1 7 495 Boiler Management Unit (BMU) LMU74... LMU75... LMU7 are digital Boiler Management Units (BMUs) for use in gas-fired appliances equipped with premixing burners. LMU74 without combustion optimization LMU75 with combustion optimization The LMU7 and this Data Sheet are intended for use by OEMs which integrate the BMUs in their products. Use The LMU7... provide all supervisory and control functions required for burner, space heating and DHW operation and using integrated communication interfaces facilitate modular system extensions. They are especially suited for: Premixing or condensing gas-fired appliances with burners modulating via PWM fan and pneumatic gas / air ratio control in intermittent operation, with direct ignition of the main flame Capacity ranges < 70 kw, kw and > 120 kw Heating boilers or combi boilers with DHW storage tanks or instantaneous DHW heaters Attention! All safety, warning and technical notes given in the Basic Documentation of the LMU7 (P7495) and in the User Manual (U7495) also apply to this document!
2 Supplementary documentation Environmental Product Declaration LMU74... / LMU E7495 Extended OEM User Manual (setting lists)... I7495 Extended OEM User Manual (setting lists) Sitherm Pro... I Basic Documentation LMU P7495 Basic Documentation Sitherm Pro... P Product Range Overview LMU7... Q7495 User Manual LMU7... U7495 Presentation of product The basic unit of the LMU7 is a combination of burner control and heating controller. It has no operating elements. Operation is effected via detached operator units and room units. The scope of functions includes: Safety and supervisory functions / protective functions for the plant DHW and heating circuit control Integration in system applications (cascades, zones, etc.) Operation / service / maintenance Parameter settings Integrated mains transformer Optional system extensions (using ClipIns) Programmable relay output / programmable digital input 2/18
3 Standards and certificates Applied directives: Low-voltage directive 2006/95/EC and 2014/35/EC Directive for gas-fired appliances 2009/142/EC Electromagnetic compatibility EMC (immunity) *) 2004/108/EC *) The compliance with EMC emission requirements must be checked after the Boiler Management Unit is installed in equipment Compliance with the regulations of the applied directives is verified by the adherence to the following standards / regulations: Automatic burner control systems for burners and appliances DIN EN 298 burning gaseous or liquid fuels Automatic electrical controls for household and similar use DIN EN Part 2-5: Particular requirements for automatic electrical burner control systems Safety and control devices for gas burners and gas burning DIN EN appliances Gas/air ratio controls for gas burners and gas burning appliances Part 2: Electronic types DIN EN The relevant valid edition of the standards can be found in the declaration of conformity! EAC Conformity mark (Eurasian Conformity mark) ISO 9001:2008 ISO 14001:2004 OHSAS 18001:2007 Life cycle Boiler Management Units LMU7... has a designed lifetime* of 250,000 burner startup cycles which, under normal operating conditions in heating mode, correspond to approx. 10 years of usage (starting from the production date given on the type field). This lifetime is based on the endurance tests specified in standard EN 298 and the table containing the relevant test documentation as published by the European Association of Component Manufacturers (Afecor) ( The designed lifetime is based on use of the BMUs according to the manufacturer s Data Sheet and Basic Documentation. After reaching the designed lifetime in terms of the number of burner startup cycles, or the respective time of usage, the BMU is to be replaced by authorized personnel. * The designed lifetime is not the warranty time specified in the Terms of Delivery 3/18
4 Mechanical design QAA75... QAA55... REA02... REA11... RVS... ACS... / OCI... OCI AGU LMU7... VGU... AGU3... AVS AVS Basic operator unit (PCB version) 7475b02e/0513 4/18
5 Technical data LMU7... General Operating voltage +10 % / -15 % Note! Ensure that conductors L and N are correctly connected! Mains frequency 50 Hz ±5 % Power consumption Max. 17 VA (without any loads) Rated surge voltage category III ( to DIN EN ) Degree of protection IP00 IP40 (must be ensured after integration into the boiler) Safety class sections of safety class 0 and sections of SELV Degree of contamination 2 Software classes - Controller section - Burner control to DIN EN class A class C Dimensions (L x H x D) 180 x 180 x 45 mm Weight approx. 0.8 kg Unit fuse T6.3H250 Mounting position optional Environmental conditions Storage DIN EN class 1K3 class 1M2 Temperature range C < 95 % r.h. (non-condensing) Transport DIN EN and DIN EN , chapter 12 class 2K2 class 2M2 Temperature range C < 95 % r.h. (non-condensing) Vibration DIN EN Operation DIN EN class 3K3 class 3M2 Temperature range C < 95 % r.h. (non-condensing) Attention! Condensation, formation of ice and ingress of water are not permitted! 5/18
