1 PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with specific criteria for projects involving design of Laboratory Exhaust and Systems. B. Refer to Design Guideline Element D3042 for the following: 1. General design criteria related Exhaust and. 2. Special Contract Document Requirements and products applicable to the Project. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. In general, laboratory exhaust systems shall comply with procedure and support room ventilation air requirements of NFPA 45, 90A, NIH, CDC, and OSHA. B. Special exhaust systems, noted below, where determined to be hazardous, shall not be housed in the same chase that houses environmental supply, return, and exhaust ducts and shall be labeled "hazardous" consistent with specification requirements.. 1. Laboratory hood exhaust systems. 2. Biological laboratory exhaust. 3. Radioactive hot lab exhaust. 4. LN 2 freezer room exhaust system. Where laboratory classification is BSL-1 or 2 and laboratory protocol does not allow for hazardous exhaust as a portion of the laboratory exhaust system, combined environmental/laboratory exhaust systems may be used and it may be located in the same chase as environmental supply and return ducts. The combination environmental/laboratory exhaust ductwork should still be labeled "hazardous" to be consistent with specification requirements. C. All other ductwork carrying make-up air that is connected to special exhaust systems may be installed in the same chase that carries environmental supply and/or return ducts. D. Exhaust fans serving laboratory hoods shall be connected to an emergency power source. Refer also to Section D3000 for additional emergency power requirements. ODG OF 7

2 2.02 LABORATORY HOOD EXHAUST FANS A. While the type of exhaust system would depend on the hood characteristics, the following features shall be incorporated into the design to avoid excessive noise levels and ensure accurate air balancing. 1. The system shall conform to OSHA Regulation 29 CFR, Part Exhaust shall be continuously monitored and an alarm system (local audible and visible alarm and an alarm at M. D. Anderson Cancer Center s central monitoring services, shall be provided for each hood and biological safety cabinet). 3. Exhaust fans shall be selected to operate at low tip speed (approximately at 50 percent of the maximum permissible tip speed) and maximum static efficiency. 4. Provide fan selection data on a performance curve and ensure that the fan discharge is directed vertically upward. 5. Design duct sizing to maintain velocity in the ductwork between 2000 and 2500 fpm. 6. Select fans with backward inclined fans. 7. Perform sound analysis for each exhaust fan and provide sound attenuation, if required. 8. To ensure design airflow is achieved on manifold and shared exhaust systems, pressure independent, factory-set, field-adjustable automatic airflow control shall be provided for each fume hood and biological safety cabinet. 9. An independent flow monitor shall be provided and alarm locally and to the building automation system (BAS). Provisions need to be incorporated in the design to allow access to the independent flow monitor. ODG OF 7

3 B. Each laboratory exhaust air system shall have a corresponding supply air system to comply with laboratory, hood exhaust air, and laboratory ventilation exhaust air change (AC/hr) requirements listed below: Room Description Occupied 3 AC/hr (minimum) Unoccupied AC/hr (minimum) Vacant 4 AC/hr (minimum) Fume Hood Rooms Radio Chemistry Laboratory Open Lab Traditional Lab Equipment Room Tissue and Culture Dark Room Storage Room Glass Wash Room Cold Room LN 2 freezer Room Notes: 1. Lab room has no fume hood. 2. Lab room has fume hood(s). 3. Occupied defined as space with personnel present during specific time. 4. Vacant defined as space that is not assigned to a lab user and that does not have equipment that generates chemicals. C. Actual air change rates may exceed the above stated rates to maintain temperatures in the laboratory or prevent a hazardous environment. BL3 s and Tissue Culture Rooms are exempt from the occupied and unoccupied air change rate. By definition, one AC/hr is the total of supply air and infiltration air from surrounding space provided in one hour divided by the total room volume. D. Laboratory exhaust fans and (30 percent filter banks, where applicable) shall be an N+1 redundant system capable of maintaining constant volume with the capacity to exhaust listed rooms at the required minimum ventilation design air change rates. E. Exhaust fans shall be direct drive. Where exhaust air filters require or merit such, exhaust fans shall be powered through the use of variable frequency drives that vary fan speeds to maintain the exhaust air requirement during exhaust air filter loading. Fan speed is determined by maintaining an airflow measurement or static pressure setpoint (adjustable) from the BAS. F. The design exhaust rate through the fume hoods, radioisotope fume hoods and (BSCs) will be determined based on using restricted sash opening and maintaining a minimum face velocity of 100 fpm at any point at the open sash. 1. Laboratory chemical hood operation: Face velocities should be between 80 and 125 fpm at the working sash height with an optimum level of 100 fpm during occupied periods. ODG OF 7

