MEMORANDUM. NFPA 54 Second Draft Technical Committee FINAL Ballot Results (A2017)

Size: px
Start display at page:

Download "MEMORANDUM. NFPA 54 Second Draft Technical Committee FINAL Ballot Results (A2017)"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: MEMORANDUM TO: FROM: Technical Committee on National Fuel Gas Code Jenny Depew, Project Administrator DATE: September 13, 2016 SUBJECT: NFPA 54 Second Draft Technical Committee FINAL Ballot Results (A2017) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 29 Members Eligible to Vote 0 Members Not Returned 22 Members Voted Affirmative on All Revisions 0 Members Vote Affirmative with Comment on one or more Revisions 5 Members Voted Negative on one or more Revisions (Brewer, Feehan, Holmes, Osterhaus, Ribbs) 2 Members Abstained on one or more Revisions (Griffith, Lemoff) The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections (c) and of the Regulations Governing the Development of NFPA Standards.

2 of 107 9/13/2016 4:08 PM Second Revision No. 20-NFPA [ Detail ] In Section , change "Schedule 40" to "Schedule 10" In Table A.5.6, make the following changes to the Material column under Pipe: Material Pipe Black Steel Minimum Schedule Galvanized Steel Minimum Schedule Wrought Iron Minimum Schedule Also known as low iron or wrought steel Stainless Steel Minimum Schedule 10 Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jun 22 12:11:43 EDT 2016 Committee Statement Committee Statement: The schedule 40 restriction was in place to safely accommodate threading of pipe. Allowing schedule 10 acknowledges different pipe joining methods. The revision will allow Schedule 10 pipe to be used for fuel gas piping in buildings. Schedule 10 pipe has a thinner wall than Schedule 40 and therefore is lighter and has a higher gas flow than Schedule 40. Schedule 10 pipe is currently allowed for fuel gas piping at pressures above 125 psig by ASME B31.1, Power Piping. As it is allowed for higher pressure than covered by the scope of the National Fuel Gas Code there is technical reason to not allow the material in NFPA 54. Due to the thinner wall of Schedule 10 pipe it cannot be threaded, and must be joined by other methods such as press connect fittings, welding, and other means. The revision does not limit the means of joining schedule 10 pipe other than not allowing threading. Schedule 10 pipe, while thinner than Schedule 40, has sufficient strength to withstand damage during installation. It should be sufficiently robust to not be dented, pinched, or punctured in normal installations in buildings. Because of the thinner wall, the inside diameter of Schedule 10 pipe is greater than Schedule 40. This results in a higher gas flow capacity of approximately 6 %. The

3 2 of 107 9/13/2016 4:08 PM current Schedule 40 pipe sizing tables can be used or a note can be added to the table to allow flow to be increased by 6% where Schedule 10 is used. Response Message: The existing table of pipe hanger spacing can be used for Schedule 10 pipe as the pipe is lighter than Schedule 40 pipe. Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 26 Affirmative All 0 Affirmative with Comments 2 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Simnick, Lynne Smith, Eric C. Swim, Peter C.

4 3 of 107 9/13/2016 4:08 PM Switzer, Jr., Franklin R. Negative with Comment Feehan, Pennie L. The statement that schedule 10 pipe is difficult to get and will not be sold in big box stores is not a good argument! It reminds me of the CSST s promised the big box stores would not carry this product and it would only be sold to plumbers that were certified to install. Today, CSST is sold in Lowes and Home Depots. Section 1.4 allows jurisdictions to approve schedule 10 whenever they choose. Once the code is changed, there will be no control on where schedule 10 pipe is installed or sold. These products will be available to use by anyone, including homeowners. Ribbs, Phillip H. I strongly disagree with this proposal. No scientific justification was presented to address internal and external corrosion affects to steel pipe as requested by the TC in their previous meeting. I have met with gas utility suppliers from Southern Nevada and Pacific Gas & Electric. Both suppliers recommend that Schedule 40 remain the minimum requirement for steel gas piping systems. The San Bruno, CA gas line failure which resulted in loss of lives and millions of dollars of property was sighted. I met with Viega (Pro-Press) representatives at the ASHE Expo. They reported no issues with Schedule 40 joining methods. Viega representatives have given presentations, which I attended, in Utah and Nor-Cal at UAPMO and IAPMO inspector chapter meetings stating the same successes. I met with design-build contractors and code enforcement officials who reported having no issues or failures with Schedule 40 installations. Lastly, the potential for the general public to improperly install Schedule 10 pipe will be greatly enhanced by this proposal. I believe there was no justification presented for the current level of health and safety to be reduced. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

5 4 of 107 9/13/2016 4:08 PM Second Revision No. 32-NFPA [ Section No ] ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA , (610) , ASTM A53, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated Welded and Seamless, ASTM A106, Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service, ASTM A254, Standard Specification for Copper-Brazed Steel Tubing, ASTM A268, Standard Specification for Seamless and Welded Ferritic and Martensitic Stainless Steel Tubing for General Service, ASTM A269, Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service, ASTM A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes, ASTM B88, Standard Specification for Seamless Copper Water Tube, ASTM B210, Standard Specification for Aluminum and Aluminum-Alloy Drawn Seamless Tubes, ASTM B241, Standard Specification for Aluminum and Aluminum-Alloy Seamless Pipe and Seamless Extruded Tube, ASTM B280, Standard Specification for Seamless Copper Tube for Air-Conditioning and Refrigeration Field Service, ASTM D2513, Standard Specification for Polyethylene (PE) Gas Pressure Pipe, Tubing, and Fittings, ASTM D2513, Standard Specification for Thermoplastic Gas Pressure Pipe, Tubing, and Fittings, 2009 ASTM E136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 Degrees C 750 C, ASTM E2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 C, ASTM F1973, Standard Specification for Factory Assembled Anodeless Risers and Transition Fittings in Polyethylene (PE) and Polyamide 11 (PA11) and Polyamide 12 (PA12) Fuel Gas Distribution Systems, ASTM F2509, Standard Specification for Field-Assembled Anodeless Riser Kits for Use on Outside Diameter Controlled Polyethylene Gas Distribution Pipe and Tubing, ASTM F2945, Standard Specification for Polyamide 11 Gas Pressure Pipe, Tubing, and Fittings, Submitter Information Verification Submitter Full Name: Laura Montville Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Thu Jun 30 15:08:04 EDT 2016

6 5 of 107 9/13/2016 4:08 PM Committee Statement Committee Statement: Response Message: Ballot Results This item has passed ballot Polyamide piping and fittings, which were removed from ASTM D2513, are now covered by ASTM F Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C.

7 6 of 107 9/13/2016 4:08 PM Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

8 7 of 107 9/13/2016 4:08 PM Second Revision No. 3-NFPA [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 31, Standard for the Installation of Oil-Burning Equipment, edition. NFPA 70, National Electrical Code, edition. NFPA 88A, Standard for Parking Structures, 2015 edition. NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2015 edition. NFPA 101, Life Safety Code, edition. NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, 2010 edition. NFPA 501, Standard on Manufactured Housing, edition. NFPA 5000, Building Construction and Safety Code, edition. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jun 20 15:30:50 EDT 2016 Committee Statement Committee Statement: Updating the extracted documents to their most recent edition. Response Message: Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P.

9 8 of 107 9/13/2016 4:08 PM Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

10 9 of 107 9/13/2016 4:08 PM Second Revision No. 1-NFPA [ Section No ] Low Pressure Boiler. A boiler for generating steam at gauge pressures not in excess of 15 psi (gauge pressure of 103 kpa) or for furnishing water at a maximum temperature of 250 F (121 C) at a maximum gauge pressure of 160 psi (gauge pressure of 1100 kpa). [31, ] Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jun 20 15:24:39 EDT 2016 Committee Statement Committee Statement: This change is made to align with the most recent edition of NFPA 31. Response Message: Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark

11 10 of 107 9/13/2016 4:08 PM Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

12 11 of 107 9/13/2016 4:08 PM Second Revision No. 2-NFPA [ Section No ] Natural Draft. Draft produced by the difference in the weight of a column of flue gases within a chimney or vent system and a corresponding column of air of equal dimension outside the chimney or vent venting system. [211 31, ] Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Mon Jun 20 15:27:19 EDT 2016 Committee Statement Committee Statement: Response Message: This change is made to align with the most recent edition of NFPA 211. The 2016 edition of NFPA 211 extracts the definition from NFPA 31. Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A.

