G821L/G822L Series Integrated Function Direct Spark Ignition Controls

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "G821L/G822L Series Integrated Function Direct Spark Ignition Controls"

Transcription

1 Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin G821L/G822L Issue Date 1199 G821L/G822L Series Integrated Function Direct Spark Ignition Controls Figure 1: G821L/G822L Integrated Function Direct Spark Ignition Control Description The CE compliant G821L/G822L is a microprocessor-based, 100% shutoff, direct spark, and remote flame sense, integrated function ignition control. The control responds to inputs from the thermostat, high limit switch, rollout sensor, pressure switch, and flame sensor. It provides outputs for timing and sequencing of the main gas valve, induced draft motor, circulator/blower, and spark igniter. The G821L/G822L utilizes quick-connect terminals for all off board connections, except thermostat inputs and spark output. The thermostat inputs are connected to a terminal strip with screw terminals and the spark output is connected by a rajah, spike, or 6.35 mm (1/4 in.) male tab-type spark connector. The G821L control is a heating only integrated ignition control, and the G822L control is a heating and cooling integrated ignition control Johnson Controls, Inc. 1 Part , Rev. Code. LIT

2 Table 1: Specifications Ignition Type Ignition Source Direct Spark High voltage spark, capacitive discharge High Voltage Cable Wire: Stranded Insulation: Minimum Insulation Temperature Rating: Termination: Maximum Cable Length: Flame Sense Cable Wire: Stranded Flame Detection Means Flame Detection Types Minimum Flame Current Flame Threshold Current (I TH) Insufficient Flame Marginal Flame Good Flame Flame Failure Response Time Spark Gap Ignition Retrials 4 Safety Time Prepurge Time Postpurge Time Purge Time Loss of Flame Signal Retrials Circulator/Blower Times Power Requirements Contact Rating Minimum Insulation Temperature Rating: Maximum Cable Length: Flame rectification Remote sensing microampere microampere ± 25% Flame current <I TH I TH < flame current <4 x I TH Flame current >4 x I TH 1 second maximum 3.17 mm (0.125 in.) nominal 11 seconds* 10 seconds* 45 seconds* 10 seconds* 4 (five total ignition attempts) On Delay 30 seconds* Line Voltage: Control: Operation Current: Main Valve: Inducer: Blower: 25 kvdc minimum rating. 150 C (302 F) or suitable for the application, whichever is higher. Appropriately insulated connector to mate with the chosen transformer option. 1,220 mm (48 in.) 150 C (302 F) or suitable for the application, whichever is higher. 1,220 mm (48 in.) Off Delay 90, 120, 180, or 240 seconds heating* 45 seconds cooling* 120/230 VAC, 50 Hz 24 VAC, 50 Hz, nominal 24 VAC 2A 24 VAC, 5A inrush 1A continuous, 240 VAC 3/4 hp, 5A continuous, 15A inrush, 240 VAC External Power Transformer Kema Keur certified to EN Secondary voltage 24 VAC nominal, 50 Hz Ambient Operating and Storage -40 to 70 C (-40 to 160 F) Temperature Humidity 95% RH non-condensing Wiring Connections Spark Options: Spike, Rajah, or 6.35 mm (1/4 in.) male spade Types of Gas Natural, Liquefied Petroleum (LP), manufactured, mixed, or LP gas-air mixture Continued on next page... *Timings listed are for 50 Hz operation. 2 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

3 Specifications (Cont.) Packaging Bulk pack supplied to original equipment manufacturer (individual pack optional). Bulk Pack Quantity 24 Bulk Pack Weight Agency Listing 8 kg (18 lb) EC Certification Number E3731 Specification Standards EN 298 Standards Complying with the EMC Directive Classification Code FMCVXN Enclosure Degree of Protection IP00 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 3

4 Application Requirements Operating Mode Definitions Following are the application requirements of the G821L/G822L control. The G821L/G822L can be used on gas-fired equipment with a maximum firing rate of 117 kw (400,000 Btu/hr). Any applications greater than 117 kw (400,000 Btu/hr) must have written approval in advance from the Heating Products Engineering Department. All G821L/G822L applications must use a redundant gas valve system with the main valve seats in series. The pressure switch must carry main valve current for redundancy. All G821L/G822L controls have volatile lockout. The following definitions describe operating conditions: Start Signal--The signal from a thermostat that begins the ignition program. Purge--The forced introduction of air through the combustion chamber and flue passages to displace any unburned gas and/or products of combustion. Prepurge--The purge that takes place between the start signal and the energization of the gas valve and ignition device. Prepurge Time--The period during which purge occurs at the proven air rate prior to the energization of the gas valve and ignition device. Safety Time--The time between energizing the main gas valve and de-energizing the main gas valve if the flame signal is not detected. Running Position--The main valve remains energized and the spark is de-energized. The appliance is in normal operation under the supervision of the ignition control and its flame detector device. Retrial--Failing an ignition attempt, the control enters a purge period and than starts another safety time. Recycling--The process of automatically repeating a startup sequence, (beginning with prepurge), after a safety shutdown (removing the power to the gas valve and igniter). Startup Sequence--The sequence of actions executed by the system that brings the burner from the start to the running position. Circulator/Blower On Delay --Fixed time delay after the flame signal is sensed until the circulator/blower is energized. Circulator/Blower Off Delay --Field selectable time delay after the thermostat contacts open when the circulator/blower remains energized. Postpurge--Time delay after successful running position period when the inducer remains energized. Volatile Lockout--The safety shutdown of the system where a startup sequence can only begin after the main power is cycled. 4 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