4 Face velocity may be reduced to 60 fpm during unoccupied periods (via zone presence sensors at the hoods or room occupancy sensors). G. Either variable or constant volume bypass type hoods will be utilized. If substantial Organic Chemistry area is included, variable volume type hoods with restricted bypasses will be utilized for those spaces. In addition to fume hoods, the BSCs, flammable storage cabinets, and acid storage cabinets will be served as follows: 1. A typical fume hood and Class II Type B1 cabinets should be included in laboratory exhaust system. 2. IIB2 BSCs typically have a greater exhaust duct static pressure requirement (-2" w.c.) than other ducted BSCs (e.g. IIA2 BSCs at -0.1" w.c.) and chemical fume hoods (-0.2" w.c.). Where possible a limited number of IIB2 BSCs (i. e. two or less) can be combined with the building general exhaust system, the A/E should consider the use of individual booster fans (one at each IIB2 BSC) to prevent the entire general exhaust system from being operated at greater negative pressures then normally required. A dedicated exhaust fan system shall be used when multiple (i.e. greater then two) IIB2 BSCs are used on the project. 3. Radioisotope hoods should have a dedicated exhaust. 4. Organic chemistry hoods may also require a dedicated exhaust air system. 5. Flammable storage cabinets and acid storage cabinets will be ventilated utilizing a 2-inch galvanized pipe directly connected from the cabinet to the fume exhaust ductwork. An exhaust air valve will not be utilized for the cabinet. 6. Some of the Class II Type B2 BSCs will utilize bag-in/bag-out percent HEPA filters located on top of the BSC cabinet, and the supply air filters are within the BSCs. H. The type of filtration components that will be placed in the laboratory exhaust shall be evaluated based on the work being performed in each of the laboratories and exhaust hoods. This determination should occur in Programming. I. Instruments that control air valves shall be capable of changing the state of room pressurization, which will be dependant on current and future use of the laboratory. J. Storage rooms that contain laboratory specialty gases or liquid nitrogen stored in dewars shall be ventilated and shall have the appropriate gas detection monitoring and alarm systems per OSHA requirements to protect personnel from accidental asphyxiation. K. LN 2 freezer rooms shall have air change rate as listed in this sections air change rate table. Exhaust duct shall be galvanized and routed to the general lab exhaust air energy recovery system. The bottom of exhaust air grilles shall be placed low to the floor where nitrogen gas if present in the room can be readily exhausted from the room. Supply air grilles shall be placed at ceiling heights. ODG OF 7

5 2.03 LABORATORY EXHAUST DUCTWORK A. Specify welded stainless steel Type 316L ductwork (18 gage minimum) for exhaust air ductwork from the BSCs, laboratory glassware washer, and chemical fume hoods where corrosive chemicals may be used, and hoods that use radioactive isotopes use a Type 316 polished at weld, stainless steel. Exhaust duct from synthesis labs should be Type 316L stainless or other suitably rugged/ inert material due to the corrosive and toxic exhaust. B. Galvanized steel can be used as the construction duct material on general exhaust systems. C. Exhaust ducts used to transport air from Biological Safety Cabinets where radioisotopes are used must be labeled with the standard Caution Radiation Symbol magenta on yellow background at 20 foot intervals. Equip Biological Safety Cabinets with proper filtration components to capture potential contaminates. D. Route the exhaust duct through the building roof at a distance of 25 feet and downwind from any outside air ventilation air intake. The final location and orientation of the laboratory exhaust or outside air intake is determined from wind tunnel results. E. The allowable exhaust air stack height shall be minimum 12 feet above centerline height of air intake or roofline. The stack discharge air velocity shall be equal to or greater than 3000 fpm (3600 fpm for NIH funded project). F. Locate exhaust discharge stack where it cannot be easily reintroduced into the building outside air intakes. Research prefers to locate outside ventilation air intakes on the side of the building and not on the roof. Refer to Design Guideline Element D3041 for additional criteria on outside air intakes. G. When high plume exhaust fans are being considered in the design of a laboratory exhaust system, the A/E needs to place the plume heights, design airflow rates, static pressure requirement, and maximum brake horsepower requirements on the equipment schedule AIR DEVICES 1. A/E shall consider wind velocities and prevailing wind direction as listed in Chapter 26 in Tables 1A, 2A and 3A of ASHRAE Handbook of Fundamentals or airport weather data. A. Refer to Sound Criteria in Design Guideline Element D3002. B. Exhaust square panel face Titus Omni directional diffusers with round necks shall be provided in open areas. Increase neck sizes for the diffuser since they are being used for exhaust air purposes. C. Air valves shall be used to control the exhaust airflow rates from rooms, hoods, and BSCs via feed back signals from stand alone controllers and setpoints (adjustable) from the BAS. ODG OF 7

