Element D Services Heating Ventilating and Air Conditioning ODG010107

Size: px
Start display at page:

Download "Element D Services Heating Ventilating and Air Conditioning ODG010107"

Transcription

1 Element D Services Heating Ventilating and Air Conditioning ODG D Vivarium Exhaust and Ventilation System Part 1. General 1. This section supplements Design Guideline Element D3042 on exhaust and ventilation with specific criteria for projects involving design of Vivariums. 2. Refer to Design Guideline Element D3042 for the following: a. General design criteria related to Exhaust and Ventilation. b. Special Contract Document Requirements and products applicable to the Project. Part 2. Design Criteria GENERAL 1. In general, Vivarium exhaust systems shall comply with animal room, procedure and support room ventilation air requirements of AALAC, NIH, CDC, and OSHA. 2. Each Vivarium exhaust air system shall have a corresponding supply air system to comply with laboratory, hood exhaust air, cage rack wash, and Vivarium (animal) room ventilation exhaust air change requirements listed below: Room Description Occupied AC/ hr Unoccupied AC / hr Necropsy Cage Wash Area Surgery Animal Holding Quarantine Room Laundry Room Bedding Storage 6 6 Chemical-Waste Storage Bio-Waste Storage Radioisotope Storage Micro PET Micro CT Central Supply Store 6 6 Procedure Room Air change rates noted above are minimum air change rates during occupied periods. Actual air change rates may exceed the stated rates due to sensible heat gain or make-up air requirements. Page 1 of 5

2 4. Vivarium exhaust fans and 30 percent roughing filters and percent HEPA filter banks shall be an N+1 redundant system capable of maintaining constant volume with the capacity to exhaust the listed rooms at required minimum ventilation design air change rates. 5. Exhaust fans shall be direct drive and controlled to maintain the exhaust air requirements to meet air change rates and building pressurization requirements. Exhaust fans shall be controlled to compensate for loading of exhaust air filters. The minimum allowable stack height to be a minimum 15 feet above centerline height of air intake or roofline. The stack discharge air velocity shall be equal to or greater than 3500 fpm. 6. During unoccupied periods in necropsy, surgery, and procedure rooms, the air change rate may be reduced to 50 percent of the occupied air change rate. Cage wash areas may be reduced to 10 air changes per hour when unoccupied. 7. The switchover from occupied period to unoccupied period will be accomplished via interlock with the room light switch. Occupancy interlock shall be with cage wash equipment control panel for cage washrooms and procedure rooms. The room light switch will not be used to setback the air change rate in animal holding rooms. 8. Emergency power shall be available to animal holding rooms, quarantine rooms, procedure rooms to maintain a controlled environment and air change rates during loss of normal power. 9. Biological Safety Cabinets shall have a face velocity equal to or greater than 100 fpm. Constant volume bypass type hoods will be utilized. a. Class II, Type A BSC- no ducted exhaust is required. The exhaust air outlets from a Class II, Type B1, B2, B3, and Class III BSCs shall be connected to the building exhaust air system. b. Some of the Class II Type B2 BSCs will utilize bag-in/bag-out percent HEPA filters within the BSC cabinet. 10. If substantial Organic Chemistry area is included, variable volume type hoods with restricted bypasses will be utilized for those spaces. 11. Specify welded stainless steel Type 316L ductwork (18 gage minimum) for exhaust air ductwork routed in inaccessible areas, cage washer, cage washroom and where exhaust air gases are not compatible with galvanized steel or for decontamination purposes. Remaining exhaust duct can be constructed using galvanized steel. 12. Design dedicated exhaust duct distribution systems to separate clean areas from dirty areas for prevention of cross contamination. 13. Label exhaust ducts used to transport contaminated air from Biological Safety Page 2 of 5

