1 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATION FOR 66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED) GETCO/E/06TS CB/R3 May12 Page 1 of 26
2 SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. In absence of this, the evaluation shall be carried out accordingly as non-submission of type test reports. 4. The bidder must fill up all the points of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure. Page 2 of 26
3 QUALIFYING REQUIREMENT DATA (For Supply) Bidder to satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be FIVE times tender/ bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPPL IED TO ORDER REFEREN CE No. & DATE ITEMS QUANTITY ORDER FULLY EXECUTED. YES/NO STATUS, IF ORDER UNDER EXECUTION REMARK e) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / or EN by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification. The type test reports shall not be older than FIVE years and shall be valid up to expiry of validity of offer. Page 3 of 26
4 TECHNICAL SPECIFICATION FOR 66 kv SF6 GAS CIRCUIT BREAKER SECTION I GENERAL TECHNICAL REQUIREMENTS 1.1 SCOPE This section covers the design, manufacture, testing, inspection, supply and delivery of 66 kv SF6 gas Circuit Breakers SPRING operated, along with associated accessories and complete in all respects specified in the schedule of requirements. 1.2 APPLICABLE STANDARDS The equipment to be supplied under this specification shall conform to the latest issue of standards, rules and codes some of which are mentioned below. 1. IEC-62271/ IS Specification for alternating current Circuit breaker 2. IEC Specification and acceptance of new Supply of sulfur Hexafluoride. 3. IS 2147 Degree of protection provided for Enclosures for low voltage switchgear and control gear. 4. IS 375 Marking and arrangement for switchgear busbar, main connections and auxiliary wiring. 5. IS 325 Specification for 3ph induction motor. 6. IS 2516 Specification for circuit breaker. 7. IS 2099 High voltage porcelain bushing. 9. IS 2629 Recommended practice for hot dip galvanizing of iron and steel. The components & accessories to be used in the manufacture of circuit breaker shall conform to relevant Indian Standards/the standard specified under respective clause in this specification. However, in the event the offered breakers confirming to any other standard, salient points of differences between the standard adopted and the specified standards shall be clearly indicated in the offer. Page 4 of 26
5 1.3 DRAWINGS/DOCUMENTS The bidder shall furnish the drawings in triplicate incorporating the following particulars. a) Drawing showing the general outlines dimensions of circuit breakers, with clear identification of parts / items. b) Drawing showing control cabinets and circuit diagrams for operating mechanism of circuit breakers. c) Drawing showing the complete operation cycle of the circuit breaker with description. d) Compression type terminal connectors for the breakers. e) All the documents required shall be submitted over and above as indicated in Section - V of the specification The Bidder shall submit the following drawings within 15 days from the date of receipt of clear order - a) Outline dimensional drawings showing all parts / items, transport weight etc. of circuit breaker & its support structure. b) Detailed drawings of operating mechanism of circuit breakers. c) Wiring and control diagram. d) Drawings of foundation details, mounting structures, spacing of bolts etc. e) Compression type terminal connectors, with STC rating, bill of materials, etc., complete with all dimensions. f) MQP, FQP, erection, operation & maintenance manuals The bidder may also, submit any other drawings found necessary in addition to the drawings stated above GENERAL DESIGN FEATURES OF CIRCUIT BREAKERS The circuit breakers shall be capable of rapid and smooth interruption of currents under all conditions completely suppressing all undesirable phenomena even under the most severe and persistent short circuit conditions or when interrupting small currents or leading or lagging reactive currents. The circuit breakers shall be Restrike-Free under all operating conditions. The details of any device incorporated to limit or control the rate of rise of restriking voltage across, the circuit breaker contacts shall be stated. The over voltages caused by circuit breaker while switching inductive or capacitive loads shall not exceed 2.5 times the highest phase to neutral voltage. The actual make and break times for the circuit breakers throughout the ranges of their operating duties shall be stated in the offer and guaranteed The arc quenching chambers shall have devices to ensure almost uniform distribution of voltage across the interrupters. Page 5 of 26
6 Breaking Capacity The interrupting capacity of the breaker for kilometric faults (short line faults) shall be equal to its interrupting capacity as per IS / IEC and shall be stated in the tender. The details of tests conducted for confirming the capability of the breakers under kilometric fault conditions shall be furnished in the offer The circuit breakers shall be designed for interrupting line charging currents without undue rise in the voltage on supply side and without any restrike and without showing signs of undue strain. The guaranteed over voltage which shall not be exceeded while interrupting the line charging currents as specified under the Clause of Section-II of this specification shall be stated in the offer The circuit breakers shall be capable of interrupting small inductive currents (occurring while switching off unloaded transformer) without giving rise to undue over voltage and without restrikes. The maximum over voltage value which will not be exceeded under such conditions shall be stated in the offer, and in