1 HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION Exflow 28 Technical Specification Page 1 of 7

2 TECHNICAL SUMMARY Terminal Unit size 12-3 ¼ x 12-3 ¼ x 23 ¾ Terminal Unit weight 3527 lb Clean filtered area 9-2 ¼ x 9-2 ¼ Partial walls finish 78 ¾ Minimum distance from Operating Room wall to clean zone 39 ½ Height to diffuser screen 8-6 x 9-6 Electrical requirements Absorbed power 20 amp three phase 460v - 60Hz Note: When optional extras are fitted i.e. Operating Lamp, power requirements increase from 20 amp to 25 amp. UCV Heat Gain BTU/hr (3.5 Kw) (Operational) Noise level 55dBA dependent on background noise level Standards unmanned HTM Supply air volume from terminal Recirc air volume 6357 CFM (Larger Volume flow rate available on request) CFM Fresh air volume CFM (To suit operating room heat gains) (100% Fresh Air System available on request). Page 2 of 7

3 Air change rates within the clean zone Approx 500 per hour Drawing No. EX 90/148 Rev H PERFORMANCE DISCHARGE AIR VELOCITY. Measured 78 ¾ from F.F.L. will be 75 FPM average within the discharge area 9-2 ¼ x 9-2 ¼ in accordance with HTM Measured 39 3/8 from F.F.L. will be not less than 39 FPM within the central operating zone /8 x /8 in accordance with HTM A critical factor governing the performance of the Exflow and its discharged air velocities is the provision of the required primary air input from the air conditioning system. The fresh air input volume requirement for the Exflow U.C.V. system is in the order of 742 CFM, for the purging of pollutants. However, to ensure satisfactory climatic control within the operating room a volume of CFM should be provided subject to local conditions. A further factor affecting the Exflow airflow pattern is the temperature differential between the supply air and the room air. The supply air temperature should not exceed room temperature i.e. room air temperature measured in the return air duct. Optimum performance will be achieved when the supply air is maintained at 1 C below the room air temperature. Bacteria levels within the Ultra Clean zone shall not exceed the maximum levels as recognised by international infection control guidelines as follows. Bacteria shall be measured as evidenced by the presence of Colony Forming Units (CFU). Average within 11 7/8 of wound site less than 10 CFU per 35.3 cubic feet of air. Average in the remainder of the clean zone, less than 20 CFU per 35.3 cubic feet of air. Page 3 of 7

4 STANDARDS The Exflow U.C.V. system complies with the following standards. HTM ventilation in healthcare premises. All classifications are given as the minimum standards achieved in the unmanned state. Page 4 of 7

5 GENERAL SPECIFICATION The Integral Exflow has four fans housed within the canopy corner sections each with sound attenuation to all air inlets and outlets. As a result of being self-contained NO additional space is required in the hospital plant room to accommodate fan units. This model is therefore the most economical for retro-fitting to upgrade an existing operating room or where space is otherwise limited. The overall dimensions of the unit are 12-3¼ x 12-3¼ x 23¾ deep and the unit can be surface mounted or almost totally recessed into the ceiling void (21½ max.). Fan units are double inlet with built-in, external rotor motor, speed variable via VFD (Variable Frequency Drive). Primary or pre-filtration of the recirculated air from the room is by G3 / EN779 filters. The pre-filters are located within the return air grilles on the underside face of the canopy and are easy to replace. Final filtration is by 8 HEPA (high efficiency particulate air) filters having an efficiency of % MPPS (Most Penetrating Particle Size) H14/EN1822. These filters are fitted in the ceiling of the 9-2 ¼ zone. A magnehelic pressure differential gauge is fitted to the Exflow unit to monitor HEPA filter soiling. Clear acrylic partial walls 0.39 thick extend down from the underside of the canopy and terminate 78¾ from finished floor level. Discharge area within the clear partial walls size 9-2½ x 9-2½. Mounting frame height will be between 9-7¼ and 11 7/8 from F.F.L. The Exflow and any associated optional equipment are powered from a separate cabinet containing all circuit breakers, terminals, contactors, relays, VFD s, etc., with door mounted system malfunction warning lights; surface mounted to the wall in the plantroom or other non-sterile most convenient place within 50 ft of the operating room. Controls include individual VFD s, one per fan, (4 fans), individual fan fail warning lights and dirty filter indicator. Size of basic panel: /8 Wide x 2 7 ½ High x 1 Deep. Note: When optional extras are fitted as referred to in Technical Summary, panel aspect size increases to 2 7 ½ Wide x 2 7 ½ High x 1 Deep. Page 5 of 7