3 Cabinets and Necropsy with Caution Biological Hazard using black on red background at 20 foot intervals. 14. Exhaust ducts used to transport air from Biological Safety Cabinets where radioisotopes are used must be labeled with the standard Caution Radiation symbol: magenta on yellow background at 20 foot intervals. Equip Biological Safety Cabinets with proper filtration components to capture potential contaminates. Maximum duct velocities shall be based on the medium being transported and also based on noise criteria where noise generated from air moving at a high velocity can create a disturbance. 15. Exhaust ducts from both clean and dirty animal rooms shall have cleanouts at the bottom of vertical duct riser sections and at all changes in direction. 16. Exhaust duct elbows shall be radius type. Do not design turning vanes in duct fittings of the dedicated Vivarium exhaust distribution system from animal holding or procedure rooms. 17. Provide exhaust air thimble connections in animal holding areas for flexible hose hook up at each cage rack. 18. Filter all Vivarium exhaust using exhaust filter unit housings. Each filter unit housing shall have a bank of 30 percent efficient pre-filters followed by high capacity percent HEPA filters. The last final filter will be comprised of a bank of charcoal absorbers. 19. Route the cage washer room exhaust duct through the building roof at a distance of 25 feet and downwind from any outside air intake. Specify the minimum allowable stack height to be a minimum 15 feet above centerline height of air intake or roofline. The stack discharge air velocity shall be equal to or greater then 3500 fpm. 20. Food Storage and Cold Rooms are refrigerated spaces where the air cooled condensing units for conditioning the rooms are typically located in an interstitial space or equipment room penthouse. AIR DEVICES 1. Refer to Sound Criteria in Design Guideline Element D Exhaust square panel face Omni directional diffusers with round necks shall be provided in open areas. Increase neck sizes for the diffuser since they are being used for exhaust air purposes. 3. Animal holding rooms and procedure rooms can be exhausted with the use of thimble connections and ventilated and conventional cage racks. Electric actuated air valves shall be used to control the exhaust airflow rates via feed back signals from air measuring stations and setpoints (adjustable) from the building automation system (BAS). Page 3 of 5

4 4. The animal surgery room shall have two sidewall exhaust grilles with the bottom of the grilles are located at opposite corners of the room, and 6 inches above the finished floor. Locate grilles in opposite corners of the surgery room. 5. Necropsy room shall have side wall exhaust grilles with the bottom of the grille located 6 inches above the floor. Size the exhaust grille and exhaust hood to properly exhaust the Necropsy room to maintain required air change rate and to keep the room negative with respect to adjacent spaces. Provide an exhaust duct connection for the downdraft necropsy table. Part 3. Special Contract Document Requirements 1. Include a single line riser diagram drawing of the general building and dedicated ventilation exhausts and building pressure relief systems in the Contract Documents. 2. The riser diagram drawing shall show isolation dampers, modulating control dampers, exhaust fans with percent system capacity ratings, and exhaust air flow rates. This single line riser diagram shall be initially provided in the Schematic Design Submittal. 3. Locate exhaust discharge where air cannot be easily reintroduced into the building outside air intakes. Part 4. Products 1. Refer to Master Construction Specification Sections. 2. Refer to Design Guideline Element D3041 for additional criteria on outside air intakes. 3. Evaluate the use of runaround coils and energy recovery components as appropriate to the application. 4. Evaluate the use of a separate AHU using percent HEPA final filter bank designed for and dedicated to the surgery room. Using a surgical room recirculation rates as indicated in the Table shown in Part 2 of this section, and a minimum outdoor air change rate of 4 air changes per hour. The return air grilles would be used in place of the exhaust air grilles. 5. Class II, Type 1A Biological Safety Cabinets will be UL listed and equipped with percent high capacity HEPA filters. This particular class of cabinet does not have to be hard ducted; a general exhaust air grille can be located near the Type 1A cabinets to exhaust odors. 6. Preferred direct drive exhaust fans shall be similar to Strobic axial fans. Exhaust air plenum with modulating face and bypass control dampers. Page 4 of 5