5 rmal Sequence of Operation Call for Heat Call for Cool Call for Manual Fan Figure 2 illustrates the sequence of operation of the G821L/G822L control. The G821L/G822L control is energized upon receiving a start signal from the system thermostat. 1. Pressure Switch Detection--The control checks the inducer pressure switch to ensure that it is open. 2. Prepurge--The control energizes the inducer motor and verifies that the pressure switch closes. The control delays for the prepurge time before continuing to the safety time. 3. Safety Time--The control simultaneously energizes the spark igniter and gas valve in an attempt to light the main burner. During the safety time, the igniter is energized until a flame signal is detected or until the safety time is complete, whichever occurs first. 4. Running Position--If main burner flame is sensed anytime during the safety time, the gas valve and inducer remain energized for the duration of the start signal. The circulator/blower is energized after the blower on delay time and remains energized for the duration of the heat call. 5. Postpurge--Once the start signal is removed, the gas valve is de-energized and the inducer remains energized until the postpurge period ends. The circulator/blower remains energized until the selected blower off delay time has elapsed. Upon receiving a start signal for cool from the system thermostat, the control energizes the blower motor at cooling speed. Once the signal is removed, the control waits for the cool fan off delay to expire before de-energizing the blower motor. Upon receiving a start signal for continuous manual fan, the control energizes the circulator/blower motor at heating fan speed. The continuous fan on request is immediately overridden by a signal for heat. G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 5

6 Start signal for cool Start Start signal for manual fan (G) Flame present when not expected Run - manual fan speed Detected Fault Run - Cool fan speed Start signal for heat Flame signal present for 10 seconds? Volatile Lockout (LED will blink with a flash code of 5) Thermostat satisfied? Cool fan blower off delay Pressure switch open? Inducer on Volatile lockout! WARNING: Personal Injury Hazard. Avoid personal injury. The ignition control has volatile lockout. The control restarts operation if the main power is cycled. End Pressure switch closed? Prepurge Maximum number of retrials attemped? Safety time Fifth loss of flame signal? Flame signal sensed? Cirulator/Blower on delay Running position Loss of flame signal? Purge Thermostat satisfied? Postpurge Circulator/Blower off delay End Figure 2: G821L/G822L Sequence of Operation 6 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

7 Abnormal System Operation Pressure Switch Detection Undesired Flame The G821L/G822L offers the following responses based on abnormal system operation. A pressure switch within the appliance provides proof of combustion air flow. During a heating cycle, the control responds to the state of this switch in the following ways: At the beginning of the start signal, if the pressure switch is not open before the inducer is energized, the control will wait for the switch to open for as long as the heat start signal is present. The Light-Emitting Diode (LED) will blink with a flash code of 3 while waiting for the pressure switch to open. If the pressure switch does not close after the inducer has been energized for 5 seconds, the control will keep the inducer energized and the LED will blink with a flash code of 3 until the pressure switch closes or the heat start signal is removed. If the pressure switch opens any time after the control has begun the safety time, the control will immediately de-energize the gas valve. If the pressure switch fault occurs after the flame signal is sensed, the circulator/blower will run for 90 seconds, the inducer motor will remain energized, and the control will go into the Pressure Switch Open Fault state. During this time, the LED will blink with a flash code of 3. As long as the heat start signal is still present, the control will continue to wait for the pressure switch to close before resuming the heating cycle. If the pressure switch fails three times with no more than 30 seconds between successive faults, the control will de-energize all outputs, the LED will blink with a flash code of 3, and will remain in this state until the control power is recycled before returning to normal operation. If the flame signal is present at power up or when it should not be, the control energizes the inducer and circulator/blower and allows the flame 10 seconds to extinguish. If the flame signal is removed within 10 seconds, the normal sequence of operation continues. If the flame signal is still present after 10 seconds, the control goes into volatile lockout. During the volatile lockout, the inducer motor and the circulator/blower remain energized and the main valve is de-energized. The LED flashes with a duty cycle of 1/2 second On, 1/2 second Off for five flashes with a longer Off time before repeating the series. The control remains in volatile lockout until the power is recycled. G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 7

8 Failure to Sense Flame Signal within Safety Time Loss of Flame Signal Interrupted Thermostat High Limit Switch If a flame signal is not sensed by the end of the safety time, the gas valve is de-energized, the inducer remains energized throughout the 10-second purge period, and another safety time begins. If the flame signal is not sensed by the end of the maximum number of safety times, in any given start signal, the control enters volatile lockout. The control remains in volatile lockout until the power is recycled. If the main burner flame is established and then lost, the gas valve is de-energized and the inducer and circulator/blower run through the purge period. Once the purge period expires, the control initiates another safety time. After the fifth loss of flame signal in any given start signal, the control will go into volatile lockout. The control remains in volatile lockout until the power is recycled. The G821L/G822L offers the following responses to the two possible interrupted thermostat situations: If the start signal for heat is removed before flame is sensed, the control will de-energize all outputs and return to the Off state. If the start signal for heat is removed any time after flame is sensed, the gas valve and spark igniter (if energized) are de-energized, the inducer motor remains energized through the postpurge period, and the circulator/blower remains energized for the selected blower off delay time. The high limit switch is monitored whenever a start signal for heat is present. Any time the switch opens, the gas valve and igniter are de-energized, and the inducer and circulator/blower run continuously. When the switch is reset, the inducer and circulator/blower run for 180 seconds (the control LED will blink with a flash code of 4) before the control returns to normal operation. Whenever the high limit switch is open while the start signal for heat is present, the control LED will blink with a flash code of 4. IMPORTANT: The G821L/G822L ignition control does not respond to a high limit fault with non-volatile lockout. Therefore, a manually resettable high limit switch must be used with this control to meet European agency operating requirements. 8 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

9 Control Timings Figure 3 illustrates the control s timings. rmal Heating Cycle LNE P T P1 T S T BON T R T P3 T BOFF Multiple Trials LNE P T BON T BOFF T P1 T S T P2 T S T R T P3 Loss of Flame Signal LNE P T BON T BOFF T P1 T S T R T P2 T S T R T P3 LNE P - Power - Thermostat - Inducer - Pressure Switch - Gas Valve - Spark Ignition - Main Blower Legend T P1 T S T BON T R T P2 T BOFF T P3 - Prepurge Time - Safety Time - Blower On-delay Time (Warm Up) - Running Position Time - Interpurge Time - Blower Off-delay Time (Cool Down) - Postpurge Time Figure 3: Timing Charts G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 9

