Micro-hydropower Plant. Site Completion Test Manual

Size: px
Start display at page:

Download "Micro-hydropower Plant. Site Completion Test Manual"

Transcription

1 MHP 4 DEPARTMENT OF ENERGY ENERGY UTILIZATION MANAGEMENT BUREAU Micro-hydropower Plant Site Completion Test Manual June 2009

2 This manual was developed by the Department of Energy (DOE) through the technical assistance under the Project on Sustainability Improvement of Renewable Energy Development for Village Electrification in the Philippines which was provided by the Japan International Cooperation Agency (JICA).

3 Table of Contents 1 General Scope Objectives Implementation structure Management structure Roles and responsibilities Test Instruction Civil and metal structures Common Gate and stoplog Concrete structures Operation & maintenance manuals/instructions Documents to be prepared Electro-mechanical equipment Inlet valve and drain valve for penstock water Comprehensive test Operation & maintenance manuals/instructions Documents to be prepared Transmission and distribution facilities Common Operation and maintenance manuals/instructions Documents to be provided Amendment of the manual... 8

4 LIST OF ANNEXES ANNEX 1 ANNEX 2 : Appearance checklist for civil and metal structures : Example procedures of comprehensive test for electro-mechanical equipment

5 1 General This manual is intended to specify standardized test items and procedures for the completion test of micro-hydropower plants. Accordingly, an actual on-site test was conducted taking into account the real conditions of the plants which served as the reference basis for the test instructions and record forms shown in this manual. 2 Scope This manual shall be used for the on-site completion test conducted in conjunction with the new construction of micro-hydropower plants. Users also may utilize this manual for performance tests after the rehabilitation and upgrade of existing micro-hydropower plants by choosing the appropriate test items. 3 Objectives The objectives of this manual are: (1) to verify if the installed equipment meets the requirements, and (2) to secure the safety of the equipment and people after commissioning through the precise implementation of a field performance test. 4 Implementation structure 4.1 Management structure The following figure shows the management structure of the completion test. Proponent Inspection report/ Drawings Specifications Manufacturer/ Supplier Instruction/ Advice Report Implementation of test Contractor Assistance Mobilized Local Residents Figure 1 Implementation structure of the completion test 1

6 4.2 Roles and responsibilities The roles and responsibilities of each component in the planning and implementation of the completion test have been summarized in the following table. Component Proponent Contractor Local residents Role Factory inspection report/drawing collection Test plan approval Test result approval Test record maintenance Test plan preparation Test implementation Asssistance in implementing the tests (1) Factory inspection report/drawing collection The proponent shall collect factory inspection reports and drawings for purchased equipment from manufacturers/suppliers prior to their acceptance. Even in the case of standardized equipment, submission of related documents that show the characteristics of the equipment shall be required for future maintenance. (2) Test plan preparation The contractor shall prepare a plan for the completion test and submit it to the proponent in advance for approval. Test items shall be identified according to the composition of the installed equipment and concrete test procedures shall be proposed for each test item. (3) Test plan approval The proponent shall review the submitted test plan to be approved after providing necessary instructions to the contractor. (4) Test implementation The contractor shall conduct the completion test in accordance with the approved test plan and record the results on the record forms. The local residents shall assist with the implementation of on-site testing. Test records shall be submitted to the proponent for approval. (5) Approval of test results The proponent shall review the submitted test record to be approved after providing necessary advice and instruction to the contractor. (6) Test record maintenance Test records shall be maintained by the proponent. 2

7 5 Test Instruction 5.1 Civil and metal structures Common (1) Appearance check Civil and metal structures shall be inspected visually to identify any defects and/or evidence of water leakage. Examples of checklist items are shown in ANNEX1. (2) Dimensional test A dimensions test of civil and metal structures shall be implemented based on the drawings to ensure that these structures possess the required capabilities. The criteria for evaluation are as follows: Item Instruments Criteria Location Elevation, Slope Length, Size Measuring tape Transit Level gauge Within 500 mm Within 100 mm * Penstock shall not be inverse or horizontal Within smaller value of 5% of design value (3) Water-filling and dewatering test A watertight inspection along the waterway shall be executed by means of a water filling and dewatering test. The targets include the weir, the headrace open channel, the settling basin, the spillway, the penstock, the powerhouse, the tailrace, and their auxiliary structures, such as the gate and stoplog. Leakage shall not be observed during this test (10-minute operation under maximum design head and design discharge). (4) Operation test An operations test shall be conducted in order to verify that no serious vibrational disturbance of the civil and metal structures will occur when the plant and equipment are in operation Gate and stoplog (1) Running test A running test shall be carried out to verify the smooth and reliable operation of the gate and stoplogs. 3

8 5.1.3 Concrete structures (1) Crack inspection No cracks larger than 0.4 mm shall be allowed on the concrete structures through which water is run such as the weir, the headrace open channel, the settling basin, the spillway, and the tailrace. Photographs and sketches are useful for monitoring development of the cracks Operation & maintenance manuals/instructions The contractor shall submit operation and maintenance manuals/instructions. Methods and frequency of inspection, repair and maintenance (including painting of penstock, gate and screen, sand flushing valve etc.) shall be described in the manuals/instructions Documents to be prepared The contractor shall provide the following documents one week prior to the completion test. (1) As-built drawings (layout, major structures) (2) Head-loss calculation (3) Maximum output power calculation 5.2 Electro-mechanical equipment Inlet valve and drain valve for penstock water After the inlet and drain valve for the penstock have been installed, and before putting the unit into service, the following performance tests shall be carried out by the contractor. (1) Watertight test To check water leakage from a closed inlet valve and measure the amount if necessary. Test item Content Watertight test To check the water leakage from a closed inlet valve and measure the amount if necessary Comprehensive test After the electro-mechanical equipment, such as the turbine, generator, control panel, and auxiliaries have been installed, and before putting the unit into service, the following tests shall be carried out by the contractor in order to verify comprehensive performance. A series of example procedures for each test are shown in ANNEX2. 4