conformity to this, test reports along with oscillograph shall be furnished in the offer Restriking Voltage The circuit breakers shall be capable of interrupting the rated power when the restriking voltage has a frequency of not less than 400 Hz and with a restriking voltage having frequency of 2000 Hz. The circuit breakers shall be capable of interrupting at least 50% of nominal breaking capacity The measures adopted for ensuring proper operation at high rate of rise of restriking voltage and for limiting the actual voltage values across the breaks shall be described in the tender. The type characteristics and rating of the resistor used, if any, to shunt the breaker contacts and of the auxiliary switching devices used for interrupting the resistor current shall be clearly stated Recovery voltage and power Factor The circuit breaker shall be capable of interrupting the rated power with recovery voltage equal to the rated maximum line to line service voltage at rated frequency and at a power factor not exceeding The circuit breakers shall also be capable of satisfactory operation even under conditions of phase opposition that may arise due to faulty synchronizing. The maximum power which the breaker can satisfactorily interrupt under phase opposition shall be stated in the offer. Page 6 of 26
7 The operating duty of the circuit breaker shall be as specified under Clause of specific technical requirement for breakers Temperature Rise The temperature rise and the maximum temperature on any part of the breaker when in service under continuous full load conditions and exposed continuously to the direct sun-rays shall not exceed the permissible limits as per relevant ISS. When the standard specifies the limits of temperature rise, this shall not be exceeded when corrected for the difference between ambient temperature at site and the ambient temperature specified in the relevant specification. The correction proposed shall be stated in offer and shall be subject to the approval of the purchaser General Features of Circuit Breakers The circuit breakers shall be suitable for outdoor operation under the climatic conditions specified in section-ii of this specification (a) The circuit breakers operating mechanism shall have two nos. of tripping coils and one no. of closing coil for both 66 kv SF6 Gas CB for better reliability. There shall be separate contactor for each coil Exposed live parts shall be placed high enough above ground to meet the requirements of local safety codes All similar parts, particularly removable one and shall be interchangeable with one another Insulation of the Circuit Breaker The insulation to ground, the insulation between open contacts and the insulation between phases of the completely assembled circuit breaker shall capable of withstanding satisfactorily die-electric test voltages corresponding to BIL specified in Clause of this specification (a) 1.4.5(b) The minimum clearances in open air shall be as under in case of SF-6 Breakers Minimum clearance between phase As per relevant IS. Minimum clearance between live parts As per relevant IS. and grounded objects. Adequate clearance in air shall be provided between phase and from phase to ground. The clearance shall be such that the breaker shall withstand the BIL specified in the specification. The minimum clearance from live parts to ground level shall not be less than 4000 mm including plinth height as 300 mm. Page 7 of 26
8 1.4.6 Contacts of Circuit Breaker The main contacts shall have adequate area and contact pressure for carrying the rated currents and the short time rated breaking currents of the breaker without excessive temperature rise. Contacts shall be easily replaceable and shall have a minimum of movable parts and adjustments. The main contacts shall be first to open and last to close so that burning of the contact may be negligible Operating Mechanism of Circuit Breakers Circuit breakers shall be power operated by a motor compressed spring charging mechanism; the mechanism will be trip-free electrically and mechanically. The mechanism shall be strong, quick in action and shall be removable without disturbing other parts of the circuit breakers. All the working parts in the mechanism shall be of corrosion resistant materials and all bearings which require greasing, shall be equipped with pressure grease fittings. The mechanism and breaker shall be such that the failure of any spring will not prevent tripping and will not cause tripping or closing The circuit breakers shall be designed for remote control from the control room and there shall be provision for manual operation of circuit breakers during maintenance and for local tripping and closing by normal means The circuit breaker shall have a mechanical ON-OFF indicator in addition to facilities for remote electrical indicator The operating mechanism along with its accessories shall be suitable for electrical operation and shall be mounted in a weather proof cabinet with hinged doors located near the breakers. The cabinet shall be suitable for IP 55 degree of protection. The operation shall be possible from ground or necessary HDG stand/platform of suitable height maintaining all safety clearance with live parts shall be supplied as a part of breaker. The local control switch and the breaker position indicator shall be provided in this cabinet, which shall be free standing and supported by suitable arrangement. The control circuit shall be designed to operate on D.C. as specified in section-ii of this specification. The closing and opening coils shall be designed to operate satisfactorily at any control voltage from 85% to 110% & 70% to 110% of the normal voltage, respectively. A heater of adequate capacity with thermostat shall be provided in the cabinet to avoid moisture condensation (a) The terminal block shall of 1.1 KV voltage grade & shall be with stud type connections instead of with screw types connections. Page 8 of 26
