Jack Hammering of Electrical Conduit Incident Root Cause Analysis Final Report
|
|
- Bernard Bryan Ray
- 5 years ago
- Views:
Transcription
1 Root Cause Analysis Final Report Department: O&M Incident Date: Jobsite: Sun Valley Mall just outside of Lucille s Smokehouse BBQ Nature/Severity: No injury; Damage to 480 V electrical power line Incident Summary: A crew was in the process of installing two new service lines, meters and a backflow device for a restaurant. Based on design drawings produced by Engineering all known utilities had been located through the USA process and some design changes had already been discussed with the Design Engineer due to actual field conditions. After installation of the new lines and the completion of cut-overs, the existing service lines were to be abandoned. Design drawings provided by Engineering indicated a 21 KV duct bank would transverse the trench. This duct bank was located during trenching without incident. However, a private 4 electrical conduit that ran parallel with trench was not shown in the Engineering drawings. The applicant provided the background survey and utility data to assist in design development. However, Engineering did not cross check the utility record information directly from Sun Valley Mall staff. Later, Sun Valley Mall staff provided O&M a drawing indicating a private electrical conduit was also present in the trench area but their drawing was imprecise and the electrical conduit s depth was not provided. The private 4 electrical conduit was not marked in the USA process so CCWD s locators were called in to assist in marking it. Based on information from Mall staff, CCWD locators identified an electrical line running parallel at the location where the crew was planning to trench. The electrical marking was within two or three inches of the actual 4 electrical conduit location. The crew decided to trench at the location of the marked electrical line because other existing utility conflicts indicated on the drawings and located in the field, precluded them from working around the marking. The crew was able to safely expose the 4 electrical conduit in the beginning of the trench at a depth of two feet. Later in the trench work, a crew member was jack hammering the sidewalk near the electrical conduit markings when an electrical contractor from inside Lucille s BBQ informed the crew that a loud arc blast occurred at electrical equipment located in the basement. The jack hammer had struck a 480 V electrical line that was encased in the concrete sidewalk just 10 inches from the surface causing the power to go out at the nearby Firestone business. The crew member did not sense an electrical shock and was not injured in any way. He was wearing safety boots and leather gloves. The 4 electrical conduit was encased in the sidewalk concrete and not visible when the incident occurred. The electrical power was turned off and locked out by Mall staff prior to fully exposing the broken conduit. The crew carefully chipped the concrete to expose the conduit without further damage.
2 Page 2 of 5 View of the site just after a 480 V conduit was struck by a jack hammer. The conduit is not visible. 480 V conduit was encased in concrete 10 inches below the sidewalk surface. Note the conduit s locating mark between the feet of the worker. At the lower right, an unmarked 4 communication conduit was safely exposed though just inches below the pavement section. The 4 conduit was later identified as AT&T who had failed to mark it during USA clearence.
3 Page 3 of 5 Section of punctured metal electrical conduit along with jack hammer gad with burned point. Note the two private electrical conduits are not encased and very shallow to clear an old concrete wall.