6 PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. Include a single line riser drawing of the general exhaust ventilation exhaust systems in the Contract Documents. This shall be initially provided in the Schematic Design Submittal. PART 4 - PRODUCTS 4.01 GENERAL A. Refer to Owner s Master Construction Specifications. These are available on the Owner s Design Guidelines website: B. Evaluate energy recovery units as appropriate to the application in accordance with the latest edition of ANSI/ASHRAE/IESNA Refer to Section D3041 for energy recovery requirements. C. Evaluate the use of proximity occupant sensors on each hood to reduce the open sash face velocity to 60 fpm when the workspace in front of the fume hood is not occupied. Refer also to 2.02 above. D. The preferred direct drive exhaust fans are high plume dilution mixed flow fans, where feasible. E. Evaluate and provide test data for other laboratory HVAC airflow tracking equipment Phoenix (Accel II) or Tek-Air Valves that control the temperatures and exhaust airflow rates from the individual room or spaces. These systems should be operating with BACnet open protocol and also be compatible system with the existing BAS. F. Evaluate an exhaust duct material that is capable of withstanding the corrosion products from a synthesis laboratory. G. Evaluate recirculation of air in non-laboratory areas. H. Evaluate sensible cooling in low hazard, high heat load areas. ODG OF 7

7 PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Revisor Initial Adoption of Element Rev Part 2 Laboratory Exhaust Hoods added Titus; Part 2.1 revised Table for Tissue Culture Room AC rate from 8 to 12 for unoccupied mode; revised to exception on AC rates lab temp, and prevent hazardous environment; revised 150 to 125 fpm; deleted B3 and Class III BSCs; revised 10 ft to12 ft on exhaust stacks; revised Air Devices; added criteria that A/E to evaluate use of duct material serving synthesis labs; deleted additional exhaust requirement for RI room. Rev Revised AC/hr values in the table of 2.02 B. including the additions of notes and editorial format changes. Rev Added 2.01B.4., added AC/hr value in the table of 2.02 B. for LN 2 Freezer Room, revised J. and added 2.02 K.. Rev Included sustainability requirements throughout document based upon TGCE's evaluation. (Paragraphs 2.01 B; 2.01 B 4; 2.01 D; 2.02 D; 2.02 E; 2.02 F; 2.02 G; 2.02 H; 4.01 B & 4.01C) PDN PDN / CC Rev Revised AC/hr values and note 2 in the table of 2.02 B. PDN / CC JCD PDN END OF ELEMENT D ODG OF 7

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Laboratory Exhaust and PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3042 on exhaust and ventilation with additional criteria for projects involving design of laboratory

More information

Element D Services Heating Ventilating and Air Conditioning ODG010107

Element D Services Heating Ventilating and Air Conditioning ODG010107 Element D Services Heating Ventilating and Air Conditioning ODG010107 D304202 Laboratory Exhaust and Ventilation Part 1. General 1. This section supplements Design Guideline Element D3042 on air handling

More information

Element D Services Heating Ventilating and Air Conditioning ODG010107

Element D Services Heating Ventilating and Air Conditioning ODG010107 Element D Services Heating Ventilating and Air Conditioning ODG010107 D304203 Vivarium Exhaust and Ventilation System Part 1. General 1. This section supplements Design Guideline Element D3042 on exhaust

More information

Design Standard - Fume Hoods & Fume Hood Exhausts

Design Standard - Fume Hoods & Fume Hood Exhausts Design Standard - Fume Hoods & Fume Hood Exhausts 1.0 Introduction The fume hood is the primary control device in most laboratories for protecting employees and students from exposure to hazardous chemicals.

