Design Guide for Integration of Fixed-Mount Circuit Breakers

Size: px
Start display at page:

Download "Design Guide for Integration of Fixed-Mount Circuit Breakers"

Transcription

1 Design Guide Design Guide for Integration of Fixed-Mount Circuit Breakers WL Low Voltage Power Circuit Breakers

2

3 Contents Introduction... 3 Mounting... 3 Mounting Surface... 3 Mounting Hardware... 4 Compartment Design... 5 Minimum Compartment Size... 5 Electrical Clearances... 6 Bus Bar Connections Rear Horizontal Bus Terminals Rear Vertical Bus Terminals Front-accessible Bus Terminals Front Bus Terminal Lug Kits Bus Bracing Phase Barriers Door Cut-Outs Flush Mounted Semi-Flush Mounted Control Wiring Space Additional Resources... 30

4 Design Guide for Integration of Fixed-Mount WL Low Voltage Power Circuit Breakers Introduction When designing electrical power distribution equipment, there are many important questions that must be answered. Improperly installed fixed-mount power circuit breakers can reduce the performance characteristics or the overall life span of the product. The following guidelines are offered as recommended practices for installing fixed-mounted Siemens type WL low-voltage power circuit breakers, covering topics such as mounting requirements, compartment size, minimum ventilation, electrical clearances, bus bar connections, and bus bracing. In addition to these recommended practices, applicable industry standards and regional code requirements should be considered. This Guide will highlight some of these issues and recommend corresponding solutions applying the Siemens type WL family of low voltage power circuit breakers. Mounting Mounting Surface WL Circuit Breakers should be mounted to a surface capable of supporting the weight of the circuit breaker and which is flat to within 3/64 inch. The approximate weights of the circuit breaker are listed in Table 1. Table 1: Weights Frame Size No. of Poles Interrupting Class Frame Rating (A) I 3 S, H, L II 3 S, L C S, H, L III 3 L H, L Approximate Weight (lbs) 3 WL Low Voltage Power Circuit Breakers Design Guide

5 3/64 The mounting surface may be tilted up to 30 in any direction, or combination thereof. Mounting Hardware The feet of the circuit breaker include four captive nuts, sized as shown in Table 2. Mounting hardware kits may be purchased from Siemens. Table 2 Frame Size Nut Size Hardware Kit Contents Recommended Torque I M8 WLMETRC M8 bolt (4) 15 lb-ft II M8 lockwasher (4) M8 flat washer (4) III M10 WLMETRC3 M10 bolt (4) M10 lockwasher (4) M10 flat washer (4) 30 lb-ft WL Low Voltage Power Circuit Breakers Design Guide 4

6 Compartment Design The following recommendations provide guidelines for minimum sizing of and clearances within the circuit breaker compartment. Other arrangements may be feasible, but must be validated by design testing in accordance with ANSI C37.50 or UL 489, as applicable. Minimum Compartment Size Minimum circuit breaker compartment sizes should be met in order to provide adequate interrupting and circuit breaker cooling space. Table 3 describes the recommended minimum circuit breaker compartment sizes. All fixed-mount WL circuit breakers are considered 100% rated when applied in accordance with Table 3. Note that WL circuit breakers rated below 3000 amperes do not require any ventilation openings within the circuit breaker compartment. For the greatest overall effectiveness of the ventilation (when necessary), the openings should be situated above and below the circuit breaker terminals. Table 3: Minimum Circuit Breaker Compartment Size Recommendations Frame Size No. of Poles Interrupting Class Frame Rating (A) Width (in.) Height (in.) Depth (in.) Cubicle Ventilation Top (in 2 ) I 3 S, H, L II 3 S, L, C S, H, L III 3 L C H, L Bottom (in 2 ) 5 WL Low Voltage Power Circuit Breakers Design Guide

7 Electrical Clearances In order to prevent flashover from phase-to-phase or phase-to-ground during circuit breaker operations, it is recommended that the specified minimum clearances be maintained at all times. Tables 4-8 describe various minimum recommended clearances for different construction considerations. Table 4 describes the minimum clearances to phase conductors or grounded metal components for an open circuit breaker compartment with no internal barriers. Maintaining these clearances will provide adequate arcing space above the circuit breaker to prevent a phase-to-phase or phase-to-ground arc flash event. Table 4: Minimum Clearances to Phase Conductors or Grounded Metal Components Frame Size No. of Poles Interrupting Class A1 (in.) B1 (in.) C1 (in.) System Voltage 480 V 600 V 480 V 600 V 480 V 600 V I 3 S H L II 3 S L S, H, L III 3 L H, L D A1 B1 C1 cubicle door / deadfront cover minimum distance from the top of the arc chute to the nearest grounded metal barrier or live parts above the circuit breaker minimum horizontal space above the arc chutes free of obstruction minimum distance to phase or neutral conductors located behind the circuit breaker WL Low Voltage Power Circuit Breakers Design Guide 6

