Distributed Power System SD3100 DC Power Modules

Size: px
Start display at page:

Download "Distributed Power System SD3100 DC Power Modules"

Transcription

1 Distributed Power System SD3100 DC Power Modules 1250A, 1650A, 3000A DC Instruction Manual S-3064

2 Throughout this manual, the following notes are used to alert you to safety considerations:! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product.! ATTENTION: Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. ATTENTION: Verify that all sources of AC and DC power are deenergized and locked out or tagged out in accordance with the requirements of ANSI/NFPA 70E, Part II. ATTENTION: The user must provide an external, hardwired stop circuit outside of the drive circuitry. This circuit must disable the system in case of improper operation. Uncontrolled machine operation may result if this procedure is not followed. Failure to observe this precaution could result in bodily injury. ATTENTION: The system may contain stored energy devices. To avoid the hazard of electrical shock, verify that all voltage on capacitros has been discharged before attempting to service, repair, or remove a drive system or its components. You should only attempt the procedures in this manual if you are qualified to do so and are familiar with solid-state control equipment and the safety procedures in publication 70E. ATTENTION: An incorrectly applied or incorrectly installed drive system can result in component damage and/or a reduction in product life. Wiring or application errors such as undersizing the motor, incorrect or inadequate AC supply, and excessive ambient temperatures can result in the malfunction of hte drive equipment. ATTENTION: The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. ATTENTION: This drive system contains parts and assemblies that are sensitive to ESD (electrostatic discharge). Static control precautions are required when installing, testing, or repairing this assembly. Component damage can result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Rockwell Automation publication , Guarding Against Electrostatic Damage, or another adequate handbook on ESD protection. The information in this users manual is subject to change without notice. AutoMax is a trademark of Rockwell Automation 1998 Rockwell International Corporation

3 CONTENTS Chapter 1 Chapter 2 Chapter 3 Introduction 1.1 Field Power Module Standard Features Optional Features Related Publications Terms Used in this Manual Mechanical/Electrical Description 2.1 Mechanical Overview Control Components Power Components Incoming Power Armature Power Components Field Power Module Components Electrical Overview A Power Module Description A Power Module Component Layout A Power Module Dimensions A Power Module Description A Power Module Component Layout A Power Module Dimensions A Power Module Description A Power Module Component Layout A Power Module Dimensions Installation Guidelines 3.1 Planning the Installation Physically Installing the Power Module Wiring AC Input Power to the Power Module AC Input Wire Selection Making an Input Entry Hole Connecting the AC Input Wires to the Busbars Wiring AC Input to the Field Power Module Installing the Field Isolation Transformer Wiring the Motor Selecting Wires for the Armature and Field Lines Connecting the Motor to the Power Module Installing Feedback Devices Meter Port Connections Grounding the Drive For Information on Initial Start-Up of the Drive Table of Contents I

4 Chapter 4 Maintenance and Troubleshooting 4.1 Recommended Test Equipment System Diagnostics Power Module Faults Shorted SCR Fault (Bit 0) AC Line Synchronization Fault (Bit 3) Instantaneous Overcurrent Fault (Bit 4) Conduction Timeout Fault (Bit 5) Loss of Field Fault (Bit 6) Power Module Warnings Three-phase Bridge SCR Not Firing Warning (Bit 0) Low Line Voltage/Phase Missing Warning (Bit 1) Synchronization Loss Fault Avoided Warning (Bit 3) Current Reference Limit Warning (Bit 4) Identification Test Error Warning (Bit 5) Field Power Module Overcurrent Warning (Bit 6) Fan Loss Warning (Bit 12) Component Replacement Spare Parts Kits PMI Regulator Parallel Gate Amplifier Field Power Module Replacing Internal Field Power Module AC Input Fuses Replacing Field Power Module Components Appendix A Technical Specifications... A-1 Appendix B Schematics... B-1 Appendix C Replacement Parts... C-1 Index...Index-1 II SD3100 Power Modules

5 List of Figures Figure 1.1 SD3100 Catalog Numbering Scheme Figure 2.1 SD3100 Power Module System Components Figure 2.2 Regulator Assembly Figure 2.3 Armature Bridge (Non-Regenerative) Figure 2.4 Armature Bridge (Regenerative) Figure A Power Module Component Layout Figure A Power Module Dimensions Figure A Power Module Component Layout Figure A Power Module Dimensions Figure A Power Module Component Layout Figure A Power Module Dimensions Figure 3.1 Area Available for Conduit Entry (Top View of Leftmost Bay) Figure 3.2 Field Terminal Wiring Figure 3.3 Drive I/O Connections (TB4) Figure 3.4 Resolver and Analog Input Connections (TB5) Figure 3.5 Meter Port Connections (TB6) Figure 3.6 SD3100 Grounding Figure A.1 Altitude Derating Chart...A-1 Figure A.2 Power Dissipation vs. Armature Current (1250A Power Module)...A-3 Figure A.3 Recommended Circuit Breaker Settings (1250A Power Module)...A-3 Figure A.4 AC Input Busbars (1250A Power Module)...A-4 Figure A.5 Power Dissipation vs. Armature Current (1650A Power Module)...A-6 Figure A.6 Recommended Circuit Breaker Settings (1650A Power Module)...A-6 Figure A.7 AC Input Busbars (1650A Power Module)...A-7 Figure A.8 Power Dissipation vs. Armature Current (3000A Power Module...A-9 Figure A.9 Recommended Circuit Breaker Settings (3000A Power Module)...A-9 Figure A.10 AC Input Busbars (3000A Power Module)...A-10 Figure A.11 Air Baffle Layout (1250A and 1650A Power Modules)...A-11 Figure A.12 Air Baffle Layout (3000A Power Module)...A-12 Figure B.1 DC Blower Motor Connections...B-1 Figure B A and 1650A Power Modules (Non-Regenerative), Sheet 1...B-2 Figure B A and 1650A Power Modules (Non-Regenerative), Sheet 2...B-3 Figure B A and 1650A Power Modules (Regenerative), Sheet 1...B-4 Figure B A and 1650A Power Modules (Regenerative), Sheet 2...B-5 Figure B A Power Module (Regenerative), Sheet 1...B-6 Figure B A Power Module (Regenerative), Sheet 2...B-7 Table of Contents III

6 IV SD3100 Power Modules

7 List of Tables Table 1.1 SD3100 Drive Options Table 1.2 Field Power Module Part Numbers Table 1.3 Distributed Power System DC Drives Documentation Table 1.4 Related Motor Control Center Documentation Table A Configurations Table A Power Module Symbol-to-Component Reference Table A Configurations Table A Power Module Symbol-to-Component Reference Table A Configurations Table A Power Module Symbol-to-Component Reference Table 3.1 Recommended AC Input Wiring Table 3.2 Isolation Transformer Wiring Requirements Table 3.3 Armature Wire Selection Table 3.4 Field Wire Selection Table 4.1 Field Power Module Input Fuses Table A.1 Electrical Specifications (1250A Power Module)...A-2 Table A.2 Electrical Specifications (1650A Power Module)...A-5 Table A.3 Electrical Specifications (3000A Power Module)...A-8 Table of Contents V

8 VI SD3100 Power Modules

9 CHAPTER 1 Introduction SD3100 DC Power Modules convert fixed voltage and frequency three-phase AC power to adjustable voltage DC power, which can be used to supply the armature or field of a DC motor. An SD3100 Power Module operates within the AutoMax Distributed Power System (DPS) environment, and is controlled by the AutoMax Programming Executive software. The Power Module communicates with the AutoMax system via an internally mounted Power Module Interface (PMI) rack, which contains the drive s control circuits and executes the motor control algorithm. The SD3100 configuration provides control of DC motors, rated 700 to 2500 HP, with current ratings of 1250, 1650, and 3000A. Input voltages of 460, 575, and 660 VAC are available. Figure 1.1 shows the SD3100 catalog numbering scheme. Distributed Power System Drive Number AC Input Voltage1 HP Unit 2 4 Configuration Enclosure Options SD3100 B 64 N AA B = 460 VAC C = 575 VAC F = 660 VAC 64 = 700 HP 65 = 750 HP 66 = 800 HP 67 = 900 HP 68 = 1000 HP 69 = 1250 HP 70 = 1500 HP 71 = 1750 HP 72 = 2000 HP 73 = 2250 HP 74 = 2500 HP N = Non-regenerative, 6-pulse R = Regenerative, 6-pulse 3 AA = NEMA Type 1 without gaskets and door fan filters AJ = NEMA Type 1 with gaskets and door fan filters Refer to table 1.1, SD3100 Drive Options. 1. A separately-ordered, separately-mounted 7.5 to 25kVA field isolation transformer is required. See section Units accommodate top entry and bottom exit. An additional section is required for bottom entry. A separate additional section is required for top exit. 3. Non-regenerative units not offered for 3000A modules. 4. Add option codes here. Separate option codes with dashes. Figure 1.1 SD3100 Catalog Numbering Scheme Introduction 1-1