6 Exflow theatre control panel (24 volt) will be suitable for being flush mounted into a prepared opening 1-1¾ (High) x 1-1¾ (Wide) x 3 1/8 (Deep) in the operating theatre wall. This displays the standard user controls for the Exflow, i.e. standby/operational mode switches, emergency stop switch, system fault warning indicator, Exflow perimeter light switch and a lamp test switch. Perimeter lighting is by 8 integral luminaires recessed into the Exflow return air grille panels each containing 2 x 4 ft colour corrected K4000 fluorescent lamps controlled by high frequency ballasts to provide a minimum lighting level of 92.9 ft/candles within the ultra clean zone 39 3/8 from F.F.L. Graded air diffusers, produced as 4 single sheet perforate panels, suspended directly below the terminal HEPA filters are secured by quick - release catches. The panels are easily removed to facilitate changing of HEPA filters. The exclusive design of this diffuser is material in creating the concentrically graded airflow profile. Construction - The Exflow unit is constructed from welded, zintec steel sheet in 4 separate sections to fit round the operating light stem. The 4 sections are bolted together and to a 4 x 2 RSC mounting frame on site. This is either supported on drop rods or bolted directly to the slab/steelwork. Finish - Polyester powder coated. Standard colour RAL 9010 textured 20% gloss. Fresh Air Inlets are provided into the fan mixing chambers for the introduction of climatic controlled air. These can be located on the top or into the sides of the fan sections as required to suit space limitations. Howorth Air Technology reserves the right to change the product specifications and design without prior notice. Page 6 of 7

7 OPTIONAL EXTRA FEATURES OPERATING LAMPS Howorth Air Technology should always be consulted before selection of an operating lamp to ensure compatibility and optimisation of the airflow. Controls for the operating lamp can be incorporated in the Exflow theatre control panel with associated transformers, relays, emergency battery changeover switch, etc. located in the Exflow power distribution cabinet. Early selection of the operating lamp is essential to ensure that its mounting stem can be provided to the correct length and installed prior to the Exflow 1st fix. Page 7 of 7

HORD HOSPITAL OPERATING ROOM AIR CURTAIN

HORD HOSPITAL OPERATING ROOM AIR CURTAIN HORD HOSPITAL OPERATING ROOM AIR CURTAIN The Hospital Operating Room Diffuser (HORD) air curtain system is engineered specifically for the demanding needs of operating room environments. The HORD air curtain

More information

HORD HOSPITAL OPERATING ROOM AIR CURTAIN

HORD HOSPITAL OPERATING ROOM AIR CURTAIN HORD HOSPITAL OPERATING ROOM AIR CURTAIN The Hospital Operating Room Diffuser (HORD) air curtain system is engineered specifically for the demanding needs of operating room environments. The HORD air curtain

More information

Clean Air Products Straight Thru Standard Profile Single Door Air Shower Purchase Specification

Clean Air Products Straight Thru Standard Profile Single Door Air Shower Purchase Specification Clean Air Products Straight Thru Standard Profile Single Door Air Shower Purchase Specification 1. Purpose This specification describes a single person air shower (aka decontamination shower) used to remove

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Horizontal swirling air discharge Adjustable blades Protective cage For high rooms, with adjustable air control blades Circular ceiling swirl diffusers,

More information

Laminar ceilings, exhaust columns, exhaust grilles

Laminar ceilings, exhaust columns, exhaust grilles Laminar ceilings, exhaust columns, exhaust grilles 1 Table of Contents: 1. Laminar ceilings general information... 3 2. Laminar ceilings design and operation principles... 4 3. Parameters of air in the

More information

AMENDMENTS Dated: August 25, 2010

AMENDMENTS Dated: August 25, 2010 AMENDMENTS Dated: August 25, 2010 The Guidelines for Air Conditioning of OT as mentioned in Glossary at page no. 114-115 is replaced by following text. Air OT Conditioning The Revised Guidelines for Air-Conditioning

More information

Total comfort control

Total comfort control Total comfort control YORK ACTIVE CHILLED BEAM WITH PERFORATED RETURN DIFFUSER Table of contents Concept & Technology Air Distribution & Facade Orientation Product Features Dimensions Performance Data

More information

Mediclean Complanate Ultra Clean Ventilation

Mediclean Complanate Ultra Clean Ventilation Mediclean Complanate Ultra Clean Ventilation complanate adjective com pla nate \ kämpləˌn t\ : made level : in one plane, flattened to a level surface : Latin complantus Mediclean Brandon Medical Brandon

More information

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades X X testregistrierung Type Vertical air discharge Horizontal air discharge For large temperature differences in heating mode, high penetration of air, with adjustable air control blades Circular ceiling

More information

Disc valves. Type Z-LVS. For supply air. 03/2017 DE/en PD Z-LVS 1

Disc valves. Type Z-LVS. For supply air. 03/2017 DE/en PD Z-LVS 1 X X testregistrierung Disc valves Type For supply air Circular disc valves with manually adjustable annular gap Nominal sizes 100, 125, 160, 200 mm Volume flow rate range 10 90 l/s or 36 324 m³/h Diffuser

More information

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES Circular ceiling swirl diffusers, with manual or motorised adjustment of the

More information

CG2010 Cytogard Cytotoxic Drug Safety Cabinets

CG2010 Cytogard Cytotoxic Drug Safety Cabinets CG2010 Cytogard Cytotoxic Drug Safety Cabinets Applications Cytotoxic drug safety cabinets are defined in Australian Standard AS2252.5 as the primary barrier against exposure to aerosols that are produced