6 Technical data (cont d) Electrical connections Total current of all mains components connected to the LMU7... and the ClipIns Mains extension (X1-02) fan (X2-01) K1 (X2-02) K2 (X2-03) K3 (X2-04) Flame supervision / ionization probe (X2-05) - Switching thresholds - Response time in the event of loss of flame - Touching of flame detector Safety limiter (X3-01) Fuel valve (X3-02) - AC output 5 A (at UN = ; Tu = 60 C) +10 % / -15 % Depending on power consumption heating circuit pump, programmable output, fuel valve, DHW charging pump, external ignition transformer and used ClipIn +10 % / -15 % Depending on used fan +10 % / -15 % 5 ma 1 A, cos > % / -15 % 5 ma 1 A, cos > % / -15 % 5 ma 1 A, cos >0.8 Min. 0.8 µa (required DC) Typical 1.6 µa Max. 2.4 µa <1 s Not permitted 1 m +10 % / -24 % 5 ma 1 A, cos > 0.6 carrying power supply for fuel valve and ignition +10 % / -24 % valve must still open at AC 175 V 5 ma 0.5 A, cos > 0.8 Note: Fuel valves with rectifier may be connected to the fuel valve output only after consultation with Siemens! In that case, additional protective measures inside the LMU7 are required (optional PCB). RAC output - Pmax General data for fuel valve connection - Leak current at 1.06 x rated voltage - Capacitive extra circuitry or surge voltage limiting protective elements R +10 % / -15 %, 100 Hz valve must still open at AC 175 V 20 W, cos > 0.9 Max. 3 m Max. 0.5 ma Not permitted 6/18
7 Technical data (cont d) External ignition module (X3-03) +10 % / -15 % 5 ma 0.5 A, cos > 0.8 must still ignite at AC 175 V Max. 3 m Any external ignition modules used must be approved by Siemens to ensure their switching performance meets the requirements! Fan speed (X14) Refer to separate Siemens specification: Spezifikation_LMU5x_TrafoGebläse_de_VX.Y.doc (mandatory) Boiler temperature sensor (X11) - Continuously temperature - Short-time temperature - Sensor tolerance - Aging - - Other requirements - Temperature resistance characteristic NTC 10 k Max. 100 C Max. 125 C ±2 K 3 m ±3 % 20 s To DIN EN Temperature [ C] RNTC [k] Temperature [ C] RNTC [k] Remarks: QAx36... must be used depending on relevant specification. Return temperature sensor (X11) DHW temperature sensor (X11) Flue gas sensor (X11) Outside sensor (X10-06) NTC 10 k Described above under boiler temperature sensor NTC 10 k Refer to specification QALx6 10 m (When connecting a thermostat to the DHW sensor input, high-quality contact material (e.g. gold-plated contacts) must be used since the signal voltage at this input is DC 5 V NTC 10 k Refer to specification QAx3 3 m NTC 1 k Refer to specification QAC34 40 m 7/18
8 Technical data (cont d) Pressure sensor (X11) - Output voltage LMU Input voltage LMU Huba Control - Huba Control - Imit Heating circuit Flow Switch (X11) - Output voltage LMU Contact resistance DHW Flow Switch (X11) - Output voltage LMU Contact resistance Safety shutdown / gas pressure switch (X10-03) - Output voltage LMU Contact resistance Programmable digital input / air pressure switch (X10-04) - Output voltage LMU Contact resistance Room thermostat / time switch 2 (X10-01) Room thermostat 1, time switch 1 (X10-02) - Output voltage LMU Contact resistance Stepper motor control for combustion optimization (X12) Min. DC 9 V at 5 ma Typical DC 14 V at 5 ma Max. DC 19 V at 5 ma Max. DC 20 V at 0 ma Max. 10 ma DC 5 V (measuring range V) with a load of 12 k 3 m 0 4 bar (type 502) 0 10 bar (type 503) On request Min. RAC 19 V at 7 ma Typical at 10 ma Max. RAC 31.5 V at 12 ma (50 Hz half-wave rectified) Max m Min. RAC 19 V at 7 ma Typical at 10 ma Max. RAC 31.5 V at 12 ma (50 Hz half-wave rectified) Max m Min. RAC 19 V at 7 ma Typical at 10 ma Max. RAC 31.5 V at 12 ma (50 Hz half-wave rectified) Max m Min. RAC 19 V at 7 ma Typical at 10 ma Max. RAC 31.5 V at 12 ma (50 Hz half-wave rectified) Max m Min. RAC 19 V at 7 ma Typical at 10 ma Max. RAC 31.5 V at 12 ma (50 Hz half-wave rectified) Max m Refer to VGU specification 1 m 8/18
9 Technical data (cont d) Electrical connections BSB users Operator unit (X30) Room unit (X16) - Connection - Cable resistance - Cross-sectional area Users PWM control for heating circuit pump (X11) - PWM frequency - Output voltage LMU7... DHW thermostat of the DHW sensor input AVS37... QAA55... / QAA or 3-wire Max. 200 m Max. 3 x 14 Min. 0.5 mm² Max. 4 (1 operator unit, 2 room units, 1 service unit) Preconditions: 1. Only one QAA75... or two QAA55... may be connected via 2-wire! 2. Max. 3 units may be connected via 3-wire! khz ±2 % Min. DC 5 V at 5 ma Typical DC 10 V at 7 ma Max. DC 15 V at 10 ma Max. DC 20 V at 0 ma 3 m DC 5 V 1.5 ma Cable length LMU7... ClipIn) - Connection LMU7... ClipIn (OCI / AGU ) Max. 1 m Connectors Connection Component Connector type * X11 LMU7... external sensor Connector (RAST2.5) 13-pole Suppliers e.g. Lumberg Duomodul K00 X12 LMU7... VO stepper motor Connector (RAST2.5) 6-pole Suppliers e.g. Lumberg Duomodul K00 X14 LMU7... Connector (RAST2.5) 4-pole Suppliers e.g. Lumberg Duomodul K00 X30 LMU7... to AVS37 Connector (RAST2.5) 5-pole Suppliers e.g. Lumberg Duomodul K23 X40 LMU7... to OCI Connector (RAST2.5) 5-pole Suppliers e.g. Lumberg Duomodul K04 X50 LMU7... to AGU2.500 Connector (RAST2.5) 5-pole Suppliers e.g. Lumberg Duomodul K04 * Connector required for the component (to be provided by OEM). Recommended cross-section area of cable for X11...X15: 0.38 mm² 9/18