10 Table 1.1 SD3100 Drive Options Drive Option Code Description 6P Standard capacity control transformer with primary fusing Control Power Source 1 6TB 115 VAC control power, factory wired from 115 VAC control bus to drive unit (1250 and 1650A units only). Requires option CB90 6SC 115 VAC control power supplied by others Dynamic Braking Contactor 2 14DB Dynamic braking contactor option Unit Door Nameplate 1 M3EW White background with black lettering; phenolic label Miscellaneous Auxiliary Contacts Blower Starters 5, 6 14WLBL Brady Datab wire labels 3 J12 15 VDC, 15A duplex receptacle, user-wired 4 J11 989X 14BN 14B2N 14B2NX 14BI 14B2I 14B2IX Audio phone jack (2) normally open and (2) normally closed contactors mounted internally in 1250/1650A unit, or (4) normally open and (4) normally closed contactors mounted internally in 3000A unit (1) NEMA 1 FVNR starter assembly internally mounted with 30A fuse blocks (2) NEMA 1 FVNR starter assemblies internally mounted with 30A fuse blocks (2) NEMA 2 FVNR starter assemblies internally mounted with 60A fuse blocks (1) IEC 24A starter assembly internally mounted with 30A fuse blocks (2) IEC 24A starter assemblies internally mounted with 30A fuse blocks (2) IEC 30A starter assemblies internally mounted with 60A fuse blocks 14LSP Line RC suppressor module 7 Protection 14AFL Air flow loss switches Field Supply Upgrade 8, 9 14FX Field supply upgrade for fields requiring 15 to 60A Incoming Protection 1 CM Circuit breaker LF Line fuses Horizontal Power Bus 5 HB A AC power bus for 1250 and 1650A units with 460 or 575 VAC inputs HB A AC power bus for 1250A units with 460 or575 VAC inputs HB A AC power bus for 1250 and 1650A units with 460 or 575 VAC inputs Horizontal Control Bus CB90 Input Option 14HBC 90A AC control bus for 1250 and 1650A units that have a horizontal power bus option AC power input is wired from the horizontal thru-bus to the circuit breaker/line fuses for 1250 and 1650A units that have a horizontal power bus option 1. User must select one option from this group. 2. This option includes a dynamic braking contactor mounted in a separate 20 MCC section. 3. Cloth wire labels are standard. Datab labels provide a clear plastic cover on top of the labels for added protection. 4. User must supply 115 VAC control power and wiring to the duplex receptacle. 5. User may select one option from this group. 6. Fuses and overload elements are user-supplied and must be power-matched to the installation. 7. Line RC suppressor is required for installations where the primary of the distribution transformer is 2300 VAC or greater. 8. Standard Field Power Module is rated to supply field currents up to 15A. The upgrade provides a Field Power Module rated up to 60A. (Nominal field currents based on 85% efficiency, unit control power usage, and a 300V field supply.) 9. A separately-ordered, separately-mounted 7.5kVA to 25kVA field isolation transformer is required. See the following section. 1-2 SD3100 Power Modules

11 1.1 Field Power Module The single-phase Field Power Module is integrally mounted within the SD3100 Power Module to provide the motor field excitation. The Field Power Module is rated 15 or 60 amps at 230/460 VAC. The 15A unit is supplied as standard. The 60A unit is available as an option. The Field Power Module requires a separately-ordered, separately-mounted field isolation transformer. The Field Power Module s AC input lines are connected through the isolation transformer to the L1 and L3 inputs of the SD3100. The 15A module requires a step-down transformer rated up to 7.5kVA (application dependent). The 60A module requires a step-down transformer rated 7.5kVA to 25kVA (application dependent). All systems operate on three-phase 50/60 Hz., 460 to 660 VAC. The Field Power Module is available in the configurations listed in table Standard Features Table 1.2 Field Power Module Part Numbers Part No. Amps AC Input Description Mounting R / 460 VAC Reversing (S2R) Integral R / 460 VAC Reversing (S2R) Integral 1. For application information see instruction manual S SD3100 DC Power Modules have the following features: Three-phase 460, 575, or 690 VAC input 1250, 1650, and 3000 amp units S6 (non-regenerating) and S6R (regenerating) configurations 15 amp Field Power Module DC output contactor PE / TE bus Choice of incoming circuit breaker or input line fuse protection Electronic motor overload protection SCR power semiconductors / dv/dt protection SCR leg fuses Cell chokes Protection against unequal current sharing among SCRs Protection from AC line dips and transients Top AC entry / Bottom DC exit Power through-bus (1250A and 1650A Power Modules) Introduction 1-3

12 115VAC control bus (90A) Fiber-optic communication with the Distributed Power System Universal Drive Controller (UDC) module Drive nameplate - white/black letters 1.3 Optional Features The following features are available as options: 60 amp Field Power Module NEMA blower starter IEC blower starter Air flow switch Line suppressor 115 VAC convenience outlet Phone jack 1.4 Related Publications The instruction manuals in binder S-3000 describe the other system hardware, system software, and communications, as listed in table 1.3. It is assumed that the user is familiar with these manuals before installing, operating, or performing maintenance upon SD3100 DC Power Modules. Further information pertaining to SD3100 Power Modules can be found in instruction manuals S-3045 and S-3060, as listed in the table. Table 1.3 Distributed Power System DC Drives Documentation Publication Number Description S-3000 Distributed Power System DC Drives Binder S-3005 AutoMax Distributed Power System Overview S-3006 SD3000 Drive Configuration and Programming S-3007 Universal Drive Controller Module S-3008 Power Module Interface Rack and Modules S-3009 Fiber Optic Cabling S-3011 Diagnostics, Troubleshooting and Start-up Guidelines Related DPS Documentation S-3045 DPS Parallel Gate Amplifier System S-3060 DPS Single-Phase Field Power Modules 1-4 SD3100 Power Modules

13 Installation of the motor control center (MCC) is described in the manuals listed in table 1.4. Additional information about using SD3100 Power Modules as part of a Distributed Power System is found in the wiring diagrams, prints, and other documentation shipped with each drive system. Always consult the prints shipped with the drive for specific mounting and connecting information about your system. 1.5 Terms Used in this Manual Table 1.4 Related Motor Control Center Documentation Publication Number Description Instructions - Receiving, Handling, And Storing Motor Control Centers Bulletin 2300 Family of Drive Systems Hardware The terms listed in this section have the specific meanings given below when they appear in this manual. Application - The process for which the combination of hardware and control software is being used. Armature Power Module - the power structure containing the three-phase SCR power bridge and related hardware components used to control the armature current. Diagnostic - a software routine or hardware circuit specifically designed to check for error conditions. Drive - the combination of a UDC, a PMI, a Field Power Module, and an Armature Power Module as a means or apparatus for transmitting motion to a machine or machine part. Drive warning - a potentially hazardous or undesirable operating condition checked for by the PMI operating system. Drive warnings are reported in register 203/1203 in the UDC. A drive warning will not shut down the drive. System response is determined by the application task. Error - any operating condition other than the desired one. Drive fault - an error, specifically checked for by the PMI Processor operating system, that will shut down the drive. Drive faults are reported in register 202/1202 in the UDC. Field Power Module - a single-phase power unit, used to supply the motor field. The Field Power Module is integrally mounted within the SD3100 Power Module. Non-regenerative drive - a drive capable of motoring operation only (S6 configuration). Regenerative drive - a drive capable of motoring or regenerating operation, forward or reverse (S6R configuration). Introduction 1-5