9 Test item Visual inspection Earth resistance measurement Insulation resistance test Initial run test Bearing run test Excitation characteristic test Protection function test DL governor function test Output vs. guide vane opening test *1 Load rejection test *2 Load run test Overnight operation data collection Content To check visually the installation conditions of the electro-mechanical equipment in the powerhouse. To measure the earth resistance using an earth tester at the grounding electrode, and check that the equipment is connected firmly to the electrode. To measure the insulation resistance of the generator windings and the dummy load heaters using an insulation tester, and check that they maintain the necessary insulation performance. To check for any abnormal sound, vibration and contact with the stationary parts by rotating the turbine-generator at low rotational speed. To measure the temperature rise of the bearings and the generator cover by continuously operating the generator-turbine at the rated rotational speed and no load. To measure the generator voltage, exciter voltage and exciter current for the frequency stepwise changed in the no load operation, and draw a graph of the excitation characteristic. To check the characteristics and setting values of protective functions for the ELC panel box by changing the values of the trimmers. To check that the frequency is kept constant regardless of a change in the actual load which is substituted by a water resister. To measure the relationship between the guide vane opening and the generator output. To check that the frequency is kept constant regardless of a sudden change in the actual load by manually cutting off the parallel-in circuit breaker (MCCB). To measure the temperature rise of the bearings and the generator cover by continuously operating the generator-turbine at the rated rotational speed and full output. To check that the dummy load governor functions properly during actual operations. Notes: *1 The total and turbine efficiency can be estimated by measuring the turbine discharge via utilization of a portable ultrasonic flow meter during the test. *2 The load rejection test is to be used for a system equipped with a governing system such as a dummy load governor. 5

10 5.2.3 Operation & maintenance manuals/instructions The contractor shall submit operation and maintenance manuals/instructions. Assembling and disassembling methods, maintenance period, and the interval of greasing, etc. for the following equipment and devices is described in the manuals/instructions. (1) Turbine (2) Generator (3) Inlet valve (4) Driving system (5) Governing system (Electronic Load Controller: ELC) (6) Automatic voltage regulator (AVR) (7) Generator panel Documents to be prepared The contractor shall provide the following documents. (1) Single line diagram main & control circuits (2) Power plant equipment layout drawings (3) Specifications and generator panel drawing (4) Unit control & protection system diagram (5) Drawings of the dummy load heater (6) Drawings of the inlet valve (7) Drawings of the connecting pipe (8) Connection diagrams of the generator panel (9) Connection diagrams of the AVR (10) Connection diagrams of the governor (11) Connection diagrams of the control system (12) Efficiency and output curve of the turbine (13) Efficiency curves of the generator (14) Test reports for all equipment/devices (15) List of tools and spare parts (16) Operation and maintenance manuals/instructions for all equipment/devices 6

11 5.3 Transmission and distribution facilities Common After the transmission and distribution facilities have been installed, and before putting the unit into service, the following tests shall be carried out by the contractor. Test item Visual inspection Earth resistance measurement Insulation resistance test Power transmission test Content To check visually that the transmission and distribution line components, such as the pole, cross arm, insulator, guy wire, cable, conductor, switchgear, and arrester are installed adequately, and that offset distances between the conductors and trees are maintained by walking along the route. To measure the earth resistance using an earth tester at the grounding electrode, and check that the equipment is connected firmly to the electrode. To measure the insulation resistance of the cables and conductors using an insulation tester, and check that they maintain the necessary insulation performance. To check visually the condition of the transmission and distribution lines energized by operating the generator-turbine, and verify that they are installed adequately without short circuits and grounding Operation and maintenance manuals/instructions The Contractor shall submit operation and maintenance manuals/instructions. Assembling and disassembling methods, and maintenance period, etc, for the following equipment and devices shall be described in the manuals/instructions. (1) Transformers (2) Circuit breaker (3) Lightning arresters (4) Fuse cutouts and fuse links Documents to be provided The Contractor shall provide the following documents: (1) Distribution line route drawing (2) Single line diagram distribution line (3) Supporting structure arrangement drawings for the distribution line, including the service wire (4) Detailed drawings of a fuse cutout 7

12 (5) Detailed drawings of lightning arresters (6) Specifications and drawings of conductors/cables (7) Specifications and drawings of insulators and hardware (cross-arm, strap, u-bolts, bands, etc.) (8) Test reports for all equipment/devices (9) List of tools and spare parts (10) Operation and maintenance manuals/instructions for all equipment/device 6 Amendment of the manual The DOE shall review this manual annually, and amend it, if necessary, according to the surrounding circumstances in rural electrification of the country. The amended manual shall be fully authorized among the DOE and approved by Director of Energy Utilization Management Bureau of the DOE. 8

13 ANNEX1 Appearance checklist for civil and metal structures (1/2) Equipment Item Check Method Result Remarks Weir body Appearance check Sliding timber Water leakage Insert condition Intake weir Bar screen Appearance check Intake Appearance check Stability of water intake Intake Intake body Appearance check Stability of water intake Forebay body Appearance check Checking of variation in WL in operation Forebay Screen Appearance check (Pitch, Installation angle) Flushing gate Appearance check Gate operation Operational check Water leakage Bank protection / Retaining wall Bank protection / Retaining wall Appearance check Appearance check Penstock Penstock Leakage from welded area Vibrations in operation and palpation Expansion pipe Leakage Small supporting table Fixed base Air pipe Appearance check Appearance check Appearance check Other Slope along penstock i

