Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker

Size: px
Start display at page:

Download "Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker"

Transcription

1 Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker Circuit Breaker Sales, Inc Columbine Drive Gainesville, TX (940) Revision 2 March 2012

2 FIGURE 1 - CBS KVAN-1125M, 1200A KVAN-1125M 2 Rev. 2

3 CONTENTS 1.0 INTRODUCTION SAFETY RECEIVING, HANDLING, AND STORAGE RECEIVING AND HANDLING STORAGE DESCRIPTION AND OPERATION INTRODUCTION DESCRIPTION (Figure 4) MOVABLE FRAME STORED ENERGY OPERATING MECHANISM (Figure 6) OPERATION CHARGING OPERATION (Figure 10) CLOSING OPERATION (Figure 11) OPEN (TRIPPING OPERATION) (Figure 12) TRIP-FREE OPERATION RAPID AUTO-RECLOSE OPERATION CONTROLS AND INDICATIONS PREVENTATIVE MAINTENANCE AND ADJUSTMENTS GENERAL RECOMMENDED HAND TOOLS PREVENTATIVE MAINTENANCE RECOMMENDED ANNUAL INSPECTIONS PRIMARY POWER PATH CHECKS STORED ENERGY OPERATING MECHANISM CHECKS HIGH-POTENTIAL TESTS KVAN-1125M 3 Rev. 2

4 FIGURES Figure 1 - CBS KVAN-1125M, 1200A... 2 Figure 2 - CBS KVAN-1125M CIRCUIT BREAKER... 5 Figure 3 - CIRCUIT BREAKER LIFT POINTS... 7 Figure 4 - CIRCUIT BREAKER FRAME AND COMPONENTS... 8 Figure 5 - CIRCUIT BREAKER RATINGS NAMEPLATE... 9 Figure 6 - STORED ENERGY OPERATING MECHANISM Figure 7 - DISCONNECT ASSEMBLY Figure 8 - VACUUM INTERRUPTER, DETAIL Figure 9 - WIRING DIAGRAM Figure 10 - OPERATING MECHANISM, CIRCUIT BREAKER OPEN, CHARGING OPERATION Figure 11 - OPERATING MECHANISM, CIRCUIT BREAKER OPEN AND CHARGED - CLOSING OPERATION Figure 12 - OPERATING MECHANISM, CIRCUIT BREAKER OPEN AND CHARGED - OPENING OPERATION Figure 13 - CIRCUIT BREAKER CONTROLS Figure 14 - VACUUM INTERRUPTER EROSION MARK... Error! Bookmark not defined. Figure 15 - CONTACT WIPE GAP MEASUREMENT... Error! Bookmark not defined. Figure 16 - OPERATING MECHANISM COMPONENTS AND LUBRICATION POINTS Circuit Breaker Sales circuit breakers are tested and certified to ensure they are free of partial discharge. Circuit Breaker Sales recommends CBS ArcSafe remote racking solutions. KVAN-1125M 4 Rev. 2

5 FIGURE 2 - CBS KVAN-1125M CIRCUIT BREAKER 1.0 INTRODUCTION This manual covers the description; installation, operation, and maintenance of Circuit Breaker Sales (CBS ) Maxi-Vac type KVAN-1125 medium voltage vacuum circuit breakers. Personnel responsible for the operation of this equipment should be familiar with the procedures for the CBS type KVAN. 2.0 SAFETY Each user is responsible for maintaining a safety program to ensure the protection of personnel and equipment from the hazards associated with electrical equipment. The following basic industrial safety requirements apply to all major electrical equipment such as switchgear or switchboards. The following requirements are intended to augment the user s safety program but NOT supplant the user s responsibility for devising a complete safety program. CBS assumes no responsibility for practices that deviate from the following: ALL CONDUCTORS MUST BE ASSUMED TO BE ENERGIZED UNLESS THEIR POTENTIAL HAS BEEN MEASURED TO GROUND AND ADEQUATE CAPACITY GROUNDING ASSEMBLIES HAVE BEEN APPLIED TO PREVENT ENERGIZING. Many accidents have been caused by unplanned energization from unforeseen back feeds, equipment malfunctions, and other sources. VACUUM CIRCUIT BREAKERS ARE NOT TO BE CONSIDERED AS AN ISOLATING MEANS FOR PROVIDING SAFETY TO PERSONNEL UNLESS FULLY WITHDRAWN TO THE TEST POSITION. In the CONNECTED position with the breaker open, small leakage current with high voltage can flow across the open contacts. Also, leakage current can flow across the vacuum bottle or interrupter assembly if dirt or high humidity provides a path for tracking. It is strongly recommended that all equipment be completely de-energized, verified to be dead, and then grounded with adequate capacity grounding assemblies prior to performing any maintenance or troubleshooting. The grounding cable assemblies must be able to withstand energizing fault levels such that protective equipment may clear the circuit safely. See Chapter 20 of ANSI/NFPA 70B, Electrical Equipment Maintenance, for further information. Specific hazards throughout this instruction manual are presented in red danger call-outs, such as the following example: RED boxes contain information that point out potential hazards to personnel and equipment. KVAN-1125M 5 Rev. 2