8 Table 5 describes the minimum clearances to grounded metal components for an open circuit breaker compartment with grounded metallic internal barriers either behind the circuit breaker, above the circuit breaker, or both. Maintaining these clearances will provide adequate arcing space above the circuit breaker to prevent a phase-to-phase or phase-to-ground arc flash event. Table 5: Minimum Clearances to Grounded Metal Components Frame Size No. of Poles Interrupting Class A2 (in.) B2 (in.) C2 (in.) System Voltage 480 V 600 V 480 V 600 V 480 V 600 V I 3 S H L II 3 S L S, H, L III 3 L H, L D A2 B2 C2 cubicle door / deadfront cover minimum distance from the top of the arc chute to the nearest grounded metal barrier or live parts above the circuit breaker minimum horizontal space above the arc chutes free of obstruction minimum distance to an insulator or grounded metal barrier separating the circuit breaker from phase or neutral conductors 7 WL Low Voltage Power Circuit Breakers Design Guide

9 Table 6 describes the minimum clearances to phase conductors or insulated components for an open circuit breaker compartment with no internal barriers. Maintaining these clearances will provide adequate arcing space above the circuit breaker to prevent a phase-to-phase or phase-to-ground arc flash event. Table 6: Minimum Clearances to Insulated Materials Frame Size No. of Poles Interrupting Class A3 (in.) B3 (in.) C3 (in.) System Voltage 480 V 600 V 480 V 600 V 480 V 600 V I 3 S H L II 3 S L C S, H, L III 3 L C H, L D A3 B3 C3 cubicle door / deadfront cover minimum distance from the top of the arc chute to the nearest grounded metal barrier or live parts above the circuit breaker minimum horizontal space above the arc chutes free of obstruction minimum distance to phase or neutral conductors located behind the circuit breaker WL Low Voltage Power Circuit Breakers Design Guide 8

10 Table 7 describes the minimum clearances to insulated components for an open circuit breaker compartment with grounded metallic internal barriers either behind the circuit breaker, above the circuit breaker, or both. Maintaining these clearances will provide adequate arcing space above the circuit breaker to prevent a phase-to-phase or phase-to-ground arc flash event. Table 7: Minimum Clearances to Insulated Materials Frame Size No. of Poles Interrupting Class A4 (in.) B4 (in.) C4 (in.) System Voltage 480 V 600 V 480 V 600 V 480 V 600 V I 3 S H L II 3 S L C S, H, L III 3 L C H, L D A4 B4 C4 cubicle door / deadfront cover minimum distance from the top of the arc chute to an insulating barrier or insulated parts above the circuit breaker minimum horizontal space above the arc chutes free of obstruction minimum distance to an insulator or grounded metal barrier separating the circuit breaker from phase or neutral conductors 9 WL Low Voltage Power Circuit Breakers Design Guide

11 Table 8 describes the minimum clearances to an L -shaped insulation barrier isolating the arcing space above the circuit breaker from the rest of the circuit breaker compartment. Maintaining these clearances will provide adequate arcing space above the circuit breaker to prevent a phase-to-phase or phase-to-ground arc flash event. Table 8: Minimum Clearances to Insulated Materials Frame Size No. of Poles Interrupting Class A5 (in.) B5 (in.) System Voltage 480 V 600 V 480 V 600 V I 3 S H L II 3 S L C S, H, L III 3 L C H, L D A5 B5 cubicle door / deadfront cover minimum distance from the top of the arc chute to an insulating barrier above the circuit breaker minimum horizontal space above the arc chutes free of obstruction WL Low Voltage Power Circuit Breakers Design Guide 10