14 1-6 SD3100 Power Modules

15 CHAPTER 2 Mechanical/Electrical Description Rockwell Automation SD3100 DC Power Modules are built using a Distributed Power System PMI regulator and a high-horsepower silicon-controlled rectifier (SCR) bridge. All components are housed in a NEMA 1 metal enclosure. This chapter provides general information on the mechanical and electrical characteristics of SD3100 Power Modules, followed by specific information on the 1250A, 1650A, and 3000A units. LINE FUSES OR CIRCUIT BREAKER CURRENT XFMRS FU-A FU-B EXTERNAL FIELD ISO XFMR L1 L2 L3 RESISTOR SCALING MODULE DELTA/WYE PHASING XFMR L1 L2 L3 FIELD POWER MODULE FROM DC ARMATURE FWD GATE SIGNALS TO P4/ DCPT SCALING UNIT ARMATURE FEEDBACK REV GATE SIGNALS GATE COUPLING CIRCUITS + FWD GATE SIGNALS REV GATE SIGNALS TO FIELD POWER MODULE 115 VAC ARMATURE POWER STRUCTURE (S6R) DC MOTOR PMI RACK PGA RACK RESOLVER DRIVE I/O RESOLVER FEEDBACK TO RESISTOR SCALING UNIT Figure 2.1 SD3100 Power Module System Components Mechanical/Electrical Description 2-1

16 2.1 Mechanical Overview The SD3100 Power Module is composed of the basic components shown in figure 2.1. These components consist of: Control components that provide the interface to the AutoMax Distributed Power System and control for the Power Module, and Power components that convert AC line power to DC power for the motor Control Components The control components are contained in the regulator assembly, along with the Field Power Module. The regulator assembly is mounted in the lower compartment of the Power Module s Disconnect Bay. FU-A FU-B FIELD ISOLATION XFRM FUSES SCALING UNIT TB1 PMI RACK FIELD POWER MODULE PGA RACK TB2 TB3 TB4 TB5 TB6 FWD REV TO GATE COUPLERS Figure 2.2 Regulator Assembly The PMI rack contains the four modules that make up the PMI Regulator: the PMI s Power Supply, Processor module, Resolver and Drive I/O module, and DC Power Technology module. The PMI Processor executes the control algorithm and communicates with the AutoMax processor via its fiber-optic ports. The Resolver and Drive I/O module provides the interface for speed feedback and control signals. The DC Power Technology module provides the armature feedback, armature forward gate control, armature reverse gate control (regenerative models only), and the field feedback and gate control signals for the Field Power Module. 2-2 SD3100 Power Modules

17 Below the PMI rack is a DPS Parallel Gate Amplifier (PGA), which provides isolation and amplification of the forward and reverse gate drive signals. The Field Power Module is mounted to the left of the PMI and PGA racks. At the top of the assembly are the field isolation transformer fuses and a scaling unit that conditions the armature feedback signals received via terminal block TB1. Terminal blocks at the bottom of the assembly provide connection for the field gate and feedback signals (TB2), control power (TB3), drive I/O (TB4), the resolver (TB5), and the meter ports (TB6). The forward and reverse armature gate coupler circuits connect to the control circuitry at the lower right of the compartment. The Power Module is shipped with the PMI Regulator and all related control components installed. The PMI is described in detail in the Power Module Interface Rack and Modules instruction manual (S-3008). Please refer to this manual for further information. Additional information on the PGA can be found in instruction manual S Power Components Power components manage and handle the power of the drive under the direction of the PMI regulator. The power components consist of: the incoming power components the armature power bridge components the Field Power Module Incoming Power The incoming power components handle the input power and provide it to the Field Power Module and armature power bridge assemblies. The following components are used to provide incoming power: circuit breaker or input line fuses user-supplied input line reactor or isolation transformer control power and Field Power Module tap user-supplied field isolation transformer AC line RC suppressor Circuit Breaker Power Modules are provided with circuit breakers to protect the input power wiring. Recommended circuit breaker settings are shown in Appendix A. Input Line Reactor or Isolation Transformer The SD3100 system requires a user-supplied line reactor or isolation transformer to reduce peak currents and harmonics in the incoming power lines. This device is needed to provide isolation to other equipment on the power lines during regeneration. Important: Failure to use an input isolation device may result in damage to the Power Module during regeneration. Mechanical/Electrical Description 2-3

18 Control Power and Field Power Module Tap The first (L1) and third (L3) phase of the incoming power are tapped off and fused to provide single-phase AC power to the primary of the control power transformer and the Field Power Module. Field Isolation Transformer A user-supplied field isolation transformer must be installed on the AC input of the Field Power Module as described in section of this manual. Using a field isolation transformer provides the following advantages: Provides power matching to the Field Power Module. Permits the Field Power Module to continue operating in the event of a ground fault in the field windings of the motor. Provides a known minimum AC input impedance for the snubbers to operate against. Protects other circuits sharing the same power source from line notching interference caused by the Field Power Module. Provides source impedance to guarantee SCR protection in the event of a short circuit. AC Line RC Suppressor The optional AC line RC suppressor is a device used for limiting line voltage spikes when the medium voltage source to the primary of the distribution transformer is switched. This option is required for a primary voltage of 2300V or greater. Output Inductor Note that some systems may require an output inductor in series with the armature, especially for some DC motors that do not have enough internal inductance for a proper armature commutation process Armature Power Components The armature power components convert the 3-phase AC input to a DC output used for powering the motor armature. The following components make up the armature power circuitry: armature SCR bridge (and its subordinate components) leg fuses gate coupler cards (GCCs) DC contactor 2-4 SD3100 Power Modules

19 The non-regenerative bridge is shown in figure 2.3. Cell fuses protect the thyristors in the event of a bridge failure. Main Contactor SNUBBER *&& SNUBBER *&& SNUBBER *&& A1 3-Phase AC Input Armature Voltage SNUBBER *&& *&& *&& SNUBBER SNUBBER A2 Figure 2.3 Armature Bridge (Non-Regenerative) Mechanical/Electrical Description 2-5

20 The regenerative bridge, shown in figure 2.4, allows the bridge to direct regenerated power back onto the incoming lines. Main Contactor SNUBBER *&& SNUBBER *&& SNUBBER *&& A1 *&& *&& *&& 3-Phase AC Input Armature Voltage *&& *&& *&& SNUBBER *&& SNUBBER *&& SNUBBER *&& A2 Armature Bridge Components The armature bridge consists of the following components: Silicon-Controlled Rectifiers (SCRs) Each Power Module uses silicon-controlled rectifiers (SCRs) in the armature bridge to switch the incoming 3-phase AC power to DC output power. These SCRs allow current to flow from anode to cathode when two conditions are met. First, like a diode, the SCR must be forward biased. Second, an appropriate pulse must be applied to the gate (through the pulse transformer board). The current will continue through the SCR until the voltage across it reverses and the current drops to zero (line commutation). Snubbers Figure 2.4 Armature Bridge (Regenerative) Snubbers (resistor/capacitor assemblies) are installed in parallel with the SCRs to protect the SCRs from rapid voltage changes (inductive kick) when the SCRs switch off by suppressing and dissipating the excess voltage. 2-6 SD3100 Power Modules

21 Gate Coupler Cards Gate coupler cards amplify the gate signal pulses from the DC Power Technology module to trigger the SCRs. In addition, these cards provide gate driver isolation from the control circuits in the PMI rack. Main DC Contactor The main DC contactor is used to isolate the DC motor armature and to interrupt the DC current to the motor armature. Coil voltage to the contactor is controlled by contacts from the pilot relay Field Power Module Components The Field Power Module operates on single-phase AC, which must be taken from the three-phase armature power bridge s L1 and L3 input lines. The incoming AC must be supplied to the Field Power Module through an isolation transformer. The Field Power Module rectifier consists of 8 SCRs in two full-wave bridges, connected in anti-parallel. Snubber protection is provided to permit operation on a common bus with other Power Modules. A Hall effect device is used to monitor the DC output current. $ ILHOG FODPS DVVHPEO\ LV SURYLGHG WR PRQLWRU WKH YROWDJH EHWZHHQ WKH )LHOG 3RZHU 0RGXOH V RXWSXW WHUPLQDOV DQG,I DQ RYHUYROWDJH RFFXUV WKH ILHOG FODPS ILUHV D FURZEDU 6&5 WKDW VDIHO\ GLVVLSDWHV WKH HQHUJ\ LQ WKH ILHOG 2.2 Electrical Overview SD3100 DC Power Modules convert fixed voltage and frequency three-phase AC power to adjustable voltage DC power for motor armatures, fields, or other applications that require controlled DC power. Power Module operation is programmed and controlled in the UDC module in the AutoMax rack and the PMI Processor in the drive s internal PMI rack. Incoming power is supplied from a three-phase AC line. A phasing transformer provides AC line sequencing and zero-crossing information for each input phase to determine when SCRs should be fired. The Power Module is capable of auto-phasing under software control and can adapt to ABC or ACB phase rotation. The non-regenerative Power Module rectifier consists of 6 SCRs, configured in a full-wave power bridge. The regenerative Power Module rectifier consists of 12 SCRs in two full-wave bridges, connected in anti-parallel. Snubber circuits provide dv/dt protection for the SCRs in each bridge leg. The firing angle for each SCR is determined by the current regulation algorithm executing in the PMI Processor. SCR gating signals are provided by the DC Power Technology module, under the control of the PMI Processor. The gating signals and firing angles are synchronized with the AC line. The PMI Processor regulates the current for the application by varying the point in the AC line cycle at which forward SCR conduction begins. The PMI Processor receives the current reference from the UDC module in the AutoMax rack. The UDC runs the application task that provides overall control of the Power Module. The three-phase SCR power bridge in a non-regenerative Power Module controls forward rotation (motoring) only. Torque is in the same direction as rotation. Mechanical/Electrical Description 2-7