5 7. Specify Phoenix (Accel II) or TriaTek Venturi Air Valves and BACnet compatible systems are to be used to control the exhaust airflow rates from the individual room or spaces. System must also be able to integrate with Edstrom Watchdog Monitoring System. 8. The cage wash system exhaust fans shall be constructed as backward inclined blade types. Shafts shall be polished carbon steel and shall also have a phenolic coating applied to all fan parts that are directly in contact with the exhaust airstream. 7. Specify welded stainless steel Type 316L ductwork (18 gage minimum) for exhaust air ductwork from the Biological Safety Cabinets, necropsy room, cage washer, and cage washroom. Remaining exhaust duct can be constructed using galvanized steel. 8. Ductwork and air devices shall be constructed or fabricated from non ferrous materials when used or near imaging rooms or suites. Follow the manufacturer s recommendations for material, sizing, and routing duct used for cryogenic exhaust of magnetic resonance imaging equipment. Document Revision History Issue Date Revision Description Revisor Initial Adoption of Element Rev. 1 Rev. 2 Rev. 3 Rev. 4 Rev. 5 Page 5 of 5

Element D Services Heating Ventilating and Air Conditioning ODG010107

Element D Services Heating Ventilating and Air Conditioning ODG010107 Element D Services Heating Ventilating and Air Conditioning ODG010107 D304202 Laboratory Exhaust and Ventilation Part 1. General 1. This section supplements Design Guideline Element D3042 on air handling

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with specific criteria for projects involving design of Laboratory Exhaust and Systems.

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Laboratory Exhaust and PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with additional criteria for projects involving design of laboratory

More information

Design Standard - Fume Hoods & Fume Hood Exhausts

Design Standard - Fume Hoods & Fume Hood Exhausts Design Standard - Fume Hoods & Fume Hood Exhausts 1.0 Introduction The fume hood is the primary control device in most laboratories for protecting employees and students from exposure to hazardous chemicals.

More information

STATE UNIVERSITY CONSTRUCTION FUND

STATE UNIVERSITY CONSTRUCTION FUND DIRECTIVE 15H-8 Issue date: June 2016 1. General Design Criteria LABORATORY DESIGN a. Design a Pressure Independent Variable Volume system that satisfies the airflow demand of the fume hoods, minimum air

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS JANUARY 2012 SECTION FUME HOODS AND LOCAL EXHAUST SYSTEMS

UNIVERSITY OF ROCHESTER DESIGN STANDARDS JANUARY 2012 SECTION FUME HOODS AND LOCAL EXHAUST SYSTEMS SECTION 15860 - FUME HOODS AND LOCAL EXHAUST SYSTEMS This standard describes fundamental good practices relating to the design, selection, installation, commissioning, and testing of local exhaust systems

More information

January, 2014 Page 1 of 6

January, 2014 Page 1 of 6 Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying chemical fume hood modifications or installations. These standards are not intended to restrict or replace

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Underutilized Technologies

Underutilized Technologies Underutilized Technologies in Performance Contracting Underutilized Technologies Jeffrey A. Means Department of Veterans Affairs August 16, 2017 Tampa Convention Center Tampa, Florida Underutilized Technologies

More information

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive Centrifugal Inline s Models SQ-M and BSQ-M Direct and Belt Drive July 2010 Centrifugal Inline Duct s Greenheck's model SQ-M and BSQ-M centrifugal square inline fans feature a unique combination of installation

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

Model ND-2 Specification

Model ND-2 Specification Model ND-2 Specification The model ND-2 is an exhaust only canopy hood rated for all types of cooking equipment. The hood shall have the size, shape and performance specified on drawings. Construction

More information

Ventilated Balance Enclosures

Ventilated Balance Enclosures Ventilated Balance Enclosures by PLAS n LABS Meets and exceeds ANSI/ASHRAE 110:2016 standard for containment & performance PLAS n LABS, INC. www.plas-labs.com PLI@PLAS-LABS.com 517-372-7177 Ventilated