10 Technical data (cont d) ClipIn AGU Outputs Electrical connection Mechanical design - AGU2.500x109 - AGU2.500x209 Mixing circuit pump and mixer - Mains frequency Housing version PCB version +10 % / -15 % 5 ma 1 A, cos > Hz ±5 % Note: With regards to the outputs, the total current draw of the LMU7... system must be taken into consideration! Degree of protection IP00 Min. IP40 (must be ensured when fitted inside the boiler) Safety class Parts of safety class 0 and of SELV Degree of pollution 2 Software classes To DIN EN Controller part Class A Housing - Material - Color - Flame protection class Polycarbonate RAL 7035 (light-grey) To UL 94: V-2 Environmental conditions Storage DIN EN Class 1K3 Class 1M2 Temperature range C Transport DIN EN and DIN EN chapter 12 Class 2K3 Class 2M2 Temperature range C Vibration DIN EN Operation DIN EN Class 3K3 Class 3M2 Temperature range C Warning! Condensation, formation of ice and ingress of water are not permitted! Conformity with EEC directives - Electromagnetic compatibility EMC (immunity) 2004/108/EC Input Flow sensor NTC 10 k Same as boiler sensor 10/18
11 Technical data (cont d) ClipIn AGU Outputs Maximum 3 outputs (K1...K3) When using 2 ClipIns with the LMU7..., only 2 outputs possible Electrical connection - Mains frequency +10 % / -15 % 5 ma 1 A, cos > Hz ±5 % Note: With regard to the outputs K1...K, the total current draw of the LMU7... system must be taken into consideration! Degree of protection Safety class Degree of pollution 2 Software classes - Controller part Housing - Material - Color - Flame protection class IP00 Min. IP40 (must be ensured when fitted inside the boiler) Parts of safety class 0 and of SELV To DIN EN Class A Polycarbonate RAL 7035 (light-grey) To UL 94: V-2 Environmental conditions Storage DIN EN Class 1K3 Class 1M2 Temperature range C Transport DIN EN and DIN EN chapter 12 Class 2K3 Class 2M2 Temperature range C Vibration DIN EN Operation DIN EN Class 3K3 Class 3M2 Temperature range C Warning! Condensation, formation of ice and ingress of water are not permitted! Conformity with EEC directives - Electromagnetic compatibility EMC (immunity) 2004/108/EC Input Type reference Input Note AGU2.511A V Observe polarity AGU2.513A109 (0) ma Observe polarity AGU2.514A109 NTC 10 k Same as boiler sensor AGU2.515A109 1) 1) Contact rating: Nom. DC 34 V / 5 ma Note: Only safety extra low-voltage (SELV) may be applied to the inputs. Also, the inputs must not be connected to PE! 11/18
12 Technical data (cont d) Solar ClipIn AGU2.530A109 Outputs Electrical connection Free programmable - Mains frequency +10 % / -15 % 5 ma 1 A, cos > Hz ±5 % Note With regard to the outputs, the total current draw of the LMU7... system must be taken into consideration! Degree of protection IP00 Min. IP40 (to be ensured when fitted inside the boiler) Safety class Parts of safety class 0 and of SELV Degree of pollution 2 Software classes To DIN EN Controller part Class A Housing - Material - Color - Flame protection class Polycarbonate RAL 7035 (light-grey) To UL 94: V-2 Environmental conditions Storage DIN EN Class 1K3 Class 1M2 Temperature range C Transport DIN EN and DIN EN chapter 12 Class 2K3 Class 2M2 Temperature range C Vibration DIN EN Operation DIN EN Class 3K3 Class 3M2 Temperature range C Warning! Condensation, formation of ice and ingress of water are not permitted! Condensation, formation of ice and ingress of water are not permitted! Conformity with EEC directives - Electromagnetic compatibility EMC (immunity) 2004/108/EC Input Collector sensor NTC 10 k 12/18
13 Technical data (cont d) LPB ClipIn OCI420 Environmental conditions Degree of protection IP00 Min. IP40 (must be ensured when fitted inside the boiler) Safety class III (SELV) Degree of pollution 2 Software classes To DIN EN Controller part Class A Housing - Material - Color - Flame protection class Polycarbonate RAL 7035 (light-grey) To UL 94: V-2 Storage DIN EN Class 1K3 Class 1M2 Temperature range C Transport DIN EN and DIN EN chapter 12 Class 2K3 Class 2M2 Temperature range C Vibration DIN EN Operation DIN EN Class 3K3 Class 3M2 Temperature range C Warning! Condensation, formation of ice and ingress of water are not permitted! Conformity with EEC directives - Electromagnetic compatibility EMC (immunity) 2004/108/EC External components RAST5 connector Insulation displacement connector E.g. Lumberg type 3625 (stranded wire mm²) or Connector with screwed terminals E.g. Lumberg type 3611 (stranded wire up to 2.5 mm²) Fan with DC 24 V motor Nominal data Refer to separate Siemens specification Spezifikation_LMU5x_TrafoGebläse_de_VX.Y.doc (mandatory) 13/18
14 Functions Heat source boiler Heat source solar Heating circuit control DHW temperature control Electronic temperature controller Minimum and maximum limitation of the boiler temperature Optimum start control with minimum limitation of the boiler temperature Boiler overtemperature protection (pump overrun) Burner cycling protection via minimum burner running time Frost protection boiler Forced intermittent operation Burner control programs for 3 capacity ranges Acquisition of actual values Flue gas temperature supervision Electronic (safety) limit thermostat Temperature limiter function Proof of flow / water pressure supervision Pressure sensor Output / speed limitation Ionization current limitation / ionization current supervision Burner lock Continuous pump run Boiler control Determination of compensation variants Consumer management (CM) Modulating pump with delta-t supervision DHW storage tank charging solar Overtemperature protection collector