22 The two anti-parallel SCR power bridges in a regenerative Power Module control the direction of motor rotation and the direction of torque, in both forward (motoring) and reverse (regenerating) directions. The regenerative Power Module allows for regeneration of power into the AC line under the condition of an overhauling load. Field Power Module Operation of the Field Power Module is programmed and controlled in the UDC module in the AutoMax rack and the PMI Processor in the PMI rack. The firing angle for each SCR is determined by the field current regulation algorithm executing in the PMI Processor. The field SCR gating signals are provided by the DC Power Technology module, under the control of the PMI Processor. The firing angle for each SCR is synchronized with the AC line feeding it. The PMI Processor regulates the amount of motor field current by varying the point in the AC line cycle at which forward conduction begins. The PMI Processor receives the field current reference from the UDC module in the AutoMax rack. The UDC runs the application task that provides overall control of the application. For a full description of the Field Power Module, please refer to instruction manual S SD3100 Power Modules

23 A Power Module Description Table A Configurations Input Voltage (VAC) Output HP The 1250A Power Module is supplied in the configurations shown in table 2.1. The 1250A Power Module has the following features: The 1250A Power Module uses twelve SCRs (regenerative) or six SCRs (non-regenerative) in the armature bridge to convert the 3-phase AC input to a DC output. The SCRs are built into a heatsink assembly that is cooled by the bridge fan. The 1250A Power Module is protected from incoming fault currents by a circuit breaker or input line fuses. The components of the Power Module (the armature bridge, field bridge, and control components) are protected by fuses, MOVs, snubbers, and/or chokes. The 1250A Power Module is constructed and housed in three bays. The first bay contains the AC input and control hardware, the second bay contains the armature bridge hardware, and the third bay contains the DC output hardware. The 1250A Power Module can be built to allow alternative input entry, using either an optional bottom-entry bay (on the left of the disconnect bay) or an optional top-hat extension over the AC input bay. The 1250A Power Module can be built with an optional through bus assembly, allowing the 1250A Power Module and other connected Power Modules to tap off power from the same AC input. Figures 2.5 and 2.6 show component locations and Power Module dimensions. Please refer to these figures when installing or servicing the Power Module. Refer to Appendix B for wiring diagrams of both the regenerative and non-regenerative versions of the Power Module. Mechanical/Electrical Description 2-9

24 A Power Module Component Layout PP1 PP2 PP3 CB11* or F51* F52* F53* A14R A11F A16R A13F A12R A15F M1 F12 F12A F11 F11A F10 F10A SP1 SP2 SP3 SP4 ACT1 F31, F32, F33 L1 L2 L3 * EA4 * ACT3 F1, F2, F3 F9 F9A F8 F8A F7 F7A D1 MP R1 F17, F18, F19 M11 * * F27, F28, F29 * * M12 FU-A FU-B SCALING UNIT TB1 A14F A16F A12F A11R A13R A15R F16 F14 F14 F15 F15 PMI RACK TB1- FAN PP4 PP5 PP6 A2(-) A1(+) FIELD SUPPLY PGA RACK TB2 TB6 TB3 TB4 TB5 FWD REV PT2 'LVFRQQHFW %D\ %ULGJH %D\ &RQWDFWRU %D\ Figure A Power Module Component Layout 2-10 SD3100 Power Modules

25 Table A Power Module Symbol-to-Component Reference Symbol Description Option 460 VAC 575 VAC 660 VAC A1(+), A2(-) Armature outputs A11F - A16F Armature pulse transformer PCB A11R - A16R Armature pulse transformer PCB ACT1, ACT3 Line current transformers 2000:1 CB11 Circuit breaker 1200A, N-frame F51 - F53 AC line fuses A, KRPC D1 M1 bridge diode EA4 Line RC suppressor F1 - F3 Control branch/feedback PCB fuses 1A KTK 1A KTK 10A A70P F7 - F12, F7A - F12A Armature bridge cell fuses $ 9 0 F14, F15 Control power transformer, primary fuses $./'5 9 10A, 1500V Form 101-Type 4 F16 Control power xfmr, secondary fuse 9A KLDR, 600V F17 - F19, F27 - F29 Blower motor fuses F31 - F33 Line RC snubber fuses 25A KTK 25A KTK 25A A70P FU-A, FU-B External field isolation transformer fuses Forward gate connector Reverse gate connector 15A unit: 30A, 700V 60A unit: 100A, 700V FWD REV M1 DC armature contactor 1800A M11, M12 Blower motor starters MP Main pilot for pilot relay PP1-6 Armature power poles PT2 Control transformer 2kVA R1 M1 suppressor resistor 1k Ω, 50Ω SP1-3 Line-to-line MOVs 460J, 320VAC 550J, 385VAC 600J, 420VAC SP4 Neutral-to-ground MOV 760J, 680VAC 760J, 680VAC 1050J, 750VAC TB1-FAN Bridge fan & capacitor terminal block TB1 Armature feedback terminal block TB2 Field terminal block TB3 Control power terminal block TB4 Drive I/O terminal block TB5 Resolver feedback terminal block TB6 Meter ports connector 1. Note that if the 1250A unit has the AC line fuse option, the 1650A unit s busbars are used in place of the standard 1250A busbars. See Appendix A for busbar illustrations. Mechanical/Electrical Description 2-11

26 A Power Module Dimensions 20 inches (508 mm) 91.5 inches (2324 mm) 20 inches (508 mm) 20 inches (508 mm) 35 inches (889 mm) 20 inches (508 mm) 20 inches (508 mm) Figure A Power Module Dimensions For other details on the 1250A Power Module and its components, please refer to the appendices of this manual SD3100 Power Modules

27 A Power Module Description Table A Configurations Input Voltage (VAC) Output HP The 1650A Power Module is supplied in the configurations shown in table 2.3. The 1650A Power Module has the following features: The 1650A Power Module uses twelve SCRs (regenerative) or six SCRs (non-regenerative) in the armature bridge to convert the 3-phase AC input to a DC output. The SCRs are built into a heatsink assembly that is cooled by the bridge fan. The 1650A Power Module is protected from incoming fault currents by a circuit breaker or input line fuses. The DC output is protected from fault currents by a DC contactor. The components of the Power Module (the armature bridge, field bridge, and control components) are guarded by fuses, MOVs, snubbers, and/or chokes. The 1650A Power Module is constructed and housed in three bays. The first bay contains the AC input and control hardware, the second bay contains the armature bridge hardware, and the third bay contains the DC output hardware. The 1650A Power Module can be built to allow alternative input entry, using either an optional bottom-entry bay (to the left side of the disconnect bay) or an optional top-hat extension over the AC input bay. The 1650A Power Module can be built with an optional through bus assembly, allowing the 1650A Power Module and other connected Power Modules to tap off power from the same AC input. Figures 2.7 and 2.8 show component locations and Power Module dimensions. Please refer to these figures when installing or servicing the Power Module. Refer to Appendix B for wiring diagrams of both the regenerative and non-regenerative versions of the Power Module. Mechanical/Electrical Description 2-13