4 Page 4 of V conduit after repair made.
5 Page 5 of 5 Contributing Factor(s): Though the 480 V electrical conduit was located and marked, it was at a shallower depth than the crew expected and encased in non-red-colored concrete (along with the sidewalk). There was not enough room to excavate while avoiding all utility conflicts. Root Cause (s): The Excavation SOP does not cover the safe removal of pavement within 24 inches of electrical markings. The procedures do not include the required use of electricallyrated PPE such as insulated boots, gloves or mats. Corrective Action Plan: Revise the Excavation SOP to include a request for the deenergization and lockout-tagout of electrical lines suspected of being less than two feet from the surface prior to powered pavement removal. If the electrical line cannot be deenergized or cannot be positively identified but known to be present in the vicinity, use insulating mats, gloves and boots rated for the hazard. As an additional precaution, ground the jack hammer where a proper ground is available. Update the Excavation Awareness training program to include changes to the Excavation SOP and to instruct employees not to assume depths of utilities to remain constant, and where possible, fully expose utilities to identify alignment by soft-digging before proceeding to power excavate, jack hammer or saw cut. Although not a factor in this incident, update Engineering Standard Practices to ensure all survey information is obtained and cross checked, where feasible, as part of the design development. Person Responsible: Pete Schoemann Spiro Zapantis Due Date: 6/15/13 Spiro Zapantis 6/15/13 Rachel Murphy 8/15/13
OSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926)
OSHA Update Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926) 5/14/2014 Significant Changes to the Standards General Training Host Employer & Contractor Responsibilities
More informationBP OIL -- TOLEDO REFINERY
BP OIL -- TOLEDO REFINERY Document Type: Procedure Effective Date: August 31, 2017 Owner: Dane P. Clark Refinery Wide Electrical Distribution System Switching and Isolation Auth. By: Rick J. Chmelovski
More informationELECTRICAL SAFET Y FOR CONTRACTORS
ELECTRICAL SAFET Y FOR CONTRACTORS TABLE OF CONTENTS Electricity Demands Respect... 2 Before Starting to Work Let Us Help You...2 Basic Rules for Electrical Safety...2 Common Dangers for Contractors...3
More informationAVOIDING ELECTROCUTION HAZARDS
Print AVOIDING ELECTROCUTION HAZARDS MODULE DESCRIPTION This module will provide information that helps you recognize and avoid common electrocution hazards in your work environment. OBJECTIVES After completing
More informationSAFETY ALERT - # TOWING INCIDENT
Incident Summary: An injury recently occurred on an oil and gas site undergoing production workover activities. A worker had the first three fingers of his right hand pinched and severely injured in the
More informationGEORGIA DEPARTMENT OF CORRECTIONS Standard Operating Procedures IVN Authority: Effective Date: Page 1 of WETHERINGTON/HODGE 4/01/02 5
GEORGIA DEPARTMENT OF CORRECTIONS Standard Operating Procedures Functional Area: SUPPORT SERVICES/FIRE SERVICES Subject: EMERGENCY OPERATIONS/MOTOR VEHICLE FIRES Revises Previous Authority: Page 1 of WETHERINGTON/HODGE
More informationElectrical Safety Slide Show Presenter s Notes
Contractor Beware Electrical Safety Slide Show Presenter s Notes Slide 1 Before darkening the room, offer a welcome and overview. Begin by introducing the program and its topic: Today s training session
More informationEnergized Electrical Work
Manitoba STANDARD PROCEDURE INSTRUCTION Title Energized Electrical Work Department Supersedes SPI Dated N/A SPI 32-4 Effective Date MAR 30, 2012 Energized Electrical Work SPI 32-4 Page 1 of 9 STANDARD
More informationSSMP ELEMENT 4 O & M Program APPENDIX 4.3. Sewer Pipe Cleaning Standard Operating Procedures (SOPs)
SSMP ELEMENT 4 O & M Program APPENDIX 4.3 Sewer Pipe Cleaning Standard Operating Procedures (SOPs) City of San Mateo CODE OF SAFE PRACTICES Table of Contents A B C D E F G Air Compressor and Pressure Vessel
More informationNewmont USA Ltd. Genesis Mine June 6, 2009
Newmont USA Ltd. Genesis Mine June 6, 2009 What are the Potential Hazards? Flatbed Truck Collecting drill cuttings Three Bench Drills Operating Service Truck Accident Time Line About 12:00 PM, the victim
More informationCould also be a Near Hit
A near miss is an unplanned event that did not result in a fatal injury but had the potential to do so. Only a fortunate break in the chain of events prevented an injury, fatality or damage; in other words,