More information

January, 2014 Page 1 of 6

January, 2014 Page 1 of 6 Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying chemical fume hood modifications or installations. These standards are not intended to restrict or replace

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS JANUARY 2012 SECTION FUME HOODS AND LOCAL EXHAUST SYSTEMS

UNIVERSITY OF ROCHESTER DESIGN STANDARDS JANUARY 2012 SECTION FUME HOODS AND LOCAL EXHAUST SYSTEMS SECTION 15860 - FUME HOODS AND LOCAL EXHAUST SYSTEMS This standard describes fundamental good practices relating to the design, selection, installation, commissioning, and testing of local exhaust systems

More information

STATE UNIVERSITY CONSTRUCTION FUND

STATE UNIVERSITY CONSTRUCTION FUND DIRECTIVE 15H-8 Issue date: June 2016 1. General Design Criteria LABORATORY DESIGN a. Design a Pressure Independent Variable Volume system that satisfies the airflow demand of the fume hoods, minimum air

More information

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall:

Fume Hood Standard. The appropriate maintenance/engineering division on each campus or other business unit operating on UofT property shall: Fume Hood Standard A fume hood is an enclosed working chamber fitted with an exhaust ventilation system. It is one component of an exposure control system which is designed to contain, dilute and disperse

More information

3.5 Exposure Control Measures

3.5 Exposure Control Measures 3.5 Exposure Control Measures 3.5.1 Chemical Fume Hoods Chemical fume hoods are the most reliable and primary engineering control used in the laboratory to protect against the inhalation of hazardous vapors

More information

DEPAUL UNIVERSITY. Fume Hoods Manual. Environmental Health & Safety. April 2017

DEPAUL UNIVERSITY. Fume Hoods Manual. Environmental Health & Safety. April 2017 DEPAUL UNIVERSITY Fume Hoods Manual Environmental Health & Safety April 2017 1 TABLE OF CONTENTS SECTION PAGE NO. 1. INTRODUCTION 2 2. TYPES OF FUME HOODS 2 2.1 CONVENTIONAL FUME HOODS 2 2.2 HIGH PERFORMANCE

More information

How to Use a Chemical Fume Hood Safely

How to Use a Chemical Fume Hood Safely Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) How to Use a Chemical Fume Hood Safely SafetyNet #: 35 A chemical fume hood is designed to protect the worker from volatile and

More information

TABLE OF CONTENTS STANDARDS FOR THE DESIGN, CONSTRUCTION, MAINTENANCE AND USE OF LABORATORY FUME HOODS. Effective August 2010

TABLE OF CONTENTS STANDARDS FOR THE DESIGN, CONSTRUCTION, MAINTENANCE AND USE OF LABORATORY FUME HOODS. Effective August 2010 TABLE OF CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 2 BACKGROUND... 2 FUME HOOD DESIGN AND CONSTRUCTION... 3 VARIABLE AIR VOLUME FUME HOODS... 3 RECIRCULATING HOODS... 3 SPECIAL LABORATORY FUME HOODS...

More information

Fume Hood Program. Program originated: 08/2008 Updated: 06/2016. Gordon Krueger Environmental Safety Specialist

Fume Hood Program. Program originated: 08/2008 Updated: 06/2016. Gordon Krueger Environmental Safety Specialist Fume Hood Program Program originated: 08/2008 Updated: 06/2016 Gordon Krueger Environmental Safety Specialist 1 TABLE OF CONTENTS I. INTRODUCTION 3 II. LABORATORY VENTILATION 3 A. Chemical Fume Hood Types

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -CH and Vektor -CD Centrifugal High Plume and High Plume Dilution Exhaust System July 2015 Vektor-CH High Plume and Vektor-CD High Plume Dilution Exhaust System Greenheck

More information

UNR Ventilation Policy

UNR Ventilation Policy UNR Ventilation Policy UNR Ventilation Policy TABLE OF CONTENTS SECTION TITLE PAGE 1.0 Scope and Application 1 2.0 Responsibilities 2 2.1 EH&S 2 2.2 Facilities Services Department 3 2.3 End Users 4 3.0

More information

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans.