6 While personnel should pay particular attention to the hazards presented in red danger call-outs, it would be impossible to alert the operator to every potential hazard. It is the responsibility of knowledgeable operators to rely on safe work practices to protect them from the inherent risks associated with industrial electrical equipment. Important information throughout this instruction manual is emphasized with green attention call-outs, such as the following example. ATTENTION GREEN ATTENTION boxes contain useful information to which the reader will want to pay particular attention. Circuit Breaker Sales Maxi-Vac circuit breakers are equipped with high-energy/high-speed mechanisms. The design includes several interlocks and safety features which help to ensure safe and proper operating sequences. To ensure the safety of personnel associated with the installation, operation, and maintenance of these circuit breakers, the following recommendations MUST be followed: Always ensure the circuit breaker displays OPEN/OFF prior to insertion to or removal from the connected position. Only qualified persons who are familiar with the installation and maintenance of medium-voltage circuit breakers should be permitted to work on these circuit breakers. Read this instruction manual before attempting any installation, operation, or maintenance of these breakers. DO NOT work on an energized circuit breaker DO NOT work on a circuit breaker unless all components are disconnected by means of a visual break and secure ground. DO NOT work on a circuit breaker while power is applied to the control power receptacle. DO NOT work on a closed circuit breaker; doing so may result in bodily injury. DO NOT work on a circuit breaker with a charged closing spring; doing so may result in bodily injury. DO NOT use a circuit breaker as the sole means of isolation of a high-voltage circuit. DO NOT install or remove circuit breakers without adequate personal protective equipment and/or a specifically designed remote racking device (contact CBS for remote racking solutions). 3.0 RECEIVING, HANDLING, AND STORAGE 3.1 RECEIVING AND HANDLING Every circuit breaker is carefully tested and inspected then packaged securely to ensure the breaker arrives safely. Immediately upon recipient, the circuit breaker should be examined to ascertain if any damage was sustained during transit. If damage or evidence of rough handling is present, or the Tip n Tell indicator is missing or disturbed, file a damage claim immediately with the transportation company and contact the Circuit Breaker Sales sales office. Remove all traces of packing, crating, and foreign material carefully. Exercise care while uncrating the circuit breaker so that no damage will occur from careless or rough handling or from exposure to moisture or dirt. Save the shipping material for storing the circuit breaker when not in use. Verify the order with the packing list to ensure that no components have been overlooked or misplaced, such as racking and charging tools, test reports, and instruction booklets. The circuit breaker is normally shipped in the CLOSED position with the springs DISCHARGED to KVAN-1125M 6 Rev. 2

7 prevent damage from occurring to the vacuum interrupter during shipment. Verify the indicator flags (Figure 13-5) on the front of the circuit breaker display OPEN and DISCHARGED prior to uncrating, moving, installing, or removing. When lifting the circuit breaker, use of lift rigging is recommended. Two lift locations, one per side, are provided on the right and left sides of the circuit breaker housing (Figure 3). When lifting, ensure a properly rated lifting apparatus is used, lift and lower the circuit breaker slowly, and avoid abrupt movements. completely covered and protected from rain, snow, dirt and all other contaminants. If the breaker is stored for any length of time, it should be inspected periodically to ensure that rust is not present and that the breaker is in good mechanical condition. Should the breaker be stored under unfavorable atmospheric conditions, it should be cleaned and dried out prior to being placed into service. DO NOT improperly lift the breaker via the primary disconnects. The circuit breaker, strapped to a pallet, can be moved with a properly rated forklift. The circuit breaker weight is 300 lbs., 350 lbs. crated). 3.2 STORAGE After inspection it is recommended that the circuit breaker be put into service in its permanent location immediately. If the circuit breaker cannot be placed into service ensure the following storage criteria are met: Store the breaker unpacked, OPEN, and DISCHARGED. FIGURE 3 - CIRCUIT BREAKER LIFT POINTS The breaker should be carefully protected against condensation, preferably by storing it in a warm, dry room of moderate temperature such as 5 37⁰C (41 98⁰F). An environment high in humidity may have an adverse effect on the circuit breaker insulation and should be avoided. The breaker should be stored in a clean location, free from corrosive gases or fumes; particular care should be taken to protect the equipment from moisture and cement/mineral dust, as this combination has a very corrosive effect on many breaker components. Cover the circuit breaker with a plastic sheet to protect from dust, dirt and small animal or insect infestation. Outdoor storage is not recommended. When no other option is available, the breaker must be KVAN-1125M 7 Rev. 2

8 FIGURE 4 - CIRCUIT BREAKER FRAME AND COMPONENTS 1. Faceplate 4. Insulating Phase Barriers 6. Movable Frame (Truck) 2. Operating Mechanism 5. Primary Disconnects 7. Fixed Wheels (x4) 3. Ratings Nameplate 4.0 DESCRIPTION AND OPERATION 4.1 INTRODUCTION This section provides basic descriptions of the circuit breaker components and its operation. A thorough understanding of the KVAN-1125M circuit breaker hardware must be reached prior to installation, operation, and maintenance of the equipment. The circuit breakers described in this manual are designed and tested to operate within their nameplate ratings. OPERATION OUTSIDE OF THE RATINGS MAY CAUSE EQUIPMENT TO FAIL, RESULTING IN PROPERTY DAMAGE, BODILY INJURY, AND/OR DEATH. 4.2 DESCRIPTION (Figure 4) The KVAN-1125 circuit breaker is comprised of a movable frame (truck) (6), on which is mounted the stored energy operating mechanism (2) and the disconnect assembly (4, 5), ATTENTION All descriptions of circuit breaker operations and component locations assume the operator/reader is viewing the circuit breaker from the front unless otherwise stated MOVABLE FRAME The movable frame is constructed of heavygauge steel and is the main support structure of the circuit breaker. The frame includes of the steel wheels (Figure 4-8), and the faceplate (Figure 4-1, 2). Steel Wheels Four non-pivoting steel wheels provide a means repositioning the circuit breaker in the switchgear and removing the breaker from the cubicle for circuit isolation and maintenance. Operating Mechanism Faceplate The circuit breaker mechanism faceplate protects the operator from both the control voltage and the high-energy moving parts of the operating mechanism. The circuit breaker ratings nameplate (Figure 5) is mounted to the operating mechanism faceplate. KVAN-1125M 8 Rev. 2

9 FIGURE 5 - CIRCUIT BREAKER RATINGS NAMEPLATE KVAN-1125M 9 Rev. 2

10 FIGURE 6 - STORED ENERGY OPERATING MECHANISM 1. Auxiliary Switch 5. Operations Counter 9. Closing Spring 2. Anti-Pump Relay 6. Trip (Open) Coil 10. Motor Cut-Off Switch (LS1) 3. Charging Motor 7. Close Coil 11. Closing Spring Charged Switch 4. Aux. Switch Operating Linkage (LS2) STORED ENERGY OPERATING MECHANISM (Figure 6) The stored energy operating mechanism is the main electrical and mechanical control assembly of the circuit breaker. The mechanism consists of the following components: the charging motor (3), the closing and tripping springs (10), the dashpot assemblies, the close (9) and trip solenoids (6), the anti-pump relay (2), the auxiliary (1) and limit switches (11, 12). The stored energy operating mechanism provides for the opening and closing of the circuit breaker both mechanically and electrically. All elements of the stored energy operating mechanism are contained in the circuit breaker mechanism housing. A detailed explanation of the stored energy operating mechanism is described in Section 4.3. Charging Motor (3) The charging motor drives the operating mechanism which converts the rotational energy of the motor to compress (charge) the closing spring whenever control power is available and the spring is discharged. The operating mechanism can also be charged manually via the charging screw and handle. Closing and Tripping Springs (10) The closing and tripping springs are compressed to store energy for future breaker operation. The closing spring is located on the right side of the housing. The closing spring is charged and discharged via the rotation of the crank arm mounted on the rotating main KVAN-1125M 10 Rev. 2