12 Bus Bar Connections Siemens offers several means of connecting the primary conductors to the circuit breakers: Rear horizontal bus terminals (standard) Rear vertical bus terminals (optional accessory kit) Front-accessible bus terminals (optional accessory kit) Table 9: Bus Bar Connection Options Frame Size No. of Poles Interrupting Class Frame Rating (A) Rear Horizontal Optional Connectors Rear Vertical I 3 S, H, L Standard Standard II 3 S, L, C Standard 3000 Standard 4 S, H, L Standard 3200 Standard III 3 L Standard C Standard 4 H, L Standard Front- Accessible Types of Conductors An appropriate number of conductors should be applied to each terminal to carry the load protected by the circuit breaker. The minimum number of conductors may differ based on bus geometry, applied coatings, presence (or absence) of nearby heat sources, air flow across the conductors, and other factors. Many industry standards provide a rule-of-thumb of a current density of 1000 amperes per square-inch of copper, or no more than 700 amperes per square-inch of aluminum. The following Table includes some conductor recommendations. 11 WL Low Voltage Power Circuit Breakers Design Guide

13 Table 10: Recommended Conductor Sizing Continuous Current (A) Conductor Quantity Size 800 Cu 1 1/4 x 3 Al 1 1/4 x Cu 2 1/4 x 3 Al 2 1/4 x Cu 2 1/4 x 3 Al 2 1/4 x Cu 2 1/4 x 4 Al 2 1/4 x Cu 2 1/4 x 5 Al 4 1/4 x / 3200 Cu 3 1/4 x Cu 4 1/4 x Cu 6 1/4 x 5 5 1/4 x 6 WL Low Voltage Power Circuit Breakers Design Guide 12

14 Rear Horizontal Bus Terminals Fixed-mount WL circuit breakers are supplied with silver-plated copper terminal pads. These pads are designed to accept bus bar assemblies, supported independently from the circuit breaker.! WARNING Hazardous energy. Improper support may cause serious injury or equipment damage. During short circuit events, the following connection methods may cause excessive strain on the conductors, which could result in rupturing of the circuit breaker housing, and therefore must be avoided: 1. Cable terminations directly to the circuit breaker terminal pads. 2. Flexible conductors connected directly to the circuit breaker terminal pads. 3. Unbraced/unsupported bus bar conductors connected directly to the circuit breaker terminal pads. Cable lugs and flexible conductors should not be connected directly to the circuit breaker terminals. These types of connectors (cable lugs and flexible conductors) may be connected to bus bars connected to the circuit breaker terminals beyond the first short-circuit brace. The mounting holes on the circuit breaker terminals are ø 19/32 in. It is recommended to use ½-13 SAE grade 5 hardware, torque to 50 lb-ft. A best practice for bus bar design is to include adjustment slots, to allow for minor alignment corrections before securing the circuit breaker terminals to the power distribution equipment s bus structure.! WARNING Hazardous energy. Improper support may cause serious injury or equipment damage. Bus bracing must be installed in a manner that does not apply excessive mechanical stress to the circuit breaker terminals or accessory connector kits. In order to facilitate even current distribution and minimize the potential for excessive heating when using multiple conductors per phase, it is advisable to mount bus bars to both the top and bottom surface of the circuit breaker terminals as shown below. 13 WL Low Voltage Power Circuit Breakers Design Guide

15 Frame Size I Frame Size II Frame Size III WL Low Voltage Power Circuit Breakers Design Guide 14

16 Rear Vertical Bus Terminals An alternative method to connect the primary conductors is via the rear vertical bus accessory kits. These silver-plated copper accessories rotate the standard horizontal conductors of the circuit breaker 90 degrees to a vertical orientation. These connectors are designed to accept bus bar assemblies, supported independently from the circuit breaker. Table 11: Rear Vertical Bus Terminal Kits Frame Size No. of Poles Interrupting Class Frame Rating (A) Catalog Number I 3 S, H, L WLH1R12CONUL II 3 S, L WLL2R16CONUL 2000 WLL2R20CONUL WLL2R30CONUL C WLC2R30CONUL 4 S, H, L WL4L2R16CONUL 2000 WL4L2R20CONUL * 3200 WL4L2R32CONUL * III 3 L, C WLC3R50CONUL 4 H, L WL4L3R50CONUL * * Supplied as standard for these circuit breaker ratings. WARNING Hazardous energy. Improper support may cause serious injury or equipment damage.! During short circuit events, the following connection methods may cause excessive strain on the conductors, which could result in rupturing of the circuit breaker housing, and therefore must be avoided: 1. Cable terminations directly to the circuit breaker terminal pads. 2. Flexible conductors connected directly to the circuit breaker terminal pads. 3. Unbraced/unsupported bus bar conductors connected directly to the circuit breaker terminal pads. Cable lugs and flexible conductors must not be connected directly to the rear vertical bus terminal connectors. These types of connectors (cable lugs and flexible conductors) may be connected to bus bars connected to the rear vertical bus terminal connectors beyond the first short-circuit brace. The mounting holes on the circuit breaker terminals are ø 19/32 in. It is recommended to use ½-13 SAE grade 5 hardware, torque to 50 lb-ft. 15 WL Low Voltage Power Circuit Breakers Design Guide