and storage tank Frost protection solar Pure weather compensation Weather compensation with room temperature influence Pure room temperature compensation 1st pump circuit with 7-day program 2nd mixing / pump circuit with 7-day program Virtual room model Automatic adaptation of heating curve Automatic summer / winter changeover Automatic 24-hour heating limit Holiday program Quick setback and boost heating Optimum start / stop control Increase of reduced temperature level as a function of the outside temperature Floor curing function Frost protection for flow and plant DHW storage tank charging with 7-day program DHW charging with charging pump or diverting valve DHW charging with one sensor, 2 sensors, or thermostat Selectable priority (absolute / none) Selectable DHW heating program (according to DHW heating program / space heating programs, 24 hours) DHW push, manually or automatically Legionella function DHW discharge protection Control of DHW circulating pump Frost protection DHW ECO function Control of stratification storage tank Control of instantaneous DHW heater Aqua-booster system 14/18
15 Functions (cont d) General Automatic summer- / wintertime changeover Standard time programs Multifunctional inputs and outputs Connection facility for mixing valve module for 2nd mixing / pump circuit Connection facility for service tool (via OCI700 ) Connection facility for remote supervision (via OCI611...) Automatic sensor identification Input and output test Maintenance alarms and fault status messages Note: Some of the above functions are not available with the basic unit alone but only in connection with the respective extension modules! 15/18
16 Basic diagram Lockout (STB, TB) Safety shutdown (GP) or R BV1 BV2 Fuel valve Room thermostat 1 or time switch external ignition module Room thermostat 2 or time switch 4 modulated PWM fan Heating circuit pressure switch DHW FlowSwitch or DHW thermostat Programmable digital input e.g. for air pressure switch LMU74... PWM-moduliert Heating circuit pump DHW pump 1 or diverting valve Boiler flow sensor (tested) Programmable output Boiler flow sensor (tested) DHW sensor 1 or DHW thermostat 5 AGU ClipIn Water pressure sensor QAA55... QAA75... Outside sensor 2 / 3 Room controller HMI AVS37... Operator unit Reset button The diagram shows the full scope of functions offered by the LMU74 system. The actual functions are to be determined based on the respective execution / configuration. 16/18
17 Basic diagram (cont'd) Lockout (STB, TB) Safety shutdown (GP) or R BV1 BV2 Fuel valves Room thermostat 1 or time switch external ignition module Room thermostat 2 or time switch 4 modulated PWM fan Heating circuit pressure switch 6 Stepper motor control M (combustion optimization) DHW FlowSwitch or DHW thermostat Programmable digital input e.g. for air pressure switch Boiler flow sensor (tested) LMU75... Heating circuit pump DHW pump 1 or diverting valve Boiler return sensor (tested) Programmable output DHW sensor 1 or DHW thermostat 5 AGU ClipIn Water pressure sensor QAA55... QAA75... Outside sensor 2 / 3 Room controller HMI AVS37... Operator unit Reset button The diagram shows the full scope of functions offered by the LMU75 system. The actual functions are to be determined based on the respective execution / configuration. 17/18
18 Dimensions LMU7... Dimensions in mm ,5 24 max , O 3,5 (7 x) 7, , ,5 7495m01/ / Siemens AG, Berliner Ring 23, D Rastatt Subject to change!
Electronic Ignition Equipment
7 608 Electronic Ignition Equipment TQG3 The TQG3 consists of a cable for connection to the safety shutoff valves of the VGU gas valves and electronic ignition equipment for use on gas boilers with single-
More informationActuators for air dampers and control valves of oil burners
7 812 Actuators for air dampers and control valves of oil burners SQM1... SQM2... Reversible electromotoric actuators Torques: - SQM1... up to 10 Nm - SQM2... up to 20 Nm Running times: - SQM1... 14...100
More informationFor air dampers and control valves of oil or gas burners
7 813 Actuators For air dampers and control valves of oil or gas burners SQM33... Electromotoric actuators Torques: - SQM33.4 up to 1.2 Nm nominal output torque - SQM33.5 up to 3 Nm nominal output torque
More informationActuators. Building Technologies Division
7 802 Actuators SQ72 Electromotoric actuators for air dampers and control valves of oil or gas burners of small to medium capacity. The SQ72... and this Data Sheet are intended for use by OEs which integrate
More informationFor air / gas dampers and control valves of oil or gas burners
7 803 Actuators For air / gas dampers and control valves of oil or gas burners SQN13.xxxB9 SQN14.xxxB9 Electromotoric actuators Torque: Up to 1 Nm rated output torque Direction of rotation: - SQN13 Counterclockwise
More informationRVD G2383en. Installation. - Compact station - Control cabinet (in the front, on the inner wall or on a
4 319 2968 0 G2383en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD230 Installation Place of installation In a dry room, e.g. in the heat exchanger room
More informationActuators for air and gas dampers
7 814 Actuators for air and gas dampers SQM45... SQM48... Electromotoric actuators Torques: SQM45... up to 3 Nm SQM48... up to 20 Nm SQM48.6... up to 35 Nm Running times: 1) SQM45... 10... 120 s SQM48...