10 Installation and Wiring IMPORTANT: This technical bulletin is intended as a guide for qualified personnel installing or servicing Johnson Controls products. Carefully follow all instructions in this bulletin and all instruction on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this bulletin or on the appliance.! WARNING: Fire or Explosion Hazard. Avoid serious injury by carefully following precautions in this bulletin and all instructions on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this bulletin or on the appliance.! WARNING: Fire or Explosion Hazard. If the control is installed in an area that is exposed to water (dripping, spraying, rain, etc.), it must be protected. If the control has been exposed to water in any way, do not use it. Location and Mounting! WARNING: Shock Hazard. Avoid electrical shock and equipment damage. Disconnect the electrical power and turn off the gas before wiring the control into the circuit.! CAUTION: Equipment Damage Hazard. Do not mount the control where it will be exposed to direct infrared radiation from the main burner or to temperatures in excess of the maximum product temperature rating. Choose a location that provides the shortest, direct cable route to the spark igniter and flame sensor. Easy access to the terminals is desired for wiring and servicing. The control may be mounted in any position. Mount the control on a grounded metal surface with metal screws or bolts through the mounting holes provided on the control. 10 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

11 Electrical Connections! CAUTION: Equipment Damage Hazard. Connect the high voltage cable to the spark transformer terminal and spark igniter before applying power to the control. IMPORTANT: The G821L/G822L ignition control does not respond to a high limit fault with non-volatile lockout. Therefore, a manually resettable high limit switch must be used with this control to meet European agency operating requirements. Check the voltage rating marked on the control and ensure it is suited to the application. Use a transformer capable of providing 24 VAC under maximum load, including the valve. A transformer having excessive primary impedance due to poor coupling will affect the ignition potential. te: The transformer must be a safety insulating transformer tested to EN60742 or equivalent, and it must be installed and protected according to the manufacturer s specifications. Refer to Figure 4 for wiring diagram. All wiring should be in accordance with local codes and regulations. The high voltage spark transformer cable must not be in continuous contact with a metal surface. Use standoff insulators. Ensure that the flame sensor wire and high voltage spark transformer cable are separated from one another by a minimum distance of 6.35 mm (1/4 in.) and are not wrapped around any pipe, other wiring, or accessories. The thermostat wires must be cabled to prevent possible contact with a line voltage terminal. tes: This unit should be used only in applications that are within the limitations and provisions of the applicable European Union standards. These designs are tested to EN 298 Automatic Ignition Systems standards. Circulator/Blower Off Delay The circulator/blower off delay for heating is field selectable. To set the desired off delay, position the switches on Switch Block 1 (SW1) as presented in Table 2. (Refer to Figure 4 for SW1 location.) Table 2: Circulator/Blower Off Delay Switch Positions 1 2 Delay Off Off 90 seconds Off On 120 seconds On Off 180 seconds On On 240 seconds G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 11

12 Sensor Pressure Switch High Limit Switch Rollout Switch 24 VAC Hot Ground Flame Sense PSW High Limit In High Limit Out Rollout In Valve Spark Transformer ACB Heat CMB Blower Line VAC Hot 4.76 mm (3/16 in.) Terminal Blower Off Delay Setting W G R te: All terminals are 6.35 mm (1/4 in.) unless otherwise specified. Pressure switch must carry main valve current for redundancy. Thermostat Transformer 24 VAC Line Line L1 120 VAC or 230 VAC 24 VAC ACC 1 2 Flame Sense Spark Electrode O N 4.76 mm (3/16 in.) Terminal SW1 24 VAC Common L2 Line Neutral Redundant Main Valve Coils Circulator/Blower Motor Inducer Motor IMPORTANT: The ignition control does not respond to a high limit fault with non-volatile lockout. Therfore, a manually resettable high limit switch must be used with this control to meet European agency operating requirements. 2.5 Ampere Fuse Figure 4: G821L/G822L Wiring Diagram 12 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

13 Checkout and Startup Procedures! WARNING: Fire or Explosion Hazard. Avoid personal injury or property damage by making sure the control functions properly and there are no gas leaks. Follow this checkout and startup procedure before leaving the installation. Make sure all components function properly by performing the following shutoff test: 1. With the gas and thermostat off, turn on power to the appliance. 2. Turn on the thermostat to the highest setting and verify that the control goes through the operating sequence to a shutoff condition. te: The burner will not light because the gas is off. 3. Turn off the thermostat. 4. Turn on the gas and purge gas lines of all air. 5. Check for gas leaks on all pipe joints upstream of the gas valve with a soap solution. 6. Turn on the thermostat to the highest setting and verify successful ignition and a normal running position for at least three minutes. 7. Check for gas leaks on all pipe joints downstream of the gas valve with a soap solution. 8. Turn the thermostat down for at least 30 seconds, and then back up again. Verify successful ignition at least three times. te: The control will complete the blower off delay (90, 120, 180, or 240 seconds) before initiating another heating cycle. 9. Return the thermostat to a normal temperature setting before leaving the installation. G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 13

14 Thermostat Heat Anticipator Settings The thermostat anticipator setting is normally equal to the ignition system current draw, plus that of the main valve. Due to variations in appliance wiring and valves, it is advisable to measure the actual current draw of the heating system at the thermostat location. Measuring this current can be accomplished by opening the thermostat contacts (lowering the setpoint) and installing an AC ammeter across the terminals, or by using a clamp-on ammeter with a 10-turn multiplier attached to the terminals. See Figure 5. IMPORTANT: Measuring the current with an ammeter will energize the system. Wait until the appliance is in the running position before taking a current draw measurement. To Heating System W R AC Ammeter Low Scale Setting To Heating System W R Ten Turns Clamp-on Ammeter (Divide reading by ten.) Figure 5: Measuring the Thermostat Current 14 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