13 12 of 107 9/13/2016 4:08 PM Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

14 13 of 107 9/13/2016 4:08 PM Second Revision No. 27-NFPA [ Section No ] Effective Ground-Fault Current Path. An intentionally constructed, low impedance electrically conductive path designed and intended to carry current under ground-fault conditions from the point of a ground fault on a wiring system to the electrical supply source and that facilitates the operation of the overcurrent protective device or ground-fault detectors on high-impedance grounded systems. [70: ] Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jun 22 13:54:53 EDT 2016 Committee Statement Committee Statement: Updating extract to most recent edition. Response Message: Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A.

15 14 of 107 9/13/2016 4:08 PM Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

16 15 of 107 9/13/2016 4:08 PM Second Revision No. 19-NFPA [ Section No ] * Monitor Regulator. A regulator installed in series with a pressure regulator and that senses the same downstream pressure as the pressure regulator for the purpose of preventing an overpressure in the downstream piping system when the pressure regulator fails to control the downstream pressure. A pressure regulator that is installed in series with another pressure regulator for the purpose of preventing an overpressure in the downstream piping system. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jun 22 11:33:19 EDT 2016 Committee Statement Committee Statement: The definition is revised to be more straightforward and remove requirements. Response Message: Public Comment No. 42-NFPA [Section No ] Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike

17 16 of 107 9/13/2016 4:08 PM Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

18 17 of 107 9/13/2016 4:08 PM Second Revision No. 4-NFPA [ Section No ] Piping System Operating Pressure Limitations. The maximum design operating pressure for any piping system shall not exceed 125 psi (862 kpa). Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 12:40:01 EDT 2016 Committee Statement Committee Statement: Response Message: Current language implies operating pressure and design operating pressure could be different. Also, the design of the gas piping system may be greater than 125 PSI, but it should never operate above 125 PSI. This revision does not add "gas" to piping systems because that would be redundant based on the scope of the code. Public Comment No. 34-NFPA [Section No ] Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R.

19 18 of 107 9/13/2016 4:08 PM Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

20 19 of 107 9/13/2016 4:08 PM Second Revision No. 5-NFPA [ Section No ] Maximum Design Operating Pressure in Buildings. The maximum design operating pressure for any piping systems located inside buildings shall not exceed 5 psi (34 kpa) unless one or more of the following conditions are met: (1)* The piping joints are welded or brazed. (2) The piping joints are flanged and all pipe-to-flange connections are made by welding or brazing. (3) The piping is located in a ventilated chase or otherwise enclosed for protection against accidental gas accumulation. (4) The piping is located inside buildings or separate areas of buildings used exclusively for one of the following: (a) (b) (c) (d) Industrial processing or heating Research Warehousing Boiler or mechanical rooms (5) The piping is a temporary installation for buildings under construction. (6) The piping serves appliances or equipment used for agricultural purposes. (7) The piping system is an LP-Gas piping system with a design an operating pressure greater than 20 psi (138 kpa) and complies with NFPA 58. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 12:46:23 EDT 2016 Committee Statement Committee Statement: Response Message: Current language implies operating pressure and design operating pressure could be different. Also, the design of the gas piping system may be greater than 125 PSI, but it should never operate above 125 PSI. This revision does not add "gas" to piping systems because that would be redundant based on the scope of the code. This revision also does not add "system" because the requirements are meant to apply only to a portion of the piping system (for example the portion in a ventilated chase), not the system as a whole. Public Comment No. 33-NFPA [Section No ] Ballot Results

21 20 of 107 9/13/2016 4:08 PM This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

22 21 of 107 9/13/2016 4:08 PM Second Revision No. 6-NFPA [ Section No ] Low Temperature LP-Gas Systems Operating Below 5 F ( 21 C). LP-Gas systems designed to operate below 5 F ( 21 C) or with butane or a propane-butane mix shall be designed to either accommodate liquid LP-Gas or to prevent LP-Gas vapor from condensing back into a liquid. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 13:13:40 EDT 2016 Committee Statement Committee Statement: The term "low temperature" is subjective and this revision gives a specific threshold. Response Message: Public Comment No. 41-NFPA [Section No ] Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A.

23 22 of 107 9/13/2016 4:08 PM Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

24 23 of 107 9/13/2016 4:08 PM Second Revision No. 30-NFPA [ Section No ] Detail SR Steel, Stainless Steel, and Wrought Iron. Steel, stainless steel, and wrought-iron pipe shall be at least Schedule 40Schedule 10 and shall comply with one of the followingdimensional standards of ANSI/ASME B36.10M, Welded and Seamless Wrought Steel Pipe, and one of the following: ANSI/ASME B36.10M, Welded and Seamless Wrought-Steel Pipe (1) ASTM A53, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated Welded and Seamless (2) ASTM A106, Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service (3) ASTM A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes Submitter Information Verification Submitter Full Name: Laura Montville Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Thu Jun 30 13:23:22 EDT 2016 Committee Statement Committee Statement: Response Message: B36.10M includes only dimensional specifications while the other three cover chemical composition and manufacturing of the pipe. Note: Schedule 40 is not being changed to Schedule 10 by this revision. This is being done by Second Revision 20. Public Comment No. 57-NFPA [Section No ] Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 26 Affirmative All 0 Affirmative with Comments 1 Negative with Comments 2 Abstention

25 24 of 107 9/13/2016 4:08 PM Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Negative with Comment Ribbs, Phillip H. SEE comments SR-20 Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions. Lemoff, Theodore C. I represented Viega at the first draft meeting when this subject was introduced. I am abstaining as I represented the manufacturer of a product affected by this revision.

26 25 of 107 9/13/2016 4:08 PM Second Revision No. 29-NFPA [ Section No ] Plastic Polyamide pipe, tubing, and fittings, other than polyethylene, shall be identified in and conform to the 2008 edition of ASTM D2513 F2945, Standard Specification for Thermoplastic Polyamide 11 Gas Pressure Pipe, Tubing, and Fittings. Pipe to be used shall be marked gas and ASTM D2513 F2945. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jun 22 14:09:47 EDT 2016 Committee Statement Committee Statement: Polyamide pipe, tubing, and fittings are now covered by ASTM F2945. Response Message: Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark

27 26 of 107 9/13/2016 4:08 PM Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

28 27 of 107 9/13/2016 4:08 PM Second Revision No. 21-NFPA [ Section No ] * Pipe Joints. Pipe Schedule 40 and heavier pipe joints shall be threaded, flanged, brazed, welded, or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32, Press-Connect Metallic Fittings for Use in Fuel Gas Distribution Systems. Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000 F (538 C). Brazing alloys shall not contain more than 0.05 percent phosphorus. (A) Pipe lighter than Schedule 40 shall be connected using press-connect fittings, flanges, brazing, or welding. (B) Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000 F (538 C). (C) Brazing alloys shall not contain more than 0.05 percent phosphorus. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jun 22 12:19:06 EDT 2016 Committee Statement Committee Statement: The schedule 40 restriction was in place to safely accommodate threading of pipe. Allowing schedule 10 acknowledges different pipe joining methods. The revision will allow Schedule 10 pipe to be used for fuel gas piping in buildings. Schedule 10 pipe has a thinner wall than Schedule 40 and therefore is lighter and has a higher gas flow than Schedule 40. Schedule 10 pipe is currently allowed for fuel gas piping at pressures above 125 psig by ASME B31.1, Power Piping. As it is allowed for higher pressure than covered by the scope of the National Fuel Gas Code there is technical reason to not allow the material in NFPA 54. Due to the thinner wall of Schedule 10 pipe it cannot be threaded, and must be joined by other methods such as press connect fittings, welding, and other means. The revision does not limit the means of joining schedule 10 pipe other than not allowing threading. Schedule 10 pipe, while thinner than Schedule 40, has sufficient strength to withstand damage during installation. It should be sufficiently robust to not be dented, pinched, or punctured in normal installations in buildings. Because of the thinner wall, the inside diameter of Schedule 10 pipe is greater than Schedule 40. This results in a higher gas flow capacity of approximately 6 %. The current Schedule 40 pipe sizing tables can be used or a note can be added to the table to allow flow to be increased by 6% where Schedule 10 is used. The existing table of pipe hanger spacing can be used for Schedule 10 pipe as the pipe is lighter

29 28 of 107 9/13/2016 4:08 PM Response Message: than Schedule 40 pipe. Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R.