17 A best practice for bus bar design is to include adjustment slots, to allow for minor alignment corrections before securing the circuit breaker terminals to the bus structure of the power distribution equipment.! WARNING Hazardous energy. Improper support may cause serious injury or equipment damage. Bus bracing must be installed in a manner that does not apply excessive mechanical stress to the circuit breaker terminals or accessory connector kits. In order to facilitate even current distribution and minimize the potential for excessive heating when using multiple conductors per phase, it is advisable to mount bus bars to both the top and bottom surface of the circuit breaker terminals as shown below. Frame Size I WL Low Voltage Power Circuit Breakers Design Guide 16

18 Frame Size II 3-Pole Interrupting Class Frame Rating (A) N, S, H, L C Dimension "A" 4-Pole 17 WL Low Voltage Power Circuit Breakers Design Guide

19 Frame Size III Fill any unused slots with spacers before torquing bus hardware to keep from bending conductors. 3-Pole 4-Pole WL Low Voltage Power Circuit Breakers Design Guide 18

20 Front-Accessible Bus Terminals Another option for connecting primary conductors is via the front-accessible bus accessory kits. These silver-plated copper accessories provide connection points above/below the circuit breaker, easing the installation or removal of the circuit breaker when only the front side of the circuit breaker is accessible. These connectors are designed to accept bus bar assemblies, cable lugs, or flexible bus conductors. Table 12: Front-Accessible Bus Connector Kits Frame Size No. of Poles Interrupting Class Frame Rating (A) Catalog Number I 3 S, H, L WLH1F12CONUL II 3 S, L WLL2F16CONUL 2000 WLL2F20CONUL 2500 WLL2F25CONUL 3000 WLL2F30CONUL III 3 L WLL3F50CONUL The mounting holes on the circuit breaker terminals are ø 19/32 in. It is recommended to use ½-13 SAE grade 5 hardware, torque to 50 lb-ft. Cable lugs and flexible conductors may be connected directly to the front-accessible connectors. Frame Size I 19 WL Low Voltage Power Circuit Breakers Design Guide

21 Frame Size II (800A 2500A) Frame Rating (A) Dimension "A" Frame Size II (3000A) WL Low Voltage Power Circuit Breakers Design Guide 20

22 Frame Size III Front Bus Terminal Lug Kits The following wire connector kits are designed to allow cable conductors to be connected to the front connector accessory kits for WL circuit breakers rated 2000 A and below, and for available fault current levels of 65 ka and below. These wire connectors have been tested in accordance with UL 486A 486B for flexible stranded cables. Table 13: Lug Kits Catalog number Maximum continuous current (A) Maximum number of conductors Conductor wire size WLS2P12CONUL kcmil (Cu / Al) WLS2P20CONUL kcmil (Cu / Al) Tightening torque for conductors 325 lb-in. 375 lb-in. 21 WL Low Voltage Power Circuit Breakers Design Guide

23 Bus Bracing The bus terminals (standard or accessory kits) are not intended to support the equipment bus structure, nor are they intended to provide short circuit bracing. The following table provides recommendations for supporting the primary bus conductors. The distances vary based on the short-circuit rating of the apparatus. Longer distances and other means of support may be validated through short-time withstand testing of the equipment s bus structure. All phases may be braced together to prevent separation during short-circuit conditions. Line and load conductors may be braced separately, or braced against each other. Table 14: Minimum Bus Bracing Recommendations Short-time or short-circuit rating (ka) Distance to first brace (in.)! WARNING Hazardous energy. Improper support may cause serious injury or equipment damage. Bus bracing must be installed in a manner that does not apply excessive mechanical stress to the circuit breaker terminals or accessory connector kits. WL Low Voltage Power Circuit Breakers Design Guide 22

24 Phase Barriers In service entrance applications, it is often necessary to include a sectionalizing barrier separating line and load bus from each other. In many other applications, it is desirable to include phase-to-phase and/or phase-to-ground isolation barriers. The following circuit breaker types (see Table 14) include 5/32 in. wide groves in the rear face of the circuit breaker to facilitate addition of line/load and phase-to-phase barriers. Table 15: Integral Phase Barrier Provisions Frame Size No. of Poles Interrupting Class Interrupting Class Frame Rating (A) I 3 S, H, L S, H, L II 3 S, L, C S, L C C S, H, L S, H, L III 3 L L C C H, L H, L Integral Barrier Provisions Vertical Horizontal 23 WL Low Voltage Power Circuit Breakers Design Guide