More information

Class II biological safety cabinets

Class II biological safety cabinets Bulletin No. 203.0110 Class II biological safety cabinets Advanced technology for personnel, environment and product protection Applications Biological safety cabinets are defined in Australian standard

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Horizontal swirling air discharge Vertical air discharge Protective cage For high rooms, with adjustable air control blades Square ceiling swirl diffusers,

More information

NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG C-PREP

NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG C-PREP Item :A Prep Room NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG-200830-C-PREP Booth Working Dimensions: 20'0 Wide x 8'0 High x 30'0 Working Depth Approx. Booth Overall Dimensions: 20'4 Wide x 8'10

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Grille cores made of aluminium, with fixed horizontal blades Grille cores with special profiled blades

More information

GEA Clean Rooms. Modules with laminar air flow for ceiling installation GEA Fresh Heaven j^uu GEA Fresh Heaven j^uu=mltbo.

GEA Clean Rooms. Modules with laminar air flow for ceiling installation GEA Fresh Heaven j^uu GEA Fresh Heaven j^uu=mltbo. GEA Clean Rooms Modules with laminar air flow for ceiling installation GEA Fresh Heaven j^uu GEA Fresh Heaven j^uu=mltbo Data & Facts ÉåÖáåÉÉêáåÖ=Ñçê=~=ÄÉííÉê=ïçêäÇ db^=eé~í=bñåü~åöéêë Range of Application...

More information

AS , EN12469 (Microbiological Testing Method)

AS , EN12469 (Microbiological Testing Method) AS 1386.5, EN12469 (Microbiological Testing Method) Main Features Esco antimicrobial surface on all painted surfaces. Sentinel Microprocessor controller supervises all functions. Sterile work zone environment

More information

PRODUCT BROCHURE. Rectangular Displacement Diffuser RDW-FD RDW-FD : smartemp.com

PRODUCT BROCHURE. Rectangular Displacement Diffuser RDW-FD RDW-FD : smartemp.com PRODUCT BROCHURE Rectangular Displacement Diffuser RDW-FD smartemp.com DESCRIPTION The SMARTEMP Rectangular Displacement Diffuser, type RDW-FD (figure 1), produces a low velocity horizontal airflow pattern

More information

GRD PRODUCT CATALOG DISPLACEMENT VENTILATION PRODUCTS

GRD PRODUCT CATALOG DISPLACEMENT VENTILATION PRODUCTS GRD PRODUCT CATALOG PRODUCTS 2018 Metal Industries, Inc. PRODUCTS Displacement Ventilation systems provide conditioned air at floor level at very low velocity and allow heat sources within the room (like

More information

KLIMA Active Chilled Beams

KLIMA Active Chilled Beams KLIMA 2 600 Active Chilled Beams 0 Index Subject Page Index 1 Introduction 2 General description 3-4 Product features 5-6 Dimensions 7 Performance data 8-11 Selection example 12 Guide specifications 13

More information

PLANNING THE INSTALLATION

PLANNING THE INSTALLATION a Same for Single Speed Models (Series 1 & 2).. Table 2. F111 Air Volume Specifications for 3 Speed Models (Series 3). Particulates at Gas, V.O.C. and High a Medium Low 0.3 Micron Odor Control in cfm in

More information

Versatility. Features. By installing the SILENT MV, you will never experience the disturbance of noisy ventilation again. Benefits

Versatility. Features. By installing the SILENT MV, you will never experience the disturbance of noisy ventilation again. Benefits Ultra quiet and low profile helicocentrifugal in-line fans suitable for a wide range of domestic and commercial applications. Fitted with sound absorbent insulation and manufactured with an adjustable

More information

Model ND-2 Specification

Model ND-2 Specification Model ND-2 Specification The model ND-2 is an exhaust only canopy hood rated for all types of cooking equipment. The hood shall have the size, shape and performance specified on drawings. Construction

More information

TABLE OF CONTENTS SPECIFICATIONS 3 INSTALLATION 4. Direct Mount 4. Ducted Installations 5. Installing Plenum 5. Machine Mount Stand 5.

TABLE OF CONTENTS SPECIFICATIONS 3 INSTALLATION 4. Direct Mount 4. Ducted Installations 5. Installing Plenum 5. Machine Mount Stand 5. TABLE OF CONTENTS PAGE SPECIFICATIONS 3 INSTALLATION 4 Direct Mount 4 Ducted Installations 5 Installing Plenum 5 Machine Mount Stand 5 Ceiling Mount 6 Pedestal Stand 7 Drain Installation 7 Electrical 8

More information

PURCHASE SPECIFICATIONS FOR NUAIRE PHARMAGARD NU-NR797 NEGATIVE PRESSURE RECIRCULATING STERILE ISOLATOR

PURCHASE SPECIFICATIONS FOR NUAIRE PHARMAGARD NU-NR797 NEGATIVE PRESSURE RECIRCULATING STERILE ISOLATOR PURCHASE SPECIFICATIONS FOR NUAIRE PHARMAGARD NU-NR797 NEGATIVE PRESSURE RECIRCULATING STERILE ISOLATOR The intent herein is to provide a concise statement of requirements for a quality negative pressure