9 1.4.8 Auxiliary switches A minimum number of 6 NC + 6 NO Auxiliary switches contacts shall be provided on each circuit breaker for use in remote indication control scheme of the circular breakers and for safety interlocking. Special contacts for use with trip coils and auto reclosing operation shall also be provided. Provision shall be made for adding more auxiliary switches, if required. Auxiliary switches shall be placed in weatherproof galvanized casing and current rating of switches shall be mentioned in the offer. 1.5 BUSHING & INSULATORS The porcelain insulator used in manufacturing the bushings shall be homogeneous, free from laminations, cavities and other flaws or imperfection that might affect the mechanical or dielectric qualities. All bushings of identical ratings shall be interchangeable. The insulators shall conform to the latest edition of IS 3447 or other equivalent standard. The puncture strengths of the bushings shall be greater than their flashover values. The bushings shall be entirely free from external and internal corona. The protected and total creepage distance of the bushings shall be suitable for heavily polluted atmosphere. The minimum creepage distance of the insulator shall be 1810 mm suitable for heaving polluted atmosphere. The compressive and cantilever strength shall conform to the relevant IS. 1.6 TERMINAL CONNECTORS AND EARTHING TERMINALS Compression joint type terminal connectors suitable for single or twin ACSR panther/zebra/moose as indicated in Schedule A of respective tender, shall be supplied and they shall be suitable for both vertical and horizontal connections of the Transmission line conductor or station bus bar. Suitable terminal earth connectors (two Nos.) for earthing connections shall also be supplied. The drawings for these connectors shall be submitted. SS bolt for connector shall be provided with two Nos. of SS nuts (including lock nut & one SS washer. 1.7 TROPICALISATION All control wiring, electric motors and accessories shall be protected against fungus growth and other harmful effects due to tropical environments. 1.8 GALVANIZING Page 9 of 26
10 1.8.1 All ferrous parts of breakers and bolts, nuts etc. shall be hot-dip galvanized as per latest edition of IS Support structure s galvanizing shall be done as per IS 4843 (latest edition). Electro galvanized bolts nuts, & washers are also acceptable. 1.9 PAINTING Interior and exteriors of tanks, mechanisms, enclosures, cabinets and other metal parts shall be thoroughly cleaned to remove all rust scales, corrosion and other adhering foreign matter, steel surfaces in contacts with insulation oil, as far as possible shall be painting with not less than two coats of heat resistant, oil insoluble, insulating varnish light-grey paint shade 631 as per IS5 shall be selected to withstand tropical heat and extremes of weather TEST AND TEST REPORTS Reports of following type tests carried out in NABL / Govt. approved laboratory within five years prior to expiry of validity of offer, as per IS / IEC for A C circuit breakers shall be submitted along with the offer (i) Lightning impulse withstand voltage test (ii) Power frequency voltage withstand voltage test. (Dry as well as Wet) (iii) Temperature rise test. (iv) Measurement of resistance of main circuit (v) Short time current withstand and peak current withstand Test (vi) Mechanical endurance test (vii) Duty cycle & Single phase short circuit test. (viii) Out of phase making and breaking current test. (ix) Capacitor current switching test for isolated neutral capacitor banks. (x) Line charging current switching test (xi) Cable charging current switching test (xii) Short line fault duty test (xiii) Degree of protection test on cubicles IMPORTANT NOTE In case of non-submission of some of the type test reports, the bidder shall confirm the submission of same before commencement of supply, without affecting delivery schedule, from NABL accredited laboratory, free of cost. In absence of this confirmation, the offer will be evaluated as non submission of type test report Routine tests as per the latest edition of IS 13118/IEC for circuit breakers shall be carried out on each circuit breaker. All the acceptance tests in presence of GETCO representative shall be carried out on circuit breakers selected from offered lot. Page 10 of 26
11 In addition to above, speed curves for each breaker shall be obtained with the help of a suitable operation analyzer to determine the breaker contact movement during opening, closing, auto-re-closing and trip free operations under normal as well as limiting operating conditions (of control voltage) The tests shall show the speed of contacts directly at various stages of operation, travel of contacts, opening time, closing time, shortest time between separation and meeting of contacts at make-break operation and dynamic contact resistance measurement (DCRM) etc The test reports for type tests and routine tests in respect of associated items such as spring charging motors, instruments, pressure switches, relays, terminal connectors, etc. as per the latest edition of the relevant IS shall be supplied by the bidder. All the routine test reports for all the breakers and for all the insulators utilized shall be submitted with inspection report All tests reports for acceptance / routine tests shall be submitted in spiral bound volume and got approved from the purchaser before dispatching the breaker SPARE PARTS Bidder shall submit list of spares recommended by him for satisfactory operation of the circuit breakers for first five years and rate for each spare shall also be quoted. The purchaser will decide the actual quantity of spare parts to be ordered on the basis of the prices of the spare parts, quoted by the bidder TECHNICAL & GUARANTEED PARTICULARS The bidder shall furnish all guaranteed technical particulars as called for in section - IV of this specification. Particulars which are subject to guarantee shall be clearly stated offers not containing this information will not be considered. Deviation against any clause of this technical specification shall be clearly described separately INSTRUCTION MANUALS Three copies of operation, maintenance and erection manuals in English language shall be provided in each circuit breaker supplied. The manuals shall be bound volumes and shall contain all the drawings and instructions required for erection, operation and maintenance and in addition the following particulars Page 11 of 26