25 To assist in the securing of the barriers, mounting holes have been provided, as illustrated below. These mounting holes are intended to be used with #10-16 thread-forming screws, with a maximum installed length of 5/8 in. The following drawings provide dimension specifics for each of the different circuit breaker models. Frame Size I WL Low Voltage Power Circuit Breakers Design Guide 24

26 Frame Size II 3-Pole 4-Pole 25 WL Low Voltage Power Circuit Breakers Design Guide

27 Frame Size III 3-Pole 4-Pole WL Low Voltage Power Circuit Breakers Design Guide 26

28 Door Cut-Outs WL circuit breakers are suitable to be mounted such that the front escutcheon is either flush with the face of the circuit breaker compartment door (or dead-front cover), or with the front escutcheon protruding through the panel. Flush Mounted The following figures may be used when the circuit breaker is mounted such that the front escutcheon is intended to be flush with the front of the equipment. Frame Size I (mechanism only visible) Frame Size II and III (mechanism only visible) 27 WL Low Voltage Power Circuit Breakers Design Guide

29 Frame Size I (mechanism + ETU visible) Frame Size II and III (mechanism + ETU visible) WL Low Voltage Power Circuit Breakers Design Guide 28

30 Semi-Flush Mounted One of the following figures may be used when the circuit breaker is mounted such that the front escutcheon is intended to protrude through the front of the equipment. Frame Size I Frame Size II and III Frame Size II and III (with door sealing frame WLDSF) 29 WL Low Voltage Power Circuit Breakers Design Guide

31 Control Wiring Space Control wiring should not be routed above the arc chutes of the circuit breaker. Wiring in this space may become damaged and may cause undesirable arcing or a flashover during opening operations of the circuit breaker. Additional Resources The WL circuit breaker website has a complete set of tools for engineering solutions utilizing this family of low voltage power circuit breakers. Selection and configuration guides Online configurator Application guides Instructional videos 2-D dimensional drawings 3-D models WL Low Voltage Power Circuit Breakers Design Guide 30

32 Siemens Industry, Inc Triangle Parkway Norcross, GA Subject to change without prior notice Order No.: CBBR-FXMDG-0316 All rights reserved Printed in USA 2016 Siemens Industry, Inc. Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested performance features are binding only when they are expressly agreed upon in the concluded contract.

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker Selection and Application Guide Supplement WL UL1066 4-Pole Circuit Breakers usa.siemens.com/wlbreaker WL Power Circuit Breaker Table of Contents Ratings for UL 1066 (ANSI C37) Circuit Breakers Frame size

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Product Guide. QR Circuit Breaker. usa.siemens.com/circuitbreakers

Product Guide. QR Circuit Breaker. usa.siemens.com/circuitbreakers Product Guide QR Circuit Breaker usa.siemens.com/circuitbreakers Advantages to reduce your cost and improve installation flexibility. 250A, 240V AC breakers up to 100kAIC. Updated design includes pushtotrip

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

7. Residential Single-Family and Duplex Buildings (Dwellings)

7. Residential Single-Family and Duplex Buildings (Dwellings) Sin g le -F a mily a n d Du p le x Bu ild in g s 2016 Electric Service Requirements, 2 nd Edition Section 7 Section 7 Residential Single-Family and Duplex Buildings (Dwellings) Directory Page 7.1 General

More information

Application guide. Tmax Link OEM UL 891 Switchboard Program

Application guide. Tmax Link OEM UL 891 Switchboard Program Application guide Tmax Link OEM UL 891 Switchboard Program 04 Tmax Link Overview 04 Standards 04 UL File Extension Process Overview 05 Electrical Data 05 Technical Data 05 Ambient Conditions 08 Circuit

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

Instruction and Installation Guide

Instruction and Installation Guide Instruction and Installation Guide Type 2A Arc Resistant tiastar Motor Control Center www.usa.siemens.com/mcc DANGER Hazardous voltage. Will cause death or serious injury. Keep out. Qualified personnel

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

Save time and money, plus increase home value!

