information

MARKET RATES UPDATE Paula Gold-Williams Cory Kuchinsky

MARKET RATES UPDATE Paula Gold-Williams Cory Kuchinsky MARKET RATES UPDATE I N T R O D U C T I O N BY: Paula Gold-Williams President & Chief Executive Officer (CEO) P R E S E N T E D BY: Cory Kuchinsky Interim Vice President, Financial Services September 24,

More information

May ATR Monthly Report

May ATR Monthly Report May ATR Monthly Report Minnesota Department of Transportation Office of Transportation Data and Analysis May 2011 Introduction The purpose of this report is to examine monthly traffic trends on Minnesota

More information

Department of Market Quality and Renewable Integration November 2016

Department of Market Quality and Renewable Integration November 2016 Energy Imbalance Market March 23 June 3, 216 Available Balancing Capacity Report November 1, 216 California ISO Department of Market Quality and Renewable Integration California ISO i TABLE OF CONTENTS

More information

National Grid. Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES. 2 nd Amended Compliance Filing

National Grid. Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES. 2 nd Amended Compliance Filing National Grid Narragansett Electric Company INVESTIGATION AS TO THE PROPRIETY OF COMPLIANCE TARIFF CHANGES 2 nd Amended Compliance Filing Attachment 1: Book 2 of 2 April 2010 Submitted to: Rhode Island

More information

WIM #37 was operational for the entire month of September Volume was computed using all monthly data.

WIM #37 was operational for the entire month of September Volume was computed using all monthly data. SEPTEMBER 2016 WIM Site Location WIM #37 is located on I-94 near Otsego in Wright county. The WIM is located only on the westbound (WB) side of I-94, meaning that all data mentioned in this report pertains

More information

Demand Charges to Deal With Net Energy Metering: Key Considerations

Demand Charges to Deal With Net Energy Metering: Key Considerations Demand Charges to Deal With Net Energy Metering: Key Considerations Amparo Nieto Vice President Presented at EUCI Residential Demand Charges Symposium Calgary, Canada December 1, 2015 Key Rate Design Principles

More information

OVERVIEW OF UNIFORM TRANSMISSION RATES

OVERVIEW OF UNIFORM TRANSMISSION RATES Exhibit H1 Tab 1 Schedule 1 Page 1 of 2 1 OVERVIEW OF UNIFORM TRANSMISSION RATES 2 3 4 5 6 7 8 9 Transmission rates in Ontario have been established on a uniform basis for all transmitters in Ontario since

More information

FOR IMMEDIATE RELEASE

FOR IMMEDIATE RELEASE Article No. 7353 Available on www.roymorgan.com Roy Morgan Unemployment Profile Wednesday, 11 October 2017 2.498 million Australians (18.9%) now unemployed or under-employed In September 1.202 million

More information

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and

More information

Feasibility Study for the Q MW Solar Project

Feasibility Study for the Q MW Solar Project Feasibility Study for the Q174 74.5 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC

More information

Derivative Valuation and GASB 53 Compliance Report For the Period Ending September 30, 2015

Derivative Valuation and GASB 53 Compliance Report For the Period Ending September 30, 2015 Derivative Valuation and GASB 53 Compliance Report For the Period Ending September 30, 2015 Prepared On Behalf Of Broward County, Florida October 9, 2015 BLX Group LLC 777 S. Figueroa Street, Suite 3200

More information

UPPER CUMBERLAND ELECTRIC MEMBERSHIP CORPORATION. RESIDENTIAL RATE--SCHEDULE RS (March 2019) Availability. Character of Service.

UPPER CUMBERLAND ELECTRIC MEMBERSHIP CORPORATION. RESIDENTIAL RATE--SCHEDULE RS (March 2019) Availability. Character of Service. UPPER CUMBERLAND ELECTRIC MEMBERSHIP CORPORATION RESIDENTIAL RATE--SCHEDULE RS () Availability This rate shall apply only to electric service to a single-family dwelling (including its appurtenances if

More information

SOLAR ENERGY ASSESSMENT REPORT. For 115 kwp. Meteorological Data Source Meteonorm. Date 18 October, Name of Place California.

SOLAR ENERGY ASSESSMENT REPORT. For 115 kwp. Meteorological Data Source Meteonorm. Date 18 October, Name of Place California. SOLAR ENERGY ASSESSMENT REPORT For 115 kwp Name of Place California Client abc Capacity 115 kw Meteorological Data Source Meteonorm Email ezysolare@gmail.com Order No. #1410180005 Date 18 October, 2014

More information

3. Atmospheric Supply of Nitrogen to the Baltic Sea in 2009

3. Atmospheric Supply of Nitrogen to the Baltic Sea in 2009 3. Atmospheric Supply of Nitrogen to the Baltic Sea in 2009 Nitrogen emission data, as well as the model results presented here have been approved by the 35 th Session of the Steering Body of EMEP in Geneva

More information

RESOLUTION NO

RESOLUTION NO RESOLUTION NO. 2018-72 A RESOLUTION ESTABLISHING A SCHEDULE OF ELECTRICAL RATES TO BE CHARGED CUSTOMERS FOR ENERGY AND POWER FROM THE ELECTRIC DISTRIBUTION SYSTEM OF THE CITY; TO REPEAL CONFLICTING RATES

More information

August ATR Monthly Report

August ATR Monthly Report August ATR Monthly Report Minnesota Department of Transportation Office of Transportation Data and Analysis August 2011 Introduction The purpose of this report is to examine monthly traffic trends on

More information

October 17, Please contact the undersigned directly with any questions or concerns regarding the foregoing.