11 camshaft. The fixed end of the closing spring is attached to a support arm which in turn is bolted to the structure of the circuit breaker. The tripping spring is located on the bottom rear side of the housing. The tripping spring is connected to the jackshaft. When the closing spring is discharged, closing the circuit breaker, rotation of the jackshaft causes the tripping spring rod to extend and charge the tripping spring. Consequently, the tripping spring is automatically charged when the breaker is closed by the closing spring. Dashpot Assemblies The circuit breakers are equipped with a dashpot assembly on phases A and C, located on the rear of the housing. The dashpots are pistons, vented to oil. The dashpot piston absorbs the opening energy of the circuit breaker, limiting the force on the operating mechanism during an opening operation. Close Solenoid (9) Mechanically or electrically activating the armature of the close solenoid triggers the release of the energy stored in the closing spring, which in turn forces the three insulating push-rods to reposition the movable vacuum interrupter contacts vertically, closing the circuit breaker. Limit Switches (11, 12) In addition to the main auxiliary switch, the circuit breaker contains two limit micro-switches for use in the circuit breaker control circuitry. The motor cutoff switch (LS1) (11) is used to sense the position of the operating mechanism. The switch energizes the charging motor when the closing spring is discharged and opens once the closing spring is fully charged. The closing spring charged switch (LS2) (12) operates in conjunction with the motor cutoff switch (LS1). The closing spring charged switch allows the closing solenoid to be energized only when the closing springs are fully charged. The switch is also used in the anti-pump circuit DISCONNECT ASSEMBLY The disconnect assembly is the primary current path of the circuit breaker. The disconnect assembly is comprised of the primary (Figure 4-5) disconnects, the vacuum interrupters (Figure 8), insulating pushrods, and the phase barriers (Figure 4-4). Trip Solenoid (6) Mechanically or electrically activating the armature of the trip solenoid allows the energy stored in the tripping spring to rotate the jackshaft. Rotation of the jackshaft pulls the pushrods attached to the movable contacts within the vacuum interrupters downward, opening the circuit breaker. Anti-pump Relay (2) The anti-pump relay electrically isolates signals to the close solenoid so that a single close signal cannot cause multiple closings of the circuit breaker. The circuit breaker must be tripped, the closing springs recharged, and the close signal removed (interrupted) to reset the anti-pump relay, allowing the close solenoid to be reenergized and thus the breaker to be closed. Auxiliary Switch (1) The breaker-mounted auxiliary switch provides auxiliary contacts for the control circuitry of the circuit breaker and contacts for use in relaying and external logic circuits. The auxiliary switch is actuated by linkage connected to the jackshaft. The auxiliary switch contains both normally open (A) and normally closed (B) contacts. To clarify, when the circuit breaker is closed, A contacts are closed, while B contacts are open. FIGURE 7 - DISCONNECT ASSEMBLY Vacuum Interrupters (Figure 8) Each circuit breaker contains three vacuum interrupters (commonly known as vacuum bottles), one bottle per phase. The vacuum interrupters are essentially a KVAN-1125M 11 Rev. 2

12 movable and stationary contact enclosed within a vacuum chamber. The upper, stationary terminal of the vacuum interrupter is connected to the upper disconnect stud of the stored energy operating mechanism which in turn is connected through a copper bus-bar to the upper primary disconnect. The interrupter lower, movable terminal passes through the ring contactor of the lower disconnect stud and connects to the driving mechanism of the circuit breaker via an insulated push-rod; the lower disconnect stud is connected to the lower primary disconnect of the circuit breaker via a copper busbar. A metal bellows assembly provides a secure seal around the movable contact, preventing a loss of vacuum while permitting vertical motion of the movable contact. Insulated Push-rods There are three insulated push-rods. Each push-rod connects the movable terminal of one of the vacuum interrupters to the jackshaft of the stored energy operating mechanism. The push-rods transfer the work from the stored energy operating mechanism to the movable terminals while insulating the high voltage potential present on the primary disconnect assembly from the circuit breaker frame and operating mechanism. Primary Disconnects (Figure 4-5, Figure 7) The circuit breaker has three sets of primary disconnects, one set per phase. The three upper primaries are connected to the stationary terminals of the vacuum interrupters, the three lower primaries attach to the movable terminals. When the circuit breaker is in the CONNECTED position, the female primary disconnects connect with male, stationary disconnect studs in the cubicle. Phase Barriers (Figure 4-4) Each vacuum interrupter assembly is insulated via its vacuum interrupter phase barrier. FIGURE 8 - VACUUM INTERRUPTER, DETAIL KVAN-1125M 12 Rev. 2

13 FIGURE 9 - WIRING DIAGRAM KVAN-1125M 13 Rev. 2

14 FIGURE 10 - OPERATING MECHANISM, CIRCUIT BREAKER OPEN, CHARGING OPERATION 4.3 OPERATION This section introduces and explains the modes of CBS Maxi-Vac Type KVAN-1125 circuit breaker operation. The status conditions of the circuit breaker are the charging, closing, opening (tripping), trip-free, and rapid auto-reclosing modes of operation. Also included in this section is an explanation of the circuit breaker interlocks, spring dump and MOC actuator mechanisms CHARGING OPERATION (Figure 10) In charging operation it is assumed that the breaker is OPEN and inserted in the compartment in the TEST or CONNECTED position. When the secondary disconnect is connected, the motor disconnect switch is in the ON position and control power is applied to auxiliary disconnect pins 2 and 5, the charging motor will energize. Rotation of the charging motor rotates the bevel gear and offset shaft which translates the rotational work of the motor to the vertical, reciprocating motion of the driving pawl. As the driving pawl is lowered and raised, the lower end of the pawl engages the ratchet wheel on the operating main camshaft (6). ATTENTION All explanations assume that the reader/operator has read and understands the descriptions of the circuit breaker components in Section 4.2 and the breaker control schematic presented in Figure 11. Through ratcheting, the reciprocation of the driving pawl is converted to rotation of the main camshaft. As the camshaft is rotated the closing spring crank arm rotates and charges the closing spring. When the closing spring is charged, two cams on the mechanism camshaft open the motor cutoff limit switch (LS2), and close the closing spring charged switch (LS1). Opening the motor cutoff switch deenergizes the charging motor. The closing spring is now charged. The close hook (12-9) latches the energy stored in the closing spring from continuing to rotate the camshaft and close the breaker. The circuit breaker can also be charged manually. The circuit breaker is manually charged by inserting the charging handle into the charging screw. The charging screw is accessible through an opening in the housing faceplate. Clockwise hand rotation of the charging handle rotates the charging pinion, which charges the closing springs as previously described. ATTENTION The circuit breaker cannot be over-charged if the charging screw is excessively operated. KVAN-1125M 14 Rev. 2