14 Appearance checklist for civil and metal structures (2/2) Equipment Item Check Method Result Remarks Aqueduct bridge Penstock Appearance check Powerhouse Powerhouse Appearance check Appearance check Tailrace Tailrace body Condition of water discharge (Positional relation with riverbed) Temporary road Others Temporary road Other Appearance check Slope along temporary road Condition of riverbed around intake Disposal of surplus soil Reconnoitering Additional comments ii

15 ANNEX2 Test item Purpose Visual inspection To verify the installation conditions of the equipment as well as the cable connection. Procedure To inspect visually the installation conditions of the following equipment. (1) Turbine (2) Generator (3) Driving system (4) ELC panel box (5) Dummy loads and safety fence (6) Cable (condition of laying, connection and terminal) (7) Circuit configuration (consistency with the single line diagram) Precaution To take note of damage of the control board, faulty wiring, and looseness of the screws that might be caused by the transportation and installation. Instrument Criteria All equipment is properly installed. Cables are properly laid and connected. Main circuit is constructed in accordance with the single line diagram. i

16 Test item Purpose Earth resistance measurement To verify the earth resistance of the grounding electrode and connections between the electrode and equipment 1. Earth resistance measurement (1) To drive the auxiliary earthing rods P and C deep into the ground, at intervals of 5 10 m (straight line) from the measurement object E (2) Battery check (3) Earth voltage check (4) Auxiliary earthing resistance check (5) Earth resistance measurement Procedure 2. Earthing connection check (1) To set the tester to connection check (2) To connect the two (2) lead wires to the grounding electrode and the grounding terminal of the following equipment respectively Generator stator winding Base flame ELC panel box (3) To verify the connection of the grounding cable by the circuit tester Precaution Instrument Earth tester Circuit tester Criteria Earth resistance of the grounding electrode is at a sufficiently low setting The equipment s grounding terminal is firmly connected to the grounding electrode. ii

17 Test item Purpose Insulation resistance measurement To verify the insulation performance of the equipment by measuring the insulation resistance. To apply voltage of 500V between the measured circuit and the earth, and record the value of the insulation resistance after 1 minute. As for a generator, to continue the measurement for 10 minutes and derive the polarization index (PI) from the 1-minute value and 10-minute value in order to verify the moisture absorption of the coils. Procedure PI = 10-minute value of insulation resistance (MΩ) 1-minute value of insulation resistance (MΩ) The measurement is conducted for the following circuit sections. (1) Generator stator coil (including main circuit) (2) ELC panel box (3) Dummy loads including wiring (4) Distribution lines Precaution Residual charge must be completely discharged by shorting to earth after the measurement Instrument Insulation resistance tester (Digital MΩ HiTester) Circuit: Insulation resistance (MΩ)>0.2MΩ Rotating machine (To meet the following conditions) a. Insulation resistance (MΩ)> Rated voltage (V) Rated output (kw)+1,000 Criteria Rated voltage (V)+Rated speed (min -1 )/3 b. Insulation resistance (MΩ)> +0.5 Rated output (kw)+2,000 c. PI > 1.5 * The above criteria should be used as a reference because it is difficult to estimate progress of insulation deterioration from only the value of the insulation resistance. iii

18 Test item Purpose Initial run test To confirm abnormal sound and vibration by rotating the turbine -generator at low rotational speed Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: OFF Test procedure: (1) To open the guide vane gradually and rotate the turbine-generator at low rotational speed (2) To close the guide vane immediately after the turbine-generator starts rotating (3) To record the operation data ON/OFF Switch MCB ELC panel box Precaution The guide vane must be operated carefully to avoid a rapid speed increase of the turbine-generator Instrument Tachometer Criteria Contact between the stationary and rotary part is not observed Abnormal sound and vibration are not observed in each part of the turbine-generator iv

19 Test item Purpose Rated speed run test To confirm the existence of any abnormal sound, odor, vibration and/or temperature rise in each part of the turbine-generator by rotating the turbine -generator at the rated speed Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: OFF Test Procedures: (1) Set the Clamp on Power Hitester to the main circuit (2) Open the guide vane gradually and rotate the turbine-generator at the rated speed (3) Record the operation data (4) Close the guide vane after the bearing temperature is saturated. Precaution Instrument Tachometer Infrared thermometer Ultrasonic flow meter Clamp on Power HiTester Criteria Abnormal sound, odor, vibration and temperature rise are not observed in each part of the turbine-generator v

20 Test item Purpose Excitation characteristic test To measure excitation characteristics of the newly installed generator as the initial data Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: OFF Test Procedures (1) Check the connection of the clamp tester set to the main circuit (2) Set another Clamp on Power Hitester to the excitation circuit (3) Open the guide vane gradually to turn over the turbine-generator (4) Increase the rotational speed to 110% of the generator rated speed by 10% (5) Measure the terminal voltage, excitation voltage, and excitation current at each point (6) Close the guide vane after testing (7) Remove the clamp tester for the excitation circuit Precaution Instrument Tachometer Ultrasonic flow meter Clamp on Power HiTester Clamp meter The generator generates the rated voltage at the rated rotational speed Criteria vi

21 Test item Purpose Protection function test To verify the adjustable range for the set point of the protection function that the ELC is equipped with and to set the operating value Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: ON Test Procedures: (1) Check the connection of the clamp tester set to the main circuit (2) Open the guide vane gradually and operate the turbine-generator at the rated speed and voltage (3) Increase/decrease the frequency and voltage by changing the frequency set point and verifying the adjustable range for the set values of each protection function Over voltage Under voltage Over speed Under speed (4) Set the operating point after verifying (5) Close the guide vane after testing Precaution Clamp on Power HiTester Instrument Each protection function operates at the set value Criteria vii