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans. SECTION 23 34 43 LABORATORY HIGH PLUME EXHAUST FANS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2

---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2 Environmental Health & Safety RADIATION PROCEDURES MANUAL Procedure Cover Sheet Procedure Title: Fume Hoods Procedure Number: EHS-08-03-REV 2 Effective Date: 18 September, 2018 ---:...-- Approved By_-=--------::.--...l~---

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -HS, Vektor -MS and Vektor -CS with Variable Geometry Nozzle September 017 Vektor -HS, Vektor -MS and Vektor -CS Greenheck s Variable Geometry Nozzle exhaust systems allow

More information

Ductless Nanoparticle Containment Enclosures

Ductless Nanoparticle Containment Enclosures Ductless Nanoparticle Containment Enclosures The World s Most Extensive Selection of Ductless Containment Solutions. 24 36 48 Purair P5-24-XT (NANO) Provides Effective Containment for Personnel and Environmental

More information

LABORATORY HOOD MANUAL

LABORATORY HOOD MANUAL LABORATORY HOOD MANUAL DRAKE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY November 2015 TABLE OF CONTENTS I. INTRODUCTION... 1 II. FUME HOOD SERVICE... 2 Fume Hood Service Provided by EH&S... 2 Fume Hood Service

More information

.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section )

.1 Special Building Areas 8. Laboratories..3 Laboratory Casework (section ).4 Chemical storage cabinets (section ) Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying Laboratory Fume Hoods. These standards are not intended to restrict or replace professional judgment..2

More information

Lab Safety & Energy Optimization. Introduction & Agenda

Lab Safety & Energy Optimization. Introduction & Agenda Lab Safety & Energy Optimization Determining Appropriate Airflow Specifications for VAV Fume Hoods Thomas C. Smith tcsmith@labhoodpro.com Introduction & Agenda Thomas C. Smith President, BSME (NCSU), MSEE

More information

Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets

Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets TECHNICAL BULLETIN : ACCESSORY INFORMATION Fixed Range Exhaust Flow Canopies for NU 540 (Series 1 ), NU 543 (Series 1 ) Class II, Type A2, Biological Safety Cabinets General NuAire Class II, Type A2 (NSF/ANSI

More information

Model ND-2 Specification

Model ND-2 Specification Model ND-2 Specification The model ND-2 is an exhaust only canopy hood rated for all types of cooking equipment. The hood shall have the size, shape and performance specified on drawings. Construction

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

Underutilized Technologies

Underutilized Technologies Underutilized Technologies in Performance Contracting Underutilized Technologies Jeffrey A. Means Department of Veterans Affairs August 16, 2017 Tampa Convention Center Tampa, Florida Underutilized Technologies

More information

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

Fume hood construction details. VANGUARD FUME HOODS Listed by Intertek to UL 1805 standard page 1. Features

Fume hood construction details. VANGUARD FUME HOODS Listed by Intertek to UL 1805 standard page 1. Features Fume hood construction details 1 9 2 10 3 11 13 4 14 5 15 6 16 17 7 12 18 8 Features 1 Fluescent light fixture with interi sealed glass offering a safe and bright wking area (100 foot candles) 2 SEFA-8

More information

Fume hood construction details VANGUARD FUME HOODS. Listed by Intertek to UL 1805 standard. page 1. Features

Fume hood construction details VANGUARD FUME HOODS. Listed by Intertek to UL 1805 standard. page 1. Features Fume hood construction details 1 2 3 4 5 6 7 9 10 11 13 14 15 16 17 12 18 8 Features 1 Fluescent light fixture with interi sealed glass offering a safe and bright wking area (100 foot candles) 2 SEFA-8

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2100/2200 FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER MODEL 2100: Constant face velocity, variable volume MODEL 2200: Constant face velocity, variable volume

More information

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation

More information

General. Technical Bulletin: ACCESSORY INFORMATION

General. Technical Bulletin: ACCESSORY INFORMATION Technical Bulletin: ACCESSORY INFORMATION General Variable Range Exhaust Flow Canopies with Monitor for NU 475 (Series 1 ), NU 477 (Series 1 ), NU 480 (Series 1 ), NU 481 (Series 1 ), NU 677 (Series 1

More information

AUDIO-VISUAL EQUIPMENT

AUDIO-VISUAL EQUIPMENT 11 52 00 AUDIO-VISUAL EQUIPMENT 1. GENERAL A. Related sections: i. 00 00 13 Designing Learning Environments ii. 11 52 13 Projection Screens iii. 12 56 52 Audio-Visual Equipment iv. 72 41 00 General Audio-Visual

More information

OVERVIEW Combination Supply/Return Diffuser (SARM)

OVERVIEW Combination Supply/Return Diffuser (SARM) OVERVIEW Combination Supply/Return Diffuser (SARM) APPLICATION INFORMATION The extruded aluminum square and rectangular supply and return diffusers are designed principally for packaged roof top type heating