15 FIGURE 11 - OPERATING MECHANISM, CIRCUIT BREAKER OPEN AND CHARGED - CLOSING OPERATION CLOSING OPERATION (Figure 11) In an effort to simplify the explanation of circuit breaker operation, the initial conditions for the closing operation assume that the charging operation has occurred; the breaker is inserted in the TEST or CONNECTED position and the breaker status is OPEN and CHARGED. The charging operation ensures that the closing spring charged switch (LS2) is closed, completing a path for the closing signal For the purpose of explaining the circuit breaker closing operation it is assumed that the anti-pump circuit is satisfied. A closing signal applied to auxiliary disconnects pins 7 or 6 and 4 energizes the closing coil (52C) which forces the solenoid armature against the close hook (Figure 10-9); pushing the green close pushbutton (I) on the circuit breaker faceplate accomplishes the same task to manually close the breaker. Mechanically or electrically activating the armature of the close solenoid releases the close hook, discharging the energy stored in the closing spring which rotates the operating mechanism main camshaft. Levers on the jackshaft rotate upward, forcing the three insulating push-rods (Fig ) to reposition the movable vacuum interrupter contacts vertically (Figure 10-8), closing the circuit breaker. The trip hook (Figure 10-5) latches the trip hook roller (Figure 10-4), holding the mechanism in the closed position. During the closing operation the closing springs are discharged; thus, a charging operation will occur (Figure 10). Anti-pump circuit The anti-pump circuit electrically isolates signals to the close solenoid so that a single close signal cannot cause multiple closings of the circuit breaker. The circuit breaker must be tripped, the closing springs recharged, and the close signal removed (interrupted) to reset the anti-pump relay, allowing the close solenoid to be reenergized and thus the breaker to be closed. As discussed in the previous section, when the circuit breaker closes, the A contacts of the auxiliary switch close while the B contacts open. When the circuit breaker closes, the normally closed, auxiliary contact (52B) opens, preventing the closing coil from being energized until the circuit breaker is tripped. The anti-pump relay (52Z) is energized by closing of the normally open (52A) contacts in the closing circuit. The anti-pump relay closes a maintaining contact, keeping the relay energized until the operator removes (interrupts) the closing signal to the breaker. The relay also opens a contact in series with the closing coil (52C), removing power to the closing coil (52C). The anti-pump circuit is reset by removing power from the closing circuit. KVAN-1125M 15 Rev. 2

16 FIGURE 12 - OPERATING MECHANISM, CIRCUIT BREAKER OPEN AND CHARGED - OPENING OPERATION OPEN (TRIPPING OPERATION) (Figure 12) In an effort to simplify the explanation of circuit breaker operation, the initial conditions for the opening operation assume that the closing operation has occurred; the breaker is inserted in the TEST or CONNECTED position, and the breaker status is CLOSED and CHARGED. The closing operation rotates the jackshaft Figure 10-11) which causes the tripping spring rod to extend and charge the tripping spring. Consequently, the tripping spring is automatically charged when the breaker is closed by the closing spring. Closing the circuit breaker closes the normally open auxiliary contact (52A) in series with the tripping coil. A tripping signal applied to auxiliary disconnect pins 3 or 10 and 9 energizes the tripping coil (52T), which activates the solenoid armature against the trip hook (Figure 10-5); pushing the red trip pushbutton (O) on the circuit breaker faceplate accomplishes the same task to manually trip the breaker. Mechanically or electrically activating the armature of the trip solenoid releases the trip hook roller (Figure 10-4). Releasing the trip hook roller allows the operating mechanism to rotate; discharging the energy stored in the tripping spring, and consequently rotating the operating mechanism jackshaft. Levers on the jackshaft rotate downward, forcing the three insulating push-rods to reposition the movable vacuum interrupter contacts vertically, opening the circuit breaker TRIP-FREE OPERATION The KVAN-1125 circuit breaker is mechanically and electrically trip-free ; this important function enables the breaker to be tripped prior to, during, or after a closing operation. Whenever the circuit breaker trip hook is released and held either manually or electrically: A circuit breaker will open. A circuit breaker in the process of closing will not complete the closing operation and will remain open. An open circuit breaker will not be able to be closed RAPID AUTO-RECLOSE OPERATION As explained in Section and 4.3.2, the closing springs are recharged by the charging motor when the circuit breaker is closed, thus the circuit breaker can be closed immediately following an opening operation. The operating mechanism is capable of the OPEN CLOSE OPEN duty cycle required for rapid auto-reclosing. The trip hook prevents the release of the closing springs if the trip hook roller is not in its reset position, ensuring the mechanism does not operate trip-free on an instantaneous re-closure. KVAN-1125M 16 Rev. 2

17 1. Operations Counter 2. Manual Charging Mechanism 3. Manual Close Button 4. Manual Open Button 5. On/Off Breaker Contact Status Indicator 6. Charged/Discharged Stored Energy Operating Mechanism Indicator 7. Nameplate 5.0 CONTROLS AND INDICATIONS The controls and indications are located on the front of the circuit breaker housing; see Figure 13. FIGURE 13 - CIRCUIT BREAKER CONTROLS KVAN-1125M 17 Rev. 2