More information

HORD HOSPITAL OPERATING ROOM AIR CURTAIN

HORD HOSPITAL OPERATING ROOM AIR CURTAIN HORD HOSPITAL OPERATING ROOM AIR CURTAIN The Hospital Operating Room Diffuser (HORD) air curtain system is engineered specifically for the demanding needs of operating room environments. The HORD air curtain

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS COMMERCIAL KITCHEN APPLICATIONS Belt Driven Model VRBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

3.5 Exposure Control Measures

3.5 Exposure Control Measures 3.5 Exposure Control Measures 3.5.1 Chemical Fume Hoods Chemical fume hoods are the most reliable and primary engineering control used in the laboratory to protect against the inhalation of hazardous vapors

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -CH and Vektor -CD Centrifugal High Plume and High Plume Dilution Exhaust System July 2015 Vektor-CH High Plume and Vektor-CD High Plume Dilution Exhaust System Greenheck

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

SPECIFICATION SHEET. C5000 ( cfm)

SPECIFICATION SHEET. C5000 ( cfm) (3500 5500 cfm) CASING Double wall cabinet White exterior paint, 22GA steel Galvanized 18GA steel inner wall Access door with ¼ turn handle Insulation : 2 in 18GA Stainless Steel drain pan Drain connection

More information

Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets

Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets TECHNICAL BULLETIN : ACCESSORY INFORMATION Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets General NuAire Class II, Type A2 (NSF/ANSI

More information

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall:

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall: Fume Hood Standard A fume hood is an enclosed working chamber fitted with an exhaust ventilation system. It is one component of an exposure control system which is designed to contain, dilute and disperse

More information

How to Use a Chemical Fume Hood Safely

How to Use a Chemical Fume Hood Safely Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) How to Use a Chemical Fume Hood Safely SafetyNet #: 35 A chemical fume hood is designed to protect the worker from volatile and

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

Inline Fans [ 14 ] * UL is optional and must be specified.

Inline Fans [ 14 ] * UL is optional and must be specified. XTIF, XIB and XID models are listed for electrical (UL/C-UL US 705) File no. E40001. Model XTIF is available with the UL 762 Listing (Power Ventilators for Restaurant Exhaust Appliances). Accurex, LLC

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes activated carbon filters, automatic renewable media filters, disposable, extended area panel filters, disposable

More information

MiniRoom. Isolation cubicles flexibility with containment. Horizontal laminar flow of air for greater protection - positive or negative

MiniRoom. Isolation cubicles flexibility with containment. Horizontal laminar flow of air for greater protection - positive or negative MiniRoom Key Features Isolation cubicles flexibility with containment Custom built to your requirements Horizontal laminar flow of air for greater protection - positive or negative Electro-magnetic door

More information

Demand Based Static Pressure Reset Control for Laboratories

Demand Based Static Pressure Reset Control for Laboratories Accutrol, LLC Product Sheet Demand Based Static Pressure Reset Control for Laboratories Accutrol, LLC 21 Commerce Drive, Danbury, CT 06810 203-445-9991 www.accutrolllc.com Contents and specifications are

More information

FOR USE IN SOLUTION AIR HANDLING UNITS

FOR USE IN SOLUTION AIR HANDLING UNITS AMS-60 AIRFLOW MONITORING DEVICE APPLICATION GUIDE Supersedes: NOTHING Form 102.20-AG1 (303) FOR USE IN SOLUTION AIR HANDLING UNITS GENERAL The YORK AMS-60 is an airflow monitoring device which combines

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

HORD HOSPITAL OPERATING ROOM AIR CURTAIN

HORD HOSPITAL OPERATING ROOM AIR CURTAIN HORD HOSPITAL OPERATING ROOM AIR CURTAIN The Hospital Operating Room Diffuser (HORD) air curtain system is engineered specifically for the demanding needs of operating room environments. The HORD air curtain

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved B U I L D I N G V A L U E I N A I R. April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the

More information

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile November 204 BCF Centrifugal Cabinet Contents Standard Construction Features... 3 Options and Accessories... 4 Filter and Mixing Box Data... 5 Typical Installations...