Save time and money, plus increase home value! Save time and money, plus increase home value! Generator Ready Load Center usa.siemens.com/generators The Siemens generator ready load center can save thousands of dollars in future generator installation

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

CON EDISON EQUIPMENT

CON EDISON EQUIPMENT CON EDISON EQUIPMENT Con Ed Navtech Size Volts Amps List Spec. Cat. No Description Price 205 N-205 10x10x5 100 $72.00 205 RTN-205 10x10x5 100 190.00 215 N-215 24x12x8 200 144.00 215 RTN-215 24x12x8 200

More information

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION MPH66125 with Horn Bypass Square D brand MP Meter-Pak meter centers from Schneider Electric offer a wide range of solutions for multi-metering applications: UL Listed

More information

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION MPH66125 with Horn Bypass Square D brand MP Meter-Pak meter centers from Schneider Electric offer a wide range of solutions for multi-metering applications: UL Listed

More information

NEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry

NEMA Pump Controls. Class 82 slim line NEMA pump controller for the agricultural industry NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry See NEW preliminary information on Class 82 size 1 in an extra wide enclosure and size 2 standard enclosures. www.usa.siemens.com/controls

More information

Instruction sheet WARNING. October, 2014

Instruction sheet WARNING. October, 2014 E8700-A064-T003-A6-LCN0 Page of 6 October, 04 WARNING Hazardous voltage Can cause death or serious injury. Disconnect main power and control voltages before installation or maintenance on the equipment.

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Table of Contents TPS NQ & AQ Series Overview 2 Switchboard Technical Data 3-5 Panelboard Technical Data 5-11 1 Tier Power

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Selection and application guide

Selection and application guide Selection and application guide 30A 400A fusible panelboards Coordination Panelboard www.usa.siemens.com/fusiblepanel Coordination panelboards Table of contents Subject Page Specifications 2-3 Enclosure

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and

More information

fastfax Rock Solid TM Load Centers General Information

fastfax Rock Solid TM Load Centers General Information General Information FEATURES UL Listed. Straight-in wired, bolt-on main breaker for 100-225 amps. Neutral and ground bars have multiple 1/0 conductor terminals. Factory installed ground bars on all devices.

More information

Selection & Application Guide. BFT Main Feed Thru Modules. Power Mod. usa.siemens.com/powermod

Selection & Application Guide. BFT Main Feed Thru Modules. Power Mod. usa.siemens.com/powermod Selection & Application Guide BFT Main Feed Thru Modules Power Mod usa.siemens.com/powermod Power Mod BFT - Main Feed Thru Modules Selection and Application Guide Power Mod BFT - Main Feed Thru Modules

More information

Selection and application guide

Selection and application guide Selection and application guide Integrated Power Systems Switchboards www.usa.siemens.com/switchboards Integrated Power Systems Switchboards Contents General Product Information 2-3 General Layout Information

More information

7 Single Family Service

7 Single Family Service 7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

National Marine Manufacturers Association Product Compliance Specialist Examination D.C. Electrical (2013 MY) ABYC E-11 (08 Amended 09)

National Marine Manufacturers Association Product Compliance Specialist Examination D.C. Electrical (2013 MY) ABYC E-11 (08 Amended 09) 1. Two marine electrical technicians are discussing conductor support. Tech A says that all conductors shall be supported throughout their length or at least every 18. Tech B says that there is an exception

More information

Product guide. Enclosed NEMA starters. usa.siemens.com/controls

Product guide. Enclosed NEMA starters. usa.siemens.com/controls Product guide Enclosed NEMA starters usa.siemens.com/controls The right choice for applications that demand the best Siemens NEMA combination and non-combination starters for industrial and construction

More information

Power Mod. Introduction.

Power Mod. Introduction. Power Mod Siemens is proud to introduce Power Mod with QuickSystem - a new robust and featurerich line of modular metering designed with the contractor in mind. Power Mod features a unique combination

More information

Introduction. Features. Intelligent Technologies Motor Control Center Structures

Introduction. Features. Intelligent Technologies Motor Control Center Structures Intelligent Technologies Technical Data New Information Description Page Intelligent Technologies General............................................. 2 s.......................................................

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry Answers for industry.