18 6.0 PREVENTATIVE MAINTENANCE AND ADJUSTMENTS 6.1 GENERAL Periodic inspections and maintenance are essential to obtain safe and reliable operation of the circuit breaker. When the circuit breaker is operated infrequently (fewer than 20 times per week), and is located in a clean and dry indoor location, annual inspections are generally satisfactory. However, when the circuit breaker is operated more than 20 times per week, or when adverse environmental conditions exist, it is likely that more frequent inspections are required. The maintenance section of the operations manual is designed to provide general guidance for maintenance practices to supplement, not supplant, maintenance programs. It is the responsibility of technical personnel to adapt the following maintenance guidelines to the specific operating conditions that are present. Only qualified persons who are familiar with the installation and maintenance of medium-voltage circuit breakers should be permitted to work on these circuit breakers. Read this instruction manual before attempting any installation, operation, or maintenance of these breakers. DO NOT work on an energized circuit breaker. DO NOT work on a circuit breaker unless all components are disconnected by means of a visual break and secure ground. DO NOT work on a circuit breaker while power is applied to the control power receptacle. DO NOT work on a closed circuit breaker; doing so may result in bodily injury. DO NOT work on a circuit breaker with a charged closing spring; doing so may result in bodily injury. The circuit breaker housing protects the operator from both the control voltage and the high-energy moving parts of the operating mechanism; removing the circuit breaker housing will expose the operator to these hazards RECOMMENDED HAND TOOLS CBS Maxi-Vac KVAN-1125 circuit breakers utilize metric and standard fasteners. The following hand tools, materials and test equipment are those normally used in disassembly, re-assembly, and testing procedures: Torque Wrench, Nm (0-100 ft-lbs) Socket and Combination Wrenches 6, 8, 10, 12, 16 mm Screwdriver Set, Phillips and Standard Pliers Dry, lint-free cloths Mobil 28 Contact Grease (or equivalent) Nye RHEOLUBE 363 Grease (or equivalent) No. 1, No. 2, Isopropyl, or Isobutyl Alcohol Mobil 1 or SAE 10 Motor Oil with rust inhibitors HIGH-Potential Test Set 2500 and 500VDC Megger Micro-ohmmeter (Ductor) 6.2 PREVENTATIVE MAINTENANCE RECOMMENDED ANNUAL INSPECTIONS Periodic inspections occurring at annual, or more frequent, intervals should include all of the following tasks: Checks of the primary power path Checks of the vacuum interrupter Checks of the mechanism Checks of the control power High-potential test Inspection and cleaning KVAN-1125M 18 Rev. 2

19 As Found Tests Some users perform As Found insulation tests using a Megger or Doble testing to give an As Found value for future comparative indication of insulation change. This is especially desirable for new circuit breakers if they are to be stored for extended periods, and may absorb moisture or contaminants. Since wide variations can occur in insulation values because of atmospheric conditions, contamination, and test equipment, discrete values cannot be given. However, making and recording test values on new equipment and at regular intervals will give a comparative indication of insulation condition. Maintaining a permanent record of these values for each circuit breaker should be part of the Maintenance Program. *Always open and close breakers installed in energized switchgear by remote means PRIMARY POWER PATH CHECKS The primary power path consists of the three vacuum interrupters and the six primary disconnects. These components are checked for cleanliness and condition. The vacuum integrity of the vacuum interrupters is also verified. 1. Inspect the primary disconnect insulators for physical integrity and cleanliness, and verify they are free of marring or damage. 2. Check the fasteners of the primary power path for tightness. 3. Perform the vacuum integrity verification detailed in the high-potential test section STORED ENERGY OPERATING MECHANISM CHECKS The operating mechanism checks are divided into mechanical and electrical checks. Mechanical Checks The first series of checks determines if the mechanism operates smoothly without control power, is clean, and is adequately lubricated. A vacuum interrupter contact erosion measurement is also performed. The circuit breaker operating mechanism contains high-energy moving parts. Use caution when the circuit breaker is closed and the springs are charged. 1. Discharge the stored energy mechanism by pressing the trip button, the close button, and the trip button again in succession. 2. Remove the circuit breaker housing faceplate. 3. Inspect the circuit breaker mechanism for signs of excessive wear and general cleanliness; place special attention upon the closing spring cranks, closing camshaft, jackshaft and the various pushrods and linkages. 4. Clean the entire stored energy operating mechanism with a dry, lint-free cloth. 5. Under normal service conditions, the KVAN circuit breaker should be lubricated every 2,000 closing operations. See Figure 16 for lubrication points. 6. Lubricate all non-electrical moving or sliding surfaces with a light coat of machine oil containing a rust inhibitor: Bearing and sliding surfaces use Nye RHEOLUBE 363 grease or equivalent. Pivots and articulated joints use Mobil 1 or SAE 10 motor oil with rust inhibitors. Electrical Fastener Torque Requirements BOLT HEAD SIZE TORQUE (ft-lbs.) TORQUE (N-m) 5/ /2" / /4" ATTENTION Clean but DO NOT lubricate the dashpot assemblies. 7. Perform a fastener check. Inspect all fasteners for tightness. Both lock-nuts and retaining devices are used. Replace any fasteners that KVAN-1125M 19 Rev. 2

20 appear to have been frequently removed and replaced. 8. Visually inspect the dashpot assembly for leaks or signs of wear. 9. Manual Operation Check Check the vacuum circuit breaker operation manually. a. Manually charge the closing spring with the manual charging handle. b. Once fully charged, close the circuit breaker via the CLOSE pushbutton. c. Open the circuit breaker by pressing the OPEN pushbutton. d. Operate the circuit breaker several times successively. e. Verify the circuit breaker operates smoothly and free of defects. f. Close the circuit breaker to perform the contact erosion check. 10. Check contact wear of the vacuum interrupters. Replace the vacuum interrupters when the wipe gauge will not insert to the specified gap. 11. Perform the Spring Discharge Procedure. 12. Clean the barriers and primary insulators with a clean, lint-free cloth and No. 1 or No. 2 denatured alcohol or isopropyl or isobutyl alcohol. If the insulation material is exceptionally contaminated, clean with a mild soap with water and follow with alcohol. ATTENTION If As Found testing is desired, delay the cleaning of the insulation until testing is performed. 13. Replace all barriers, ensuring all fasteners are tight and in adequate condition. Electrical Checks The electrical controls of the KVAN-1125 circuit breaker should be tested annually after it is verified the circuit breaker is free of mechanical faults. The electrical control check verifies proper operation of the automatic spring charge, close, trip, and anti-pump circuits. Unless otherwise noted, all tests are performed without control power applied to the circuit breaker. 1. Check circuit breaker wiring and terminals. Physically check all wiring of the circuit breaker for evidence of abrasion, cuts, burning, or other physical damage. Ensure all terminals are securely attached to their respective devices. ATTENTION A temporary source of control power and test leads is required to verify the electrical circuits of the circuit breaker if a control power test plug is unavailable. 2. Energize the control power source, and verify the closing spring charged. 3. Electrically operate the circuit breaker several times to verify it is functioning properly. 4. To check the anti-pump circuits, with the circuit breaker open, apply and maintain power to the closing circuit; the breaker will close. With power applied to the closing circuit, power the trip circuit to open the circuit breaker. The circuit breaker should open and remain open. Interrupt the power applied to the closing circuit and the breaker will close. 5. The spring charge motor brushes require inspection every 7,000 operations. Use the circuit breaker operations counter to determine if brush inspection/replacement is necessary HIGH-POTENTIAL TESTS The next series of tests involve the use of highvoltage test equipment. The voltages for highpotential tests are: Equipment kv Rating 15kV Maximum Test Voltage 36kV DC HIGH-POTENTIAL tests employ HAZARDOUS VOLTAGES which will cause SEVERE PERSONAL INJURY AND/OR DEATH. Follow safe procedures, exclude unnecessary personnel and use safety barriers. Maintain a safe distance from the circuit breaker while test voltages are applied. KVAN-1125M 20 Rev. 2