More information

Variable Air Volume Dampers

Variable Air Volume Dampers OVAV 2000 SERIES OPTIMA VAV DAMPERS Overview OPTIMA make Variable Air Volume (OVAV) box is a part of an Air Conditioning system. It is located inside the duct work. VAV Dampers are designed to control

More information

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

NJK Precision Product NJK-02 Sensor Installation Guide

NJK Precision Product NJK-02 Sensor Installation Guide Precision -02 Sensor 2017 Product Line Precision Product Table of Contents Precision Company Overview - Page 2-02 Installation Guidelines - Page 3-02 Recommended Installations - Page 5-02 Non-Recommended

More information

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

COMPACT CAGE RACK VALVES

COMPACT CAGE RACK VALVES COMPACT CAGE RACK VALVES Phoenix Controls Constant Volume Compact Cage Rack Valve combines a factory-calibrated, field-tunable flow rate setting with a mechanical, pressure-independent flow regulator to

More information

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans.

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans. SECTION 23 34 43 LABORATORY HIGH PLUME EXHAUST FANS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the industry s best performance and durability

More information

Complete HVAC Capability

Complete HVAC Capability Air Handling Units Brochure 1110 January 2006 Complete HVAC Capability MEA Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels Inlet Vane Option

More information

CH5000 Heat Recovery Ventilator

CH5000 Heat Recovery Ventilator ADVANCED COMMERCIAL Heat Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 3500-5500 CFM CASING Double-wall cabinet White exterior paint, 22-gauge galvanized steel -gauge

More information

Centrifugal Inline Fans

Centrifugal Inline Fans Centrifugal Inline Fans Models SQ-M and SQ-M Direct and elt Drive UILDING VLUE IN IR. February January 2018 2017 Models SQ-M & SQ-M Centrifugal Square Inline Duct Fans Designed for indoor and outdoor clean

More information

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING -

More information

The highest energy recovery available.

The highest energy recovery available. The highest energy recovery available. RG S e r i e s Dual Core Energy Recovery Temperature Efficiency Tempeff North America products employ Dual Core regenerative technology that offers up to 95% temperature

More information

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

DESIGN GUIDELINES FANS PAGE 1 of 7

DESIGN GUIDELINES FANS PAGE 1 of 7 DESIGN GUIDELINES FANS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the

More information

Introduction to Johnson Controls Dampers

Introduction to Johnson Controls Dampers Damper and Actuator Product Guide 268.1 Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader

More information

General. Technical Bulletin: ACCESSORY INFORMATION

General. Technical Bulletin: ACCESSORY INFORMATION Technical Bulletin: ACCESSORY INFORMATION General Variable Range Exhaust Flow Canopies with Monitor for NU 475 (Series 1 ), NU 477 (Series 1 ), NU 480 (Series 1 ), NU 481 (Series 1 ), NU 677 (Series 1

More information

2001 Dodge Caravan Sport MANUAL A/C-HEATER SYSTEMS Caravan, Town & Country, & Voyager

2001 Dodge Caravan Sport MANUAL A/C-HEATER SYSTEMS Caravan, Town & Country, & Voyager SPECIFICATIONS NOTE: Information for Caravan includes the Grand Caravan. SPECIFICATIONS Application Specification Compressor Type Nippondenso 10S20H Compressor Belt Tension (1) System Oil Capacity (2)

More information

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Ductless Nanoparticle Containment Enclosures

Ductless Nanoparticle Containment Enclosures Ductless Nanoparticle Containment Enclosures The World s Most Extensive Selection of Ductless Containment Solutions. 24 36 48 Purair P5-24-XT (NANO) Provides Effective Containment for Personnel and Environmental

More information

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 705) File no. E40001 and for grease removal (UL/C-UL US 762) File no. MH11745. Accurex, LLC certifies model XRUB, XRUD, XSEB,