More informationActuators for Air and Gas Dampers
7 815 SQM5..., gear train side with drive shaft no. 7 SQM5..., rear, version without second drive shaft end SQM5..., rear, version with 2 drive shaft ends Actuators for Air and Gas Dampers with electronic
More informationS4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General
S4562C 1085 COMBI BOARD APPLICATION PRODUCT HANDBOOK The S4562C 1085 combi board is an integration of an on/off temperature control and an electronic ignition control. The S4562C 1085 combi board is intended
More informationG2515. Installation. Place of installation. Electrical installation. Permissible cable lengths. Securing the controller to the base
74 319 726 G2515 en Installation Instructions District heating controller for 2 heating circuits and d.h.w. RVD26 Keep these instructions with the controller! Installation Place of installation In a dry
More informationConnection Accessories for small Burner Controls
7 201 AGK11... plug-in base with AGK65... cable gland holder AGK11... plug-in base with AGK66 cable gland holder Connection Accessories for small Burner Controls AGK11... AGK65... AGK66 Accessories for
More informationActuators for Air and Gas Dampers
7 815 SQM5 gear side with drive shaft no. 7 SQM5 rear side, design without a second drive shaft end SQM5 rear side, design with 2 drive shaft ends Actuators for Air and Gas Dampers with electronic modules
More informationRVD110 RVD G2381en. Installation. Commissioning
4 319 2788 0 G2381en en Installation Instructions District heating and d.h.w. controller RVD110 RVD130 Installation Place of installation In a dry room, e.g. the heat exchanger room Mounting choices: -
More informationElectronic Ignition Module
7 607 Electronic Ignition Module TQO31A27 Electronic ignition module for use with oil or gas burners operating with singleor double-pole ignition. The TQO31A27 and this Data Sheet are intended for use
More informationRVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths
en Installation Instructions District heating and d.h.w. controller 74 39 68 G25 RVD2 RVD4 Keep these instructions with the controller! Installation Place of installation In a dry room, e.g. the heat exchanger
More informationRVD235. G2385en. Installation without base
2382Z04 G2385en en Installation Instructions District heating controller for one heating circuit and d.h.w. RVD235 Installation without base Place of installation Compact station front or control panel
More informationActuators for air dampers and control valves of oil burners
7 812 Actuators for air dampers and control valves of oil burners SQM1... SQM2... Reversible electromotoric actuators Torques: - SQM1... up to 10 Nm - SQM2... up to 20 Nm Running times: - SQM1... 14...100
More informationProportional controlling element
7 646 Proportional controlling element VKP... Proportional controlling element designed for fitting between counter-flanges, for integration into gas trains. Wide modulation range Flanged connections ½
More informationRVD125/109 RVD145/109
G2511 en Installation Instructions District heating and d.h.w. controller RVD125/109 RVD145/109 Installation without base Place of installation Compact station front or control panel front Permissible
More informationBurner Management System
7 550 Burner Management System LMV5... LMV50 LMV51 LMV52 Burner management system with integrated fuel / air ratio control and load control for use with forced draft burners. With specific functions for
More informationASZ... Potentiometers. Building Technologies Division. ASZxx.3x
7 921 ASZxx.7xx / ASZxx.8xx ASZxx.7xx / ASZxx.8xx ASZxx.9xx Potentiometers ASZ... For integration into SQM... and SQN... actuators to indicate the position of the actuator s drive shaft. Single and double
More informationActuators for air dampers and control valves of oil burners
7 812 ISO 9001 Actuators for air dampers and control valves of oil burners SQM1... SQM2... Reversible electromotoric actuators Torques: - SQM1... up to 10 Nm - SQM2... up to 20 Nm Run times: - SQM1...