15 Service Procedures If the system does not function properly, check the following: Are all mechanical and electrical connections tight? Is the system wired correctly? Is gas inlet pressure per manufacturer s specifications? Is the system powered? Is there a start signal for heat from the thermostat? Flash Codes Table 3: LED Flash Code Summary Flash Code Flash Code Description Slow Flash Fast Flash Flash Three Flash Four Flash Five Steady On rmal operation, no call for heat rmal operation, call for heat Pressure switch open or closed fault High limit or rollout switch open Flame sensed when not expected Internal failure (microcontroller self-check failure) Repairs and Replacement! CAUTION: Equipment Damage Hazard. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. The G821L/G822L controls are not field repairable. Do not attempt field repairs to the ignition control. Use only an exact or recommended replacement control. For a replacement control or accessories, contact the original equipment manufacturer or the nearest Johnson Control distributor. G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin 15

16 tes Controls Group E. Michigan Street FAN 121 P.O. Box 423 Installation Sheets Manual Milwaukee, WI Printed in U.S.A. 16 G G821L/G822L Series Integrated Function Direct Spark Ignition Controls Technical Bulletin

G600 Series Replacement Intermittent Pilot Ignition Controls

G600 Series Replacement Intermittent Pilot Ignition Controls Installation Instructions G600 Issue Date 0601 G600 Series ment Intermittent Pilot Ignition Controls Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

BG1600M Intermittent Pilot Ignition Control

BG1600M Intermittent Pilot Ignition Control Installation Instructions Issue Date March, 00 BG600M Intermittent Pilot Ignition Control Application The BG600M Intermittent Pilot Ignition Control is a safety control designed for indirect burner ignition

More information

ORDERING INFORMATION SPECIFICATIONS APPLICATION

ORDERING INFORMATION SPECIFICATIONS APPLICATION ORDERING INFORMATION UNIVERSAL MODELS The ordering part number for the universal model is 82UNIVERSAL. The 82UNIVERSAL comes with remote flame sense active. For internal flame sense, the supplied universal

More information

S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K Intermittent Pilot Gas Ignition Control

S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K Intermittent Pilot Gas Ignition Control S8600B,C,H,M; S8610B,C,H,M; S8670D,E,J,K Intermittent Pilot Gas Ignition Control APPLICATION The 8600 family of ignition controls provide ignition sequence, flame monitoring safety shutoff for intermittent

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

BGD258 Series BASOTROL CE Approved Class A Gas Valve

BGD258 Series BASOTROL CE Approved Class A Gas Valve Product Bulletin Issue Date May 21, 2010 BGD258 Series BASOTROL CE Approved Class A Gas Valve The BGD258 Series multi-function gas control valve works in conjunction with an electronic sequence control

More information

H15 Series BASO Automatic Shutoff Pilot Gas Valve

H15 Series BASO Automatic Shutoff Pilot Gas Valve Bulletin Issue Date June 5, 2017 H15 Series BASO Automatic Shutoff Pilot Gas The H15 Series pilot valves provide safe lighting and complete shutoff of pilot and main burner gas in the event that the flame

More information

First Correlating Revision No. 1-NFPA [ Section No ]

First Correlating Revision No. 1-NFPA [ Section No ] First Correlating Revision No. 1-NFPA 85-2013 [ Section No. 3.3.52.1 ] 3.3.52.1 Booster Fan. A device fan used to assist in the supply of air to, or the removal of flue gas products from, the combustion

More information

Primary Controls. Chapter 11. Introduction. Functions of the primary control

Primary Controls. Chapter 11. Introduction. Functions of the primary control Chapter 11 Introduction The safe, automatic operation of an oilheat system is dependent on the interaction between: The thermostat, which opens and closes a circuit based on temperature changes in the

More information

AV-8020 Series Floating Control Actuated Valve

AV-8020 Series Floating Control Actuated Valve FANs 977, 1628.3 Product/Technical Bulletin AV-8020 Issue Date 0300 AV-8020 Series Floating Control Actuated Valve The AV-8020 is an electric actuator/brass valve combination that furnishes floating control

More information

CSD Series Current Devices Split Core

CSD Series Current Devices Split Core CSD Series Current Devices Split Core Installation Instructions CSD-CF0A0-1 CSD-CF0J0-1 CSD-CA1G0-1 Part. 24-10345-34, Rev. D Issued March 31, 2014 Supersedes April 5, 2013 Applications The Current Switch

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481038 Model PVF and PVG Indirect Gas-Fired Heat Modules Indirect Gas-Fired Furnaces Installation, Operation and Maintenance Manual Please read and save these instructions for future reference.

More information

Installation- and maintenance instruction BENTOFLEX ST120KAV

Installation- and maintenance instruction BENTOFLEX ST120KAV Installation- and maintenance instruction BENTOFLEX ST120KAV 1 171 625 61 05-01 178 001 16 DESCRIPTION COMPONENTS 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw

TWO STAGE GAS BURNER GULLIVER RSD SERIES RS5D 160/ kw TWO STAGE GAS BURNER GULLIVER RSD SERIES 160/208 345 kw The Riello Gulliver is a new model of the series of two stage gas burners, characterized for its small dimensions in spite of its high combustion

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

VA-7150 Electric Valve Actuator. Features and Benefits. G 500N force output in a compact unit G Magnetic clutch. G Unique Yoke Design

VA-7150 Electric Valve Actuator. Features and Benefits. G 500N force output in a compact unit G Magnetic clutch. G Unique Yoke Design VA-7150 Electric Valve Actuator European Electronic Controls Catalogue Section E Product Bulletin VA-7150 Issue Date 03 2000 I ntroduction The VA-7150 series synchronous motor driven actuator provides