30 29 of 107 9/13/2016 4:08 PM Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

31 30 of 107 9/13/2016 4:08 PM Second Revision No. 7-NFPA [ Section No ] Where Required. A line pressure regulator or gas appliance pressure regulator, as applicable, shall be installed where the gas supply pressure exceeds the maximum allowable inlet pressure of the appliance served Listing. Line pressure regulators shall be listed in accordance with ANSI Z21.80/CSA 6.22, Line Pressure Regulators, where the outlet pressure is set to 2 psi or less. Submitter Information Verification Submitter Full Name: Laura Montville Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jun 21 13:40:16 EDT 2016 Committee Statement Committee Statement: "Gas appliance pressure regulator" was removed because appliance regulators do not fall under the scope of the code. The intent of a line pressure regulator listed in accordance with ANSI Z21.80/CSA 6.22 has to do with an installation where the appliance is rated for 0.5 PSI (typically this is an appliance listed to any one of the ANSI Z21/83 series standards) and the supply pressure is greater than 0.5 PSI. Listing to ANSI Z21.80/CSA 6.22 should be required only when its outlet pressure is 2 PSI or less. Response Message: Public Comment No. 35-NFPA [Sections 5.8.1, 5.8.2] Ballot Results This item has passed ballot 29 Eligible Voters 0 Not Returned 28 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 1 Abstention Affirmative All Antonov, Dmitry Berning, David

32 31 of 107 9/13/2016 4:08 PM Brania, Jonathan Brewer, James P. Corcoran, Shannon M. Crane, Thomas R. Davis, Gerald G. Deegan, Mike Edgar, Glen A. Fasel, Mark Feehan, Pennie L. Fossa, Alberto Jose Gorham, Mike Gress, Gregg A. Hagensen, Steen Hamilton, William T. Himes, Patricio J. Holmes, Peter T. Kulik, Marek Lemoff, Theodore C. Mortimer, Frank J. Osterhaus, James T. Papageorge, Andrea Lanier Ribbs, Phillip H. Simnick, Lynne Smith, Eric C. Swim, Peter C. Switzer, Jr., Franklin R. Abstention Griffith, Roger W Recently appointed to TC. I think it would be best for me not to vote on the Second Revisions. I would prefer to be a part of the discussions and understand the reasons behind the proposed revisions.

33 32 of 107 9/13/2016 4:08 PM Second Revision No. 8-NFPA [ Section No ]

34 33 of 107 9/13/2016 4:08 PM 6.2.1

35 34 of 107 9/13/2016 4:08 PM Table 6.2.1(a) through Table 6.2.1(x) shall be used in conjunction with one of the methods described in through for piping materials other than non-corrugated stainless steel tubing. Table 6.2.1(a) Schedule 40 Metallic Pipe Nominal: 1 2 Pipe Size (in.) Inlet Pressure: Gas: Natural Less than 2 psi Pressure Drop: 0.3 in. w.c Specific Gravity: Actual ID: Length (ft) Capacity in Cubic Feet of Gas per Hour ,060 1,580 3,050 4,860 8,580 17,500 31,700 51, , , ,090 2,090 3,340 5,900 12,000 21,800 35,300 72, , ,680 2,680 4,740 9,660 17,500 28,300 58, , ,440 2,290 4,050 8,270 15,000 24,200 49,800 90, ,280 2,030 3,590 7,330 13,300 21,500 44,100 80, ,160 1,840 3,260 6,640 12,000 19,500 40,000 72, ,060 1,690 3,000 6,110 11,100 17,900 36,800 66, ,580 2,790 5,680 10,300 16,700 34,200 62, ,480 2,610 5,330 9,650 15,600 32,100 58, ,400 2,470 5,040 9,110 14,800 30,300 55, ,240 2,190 4,460 8,080 13,100 26,900 48, ,120 1,980 4,050 7,320 11,900 24,300 44, ,030 1,820 3,720 6,730 10,900 22,400 40, ,700 3,460 6,260 10,100 20,800 37, ,500 3,070 5,550 8,990 18,500 33, ,360 2,780 5,030 8,150 16,700 30, ,250 2,560 4,630 7,490 15,400 28, ,170 2,380 4,310 6,970 14,300 26, ,090 2,230 4,040 6,540 13,400 24, ,030 2,110 3,820 6,180 12,700 23, ,000 3,620 5,870 12,100 21, ,910 3,460 5,600 11,500 20, ,830 3,310 5,360 11,000 20, ,760 3,180 5,150 10,600 19, ,690 3,060 4,960 10,200 18, ,640 2,960 4,790 9,840 17, ,580 2,860 4,640 9,530 17, ,530 2,780 4,500 9,240 16, ,490 2,700 4,370 8,970 16,300 25

36 35 of 107 9/13/2016 4:08 PM 1, ,450 2,620 4,250 8,720 15, , ,380 2,490 4,030 8,290 15, ,200 NA ,310 2,380 3,850 7,910 14, ,300 NA ,260 2,280 3,680 7,570 13, ,400 NA ,210 2,190 3,540 7,270 13, ,500 NA ,160 2,110 3,410 7,010 12, ,600 NA ,120 2,030 3,290 6,770 12, ,700 NA ,090 1,970 3,190 6,550 11, ,800 NA ,050 1,910 3,090 6,350 11, ,900 NA ,020 1,850 3,000 6,170 11, ,000 NA ,000 1,800 2,920 6,000 10, NA: A flow of less than 10 cfh. Note: All table entries are rounded to 3 significant digits. Table 6.2.1(b) Schedule 40 Metallic Pipe Nominal: 1 2 Pipe Size (in.) Inlet Pressure: Gas: Natural Less than 2 psi Pressure Drop: 0.5 in. w.c Specific Gravity: Actual ID: Length (ft) Capacity in Cubic Feet of Gas per Hour ,390 2,090 4,020 6,400 11,300 23,100 41,800 67, , , ,430 2,760 4,400 7,780 15,900 28,700 46,500 95, , ,150 2,220 3,530 6,250 12,700 23,000 37,300 76, , ,900 3,020 5,350 10,900 19,700 31,900 65, , ,680 2,680 4,740 9,660 17,500 28,300 58, , ,520 2,430 4,290 8,760 15,800 25,600 52,700 95, ,400 2,230 3,950 8,050 14,600 23,600 48,500 88, ,300 2,080 3,670 7,490 13,600 22,000 45,100 81, ,220 1,950 3,450 7,030 12,700 20,600 42,300 76, ,160 1,840 3,260 6,640 12,000 19,500 40,000 72, ,020 1,630 2,890 5,890 10,600 17,200 35,400 64, ,480 2,610 5,330 9,650 15,600 32,100 58, ,360 2,410 4,910 8,880 14,400 29,500 53, ,270 2,240 4,560 8,260 13,400 27,500 49, ,120 1,980 4,050 7,320 11,900 24,300 44, ,020 1,800 3,670 6,630 10,700 22,100 40, ,650 3,370 6,100 9,880 20,300 36, ,540 3,140 5,680 9,190 18,900 34,300 54