More information

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets KVR Capture Jet Round Island Hood with Perimeter Jets The KVR Round Island Capture Jet hood with perimeter jets is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Ventilation grilles, made of aluminium, with fixed horizontal blades also for horizontal runs Single

More information

we make clean air Air Filtration Solutions Industrial Commercial Residential quatroair.com AIR TECHNOLOGIES INC.

we make clean air Air Filtration Solutions Industrial Commercial Residential quatroair.com AIR TECHNOLOGIES INC. we make clean air Air Filtration Solutions Industrial Commercial Residential Che mic al F ilte r HE PA Filt er Filter Although very effective against very fine particles, filters do not filter out gasses

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type RFD-Sirius, cross bar Horizontal swirling air discharge Circular diffuser face, integral measuring tubes is an air terminal device combined with a VAV

More information

FILTER MODULES FILTER MODULES APPLICATIONS

FILTER MODULES FILTER MODULES APPLICATIONS FILTER MODULES FILTER MODULES APPLICATIONS MF MF filter modules were developed for use as filtration systems in centralised systems or individual work stations for the extraction of welding fumes. They

More information

Ceiling swirl diffusers with perforated face plate

Ceiling swirl diffusers with perforated face plate X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge For horizontal swirling supply air discharge creating high induction levels, with fixed air

More information

critical environment diffusers

critical environment diffusers FlowBar Critical Environment Diffusers Hard Diffusers Ceiling Table Applications of Contents 2 CRITICAL ENVIRONMENT DIFFUSERS Critical Environment Diffusers... 3 Applications... 3 General Clean Room Information...

More information

is with a variety of standard dimensions. Also our units can be custom engineered to any size.

is with a variety of standard dimensions. Also our units can be custom engineered to any size. Bio Safety Cabinet biosafe TM is designed to provide personnel, environmental and product protection. Air flow is drawn around the operator into the front grille of the cabinet, which provides personnel

More information

LAMINAR FLOW HORIZONTAL FLOW BENCH (LF) OPERATION & MAINTENANCE MANUAL

LAMINAR FLOW HORIZONTAL FLOW BENCH (LF) OPERATION & MAINTENANCE MANUAL LAMINAR FLOW HORIZONTAL FLOW BENCH (LF) OPERATION & MAINTENANCE MANUAL ENVIRCO Technical Support: 800-884-0002 Table of Contents WARNING... 3 INTRODUCTION... 3 FEATURES... 4 APPLICATIONS... 4 ASSEMBLY...

More information

Puri-Drall PDK. Puri-Clean PCK. Puri-Inlet PEK. HEPA filter air outlet with pull-down outlet element

Puri-Drall PDK. Puri-Clean PCK. Puri-Inlet PEK. HEPA filter air outlet with pull-down outlet element Cleanroom systems Puri-Drall PDK. Puri-Clean PCK. Puri-Inlet PEK. with pull-down outlet element DS 4178 E 01.201 Preliminary remarks Materials and designs As a rule, turbulent mixing ventilation is used

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with specific criteria for projects involving design of Laboratory Exhaust and Systems.

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Ventilation grilles with flat border construction also for continuous horizontal runs The new ventilation

More information

Supply air unit DYBA. Specifications. Connbox. Quick Selection DYBA, without slot, 1:3 plenum box ATTC (50 Pa)

Supply air unit DYBA. Specifications. Connbox. Quick Selection DYBA, without slot, 1:3 plenum box ATTC (50 Pa) DYBA is a quiet, ceiling-mounted supply air unit that consists of a nozzle diffuser, DYBH, and an insulated plenum box, ATTC. The nozzles of the diffuser produce a swirl pattern, which provides a highly

More information

Biological Safety Cabinet

Biological Safety Cabinet Biological Safety Cabinet Biological safety cabinets are used to provide primary containment in the laboratory when the investigator is using potentially infectious materials. There are three types of

More information

Laminar Flow Clean Benches, Horizontal and Vertical

Laminar Flow Clean Benches, Horizontal and Vertical UL 61010 Esco Airstream Horizontal Laminar Flow Clean Bench Model LHG-4AG-F_ UL 61010 Esco Airstream Vertical Laminar Flow Clean Bench Model LVG-4AG-S_ (with sliding sash) Laminar Flow Clean Benches, Horizontal

More information

TUBUS TUBUS. Key figures. Function Wall-mounted supply air diffusers

TUBUS TUBUS. Key figures. Function Wall-mounted supply air diffusers all-mounted supply air diffusers Key figures Connection: Airflow: Pressure: Sound level: Coating: 100,,160, 200, 250, 315 & 00 (mm) 10-350 l/s 70-100 Pa Always below 30 db(a) at 100 Pa, 300 l/s Standard