More information

Purifier Logic Class II Biosafety Cabinets FEATURES & BENEFITS

Purifier Logic Class II Biosafety Cabinets FEATURES & BENEFITS Purifier Logic Class II Biosafety Cabinets FEATURES & BENEFITS Optional 254 nm UV lamp Contain-Air Negative Pressure Channel Bright, glare-free fluorescent lighting Fully-closing, counterbalanced tempered

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -HS, Vektor -MS and Vektor -CS with Variable Geometry Nozzle September 017 Vektor -HS, Vektor -MS and Vektor -CS Greenheck s Variable Geometry Nozzle exhaust systems allow

More information

ECONOMIZERS. 5/2012 Supersedes

ECONOMIZERS. 5/2012 Supersedes Litho U.S.A. 2012 ECONOMIZERS 507031 01 5/2012 Supersedes 506747 01 K1ECON ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS AND OUTDOOR AIR HOODS USED WITH KG/KC/KH 024, 030, 036, 048, 060, 072, 090

More information

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS ZEPHYR CABINET Single & Twin Unit Cabinet Fans Moving Your Way TABLE OF CONTENTS Introduction, Certifications & Listings, Features & Benefits 3 Options & Accessories 4 Typical Applications & Belt Drive

More information

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD Model Features Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AMCA International Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International

More information

ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET

ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET NuAire, Inc. 2100 Fernbrook Lane Plymouth, MN 55447 U.S.A.

More information

INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS JDH/C2 DESIGNER SERIES

More information

2008 PCP COMPOUND APPLICATIONS GUIDE

2008 PCP COMPOUND APPLICATIONS GUIDE 2008 PCP COMPOUND APPLICATIONS GUIDE INTRODUCTION The Compound Populated Catalyst Panel (PCP Compound) is a combination of PCP Standard and Drop-In technologies. It may be used in conjunction with panels

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

Completing Your Fume Removal System

Completing Your Fume Removal System Once a laboratory hood has been selected, the next step is to select the proper blower and ductwork. It is important that these be sized correctly depending on hood size, application, CFM, and distance

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets KVR Capture Jet Round Island Hood with Perimeter Jets The KVR Round Island Capture Jet hood with perimeter jets is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat

More information

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges Phone: 800-348-1097 www.aeipaintbooths.com Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges Thank you for the opportunity to work with you on your paint booth project. Below

More information

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD MEL FEATURES Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

KVL-P with Plate Shelf

KVL-P with Plate Shelf The model of Capture Jet TM hood is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat emitted by cooking equipment, helping to provide a comfortable and clean environment.

More information

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile May 2007 BCF Belt Drive Cabinet s Greenheck belt drive low-profile cabinet fans, BCF, are designed for efficiency and reliability in supply, exhaust or

More information

Direct Gas-Fired Heating

Direct Gas-Fired Heating Direct Gas-Fired Heating Model DG 800 to 15,000 cfm Up to 1,600,000 BTU/hr Optional Evaporative Cooling January 2005 PRODUCT FEATURES Model DG Direct Gas-Fired Make-Up Air Unit The Greenheck model DG is

More information

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODELS & e DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODEL DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,780 CFM in high static pressure applications up to 1-1/2 w.g. Attractive

More information

Healthcare Solutions Room Pressure Monitors and Controls

Healthcare Solutions Room Pressure Monitors and Controls Healthcare Solutions Room Pressure Monitors and Controls TOUCHSCREEN ROOM PRESSURE MONITOR The Touchscreen Room Pressure Monitor (PMT) provides precise room pressure monitoring for critical spaces such

More information

LABORATORY HOOD MANUAL

LABORATORY HOOD MANUAL LABORATORY HOOD MANUAL DRAKE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY November 2015 TABLE OF CONTENTS I. INTRODUCTION... 1 II. FUME HOOD SERVICE... 2 Fume Hood Service Provided by EH&S... 2 Fume Hood Service

More information

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES

More information

KWT GALLEY WATER WASH HOOD GALLEY WATER WASH HOOD KWT. With supply air and Capture Jet technology