28 A Power Module Component Layout PP1 PP2 PP3 CB11* or F51* F52* F53* A14R A11F A16R A13F A12R A15F M1 F12 F12A F11 F11A F10 F10A SP1 SP2 SP3 SP4 ACT1 F31, F32, F33 L1 L2 L3 * EA4 * ACT3 F1, F2, F3 F9 F9A F8 F8A F7 F7A D1 MP R1 F17, F18, F19 M11 * * F27, F28, F29 * * M12 FU-A FU-B SCALING UNIT TB1 A14F A16F A12F A11R A13R A15R F16 F14 F14 F15 F15 PMI RACK TB1- FAN PP4 PP5 PP6 A2(-) A1(+) FIELD SUPPLY PGA RACK TB2 TB6 TB3 TB4 TB5 FWD REV PT2 'LVFRQQHFW %D\ %ULGJH %D\ &RQWDFWRU %D\ Figure A Power Module Component Layout 2-14 SD3100 Power Modules

29 Table A Power Module Symbol-to-Component Reference Symbol Description Option 460 VAC 575 VAC 660 VAC A1(+), A2(-) Armature outputs A11F - A16F Armature pulse transformer PCB A11R - A16R Armature pulse transformer PCB ACT1, ACT 3 Line current transducer 3000:1 CB11 Circuit breaker 1600A, R-frame F51 - F53 AC line fuses 1600A, KRPC D1 M1 bridge diode EA4 Line RC suppressor F1 - F3 Control branch/feedback PCB fuses 1A KTK 1A KTK 10A A70P F7 - F12, F7A - F12A Armature bridge cell fuses $ 9 0 F14, F15 Control power transformer, primary fuses $./'5 9 10A, 1500V Form 101-Type 4 F16 Control power xfmr, secondary fuse 9A KLDR, 600V F17 - F19, F27 -F 29 Motor blower fuses F31 - F33 Line RC snubber fuses 25A KTK 25A KTK 25A A70P FU-A, FU-B External field isolation transformer fuses Forward gate connector Reverse gate connector 15A unit: 30A, 700V 60A unit: 100A, 700V FWD REV M1 DC armature contactor 3000A M11, M12 Motor blower starters MP Main pilot for pilot relay PP1 - PP6 Armature power poles PT2 Control transformer 2kVA R1 M1 suppressor resistor 1k Ω, 50Ω SP1 - SP3 Line-to-line MOVs 460J, 320VAC 550J, 385VAC 600J, 420VAC SP4 Neutral-to-ground MOV 760J, 680VAC 760J, 680VAC 1050J, 750VAC TB1-FAN Bridge fan & capacitor terminal block TB1 Armature feedback terminal block TB2 Field terminal block TB3 Control power terminal block TB4 Drive I/O terminal block TB5 Resolver feedback terminal block TB6 Meter port connector Mechanical/Electrical Description 2-15

30 A Power Module Dimensions 20 inches (508 mm) 91.5 inches (2324 mm) 20 inches (508 mm) 20 inches (508 mm) 35 inches (889 mm) 20 inches (508 mm) 20 inches (508 mm) Figure A Power Module Dimensions For other details on the 1650A Power Module and its components, please refer to the appendices of this manual SD3100 Power Modules

31 A Power Module Description Table A Configurations Input Voltage (VAC) Output HP The 3000A Power Module is supplied in the configurations shown in table 2.5. The 3000A Power Module has the following features: The 3000A Power Module uses twelve SCRs in the armature bridge to convert the 3-phase AC input to a DC output. The SCRs are built into a heatpipe assembly that is cooled by the bridge fan. The 3000A Power Module is protected from incoming fault currents by a circuit breaker or line fuses. The DC output is protected from fault currents by a DC contactor. The components of the Power Module (the armature bridge, field bridge, and control components) are protected by fuses, MOVs, snubbers, and/or chokes. The 3000A Power Module is constructed and housed in four bays. The first bay contains the AC input and control hardware, the second bay contains the fuses, the third bay contains the armature bridge hardware, and the fourth bay contains the DC output hardware. The 3000A Power Module has a standard top-hat extension over the disconnect bay for the AC input. The Power Module can also be built to allow an alternative input entry, using an optional bottom-entry bay (on the left side of the disconnect bay). Figures 2.9 and 2.10 show component locations and Power Module dimensions. Please refer to these figures when installing or servicing the Power Module. Refer to Appendix B for wiring diagrams of both the regenerative and non-regenerative versions of the Power Module. Mechanical/Electrical Description 2-17

32 A Power Module Component Layout F11 PP1 PP2 PP3 CB11* or F51* F52* F53* F10 F12 M1 S1 S2 S3 L1A L2A L3A ACT1 ACT3 A14R A11F A16R A13F A12R A15F FU-A SP1 SP2 SP3 SP4 FU-B SCALING UNIT F1, F2, F3 TB1 F7 F8 F9 PP4 PP5 PP6 S1A S2A S3A MP F17 F18 F19 R1 M11 F27 F28 F29 M12 F14 F15 PMI RACK F16 A11R A14F A13R A16F A15R A12F F14 F15 FAN1 FIELD SUPPLY PGA RACK A2(-) A1(+) TB2 TB6 TB3 TB4 TB5 FWD REV FAN2-C1 FAN2 PT2 'LVFRQQHFW %D\ )XVH %D\ %ULGJH %D\ &RQWDFWRU %D\ Figure A Power Module Component Layout 2-18 SD3100 Power Modules

33 Table A Power Module Symbol-to-Component Reference Symbol Description Option 460 VAC 575 VAC 660 VAC A1(+), A2(-) Armature outputs A11F - A16F Armature pulse transformer PCB A11R - A16R Armature pulse transformer PCB ACT1, ACT3 Line current transducer 5000:1 CB11 Circuit breaker 3000A, SPB-frame F51 - F53 AC line fuses 3000A, KRPC FAN1 Armature bridge fan 1850 CFM FAN2 Slide-fan 1589 CFM FAN2-C2 Fan capacitor 40µF F1, F2, F3 Control branch/feedback PCB fuses 1A KTK 1A KTK 10A A70P F7 - F12 Armature bridge cell fuses $ 9 0 F14, F15 Control power transformer, primary fuses $./'5 9 F16 Control power xfmr, secondary fuse 9A KLDR, 600V F17 - F19, Blower motor fuses F27 - F29 FU-A, FU-B External field isolation transformer fuses Forward gate connector Reverse gate connector 15A unit: 30A, 700V 60A unit: 100A, 700V 10A, 1500V Form 101-Type 4 FWD REV M1 DC armature contactor 3000A M11, M12 Blower motor starters MP Main pilot for pilot relay PP1 - PP6 Armature power poles PT2 Control transformer 2kVA R1 M1 suppressor resistor 1k Ω, 50Ω SP1 - SP3 Line-to-line MOVs 460J, 320VAC 550J, 385VAC 600J, 420VAC SP4 Neutral-to-ground MOV 760J, 680VAC 760J, 680VAC 1050J, 750VAC TB1 Armature feedback terminal block TB2 Field terminal block TB3 Control power terminal block TB4 Drive I/O terminal block TB5 Resolver feedback terminal block TB6 Meter ports connector Mechanical/Electrical Description 2-19

34 A Power Module Dimensions 20 inches (508 mm) 91.5 inches (2324 mm) 20 inches (508 mm) 20 inches (508 mm) 20 inches (508 mm) 35 inches (889 mm) 20 inches (508 mm) 20 inches (508 mm) Figure A Power Module Dimensions For other details on the 3000A Power Module and its components, please refer to the appendices of this manual SD3100 Power Modules

35 CHAPTER 3 Installation Guidelines! ATTENTION: Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. This chapter describes the guidelines and wiring recommendations to be followed when installing SD3100 DC Power Modules. Additional information on installing SD3100 drives can be found in the instruction manuals listed in tables 1.3 and 1.4 on page 1-4 of this manual. The installation of the Power Module can be broken down into the following tasks: physically installing the unit wiring AC power into the Power Module wiring DC power out to the motor armature and field grounding the drive installing feedback devices Note that System wiring is to be done according to the supplied wiring diagrams (W/Es), which are application-specific. 3.1 Planning the Installation Use the following guidelines when planning your Power Module installation: Verify that the selected site will provide sufficient ventilation for the Power Module. The Power Module s fan pulls in air from the bottom of the chassis and exhausts it from the top. The ambient temperature must remain between 0 and 40 C (32 to 131 F). Be sure surrounding components do not block service access to the Power Module. Verify that the relative humidity will be between at 5 and 95% (non-condensing). Do not install the Power Module above 1000 meters (3300 ft) without derating. See figure A.1, Altitude Derating Chart, in Appendix A. Refer to figure 2.6 (1250A units), figure 2.8 (1650A units), or figure 2.10 (3000A units) for Power Module dimensions. Installation Guidelines 3-1