37 36 of 107 9/13/2016 4:08 PM ,440 2,940 5,330 8,620 17,700 32, ,360 2,780 5,030 8,150 16,700 30, ,290 2,640 4,780 7,740 15,900 28, ,240 2,520 4,560 7,380 15,200 27, ,180 2,410 4,360 7,070 14,500 26, ,140 2,320 4,190 6,790 14,000 25, ,090 2,230 4,040 6,540 13,400 24, ,060 2,160 3,900 6,320 13,000 23, ,020 2,090 3,780 6,110 12,600 22, ,020 3,660 5,930 12,200 22, ,960 3,550 5,760 11,800 21, , ,910 3,460 5,600 11,500 20, , ,810 3,280 5,320 10,900 19, , ,730 3,130 5,070 10,400 18, , ,660 3,000 4,860 9,980 18, , ,590 2,880 4,670 9,590 17, , ,530 2,780 4,500 9,240 16, , ,480 2,680 4,340 8,920 16, , ,430 2,590 4,200 8,630 15, , ,390 2,520 4,070 8,370 15, , ,350 2,440 3,960 8,130 14, ,000 NA ,310 2,380 3,850 7,910 14, NA: A flow of less than 10 cfh. Note: All table entries are rounded to 3 significant digits. Table 6.2.1(c) Schedule 40 Metallic Pipe Gas: Natural Inlet Pressure: Less than 2 psi Pressure Drop: 3.0 in. w.c. Specific Gravity: 0.60 INTENDED USE: Initial supply pressure of 8.0 in. w.c. or greater Pipe Size (in.) Nominal: Actual ID: Length (ft) Capacity in Thousands of Btu per Hour ,790 3,670 5,500 10,600 16,900 29,800 60, ,230 2,520 3,780 7,280 11,600 20,500 41, ,030 3,030 5,840 9,310 16,500 33, ,730 2,600 5,000 7,970 14,100 28, ,540 2,300 4,430 7,060 12,500 25, ,390 2,090 4,020 6,400 11,300 23, ,280 1,920 3,690 5,890 10,400 21, ,190 1,790 3,440 5,480 9,690 19, ,120 1,670 3,230 5,140 9,090 18, ,060 1,580 3,050 4,860 8,580 17,500

38 37 of 107 9/13/2016 4:08 PM Gas: Natural Inlet Pressure: Less than 2 psi Pressure Drop: 3.0 in. w.c. Specific Gravity: 0.60 INTENDED USE: Initial supply pressure of 8.0 in. w.c. or greater Pipe Size (in.) Nominal: Actual ID: Length (ft) Capacity in Thousands of Btu per Hour ,400 2,700 4,300 7,610 15, ,270 2,450 3,900 6,890 14, ,170 2,250 3,590 6,340 12, ,090 2,090 3,340 5,900 12, ,860 2,960 5,230 10, ,680 2,680 4,740 9, ,550 2,470 4,360 8, ,440 2,290 4,050 8, ,350 2,150 3,800 7, ,280 2,030 3,590 7, ,210 1,930 3,410 6, ,160 1,840 3,260 6, ,110 1,760 3,120 6, ,060 1,690 3,000 6, ,020 1,630 2,890 5, ,580 2,790 5, ,530 2,700 5, ,480 2,610 5, ,440 2,540 5, ,400 2,470 5, ,330 2,350 4, ,270 2,240 4, ,210 2,140 4, ,160 2,060 4, ,120 1,980 4, ,080 1,920 3, ,050 1,850 3, ,020 1,800 3, ,750 3, ,700 3,460 Note: All table entries are rounded to 3 significant digits. Table 6.2.1(d) Schedule 40 Metallic Pipe Gas: Natural Inlet Pressure: Less than 2 psi Pressure Drop: 6.0 in. w.c.

39 38 of 107 9/13/2016 4:08 PM Specific Gravity: 0.6 INTENDED USE: Initial supply pressure of 11.0 in. w.c. or greater Pipe Size (in.) Nominal: ½ ¾ 1 1¼ 1½ 2 2½ 3 4 Actual ID: Length (ft) Capacity in Cubic Feet of Gas per Hour ,380 2,600 5,340 8,000 15,400 24,600 43,400 88, ,790 3,670 5,500 10,600 16,900 29,800 60, ,440 2,950 4,410 8,500 13,600 24,000 48, ,230 2,520 3,780 7,280 11,600 20,500 41, ,090 2,240 3,350 6,450 10,300 18,200 37, ,030 3,030 5,840 9,310 16,500 33, ,860 2,790 5,380 8,570 15,100 30, ,730 2,600 5,000 7,970 14,100 28, ,630 2,440 4,690 7,480 13,200 27, ,540 2,300 4,430 7,060 12,500 25, ,360 2,040 3,930 6,260 11,100 22, ,230 1,850 3,560 5,670 10,000 20, ,140 1,700 3,270 5,220 9,230 18, ,056 1,580 3,050 4,860 8,580 17, ,400 2,700 4,300 7,610 15, ,270 2,450 3,900 6,890 14, ,170 2,250 3,590 6,340 12, ,090 2,090 3,340 5,900 12, ,020 1,960 3,130 5,540 11, ,860 2,960 5,230 10, ,760 2,810 4,970 10, ,680 2,680 4,740 9, ,610 2,570 4,540 9, ,550 2,470 4,360 8, ,490 2,380 4,200 8, ,440 2,290 4,050 8, ,390 2,220 3,920 8, ,350 2,150 3,800 7, ,310 2,090 3,690 7,540 1, ,280 2,030 3,590 7,330 1, ,210 1,930 3,410 6,960 1, ,160 1,840 3,260 6,640 1, ,110 1,760 3,120 6,360 1, ,060 1,690 3,000 6,110 1, ,020 1,630 2,890 5,890 1, ,580 2,790 5,680 1, ,530 2,700 5,500 1, ,480 2,610 5,330

40 39 of 107 9/13/2016 4:08 PM 1, ,440 2,540 5,180 2, ,400 2,470 5,040 Note: All table entries are rounded to 3 significant digits. Table 6.2.1(e) Schedule 40 Metallic Pipe Gas: Natural Inlet Pressure: 2.0 psi Pressure Drop: 1.0 psi Specific Gravity: 0.60 Pipe Size (in.) Nominal: Actual ID: Length (ft) Capacity in Cubic Feet of Gas per Hour 10 1,510 3,040 5,560 11,400 17,100 32,900 52,500 92, , ,070 2,150 3,930 8,070 12,100 23,300 37,100 65, , ,760 3,210 6,590 9,880 19,000 30,300 53, , ,520 2,780 5,710 8,550 16,500 26,300 46,400 94, ,360 2,490 5,110 7,650 14,700 23,500 41,500 84, ,240 2,270 4,660 6,980 13,500 21,400 37,900 77, ,150 2,100 4,320 6,470 12,500 19,900 35,100 71, ,080 1,970 4,040 6,050 11,700 18,600 32,800 67, ,010 1,850 3,810 5,700 11,000 17,500 30,900 63, ,710 3,510 5,260 10,100 16,100 28,500 58, ,530 3,140 4,700 9,060 14,400 25,500 52, ,370 2,820 4,220 8,130 13,000 22,900 46, ,270 2,601 3,910 7,530 12,000 21,200 43, ,170 2,410 3,610 6,960 11,100 19,600 40, ,040 2,140 3,210 6,180 9,850 17,400 35, ,940 2,910 5,600 8,920 15,800 32, ,790 2,670 5,150 8,210 14,500 29, ,660 2,490 4,790 7,640 13,500 27, ,560 2,330 4,500 7,170 12,700 25, ,470 2,210 4,250 6,770 12,000 24, ,400 2,090 4,030 6,430 11,400 23, ,330 2,000 3,850 6,130 10,800 22, ,280 1,910 3,680 5,870 10,400 21, ,230 1,840 3,540 5,640 9,970 20, ,180 1,770 3,410 5,440 9,610 19, ,140 1,710 3,290 5,250 9,280 18, ,100 1,650 3,190 5,080 8,980 18, ,070 1,600 3,090 4,930 8,710 17, ,040 1,560 3,000 4,780 8,460 17,200 1, ,010 1,520 2,920 4,650 8,220 16,800 1, ,440 2,770 4,420 7,810 15,900 1, ,370 2,640 4,220 7,450 15,200