12 a) Marked erection prints identifying the component parts of the circuit breakers and current transformers as dispatched with the assembly drawings. b) Details dimensions, assembly and description of all the components and catalogues for operation of the circuit breaker and accessories. c) List of recommended spare parts of circuit breaker. Page 12 of 26
13 2.1 SCOPE TECHNICAL SPECIFICATION FOR 66 kv SF6 GAS CIRCUIT BREAKER SECTION II TECHNICAL REQUIREMENTS This section covers the specific technical requirements, climatic and Isoceraunic conditions and system particulars for which the circuit breakers shall be offered as per the General Technical Requirements given in Section-I of this specification and the schedule of requirements specified herein. 2.2 CLIMATIC & ISOKERAUNIC CONDITIONS The climatic conditions under which the breaker shall operate satisfactorily are as follows a) Maximum ambient temperature of air in shade ( 0 C). b) Minimum ambient temperature of air in shade ( 0 C). c) Maximum daily average ambient temperature ( 0 C). d) Maximum yearly average ambient temperature ( 0 C) C 4 0 C 40 0 C 30 0 C e) Maximum relative humidity (%). 95 % f) Average number of thunderstorm days / annum. 15 g) Average annual rainfall (Cm.) 150 cm. h) Maximum wind pressure (Kg/m2) 150 kg/m 2. i) Height above mean see level (m). Not exceeding 1000 meters. Page 13 of 26
14 2.2.2 All breakers offered shall be suitable for continuous satisfactory operation at the full rated capacity under the above climatic conditions Since the sub-station may be near seashore or Industrial area, the breaker offered shall be suitable for heavily polluted atmosphere. 2.3 SYSTEM DETAILS i) Nominal system voltage 66 kv ii) Maximum rated voltage 72.5 kv iii) Frequency 50 Cycle / Second. iv) Number of phases 3 v) Neutral Earthing Solidly earthed. vi) Auxiliary power supply 1) 240 Volts 1-φ & 415 Volts 3-φ, 50 Hz A.C., with the variation of frequency ± 5% and voltage + 10% & -15%. 2) 110 Volts or 220 Volts 2-wire D.C. supply subject to variations of ± 10%. 2.4 The circuit breakers shall be complete with following technical requirements. 11) Number of Poles 3 2) Basic Insulation level 1) 1.2/50 Microsecond impulse withstand voltage. 2) On Minute Power Frequency withstand voltage. 350 kvp 140 kv rms 3) Rated normal current 1600 Amps. 3a) Rated symmetrical breaking capacity at highest system voltage MVA Page 14 of 26
15 4) Rated short circuit breaking capacity ka rms 5) Rated duration of short circuit 3 second. 6) Total break time for any current upto the rated breaking current. 3 cycles 7) Closing time. Not more than 10 cycles. 8) Rated characteristics for short line faults 9) Rated transient recovery voltage for terminal fault. 10) Rated line charging current breaking capacity. 11) Rated short circuit making current. As per IS / IEC As per IS / IEC Amps kap 12) Rated operating duty O 0.3 S CO 3 M CO 13) Rated SF6 Gas pressure (AT 20 0 C). 14) Total creepage distance for heavily polluted atmosphere. 15) Live part to plinth level clearance in mm 2.5 EARTH QUAKE & WIND DESIGN LOADS 5 kg / Cm mm min mm Each circuit breaker including its supporting structure shall be designed to withstand required earthquake acceleration of 0.08 x 2 g and with wind loads of 150 Kg/m2 on the projected area (nonsimultaneous) without damage to component parts and without impairment of operation. Page 15 of 26
16 TECHNICAL SPECIFICATION FOR 66 kv SF6 GAS CIRCUIT BREAKER SECTION III GENERAL DESIGN OF 66 kv SF6 GAS CIRCUIT BREAKER 3.2 GENERAL DESIGN FEATURE OF SF6 BREAKER SF6 Gas Circuit breaker shall consist of three identical single phase units with common Spring operating mechanism suitable for specified duty. Separate SF6 Gas Cylinder along with suitable gas system, incorporating required gas stop valves, copper piping of suitable size shall be provided. Required pressure switches as stated in Cl shall be provided. Gas pressure gauge shall be fitted on the common feed pipe to monitor the pressure of SF6 gas in the interrupter. Absorbent shall also be provided in each interrupting unit to keep the SF6 gas dry & absorb the decomposed product of SF6 gas, formed during arcing. Bidder shall give complete constructional details for SF6 gas circuit breaker offered by them. The insulation level of porcelain of the circuit breaker shall be so coordinated with that of the breaker that flashover shall occur externally to the breaker In case of SF6 circuit breaker, it shall be possible to arrange for either automatic tripping of the circuit breaker or tripping of circuit breaker on fault and will be automatically locked when the pressure in the individual interrupter reaches below the limit value. Arrangements shall be made to prevent closing of the breaker due to leakage of gas passing through the closing valve without a positive impulse from the closing coil The SF6 gas used in the circuit Breaker shall comply in all respect with the provisions of the latest edition of relevant standard Inter Locks 3.2.4(a) Pressure switches with the required pressure fitting must be incorporated to ensure safety of breaker operation when SF6 gas Page 16 of 26