More information

G23 Bulletin # September 1998 Supersedes June 1995

G23 Bulletin # September 1998 Supersedes June 1995 ENGINEERING DATA ELITE 80Z UP-FLOW GAS FURNACES *80.0% to 80.8% A.F.U.E. 50,000 to 150,000 Btuh (14.7 to 44.0 kw) Gas Heating Input 1 thru 6 Tons (3.5 thru 21.1 kw) Nominal Add-On Cooling *Isolated Combustion

More information

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures A419 Issue Date February 10, 2003 A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures The A419 series controls are single-stage, electronic temperature

More information

GeniSys 24V. Model Advanced 24 Vdc Burner Control. Description / Applications

GeniSys 24V. Model Advanced 24 Vdc Burner Control. Description / Applications PARTS & ACCESSORIES GeniSys 24V Model 7559 Advanced 24 Vdc Burner Control Description / Applications The Beckett GeniSys TM 24V Advanced Burner Control is a 24 Vdc primary safety control for oil burners

More information

VSD Series II Variable Speed Micro Drives

VSD Series II Variable Speed Micro Drives VSD Series II Variable Speed Micro Drives Product Bulletin Code No. LIT-12011813 Issued March 26, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Johnson Controls VSD

More information

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw

ONE STAGE GAS BURNER GULLIVER RSF SERIES RS5F kw ONE STAGE GAS BURNER GULLIVER RSF SERIES 160 330 kw The Riello Gulliver, is a new model of the series of one stage gas burners, developed to respond to any request for light industrial processes like bakery

More information

TM-9100 Series Room Command Module

TM-9100 Series Room Command Module FANs 216, 1628.3 Product/Technical Bulletin TM-9100 Issue Date 0400 TM-9100 Series Room Command Module The TM-9100 Series Room Command Modules are designed for use with the TC-9100 series of DDC (Direct

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators VA9104-xGA-1S ii01.cdr VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators Installation Instructions Part No. 14-1336-7, Rev. B Issued December 28, 2007 Supersedes April 12, 2006 Applications

More information

Installation- and maintenance instruction B20KA/K

Installation- and maintenance instruction B20KA/K Installation- and maintenance instruction B20KA/K 1 171 615 27 05-01 178 091 07 DESCRIPTION COMPONENTS 1. Air intake 2. Scale, nozzle assembly 3. Nozzle assembly adjustment 4. Test nipple 5. Ignition cables

More information

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

VA2202-xxx-2 Series Electric Spring Return Valve Actuators VA222-xxx-2 Series Electric Spring Return Valve Actuators Product Bulletin Code No. LIT-26 Issued March 25, 28 Supersedes March, 26 VA222 Series Spring Return Electric Valve Actuators are available in

More information

36C and 36D Gas Control Product Information

36C and 36D Gas Control Product Information 6C and 6D Gas Control Product Information The 6C and 6D combination gas control valves are compact multifunction controls designed to meet requirements for use with Standing Pilot systems and all types

More information

RESIDENTIAL ELECTRONIC IGNITION SYSTEMS

RESIDENTIAL ELECTRONIC IGNITION SYSTEMS Service Application Manual SAM Chapter 630-153 Section 12 RESIDENTIAL ELECTRONIC IGNITION SYSTEMS by Marcus G. Metoyer, Jr., CMS INTRODUCTION The information contained in this publication is generic in

More information

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation Instructions M9206-Bxx-2S Issue Date May 14, 2003 M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation IMPORTANT: Use this M9206-Bxx-2S Series actuator to control equipment

More information

Phoenix Inverter

Phoenix Inverter Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC

More information

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw

LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES BS1D 16/19 52 kw BS2D 35/40 91 kw BS3D 65/ kw BS4D 110/ kw LOW NOx TWO STAGE GAS BURNERS GULLIVER BSD SERIES 1/19 5 kw 35/4 91 kw 5/75 19 kw 11/14 4 kw The Riello Gulliver BSD series of two stage gas burners, is a complete range of Low NOx emission products, developed

More information

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors

Q345A, Q3451, Q3481, Q348A, Q348B, Q362A, Q373A, Q381A and Q3452 Intermittent Pilot Burner/Igniter-Sensors QA, Q, Q8, Q8A, Q8B, Q6A, QA, Q8A and Q Intermittent Pilot Burner/Igniter-Sensors FEATURES PRODUCT DATA QA Q,Q8 Q8A,B Q6A QA QA, Q8A, Q8B and QA Intermittent Pilot Burner/Igniter-Sensors are compatible

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8120A & 8126A Digital Ventilation Controller Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Safety Instructions... 3 Specifications... 4 Overview... 4 Mounting

More information

SDS Enclosed Star-Delta Starter User Guide

SDS Enclosed Star-Delta Starter User Guide SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING

More information

RIELLO 40 GS SERIES. One Stage Gas Burners FIRING RATES. S kw S kw S kw S kw

RIELLO 40 GS SERIES. One Stage Gas Burners FIRING RATES. S kw S kw S kw S kw The Riello 40 GS series of one stage gas burners, is a complete range of products developed to respond to any request for home heating. The Riello 40 GS series is available in four different models, with

More information

ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER

ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER SPECIFICATIONS: *Photo for reference only* Part number 8890439 Mode Select: Selects Battery Type Refer to Section 6. IMPORTANT: READ

More information

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER 5500 COMBUSTION SAFETY CONTROL INSTALLATION MANUAL FOR 5500 COMBUSTION SAFETY CONTROLLER WARNING This manual must be read in its entirety before installation of this controller. Installation must be performed

More information

Single & Three-Phase Soft Starters

Single & Three-Phase Soft Starters Submittal Data English Language/IP Units 11/13 Contact Information: Hyper Engineering, Pty. Ltd. 9000 Conservation Way Fort Wayne, IN 46809 www.hypereng.com sales@hypereng.com (877) 304-0724 Model Nomenclature

More information

Introduction. Series P100. Encapsulated Pressure Control. Auto-reset Standard Duty and Heavy Duty. Manual reset Standard Duty. Feature and Benefits

Introduction. Series P100. Encapsulated Pressure Control. Auto-reset Standard Duty and Heavy Duty. Manual reset Standard Duty. Feature and Benefits PSC9919 European Refrigeration Controls Catalogue Catalog Section 6 Product Bulletin P100 Series P100 Encapsulated Pressure Control. Auto-reset Standard Duty and Heavy Duty. Manual reset Standard Duty.