More informationModels. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery
AC/DC Battery Controller Power Supply TSPC-240UPS Series Compact universal 24 VDC power supply with integrated battery controller module Battery protection for over voltage, deep discharge, short circuit
More informationG72x Series Direct Spark Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G72x Issue Date 1299 G72x Series Direct Spark Ignition Controls Figure 1: G72x Direct Spark Ignition
More informationActuators for Air and Gas Dampers
7 815 SQM5..., gear train side with drive shaft no. 7 SQM5..., rear, version without second drive shaft end SQM5..., rear, version with 2 drive shaft ends Actuators for Air and Gas Dampers with electronic
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationTemperature Controller (Heat Pumps)
3 345 Temperature Controller (Heat Pumps) For comfort control in HVAC systems RWD31 RWD41 Stand-alone electronic temperature controller Four 2-position (On/Off) outputs Easy adjustment of parameters via
More informationPME Program module for burner control LME73.000
Presentation example PME7... Presentation example LME7... PME73.831... Program module for burner control LME73.000 User Documentation Application: 1-stage or modulating, direct or pilot ignited forced
More informationPME Program module for burner control LME73.000
Presentation example PME7... Presentation example LME7... PME73.831... Program module for burner control LME73.000 User Documentation Application: - 1-stage or modulating, direct or pilot ignited forced
More informationVICTRIX PRO Wall-hung modular condensing boiler for heating only
PRO Wall-hung modular condensing boiler for heating only Wide range (5 models) High efficiency and low pollutant emissions thanks to condensing technology Modulating heat output from 10 to 100% Possible
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate Highly accurate measurements with calibration certificate Simple and quick
More informationVLF45... Hot Air Valves. Siemens Building Technologies HVAC Products
7 637 Hot Air Valves VLF45... Single valve for use in the supply air line of heat generating equipment Valves used in connection with SKP... actuators open slowly and close rapidly 2-port valves of the
More informationgimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy
GE Digital Energy Technical data sheet Uninterruptible Power Supply LP11 924 Series 6 & 10 kva gimagination at work GE T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www..com General data Topology VFI,
More informationElectronic Ballast EVG 2000-T
Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications
More informationTechnical Documentation
Technical Documentation Product manual Holding brake controller Document: 0198441113316 Edition: V1.00, 03.2006 Important information The drive systems described here are products for general use that
More informationR820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017
R80 REV SERIES SCR POWER CONTROLS NOVEMBER 017 Product overview The Viconics R80 series SCR power controls are designed for cost effective, precise modulation of electric loads for most electric heating
More informationDocument: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger
Document: PRODSPEC-140 Revision: G DCN No. 106512 Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger 1. GENERAL DESCRIPTION 1.1 General Description Fully regulated, constant voltage,
More informationG821L/G822L Series Integrated Function Direct Spark Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G821L/G822L Issue Date 1199 G821L/G822L Series Integrated Function Direct Spark Ignition Controls
More informationMODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM
MODULAR THREE-PHASE AND SINGLE-PHASE UPS SYSTEM PowerLine DPA 20 120 kva Full power for industrial applications PowerLine DPA 20 120 kva Full power for industrial applications 2 ABB UPS SYSTEMS POWERLINE
More informationGULLIVER BSD SERIES. Low NOx Two Stage Gas Burners FIRING RATES. BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw.
The Riello Gulliver BSD series of two stage gas burners, is a complete range of Low NOx emission products, developed to respond to any request for home heating, conforming to the most severe standards
More informationProduct Data Sheet 632 NU-006
The engineer's choice 632 NU-006 INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 3 3 Operating Data... 4 3.1 Operating Data - Electrical Interface - Input... 4 3.2 Electrical
More informationDifferential pressure sensor
s 1 916 QBM3x20-.. QBM3x20-..D Differential pressure sensor for air and non-aggressive gases QBM3020-.. QBM3120-.. High degree of measuring accuracy Adjustable characteristic curve (pressure-linear or
More informationNEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.
Datasheet Single- and three-phase switched-mode power supply units NEW The new power supplies offer a wide range of robust solutions for demanding application requirements. C SEMI F47 US Designed for high
More informationGULLIVER BS SERIES. Low NOx One Stage Gas Burners FIRING RATES. BS kw BS kw BS kw BS kw.
The Riello Gulliver BS series of one stage gas burners, is a complete range of Low NOx emission products, developed to respond to any request for home heating, conforming to the most severe standards regarding
More informationDX³ RCCBs - ID 4P up to 100 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationVQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION
VQ400M SERIES PRODUCT HANDBOOK APPLICATION The VQ400M Series class A safety combination valves are used for control and regulation of gaseous fluids in gas power burners, atmospheric gas boilers, melting
More information822 NOVAMIX GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE
SIT Group 822 NOVAMIX MULTIFUNCTIONAL GAS CONTROL GAS FLOW RATE ADJUSTMENT AS A FUNCTION OF THE AIR FLOW GAS/AIR RATIO 1:1 DOUBLE AUTOMATIC SOLENOID SHUT-OFF VALVE SERVO-CONTROLLED PRESSURE REGULATOR PIN
More informationINVERTER/CHARGERS Off-Grid Power Solutions
EVOLUTION SERIES INVERTER/CHARGERS Off-Grid Power Solutions REMOTE LOCATIONS RV/MARINE COMMERCIAL VEHICLES BACKUP POWER www.samlexamerica.com Do you need reliable AC power in a vehicle, remote location
More informationProduct Data Sheet 8412 NHU-519
The engineer's choice 8412 NHU-519 INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 3 3 Operating Data... 4 3.1 Operating Data - Electrical Interface - Input... 4 3.2 Electrical
More informationVTZ variable speed Reciprocating compressors
MAKING MODERN LIVING POSSIBLE Application guidelines VTZ variable speed Reciprocating compressors R404A, R507, R407C, R134a www.danfoss.com CONTENT VARIABLE SPEED COMPRESSORS... 4 Speed control...4 Advantages
More informationTechnical data sheets
GE Consumer & Industrial Power Protection Technical data sheets Digital Energy Uninterruptible Power Supply LP 11 Series / 3 5 6 8 10 kva A product by: GE Consumer & Industrial SA General Electric Company
More informationJUMO safetym TB/TW Temperature limiter, temperature monitor according DIN EN
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationAir damper actuators
4 654 OPEN AIR Air damper actuators Linear version, three-position control, AC 24 V or 230 V GDB..3..2 GLB..3..2 Electric motor-driven linear actuators for three-position control, nominal linear force
More informationDycon D2430 EN54-4 Fire Alarm Power Supply Series
Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product
More informationABB component drives ACS150, 0.5 to 5 Hp
ABB component drives ACS150, 0.5 to 5 Hp Technical Catalog BUSINESS PROFILE INDUSTRIES PRODUCTS APPLICATIONS EXPERTISE PARTNERS SERVICES Contents Choice 1: Simply contact your local ABB drives sales office
More informationProduct Data Sheet ACi 4420 HHR
ACi 4420 HHR INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 4 3 Operating Data... 5 3.1 Operating Data - Electrical Interface - Input... 5 3.2 Electrical Operating Data... 5
More informationTWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw
TWO STAGE GAS BURNER GULLIVER RSD SERIES 160/208 345 kw The Riello Gulliver is a new model of the series of two stage gas burners, characterized for its small dimensions in spite of its high combustion
More informationINSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS SD UK/IE (2010/04)
INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS 300 6720613720-00.1 SD UK/IE CONTENTS Contents Contents 2 1 Safety instructions and explanation of symbols 5 1.1 General safety instructions
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More informationSolenoid Operator 0516 / 1216
nass magnet GmbH Edition no. 2 Eckenerstraße 4-6 2007-01-10 D-30179 Hannover Rev.2 070110 Solenoid Operator 0516 / 1216 Operating Instructions NN 8220 126 and EC Declaration of Conformity Dear Customer!