More information

TM Series MICROBIOLOGICAL SAFETY CABINETS. Technical Specifications

TM Series MICROBIOLOGICAL SAFETY CABINETS. Technical Specifications S@feflow TM Series MICROBIOLOGICAL SAFETY CABINETS Technical Specifications MSC Class II Type A2 Fully EN12469 certified by Tüv Last generation Microprocessor control with interactive functions Large screen

More information

FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA

FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA Fresh Breeze Fan-Filter Unit Range of Application... 3 Sizes... 3 Characteristics... 3 Fresh Breeze product line... 3 Areas of application... 3 Technical Data

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Ventilation grilles, made of sheet steel, with individually adjustable, horizontal blades Ventilation

More information

ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET

ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET ADVANCED SAFETY ENGINEERING FOR EFFECTIVE HANDLING OF HAZARDOUS PARTICULATE DRUGS AND POWDERS IN A CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET NuAire, Inc. 2100 Fernbrook Lane Plymouth, MN 55447 U.S.A.

More information

Series 577. Vertical Flow Softwall Portable Cleanroom. Series 577 Vertical Flow Softwall Portable Cleanroom

Series 577. Vertical Flow Softwall Portable Cleanroom. Series 577 Vertical Flow Softwall Portable Cleanroom Series 577 Vertical Flow Softwall Portable Cleanroom s o l u t i o n s The Series 577 softwall portable clean rooms are a cost-effective method of providing quality particulate control enclosures. The

More information

SILENT MV Ultra Quiet In-line Fans

SILENT MV Ultra Quiet In-line Fans Ultra Quiet In-line Fans 5 IP44 2 YEAR GUARANTEE Ultra quiet and low profile helicocentrifugal in-line fans suitable for a wide range of domestic and commercial applications. Fitted with sound absorbent

More information

Class II Biological Safety Cabinets The World's Most Energy Efficient, Quiet, and Compact Biosafety Cabinet

Class II Biological Safety Cabinets The World's Most Energy Efficient, Quiet, and Compact Biosafety Cabinet Class II Biological Safety Cabinets The World's Most Energy Efficient, Quiet, and Compact Biosafety Cabinet Airstream Class II, Biosafety Cabinet, Model AC2-4E_. RS 232 Serial Interface Port Send operational

More information

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser Halton DFB Conical Ceiling Diffuser Horizontal air supply, suitable also for exhaust Installation flush to the ceiling, light-weight aluminium design Circular duct connection with rubber gasket All sizes

More information

CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust

CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust 2 BERNER INTERNATIONAL Claire total At a glance CLAIRE TOTAL PRO CHEMISTRY Protection Shield The multiple award-winning Shield

More information

TECHINCAL DESCRIPTION BIO BAN

TECHINCAL DESCRIPTION BIO BAN TECHINCAL DESCRIPTION BIO BAN LAF CABINET ARTICLE DESCRIPTION CODE BIOBAN 48 00303400000 BIOBAN 72 00303500000 ST-[BIOBAN]_EN-0 Rev. 0 of 16/06/2010 Introduction Designed for the situation where is requested

More information

NOTE: The color of the actual product may differ from the color pictured in this catalog due to printing limitation.

NOTE: The color of the actual product may differ from the color pictured in this catalog due to printing limitation. www.labocon.com NOTE: The color of the actual product may differ from the color pictured in this catalog due to printing limitation. BIOLOGICAL SAFETY CABINET CLASS I LBSC-100 SERIES Labocon Biological

More information

Ceiling swirl diffusers with perforated face plate

Ceiling swirl diffusers with perforated face plate X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge Diffuser face plate with perforated circular face style and exposed discharge nozzle Diffuser

More information

Product Data. Features/Benefits. 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

Product Data. Features/Benefits. 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm Product Data 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams 11 to 190 cfm 36CBAC Chilled beam units offer: An increase in total airflow Sensible cooling and heating options Induction

More information

DFA - Conical Ceiling Diffuser. Halton DFA. Conical Ceiling Diffuser

DFA - Conical Ceiling Diffuser. Halton DFA. Conical Ceiling Diffuser Halton DFA Conical Ceiling Diffuser Horizontal air supply, suitable also for exhaust Installation flush to the ceiling, light-weight aluminium design Circular duct connection with rubber gasket Openable

More information

downflo workstation dust collectors

downflo workstation dust collectors downflo workstation dust collectors Outperforms all other collectors Downflo WorkStations (DWS) fit anywhere on the plant floor and apply NO restrictions to worker movements or visibility. The full line

More information

A Thermolab Group Company. HyZone. Class II Microbiological Safety Cabinets. for operator, environment and product protection.

A Thermolab Group Company. HyZone. Class II Microbiological Safety Cabinets. for operator, environment and product protection. A Thermolab Group Company HyZone Class II Microbiological Safety Cabinets for operator, environment and product protection. Microbiological Safety Cabinets Microbiological Safety Cabinets are used to give

More information

Central Battery Systems Loadstar AC/DC Systems

Central Battery Systems Loadstar AC/DC Systems The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources of emergency power for escape

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K .1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

Fume extractor is warranted for two years, parts and labor.