More information

Introduction. System Components

Introduction. System Components The Selectra SERIES 94 is for use with either direct or indirect gas fired units (furnaces, ovens, etc.). The system may be field installed on existing equipment or specified for new equipment installation.

More information

ATD WATT INVERTER

ATD WATT INVERTER ATD-5954 1500 WATT INVERTER Welcome. This ATD product has been carefully engineered and manufactured to give you dependable operation. Please read this manual thoroughly before operating your new ATD product,

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 11/05 Form #271 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 OPERATING INSTRUCTION Visit us at www.testequipmentdepot.com MODEL 3132 ANALOG INSULATION-CONTINUITY TESTER

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

Intelligent Charging System Series

Intelligent Charging System Series R Intelligent Charging System Series OWNER S MANUAL ON BOARD BATTERY CHARGERS Models Amperage No. Of Banks Volts 16061 s 1 Bank 12 16102 6,s 2 Banks 12 or 24 16153 6,6,s 3 Banks 12 or 24 or 36 16202 10,10

More information

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. IMPORTANT SAFEGUARDS INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL When using

More information

ATD WATT INVERTER

ATD WATT INVERTER ATD-5955 2000 WATT INVERTER Welcome. This ATD product has been carefully engineered and manufactured to give you dependable operation. Please read this manual thoroughly before operating your new ATD product,

More information

AUTO CHARGE 12 AUTOMATIC BATTERY CHARGER

AUTO CHARGE 12 AUTOMATIC BATTERY CHARGER INSTRUCTION MANUAL FILE: 091-165-12 reve Rev: E, page 8 DATE: 7-02-15 AUTO CHARGE 12 AUTOMATIC BATTERY CHARGER MODEL #091-165-12 NOTE : This charger is designed for vehicles with a single battery and negative

More information

Series 44 Installation Instructions

Series 44 Installation Instructions and field service checklist Series 44 Installation Instructions Table of Contents Page 1 Page 2 & 3 Page 4 Page 5 Page 6 Page 7 Page 8 System Components Amplifiers System Components Introduction and Dimensions

More information

R & D SPECIALTIES ROTROL I USER'S MANUAL

R & D SPECIALTIES ROTROL I USER'S MANUAL R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL

More information

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor OPERATIONS MANUAL The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor Safe, reliable ignition and flame failure protection combined with a proven, completely self-powered

More information

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide WARNING Before troubleshooting any CEN products, the service technician should: read, understand, and agree to follow all

More information

S150,S300 Series Pure Sine Wave Inverter User s Manual

S150,S300 Series Pure Sine Wave Inverter User s Manual S150,S300 Series Pure Sine Wave Inverter User s Manual List of contents 1. Important Safety Instructions 3 1-1 General Safety Precautions 3 1-2 Precautions When Working With Batteries.. 3 2. Features...

More information

Electro- Hydraulic Actuator Gas Valves GH-5000

Electro- Hydraulic Actuator Gas Valves GH-5000 Electro- Hydraulic Actuator Gas Valves GH-5000 SDI-Code: 10 280 010 E Issue Date: 01/200 Electro-Hydraulic Actuator Gas Valve GH-5000-... Function ormally closed (C). Single seat valve, fast closing, slow

More information

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators

R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators R81EAA Type Plug-In Electronic Circuit Board Kit For Series M100 Motor Actuators Installation Sheets Manual 121 Relays and Contactors Section R Technical Bulletin R81EAA Application R81 plug-in electronic

More information

INSTALLER MANUAL USER MANUAL. Contents

INSTALLER MANUAL USER MANUAL. Contents Installation & user manual two way Contents INSTALLER MANUAL Important information General 1. Technical data 2. Description Installation: 1. Positioning the unit 2. Connection. 3. Parts description. 4.

More information

ONE STAGE GAS BURNERS RS/1 SERIES RS 28/ kw RS 34/1 MZ kw RS 38/ kw RS 44/1 MZ kw

ONE STAGE GAS BURNERS RS/1 SERIES RS 28/ kw RS 34/1 MZ kw RS 38/ kw RS 44/1 MZ kw ONE STAGE GAS BURNERS RS/1 SERIES RS 28/1 163 349 kw RS 34/1 MZ 7 39 kw RS 38/1 232 465 kw RS 44/1 MZ 55 kw The RS/1 series of burners covers a firing range from 7 to 55 kw, and they have been designed

More information

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw

TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO 40 GS/M SERIES GS 10/M 22/ kw GS 20/M 43/ kw TWO STAGE PROGRESSIVE AND MODULATING GAS BURNERS RIELLO GS/M SERIES GS /M / 5 3/8 19 The Riello GS/M series of two stage progressive or modulating gas burners, is a complete range of products developed

More information

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

DPT-2015 Differential Pressure Transmitter for VAV Box Applications Installation Instructions DPT-2015 Issue Date June 25, 2015 DPT-2015 Differential Pressure Transmitter for VAV Box Applications Installation Parts Included DPT-2015 transmitter two No. 6 x 1/4 in. thread-forming

More information

3-PHASE SMART CONTROLLER STP-SCIIIC INSTALLATION GUIDE

3-PHASE SMART CONTROLLER STP-SCIIIC INSTALLATION GUIDE 3-PHASE SMART CONTROLLER STP-SCIIIC INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the

More information

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages. PM500 Voltage Regulator User Manual A Regal Brand Scan here for other languages. Introduction The PM500 is an encapsulated electronic voltage regulator intended for use with Marathon Generators PMG system.