NEMA Pump Controls Class 82 slim line NEMA pump controller for the agricultural industry Answers for industry. www.usa.siemens.com/controls NEA Pump Controls Class 82 slim line NEA pump controller for the agricultural industry Answers for industry. Class 82 Slim Line NEA Pump Controller Typical applications include:

More information

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses Page 1 2015 Heavy duty 11-gauge steel enclosure is all-welded construction for long life Corrosion proof nameplate is located to provide easy access for the operator Glass reinforced barriers meet NEMA

More information

New York City Apartment Metering Meter Sockets / Load Centers

New York City Apartment Metering Meter Sockets / Load Centers s New York City Apartment Metering Meter Sockets / Load Centers Selection and Application Guide Bulletin RPSA-S0001 Before You Begin... System Parameters Mounting: Indoor only Input: 208Y/120V AC, 3 Phase,

More information

Quik-Spec Coordination Panelboard

Quik-Spec Coordination Panelboard Read and retain for future reference Quik-Spec Coordination Panelboard Instruction Leaflet 3A1071 RevD Section TABLE OF CONTENTS Page Danger and warnings for installation of the equipment.............3-4

More information

Power distribution. RiLine fuse elements. NH fuse-switch disconnectors, size 000. For mounting plate assembly

Power distribution. RiLine fuse elements. NH fuse-switch disconnectors, size 000. For mounting plate assembly NH fuse-switch disconnectors, size 000 Version -pole, cable outlet at the top/bottom For the use of fuse inserts to EN 60 - Technical specifications to IEC/EN 60 947-, see chapter -5, page 6 see chapter

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

8300 Series Installation Guidelines

8300 Series Installation Guidelines 1-800-443-4859 8300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER

More information

Product Guide. NEMA pump controls.

Product Guide. NEMA pump controls. Product Guide NEMA pump controls www.usa.siemens.com/controls Class 87 full voltage pump controller with fusible disconnect switch and standard features Class 87 NEMA full starter pump control panels Product

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

100-Ampere Busway. Effective November 2005 New Information. Elbow, Busway and Cable Tap Box. Technical Data TD E

100-Ampere Busway. Effective November 2005 New Information. Elbow, Busway and Cable Tap Box. Technical Data TD E 100-Ampere Busway Technical Data TD01701002E Effective November 2005 New Information Elbow, Busway and Cable Tap Box Contents General Information.............................. 2 Connections...............................

More information

5300 Series Installation Guidelines

5300 Series Installation Guidelines 1-800-443-4859 5300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER

More information

Neutral section. Features. Sicat 8WL5545-4D/4F for overhead contact line systems. siemens.com/rail-electrification

Neutral section. Features. Sicat 8WL5545-4D/4F for overhead contact line systems. siemens.com/rail-electrification Neutral section Sicat 8WL5545-4D/4F for overhead contact line systems siemens.com/rail-electrification When installed in pairs, the type Sicat 8WL5545-4D/4F neutral sections serve as phase separation section

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary 14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching

More information

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to

More information

Not all Low Voltage Switchgear is created equal

Not all Low Voltage Switchgear is created equal White Paper Not all Low Voltage Switchgear is created equal The must-have solution for power distribution systems Prepared by: Tom Hawkins, Consulting Product Engineer Rahul Rajvanshi, Senior Product Engineer

More information

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3 Introduction P1 Panelboards P1 Feature Overview Key Panelboard Features Lighting and Appliance Applications Power Panelboard Applications Convertible From Top Feed to Bottom Feed and Vice Versa Change

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

Product Specifications for Phase Over Phase GOABS(r)

Product Specifications for Phase Over Phase GOABS(r) 1. General a) This specification covers the design, manufacture, and shipment of phase-over-phase, 1-way, 2-way, 3-way, and 4-way, gang-operated disconnecting switches, both air-break and load-break, for

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac 0000 00000 0000 000 0000 000000 00000 0000 00000 0000 000 0000 000000 00000 SIMOVAC and SIMOVAC-AR Medium-voltage controllers 2.3 kv - 6.9 kv usa.siemens.com/simovac 2 SIMOVAC and SIMOVAC-AR - the latest

More information

Zenith ZBTS/ ZBTSD/ZBTSCT

Zenith ZBTS/ ZBTSD/ZBTSCT Critical Power from GE Zenith ZBTS/ ZBTSD/ZBTSCT Transfer/Bypass-Isolation Transfer Switches Introduction GE s Zenith ZBTS Series Bypass Isolation Transfer Switch consists of two major modules the automatic

More information

Accessories. Accessories. Meter Mounting Equipment

Accessories. Accessories. Meter Mounting Equipment Covers & Sealing Rings..................................................................... 119 AW & H-Base Hubs.......................................................................... 119 Flush Trim

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

Contents. Power Outlet. Don t Give Up! If you don t find the product you want in this catalog, try the Flex Center at

Contents. Power Outlet. Don t Give Up! If you don t find the product you want in this catalog, try the Flex Center at -1 Power Outlet Panels Contents Description Page Surface Units................................................... -3 Pedestal Units.................................................. -3...............................................