Fume extractor is warranted for two years, parts and labor. Industrial Centralized Systems Issued Feb. 7 Index No. AY/. Welding Safety and Health Quick Specs Industrial Applications Manufacturing and fabrication Schools and training centers Processes Stick (SMAW)

More information

Price O.R. Systems AIR CURTAIN SYSTEM

Price O.R. Systems AIR CURTAIN SYSTEM Price O.R. Systems AIR CURTAIN SYSTEM The Price Air Curtain System includes non-aspirating laminar flow diffusers directly above the surgical area with a surrounding four-sided linear slot diffuser system

More information

SPD/SPDV SPD SPDV. High Velocity/High Aspiration Air Outlet. Construction

SPD/SPDV SPD SPDV. High Velocity/High Aspiration Air Outlet. Construction SPD/SPDV SPD O D-1/8 C Saturn Plaque Diffuser US Patent B H SPDV SPD Dimensions in Inches MODEL A B C D H O SPD-04 7-1/2 2 1-1/4 4 3-3/4 5-1/8 SPD-06 10 2 1-3/16 6 4 7-1/2 SPD-08 12 2 1-3/16 8 4 9-1/2

More information

PRODUCT CATALOG CLASS II BIOLOGICAL SAFETY CABINET.

PRODUCT CATALOG CLASS II BIOLOGICAL SAFETY CABINET. PRODUCT CATALOG CLASS II BIOLOGICAL SAFETY CABINET www.labstac.com CLASS II BIOLOGICAL SAFETY CABINET It operates with a negative air pressure for personnel protection and HEPA filtered laminar airflow

More information

SPECIAL REVERSE HORIZONTAL FLOW ENCLOSURE OPERATING AND MAINTENANCE MANUAL. Issue No: 1

SPECIAL REVERSE HORIZONTAL FLOW ENCLOSURE OPERATING AND MAINTENANCE MANUAL. Issue No: 1 SPECIAL REVERSE HORIZONTAL FLOW ENCLOSURE OPERATING AND MAINTENANCE MANUAL Issue No: 1 Certificate No: 0954499 CE Marking certifies that this equipment conforms to the following EEC directives: - Low Voltage

More information

Element D Services Heating Ventilating and Air Conditioning ODG010107

Element D Services Heating Ventilating and Air Conditioning ODG010107 Element D Services Heating Ventilating and Air Conditioning ODG010107 D304203 Vivarium Exhaust and Ventilation System Part 1. General 1. This section supplements Design Guideline Element D3042 on exhaust

More information

DIR. VARIZON Displacement unit with adjustable spread pattern. Quick guide

DIR. VARIZON Displacement unit with adjustable spread pattern. Quick guide VARIZON Displacement unit with adjustable spread pattern Quick facts Adjustable spread pattern and affected area Suitable for all types of rooms Simple to install Cleanable Concealed fastening Available

More information

PHOENIX MINI-GUARDIAN

PHOENIX MINI-GUARDIAN PHOENIX MINI-GUARDIAN H. E. P. A. SYSTEM Therma-Stor Products A Division of DEC International Box 8050 Madison, WI 53708 Toll Free 1-800-533-7533 Local 1-608-222-5301 Table of Contents PHOENIX MINI-GUARDIAN

More information

Class I Microbiological Safety Cabinets The Leading Energy Efficient, Quiet, and Ergonomic Biosafety Cabinet

Class I Microbiological Safety Cabinets The Leading Energy Efficient, Quiet, and Ergonomic Biosafety Cabinet Class I Microbiological Safety Cabinets The Leading Energy Efficient, Quiet, and Ergonomic Biosafety Cabinet Airstream Class I Biosafety Cabinet, Model AC1-4E8 RS 232 Port and Zero Volt Relay Contact RS

More information

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air Square ceiling diffuser with discs for supply air QUICK FACTS Adjustable discs flexible spread pattern Can be used for vertical air diffusion Swirl function Also available in the Extract air version Designed

More information

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE.

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE. TECHNICAL SELECTION DATA PACKAGE UNIT + o C -10 o C 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE LIANT SCROLL RESSOR AXIAL UNIT FEATURES SPECIFICATION SUMMARY Scroll Compressor Multiple Speed Outdoor

More information

Type VSD35. Nominal length up to 1500 mm: one spigot

Type VSD35. Nominal length up to 1500 mm: one spigot Type VSD35 Nominal length up to 1500 mm: one spigot NUMEROUS VARIANTS FOR MANY DIFFERENT INSTALLATION SITUATIONS Slot diffusers with 35 mm diffuser face (nominal width) and adjustable air control elements

More information

LAMINAR AIRFLOW EQUIPMENT

LAMINAR AIRFLOW EQUIPMENT LAMINAR AIRFLOW EQUIPMENT LAMINAR AIRFLOW EQUIPMENT Whether your business focus is profit, cost reduction, or process effectiveness, NuAire offers a comprehensive variety of Laminar Airflow Equipment that

More information

The Clima Canal is quiet even at high outputs, making it a discreet and effective heater for almost any situation

The Clima Canal is quiet even at high outputs, making it a discreet and effective heater for almost any situation The is quiet even at high outputs, making it a discreet and effective heater for almost any situation A selection of grilles and finishes are available. Installation is simple and hassle-free due to the

More information

PHARMACY Products. Compounding Aseptic Isolator (CAI) Positive pressure sterility assurance barrier isolator for complete product protection.