More information

I ntroduction. VA-7450 Electronic Terminal Unit Valve Actuator. Features and Benefits

I ntroduction. VA-7450 Electronic Terminal Unit Valve Actuator. Features and Benefits European Electronic Controls Catalogue Catalogue Section E Product Bulletin VA-7450 Issue Date 199 VA-7450 Electronic Terminal Unit Valve I ntroduction The VA-7450 Series provides floating or proportional

More information

SECTION 2.10 IGNITION SYSTEM DESCRIPTION CEC IGNITION MODULE SYSTEM MAGNETO IGNITION SYSTEM

SECTION 2.10 IGNITION SYSTEM DESCRIPTION CEC IGNITION MODULE SYSTEM MAGNETO IGNITION SYSTEM SECTION 2.10 SYSTEM DESCRIPTION CEC SYSTEM The Custom Engine Control (CEC) Ignition Module is located on the engine's left side (see Figure 2.10-1 and Figure 2.10-2). The CEC Ignition Module system consists

More information

M Ball Valve Linkage Kit

M Ball Valve Linkage Kit M9000-551 Ball Valve Linkage Kit Installation Instructions Part No. 34-636-1816, Rev. B Issued July 6, 2011 Supersedes February 7, 2006 Applications The M9000-551 Ball Valve Linkage Kit (Figure 1) is designed

More information

1329I Integrated Drive/Motor CE Filter Option Kit

1329I Integrated Drive/Motor CE Filter Option Kit Instruction Sheet 1329I Integrated Drive/Motor CE Filter Option Kit CE filter options are designed to be used with the 1329I Integrated Drive/Motor. The main function of the CE filter is to reduce the

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Series P215ST Single Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter)

Series P215ST Single Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter) PSC9733 European Refrigeration Controls Catalogue Catalog Section 4 Product Bulletin Series Single Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

Installation Instructions

Installation Instructions Smart Start Assist Kit For use with Single-Phase Residential Geothermal Heat Pumps 8-733-934-497 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY

More information

M9220-xxx-3 Electric Spring Return Actuators

M9220-xxx-3 Electric Spring Return Actuators M9220-xxx-3 Electric Spring Return Actuators Product Bulletin Code No. LIT-12011057 Issued September 2017 The M9220-xxx-3 Actuators are direct mount, spring return electric actuators that operate on these

More information

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR 125-5 P/N 9168800100 Publication: 9168800990 Revision: J 03/09 INTRODUCTION This instruction manual provides information about the operation and installation

More information

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC Automatic Battery Charger Switching mode with Micro-controlled Input:220-260Vac / Output: 12Volt DC User s Manual and Important Safety Information Model: OC-SW121080 / OC-SW121160 / OC-SW121210 FEATURES

More information

Series P74 Differential Pressure Controls, without time delay

Series P74 Differential Pressure Controls, without time delay PB_P74_11 2010 Series P74 Differential Pressure Controls, without time delay These controls are designed to sense pressure differences between two points and may be used as operating or limit controls.

More information

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN Contents 1. Safety Precautions... 1 2. Features... 3 3. Specifications... 4 4. Instrument

More information

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION SECTION 3.00 ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION Be sure that the clutch, circuit breaker, or other main power transmission device is disconnected. Generators develop voltage as soon as the

More information

Specifications of STICKTITE and PILOTPAK Nozzles

Specifications of STICKTITE and PILOTPAK Nozzles Low Temperature urners - STICKTITE and PILOTPK Nozzles 1-1.1-5 Specifications of STICKTITE and PILOTPK Nozzles This graph indicates the relationship between capacity and applied mixture differential pressure

More information

DC TO AC POWER INVERTER

DC TO AC POWER INVERTER DC TO AC POWER INVERTER 12V / 24V / 48Vdc Input 115V / 230Vac Output 150W ~ 6000W Output cont. L-Series User Manual Before install and use your Inverter, read the User Manual and safety instructions. Cooler

More information

Part List: Jandy LXI Series Heaters

Part List: Jandy LXI Series Heaters Part List: Jandy LXI Series Heaters Models LXI250, LXI400 For pool heater parts, equipment and any pool accessories, visit www.torontopoolsupplies.ca 1-844-416-7665 416-623-9334 info@torontopoolsupplies.ca

More information

Activator 282 Aircraft Battery Maintenance Charger Operator Manual

Activator 282 Aircraft Battery Maintenance Charger Operator Manual Activator 282 Aircraft Battery Maintenance Charger Operator Manual Revision 2.1a February 2013 This Operator Manual applies to the Activator 282 with a Liquid Crystal Display starting with Serial Number

More information

Operating Instructions Bedienungsanleitung Mode d emploi EWB EWB

Operating Instructions Bedienungsanleitung Mode d emploi EWB EWB Operating Instructions Bedienungsanleitung Mode d emploi DW 400 EWB 400 575 EWB 400 575 800 www.bron-kobold.com Operating instructions EWB 400.575 EWB 400.575.800 Before use Please read all the information

More information

This document describes the commissioning checklist procedures for the Capstone MicroTurbine systems.