KWT GALLEY WATER WASH HOOD GALLEY WATER WASH HOOD KWT. With supply air and Capture Jet technology KWT GALLEY WATER WASH HOOD With supply air and Capture Jet technology APPLICATIONS Halton KWT is a galley water wash hood for use in marine & offshore applications. The highly efficient KWT hood uses Halton

More information

HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION. Exflow 28 Technical Specification. Page 1 of 7

HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION. Exflow 28 Technical Specification. Page 1 of 7 HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION Exflow 28 Technical Specification Page 1 of 7 TECHNICAL SUMMARY Terminal Unit size 12-3 ¼ x 12-3 ¼ x 23 ¾ Terminal Unit weight 3527

More information

CRYSTAL-AIRE. concealed commercial air cleaners

CRYSTAL-AIRE. concealed commercial air cleaners CRYSTAL-AIRE concealed commercial air cleaners CRYSTAL-AIRE A Customized CONCEPT IN Concealed AIR CLEANING. Using a variety of accessories, Crystal-Aire can be adapted to most building configurations and

More information

ERV. Energy Recovery Ventilators. Capacity: 400 to 4,000 cfm Model: ERV500i/e, ERV1000i, ERV1500i/e, ERV2000i/e, ERV3000i/e

ERV. Energy Recovery Ventilators. Capacity: 400 to 4,000 cfm Model: ERV500i/e, ERV1000i, ERV1500i/e, ERV2000i/e, ERV3000i/e ERV Energy Recovery Ventilators Installation, Operation and Maintenance Instructions Manual Capacity: 400 to 4,000 cfm Model: ERV500i/e, ERV1000i, ERV1500i/e, ERV2000i/e, ERV3000i/e 2013 Venmar CES Inc.

More information

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS Air Zoë Centrifugal Inline Duct fans have been developed to efficiently handle the

More information

A. Each cabinet must be constructed and installed in accordance with EN12469:2000.

A. Each cabinet must be constructed and installed in accordance with EN12469:2000. BIOLOGICAL SAFETY CABINETS Class II, Biological Safety Cabinet PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this section to the extent referenced. The publications are referred

More information

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules Technical Specification Sheet Document No. 149-855 November 04, 2015 BACnet Lab and Pressurized Room Controllers with Off-board Air Modules NOTE: The 570-8xxPA BACnet laboratory controllers have new 67xx

More information

Portable filtration unit / 650 CFM (305 L/s) Portable filtration unit / 1500 CFM (710 L/s) For 1 or 2 arms configuration

Portable filtration unit / 650 CFM (305 L/s) Portable filtration unit / 1500 CFM (710 L/s) For 1 or 2 arms configuration -MC -MC Diversified Air Systems, Inc. pantone 2756 Portable filtration unit / 650 CFM (305 L/s) pantone 2756 Portable filtration unit / 1500 CFM (710 L/s) For 1 or 2 arms configuration 99.9% efficiency

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 This section applies to fans for Building Systems. PART 2 - GENERAL DESIGN REQUIREMENTS

More information

Tubular Centrifugal Inline Fans Page Introduction... 2 Construction Features... 3 Specification and Dimension Data TCN-D (Inline Fan- Direct

Tubular Centrifugal Inline Fans Page Introduction... 2 Construction Features... 3 Specification and Dimension Data TCN-D (Inline Fan- Direct Tubular Centrifugal Inline Fans Page Introduction........................................... 2 Construction Features.................................. 3 Specification and Dimension Data TCN-D (Inline Fan-

More information

KVM KVM. Capture Jet Hybrid Backshelf Hood. Capture Jet TM Hybrid Backshelf Hood

KVM KVM. Capture Jet Hybrid Backshelf Hood. Capture Jet TM Hybrid Backshelf Hood Capture Jet Hybrid Backshelf Hood The hybrid backshelf model of Capture Jet hood is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat emitted by cooking equipment,

More information