17 pressure goes below the specified pressure range due to leakage, the trip coil circuit & closing coil circuit must be cut-off. The pressure switch shall generally be temperature compensated gas pressure switch having two micro-switches, operating at different pressures one for low pressure alarm and other for low pressure cutout (b) Additional dedicated pressure switch with 4 poles for Normal, Low gas, Lockout, etc shall be provided for SCADA remote operations. L/R switch shall have spare contacts (c) Limit switch for motors shall be provided with 4 NO and 4 NC contacts. Page 17 of 26
18 SECTION IV SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 66KV SF-6 GAS Spring operated CIRCUIT BREAKERS (TO BE FILLED IN & SIGNED BY THE BIDDER) SN PARTICULARS 1. Name of Manufacturer 2. 2.a Type Designation of CB Type designation of Spring mechanism (as per Mech. Endu. test report) 3. Governing Standard 4. Rated Voltage (KV) 5. Maximum continuous rated service voltage (KV) 6. Frequency (Hz) 7. Whether outdoor breaker offered (Yes / No) 8. Nominal current rating i) Under standard condition. (Amp) ii) Under site condition (Amp). iii) Type test reports submitted of (Amp) 9. Short time current rating (ka) for 3 seconds 10. Maximum temperature rise over ambient temp. due to rated current in main contacts measured after breaking test. ( 0 C) Page 18 of 26
19 SN PARTICULARS 11. Rated short circuit breaking current a) Rated short circuit current (AC component) (KV rms). b) Percentage DC component c) Asymmetrical breaking current (including DC component (KA rms). d) Rated symmetrical breaking capacity in MVA FOR SF6 CB 12. Making capacity (ka Peak) 13. Total breaking time (Milli-seconds) a) For interruption of 10% of the rated capacity. b) For interruption of 30% of the rated capacity. c) For interruption of 60% of rated capacity. d) For interruption of the full rated capacity. 14. Arcing time ( milliseconds) 15a b. c. Making time (milliseconds) Rated closing time (milliseconds) Rated opening time (milliseconds) 16. Minimum reclosing time at rated interrupting capacity from the in fault of the trip coil energisation (Millisecond) Page 19 of 26
20 SN PARTICULARS 17. A) Minimum dead time a) 3 phase reclosing (Milliseconds). b) Limit of adjustment of dead time for 3-phase reclosing. B) Whether restrike free and trip free. (IS / IEC applicable may be stated). 18. Date on restriking voltage for 100%, 50% & 30% rated capacity a) Amplitude factor (max) b) Phase factor (max) c) Natural Frequency (Hz) d) Rate of rise of restriking voltage (V/Micro-Sec) (max) 19. Maximum interrupting capacity under phase opposition condition (MVA). 20. Maximum line charging current breaking capacity without over voltage exceeding 2.5phase neutral voltage (Amps.) 21. Maximum line charging current breaking capacity corresponding over-voltage recorded a) On supply side. b) On line side. 22. Maximum cable charging current breaking capacity & corresponding overvoltage recorded in test. a) On supply side. b) On line side. 23. Maximum shunt capacitor Bank switching capacity (MVA) Page 20 of 26
21 SN PARTICULARS 24. Maximum breaking capacity on kilometric fault (MVA) 25. Maximum over-voltage on switching transformers on no load & the charging current. 26. Dry 1 Minute power frequency test withstand voltage, for complete circuit breaker a) Between line & Grounded parts (kv rms) b) Between line with breaker contacts open (kv rms) 27. Wet 1-minute power frequency withstand voltage for complete circuit breaker a) Between line terminal & grounded parts (kv rms) b) Between terminals with breaker contacts open (kv rms) /50 Micro-second wave lightning impulse withstand test voltage for complete circuit breaker, as per type test report submitted. a) Between line terminal and ground (kv peak) b) Between terminal with circuit breaker contacts open (kv peak). SUPPORTING INSULATORS 29. Make & Type 30. Insulation Class 31. Visible Corona discharge voltage 32. Wet 1-minute power frequency flashover voltage (kv rms). Page 21 of 26
22 SN PARTICULARS 33. Dry 1-minute power frequency flashover voltage (kv rms) /50 micro-second impulse flashover voltage (kv peak) 35. Total creepage distance for heavily polluted atmosphere 36. Minimum clearance in air a) Between phases (mm) b) Live parts & earth (mm) c) Live parts to Plinth level (mm). 36.a Permissible safe cantilever loading on installed porcelain (kg.m) 36.b Permissible safe compressive strength of installed porcelain 37. No. of poles per circuit breaker 38. Breaks per pole (Nos). 39. Total length of breaks per phase (mm). 40 Type of main contacts 41. Material of main contacts 42. Whether main contacts silver plates (Yes/No) 43. Thickness of silver coating on main contacts (mm). 44. Contact pressure on main contacts (Kg/M2). 45. Type of arcing contacts 46. Contact pressure on arcing contact (Kg/M2). 47. Type of auxiliary switches Page 22 of 26
23 SN PARTICULARS 48. Material of switch contacts 49. Whether contacts silver plates (Yes/No.) 50. No. of auxiliary switch contacts operating with all three poles of breaker a) Which are closed when breaker is closed. b) Which are open when breaker is closed 51A No. of spare auxiliary switch contacts operating a) Which are closed when breaker is closed. B b) Which are open when breaker is closed. Details of SF6 Gas pressure switch and its setting for low pressure alarm and low pressure cut-out. 52. No. of operations possible without maintenance a) At full rated interrupting capacity. b) At 50% of rated interrupted capacity c) At 100% of rated current d) At 50% of rated current 53. Details of foundation Page 23 of 26