22 Test item Purpose Dummy load governor function test To verify that the frequency is kept constant even during the load change operation by normal functioning of the ELC Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: ON Test Procedures: (2) Check the connection of the clamp tester set to the main circuit (3) Set another Clamp on Power Hitester to the dummy load circuit (4) Connect the water resister to the secondary terminal of the MCB after removing the distribution lines (5) Close the MCB inside the ELC panel box (6) Open the guide vane gradually until it is fully opened and increase the generator output to the maximum * At this stage, the dummy load consumes all the generator output (7) Record the operation data at 0% of the actual load (8) Increase the actual load by inserting electrodes of the water resistor to the water tank (9) Record the operation data at 20%, 40%, 60%, 80%, 100% of the actual load (10) Close the guide vane after testing (11) Open the MCB inside the ELC panel box Precaution Operate the guide vane gradually while monitoring the response of the frequency and dummy load current in order for the ELC to function properly Instrument Criteria Tachometer Infrared thermometer Ultrasonic flow meter Clamp on Power HiTester Water resister Dummy load consumes the generator output from which the actual load is excluded Frequency is kept constant without hunting for each value of the actual load viii

23 Test item Guide vane opening vs. output test To verify the generator output by the guide vane opening Purpose Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: ON Test Procedures: (1) Check the connection of the clamp tester set to the main circuit (2) Open the guide vane gradually to turn over the turbine-generator (3) Open the guide vane to 10% of its full opening capacity (4) Record operation data at each point (5) Close the guide vane after testing Precaution Instrument Tachometer Infrared thermometer Ultrasonic flow meter Clamp on Power HiTester Criteria To understand the relationship between the guide vane opening and the generator output ix

24 Test item Purpose Procedure Precaution Instrument Criteria Load rejection test To verify that the dummy load consumes all the generator output after actual load rejection by normal functioning of the ELC and that the turbine-generator settles at the next equilibrium. Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: ON Test Procedures: (1) Check the connection of the clamp meters set to the main circuit and dummy load circuit (2) Check the connection of the water resister (3) Set the Power Meter to the main circuit to record the transient response after load rejection (4) Close the MCB inside the ELC panel box (5) Open the guide vane gradually to increase the generator output to 25% of the maximum * At this stage, the dummy load consumes all the generator output (6) Increase the actual load to the same as the generator output by inserting electrodes of the water resistor to a water tank * At this stage, the current to the dummy load current becomes zero (7) Record the operation data before load rejection. (8) Open the MCB inside the ELC panel box manually (9) Observe the transient state of the turbine-generator (10) Record the operation data after load rejection (11) Close the guide vane (12) Repeat the above procedures of (4) (11) for 50%, 75%, 100% of the maximum (13) Open the MCB inside the ELC panel box Close the guide vane immediately after a rapid increase of rotational speed occurs subsequent to the opening of the MCB Tachometer Infrared thermometer Ultrasonic flow meter Clamp on Power HiTester Water resister Power Meter After actual load rejection, the dummy load consumes all the generator output and the turbine-generator safely settles at the next equilibrium Rotational speed does not exceed the run-away speed Water pressure does not exceed the tolerance of the penstock pressure Abnormal states are not observed in each part of the turbine-generator x

25 Test item Purpose Parallel-in run test To energize the newly installed distribution lines by connecting to the turbine-generator and verifying the installation conditions Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: ON Test Procedures: (1) Check the connection of the clamp tester set to the main circuit and dummy load circuit (2) Connect the disconnected distribution lines to the secondary terminal of the MCB after removing the water resister (3) Close the MCB inside the ELC panel box (4) Open the guide vane gradually to its full opening capacity (5) Monitor the operating conditions of the equipment (6) Close the guide vane after testing Precaution Instrument Abnormal conditions are not observed during operation Criteria xi

26 Test item Purpose Load run test To verify that the turbine-generator can operate normally at the rated conditions for a long period of time Procedure Equipment conditions before testing: (1) Inlet valve: Open (2) Guide vane: Close (3) MCB for the main circuit inside the ELC panel box: Open (4) ON/OFF switch on the ELC panel box: ON Test Procedures: (1) Check the connection of the clamp tester set to the main circuit and dummy load circuit (2) Close the MCB inside the ELC panel box (3) Open the guide vane gradually to its full opening capacity (4) Monitor the operating conditions of the equipment and record the data (5) Close the guide vane after testing Precaution Instrument Tachometer Infrared thermometer Ultrasonic flow meter Clamp on Power HiTester Criteria Abnormal sound, odor, vibration and temperature rise are not observed during operation xii

27 Test item Purpose Overnight operation data collection To verify the equipment conditions by recording the operation data overnight which shows the response to actual load fluctuations To acquire the actual load operation data overnight by setting the Power Meter and the AC voltage logger at the power plant and households respectively Procedure Precaution Instrument Power Meter with Clamp AC Voltage Logger Frequency is kept constant during actual load operation Criteria xiii

28 Department of Energy Energy Complex Merritt Road, Fort Bonifacio, Taguig City, Metro Manila TEL: FAX:

MHP 5 DEPARTMENT OF ENERGY ENERGY UTILIZATION MANAGEMENT BUREAU

MHP 5 DEPARTMENT OF ENERGY ENERGY UTILIZATION MANAGEMENT BUREAU MHP 5 DEPARTMENT OF ENERGY ENERGY UTILIZATION MANAGEMENT BUREAU Micro-hydropower Operator Training Manual May 2009 This manual was developed by the Department of Energy (DOE) through the technical assistance

More information

Sano Milti Khola Hydropower Project, Fulasi VDC, Ramechhap (3 MW)