October 17, Please contact the undersigned directly with any questions or concerns regarding the foregoing. California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 October 17, 2017 Re: California

More information

Digitized for FRASER Federal Reserve Bank of St. Louis. Per cent. P Total reported (000) ^D-)>oCL

Digitized for FRASER   Federal Reserve Bank of St. Louis. Per cent. P Total reported (000) ^D-)>oCL statistical FEDERAL release RESERVE ^D-)>oCL For immedia < t4 6 relea I s February 13, 1968 AUTOM3BILE LOANS BY MAJOR SALES FINANCE COMPANIES IN THE FOURTH QlJARTP^HE PROPORTION OF 3 YEAR NEW CAR CONTRACTS

More information

Customer and Utility Energy Management Fundamentals 101

Customer and Utility Energy Management Fundamentals 101 Customer and Utility Energy Management Fundamentals 101 Minneapolis October 24 th 2016 Today s Show Brought to you by: Danny Zagotta Barry Mosser Thank you very much, Janet Booker What s your Energy Management

More information

KCP&L GREATER MISSOURI OPERATIONS COMPANY P.S.C. MO. No. 1 1st Revised Sheet No. 149 Canceling P.S.C. MO. No. 1 Original Sheet No.

KCP&L GREATER MISSOURI OPERATIONS COMPANY P.S.C. MO. No. 1 1st Revised Sheet No. 149 Canceling P.S.C. MO. No. 1 Original Sheet No. P.S.C. MO. No. 1 1st Revised Sheet No. 149 Canceling P.S.C. MO. No. 1 Original Sheet No. 149 AVAILABILITY This schedule is available for all general service use, such as combined lighting and power service

More information

Passive Investors and Managed Money in Commodity Futures. Part 2: Liquidity. Prepared for: The CME Group. Prepared by:

Passive Investors and Managed Money in Commodity Futures. Part 2: Liquidity. Prepared for: The CME Group. Prepared by: Passive Investors and Managed Money in Commodity Futures Part 2: Liquidity Prepared for: The CME Group Prepared by: October, 2008 Table of Contents Section Slide Number Objectives and Approach 3 Findings

More information

Hybrid Electric Vehicle End-of-Life Testing On Honda Insights, Honda Gen I Civics and Toyota Gen I Priuses

Hybrid Electric Vehicle End-of-Life Testing On Honda Insights, Honda Gen I Civics and Toyota Gen I Priuses INL/EXT-06-01262 U.S. Department of Energy FreedomCAR & Vehicle Technologies Program Hybrid Electric Vehicle End-of-Life Testing On Honda Insights, Honda Gen I Civics and Toyota Gen I Priuses TECHNICAL

More information

Impact Evaluation of 2004 Compressed Air Prescriptive Rebates

Impact Evaluation of 2004 Compressed Air Prescriptive Rebates Impact Evaluation of 2004 Compressed Air Prescriptive Rebates May 15, 2006 Prepared for: National Grid USA Service Company P.O. 0000027684 DMI# 05006.520 Prepared by: DMI 450 Lexington Street Newton, MA

More information

Current Development of the Tariff Structure in the Electricity System of the Republic of Macedonia

Current Development of the Tariff Structure in the Electricity System of the Republic of Macedonia Current Development of the Tariff Structure in the Electricity System of the Republic of Macedonia Partnership Program ERC, Republic of Macedonia - PSB, Vermont Skopje, 25-29, October, 2004 1 Existing

More information

THE EMPIRE DISTRICT ELECTRIC COMPANY P.S.C. Mo. No. 5 Sec. 4 1st Revised Sheet No. 23

THE EMPIRE DISTRICT ELECTRIC COMPANY P.S.C. Mo. No. 5 Sec. 4 1st Revised Sheet No. 23 P.S.C. Mo. No. 5 Sec. 4 1st Revised Sheet No. 23 Canceling P.S.C. Mo. No. 5 Sec. 4 Original Sheet No. 23 PURPOSE: The purpose of this Rider SR is to implement the solar rebate established through 393.1030

More information

GENERAL INFORMATION 15. MARKET SUPPLY CHARGE ("MSC")

GENERAL INFORMATION 15. MARKET SUPPLY CHARGE (MSC) P.S.C. NO. 3 ELECTRICITY LEAF: 214 ORANGE AND ROCKLAND UTILITIES, INC. REVISION: 3 INITIAL EFFECTIVE DATE: November 1, 2015 SUPERSEDING REVISION: 1 Issued in compliance with Order in Case 14-E-0493 dated

More information

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING Third Revised Sheet 55a Cancels Second Revised Sheet 55a A. ELIGIBLE CUSTOMER-GENERATOR RULE NO. 17 NET ENERGY METERING Net energy metering is available to eligible customer-generators, defined as, permanent

More information

Used Vehicle Supply: Future Outlook and the Impact on Used Vehicle Prices

Used Vehicle Supply: Future Outlook and the Impact on Used Vehicle Prices Used Vehicle Supply: Future Outlook and the Impact on Used Vehicle Prices AT A GLANCE When to expect an increase in used supply Recent trends in new vehicle sales Changes in used supply by vehicle segment

More information