More informationELECTRICAL HAZARD EXAMPLES
ELECTRICAL HAZARD EXAMPLES UNFORTUNATELY, THE EVENTS LISTED BELOW ARE MORE COMMON THAN YOU WOULD EXPECT Circuit breaker does not open the circuit when operated manually or remotely. The contacts within
More informationElectrical Safety CSA Z462 & NB Regulations
Electrical Safety CSA Z462 & NB Regulations WorkSafeNB s 2014 Health and Safety Conference Daniel Roberts Senior Manager, Electrical Safety Consulting at Schneider Electric Vice-chair CSA Z462 daniel.roberts@schneider-electric.com
More informationBP-Husky Refinery Toledo, OH
BP-Husky Refinery Toledo, OH Document Type: Procedure Refinery Wide Procedure No.: SAF 095 Effective Date: 2/25/16 Owner: D. Clark Working on or near Energized Electrical Equipment Rev. No.: 6 Auth. By:
More informationSafe use of quick hitch devices on excavators. SIM 02/2007/01 Version 2. Target Audience: Construction Division Staff Construction Inspectors
Safe use of quick hitch devices on excavators SIM 02/2007/01 Version 2 Target Audience: Construction Division Staff Construction Inspectors Date issued: 2007-06-27 Review date: 2011-06-27 OG Status: Fully
More informationElectrical Awareness for Construction Activities. Overhead Power Lines & Underground Cables
Electrical Awareness for Construction Activities Overhead Power Lines & Underground Cables Electrical Awareness for Construction Activities Electrical appreciation Agenda Overview of the electrical distribution
More informationPresenter s Notes SLIDE 1. Before darkening the room, offer a welcome and overview. Begin by introducing the program and its topic:
Before darkening the room, offer a welcome and overview. Begin by introducing the program and its topic: Today s training session focuses on working safely around overhead and underground electric power
More informationP. & I. Pascoe Limited
P. & I. Pascoe Limited www.hh.net.nz Significant Hazard Register and Safe Operating Procedures (SOP s) Diggers / Roller / Bulldozer / Loader July 2008 Significant Hazard Register & Safe Operating Procedures
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 04/25/18 Specifications for Residential Construction Revision List REVISION Date Page No. Description 03/20/00 6.1-6.2 Added Armorcast
More informationHighway Construction Worker Dies When Struck By Semi-Tractor Trailer Incident Number: 03KY030
Highway Construction Worker Dies When Struck By Semi-Tractor Trailer Incident Number: 03KY030 Kentucky Fatality Assessment and Control Evaluation Program Kentucky Injury Prevention and Research Center
More informationGuidelines when working near TasNetworks electrical assets
Guidelines when working near TasNetworks electrical assets About TasNetworks Tasmanian Networks Pty Ltd (ACN 167 357 299) ( TasNetworks ) is the owner and operator of the regulated electricity network
More informationTOOL BOX TALKS. Municipality General Safety Rules SAFE (7233)
TOOL BOX TALKS Municipality General Safety Rules Safety is of the utmost importance in the discharge of work or duty. These safety rules are designed to promote proper safety practices on the job. They
More informationSTANDARD OPERATING PROCEDURES. ELECTRICAL HAZARDS SAFETY PROCEDURES PURPOSE: To provide safety procedures for the removal of electric meters,
PURPOSE: To provide safety procedures for the removal of electric meters, SCOPE: All firefighting personnel. I. ELECTRIC METERS: The following are safety procedures for the removal of an electric meter
More informationPublic Works Operations Manual Standard Operating Procedures for Water and Sewer WS - B311 Sanitary Sewer Connection Repair
Public Works Operations Manual Standard Operating Procedures for Water and Sewer WS - B311 Sanitary Sewer Connection Repair 1. Objective: 1.1. To repair the sanitary sewer connection in a timely and efficient
More information1. Cranes. 3. Hazardous Chemicals. 4. Signs. 2. Trenching and Excavations
A Safe Operation Safety Tips for Heavy Construction 1. Cranes Cranes are a common piece of equipment on heavy construction jobsites. Always perform a walk around inspection before and after each shift
More informationPublic Works Operations Manual Standard Operating Procedures for Water and Sewer WS-B111 Sewer Main Repair
Public Works Operations Manual Standard Operating Procedures for Water and Sewer WS-B111 Sewer Main Repair 1. Objective: 1.1. To repair the sewer main in a timely and efficient manner, minimizing disruption