41 40 of 107 9/13/2016 4:08 PM Gas: Natural Inlet Pressure: 2.0 psi Pressure Drop: 1.0 psi Specific Gravity: 0.60 Pipe Size (in.) Nominal: Actual ID: Length (ft) Capacity in Cubic Feet of Gas per Hour 1, ,320 2,530 4,040 7,140 14,600 1, ,260 2,430 3,880 6,860 14,000 1, ,220 2,340 3,740 6,600 13,500 1, ,180 2,260 3,610 6,380 13,000 1, ,140 2,190 3,490 6,170 12,600 1, ,100 2,120 3,390 5,980 12,200 1, ,070 2,060 3,290 5,810 11,900 2, ,040 2,010 3,200 5,650 11,500 Note: All table entries are rounded to 3 significant digits. Table 6.2.1(f) Schedule 40 Metallic Pipe Gas: Natural Inlet Pressure: 3.0 psi Pressure Drop: 2.0 psi Specific Gravity: 0.60 Pipe Size (in.) Nominal: Actual ID: Length (ft) Capacity in Cubic Feet of Gas per Hour 10 2,350 4,920 9,270 19,000 28,500 54,900 87, , , ,620 3,380 6,370 13,100 19,600 37,700 60, , , ,300 2,720 5,110 10,500 15,700 30,300 48,300 85, , ,110 2,320 4,380 8,990 13,500 25,900 41,300 73, , ,060 3,880 7,970 11,900 23,000 36,600 64, , ,870 3,520 7,220 10,800 20,800 33,200 58, , ,720 3,230 6,640 9,950 19,200 30,500 54, , ,600 3,010 6,180 9,260 17,800 28,400 50, , ,500 2,820 5,800 8,680 16,700 26,700 47,100 96, ,420 2,670 5,470 8,200 15,800 25,200 44,500 90, ,250 2,360 4,850 7,270 14,000 22,300 39,500 80, ,140 2,140 4,400 6,590 12,700 20,200 35,700 72, ,050 1,970 4,040 6,060 11,700 18,600 32,900 67, ,830 3,760 5,640 10,900 17,300 30,600 62, ,620 3,330 5,000 9,620 15,300 27,100 55, ,470 3,020 4,530 8,720 13,900 24,600 50, ,350 2,780 4,170 8,020 12,800 22,600 46,100

MEMORANDUM. NFPA 1936 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 1936 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fire Department Rescue Tools

More information

National Fire Protection Association

National Fire Protection Association National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Liquefied Petroleum

More information

MEMORANDUM. NFPA Technical Committee on Aircraft Rescue and Fire Fighting. NFPA 414 First Draft TC Supplemental Ballot Results FR-6 (A2016)

MEMORANDUM. NFPA Technical Committee on Aircraft Rescue and Fire Fighting. NFPA 414 First Draft TC Supplemental Ballot Results FR-6 (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Aircraft Rescue and Fire

More information

Description. The correlating committee may override this FR with a First Correlating Revision or with a Committee Note

Description. The correlating committee may override this FR with a First Correlating Revision or with a Committee Note First Revision No. 124-NFPA 85-2013 [ Global Input ] Revise all fuel gas system diagrams in mandatory and annex sections to identify the equipment isolation valve or valves. Change "Outside Boiler Room"

More information

A. This Section includes natural gas piping, specialties, and accessories within the building.

A. This Section includes natural gas piping, specialties, and accessories within the building. SECTION 226313 NATURAL GAS PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems.

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems. SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS A. Section 099000

More information

Standard Specification for Threaded Couplings, Steel, Black or Zinc-Coated (Galvanized) Welded or Seamless, for Use in Steel Pipe Joints 1

Standard Specification for Threaded Couplings, Steel, Black or Zinc-Coated (Galvanized) Welded or Seamless, for Use in Steel Pipe Joints 1 Designation: A 865 97 AMERICAN SOCIETY FOR TESTING AND MATERIALS 00 Barr Harbor Dr., est Conshohocken, PA 9428 Reprinted from the Annual Book of ASTM Standards. Copyright ASTM Standard Specification for

More information

Second Revision No. 3-NFPA [ New Section after ]

Second Revision No. 3-NFPA [ New Section after ] Second Revision No. 3-NFPA 30-2013 [ New Section after 17.3.1 ] 17.3.1.1 Permanent process plant buildings shall be located in accordance with the requirements of API RP 752, Management of Hazards Associated

More information

Second Correlating Revision No. 3 NFPA [ Section No ]

Second Correlating Revision No. 3 NFPA [ Section No ] Second Correlating Revision No. 3 NFPA 1991 2015 [ Section No. 2.3.2 ] 2.3.2 ASTM Publications. American Society for Testing and Materials, 100 Barr Harbor Drive, West Conshohocken, PA 19428 2959. ASTM

More information

Natural Gas Reference Guide

Natural Gas Reference Guide Natural Gas Reference Guide NICOR GAS NATURAL GAS REFERENCE GUIDE A guide to industry code specifications and guidelines Always check your local building code department to ensure correctness of information

More information

SECTION FACILITY NATURAL GAS PIPING

SECTION FACILITY NATURAL GAS PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

First Correlating Revision No. 1-NFPA [ Section No ]

First Correlating Revision No. 1-NFPA [ Section No ] First Correlating Revision No. 1-NFPA 85-2013 [ Section No. 3.3.52.1 ] 3.3.52.1 Booster Fan. A device fan used to assist in the supply of air to, or the removal of flue gas products from, the combustion

More information

SECTION FACILITY FUEL - NATURAL GAS PIPING AND SYSTEMS

SECTION FACILITY FUEL - NATURAL GAS PIPING AND SYSTEMS SECTION 23 11 23 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Fuel Pipe and Pipe Fittings - General 2. Steel Pipe and Fittings, Above Grade 3. Steel Pipe and Fittings, Below Grade 4. Polyethylene

More information

NFPA 105 Public Input Report Page 1 of 22

NFPA 105 Public Input Report Page 1 of 22 of 20 11/4/2016 5:57 PM Public Input No. 6-NFPA 105-2016 [ Section No. 2.3.2 ] 2.3.2 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. ANSI/UL 10B, Standard

More information

GENERAL-SERVICE COMPRESSED-AIR PIPING SECTION GENERAL-SERVICE COMPRESSED-AIR PIPING PART 1 - GENERAL

GENERAL-SERVICE COMPRESSED-AIR PIPING SECTION GENERAL-SERVICE COMPRESSED-AIR PIPING PART 1 - GENERAL 13686.00 GENERAL-SERVICE COMPRESSED-AIR PIPING 221513-1 SECTION 22 1513 - GENERAL-SERVICE COMPRESSED-AIR PIPING 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract,

More information

CHAPTER 13 FUEL GAS PIPING

CHAPTER 13 FUEL GAS PIPING .0 Scope General. Part I Fuel Piping.. Coverage of Piping System. Coverage of piping systems shall extend from the point of delivery to the appliance connections with each device. For other than undiluted

More information

SECTION FUEL GAS PIPING

SECTION FUEL GAS PIPING SECTION 15194 PART I - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to

More information

First Revision No. 9-NFPA [ Chapter 2 ]

First Revision No. 9-NFPA [ Chapter 2 ] 1 of 14 12/30/2015 11:56 AM First Revision No. 9-NFPA 1127-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Aircraft Rescue

More information

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR PIPING FOR LABORATORY FACILITIES Page 226113-1 SECTION 226113 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Second Revision No. 7-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement 9/17/2015 2:57 PM

Second Revision No. 7-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement 9/17/2015 2:57 PM Second Revision No. 7-NFPA 1142-2015 [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 1, Fire Code, 2015 edition. NFPA 13D, Standard for the Installation of Sprinkler Systems

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-32159-8 Any reference to SABS 1551-1 is deemed to be a reference to this standard (Government Notice No. 1373 of 8 November 2002) SOUTH AFRICAN NATIONAL STANDARD Check valves (flanged and

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 23 22 13 STEAM AND CONDENSATE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

13900 Series. Consolidated * Valves. Pilot-Operated Safety Relief Valve

13900 Series. Consolidated * Valves. Pilot-Operated Safety Relief Valve GE Oil & Gas Technical Specifications 08/2014 Consolidated * Valves 13900 Series Pilot-Operated Safety Relief Valve Designed specifically for high capacity steam applications, this series of valves contributes

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481038 Model PVF and PVG Indirect Gas-Fired Heat Modules Indirect Gas-Fired Furnaces Installation, Operation and Maintenance Manual Please read and save these instructions for future reference.