More information

Lighting Panelboards. P2 Panelboards

Lighting Panelboards. P2 Panelboards Lighting Panelboards P2 Panelboards Features Flexibility is the hallmark of the P2 panel. This panel offers a wide array of factory-assembled options to meet virtually any lighting panel application. The

More information

Generator Termination Bus-bar Arrangement - Design requirements: Utility Perspective

Generator Termination Bus-bar Arrangement - Design requirements: Utility Perspective Generator Termination Bus-bar Arrangement - Design requirements: Utility Perspective D. K. Chaturvedi (NTPC) Harshvardhan Senghani (NTPC) K Venugopal (CS Electric) This paper appraise user on the termination

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

UNDERGROUND SERVICES - SECONDARY

UNDERGROUND SERVICES - SECONDARY UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service

More information

WL Low Voltage Metal-Enclosed Switchgear. Selection and Application Guide.

WL Low Voltage Metal-Enclosed Switchgear. Selection and Application Guide. WL Low Voltage Metal-Enclosed Switchgear Selection and Application Guide www.sea.siemens.com/switchgear 3 Table of Contents General Information...............................................................................................

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers White Paper Ground Fault Application Guide WL Low Voltage Power Circuit Breakers Table of Contents Introduction 3 Need for ground fault tripping 3 Requirements from industry standards 3 National Electrical

More information

Panelboard Renewal Parts Supplement

Panelboard Renewal Parts Supplement Panelboard Renewal Parts Supplement Contents Page Page Contents Page PRL 1a and a Neutral Assemblies..................................................... 3 PRL 1a and a Ground Assemblies.......................................................

More information

Not all Low Voltage Switchgear is created equal

Not all Low Voltage Switchgear is created equal Not all Low Voltage Switchgear is created equal White Paper The must-have solution for power distribution systems Introduction Reliability and safety are the two most important criteria in the proper functioning

More information

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor Page 1 2016 EPM-PCS-35-320P-R2/ESW-GCM6-2S-SA Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton's CPS LRTPs 35 kv Elliott Air-Insulated SuperWell Bushings 21.1/36.6 kv Grounded Wye Max Design, 150

More information

ASCO 7000 Series Power Transfer Switch Technical Data and Ordering Information

ASCO 7000 Series Power Transfer Switch Technical Data and Ordering Information ASCO 7000 Series Power Transfer Switch Technical Data and Ordering Information 7000 SERIES ORDERIN INFORMATION To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number:

More information

PANEL PANEL MOUNTING COMPONENTS

PANEL PANEL MOUNTING COMPONENTS PANEL PANEL MOUNTING COMPONENTS For conventional wiring, Wöhner offers a comprehensive range of panel components for fastening to a DIN rail or mounting plate. The fuses and associated connection technology

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT All electrical systems and electrically energized equipment

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

OVERHEAD SERVICE. Items to consider

OVERHEAD SERVICE. Items to consider OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

5.2. Power Pedestals. Contents Description

5.2. Power Pedestals. Contents Description .2 Power Outlet Panels Contents Description Product Overview......................... Application Description.................. Features and Benefits................... Standards and Certifications..............

More information

Power Mod. Standard Tapboxes.

Power Mod. Standard Tapboxes. Power Mod Standard tapbox modules (type WTB) are designed for versatility, space savings, and flexibility. Features include: J QuickSystem features J Standard compression lug capability J Invertibility:

More information

Modular Metering Application Guide

Modular Metering Application Guide GE Energy Connections Modular Metering Application Guide Mini Mod* III Product Family Table of Contents Page No. Nomenclature 3 Mini Mod III Photos 4 Mini Mod III Ring -Type and Ringless 5 Mini Mod III

More information

WL Low Voltage Metal-Enclosed Switchgear

WL Low Voltage Metal-Enclosed Switchgear www.usa.siemens.com/switchgear WL Low Voltage Metal-Enclosed Switchgear Selection and Application Guide Answers for industry. Table of Contents General Information... 2 Construction Details... 3-5 WL

More information

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS Supersedes: 160.75-PW2 (508) Form 160.75-PW2 (311) FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS WIRING DIAGRAM CONTRACTOR ORDER NO. YORK CONTRACT NO.

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

Fused Coordination Panelboard

Fused Coordination Panelboard Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined

More information

6.2. Power Pedestals. Contents

6.2. Power Pedestals. Contents Power Pedestals.2 Power Outlet Panels Contents Description Page Product Overview................................. 287 Application Description.......................... 288 Features and Benefits...........................

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by

More information