36 3.2 Physically Installing the Power Module! ATTENTION: The Power Module is at line voltage when connected to incoming AC power. Disconnect, lock out, and tag all incoming power to the drive before performing the following procedures. Failure to observe this precaution could result in severe bodily injury or loss of life. To move and position the unit at your site, follow the instructions given in publication , titled Instructions - Receiving, Handling, And Storing Motor Control Centers. This publication contains instructions for the proper handling, moving, and positioning of the Power Module. After the Power Module is properly positioned, follow the instructions given in publication , titled Bulletin 2300 Family of Drive Systems Hardware. This publication describes how to splice busbars, how to attach the Power Module in a multiple drive configuration, and how to join MCC sections together (if necessary). 3.3 Wiring AC Input Power to the Power Module! ATTENTION: The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment. To wire AC input power to the Power Module, you will need to do the following: install an isolation transformer select and provide appropriate input power wire prepare the drive enclosure connect the input power Take precautions to separate AC and DC power leads from signal leads, such as resolver or tach wiring, to minimize electromagnetic interference. Wiring should comply with ANSI/IEEE Standard 518. Follow the instructions on separating wiring found in the wiring diagrams and in instruction manual D Refer to figure 2.5 (1250A units), figure 2.7 (1650A units), or figure 2.9 (3000A units) for component and terminal locations AC Input Wire Selection Table 3.1 shows the recommended AC input wiring. Note that this table reflects NFPA 70, 75 C wiring. Refer to the applicable local codes for specific guidelines. DC Bus Current (Amps) Table 3.1 Recommended AC Input Wiring Incoming Wires (For Each Phase or Connection, AWG) kcmil kcmil kcmil 3-2 SD3100 Power Modules

37 3.3.2 Making an Input Entry Hole If your Power Module has an extra input bay installed, proceed as follows. If your Power Module will have a top-hat enclosure over the disconnect bay, mount the top-hat enclosure before continuing. To make an input entry hole, select the ideal hole placement (within the constraints shown in figure 3.1), then perform the steps that follow. The width allowed is 2.28 inches shorter than your cabinet's width, as shown. 1.25" 20.00" (Back of Enclosure) Cabinet Width Width of Area 20.00" (508 mm) 17.72" (450 mm) 25.00" (635 mm) 22.72" (577 mm) 30.00" (762 mm) 27.72" (704 mm) 35.00" (889 mm) 32.72" (831 mm) 11.50" Area Available For Conduit Entry 1.14" 17.72" 20.00" (Front of Enclosure) c 3000A units allow a depth of 16.75" for conduit entry. Figure 3.1 Area Available for Conduit Entry (Top View of Leftmost Bay) Step 1. Step 2. Remove the lifting angle, if it is still attached. Remove the top plate from the disconnect bay (or from the top-hat enclosure). Step 3. Punch hole(s) for the AC input entry within the area shown in figure 3.1. Step 4. Step 5. Replace the top plate on the drive. Replace the lifting angle Connecting the AC Input Wires to the Busbars Use the following procedure to connect the input wires to the input busbars in the disconnect bay. Refer to Appendix A for busbar specifications. Step 1. Step 2. Step 3. Thread the input wires through the entry hole on the top of your drive. Fasten the input wires for each phase onto the appropriate phase busbar (see the busbar illustrations shown in Appendix A). Torque all bolts to 45 lb-ft. Installation Guidelines 3-3

38 3.4 Wiring AC Input to the Field Power Module AC power connections to the single-phase Field Power Module are made to terminal block TB2 at the bottom left of the control compartment. Phase control for the Field Power Module is determined by the PMI Regulator, which also controls phasing for the armature power devices. The Field Power Module s AC input terminals must be connected to AC input lines L1 and L3 through an isolation transformer. Terminal block TB2 has been provided for these connections Installing the Field Isolation Transformer The field isolation transformer should be installed at an appropriate location external to the Power Module, and in conformance with the NEC/CEC and all applicable local, national, and international codes. The transformer s input fuse ratings and required minimum wire sizes for use with the Field Power Module are listed in table 3.2. Field Power Module (Amps) Table 3.2 Isolation Transformer Wiring Requirements Isolation Transformer Fuse Rating (Maximum Amps) Minimum Required Wire Size (AWG) # #4 Wire the field isolation transformer as shown in figure 3.2. Connect terminal 31 on TB2 to H2 on the field isolation transformer and terminal 30 to H1. Connect X1 to terminal L1A and X2 to terminal L3A. Important: The isolation transformer must be connected to terminal block TB2 as shown in figure 3.2. Improper drive regulation and/or fuse clearing may result if the Field Power Module s AC inputs are incorrectly wired L1A L3A TERMINAL BLOCK TB2 TO MOTOR FIELD + H1 H2 FIELD ISOLATION TRANSFORMER X1 X2 Figure 3.2 Field Terminal Wiring 3-4 SD3100 Power Modules

Pulse Encoder Interface Kit For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 907FK0101

Pulse Encoder Interface Kit For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 907FK0101 Pulse Encoder Interface Kit For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 907FK0101 Instruction Manual D2-3302-3 The information in this manual is subject to change without notice. Throughout

More information

MaxPak Plus Analog DC V S Drive

MaxPak Plus Analog DC V S Drive Three-Phase 3-600 HP non-regenerative and 5-150 HP regenerative drives Designed to accommodate a wide range of industrial requirements, the DC V S Drive has been widely applied worldwide. Selected ratings

More information

1/6 through 5 HP Adjustable Speed, DC Motor Controllers

1/6 through 5 HP Adjustable Speed, DC Motor Controllers 1/6 through 5 HP Adjustable Speed, DC Motor Controllers 1/6-5 HP 115 or 230 V, Single Phase - Reconnectable Four Quadrant Regenerative Selectable Deadband AC Line Starting DC Tachometer Feedback Run Contact

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS MANUAL NUMBER: 64073 REV: 2 DATE: October 3, 2006 INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS AMERICAN BATTERY CHARGING, INC. P.O. BOX 17040 28 MAPLE AVENUE SMITHFIELD,

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

Fincor Series 2230 MKII/2240

Fincor Series 2230 MKII/2240 Fincor Series 2230 MKII/ Fincor Series 2200 regenerative drives are ideal for your more demanding applications. They feature flexibility with ratings up to 5 horsepower. The Series 2230 MKII offers new

More information

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible DC Drives Flexible & Powerful single-phase DC drives provide a complete family solution from the compact Series 2120 chassis drive to the powerful Series 2230 and it s feature rich application specific

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Trane Liqui-Flo Addendum. Instruction Manual D2-3415

Trane Liqui-Flo Addendum. Instruction Manual D2-3415 Trane Liqui-Flo Addendum Instruction Manual D2-3415 The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety considerations:!

More information

Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to VAC, 3 HP to VAC without NEMA1 Enclosures

Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to VAC, 3 HP to VAC without NEMA1 Enclosures Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to 150 HP @ 230 VAC, 3 HP to 600 HP @ 460 VAC without NEA1 Enclosures odel Numbers 912FKxxxx and 913FKxxxx Instruction anual

More information

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN Form 1254 BRAKETRON Electronic Motor Brake Instructions SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN TABLE OF CONTENTS SECTION TITLE PAGE I. Introduction 1 II. Specifications 1 III. Principles

More information

1395 Digital DC Drive Page 5 of 19 Renewal Parts

1395 Digital DC Drive Page 5 of 19 Renewal Parts 1395 Digital DC Drive Page 5 of 19 Current Rated (Continued) Series A Drives, 3.6A to 345A, 50/60 Hz, 230, 380, 415 & 460 Volt AC Inputs. 3.6-20- 57-81- Description 19A 56A 80A 110A Per Drive Line Fuse,

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

1395 Digital DC Drive Renewal Parts

1395 Digital DC Drive Renewal Parts Important Information, Read First 1395 Digital DC Drive Page 1 of 19 The 1395 Product Line has evolved from current rated units to horsepower rated units. Within the range of sizes there are various series

More information

AutoMax DPS DC Power Module Instruction Manual

AutoMax DPS DC Power Module Instruction Manual AutoMax DPS DC Power Module Instruction Manual User Manual: 49 1335-e (06) Publication: AMXDPS-UM003D-EN TABLE OF CONTENTS GENERAL NOTES Chapter 1. DESCRIPTION WITH SCHEMATIC DIAGRAM 1...5 Features...