PHARMACY Products. Compounding Aseptic Isolator (CAI) Positive pressure sterility assurance barrier isolator for complete product protection. PHARMACY Products SterilSHIELD Compounding Aseptic Isolator (CAI) Positive pressure sterility assurance barrier isolator for complete product protection. Underwriter Laboratories Listed SterilSHIELD Compounding

More information

OptimAir NF. Active Chilled Beam OptimAir NF. Nov

OptimAir NF. Active Chilled Beam OptimAir NF. Nov OptimAir NF Active Chilled Beam OptimAir NF Functions The OptimAir active chilled beam is a two-way induction type air-conditioningunit that is designed for integrated installation, mounted directly in

More information

R-4122 Sleeper Heater/ Air Conditioner Unit. R-2550 Heater/Air Conditioner Unit RED DOT UNITS HEATER-A/C RESCUE VEHICLES

R-4122 Sleeper Heater/ Air Conditioner Unit. R-2550 Heater/Air Conditioner Unit RED DOT UNITS HEATER-A/C RESCUE VEHICLES R-2550 Heater/Air Conditioner Unit RESCUE VEHICLES The R-2550 is specifically designed for ambulances and other lighter-duty vehicles with large interior spaces to heat and cool quickly. R-2550 SPECIFICATIONS

More information

Halton - Advanced Air Purification, Now with ELF Extended Life Filters!

Halton - Advanced Air Purification, Now with ELF Extended Life Filters! Halton - Advanced Air Purification, Now with ELF Extended Life Filters! Meets NYC Emission Requirements. Enabling Wellbeing Form#: BR-007 EcoloAir Brochure ECOLOAIR - ECOLO Halton has the equipment, design

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS TM TECHNICAL SPECIFICATIONS Model PPH2SD Series M1200 Product Line Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units M1200 12 YEAR ALL PARTS LIMITED WARRANTY M1200 WITH UPGRADED WARRANTY PACKAGE

More information

Ultra-quiet circular duct fans TD-SILENT ECOWATT Series

Ultra-quiet circular duct fans TD-SILENT ECOWATT Series TD-SILENT ECOWATT - MODELS 5 to TD-SILENT ECOWATT - MODELS AND At 5% of full speed fan power consumption is reduced by 7% Low profile Mixed-flow fans with sound-absorbent insulation, extremely quiet, fan

More information

CCE - Adaptable active chilled beam for exposed installation. Halton CCE. Adaptable active chilled beam for exposed installation

CCE - Adaptable active chilled beam for exposed installation. Halton CCE. Adaptable active chilled beam for exposed installation Halton CCE Adaptable active chilled beam for exposed installation Combined cooling, heating, and supply air unit for exposed installation Ideal solution for applications where good indoor environment,

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Laboratory Exhaust and PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with additional criteria for projects involving design of laboratory

More information

P8SE Series. 14 SEER, Three Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units

P8SE Series. 14 SEER, Three Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units TECHNICAL SPECIFICATIONS P8SE Series 14 SEER, Three Phase Packaged Air Conditioner 3, 4, 5 Ton Units The P8 Series single packaged air conditioners are high efficiency self contained cooling units that

More information

ADAPTTM. Sphere. Active communicative, supply air diffuser for the WISE system. Quick Selection

ADAPTTM. Sphere. Active communicative, supply air diffuser for the WISE system. Quick Selection ADAPTTM Sphere Active communicative, supply air diffuser for the WISE system Quick facts Supply air diffuser with an active damper Pressure-dependent and cleanable Integrated sensor module Simple wiring,

More information

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL APPLICATION OF DUST CONTROL EQUIPMENT: CAUTION - Warning Improper operation of dust control system may contribute to conditions in the work area or facility that could result in severe personal injury

More information

INDEX. SUPER VENT By Beta Industrial. pages INTRODUCTION CONSTRUCTION PERFORMANCE CHART ACOUSTIC DATA CHART DIMENSION SHEET - SINGLE CABINET FANS

INDEX. SUPER VENT By Beta Industrial. pages INTRODUCTION CONSTRUCTION PERFORMANCE CHART ACOUSTIC DATA CHART DIMENSION SHEET - SINGLE CABINET FANS Cabinet Fan SV-1 INDEX INTRODUCTION CONSTRUCTION PERFORMANCE CHART ACOUSTIC DATA CHART pages 01 02 03 04 DIMENSION SHEET - SINGLE CABINET FANS DIMENSION SHEET - TWIN CABINET FANS PERFORMANCE GRAPH WIRING