21 Vacuum interrupters may emit X-RAY RADIATION which can cause BODILY INJURY. X-rays can be produced when a high voltage is placed across two circuit elements in a vacuum. Keep personnel more than six (6) DO NOT use DC HIGH-POTENTIAL test devices incorporating half-wave rectification; these devices produce HIGH PEAK VOLTAGES. High peak voltages will produce X-ray radiation; these devices also show erroneous readings of leakage current when testing vacuum circuit breakers. 1. Vacuum Interrupter Integrity Verification A high-potential test is used to verify the vacuum integrity of the circuit breaker. a. Observe safety precautions listed in the danger call-outs. b. Ensure the circuit breaker is OPEN. c. Ground each pole not under test. 2. Apply test voltage across each pole for one minute. 3. The vacuum integrity is verified if the pole sustains the test voltage for the duration it is applied. 4. As-found Insulation Tests Insulation tests verify the integrity of the breaker insulation system. Megger and/or Doble tests performed on the circuit breaker at the factory prior to installation provide a basis for future comparison to detect changes in the protection afforded by the insulation system. A permanent record of as-found tests enables the maintenance organization to determine when corrective actions are required by watching for sudden deterioration in insulation resistance or increases in contact resistance. a. Observe safety precautions listed in the red danger call-outs. b. Manually charge and close the circuit breaker using the procedures detailed in Section 1.2. c. Ground each pole not under test d. Apply a 2500VDC high-potential test voltage between a primary conductor of the pole and ground for one minute. e. If no disruptive discharge occurs over the duration of the applied voltage and/or insulation resistance levels are >1,000MΩ, the insulation system is satisfactory. f. After the test, ground each end and the center of each vacuum bottle to dissipate any static charge. Repeat the test pole-topole and across open poles. g. Disconnect the leads to the charging motor. h. Connect all points of the control power plug to a shorting wire(s). Connect the shorting wire(s) to the high-potential lead of a 500VDC Megger set and the breaker housing to ground. i. If no disruptive discharge occurs and/or insulation resistance levels are >50MΩ, the control power wiring insulation level is satisfactory. j. Remove the shorting wire(s) and re-attach the charging motor leads. k. Using a micro-ohmmeter (Ductor), perform contact resistance test of the primary contacts. Investigate any values which deviate from other poles and historical data by more than 50 percent of the lowest value. l. Make a permanent record of all tests performed for trending/analysis. KVAN-1125M 21 Rev. 2

22 FIGURE 14 - OPERATING MECHANISM COMPONENTS AND LUBRICATION POINTS KVAN-1125M 22 Rev. 2

23 KVAN 23 Rev. 9 Notes:

24 KVAN 24 Rev. 9

25

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breaker (Vehicle) Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers DEH41480 Test Cabinet (Inspection Box) for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers Instructions 1 Table of Contents Section 1. Introduction

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type GER 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9978D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

S&C Type FVR Substation Circuit Breaker

S&C Type FVR Substation Circuit Breaker S&C Type FVR Substation Circuit Breaker 15 kv to 38 kv, 200 kv BIL, 1200 A, Class 6065 Instructions for Installation 60553014 S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

EISHO TEK. Vacuum Circuit Breaker

EISHO TEK. Vacuum Circuit Breaker EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who

More information

PowlVac Type PV STD/CDR Vacuum Circuit Breaker

PowlVac Type PV STD/CDR Vacuum Circuit Breaker Instructions PowlVac Type PV STD/CDR Vacuum Circuit Breaker Installation Maintenance Renewal Parts POWELL ELECTRICAL MANUFACTURING COMPANY 8550 MOSLEY DRIVE HOUSTON, TEXAS 77075 USA PHONE (713) 944-6900

More information

IB PowlVac CDR Vacuum Circuit Breaker. 5kV & 15kV 1200A, 2000A, & 3000A. Powered by Safety

IB PowlVac CDR Vacuum Circuit Breaker. 5kV & 15kV 1200A, 2000A, & 3000A. Powered by Safety IB-60202 PowlVac CDR Vacuum Circuit Breaker 5kV & 15kV 1200A, 2000A, & 3000A Powered by Safety IB-60202 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com Service

More information

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988 Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

IB PowlVac ITE-HK Remote Racking Device

IB PowlVac ITE-HK Remote Racking Device IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type AMR For Allis Chalmers 5kV Instructions Installation Operation Maintenance E50001-U229-A289-X-US00 Hazardous voltages and high-speed moving parts. Will cause death,

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Type 3AH kv to 38 kv vacuum circuit breaker operator module instruction manual

Type 3AH kv to 38 kv vacuum circuit breaker operator module instruction manual Type 3AH35 15.5 kv to 38 kv vacuum circuit breaker operator module instruction manual Installation operation maintenance E50001-F710-376-X-4A00 Answers for energy. Hazardous voltages and high speed moving

More information

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968 Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9968 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices IB 6.2.13.7-1 1 Rev. 4, June 2000 ADVAC TM INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices Power T&D Company, Inc. Distribution Systems Division

More information

Powered by Safety 01.4IB.77000B PowlVac-ND Vacuum Circuit Breaker

Powered by Safety 01.4IB.77000B PowlVac-ND Vacuum Circuit Breaker Powered by Safety PowlVac-ND Vacuum Circuit Breaker 5kV / 1200A & 2000A / 36kA & 50kA PowlVac-ND Vacuum Circuit Breaker Contact Information Powell Electrical Systems, Inc. powellind.com info@powellind.com

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers User manual W-VACi W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers 65A7355H01 Rev.04 January 2013 www.eaton.com 2 Table of contents 1 Safety... 5 1.1 Safety precautions...5 1.2 Safety practices...5

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9968A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

1. Safety practices General Introduction Standards...3

1. Safety practices General Introduction Standards...3 1. Safety practices...2 2. General...3 2.1 Introduction...3 2.2 Standards...3 3. Technical data...3 3.1 Designation...3 3.2 Electrical ratings and dimensions...4 3.3 Fixation...6 3.4 Connecting terminals...6

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.