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP) Rev. 02/97 SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP) TABLE OF CONTENTS SECTION TITLE PAGE I GENERAL INFORMATION 1 Introduction 1 General Description 1 Model Types 1 Motor

More information

DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D AI M/N DC3N-12D-4X-010-AI

DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D AI M/N DC3N-12D-4X-010-AI 250-0287-rev2.qxd 3/12/01 10:27 AM Page a DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D-00-010-AI M/N DC3N-12D-4X-010-AI Instruction Manual D2-3452-1 250-0287-rev2.qxd

More information

2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / /

2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / / Non-Regen Drives Non-regenerative drives are typically used on applications which primarily motor in one direction and stopping is achieved through friction or infrequent use of a dynamic braking resistor.

More information

SDC,Inc. SCR-Regenerative Ac Drive

SDC,Inc. SCR-Regenerative Ac Drive SDC,Inc WWW.STEVENSDRIVES.COM APPLICATION NOTE #: AN_REG_GEN000 EFFECTIVE DATE: 12 MAR 02 SUPERSEDES DATE: Original NO. OF PAGES: 10 SCR-Regenerative Ac Drive Using a regeneration controller with adjustable-frequency

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives VAC and VAC

Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives VAC and VAC Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 40-75 HP @ 230 VAC and 75-150 HP @ 460 VAC Model Numbers: 906FK1101 and 906FK1201 Instruction Manual D2-3330-2! ATTENTION:

More information

FlexPak 3000 Digital DC Drive Hardware Reference, Installation and Troubleshooting Version 4.3

FlexPak 3000 Digital DC Drive Hardware Reference, Installation and Troubleshooting Version 4.3 FlexPak 3000 Digital DC Drive Hardware Reference, Installation and Troubleshooting Version 4.3 Instruction Manual D2-3404-2 The information in this manual is subject to change without notice. Throughout

More information

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

Allen-Bradley Motors. NRU Diode Bridge Assembly Replacement ( A DC) REPLACEMENT KIT INSTRUCTIONS. Contents. What This Kit Contains

Allen-Bradley Motors. NRU Diode Bridge Assembly Replacement ( A DC) REPLACEMENT KIT INSTRUCTIONS. Contents. What This Kit Contains REPLACEMENT KIT INSTRUCTIONS NRU Diode Bridge Assembly Replacement (180-350A DC) Contents In 180A DC and 350A DC NRUs, all 6 diodes (D1 - D6) and the both the positive and negative heatsinks (HS1 - HS2)

More information

DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC

DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC Instruction Manual D2-3453 The information in this manual is subject to change without notice. Throughout this manual, the following notes

More information

Data Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA

Data Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA Data Bulletin Raleigh, NC, USA ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION The ALTIVAR FLEX58 chassis drive controller offers OEMs, panel builders, integrators, and users a unique

More information

CONTROL FEATURES AVAILABLE OPTIONS

CONTROL FEATURES AVAILABLE OPTIONS Vari Speed A2000 TABLE OF CONTENTS Control Features Options Application Data Operating Condition s Control Ratings Chart Mounting Dimensions Installation and Wiring Typical Wiring Diagram Schematic (Block

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Power Fuse Assembly Replacement (for 3000A 1395 DC Drives)

Power Fuse Assembly Replacement (for 3000A 1395 DC Drives) REPLACEMENT KIT INSTRUCTIONS Power Fuse Assembly Replacement (for 3000A 1395 DC Drives) Contents What This Kit Contains This document shows how to remove and replace a power fuse assembly (and how to replace

More information

Double Pole Circuit Breaker Kit for Non-Regenerative MinPak Plus DC Drives

Double Pole Circuit Breaker Kit for Non-Regenerative MinPak Plus DC Drives Double Pole Circuit Breaker Kit for Non-Regenerative MinPak Plus DC Drives Model Numbers 14C210, 14C211, 14C212, and 14C213 Instruction Manual D2-3385! ATTENTION: Only qualified electrical personnel familiar

More information

RENEWAL PARTS Supersedes: RP4 (1012) Form RP4 (813)

RENEWAL PARTS Supersedes: RP4 (1012) Form RP4 (813) VARIABLE SPEED DRIVE RENEWAL PARTS Supersedes: 160.00-RP4 (1012) Form 160.00-RP4 (813) 292 HP 50 HZ, 400VAC (P/N 371-03700-XXX) 351 HP 60 HZ, 460VAC (P/N 371-02767-XXX) 419 HP 50 HZ, 400VAC (P/N 371-03789-XXX)

More information

PCCA POWER CONNECT CARD. DS200PCCAG1A thru DS200PCCAG10A

PCCA POWER CONNECT CARD. DS200PCCAG1A thru DS200PCCAG10A (Supersedes GEI-100161A) PCCA POWER CONNECT CARD DS200PCCAG1A thru DS200PCCAG10A These instructions do not purport to cover all details or variations in equipment, nor to provide every possible contingency

More information

15 Recommended Spare Parts

15 Recommended Spare Parts 15.1 QUANTUM III SPARE PARTS KITS Control Techniques offers a Spares Kit A and Kit B for each Quantum III model. They represent a significant savings over purchasing the items separately. Kit A will be

More information

STR3. Step Motor Drive. User Manual

STR3. Step Motor Drive. User Manual STR3 Step Motor Drive User Manual Contents 1 Introduction... 3 1.1 Overview... 3 1.2 Features... 3 1.3 Block Diagram... 4 1.4 Safety Instructions... 5 2 Getting Started... 6 2.1 Mounting Hardware... 6

More information

MELLTRONICS DRIVES. Single Phase Regenerative DC Drives ¼ HP TO 7½ HP INSTALLATION OPERATION MAINTENANCE

MELLTRONICS DRIVES. Single Phase Regenerative DC Drives ¼ HP TO 7½ HP INSTALLATION OPERATION MAINTENANCE INSTALLATION OPERATION MAINTENANCE MELLTRONICS DRIVES Single Phase Regenerative DC Drives ¼ HP TO 7½ HP MAIL: PO BOX 68 INDIAN TRAIL, NC 8079-68 SHIPPING: 479 GRIBBLE ROAD MATTHEWS, NC 804-84 PHONE: 704-8-66

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

WARRANTY INFORMATION...

WARRANTY INFORMATION... Table of contents 1 General Information... 3 1.1 Description... 3 1.2 Features... 3 1.3 Specifications... 4 1.4 Receiving and Unpacking... 4 1.5 Dimensions... 4 2 Installation... 5 2.1 Wiring... 5 3 Operation...

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation MATRIX FILTER SERIES D 480 Volts, 60HZ USER MANUAL PART NO. INSTR 024 REL. 120628 REV. 012 2012 MTE Corporation Matrix Series D User s Manual 480VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

MOTORTRONICS Solid State AC Motor Control

MOTORTRONICS Solid State AC Motor Control Solid State AC Motor Control MWH Series Solid State Motor Winding Heater 10 to 80 Amps INSTALLATION & START-UP MANUAL REV 4 6091101MN Table of Contents Chapter 1: General Information... 1 1.1 Introduction

More information

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components

More information

Series 2330MKII. Single-Phase. Adjustable-Speed. DC Motor Controllers (1/6 3 HP) BOOK 0958-B

Series 2330MKII. Single-Phase. Adjustable-Speed. DC Motor Controllers (1/6 3 HP) BOOK 0958-B Series 2330MKII Single-Phase Adjustable-Speed DC Motor Controllers (1/6 3 HP) Control Techniques 3750 East Market Street York, PA 17402-2798 717-751-4200, FAX 717-751-4263 www.fincor.net BOOK 0958-B SERIES

More information

Boston Gear Ratiotrol

Boston Gear Ratiotrol Boston Gear Ratiotrol DC Motor Speed Control Installation and Operation Doc. No. 57766 Beta Plus Series Single Phase 1/6-3 HP Inside Front Cover BLANK Table of Contents SECTION TITLE PAGE WARNINGS... 3

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

AC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave

AC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave Rectifiers for use with Armature Actuated Brakes Product Overview NOTE: For brake response times with and without rectifiers see page 94. Full Wave A rectifier in which both positive and negative half-cycles

More information

1800/1000 Frame RC Snubber Board IS200RCSAG1A

1800/1000 Frame RC Snubber Board IS200RCSAG1A GEI-100303 g GE Industrial Systems 1800/1000 Frame RC Snubber Board IS200RCSAG1A Safety Symbol Legend Indicates a procedure or condition that, if not strictly observed, could result in personal injury

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

SERIES 2600/2610 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-5 HP)