24 SN PARTICULARS 54. Type of operating mechanism (motor operated spring charged). a) Opening b) Closing c) Control voltage aux. 54a Details of spring charging motor i) Type ii) Rated supply voltage iii) Wattage iv) Max time for charging spring 55. Tripping & closing circuit voltage (V). (110 V/220 V.) As per requirement. 56. Power required for trip coil (in watts). 57. Power required for closing coil (in watts). 58. Weight of 3-φ breaker complete with operating mechanism, supporting, insulators, frame work etc. 59. Impact loading for foundation design to include dead load plug impact value on opening it maximum interrupting rating in terms of equivalent static load. 60. Weight of heaviest package (Kgs) space requirements (Length, Width, Height). Page 24 of 26
25 SN PARTICULARS 61. A) Details of Gas pressure switch and its setting for low pressure alarm and low pressure cut-out. 62 SF6 GAS DETAILS a) Rated SF6 Gas pressure (temperature 20 0 C) (Kg/cm 2 ) b) IS / Equivalent standard applicable for SF6 Gas. c) Quantity in each pole d) Total quantity e) Spare gas quantity (%) 63 Terminal connector (Bimetallic compression type) 64 Seismic level (g) SEAL OF THE FIRM SIGNATURE OF TENDERER Page 25 of 26
26 SECTION V List of documents attached with technical bid Bidder shall invariably attach the following documents and clearly marked and duly flagged in technical bid. In absence of these documents offer will be evaluated as a non submission. Sr. No. Particulars of document 1 Drawings in AutoCAD format 2 Drawings hard copies as indicated in specification 3 Manual in PDF format 4 QAP for manufacturing process in SOFT format 5 QAP for manufacturing process in Hard format 6 FQP in SOFT format 7 FQP in Hard copy 8 Type test Reports in hard copies a for breaker b for clamps & connectors 9 Confirmation regarding type tests as per clause no. 1.10(a) page no. 10 IMPORTANT NOTE 10 Guaranteed Technical Particulars, completely filled in 11 Any other essential documents Whether attached the with technical bid SIGNATURE OF BIDDER COMPANY S ROUND SEAL DATE PLACE Page 26 of 26
TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH
TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:
More informationTECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK
TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers
More information023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA
023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationTechnical Specification for 33 KV 200 AMPs,H.G,Fuse set.
Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable
More informationشركة كهرباء محافظة القدس المساهمة المحدودة
Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories
More informationVOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS
VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More information33KV INDOOR SWITCHGEAR
33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More information400 kv SF6 CIRCUIT BREAKERS (with PIR and Spring Spring Mechanism)
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS OF 400 kv SF6 CIRCUIT BREAKERS (with PIR and Spring Spring Mechanism) GETCO/E/4TS
More information017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA
017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality
More informationTECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :
TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break
More informationTECHNICAL SPECIFICATIONS FOR HARDWARE & ACCESSORIES -ACSR DOG CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS FOR HARDWARE & ACCESSORIES -ACSR DOG CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS
More informationTECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:
TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: (1) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in
More informationTechnical Specifications
LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for
More informationTECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES:
TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES: 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break
More informationTechnical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make
Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch 1. Scope:- This specification covers manufacturing, testing and supply of 11KV 200Amp. 50Hz Air Break switches for outdoor installation
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationTECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)
TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop
More informationTECHNICAL SPECIFICATIONS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR SELECTIVE LEVEL METER GETCO/E/TS- PACC SLM 03504/R0, Dt: 2.04.2008 Page
More informationPublication No.: PSG
TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06
More informationSPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. The networks are mainly of outdoor type. The basic parameters are set out below:
SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. A. SYSTEM INFORMATION A-1 System Conditions The networks are mainly of outdoor type. The basic parameters are set out below: Nominal system voltage between
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 110 V, 100 Ah / 250 Ah & 220 V, 250 Ah / 350Ah TUBULAR LEAD ACID BATTERY SETS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 110 V, 100 Ah / 250 Ah & 220 V, 250 Ah / 350Ah TUBULAR LEAD ACID BATTERY
More informationTECHNICAL SPECIFICATION FOR 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER
1. SCOPE : TECHNICAL SPECIFICATION FOR 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER This Specifications intended to cover the design, manufacture, assembly and Testing at manufacturer s works of 33 KV, 3 Ph.,
More informationHARYANA VIDYUT PRASARAN NIGAM LTD.