More information

ADVAC Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual

ADVAC Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual ADVAC Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual 1 2 TABLE OF CONTENTS FORWARD... 3 INTRODUCTION & SAFE PRACTICES... 4 RECEIVING, HANDLING, & STORAGE... 5 ACCESSORIES... 6

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

Power Break Circuit Breakers

Power Break Circuit Breakers Draw Out 800-4000 Amperes GEH-46988 Installation Instructions Power Break Circuit Breakers POWER BREAK Draw Out Circuit Breaker (SOOA 4000A) DESCRIPTION Types TC, and THC Power Break draw out circuit breakers

More information

Type 38-3AH3 38 kv vacuum circuit breaker instruction manual. Installation operation maintenance E50001-F710-A238-V1-4A00. Answers for energy.

Type 38-3AH3 38 kv vacuum circuit breaker instruction manual. Installation operation maintenance E50001-F710-A238-V1-4A00. Answers for energy. Type 38-3AH3 38 kv vacuum circuit breaker instruction manual Installation operation maintenance E50001-F710-A238-V1-4A00 Answers for energy. Hazardous voltages and high speed moving parts. Will cause death,

More information

Instruction manual. Types GMSG and GMSG-GCB 5 kv to 15 kv vacuum circuit breakers.

Instruction manual. Types GMSG and GMSG-GCB 5 kv to 15 kv vacuum circuit breakers. Instruction manual Types GMSG and GMSG-GCB 5 kv to 15 kv vacuum circuit breakers Installation operation maintenance E50001-F710-A231-V3-4A00 www.usa.siemens.com/mvswitchgear Hazardous voltages and high

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...

More information

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator GE Consumer & Industrial Electrical Distribution Operation & Maintenance Manual GEK-99986 Catalog # WPEGRRLV 115 VAC, 60/50 Hz Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking

More information

ADVAC TM Model 03 Medium Voltage Vacuum Power Circuit Breakers and Auxiliary

ADVAC TM Model 03 Medium Voltage Vacuum Power Circuit Breakers and Auxiliary 1 ABB IB 6.2.15.7-1C ADVAC TM Model 03 Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Installation/Maintenance Instructions IB 6.2.15.7-1C November 2005 ABB IB 6.2.15.7-1C 2 TABLE OF CONTENTS

More information

ADVAC Model 3 Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual

ADVAC Model 3 Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual DISTRIBUTION SOLUTIONS ADVAC Model 3 Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual Table of contents Forward 2 Introduction & Safe pratices 3 Receiving, handling, and storage

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure

More information

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) Inspection Recommendations for Switchgear with Type AT-3 Source- Transfer Controls Table of Contents Section

More information

Introduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)

Introduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) Inspection Recommendations for Switchgear Equipped with Type AT-2 Source-Transfer Controls Table of Contents

More information

Quick Start Guide TS 910

Quick Start Guide TS 910 Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible

More information

5HK-VR, 15HK-VR, & 17HK-VR - (Model 03) Replacement Circuit Breaker

5HK-VR, 15HK-VR, & 17HK-VR - (Model 03) Replacement Circuit Breaker Instruction Book IB182052EN Supersedes July 2017 Effective October 2018 5HK-VR, 15HK-VR, & 17HK-VR - (Model 03) 5HK-VR 250 1200A Shown DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

AM4.16/7.2/13.8-VR + VR-Series + Replacement Circuit Breaker

AM4.16/7.2/13.8-VR + VR-Series + Replacement Circuit Breaker Instruction Book IB182921EN Supersedes May 2017 Effective August 2018 AM4.16/7.2/13.8-VR + AM4.16-VR + 250 1200A Shown DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC Vacuum Circuit Breaker Type PVDB1 15.5 kv ML18/ML18H Spring Operating Mechanism Instruction Number GEK-90211C Table of Contents Section 1. Introduction 1-1 Safety...

More information

AMH-4.76-VR Replacement Circuit Breaker

AMH-4.76-VR Replacement Circuit Breaker Instruction Book IB182023EN Supercedes October 2013 Effective March 2016 AMH-4.76-VR AMH-4.76-VR 4.76 1200A Shown DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

CA Breaker Instruction Manual

CA Breaker Instruction Manual Volume 1 HOMEWOOD PRODUCTS CORPORATION Westinghouse Technology CA Breaker Instruction Manual HOMEWOOD PRODUCTS CORPORATION Compressed Air Circuit Breaker Homewood Products Corporation 820 Washington Blvd.

More information

McCANNA Actuation Systems B

McCANNA Actuation Systems B 17710-B Ramcon Series 8/25 C/CR, 50/100 B/BR, 250/500 B/BR Electric Actuators Installation, Operation and Maintenance Instructions Contents Storage...........................................................................................................