SERIES 2600/2610 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-5 HP) Rev. 11/01 SERIES 2600/2610 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-5 HP) TABLE OF CONTENTS SECTION TITLE PAGE I GENERAL INFORMATION 1 Introduction 1 General Description 1 Model Types 1

More information

1329I Integrated Drive/Motor CE Filter Option Kit

1329I Integrated Drive/Motor CE Filter Option Kit Instruction Sheet 1329I Integrated Drive/Motor CE Filter Option Kit CE filter options are designed to be used with the 1329I Integrated Drive/Motor. The main function of the CE filter is to reduce the

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 120628 REV. 007 2012 MTE Corporation Matrix Series D User s Manual 600VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

Installation Instructions. PowerFlex 700 Drive - Frame 8 Components Replacement

Installation Instructions. PowerFlex 700 Drive - Frame 8 Components Replacement Installation Instructions PowerFlex 700 Drive - Frame 8 Components Replacement Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) 1. Which drawing type shows physical details as seen by the eye? 2. Which drawing is similar to a pictorial drawing but has

More information

Allen-Bradley Parts. CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns. Installation Instructions. Catalog Number 2500

Allen-Bradley Parts. CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns. Installation Instructions. Catalog Number 2500 Installation Instructions CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns Catalog Number 2500 Topic Page Important User Information 2 Location Planning 3 Environment 3 Removal

More information

SR3-mini. Step Motor Drive User Manual. AMP & MOONS Automation

SR3-mini. Step Motor Drive User Manual. AMP & MOONS Automation SR3-mini Step Motor Drive User Manual AMP & MOONS Automation Contents 1 Introduction... 3 1.1 Overview...3 1.2 Features...3 1.3 Block Diagram...4 1.4 Safety Instructions...5 2 Getting Started... 6 2.1

More information

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

USERS MANUAL MCD REMOTE OPERATOR

USERS MANUAL MCD REMOTE OPERATOR USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3

More information

Installation & Operation Manual

Installation & Operation Manual Installation & Operation Manual SECO SE 2000 Series DC Motor Controller 1 Through 5 HP 115/230 VAC 1 Phase Input TABLE OF CONTENTS Section Page 1.0 GENERAL INFORMATION... 3 1.1 Controller... 4 1.2 Specifications...

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 080920 2008 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic mitigation

More information

PowerFlex 700 Drive - Frame 9 Components Replacement

PowerFlex 700 Drive - Frame 9 Components Replacement Installation Instructions PowerFlex 700 Drive - Frame 9 Components Replacement Catalog Numbers XXX XXX XXXX XXX XXX XXX Important User Information Solid-state equipment has operational characteristics

More information

SOLSTART Instruction Manual

SOLSTART Instruction Manual Solstart Analog Soft Starter 8-58A, 220-600V Instruction Manual Ver. 23/03/2009 2 Table of Content SOLSTART Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits. Chapter 8 Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits. Article 430 of the NEC covers application and installation of

More information

Standard Features 200-600V, 50/60Hz input power supply Built-in run rated (AC1) By-pass contactor up to 820 A * Rated 450% current Conformal coated circuit board Voltage ramp or current limit start modes

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

The Z Series. SCR Power controllers for resistance heating applications. Zero-Fired SCR Power Controllers AMPS VAC

The Z Series. SCR Power controllers for resistance heating applications. Zero-Fired SCR Power Controllers AMPS VAC The Z Series Zero-Fired SCR Power Controllers 60-1200 AMPS 120-600 VAC SCR Power controllers for resistance heating applications. ROBICON 1996 Rev. 7/96 Applications Robicon s Z series power controls are

More information

MATRIX FILTER USER MANUAL. SERIES D 400 Volts, 50HZ PART NO. INSTR 025 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 400 Volts, 50HZ PART NO. INSTR 025 REL REV MTE Corporation MATRIX FILTER SERIES D 400 Volts, 50HZ USER MANUAL PART NO. INSTR 025 REL. 110624 REV. 006 2011 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic

More information

PowerFlex 700 Drive - Frame 8 Components Replacement

PowerFlex 700 Drive - Frame 8 Components Replacement Installation Instructions PowerFlex 700 Drive - Frame 8 Components Replacement Catalog Numbers 20B Important User Information Read this document and the documents listed in the additional resources section

More information

MV SMC-Flex OEM Components

MV SMC-Flex OEM Components MV SMC-Flex OEM Components Bulletin 1503E Installation Instructions Important User Information Read this document and the documents listed in the Additional Resources section about installation, configuration,

More information

BR Second Position Voltages. AA Fourth Position

BR Second Position Voltages. AA Fourth Position 1336S First Position Bulletin Number BR Second Position Voltage Letter AQ BR CW A B BP BX C Q R RX W Voltages 200-240V AC or 3V DC 380-480VAC or 513-620V DC 500-600V AC or 775V DC or 200-240V AC 380-480V

More information

Application Note CTAN #127

Application Note CTAN #127 Application Note CTAN #127 Guidelines and Considerations for Common Bus Connection of AC Drives An important advantage of AC drives with a fixed DC is the ability to connect the es together so that energy

More information

Installation Instructions. Y-Series Brushless Servo Motor

Installation Instructions. Y-Series Brushless Servo Motor Installation Instructions Y-Series Brushless Servo Motor Catalog Number Y-1002-1, Y-1002-2, Y-1003-1, Y-1003-2, Y-2006-1, Y-2006-2, Y-2012-1, Y-2012-2, and Y-3023-2 These installation instructions describe

More information

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2 RCP200 Series Motor Controls Instruction Manual Model RCP202-000 Model RCP205-000 Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2 You ve just purchased the best! Congratulations! You ve just purchased

More information

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017 R80 REV SERIES SCR POWER CONTROLS NOVEMBER 017 Product overview The Viconics R80 series SCR power controls are designed for cost effective, precise modulation of electric loads for most electric heating

More information

ALTIVAR FLEX58 Chassis Drive Controller Product Selection

ALTIVAR FLEX58 Chassis Drive Controller Product Selection ALTIVAR FLEX58 Chassis Drive Controller Product Selection Class 8806 CONTENTS Description Page General Information and Selection....................................... 2 Specifications and Ratings...........................................

More information

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means,

More information

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C C Mobile Communications 13 AMPERE POWER SUPPLY 19A704647P1-P3 CAUTION THESE SERVICING INSTRUCTIONS ARE FOR USE BY QUALI- FIED PERSONNEL ONLY. TO AVOID ELECTRIC SHOCK DO NOT PERFORM ANY SERVICING OTHER

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS Supersedes: 160.75-PW2 (508) Form 160.75-PW2 (311) FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS WIRING DIAGRAM CONTRACTOR ORDER NO. YORK CONTRACT NO.

More information

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions Harmonic Filter AHF 005/010 Instruction Manual Drives Solutions Contents Safety... 2 Warnings... 2 Symbols used in this manual... 2 Operator s safety... 2 Avoid filter module damage... 2 DC-link resonance...

More information

CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR

CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR WIRING DIAGRAMS CONTRACTOR ORDER NO. JCI CONTRACT NO. JCI ORDER NO. Supersedes: 160.80-PW4 (1099) Form: 160.80-PW4 (215) FIELD CONNECTIONS ROTARY SCREW CHILLER WITH GRAPHIC CONTROL CENTER AND YORK MOD

More information

SE2000BX Static Exciter

SE2000BX Static Exciter Rev 3 SE2000BX Static Exciter The SE2000BX Static Exciter is designed to replace most electronic, saturable reactor and rotary exciters used on slip ring or rotor fed electric generators. The SE2000BX

More information

Boston Gear Ratiotrol

Boston Gear Ratiotrol Boston Gear Ratiotrol DC Motor Speed Control Installation and Operation Doc. No. 3721 RG1 and RG2 Models 1/6-1 HP GENERAL INFORMATION DESCRIPTION Series RG Controllers statically convert single-phase AC

More information

********SERVICE MANUAL********* MODELS:

********SERVICE MANUAL********* MODELS: ********SERVICE MANUAL********* MODELS: -------------- 7553-70 Variable Speed Drive/Controller System, 600 rpm, 115v 7553-71 Variable Speed Controller only, 600 rpm,115v 7553-80 Variable Speed Drive/Controller

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY CONNECTIONS INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!! FOLLOW NATIONAL, STATE AND LOCAL CODES! READ THESE INSTRUCTIONS

More information

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarters. Softstarters Type SSM Medium voltage ,800V 1 Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum

More information