More information

AUDIO-VISUAL EQUIPMENT

AUDIO-VISUAL EQUIPMENT 11 52 00 AUDIO-VISUAL EQUIPMENT 1. GENERAL A. Related sections: i. 00 00 13 Designing Learning Environments ii. 11 52 13 Projection Screens iii. 12 56 52 Audio-Visual Equipment iv. 72 41 00 General Audio-Visual

More information

HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION. Exflow 28 Technical Specification. Page 1 of 7

HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION. Exflow 28 Technical Specification. Page 1 of 7 HOWORTH EXFLOW 28 PREVENTS AIRBORNE INFECTION TECHNICAL SPECIFICATION Exflow 28 Technical Specification Page 1 of 7 TECHNICAL SUMMARY Terminal Unit size 12-3 ¼ x 12-3 ¼ x 23 ¾ Terminal Unit weight 3527

More information

Completing Your Fume Removal System

Completing Your Fume Removal System Once a laboratory hood has been selected, the next step is to select the proper blower and ductwork. It is important that these be sized correctly depending on hood size, application, CFM, and distance

More information

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Class II biological safety cabinets

Class II biological safety cabinets Bulletin No. 203.0110 Class II biological safety cabinets Advanced technology for personnel, environment and product protection Applications Biological safety cabinets are defined in Australian standard

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS COMMERCIAL KITCHEN APPLICATIONS Belt Driven Model VRBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

FXV/CXV & FXV3/CXV3 Layout Guidelines

FXV/CXV & FXV3/CXV3 Layout Guidelines FXV/CXV & FXV3/CXV3 Layout Guidelines Open circuit cooling towers, closed circuit cooling towers, and evaporative condensers all depend upon an adequate supply of fresh, ambient air to provide design capacity.

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT

INSTALLATION INSTRUCTIONS ISLAND LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AMCA International Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International

More information

Polypropylene Total Exhaust Fume Hoods

Polypropylene Total Exhaust Fume Hoods Polypropylene Total Exhaust Fume Hoods 24 36 48 Provides Comprehensive Operator Protection and Optimum Performance 60 72 96 PTEFH-48 shown on optional vented base cabinet Provides Personnel Protection

More information

CG2010 Cytogard Cytotoxic Drug Safety Cabinets

CG2010 Cytogard Cytotoxic Drug Safety Cabinets CG2010 Cytogard Cytotoxic Drug Safety Cabinets Applications Cytotoxic drug safety cabinets are defined in Australian Standard AS2252.5 as the primary barrier against exposure to aerosols that are produced

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes activated carbon filters, automatic renewable media filters, disposable, extended area panel filters, disposable

More information

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ISLAND RANGE HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

new fume hoods providing performance and protection

new fume hoods providing performance and protection new fume hoods providing performance and protection five questions to get us started 1. Will the use of your hood require a special application hood? 2. How high of a priority is energy conservation? 3.

More information

FUME HOOD SELECTION GUIDE

FUME HOOD SELECTION GUIDE FUME HOOD SELECTION GUIDE FUME HOOD SELECTION GUIDE Laboratory fume hoods are one of the most vital pieces of safety equipment in a working laboratory. Fume hoods are designed to safely exhaust dangerous

More information

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven BULLETIN 456 July 1997 VANEAXIAL FANS Type W Direct Drive/Belt Driven Model VW Direct Drive Model VWBD Belt Driven Aerovent certifies that the Type W Vaneaxial Fans shown herein are licensed to bear the

More information

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Ventilated Balance Enclosures

Ventilated Balance Enclosures Ventilated Balance Enclosures by PLAS n LABS Meets and exceeds ANSI/ASHRAE 110:2016 standard for containment & performance PLAS n LABS, INC. www.plas-labs.com PLI@PLAS-LABS.com 517-372-7177 Ventilated

More information

Proposed Addendum ag to Standard , Ventilation for Acceptable Indoor Air Quality

Proposed Addendum ag to Standard , Ventilation for Acceptable Indoor Air Quality BSR/ASHRAE Addendum ag to ANSI/ASHRAE Standard 62.1-2016 Public Review Draft Proposed Addendum ag to Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality First Public Review (January 2019)

More information

ENVIRO UNIT CES SERIES

ENVIRO UNIT CES SERIES ENVIRO UNIT CES SERIES ENVIRO UNIT FILTER BOX Commercial Kitchen Exhaust CES-ISH 1,000 to 40,000 CFM Operation The grease laden air rises from the cooking equipment into the NFPA- 96 commercial kitchen