More informationTEMPORARY ELECTRICAL SERVICE
ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us/energyservices TEMPORARY ELECTRICAL SERVICE A. INTRODUCTION
More informationPresenter s Notes SLIDE 1
Before darkening the room, offer a welcome and overview. Begin by introducing the program and its topic: Today s training session focuses on working safely around overhead and underground electric power
More informationConcrete Delivery Requirements
BORAL CONCRETE Build something great Customer Notification Concrete Delivery Requirements MARCH 2017 CONCRETE DELIVERY REQUIREMENTS - TRAFFIC MANAGEMENT, ENVIRONMENTAL At Boral we regard the safety and
More informationMORELAND CITY COUNCIL Operations Centre 7-9 Walter Street Hadfield Vic 3046 Tel:
MORELAND CITY COUNCIL Operations Centre 7-9 Walter Street Hadfield Vic 3046 Tel: 8311 4300 Approved by the Walter Street OHS committee Date: Operation Brief Description of Activity Waste Collection Using
More informationDriver Fatally Injured by Fall from Truck Date of Incident: March 5, 2007 Type of Incident: Fatality
Driver Fatally Injured by Fall from Truck Date of Incident: March 5, 2007 Type of Incident: Fatality TABLE OF CONTENTS PAGE NUMBER SECTION 1.0 DATE AND TIME OF INCIDENT 3 SECTION 2.0 NAME & ADDRESS OF
More informationPT4 Pump Station, Turkey
HEALTH AND SAFETY 9 PT4 Pump Station, Turkey PSG2 employees, Georgia KP 377, Azerbaijan 9 9 HEALTH AND SAFETY All efforts continued this quarter to observe the stringent health and safety targets set by
More informationElectrical Safety. Facilitator Guide
Electrical Safety Facilitator Guide Contents Overview...................................................2 Tips For Conducting An Effective Training Session..................... Successful Safety Programs.......................................
More informationSafe Working on or near low voltage electrical installations & equipment
Safe Working on or near low voltage electrical installations & equipment Guidance Notes Version 1.11 28 June 2017 Gippsland Water Document Details Business Owner Procedure Process Owner/s Document Title
More informationPERMANENT RESIDENTIAL UNDERGROUND SERVICE
CITY OF RICHLAND ENERGY SERVICES DEPARTMENT 505 Swift Boulevard, MS-21 Richland, WA 99352 Telephone (509) 942-7403 Fax (509) 942-7405 PERMANENT RESIDENTIAL UNDERGROUND SERVICE A. INTRODUCTION This guide
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 10/03/17 Specifications for Residential Construction Revision List REVISION Date Page No. Description 8/18/09 T.O.C., 8.1-8.1.5 &
More informationElectrical Safety Program
Electrical Safety Program Medford Area Public School District 124 West State St School District: Medford, WI 54451 715 748 4620 Review Date(s): January 2018 Program Dave Makovsky Coordinator: Purpose and
More informationThe New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016
The New 2017 National Electric Safety Code Overview and Significant Changes Presented by Mickey Gunter October 28, 2016 NESC Technical Subcommittees Subcommittee 1 Coordination, Definitions Subcommittee
More informationINLAND NORTHWEST REGIONAL PAVEMENT CUT POLICY
INLAND NORTHWEST REGIONAL PAVEMENT CUT POLICY Howard Hamby Spokane County Road Maintenance Administrator PAVEMENT CUT FAILURES 1. Sloughing 2. Poor Compaction 3. Poor
More informationFor Conduit Inspections
Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit
More informationInvestigation Report Worker Run Over by Packer Fatality - July 1, 2013
Workplace Standards Delivery Investigation Report Worker Run Over by Packer Fatality - July 1, 2013 Report No- F- OHS-044337-65269 January 2015 This document reports OHS investigation of a fatal incident
More informationRadiological Preparedness & Emergency Response. Session IV. Scenario. PPE and Decontamination Principles
Radiological Preparedness & Emergency Response Session IV PPE and Decontamination Principles Scenario 1 Objectives Discuss the different types of PPE. Describe radiological decontamination. Describe chemical
More informationAir Transat Flight 236
www.sassofia.com office@sassofia.com Air Transat Flight 236 Photo of removed fuel line showing crack The accident investigators determined that the fuel leak leading to the fuel exhaustion and dual engine
More informationCRAWLER EXCAVATOR OUTLINE
Lesson 1: Lesson 2: Lesson 3: Goals & Objectives of this Lesson - Safe Productivity. - Introduction. - Goals and Objectives. - What is a professional? Components & Control Identification - Key Components.