Sano Milti Khola Hydropower Project, Fulasi VDC, Ramechhap (3 MW) Sano Milti Khola Hydropower Project, Fulasi VDC, Ramechhap (3 MW) Monthly Progress Report Prepared by : Sano Milti Khola Hydropower Limited www.smi.com.np smi.investment.limited@gmail.com Date : June,

More information

Appendix 5 Sample Specifications. Specifications for Socioeconomic Survey in Rural Areas in Myanmar

Appendix 5 Sample Specifications. Specifications for Socioeconomic Survey in Rural Areas in Myanmar Part 6-2 Appendix 5 Appendix 5 Sample Specifications Appendix 5-1 Appendix 5-2 Appendix 5-3 Appendix 5-4 Appendix 5-5 Appendix 5-6 Specifications for Socioeconomic Survey in Rural Areas in Myanmar Technical

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,

More information

XS500 Load Bank. Read all instructions before using the load bank. Contents

XS500 Load Bank. Read all instructions before using the load bank. Contents XS500 Load Bank Read all instructions before using the load bank Contents Contents... 2 1) Receiving... 4 a. Load Bank... 4 b. Manual... 4 2) Specifications... 5 a. Mechanical... 5 i. Lifting... 5 ii.

More information

3) The water conductor system consisting of RCC, partly cut and cover, conduit of size 10.5m x 7m and m long to lead the water to the forebay.

3) The water conductor system consisting of RCC, partly cut and cover, conduit of size 10.5m x 7m and m long to lead the water to the forebay. Project: Mannapitlu Mini Hydel Scheme - 15 MW Overview: Mannapitlu Mini Hydel Scheme is the first of the 4 cascading Mini Hydro Electric Projects planned on Gurupur river in Dakshina Kannada District of

More information

Electric Utility Power Systems. Generation of Electricity

Electric Utility Power Systems. Generation of Electricity Electric Utility Power Systems Generation of Electricity 1 Demand of an Electrical System The total power drawn by a customer of a large utility system fluctuates between wide limits, depending on the

More information

XL1000 Load Bank. Read all instructions before using the load bank. Contents

XL1000 Load Bank. Read all instructions before using the load bank. Contents XL1000 Load Bank Read all instructions before using the load bank Contents Contents... 2 1) Receiving... 4 a. Load Bank... 4 b. Manual... 4 2) Specifications... 5 a. Mechanical... 5 i. Lifting... 5 ii.

More information

Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service

Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service 39 KAZUHIKO TAKAHASHI *1 MITSURU ONODA *1 KIYOTERU TANAKA *2 SEIJIRO MURAMATSU,

More information

NP NLH NLH General Rate Application Page 1 of 1

NP NLH NLH General Rate Application Page 1 of 1 NP NLH 022 2013 NLH General Rate Application Page 1 of 1 1 2 3 4 5 Q. Reference: Finance Please provide detailed amortization schedules for the amortization expense for 2012, 2013 test year (provided in

More information

Ladder Safety Program

Ladder Safety Program Ladder Safety Program For Adopted LC-1022 Rev. 06/16 Page 1 I. Introduction The Organization recognizes that employees use ladders on a regular

More information

STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT

STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT Electro-Mechanical Works Guidelines for Specifications for Procurement of SHP Generating Equipment Sponsor: Ministry of New and Renewable Energy

More information

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles The UK trade body for the caravan, motorhome, caravan holiday and park home industry. NCC Leisure Battery Verification Scheme Leisure Accommodation Vehicles Page 1 of 11 1 Scope The NCC Battery Verification

More information

PRECISION UK Ltd DUPLEX AGSS PLANT

PRECISION UK Ltd DUPLEX AGSS PLANT DUPLEX AGSS PLANT Contents Page Section Page Product Description General 3 AGSS Plant 3 AGSS Remote Switch 3 Operation General 4 Safety General 5 Installation General 5 Mechanical 5 Electrical 7 Wiring

More information

Item L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.)

Item L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.) Village Hydro Specifications Line Distribution Description of Requirement Item L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.) Recommendation 2.

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

Use and Care Instructions for your new T5 Turgo Micro-Hydroelectric Generator

Use and Care Instructions for your new T5 Turgo Micro-Hydroelectric Generator Use and Care Instructions for your new T5 Turgo Micro-Hydroelectric Generator READ THIS FIRST This manual contains important information concerning your new APR T5 Turgo microhydroelectric generator. You

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO BILL 1 MAINS POWER DISTRIBUTION 2-1 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Supply, install, test, commission and set to work the following:- 1.01 Free-standing purpose made front access sub main switchboard

More information

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS 717.1 Scope The particular requirements of this section apply to a.c. and d.c. installations for mobile or transportable

More information

SERIES PC INSTRUCTION AND OPERATION MANUAL

SERIES PC INSTRUCTION AND OPERATION MANUAL MEGGA SERIES PC INSTRUCTION AND OPERATION MANUAL Models PCT and PCF Close-coupled and frame-mounted single-stage horizontal end-suction pumps. WARNING: Read this manual before installing or operating this

More information

5. High voltage warning labels should be placed on all cabinet doors and terminal covers enclosing equipment operating at above 50 volts.

5. High voltage warning labels should be placed on all cabinet doors and terminal covers enclosing equipment operating at above 50 volts. Village hydro specifications Electrical components E1. Labels and notices Requirement 1. All electrical components must carry labels describing their function. This applies particularly to switches and

More information

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2 Solid-state Contactor (New Heat Sink Construction) G3PB Space and working time saved with new heat sink construction. Series now includes 480-VAC models to allow use in a greater range of applications.