HARYANA VIDYUT PRASARAN NIGAM LTD. TECHNICAL SPECIFICATION SSD/S-03/R-1/DGM-605 TECHNICAL SPECIFICATION FOR 33 KV CAPACITOR BANKS CHIEF ENGINEER/MM HVPNL, PANCHKULA TELEPHONE & FAX: 0172-2583724 MARCH-2017-0
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE GETCO/E/TS
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS
More informationMGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-
MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- 01) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in 50Hz, 11KV distribution
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GETCO / E / TS- BCHR 3202 / R2 Oct 15 Seal & Sign
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-ACSR PANTHER CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-ACSR PANTHER CONDUCTOR FOR TRANSMISSION LINE GETCO/ENGG/TECH.
More informationSPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /
SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / 2005-06 SR.NO ITEM PAGE 1. SCOPE 2 2. WEATHER CONDITIONS 2 3. RATED VOLTAGE & FREQUENCY 2 4. GENERAL REQUIREMENT
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More information34-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES
More information33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT
33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,
More informationOutdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv
Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationProduct Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationBHARAT HEAVY ELECTRICALS LIMITED, JHANSI
BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause
More informationTechnical Specification
Section - 7 Technical Specification OF 33KV OUTDOOR DROP OUT FUSE CUT-OUT AND FUSE LINK AND 33KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER 84 7.1. TECHNICAL SPECIFICATION OF
More information(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB
Annexure-V (Under Two Part Bid System) Tender No: NFV/ PUR/ BEC 160546 K for VCB Technical specification for NIT SL NO 1 S.No. Description NFL requirement as per NIT Vendors Comment [Agreed / If not agreed,
More informationMV Air Insulated Switchgear TAP17. Technical Data TGOOD
MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)
More informationTECHNICAL SPECIFICATION
SECTION - III TECHNICAL SPECIFICATION OF AB SWITCH & HG FUSE NESCO : TN/ 17427/14.11.11-1 - 1. 33 KV 200 Amp 3 Pole HG Fuse (Horizontal Mounting Type) Quantity 15 Sets Technical Specification 1. SCOPE:
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax
More information(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:
10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1
More informationDakshin Gujarat Vij Company Limited
Dakshin Gujarat Vij Company Limited CIN U40102GJ2003SGCO42909 Regd. & Corporate Office: Urja Sadan, Nana Varachha Road, Kapodara Char Rasta,Surat 395 006 C & R DEPARTMENT Phone No.: 0261 2506100-200-175
More information: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS :
: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : FOREWORD : Even though 11KV Drop Cut Fuse Cut Outs are widely used for protection / isolation of distribution transformers, their quality
More informationProduct Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More informationBHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2
BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002
More informationEMPAC Metal enclosed capacitor bank for wind applications
EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS FOR
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 11 kv Indoor VCB SWITCHGEAR PANEL/BOARD GETCO / E / TS HTPB 5401 / R0
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES TWIN AL59 CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES TWIN AL59 CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS
More informationHigh-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
More informationOutdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications
Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers
More information43-SDMS-04 REV. 00 SPECIFICATIONS FOR
43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR 400 KV TRANSMISSION LINE WITH QUAD ACSR MOOSE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR 400 KV TRANSMISSION LINE
More informationWESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2
Sl. No. WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO GUARANTEED TECHNICAL PARTICULARS 1 of 2 REQUIREMENTS 11 Kv, 200 Amps, A.B Switches. Particulars 1 Maker's name and Country of origin. 2 Type
More informationANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.
ANNEXURE XI (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. Sr. No Technical Particulars Confirmation to be given by bidder (Please strike out which ever not applicable)
More informationNLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX
NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More information43-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3
More informationWEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A
Technical Specification Of 12KV, 400A, 18.4 KA Floor Mounted totally enclosed Ring Main Unit consisting of 2 nos. Vacuum Interrupting Incoming Unit and one no. Series Trip Metering Switchgear with Vacuum
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:
More information34-SDMS-02 SPECIFICATIONS FOR
SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE
More informationOutdoor vacuum breaker for railway applications - FSK II
Outdoor vacuum breaker for railway applications - FSK II Single or two-pole outdoor vacuum breaker with magnetic actuator 27.5 kv - 250 kv BIL - 1250 A. 2000 A - 25.0 ka - 50/60 Hz 27.5 kv - 200 kv BIL
More informationREFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS
TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3
More informationCIRCUIT BREAKER. March 2015 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
CIRCUIT BREAKER March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationAmendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV).
Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Sr. No. Clause No Existing Proposed 1 8.0 Dischar ge device 2 15.0
More informationBHAVNAGAR ENERGY CORPORATION LIMITED 2X250 MW CFBC LIGNITE BASED TPP
BHAVNAGAR ENERGY CORPORATION LIMITED 2X250 MW CFBC LIGNITE BASED TPP VOLUME - IIB TECHNICAL SPECIFICATION FOR SPECIFICATION NO.: PE-TS-356-510-E001 (REV. 00) BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR
More informationTechnical Specification of GECOL. Packaged Transformers
GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...
More informationTECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY.
TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY. 1.0 SCOPE: This specification covers the design, manufacturing and testing of LT Distribution
More informationCP Automatic capacitor bank
CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor
More informationPantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance
Pantograph disconnector type GW54, up to 550 kv Maximum reliability and minimal maintenance Table of contents 02 03 04 05 06 07 08 Disconnectors from ABB Maximum reliability and minimal maintenance Technical
More informationAF series contactors (9 2650)
R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00
More informationTechnical Specification for 11 kv Outdoor Circuit Breaker
WESCO ( APDRP Scheme) Technical Specification for 11 Outdoor Circuit Breaker - 1 - TABLE OF CONTENTS PART 1: GENERAL 1. SCOPE...4 2. STANDARDS...5 3. SERVICE CONDITIONS...6 4. SYSTEM CONDITIONS...7 5.
More informationDATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT
44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7
More information026-2 : 1996 CEB STANDARD
026-2 : 1996 CEB STANDARD COMPRESSION CONNECTORS & TERMINATIONS FOR OVERHEAD LINE CONDUCTORS CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable
More informationSION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG
Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.0 008 Answers for energy. R-HG11-17.tif Siemens HG 11.0 008 Contents Contents Page SION Vacuum Circuit-Breakers Description General Construction
More informationWest Bengal State Electricity Distribution Co. Ltd.
West Bengal State Electricity Distribution Co. Ltd. TECHNICAL SPECIFICATIONS FOR D. C. DISTRIBUTION BOARD (FOR 33 KV SUB STATIONS) Page 1 of 14 1.0 SCOPE: This specification covers the design, manufacturing,
More informationComparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010
1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,
More informationSECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENT AND QUANTITIES
Tamil Nadu Transmission Corporation Limited Bharat Heavy Electricals Limited 400/110 KV Substation at Thappagundu & 400/230-110 KV Substation at Anikadavu, Technical specification for 420/245/132kV Isolators
More informationSPECIFICATION FOR HARDWARE FITTINGS SUITABLE FOR TENSION STRING TO BE USED FOR 11KV/22KV LINE
SPECIFICATION FOR HARDWARE FITTINGS SUITABLE FOR TENSION STRING TO BE USED FOR 11KV/22KV LINE The hardware fittings suitable for tension string to be used for 11KV / 22 KV consisting of following components.
More informationWESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA WESCO ( APDRP Scheme ) Technical Specification for 33 kv Outdoor Circuit Breaker
Technical Specification for 33 Outdoor Circuit Breaker TABLE OF CONTENTS PART 1: GENERAL 1. SCOPE... 5 2. STANDARDS... 6 3. SERVICE CONDITIONS... 7 4. SYSTEM CONDITIONS... 8 PART 2: TECHNICAL 5. BASIC
More information400 kv / 220 kv / 132 kv / 66 kv GAS INSULATED SWITCHGEAR (GIS)
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 400 kv / 220 kv / 132 kv / 66 kv GAS INSULATED SWITCHGEAR (GIS) GETCO/
More informationSPECIFICATIONS FOR 50 V, 600 AH LEAD ACID BATTERY
(I) INTRODUCTION: Power Line Carrier Communication (PLCC) System is being used by Gujarat Energy Transmission Corporation Ltd. for Speech, Data, Protection and Teleprinter signal transmission purpose throughout
More informationThe vacuum circuit breaker for commercial buildings, industrial plants and utilities
The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationSF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314
More informationTENDER NO. MGVCL / PP / D2 / 4017/Metal LTDB
200 KVA L.T. DISTRIBUTION BOX WITH ACB DETAILED TECHNICAL SPECIFICATIONS(Metal Made) Specification for 200 KVA L.T. Distribution Boxes with ACBs on outgoing and incoming side: 1. SCOPE: This specification
More informationSPECIFICATIONS OF REWIRABLE KIT KAT FUSES
SPECIFICATIONS OF REWIRABLE KIT KAT FUSES 1. SCOPE: This application cover the manufacture, testing at works and supply of porcelain rewire able kit kat fuses suitable for AC 3 phase 415 V 50 HZ solidly
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationINTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)
INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements
More information