More information

Q6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 13 SEER, 7.7 HSPF Three Phase, Packaged Heat Pump 3-5 Ton Units WARRANTY

Q6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 13 SEER, 7.7 HSPF Three Phase, Packaged Heat Pump 3-5 Ton Units WARRANTY TECHNICAL SPECIFICATIONS Q6SD Series 13 SEER, 7.7 HSPF Three Phase, Packaged Heat Pump 3-5 Ton Units The Q6SD Series packaged units are high efficiency self contained cooling and heating units that can

More information

R6GF Series Rev B TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Gas/Electric Units Two-Stage Heat/Cool with Variable Speed Blower

R6GF Series Rev B TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Gas/Electric Units Two-Stage Heat/Cool with Variable Speed Blower TECHNICAL SPECIFICATIONS R6GF Series Rev B Single Packaged Gas/Electric Units Two-Stage Heat/Cool with Variable Speed Blower R6GF 15 SEER, 81% AFUE 2-5 Ton Units These single packaged gas/electric systems

More information

Element D Services Heating Ventilating and Air Conditioning ODG010107

Element D Services Heating Ventilating and Air Conditioning ODG010107 Element D Services Heating Ventilating and Air Conditioning ODG010107 D304202 Laboratory Exhaust and Ventilation Part 1. General 1. This section supplements Design Guideline Element D3042 on air handling

More information

Thermo Scientific 1300 Series A2. Class II, Type A2 Biological Safety Cabinets. Good for you good for the environment

Thermo Scientific 1300 Series A2. Class II, Type A2 Biological Safety Cabinets. Good for you good for the environment Thermo Scientific 1300 Series A2 Class II, Type A2 Biological Safety Cabinets Good for you good for the environment Thermo Scientific 1300 Series A2 Enjoy best-in-class performance and value g Superior

More information

DAC - Conical Diffuser. Halton DAC. Conical diffuser

DAC - Conical Diffuser. Halton DAC. Conical diffuser Halton DAC Conical diffuser Coanda effect provided with a wide range of air flow rates, thanks to the special profile of the diffuser blades Diffuser adapted for variable air flow Supply in four directions

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Sound Enclosure and Subbase Fuel Tank Package Applicable to the following models: KD800 - KD2500 (includes KD1250-A) Level 1 Sound Enclosure with Lift Base Sound Level

More information

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Ceiling swirl diffusers with perforated face plate > Type DCS Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION

More information

PRECISE. Glove Boxes

PRECISE. Glove Boxes PRECISE Glove Boxes PRECISE Basic Glove Boxes All models feature: One-piece molded, medium-density polyethylene shell. Dry powder epoxy-coated steel superstructure. 1/4" thick laminated safety glass viewing

More information

Slot diffusers for ceiling installation

Slot diffusers for ceiling installation X X testregistrierung Slot diffusers for ceiling installation Type lenum box with damper blade (optional) Alternating horizontal air discharge Concealed screw fixing With wide diffuser face for larger

More information

IN STAL LA TION IN STRUC TIONS FOR CON CEN TRIC DIF FUSER

IN STAL LA TION IN STRUC TIONS FOR CON CEN TRIC DIF FUSER IN STAL LA TION IN STRUC TIONS FOR CON CEN TRIC DIF FUSER UNIT FILTER PLENUM CONTROL MOTOR ECONOMIZER FRESH AIR EXHAUST AIR ROOF CURB FLEXIBLE DUCT CON CEN TRIC DIFFUSER BOX Concentric Diffuser Flush Mount

More information

Nozzle diffuser DYRH / Supply air unit DYRB (=DYRH+ATTD)

Nozzle diffuser DYRH / Supply air unit DYRB (=DYRH+ATTD) Nozzle diffuser DYRH / Supply air unit DYRB (=DYRH+ATTD) The DYRB is a quiet, ceiling-mounted supply air unit that consists of a nozzle diffuser, DYRH, and a plenum box, ATTD. The diffuser has adjustable

More information

ADAPTTM. Free. Active communicative, supply air diffuser for the WISE system, ADAPT F

ADAPTTM. Free. Active communicative, supply air diffuser for the WISE system, ADAPT F ADAPTTM Free Active communicative, supply air diffuser for the WISE system, ADAPT F Quick facts Supply air diffuser with an active damper Pressure-dependent and cleanable Integrated sensor module Simple

More information

Affordable portable filtration unit

Affordable portable filtration unit AQC source capture equipment Affordable portable filtration unit 750 to 800 CFM at the hood High efficiency cartridge Ideal for welding applications MAXAIR 6 X 10 fume arm included Filter pressure status

More information

Downflo workstation DuSt ColleCtorS

Downflo workstation DuSt ColleCtorS Downflo WorkStation Dust Collectors Outperforms All Other Collectors Downflo WorkStations (DWS) fit anywhere on the plant floor and apply NO restrictions to worker movements or visibility. The full line

More information