More information

Service and Rehabilitation Electrical Power Systems

Service and Rehabilitation Electrical Power Systems Service and Rehabilitation Electrical Power Systems From water to wire 3 ANDRITZ HYDRO Electrical Power System Modernization and rehabilitation International technology group ANDRITZ is a globally leading

More information

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps EI-700-008 Rev -- Table of Contents Safety Guidelines 3 Caution 4 Wiring 4 Maintenance 4 Nameplate format 4 Prior to Operation

More information

STANDARD PRACTICE INSTRUCTION

STANDARD PRACTICE INSTRUCTION STANDARD PRACTICE INSTRUCTION DATE: March 1, 2010 SUBJECT: Ladder Safety Program. REGULATORY STANDARD: 29 CFR 1910.25 Portable Wood Ladders. 29 CFR 1910.26 Portable Metal Ladders. 29 CFR 1926.1052-1060

More information

Need Assessment Document (NAD) DDUGJY

Need Assessment Document (NAD) DDUGJY Need Assessment Document (NAD) DDUGJY Index SNo. Details Page No. 1.0 General Instruction 3 2.0 Objectives of DDUGJY 5 3.0 Scope of works 7 4.0 General information of project area 10 5.0 Details of existing

More information

COMPRESSOR STATION OPERATIONS

COMPRESSOR STATION OPERATIONS CONTENTS FIGURES AND TABLES... viii PREFACE... xi ACKNOWLEDGEMENTS... xiii CHAPTER 1. INTRODUCTION... 1 Scope and Outline... 1 Types of Stations... 2 Production Stations... 2 Storage Stations... 3 Transmission

More information

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 CAT-1 Series 3 Installation Guide The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 (203) 431-0262 (203) 431-0296 FAX tvg@cat-1.com Installation of Load Cells for CAT-1 Systems

More information

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

Extra-High-Voltage SF 6 Gas-Insulated Switchgear Extra-High-Voltage SF 6 Gas-Insulated Switchgear Shuichi Sugiyama Masahiko Fujita Takahiro Shinohara 1. Introduction Due to location criteria and toughened restrictions on transportation, it has become

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

COMMISSION REGULATION (EU) / of XXX

COMMISSION REGULATION (EU) / of XXX EUROPEAN COMMISSION Brussels, XXX [ ](2017) XXX draft COMMISSION REGULATION (EU) / of XXX implementing Regulation (EU) No 595/2009 of the European Parliament and of the Council as regards the determination

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

PORTABLE LADDER SAFETY PROGRAM

PORTABLE LADDER SAFETY PROGRAM PORTABLE LADDER SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.25 Portable Wood Ladders* - 29 CFR 1910.26 Portable Metal Ladders* - 29 CFR 1926.1050-1060* *The above standards are intended to prescribe

More information

UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS

UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS Electrical/Electronic Systems UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS LESSON 3: TEST electrical circuits I. Types of electrical circuit tests and electrical faults A. Different types of electrical

More information

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 32 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976 1 Title Chapter 14:08 Factories and Works (Electrical) Regulations, 1976 2 Interpretation of terms 3 Fencing and enclosure 4 Notices 5 Safety precautions 6 Switch-boards 7 Portable electric tools and lights

More information

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655) - (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility

More information

McNary Northshore Fishway Hydro Project. History & Lessons Learned

McNary Northshore Fishway Hydro Project. History & Lessons Learned McNary Northshore Fishway Hydro Project History & Lessons Learned May 6, 2017 21 th Annual TECHNICAL SEMINAR Machines, Maintenance, and Management: Keeping Hydro Facilities Up and Running History & Lessons

More information

UniSec Maintenance solutions

UniSec Maintenance solutions DISTRIBUTION SOLUTIONS UniSec Maintenance solutions ABB supports you to improve the reliability, safety and efficiency of your electrical equipment UniSec Maintenance solutions Table of contents 004 00

More information

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Northeastern Rural Electric Membership Corporation Columbia City, Indiana Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

CLOSED CIRCUIT HYDROSTATIC TRANSMISSION

CLOSED CIRCUIT HYDROSTATIC TRANSMISSION Energy conservation and other advantages in Mobile Equipment Through CLOSED CIRCUIT HYDROSTATIC TRANSMISSION C. Ramakantha Murthy Technical Consultant Various features/advantages of HST Hydrostatic transmissions

More information

The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector

The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector Know the Rules on Temporary Wiring OSHA Standard 1910.305, Wiring methods, components, and equipment for general use, addresses wiring methods, components, and equipment for general use as one of several

More information

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay 41-100K 2.0 CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit

More information

.2 Section Waste Management and Disposal..5 Section Thermometers and Pressure Gauges Piping Systems.

.2 Section Waste Management and Disposal..5 Section Thermometers and Pressure Gauges Piping Systems. Issued 2005/06/01 Section 15440 Plumbing Pumps Page 1 of 9 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3 Section 01780 Closeout

More information

BRUSHLESS EXCITERS FOR TURBINE GENERATORS

BRUSHLESS EXCITERS FOR TURBINE GENERATORS BRUSHLESS EXCITERS FOR TURBINE GENERATORS Economical, Manpower Saving Exciters Based on State-of-the-Art Technology. Mitsubishi Electrical manufactures brushless exciters for all types of turbine generator,

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Operating & Installation Manual

Operating & Installation Manual Operating & Installation Manual (ZH1.5kw wind turbine system) Company Name:YUEQING ZONHAN WINDPOWER CO.,LTD. Address:NO.195,Chengxi Road,Yuecheng,Yueqing,Zhejiang,P.R.China Zip Code:325600 Tel:86-577-62529820

More information

Unit AE01K Knowledge of Locating and Correcting Simple Electrical Faults in the Automotive Workplace