More information

SECTION FACILITY FUEL OIL PIPING

SECTION FACILITY FUEL OIL PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

California Department of Food and Agriculture Division of Measurement Standards Petroleum Products Program Fuels and Lubricants Laboratory

California Department of Food and Agriculture Division of Measurement Standards Petroleum Products Program Fuels and Lubricants Laboratory California Department of Food and Agriculture Division of Measurement Petroleum Products Program Fuels and Lubricants Laboratory Development of Fuel Quality Specification for Ammonia NH3 Fuel Association

More information

Joint Meeting Standards Working Group Report of the second meeting, Bern, March 2003

Joint Meeting Standards Working Group Report of the second meeting, Bern, March 2003 Joint Meeting of the RID Safety Committee INF. 48 and the Working Party on the Transport of Dangerous Goods (Bern, 24-28 March 2003) Joint Meeting Standards Working Group Report of the second meeting,

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Jeanne Moreau DATE: April 23, 2010 SUBJECT: NFPA 85 F10 ROC Letter Ballot The ROC letter ballot for

More information

COMMERCIAL ITEM DESCRIPTION HOSE ASSEMBLY, NONMETALLIC, FIRE FIGHTING, WITH COUPLINGS

COMMERCIAL ITEM DESCRIPTION HOSE ASSEMBLY, NONMETALLIC, FIRE FIGHTING, WITH COUPLINGS [INCH-POUND] A-A-59226 May 18, 1998 SUPERSEDING ZZ-H-451G January 13, 1984 COMMERCIAL ITEM DESCRIPTION HOSE ASSEMBLY, NONMETALLIC, FIRE FIGHTING, WITH COUPLINGS The General Services Administration has

More information

ADOPTED REGULATION OF THE STATE BOARD OF AGRICULTURE. LCB File No. R Effective February 20, 2013

ADOPTED REGULATION OF THE STATE BOARD OF AGRICULTURE. LCB File No. R Effective February 20, 2013 ADOPTED REGULATION OF THE STATE BOARD OF AGRICULTURE LCB File No. R106-10 Effective February 20, 2013 EXPLANATION Matter in italics is new; matter in brackets [omitted material] is material to be omitted.

More information

KKAI Report No Rev 1 Prepared for BioHeatUSA April 28, 2009

KKAI Report No Rev 1 Prepared for BioHeatUSA April 28, 2009 1. Summary... 3 2. Background... 3 3. Scope... 3 4. European Suppliers... 4 5. Materials... 4 6. Design... 4 7. Fabrication... 5 8. Examination... 6 9. Inspection... 6 10. Testing... 8 11. Quality Control

More information

Second Revision No. 25-NFPA [ Section No ]

Second Revision No. 25-NFPA [ Section No ] Second Revision No. 25-NFPA 79-2013 [ Section No. 1.1.1 ] 1.1.1 The provisions of this standard shall apply to the electrical/electronic equipment, apparatus, or systems of industrial machines operating

More information

First Revision No. 1-NFPA [ Global Input ]

First Revision No. 1-NFPA [ Global Input ] Page 1 of 228 First Revision No. 1-NFPA 1906-2013 [ Global Input ] Provide missing extract references in NFPA 1906 from NFPA 1901 where applicable. The list below contains some of the sections identified

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 481038 Model PVF(-H) and PVG Indirect Gas-Fired Heat Modules Indirect Gas-Fired Furnaces Installation, Operation and Maintenance Manual Please read and save these instructions for future reference.

More information

Electroinsulating Footwear and Overboots for Live Working Practical Experience and Evolution of Standards

Electroinsulating Footwear and Overboots for Live Working Practical Experience and Evolution of Standards Electroinsulating Footwear and Overboots for Live Working Practical Experience and Evolution of Standards Marek Łoboda, Bogumił Dudek Polish Committee of Standardization TC 72 Equipment for Live Working

More information

Table of Contents. Introduction. Description. Greater Total System Efficiency. Improved Design. Easy Installation and Maintenance

Table of Contents. Introduction. Description. Greater Total System Efficiency. Improved Design. Easy Installation and Maintenance Features & Benefits Table of Contents Features & Benefits................................................................ 13900.1 Scope of Design...................................................................

More information

Saf-T Vent EZ Seal. Technical and Dimensional Data. Single Wall AL 29-4C Stainless Steel Special Gas Vent

Saf-T Vent EZ Seal. Technical and Dimensional Data. Single Wall AL 29-4C Stainless Steel Special Gas Vent Technical and Dimensional Data Saf-T Vent EZ Seal Single Wall AL 29-4C Stainless Steel Special Gas Vent 130 Industrial Boulevard Turners Falls, MA 01376 Copyright 2001 Heat-fab, Incorporated Saf-T Vent

More information

GAS DISTRIBUTION PRODUCTS METER RISERS

GAS DISTRIBUTION PRODUCTS METER RISERS GAS DISTRIBUTION PRODUCTS METER RISERS INDUSTRIES ABOUT US THE ULTIMATE CONNECTION Our Company Continental Industries, headquartered in Tulsa, Oklahoma, was formed in 1958 and is today a leading manufacturer

More information

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC VALVES

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION HVAC VALVES DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 05 23 PART 1 GENERAL 1.01 DESCRIPTION A. Provide valves for the following systems: 1. Heating Hot Water 2. Chilled Water 3. Condenser

More information

Technical Information

Technical Information IMPORTANT INFORMATION: Product must be installed and used in strict conformance with NFPA Pamphlet 58 and/or NFPA pamphlet 54 and all other codes, regulations and manufacturer recommendations. Failure

More information

Committee on NFPA 31

Committee on NFPA 31 Committee on NFPA 31 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Liquid Fuel Burning Equipment Jeanne Moreau-Correia DATE: September 24, 2009 SUBJECT: NFPA 31 ROP Letter Ballot The ROP letter

More information

394C. Series 6400/6600. Safety Valves for Power Boiler Service

394C. Series 6400/6600. Safety Valves for Power Boiler Service 394C Series 6400/6600 Safety Valves for Power Boiler Service Series 6400/6600 Designed with the user in mind, Series 6400 and 6600 safety valves represent the most advanced technology in valves designed

More information

SECTION METERS AND GAGES FOR PLUMBING PIPING

SECTION METERS AND GAGES FOR PLUMBING PIPING PART 1 GENERAL 1.01 SECTION INCLUDES A. Positive displacement meters. B. Flow meters. SECTION 22 0519 METERS AND GAGES FOR C. Pressure gages and pressure gage taps. D. Thermometers and thermometer wells.

More information

Welded and Seamless Wrought Steel Pipe

Welded and Seamless Wrought Steel Pipe (Revision of ASME B36.10M-2000) Welded and Seamless Wrought Steel Pipe AN AMERICAN NATIONAL STANDARD ment Copyright provided ASME by IHS International Licensee=Bureau Veritas/5959906001, 10/28/2004 6:59

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 6 From: Kimberly Shea, Project Administrator

More information

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY SECTION 230533 - PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pressure gages. 2. Pressure gage taps. 3. Thermometers. 4. Thermometer supports. 5. Test plugs. 6. Static pressure

More information

Crosby Series 800 and 900 OMNI-TRIM Pressure Relief Valves. Flow Control

Crosby Series 800 and 900 OMNI-TRIM Pressure Relief Valves. Flow Control Crosby s Series 800 adjustable blowdown and Series 900 fixed blowdown OMNI-TRIM full nozzle pressure relief valves have a simplified, single trim design with superior application versatility. Features

More information

Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE)

Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE) Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE) Town of Lake George, New York Compliance with the following permit will allow the installation and operation of electric

More information

VMA Presentation Pressure Seal (MSS-SP-144) and ASME B Update Carlos E. Davila, PE March 2014

VMA Presentation Pressure Seal (MSS-SP-144) and ASME B Update Carlos E. Davila, PE March 2014 VMA Presentation Pressure Seal (MSS-SP-144) and ASME B16-2013 Update Carlos E. Davila, PE March 2014 CRANE FLUID HANDLING Fugitive Emissions Update EPA has been reducing the allowable fugitive emissions

More information

Installation Manual. English. French

Installation Manual. English. French Installation Manual For model N400 - a 4.5 cu. ft., 2-way or 3-way, refrigerator. For model N500 - a 5.5 cu. ft., 2-way or 3-way, refrigerator. For model N510 - a 5.5 cu. ft., 2-way or 3-way, refrigerator.