More informationInitial Issue Date Revision Date: Revision No. Next Revision Date: Reliant Holdings Ltd Safety Management System. Issuing Dept: Safety
BLASTING Preparation: Mgr SOP-1 Page: Page 1 of 10 Purpose The purpose of this program is to provide safe guidelines for the operation and maintenance of abrasive blasting equipment and their related components
More informationSafe Work Instructions Tools and Equipment
Safe Work Instructions Version 1.00! 23 March 2015 Table of Contents PURPOSE AND SCOPE...4 HAND TOOLS...6 ELECTRIC POWER TOOLS...7 PETROL POWERED TOOLS...9 PORTABLE ELECTRICITY GENERATOR...12 PNEUMATIC
More informationDELETE first sentence of first paragraph that reads: REPLACE with the following:
To Bidder of Record: SAN ANTONIO WATER SYSTEM Addendum 2 To Construction Documents For 2012 WATER & SEWER CONSTRUCTION CONTRACT, PACKAGE I SAWS WATER JOB NO. 12-5001 SAWS SEWER JOB NO. 12-5501 Solicitation
More informationInvestigation Report. Worker Fatally Crushed by Pipe Rolling into Trench. July 16, Report No: F-OHS CC7F August 2015 Page 1 of 6
Investigation Report Worker Fatally Crushed by Pipe Rolling into Trench July 16, 2013 Report No: F-OHS-045232-7CC7F August 2015 Page 1 of 6 The contents of this report This document reports s investigation
More informationEXPEDITION FIRE- BURNED DOZER
EXPEDITION FIRE- BURNED DOZER FACILITATED LEARNING ANALYSIS Figure 1: Wakulla 2 Tractor Plow post incident SUMMARY On April 27, 2012 the Apalachicola National Forest responded to a wildfire in burn unit
More informationThe cost estimation methodology used to update the charges and credits is the same methodology the Company utilized in the prior year s filing.
LISA D. NORDSTROM Lead Counsel lnordstrom@idahopower.com December 28, 2018 Public Utility Commission of Oregon Filing Center 201 High Street SE, Suite 100 P.O. Box 1088 Salem, Oregon 97301 Re: Tariff Advice
More informationESSENTIAL SAFETY RESOURCES
ESSENTIAL SAFETY RESOURCES GS-3029 Originator: Safety Advisor s Signature: Type Name Approval: HSE Manager s Signature: Type Name Approval: Operations Manager s Signature: Type Name Table of Contents PURPOSE...