More informationONE STAGE GAS BURNERS RDBS SERIES
ONE STAGE GAS BURNERS RDBS SERIES 16 47 kw RDBS.1 16 47 kw The Riello RDBS is a new series of one stage gas burners with integrated gas train, characterised by its small dimensions in spite of its high
More informationDifferential Pressure Sensors
1 910 1910P01 Differential Pressure Sensors for air or nonaggressive gases QBM66... Pressure-linear characteristic with selectable pressure measuring range Operating voltage AC 24 V or DC 13.5...33 V Output
More informationTechnical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality
GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino
More informationburners with or without fan. It conforms to EN C). APPROVAL EU type test approval as per EU Gas Appliance Directive.
LAST UPDATE 29/08/12 INSTALLATION INSTRUCTIONS v. 3 UNIT SPECIFICATIONS Main Gas Valve, Pilot Gas Valve Ionisation, Ignition and Flame Monitoring with Common Electrode or Remote Sensor Integrated Cyclic
More informationSingle & Three-Phase Soft Starters
Submittal Data English Language/IP Units 11/13 Contact Information: Hyper Engineering, Pty. Ltd. 9000 Conservation Way Fort Wayne, IN 46809 www.hypereng.com sales@hypereng.com (877) 304-0724 Model Nomenclature
More informationVSD Series II Variable Speed Micro Drives
VSD Series II Variable Speed Micro Drives Product Bulletin Code No. LIT-12011813 Issued March 26, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Johnson Controls VSD
More informationMINI-DC-UPS/24DC/2. Extract from the online catalog. Order No.:
Extract from the online catalog MINI-DC-UPS/24DC/2 Order No.: 2866640 Uninterruptible power supply with integrated power supply unit, 2 A, in combination with MINI-BAT/24/DC 0.8 AH or 1.3 AH Commercial
More informationUser Manual. Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5
More informationTX³ RCCBs 2P up to 100 A
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationSPARE PARTS EXPLODED VIEW COMMUNAL GAS BOILERS Model
SPARE PARTS EXPLODED VIEW COMMUNAL GAS BOILERS Model R 600 R8203221-04EN - Edition 04-19/01/2011 12082430 R601 ELCO STANDARD 04/08 12/10 12082507 R601 ELCO M. E8 HEIZKR.-REGLER 04/08 12/10 12082584 R601
More informationPower supply kit (70 W)
Cerberus FIT Power supply kit (70 W) FP120-Z1 This standalone power supply is intended for decentralized supply to external devices. FP120-Z1 has an integrated operating and fault indicator, and makes
More informationTWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw
TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO GS/M SERIES GS /M / 5 3/8 19 The Riello GS/M series of two stage progressive or modulating gas burners, is a complete range of products developed
More informationDifferential Pressure Sensors
1 910 1910P01 Differential Pressure Sensors for air or nonaggressive gases QBM66... Pressure-linear characteristic with selectable pressure measuring range Operating voltage AC 24 V or DC 13.5...33 V Output
More informationApplication. Battery. Public Grid GS HYBRID INVERTER
GS HYBRID SOLAR INVERTER Feed from Solar and Power, Grid backup, Build-in Transfer Switch / Solar Charger/ AC Charger, 500W~3kW, Pure Sine Wave Output GSH-15XX and GSH-30XX are the ideal solutions for
More informationE Series CE Approved Intermittent Pilot Ignition Control
Installation Instructions Issue Date January 11, 2013 E Series CE Approved Intermittent Pilot Ignition Control Application The E Series CE Approved Intermittent Pilot Ignition Control is a safety control
More informationHoneywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION
Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION The VV Series class A vent valves are intended to be used in combination with the VQ400M series combination valve.
More informationJUMO dtrans p35. Pressure Sensor with IO-Link. Application. Brief description. Customer benefits. Special features
sales@jumo.co.uk info.us@jumo.net Page 1/10 JUMO dtrns p5 Pressure Sensor with IO-Link pplication Process automation Machines for the food and beverage industry General mechanical and apparatus engineering
More informationProduct Data Sheet 4184 N/17X. The engineer's choice
Product Data Sheet 4184 N/17X The engineer's choice 4184 N/17X INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 3 3 Operating Data... 4 3.1 Electrical Operating Data... 4 3.2 Electrical
More informationLOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw
LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES 1/19 5 kw 35/4 91 kw 5/75 19 kw 11/14 4 kw The Riello Gulliver BSD series of two stage gas burners, is a complete range of Low NOx emission products, developed
More informationEPS/ELA-Series User Manual EPS/ELA 250W
EPS/ELA-Series User Manual EPS/ELA 250W EPS Stromversorgung GmbH Tel: +49 (0)821 570451 0 Index 3 Page: 1 Table of contents: Page 1. Features of ELA-Series... 3 1.1 Basic Functions... 3 1.2 Options...