More information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 7: TUBING AND PIPING

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 7: TUBING AND PIPING SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 7: TUBING AND PIPING UNIT OBJECTIVES After studying this unit you should be able to list the different types of tubing used in heating, air conditioning,

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1012 - REVISED: 2009 Backflow Preventers with an Intermediate Atmospheric Vent Separate, complete laboratory evaluation

More information

50 HERTZ METRIC BLOWER

50 HERTZ METRIC BLOWER CAPACITIES 50 HERTZ METRIC BLOWER Pressure Range 500mm 20 wc 12 osi 700mm 27 wc 16 osi 900mm 35 wc 20 osi 1100mm 43 wc 24 osi Model Number TBA 500-1.5 TBA 500-2.2 TBA 500-3 TBA 500-4 TBA 500-5.5 TBA 500-

More information

Date: Project #: Engineer: Prepared By: Bid Date:

Date: Project #: Engineer: Prepared By: Bid Date: NEOTHERM Hydronic Boiler NTH Hydronic Boiler Indoor Sizes 285-850 Date: Submittal Data Project #: Engineer: Project Name: Prepared By: Location: Bid Date: Contractor: Standard Equipment High condensing

More information

CHEVRON PHILLIPS CHEMICAL PIPELINE COMPANY LLC PETROCHEMICAL PRODUCTS (AS DEFINED HEREIN)

CHEVRON PHILLIPS CHEMICAL PIPELINE COMPANY LLC PETROCHEMICAL PRODUCTS (AS DEFINED HEREIN) (Cancels T.R.S. No. 48.0.0) CHEVRON PHILLIPS CHEMICAL PIPELINE COMPANY LLC LOCAL TARIFF Applying on Intrastate Transportation of PETROCHEMICAL PRODUCTS (AS DEFINED HEREIN) [C] Ethane-Propane Mixture System

More information

CASES OF THE B16 VALVE, FLANGES, FITTINGS AND GASKETS STANDARDS. Approval Date: December 16, 2013

CASES OF THE B16 VALVE, FLANGES, FITTINGS AND GASKETS STANDARDS. Approval Date: December 16, 2013 Approval Date: December 16, 2013 Cases will remain available for use until annulled by the applicable Standards Committee B16 Case 1 High Strength/High Temperature Material ASME B16.34 Group 3 Valves ASME

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IS0 7483 First edition 1991-10-01 --- ---- -.----.----_-- -_ ----- - - Dimensions of gaskets for use with flanges to IS0 7005 Dimensions des joints B utiliser avec les brides de

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Fighter

More information

FREE STANDING WORK STATION JIB CRANE

FREE STANDING WORK STATION JIB CRANE SECTION 14661 FREE STANDING WORK STATION JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and

More information

Direct or Non-Direct Venting

Direct or Non-Direct Venting Venting Direct or Non-Direct Venting All furnaces are dual certified, and built with a 2 vent/ intake pipe and connectors. Transitioning from 2 to 3 PVC pipe should be done as close to the furnace as possible.

More information

Panel 11 FD Agenda Page 1

Panel 11 FD Agenda Page 1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NEC Code-Making Panel 11 First Draft Meeting January 15-17, 2015

More information

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING SECTION 220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING PART 1 - GENERAL 1.1 SUMMARY A. General: Refer to General and Special Condition Specifications in Division 01 for all required submissions of this

More information

E. Augusta, Spokane, WA (509) E. Augusta, Spokane, WA (509)

E. Augusta, Spokane, WA (509) E. Augusta, Spokane, WA (509) Notice of Construction (NOC) Approval Issued in accordance with: Chapter 70.94 RCW, SRCAA Regulation I, Article V, Chapter 173-400 WAC, and Chapter 173-491 WAC 3104 3104 E. Augusta, Spokane, WA 99207 (509)

More information

ELECTRICAL GENERATING STEAM BOILERS, REPLACEMENT UNITS AND NEW UNITS (Adopted 1/18/94; Rev. Adopted & Effective 12/12/95)

ELECTRICAL GENERATING STEAM BOILERS, REPLACEMENT UNITS AND NEW UNITS (Adopted 1/18/94; Rev. Adopted & Effective 12/12/95) RULE 69. ELECTRICAL GENERATING STEAM BOILERS, REPLACEMENT UNITS AND NEW UNITS (Adopted 1/18/94; Rev. Adopted & Effective 12/12/95) (a) APPLICABILITY (1) Except as provided in Section (b) or otherwise specified

More information

BLUE ULTRA Pipe & Tubing contains no regrind resin in its manufacture

BLUE ULTRA Pipe & Tubing contains no regrind resin in its manufacture BLUE ULTRA is extruded using current state of the art 100% pure PE4710 virgin resin with decades of successful history - no extra wall thickness is required to retain its extreme level of UV protection

More information

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems.

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems. SECTION 220523 - PLUMBING VALVES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball valves. 2. Butterfly valves. 3. Swing check valves. 4. Spring loaded check valves. 5. Water pressure reducing

More information

GAS DISTRIBUTION PRODUCTS CON-STAB ID SEAL FITTINGS

GAS DISTRIBUTION PRODUCTS CON-STAB ID SEAL FITTINGS GAS DISTRIBUTION PRODUCTS CON-STAB ID SEAL FITTINGS CONTINENTAL INDUSTRIES ABOUT US THE ULTIMATE CONNECTION Our Company Continental Industries, headquartered in Tulsa, Oklahoma, was formed in 1958 and

More information

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data Worldwide Contacts www.tyco-fire.com Model CV-FR Grooved-End Riser Check Valves Inch to Inch (DN0 to DN00) General Description The TYCO Model CV-FR Grooved- End Riser Check Valve is a compact and rugged

More information

SELKIRK CORP INSTALLATION INSTRUCTION SUPPLEMENT MODEL G - CHIMNEY LINER

SELKIRK CORP INSTALLATION INSTRUCTION SUPPLEMENT MODEL G - CHIMNEY LINER SELKIRK CORP MODEL G - CHIMNEY LINER These instructions are supplemental to the General Installation Instructions for Selkirk Model G, PS, IPS and ZC Single Wall, Double Wall Air & Fiber Insulated Positive

More information

GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models)

GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models) FORM NO. GSC-515 GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models) TWO STAGE DOWNFLOW GAS FURNACES The Sure Comfort 2-Stage line of downflow gas furnaces

More information

DISCUSSION DOCUMENT. New standards for off-road small spark-ignition engines under consideration

DISCUSSION DOCUMENT. New standards for off-road small spark-ignition engines under consideration DISCUSSION DOCUMENT New standards for off-road small spark-ignition engines under consideration Background The Off-Road Small Spark-Ignition Engine Emission Regulations (hereinafter referred to as the

More information

Table of Contents GF801U Series

Table of Contents GF801U Series FORM NO. GSC-520 GF801U SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] 80% A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES The Sure Comfort line of upflow/horizontal gas furnaces are designed

More information

SAMPLE. Engine Driven Welding Power Sources. Topic 5. Welding Process Training Series

SAMPLE. Engine Driven Welding Power Sources. Topic 5. Welding Process Training Series Topic 5. Welding Process Training Series Engine Driven Welding Power Sources Prepared by the Miller Electric Mfg. Co. Training Department. 2014 Miller Electric Mfg. Co. The contents of this publication

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-5 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR AIR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for difficult

More information

STANDARDS and SPECIFICATIONS

STANDARDS and SPECIFICATIONS ANSI (American National Standards Institute) ANSI B31.4 - Liquid petroleum transportation piping system. ANSI B31.4 - Gas transmission and distribution piping system. API (American Petroleum Institute)

More information

NEC Code-Making Panel 11. Second Draft Meeting Agenda. November 5-7, San Diego, CA Introduction of Members and Guests

NEC Code-Making Panel 11. Second Draft Meeting Agenda. November 5-7, San Diego, CA Introduction of Members and Guests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NEC Code-Making Panel 11 Second Draft Meeting Agenda November 5-7, 2015

More information

DIN 2445 Part-1 SEAMLESS STEEL TUBES FOR DYNAMIC LOADS HOT FINISHED TUBES NOMINAL PRESSURES 100 TO 400

DIN 2445 Part-1 SEAMLESS STEEL TUBES FOR DYNAMIC LOADS HOT FINISHED TUBES NOMINAL PRESSURES 100 TO 400 DIN Part- SEAMLESS STEEL TUBES FOR DYNAMIC LOADS HOT FINISHED TUBES NOMINAL PRESSURES 00 TO 00. General information This Standard includes a suary of hot finished seamless steel tubes for dynamic loads,

More information

A. This Section includes piping and related specialties for general-service compressed-air systems operating at 150 psig or less.