Unit AE01K Knowledge of Locating and Correcting Simple Electrical Faults in the Automotive Workplace Assessment Requirements Unit AE01K Knowledge of Locating and Correcting Simple Electrical Faults in the Automotive Workplace Content: Basic electrical principles a. Explain the direction of current flow

More information

User Manual Digital Water Level Indicator for rain water storage tanks

User Manual Digital Water Level Indicator for rain water storage tanks User Manual Digital Water Level Indicator for rain water storage tanks We congratulate you on the purchase of Digital Water Level measuring device. You have purchased a high-quality product built to the

More information

Advance Electronic Load Controller for Micro Hydro Power Plant

Advance Electronic Load Controller for Micro Hydro Power Plant Journal of Energy and Power Engineering 8 (2014) 1802-1810 D DAVID PUBLISHING Advance Electronic Load Controller for Micro Hydro Power Plant Dipesh Shrestha, Ankit Babu Rajbanshi, Kushal Shrestha and Indraman

More information

SYDNEY TRAMWAY MUSEUM TROLLEY WIRE INSPECTION PROCEDURE

SYDNEY TRAMWAY MUSEUM TROLLEY WIRE INSPECTION PROCEDURE TROLLEY WIRE INSPECTION PROCEDURE JUNE 2014 1. Document Details: Name: SYDNEY TRAMWAY MUSEUM Document Control Record Number STM 6029 Version Number: 15 TrolleyWire Inspection Procedure Document Status:

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5 Columbia City, Indiana Page 1 of 5 SCHEDULE DG-2 LARGE POWER DISTRIBUTED GENERATION I. AVAILABILITY This Distributed Generation Rate is available to any member in good standing of Northeastern REMC (Northeastern)

More information

Ex-Ante Evaluation (for Japanese ODA Loan)

Ex-Ante Evaluation (for Japanese ODA Loan) Japanese ODA Loan Ex-Ante Evaluation (for Japanese ODA Loan) 1. Name of the Project Country: India Project: Delhi Mass Rapid Transport System Project Phase 2 (V) Loan Agreement: March 31, 2010 Loan Amount:

More information

BM kv Digital Insulation Tester USER MANUAL

BM kv Digital Insulation Tester USER MANUAL M BM5200 5 kv Digital Insulation Tester USER MANUAL CONTENTS Safety warnings...3 Symbols used on instrument...4 Cleaning...4 General description...5 Insulation resistance test modes...5 Automatic discharge...5

More information

ELECTRICAL SYSTEM CONTENTS LOCATION OF ELECTRICAL COMPONENTS 5-1 IGNITION SYSTEM 5-3 CHARGING SYSTEM 5-7

ELECTRICAL SYSTEM CONTENTS LOCATION OF ELECTRICAL COMPONENTS 5-1 IGNITION SYSTEM 5-3 CHARGING SYSTEM 5-7 ELECTRICAL SYSTEM CONTENTS LOCATION OF ELECTRICAL COMPONENTS 5-1 IGNITION SYSTEM 5-3 CHARGING SYSTEM 5-7 STARTER SYSTEM AND SIDE STAND IGNITION INTERLOCK SYSTEM 5-11 SWITCHES 5-15 LAMP 5-16 BATTERY 5-18

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates

More information

Specification Approval Sheet

Specification Approval Sheet Page No. 1/11 Specification Approval Sheet Model:IFR14500EC-600mAh Prepared by Approved by R&D Approved by SALES Approved by QA Signature Date Customer Approval Company Name : Company Stamp : O CELL New

More information

Preventive Maintenance Checklist:

Preventive Maintenance Checklist: Description: MO -, EMERGENCY (CATERPILLAR) (File # ) GNMO Frequency: Monthly Estimated Time (hours):. (T)ools, (S)afety Equipment, and (M)aterials Required Safety Procedures 0 Procedures Mechanics/Electricians

More information

CHAPTER 20: Operation and maintenance

CHAPTER 20: Operation and maintenance Pressurized Irrigation Techniques 20.1 CHAPTER 20: Operation and maintenance INTRODUCTION The efficient operation of an irrigation system depends mainly on the ability of the farmer to make the best use

More information

Books. Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication

Books. Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication Books Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication Available: 2008 Format: Paperback Product Code: PWR08630 ISBN: 978-0-86341-833-4 Pagination:

More information

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

Supply of 63 kva DIESEL GENERATOR SET WITH AMF

Supply of 63 kva DIESEL GENERATOR SET WITH AMF No. NIQ/INKEL/2015-16/162 24 TH Nov 2015 NOTICE INVITING QUOTATION Sealed Quotations are invited for and on behalf of INKEL Limited, having its registered office at INKEL Centre, Off Vallathol junction,

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Instruction Manual. Table of Contents. Powder Clutch, Brake MODEL ZKB-AN,BN Powder Clutch ZKB-YN,XN Powder Brake

Instruction Manual. Table of Contents. Powder Clutch, Brake MODEL ZKB-AN,BN Powder Clutch ZKB-YN,XN Powder Brake ZJ-267A Powder Clutch, Brake MODEL ZKB-AN,BN Powder Clutch ZKB-YN,XN Powder Brake Instruction Manual Table of Contents Cautions on Safety - - - - - - - - - - - - - - - - - 1 1. Cautions before use - -

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

HINDUSTAN PETROLEUM CORPORATION LIMITED MUMBAI REFINERY DHT PROJECT SULPHUR BLOCK PART V SECTION 3.3

HINDUSTAN PETROLEUM CORPORATION LIMITED MUMBAI REFINERY DHT PROJECT SULPHUR BLOCK PART V SECTION 3.3 Page 1 of 7 HINDUSTAN PETROLEUM CORPORATION LIMITED MUMBAI REFINERY DHT PROJECT SULPHUR BLOCK PART V SECTION 3.3 STANDARD SPECIFICATION FOR OIL MIST LUBRICATION SYSTEM DOCUMENT NO : 44LK-5100-704/M.02/0024/A4

More information

In any of the 5 star hotels. The exact venue will be informed once finalized.