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS
San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance
More informationPURPOSE POLICY. Page 1 of 6 / S.O.G Highway Operations Pascal Arnes Chief of Fire
DECATUR TOWNSHIP FIRE DEPARTMENT STANDARD OPERATING GUIDELINE TITLE: HIGHWAY OPERATIONS SECTION: SAFETY NUMBER: 6.01 EFFECTIVE: JULY 1, 2014 THIS GUIDELINE SUPERSEDES ALL PREVIOUS GENERAL ORDERS, POLICIES,
More informationPresentation Objectives Provide a description of how Directional Boring works Cover the basics for planning a Directional Bore Discuss the advantages
Directional Boring { An Introduction to the HDD Process Presentation Objectives Provide a description of how Directional Boring works Cover the basics for planning a Directional Bore Discuss the advantages
More informationElectrical Hazards in Construction
Electrical Hazards in Construction WELCOME Tim Dawson Presentation developed by Dawson Safety Services - 2013 Dangers of Electrical Shock Currents above 10 ma* can paralyze or freeze muscles. Currents
More informationSafety Training Topic ELECTRICAL SAFETY
Safety Training Topic Purpose of Meeting To remind workers that electrical hazards can result in a serious injury. To reinforce electrical safety rules. To consider ways to protect yourself from electrical
More informationMIFACE INVESTIGATION #06MI209
MIFACE INVESTIGATION #06MI209 SUBJECT: Heavy Equipment Operator Dies After Being Pinned Between the Boom and Cab of an Excavator Summary On December 4, 2006, a 51-year-old male heavy equipment operator
More informationRAILROAD ACCIDENT INVESTIGATION. Report No THE NEW YORK CENTRAL RAILROAD COMPANY POCA, W. VA. NOVEMBER 21, 1961 INTERSTATE COMMERCE COMMISSION
RAILROAD ACCIDENT INVESTIGATION Report No. THE NEW YORK CENTRAL RAILROAD COMPANY POCA, W. VA. NOVEMBER 21, 1961 INTERSTATE COMMERCE COMMISSION Washington 2 SUMMARY DATE: November 21, 1961 RAILROAD: New
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS
San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance
More informationAppalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary:
Appalachian Power Company Policy No. 2 Cover Up Procedures Policy Summary: A. When a worker is in a position where the worker or a conductive object in the worker s hand can go or reach within the minimum
More informationLaborer Dies When Caught in Arms of a Skidsteer Loader Incident Number: 03KY087
Laborer Dies When Caught in Arms of a Skidsteer Loader Incident Number: 03KY087 Borrowed skidsteer involved in fatality. Kentucky Fatality Assessment and Control Evaluation Program Kentucky Injury Prevention
More informationFatality Investigation Report Worker Crushed February 16, 2013
Fatality Investigation Report Worker Crushed February 16, 2013 Report No-F-036953-7C395 July, 2015 The contents of this report This document reports OHS investigation of a fatal accident in February 2013.
More informationSafety Working with LV Drives
US1008e_LV Drive Safety_C, April 2009 Safety Working with LV Drives Intended Audience Only qualified electricians and engineers are allowed to install and maintain a LV Drive Students of this training
More informationFirst Responder Beware
First Responder Beware Electrical Safety Slide Show Presenter s Notes Slide 1 Before darkening the room, offer a welcome and overview. Begin by introducing the program and its topic: Welcome to First Responder
More informationTheory Test Questions Contents
Theory Test s Contents To view a specific Bank click on the title of the category in the Category Desription column. To return to the Contents page click on the CPCS Logo within the question bank (1st
More informationSAFETY BULLETIN ELECTRICITY THE RULES HOW TO STAY SAFE WHEN WORKING AROUND POWER LINES AMERICAN CONCRETE PUMPING ASSOCIATION
SAFETY BULLETIN ELECTRICITY THE RULES HOW TO STAY SAFE WHEN WORKING AROUND POWER LINES AMERICAN CONCRETE PUMPING ASSOCIATION WWW.CONCRETEPUMPERS.COM Electricity The Rules 1. You MUST maintain 20 feet clearance
More informationCity of Grand Island Tuesday, February 13, 2018 Council Session
City of Grand Island Tuesday, February 13, 2018 Council Session Item G-7 #2018-34 - Approving Certificate of Final Completion for the Construction of North Interceptor Phase I; Project No. 2012-S-6 Staff
More informationWork safely around power lines.
CONTRACTOR BEWARE Work safely around power lines. Click your mouse to navigate through the slide show. Respect the Power of Electricity 2 When you arrive at a job site, always identify power lines and
More informationHybrid & Electric Cars Guidance for organisers of Speed events
Hybrid & Electric Cars Guidance for organisers of Speed events Electric vehicles rely on stored electrical energy to power an electric motor to provide propulsion. Hybrids are primarily powered by an internal
More informationPhoto of NARM site here?