This document describes the commissioning checklist procedures for the Capstone MicroTurbine systems. Capstone Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA Telephone: (818) 734-5300 Facsimile: (818) 734-5320 Website: www.microturbine.com Work Instructions Commissioning Checklist

More information

poollux Power plx-pw60 & plx-pw100

poollux Power plx-pw60 & plx-pw100 poollux Power plx-pw60 & plx-pw100 ETL LISTED Conforms to UL STD 379; Certifi.ed.to.CSA.STD.C22.2.#218.1 5005508 Installation Instructions Read all instructions before attempting to perform installation

More information

DKG-114 MANUAL AND REMOTE START UNIT

DKG-114 MANUAL AND REMOTE START UNIT DKG-114 MANUAL AND REMOTE START UNIT FEATURES Both manual and remote controlled engine starting and stopping, Automatic shutdown on fault condition, Optional cooldown cycle on remote start operation, Optional

More information

O W N E R ' S M A N U A L

O W N E R ' S M A N U A L 1500 Watt DC to AC Power Inverter C o n v e r t s 1 2 V D C B a t t e r y P o w e r t o 1 1 0 V A C H o m e P o w e r O W N E R ' S M A N U A L SAVE THESE INSTRUCTIONS The recommended source of power is

More information

Phone: Fax: Web: -

Phone: Fax: Web:  - Timer - Delay-on-Make The TAC1 Series was designed to delay the operation of a compressor relay. It eliminates the possibility of relay chatter due to half-wave failure of the output. It connects in series

More information

Instruction Manual for the 110 VAC Draw-off Controller System

Instruction Manual for the 110 VAC Draw-off Controller System 1 Instruction Manual for the 110 VAC Draw-off Controller System Introduction This Electronic Draw-off Controller is specifically designed for use in the Maple syrup industry. It has several features designed

More information

INSTRUCTION MANUAL. 12-Station HD Shop 12V Portable Battery Charger

INSTRUCTION MANUAL. 12-Station HD Shop 12V Portable Battery Charger INSTRUCTION MANUAL 12-Station HD Shop 12V Portable Battery Charger IMPORTANT SAFETY INSTRUCTIONS 1. SAVE THESE INSTRUCTIONS This manual contains important safety and operating instructions for your HD

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated DC-4 SEQUENCE OVERFIRE DRAFT CONTROL SYSTEM OPERATING AND MAINTENANCE MANUAL THE POWER TO MANAGE ENERGY 2001 South 21 st Street, Parsons, Kansas 67357 Telephone 620-421-0480, Fax

More information

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS MANUAL NUMBER: 64073 REV: 2 DATE: October 3, 2006 INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS AMERICAN BATTERY CHARGING, INC. P.O. BOX 17040 28 MAPLE AVENUE SMITHFIELD,

More information

To ensure proper installation, digital pictures with contact information to before startup.

To ensure proper installation,  digital pictures with contact information to before startup. Check List for Optimal Filter Performance [ ] There should be no back-pressure on the flush line. A 1 valve should have a 2 waste line, and 2 valve should have a 3 waste line. Do not use rubber hosing

More information

GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models)

GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models) FORM NO. GSC-515 GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models) TWO STAGE DOWNFLOW GAS FURNACES The Sure Comfort 2-Stage line of downflow gas furnaces

More information

HIGH FREQUENCY AUTOMATIC BATTERY CHARGER

HIGH FREQUENCY AUTOMATIC BATTERY CHARGER HIGH FREQUENCY AUTOMATIC BATTERY CHARGER MODEL NO: HFBC12 PART NO: 6267000 OPERATION & MAINTENANCE INSTRUCTIONS LS0814 INTRODUCTION Thank you for purchasing this CLARKE High Frequency Automatic Battery

More information

Operating instructions EWB 200

Operating instructions EWB 200 Operating instructions EWB 200 www.bron-kobold.com 1 Operating instructions EWB 200 Before use Please read all the information contained in these operating instructions carefully. They contain important

More information

M9203-xxx-2(Z) Series Electric Spring Return Actuators

M9203-xxx-2(Z) Series Electric Spring Return Actuators M9203-AGx-2(Z), M9203-GGx-2(Z), M9203-Bxx-2(Z) M9203-xxx-2(Z) Series Electric Spring Return Actuators Code No. LIT-1900682 Issued February 16, 2011 Description The M9203-xxx-2(Z) Series Electric Spring

More information

GMS8/GDS8/GHS8. Single-Stage, Multi-Speed, Multi-Position Gas Furnace 80% AFUE. Heating Input : 40, ,000 BTU/h

GMS8/GDS8/GHS8. Single-Stage, Multi-Speed, Multi-Position Gas Furnace 80% AFUE. Heating Input : 40, ,000 BTU/h // Heating Input : 40,000 140,000 BTU/h Single-Stage, Multi-Speed, Multi-Position Gas Furnace 80% AFUE Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 5 Airflow Data... 8 Wiring Diagrams...

More information

1000-Watt Energy Center

1000-Watt Energy Center 1000-Watt Energy Center OPERATING INSTRUCTIONS Patent Pending Sierra Wave 1000-Watt Energy Center #9675 The Sierra Wave 1000-Watt Energy Center is a heavy duty and efficient portable power center offering

More information

HI-POT/CONTINUITY TESTER Model PLEP01

HI-POT/CONTINUITY TESTER Model PLEP01 HI-POT/CONTINUITY TESTER Model PLEP01 Instruction Manual MITCHELL INSTRUMENT CO. Dear Customer: Congratulations! Mitchell Instrument Co. is please to present you with your Hipot/Continuity Tester. This

More information

DD80HS. Two-Stage, Convertible Multi-Speed Gas Furnace 80% AFUE. Heating Input: 40, ,000 BTU/h

DD80HS. Two-Stage, Convertible Multi-Speed Gas Furnace 80% AFUE. Heating Input: 40, ,000 BTU/h Two-Stage, Convertible Multi-Speed Gas Furnace 80% AFUE Heating Input: 40,000 100,000 BTU/h Contents Nomenclature...2 Product Specifications...3 Dimensions...4 Airflow Data...5 Wiring Diagram...7 Accessories...8

More information

NT PROPORTIONAL CONTROL VALVE, MODEL 6300

NT PROPORTIONAL CONTROL VALVE, MODEL 6300 P/N 1365 (Rev. B 4/14) NT PROPORTIONAL CONTROL VALVE, MODEL 63 User Guide Table of Contents Introduction... 2 Principle of Operation... 2 Factory Configured... 2 General Considerations... 2 Line Pressure...

More information