A. This Section includes piping and related specialties for general-service compressed-air systems operating at 150 psig or less. SECTION 221513 - COMPRESSED-AIR PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes piping and related specialties for general-service compressed-air systems operating at 150 psig or less. 1.2

More information

IMMERSION FIRED HOT WATER BOILER

IMMERSION FIRED HOT WATER BOILER 918 W WALNUT ST, DANVILLE, KENTUCKY 40422-0048 PHONE (859) 236-3181 www.sellersmfg.com SPECIFICATION SHEET NO. 8301 IMMERSION FIRED HOT WATER BOILER GENERAL DESCRIPTION The Sellers immersion fired S-Series

More information

AIR QUALITY PERMIT. Kennesaw State University - Marietta Campus

AIR QUALITY PERMIT. Kennesaw State University - Marietta Campus AIR QUALITY PERMIT Permit No. Effective Date February 11, 2016 In accordance with the provisions of the Georgia Air Quality Act, O.C.G.A. Section 12-9-1, et seq and the Rules, Chapter 391-3-1, adopted

More information

MILITARY STANDARD SCHEDULE OF PIPING, VALVES, FITTINGS, AND ASSOCIATED PIPING COMPONENTS FOR NAVAL SURFACE SHIPS

MILITARY STANDARD SCHEDULE OF PIPING, VALVES, FITTINGS, AND ASSOCIATED PIPING COMPONENTS FOR NAVAL SURFACE SHIPS NOTICE OF CHANGE INCH-POUND ) 8 July 2002 MILITARY STANDARD SCHEDULE OF PIPING, VALVES, FITTINGS, AND ASSOCIATED PIPING COMPONENTS FOR NAVAL SURFACE SHIPS TO ALL HOLDERS OF : 1. THE FOLLOWING PAGES OF

More information

Model ND-2 Specification

Model ND-2 Specification Model ND-2 Specification The model ND-2 is an exhaust only canopy hood rated for all types of cooking equipment. The hood shall have the size, shape and performance specified on drawings. Construction

More information

MSC Guidelines for Fuel Oil Systems

MSC Guidelines for Fuel Oil Systems P. W. Gooding, CDR, Chief, Engineering Division References: Contact Information: a. 46 CFR 56.50-60 Systems containing oil (Subchapter F) b. 46 CFR 56.50-65 Burner fuel-oil service systems (Subchapter

More information

cs200 series commercial / Industrial pressure reducing regulators

cs200 series commercial / Industrial pressure reducing regulators November 2013 cs200 series commercial / Industrial pressure reducing regulators P1188 Figure 1. Typical CS200 Series Pressure Reducing Regulator Features and Benefits Wide Range of Body Sizes and End Connections

More information

PTFE Lined Pipe and Fittings

PTFE Lined Pipe and Fittings Allied Supreme Corp. - 1 - PTFE Lined Pipe and Fittings Allied Supreme Corp. - 2 - Index Specification For PTFE Lined Pipe and Fittings..3 PTFE Lined Pipe 7 PTFE Lined 90 Elbow. 8 PTFE Lined 45 Elbow.9

More information

NEC Code-Making Panel 5. Second Draft Meeting Agenda. November 9-14, San Diego, CA Introduction of Members and Guests

NEC Code-Making Panel 5. Second Draft Meeting Agenda. November 9-14, San Diego, CA Introduction of Members and Guests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NEC Code-Making Panel 5 Second Draft Meeting Agenda November 9-14, 2015

More information

Product Data. S Variable-speed ECM blower motor. S Two heating stages. S Humidity control when using a humidity sensing thermostat

Product Data. S Variable-speed ECM blower motor. S Two heating stages. S Humidity control when using a humidity sensing thermostat PG8MVA PG8JVA 4 --- WAY MULTIPOISE INDUCED---COMBUSTION GAS FURNACE INPUT CAPACITIES: 70,000 thru 135,000 Btuh SERIES A Product Data multipoise design, through -the-furnace downflow venting, 13 different

More information

ASME B31.8 INTERPRETATIONS VOLUME 13

ASME B31.8 INTERPRETATIONS VOLUME 13 ASME B31.8 INTERPRETATIONS VOLUME 13 Replies to Technical Inquiries July 2001 Through December 2003 Interpretations 13-1 Through 13-8 It has been agreed to publish intepretations issued by the B31 Committee

More information

Automatic Roof Door Vents

Automatic Roof Door Vents DATA SHEET Automatic Roof Door Vents Features n UL Listed for use as an automatic smoke vent n FM Approved as an automatic door vent for use in high expansion foam systems n Available in multiple sizes

More information

GROOVED COUPLINGS - STANDARD FLEXIBLE Model 101

GROOVED COUPLINGS - STANDARD FLEXIBLE Model 101 GROOVED COUPLINGS - STANDARD FLEXIBLE Model 101 Available Sizes 1" through 12" (25 through ) Pipe Material Carbon steel, Schedule 10, Schedule 40. For use with alternative materials and wall thicknesses

More information

COMMERCIAL ITEM DESCRIPTION DRY CLEANING AND DEGREASING SOLVENT, PD680

COMMERCIAL ITEM DESCRIPTION DRY CLEANING AND DEGREASING SOLVENT, PD680 NOT MEASUREMENT SENSITIVE 27 September 00 COMMERCIAL ITEM DESCRIPTION DRY CLEANING AND DEGREASING SOLVENT, PD680 The General Services Administration has authorized the use of this commercial item description

More information

SAN JOAQUIN VALLEY UNIFIED AIR POLLUTION CONTROL DISTRICT DRAFT STAFF REPORT

SAN JOAQUIN VALLEY UNIFIED AIR POLLUTION CONTROL DISTRICT DRAFT STAFF REPORT DRAFT STAFF REPORT Draft Amendments to Rule 4621 (Gasoline Transfer into Stationary Storage Containers, Delivery Vessels, and Bulk Plants) and Rule 4622 (Gasoline Transfer into Motor Vehicle Fuel Tanks)

More information

The requirements of this standard shall apply to the following coupling and adapters in the sizes defined in Section 1.1.

The requirements of this standard shall apply to the following coupling and adapters in the sizes defined in Section 1.1. NFPA STANDARDS DEVELOPMENT SITE SECOND DRAFT REPORT Closing Date: July 19, 2013 NOTE: All Public Comment must be received by 5:00 pm EST/EDST on the published Closing Date. NFPA 1963, Standard for Fire

More information

TRANSMITTAL THE COUNCIL SEP THE MAYOR TRANSMITTED FOR YOUR CONSIDERATION. PLEASE SEE ATTACHED. ERIC GARCET Mayor.

TRANSMITTAL THE COUNCIL SEP THE MAYOR TRANSMITTED FOR YOUR CONSIDERATION. PLEASE SEE ATTACHED. ERIC GARCET Mayor. TRANSMITTAL To: From: Date: THE COUNCIL SEP 3 0 2015 THE MAYOR TRANSMITTED FOR YOUR CONSIDERATION. PLEASE SEE ATTACHED. Ana Guerrero ERIC GARCET Mayor \ i BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN

More information

The Commonwealth of Massachusetts

The Commonwealth of Massachusetts The Commonwealth of Massachusetts DEPARTMENT OF PUBLIC UTILITIES D.P.U. 16-64-H November 6, 2017 Investigation of the Department of Public Utilities, on its own Motion, Commencing a Rulemaking pursuant

More information

Design and Construction Standards SECTION PLUMBING PIPING

Design and Construction Standards SECTION PLUMBING PIPING SECTION 15420 PLUMBING PIPING PART 1 GENERAL 1.1 SCOPE A. Work consists of all plumbing work indicated on drawings and specified herein. Included are requirements for fees/permits for installation and

More information

Standard Classification System for Carbon Blacks Used in Rubber Products 1

Standard Classification System for Carbon Blacks Used in Rubber Products 1 Designation: D 1765 04 Standard Classification System for Carbon Blacks Used in Rubber Products 1 This standard is issued under the fixed designation D 1765; the number immediately following the designation

More information

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications

Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer. Exhibit 2 System Specifications Executive Order VR-205-B VST Phase II EVR System with Hirt Thermal Oxidizer Exhibit 2 System Specifications This exhibit contains the installation, maintenance and compliance standards and specifications

More information