Photo of NARM site here? Ground Monitoring System Fault Investigation North Antelope Rochelle Mine Lyle Hunt / Scott Svoboda - Peabody Energy David Shipp / Mike Peters - Eaton Electrical Engineering Services
More informationBeckley Village Hall BVH DN9. HSE Risk Assessment
What are the hazards? 1 Slips, trips and falls E.g. uneven surface of car park, cleaning floors etc. Who might be harmed and how? Users of the hall and car park may suffer injuries such as fractures or
More informationElectricCourseCatalog.
ElectricCourseCatalog www.energyu.org www.midwestenergy.org Electric Library (01000 Substations)...6 ELEC 01011 Circuit Breaker Timing and Testing... 6 ELEC 01012 Overhaul Maintenance of Substation Circuit
More informationEnergize Eastside. Underground transmission lines and EMF webinar. Leann Kostek. Senior Project Manager, Puget Sound Energy
Energize Eastside Underground transmission lines and EMF webinar Leann Kostek Senior Project Manager, Puget Sound Energy March 11, 2014 Webinar orientation Welcome to the webinar Presentation #1: Undergrounding
More informationExcavator 360 above 10 Tonnes A59
Excavator 360 above 10 Tonnes A59 What is the definition of, or how can a hazard be described? What is the purpose of a risk assessment? List SIX typical subject areas that should be covered in a site
More informationSTATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2012
Safety Services 16 th floor, Commerce Place Tel: 1-866-421-6929 10155 102 nd Street Fax: 780-427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS ELECTRICAL INCIDENTS IN ALBERTA January 1 to December 31,
More informationLeak Detector, Red Jacket #FX1V
ITEM 1 SUBMERSIBLE REMOTE PUMPS A. 2. Manufacturer EACH Red Jacket Red Jacket 4. Effective date of schedule EACH Oct. 3, 2005 July 1, 2006 B. Red Jacket Equipment 1. Leak Detector, Red Jacket #FX1V 215.00
More informationAqua Green Utility Inc.
Aqua Green Utility Inc. Individual septic tank and pump tank requirements. Only configurations and equipment approved by Aqua Green Utility Inc. may be used. Not following these configurations shall be
More information120-ELECTRICAL SAFETY PROGRAM
120.1 PURPOSE A. To set forth procedures for the safe use of electrical equipment, tools, and appliances at Central New Mexico Community College (CNM). 120.2 SCOPE A. This program applies to all CNM employees
More informationDefinitions. Exposed part. Live or energized part. De-energized part
Electrical Safety Definitions Exposed part Live or energized part De-energized part 1a Definitions De-energized exposed parts that are not locked/tagged are considered to be energized exposed parts 1b
More informationAvoidance of Danger from Electricity Overhead Lines and Underground Cables
Avoidance of Danger from Electricity Overhead Lines and Underground Cables 1 Avoidance of Danger from Electricity Overhead Lines and Underground Cables Introduction In the UK on average, 20 people are
More informationStandard Operating Procedure
Procedure Type: Creation Date: Revision Date: Critical 12/22/2014 04/06/2015 Purpose: Ensure that the Isolation of Hazardous Energy is done effectively and to maintain the safety of personnel working on
More informationSUBTOTAL SITE WORK & DEMOLITION (UTILITIES) $180, $348, $319,943.71
BASE BID 1.00 GENERAL CONDITIONS 1.01 Mobilization (Maximum 5% of Base Bid) LS 1 84,000.00 $ 84,000.00 100,000.00 $ 100,000.00 85,000.00 $ 85,000.00 1.02 Bonding, Insurance, Permits (including Plumbing,
More informationNEAR MISS report EVENT DESCRIPTION: KEY LEARNINGS: KEY TAKEAWAYS:
A CPC contractor noticed municipal contractors working nearby who were digging without approval on Line 18 ROW. Work was stopped without incident but the excavator had gotten within 2-feet of the pipeline.
More informationSTATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2017
Community and Technical Support 16 th floor, Commerce Place Tel: 1-866-421-6929 10155 102 nd Street Fax: 780-427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS ELECTRICAL INCIDENTS IN ALBERTA January
More informationHazards SAFETY CORNER. of Establishing an. Work Condition
Hazards of Establishing an Electrically Safe Work Condition Written By Tony Demaria & Dean Naylor, Tony Demaria Electric, Mose Ramieh, III, Power Generation & Testing When working around electrical equipment,
More informationLevel crossing collision, near Dymchurch, 10 September 2016
Level crossing collision, near Dymchurch, 10 September 2016 1. Important safety messages In this instance, the tractor driver did not use the level crossing in accordance with the instructions provided
More informationBoeing , G-CIVX. None N/A. N/A hours Last 90 days - N/A hours Last 28 days - N/A hours. AAIB Field Investigation
INCIDENT Aircraft Type and Registration: No & Type of Engines: Boeing 747-436, G-CIVX 4 x Rolls-Royce RB211-524G2 turbine engines Year of Manufacture: 1998 (Serial no: 28852) Date & Time (UTC): Location:
More informationToday, we re going to talk about battery safety. We ll discuss all the key issues associated with using batteries safely, including battery hazards,
Today, we re going to talk about battery safety. We ll discuss all the key issues associated with using batteries safely, including battery hazards, battery charging, and battery maintenance. Although
More informationCONSTANTINOPLE. Page 1 of 5
CONSTANTINOPLE This is the very much abridged story of a large private miniature railway built by Mini Train Systems in late 2011. The owners have asked for their privacy to be respected but have kindly
More informationHighway worker crushed by swinging backhoe boom
Highway worker crushed by swinging backhoe boom SUMMARY On July 1, 2007, a 47-year-old road construction worker was killed while working on the ground alongside a backhoe. The worker was a journeyman equipment
More informationSTATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA to
Safety Services 16 th floor, Commerce Place Tel 1-866/421-6929 10155 102 nd Street Fax 780/427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA 01 01 to 12 31 Regulations
More informationDowntown Lee s Summit Parking Study
Downtown Lee s Summit Parking Study As part of the Downtown Lee s Summit Master Plan, a downtown parking and traffic study was completed by TranSystems Corporation in November 2003. The parking analysis
More informationIn This Document MODULE DESCRIPTION This module provides information on the safety concerns and
Crane Safety Fact Sheet In This Document MODULE DESCRIPTION This module provides information on the safety concerns and Introduction necessary precautions you will need to be aware of when working Crane
More informationDropped Object Incidents on Chevron operated assets
Dropped Object Incidents on Chevron operated assets January 2010 2010 Chevron Summary There were three RIDDOR-reportable Dropped Objects on Chevron operated assets in January 2010: No personnel were injured
More informationExcavation worker killed by flying rigging when hook fails
Excavation worker killed by flying rigging when hook fails SUMMARY On June 10, 2005, a 40-year-old pipelayer was struck in the head by the flying rigging of a towline that failed at an excavation site,
More informationNewport News Shipbuilding Contractor Environmental, Health and Safety Resource Manual Cranes
Newport News Shipbuilding Contractor Environmental, Health and Safety Resource Manual Cranes Newport News Shipbuilding Page 1 CRANES 1. Hazard and Reference The use of cranes at NNS presents a serious
More informationSPECIFICATIONS FOR COMMERCIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR COMMERCIAL CONSTRUCTION REVISED 06/28/18 Commercial Construction Specifications Revision List REVISION Date Page No. Description 03/01/00 4.2-4.3 Changed leveling
More informationADVANCING THE LEGEND TYPICAL EXCAVATOR MARKETS APPLICATIONS. New with GRADALL Series V excavators
Gradall Series V excavators represent a unique combination of power, speed, productivity and versatility unmatched by any machine anywhere in the world. First invented to meet the global need for one machine
More informationKey Issues and Considerations when for. Working around Concrete Pumps, Concrete Pump Trucks, and Crane Lift Buckets
Key Issues and Considerations when for Working around Concrete Pumps, Concrete Pump Trucks, and Crane Lift Buckets Page 1 of 15 INTRODUCTION This document is created to highlight issues confronted by members
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More information