More informationDEVICE STATE/BYPASSED FAILURE OVERLOAD
Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated
More informationABB i-bus EIB EIB Power Supply Units SV/S SV/S SU/S
Product Manual ABB i-bus EIB EIB Power Supply Units SV/S 30.320.5 SV/S 30.640.5 SU/S 30.640. Intelligent Installation Systems Contents Page EIB Power Supply Units. Introduction.........................................
More informationTechnical Data Sheets
GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01
More informationSwitchmode rectifier type. Type UP phase. »We store the world's energy« Network
Type UP 610 3-phase»We store the world's energy« > Two level charging Suits all types of batteries, Shorter recharge time. > Excellent load and line regulation Increased battery lifetime. > High efficiency
More informationControl Solutions Biofloor
MCF234 Distributor for Wired Control System COMAP proposes a new control system for heating and cooling underfloor. Consisting of a 6 or 10- channels controller (MCF234), analogic (TAF234) or electronic
More informationControl Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD
Bulletin Product Selection Open Type and Non-Combination Enclosed (IP, NEMA /) Controllers For use with Line-Connected Motors Rated Voltage [V AC] / Motor Current [A]...... Max. kw, Hz Max. Hp, Hz Control
More informationJ TS 7090 Thyristor power switch
M. K. JUCHHEIM GmbH & Co Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
More informationHamilton 3VO Submittal
Job RESET FORM Engineer Hamilton 3VO Submittal BOILER s H3H 750 WATER HEATER s H3D 750 Contractor Prepared By Date Input 100% factory fire tested Efficiency: up to 99.8% (based on incoming water) Maximum
More informationSKPx5... Actuators for Gas Valves. Building Technologies HVAC Products SKP15... SKP25... / SKL25 SKP55... SKP75...
7 643 SKP15... SKP25... / SKL25 SKP55... SKP75... Actuators for Gas Valves SKPx5... SKL25 ON / OFF safety shutoff feature conforming to EN 161 in connection with SKPx5 actuators and gas valves from Siemens
More informationSQN9... Damper Actuators. Building Technologies HVAC Products. SQN9..., front (covers removed) SQN9..., rear (covers fitted)
7 806 SQN9..., front (covers removed) Damper Actuators SQN9..., rear (covers fitted) SQN9... Reversible electromotoric actuators for air dampers and valves of oil or gas burners of small to medium capacity.
More informationABB Component Drives ACS150, 0.5 to 5 Hp
ABB Component Drives ACS150, 0.5 to 5 Hp Technical Catalog BUSINESS PROFILE INDUSTRIES PRODUCTS APPLICATIONS EXPERTISE PARTNERS SERVICES Contents Choice 1: Simply contact your local ABB drives sales office
More informationProduct Data Sheet ACi 4420 MLR
ACi 4420 MLR INDEX 1 General... 3 2 Mechanics... 3 2.1 General... 3 2.2 Connections... 4 3 Operating Data... 5 3.1 Operating Data - Electrical Interface - Input... 5 3.2 Electrical Operating Data... 5
More informationOff-Grid Power Solutions EVOLUTION SERIES INVERTER/CHARGERS COMMERCIAL VEHICLES BACKUP POWER
Off-Grid Power Solutions EVOLUTION SERIES INVERTER/CHARGERS REMOTE LOCATIONS COMMERCIAL VEHICLES RV/MARINE BACKUP POWER Do you need reliable AC power in a vehicle, remote location or for emergency backup?
More informationavailable in battery up to 4 units for a total of 560 kw
MODULATING CONDENSING BOILER with double premix low NOx burner and double heat exchanger EXPANDABLE IN BATTERY for indoor and outdoor installations (IPX5D) OUTPUT RANGE from 10 to 560 kw (in battery) WORKING
More informationSolenoid Operator 0513 / 1213
nass magnet GmbH Run Nr. 5 Eckenerstraße 4-6 24.10.2006 D-30179 Hannover Rev. 5 061024 Solenoid Operator 0513 / 1213 Operating Instructions NN 8220 112 and EC Declaration of Conformity Dear Customer! In
More informationSafety Standards. Model Number:
Highlights & Features RoHS Compliant Relay alarm indirection Built-in 2 channel DC OK signal Caused by rugged handing Conformal coating on PCBA to protect against chemical and dust pollutants Class I,
More informationc-go 24V/6A 24V/8A 24V/12A
c-go 24V/6A 24V/8A 24V/12A Battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Quick start guide... 4 4. Operation... 4 5. Problem solving... 6 6. Specifications...
More informationSPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model ACO. R EN - Edition 04-01/04/2008
SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model ACO R8215222-04EN - Edition 04-01/04/2008 Domestic Gas Boilers ACO 537060 ACO 27 MFFI MET...... 537061 ACO 27 MFFI GPL...... 537062 ACO 27 RFFI SYSTEM MET......
More information27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2