In any of the 5 star hotels. The exact venue will be informed once finalized. Training Title ELECTRIC DISTRIBUTION SYSTEM EQUIPMENT: Transformers, Switchgears, Circuit Breakers, Relays, Capacitors, Surge Arresters, Cables & Meters: Operation, Inspection, Testing, Evaluation, Maintenance

More information

STANDARD PRACTICE INSTRUCTION

STANDARD PRACTICE INSTRUCTION STANDARD PRACTICE INSTRUCTION DATE: March 1, 2001 SUBJECT: Ladder Safety Program. REGULATORY STANDARD: 29 CFR 1910.25 Portable Wood Ladders. 29 CFR 1910.26 Portable Metal Ladders. 29 CFR 1926.1053-1060

More information

VOLT POT 1K R220. OPEN FOR 60 Hz STAB A.V.R. R220. Installation and maintenance

VOLT POT 1K R220. OPEN FOR 60 Hz STAB A.V.R. R220. Installation and maintenance VOLT POT 1K 110 0V E+ E- OPEN FOR 60 Hz STAB This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test)

SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) ANNEXURE I SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) Paper I & Paper II for General Category of S.C.C. Examination Paper I & Paper

More information

Specification Approval Sheet

Specification Approval Sheet Page No. 1/11 Specification Approval Sheet Model:IFR18650EC-1.5Ah Prepared By/Date(RD) Reviewed by/date Checked By/Date (QA) Approved By/Date Bing Zeng/2012.4.26 Wu Chen/2012.4.26 SiBiao Jin/2012.4.26

More information

Minnesota Department of Transportation (Mn/DOT) Historic Bridge Management Plan

Minnesota Department of Transportation (Mn/DOT) Historic Bridge Management Plan 6.5 Recommended maintenance activities Routine maintenance is the ongoing work required to prevent and control the deterioration of the bridge components. Because the Stillwater Lift Bridge is movable,

More information

MHI Integrally Geared Type Compressor for Large Capacity Application and Process Gas Application

MHI Integrally Geared Type Compressor for Large Capacity Application and Process Gas Application MHI Integrally Geared Type for Large Capacity Application and Process Gas Application NAOTO YONEMURA* 1 YUJI FUTAGAMI* 1 SEIICHI IBARAKI* 2 This paper introduces an outline of the structures, features,

More information

ELECTRICAL INSTALLER THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET

ELECTRICAL INSTALLER THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET Candidate Code No. EIN 08 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSTALLER THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

EISHO TEK. Vacuum Circuit Breaker

EISHO TEK. Vacuum Circuit Breaker EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who

More information

MOTORS. Part 2: The Stepping Motor July 8, 2015 ELEC This lab must be handed in at the end of the lab period

MOTORS. Part 2: The Stepping Motor July 8, 2015 ELEC This lab must be handed in at the end of the lab period MOTORS Part 2: The Stepping Motor July 8, 2015 ELEC 3105 This lab must be handed in at the end of the lab period 1.0 Introduction The objective of this lab is to examine the operation of a typical stepping

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented

More information

PHASERS. Operating and Instruction Manual. a n d A C C E S S O R I E S

PHASERS. Operating and Instruction Manual. a n d A C C E S S O R I E S VOLTMETERS PHASERS a n d A C C E S S O R I E S Operating and Instruction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E WA U K E G A N, I L L I N O I S 6 0 0 8 5 U. S. A. PHONE 847.473.4980

More information

APPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1

APPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1 Table of Contents APPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1 B.01 SCOPE... B-1 B.02 GENERAL... B-1 B.03 ELECTRICAL QUALIFICATION... B-1 B.04 EQUIPMENT RECONDITIONING... B-2

More information

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2 WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 DESCRIPTION OF SERVICE A. General: RULE NO. 2 1. Alternating current service at 60-hertz (cycles per second)

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

a. Design: i. Supplier may visit to the site and get familiarized with the exact requirements

a. Design: i. Supplier may visit to the site and get familiarized with the exact requirements 1. Design, Fabrication, Supply, Installation, Commissioning, Warranty of Control Panel for 30/5 Te Outdoor Goliath Crane in adherence to attached specifications, dismantling & removal of the existing pedestal

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

9. Effects of an electric current

9. Effects of an electric current Leaving Cert Physics Long Questions 2017-2002 9. Effects of an electric current Please remember to photocopy 4 pages onto one sheet by going A3 A4 and using back to back on the photocopier Contents Ordinary

More information

36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS

36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS 36-27-1. General. 1.1. Scope. -- Rules and Regulations Governing Surface Areas. 1.2.

More information

Interconnection Process for Generation Systems

Interconnection Process for Generation Systems Interconnection Process for Generation Systems I. INTRODUCTION...1 II. GENERAL INFORMATION...2 A. Definitions...2 B. Nodak Electric Cooperative, Inc. Generation Interconnection Contacts...3 C. Engineering

More information

Nanometrics Solar Power System

Nanometrics Solar Power System Nanometrics Solar Power System Installation Guide Nanometrics Inc. Kanata, Ontario Canada 2003 Nanometrics Inc. All Rights Reserved. Installation Guide The information in this document has been carefully

More information

Monocellular centrifugal electro-pumps

Monocellular centrifugal electro-pumps Réf. 2100 - O33 / a - 5.95 This manual must be given to the end user LS Monocellular centrifugal electro-pumps Installation and maintenance 1 - GENERAL The LS range of monobloc electro-pump units should

More information