More information

Ductless Nanoparticle Containment Enclosures

Ductless Nanoparticle Containment Enclosures Ductless Nanoparticle Containment Enclosures The World s Most Extensive Selection of Ductless Containment Solutions. 24 36 48 Purair P5-24-XT (NANO) Provides Effective Containment for Personnel and Environmental

More information

is with a variety of standard dimensions. Also our units can be custom engineered to any size.

is with a variety of standard dimensions. Also our units can be custom engineered to any size. Bio Safety Cabinet biosafe TM is designed to provide personnel, environmental and product protection. Air flow is drawn around the operator into the front grille of the cabinet, which provides personnel

More information

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Application. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203)

Application. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203) TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2600 SASH SENSING VAV FUME HOOD SYSTEM MODEL 2600: Variable volume control based on sash position utilizes microprocessor based electronics and linear air control

More information

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWUH9 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

Accessories Standard Service Fixture Kits

Accessories Standard Service Fixture Kits Standard Service Fixture Kits For mounting on the left or right side of any Protector Premier, XStream, XL, XLE or PVC Hood. Each kit includes one remotely-controlled service fixture with valve and 0.25"

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -MH and Vektor -MD Mixed Flow High Plume and High Plume Dilution Blower August 2013 Vektor-MH High Plume and High Plume Dilution Blower Greenheck s Vektor-MH high plume

More information

KVL-P with Plate Shelf

KVL-P with Plate Shelf The model of Capture Jet TM hood is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat emitted by cooking equipment, helping to provide a comfortable and clean environment.

More information

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD R CONTENTS MODEL: KYODO / KYODO-R... 1 INTRODUCTION... 1 APPLICATION... 1 VARIABLE AIR VOLUME SYSTEM... 1 FEATURES... 2 MATERIALS... 3 AIR VOLUME CONTROL

More information

Demand Based Static Pressure Reset Control for Laboratories

Demand Based Static Pressure Reset Control for Laboratories Accutrol, LLC Product Sheet Demand Based Static Pressure Reset Control for Laboratories Accutrol, LLC 21 Commerce Drive, Danbury, CT 06810 203-445-9991 www.accutrolllc.com Contents and specifications are

More information

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO ISLAND RANGE HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO

More information

Thermo Scientific 1300 Series A2. Class II, Type A2 Biological Safety Cabinets. Good for you good for the environment

Thermo Scientific 1300 Series A2. Class II, Type A2 Biological Safety Cabinets. Good for you good for the environment Thermo Scientific 1300 Series A2 Class II, Type A2 Biological Safety Cabinets Good for you good for the environment Thermo Scientific 1300 Series A2 Enjoy best-in-class performance and value g Superior

More information

BAC, BAF, BAH Central Station Air Handlers

BAC, BAF, BAH Central Station Air Handlers PRODUCT DATA & INSTALLATION Bulletin B80-BA-PDI-5 Part # 1097717 PRODUCT SUPPORT web: b-rp.ca/bah email: ahu@b-rp.ca call: 1-844-893-3222 x527 scan: BAC, BAF, BAH Central Station Air Handlers Indoor and

More information

LABORATORY FUME HOODS

LABORATORY FUME HOODS Fume Hoods Fume Hood Applications Laboratory professionals and students across the country, and all over the world, depend on the safety of our hoods. Your protection is our first concern and the fume

More information

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile November 204 BCF Centrifugal Cabinet Contents Standard Construction Features... 3 Options and Accessories... 4 Filter and Mixing Box Data... 5 Typical Installations...

More information

CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust

CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust CLAIRE TOTAL SAFETY CABINET TYPE B2 Safe for chemicals due to Total Exhaust 2 BERNER INTERNATIONAL Claire total At a glance CLAIRE TOTAL PRO CHEMISTRY Protection Shield The multiple award-winning Shield

More information

SPECIFICATION SHEET. C5000 ( cfm)

SPECIFICATION SHEET. C5000 ( cfm) (3500 5500 cfm) CASING Double wall cabinet White exterior paint, 22GA steel Galvanized 18GA steel inner wall Access door with ¼ turn handle Insulation : 2 in 18GA Stainless Steel drain pan Drain connection

More information

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules Technical Specification Sheet Document No. 149-855 November 04, 2015 BACnet Lab and Pressurized Room Controllers with Off-board Air Modules NOTE: The 570-8xxPA BACnet laboratory controllers have new 67xx