More information

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use. Instruction Bulletin Retain for future use. MASTERCLAD Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class 6055 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

COOKSON OWNER'S MANUAL

COOKSON OWNER'S MANUAL COOKSON OWNER'S MANUAL FDO-A10 INDUSTRIAL DUTY FIRE DOOR OPERATOR R L I S T E D 3040233 US CONTROL PANEL SERIAL# OPERATOR SERIAL# 9001.DWG ECN 0959 REV 4 SPECIFICATIONS MOTOR TYPE:...INTERMITTENT HORSEPOWER:...1/8

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

Circuit breaker interlocking and operation requirements SIEMENS

Circuit breaker interlocking and operation requirements SIEMENS Circuit breaker interlocking and operation requirements SIEMENS When manufacturers and specifiers discuss circuit breaker operational and interlocking requirements, several terms are used repeatedly. Despite

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version IB131018EN Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version Contents Description Page 1. Introduction...2 2. Description...2

More information

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12 ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12 We thank you for having purchased VCB s from us. We are sure you will be very happy with the performance and service of

More information

SecoVac * R Retrofill Vacuum Circuit Breaker

SecoVac * R Retrofill Vacuum Circuit Breaker GE DEH-5000 User Manual SecoVac * R Retrofill Vacuum Circuit Breaker 5-5kV 200A & 2000A Table of Contents. Introduction...5 Definitions...5 2. Safety...6 3. Receiving...7 Inspecting for Damage...7 Filing

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker

More information

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B. Cutler-Hammer Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS BOOKLET IN ITS

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers Instruction Leaflet IL2A12995H02 effective March 2012 Trip Indicator with Remote Reset for Magnum WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS

More information

Quick Start Guide TS 910 & TS 920

Quick Start Guide TS 910 & TS 920 Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer

More information

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters

More information

AM-4.16/7.2/13.8-VR Replacement Circuit Breaker

AM-4.16/7.2/13.8-VR Replacement Circuit Breaker Instruction Book IB182021EN Supercedes February 2016 Effective April 2016 AM-4.16/7.2/13.8-VR GE-AM-13.8-VR 500XU 2000A Shown DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

ES25 Battery-powered ACSR Cutter with 120 V Charger with 220 V Charger

ES25 Battery-powered ACSR Cutter with 120 V Charger with 220 V Charger INSTRUCTION MANUAL ES25 Battery-powered ACSR Cutter 22131 with 120 V Charger 22132 with 220 V Charger Read and understand all of the instructions and safety information in this manual before operating

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 Supersedes July 1997 IB694C694-02 Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 PURPOSE This

More information

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism AMVAC Universal applications: Medium voltage motor starting applications Capacitor switching Retrofit applications to replace

More information

ibusway for Data Center

ibusway for Data Center ibusway for Data Center PBPQOD Plug-In Units with 15 60 A Circuit Breakers for Use On Busway Straight Sections Class 5600 Installation S1B99523 06/2012 Hazard Categories and Special Symbols Read these

More information

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION Page: 1 Instructions for the Type VCP-W Ground & Test Device (Simple) Upper Terminal Set Version IB131007EN Effective May 2015 Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear

More information

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release)

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release) Document: GF07Z304 Rev. 2 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release) Issued: 10/2006

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES

More information

Operation and Maintenance Manual

Operation and Maintenance Manual DEH-41482 GE Energy Industrial Solutions Low Voltage Switchgear Remote Racking Operator For AKR Circuit Breakers Cat. # AKREGRR 115 VAC, 60/50 Hertz Operation and Maintenance Manual TABLE OF CONTENTS Section

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

HYDRAULIC SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL

HYDRAULIC SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL HYDRAULIC SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL TABLE OF CONTENTS SYSTEM...... Warning...... Description..... Prior to Operation... Preventative Maintenance..... OPERATION... Warning... Extending

More information

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Abstract: The development of the magnetically actuated vacuum interrupter

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual HQ 005. ELECTRIC ACTUATORS QUARTER-TURN ELECTRIC ACTUATORS Installation, Operation and Maintenance Manual s Version Ver. 1 Revision Rev. 1 Document No. HKQI-611 Small & Compact Design High corrosion resistance

More information

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36 ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36 We thank you for having purchased VCB s from us. We are sure you will be very happy with the performance and service of

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA) Instructions for the Use, Operation and Maintenance of Types T-VAC and T-VACR Vacuum Circuit Breakers Effective November 2017 T- VACR Fixed (up to 25kA) T-VAC Draw out (up to 25kA) T- VACR Fixed (up to

More information

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION Instruction Bulletin Bulletin No. 44027-017-01 Middletown, OH USA Class 6035 INTRODUCTION This bulletin contains instructions for adding a shunt trip assembly to a manual DS/DSL circuit breaker and modifying

More information

Instructions for Replacing

Instructions for Replacing e Instructions for Replacing Vacuum Bottle Subassemblies a on Type SJA, SJS and SJO 360 Amp Contactors l.l. 16-200-348 This l.l. includes illustrations and instructions for replacing vacuum bottle subassemblies

More information

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version Optimal Series Automatic Transfer Switch Installation and User Manual for the OPT2225 Automatic Transfer Switch Full Version File: OPT2225 Rev2.5.doc November, 2004 2 Thank You For Purchasing This DynaGen

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

O & M Manual for the EATON Generator Ready Loadcenter

O & M Manual for the EATON Generator Ready Loadcenter O & M Manual for the EATON Instructional Booklet New Information Description Page 1. Introduction............................... 2 2. Receiving, Handling, and Storage................ 4 3. Equipment Description........................

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com Instructions for Parcel-Line Type DH-P Circuit Breakers with Post Insulator Type Pole Units (Supplements I. B. 32-253-2) Westinghouse Electric Corporation Switchgear Division, East Pittsburgh, Pa. 15112

More information

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Door Restrictor Assembly. Model R2

Door Restrictor Assembly. Model R2 Door Restrictor Assembly Model R2 Every attempt has been made to ensure that this documentation is as accurate and up-to-date as possible. However, Vertical Express assumes no liability for consequences,

More information

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum

More information

INSTRUCTION MANUAL. HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) INSTALLATION - OPERATION - MAINTENANCE Document: GF07Z303 Rev 1 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6FS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes (Fast Closing) APPLICABLE MODEL NUMBERS: (Motor Operation

More information

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Voltage Regulators QD3/T350 Main Movable Contact Assembly Kit Kit 5741325B04 Service Information S225-50-42 Contents General..................................... 1 Tools Required..............................

More information

INSTRUCTION MANUAL. HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes INSTALLATION - OPERATION - MAINTENANCE Document: GF07Z301 Rev. 1 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HV6AS Vacuum Circuit Breakers Fixed Type 4.8 & 7.2kV Voltage Classes APPLICABLE MODEL NUMBERS: (Manual Operation Types)

More information

NAVSEA STANDARD ITEM 3. REQUIREMENTS:

NAVSEA STANDARD ITEM 3. REQUIREMENTS: NAVSEA STANDARD ITEM ITEM NO: 009-75 DATE: 01 OCT 2017 CATEGORY: II 1. SCOPE: 1.1 Title: Circuit Breaker; repair 2. REFERENCES: 2.1 Equipment Technical Manual 3. REQUIREMENTS: 3.1 Identify and pull back

More information