More information

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS CWSH3 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

KVM KVM. Capture Jet Hybrid Backshelf Hood. Capture Jet TM Hybrid Backshelf Hood

KVM KVM. Capture Jet Hybrid Backshelf Hood. Capture Jet TM Hybrid Backshelf Hood Capture Jet Hybrid Backshelf Hood The hybrid backshelf model of Capture Jet hood is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat emitted by cooking equipment,

More information

High Performance Ductless Balance Enclosures

High Performance Ductless Balance Enclosures High Performance Ductless Balance Enclosures The World s Most Extensive Selection of Ductless Fume Hoods. 24 36 48 Purair 800 795 Also Meets or Exceeds OSHA, ANSI and other International Standards p:2

More information

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets KVR Capture Jet Round Island Hood with Perimeter Jets The KVR Round Island Capture Jet hood with perimeter jets is a highly efficient kitchen ventilation hood that removes contaminated air and excess heat

More information

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING -

More information

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm Product Data 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems 40 to 3700 cfm The 35J retrofit terminal units offer: Unit casing of 22-gage galvanized steel construction (optional

More information

NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues. March 27, 2014

NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues. March 27, 2014 NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues March 27, 2014 0 Moderator Tom Hanlon NEBB s TAB Committee Tom has forty years of experience in refrigeration systems control system

More information

Energy Recovery Laboratory Exhaust

Energy Recovery Laboratory Exhaust Energy Recovery Laboratory Exhaust Model Vektor -ERS For Vektor-M, MH and MS Systems January 2018 Model Vektor -ERS Greenheck s Vektor -ERS is a pre-engineered laboratory exhaust energy recovery system.

More information

Introduction to Johnson Controls Dampers

Introduction to Johnson Controls Dampers Damper and Actuator Product Guide 268.1 Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader

More information

Cytotoxic Safety Cabinets ENVAIR eco safe Plus

Cytotoxic Safety Cabinets ENVAIR eco safe Plus Cytotoxic Safety Cabinets ENVAIR eco safe Plus Class Cytotoxic Standard Width (m) II Safety EN 12469 0.9 / 1.2 Cabinet DIN 12980 1.5 / 1.8 Clean technology for a clean environment ENVAIR eco safe Plus

More information

LABORATORY FUME HOODS

LABORATORY FUME HOODS Fume Hoods Fume Hood Applications Laboratory professionals and students across the country, and all over the world, depend on the safety of our hoods. Your protection is our first concern and the fume

More information

Centrifugal Inline Fans

Centrifugal Inline Fans Centrifugal Inline Fans Models SQ-M and SQ-M Direct and elt Drive UILDING VLUE IN IR. February January 2018 2017 Models SQ-M & SQ-M Centrifugal Square Inline Duct Fans Designed for indoor and outdoor clean

More information

Protector XStream Laboratory Hoods

Protector XStream Laboratory Hoods High Performance Hood offers enhanced containment combined with energy savings. With its unsurpassed containment and substantial energy savings potential, the patented* Protector XStream Fume Hood delivers

More information

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS ZTH WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD

INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES WALL MOUNT HOOD WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS JCH/C2 DESIGNER SERIES

More information

Ductless Nanoparticle Containment Enclosures

Ductless Nanoparticle Containment Enclosures Ductless Nanoparticle Containment Enclosures The World s Most Extensive Selection of Ductless Containment Solutions. 24 36 48 Purair P5-24-XT (NANO) Provides Effective Containment for Personnel and Environmental

More information

Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust XRUB, XRUD, XSEB, XSED, and XRUBS models are listed for electrical (UL/C-UL US 705) File no. E40001 and for grease removal (UL/C-UL US 762) File no. MH11745. Accurex, LLC certifies model XRUB, XRUD, XSEB,

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

Central Station Air-Handling Units

Central Station Air-Handling Units 2008 STANDARD FOR Standard 430 Central Station Air-Handling Units ISHRAE ( INDIAN SOCIETY OF HEATING, REFRIGERATING & AIR CONDITIONING ENGINEERS 4100 N. FAIRFAX DR., STE. 200 ARLINGTON, VIRGINIA 22203

More information

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07 belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07 model vp - belt drive utility set Application VENT-PAK fan wheels are the versatile, quiet, energy efficiency backward inclined

More information