GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS FOR

Size: px
Start display at page:

Download "GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS FOR"

Transcription

1 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS FOR 11 kv Indoor VCB SWITCHGEAR PANEL/BOARD GETCO / E / TS HTPB 5401 / R0 Dt Seal and Sign of Bidder Page 1 of 26

2 SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan for manufacturing process and Field Quality Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. In case of non-submission of the type test reports with the offer, the bid shall be liable to be rejected. 4. The bidder must fill up all the point of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure. 9. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). Seal and Sign of Bidder Page 2 of 26

3 QUALIFYING REQUIREMENT DATA (For Supply) Bidder to satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be 5 times tender / bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPPLIED TO ORDER REFERENCE No. & DATE ITEMS QUANTITY ORDER FULLY EXECUTED. YES/NO STATUS, IF ORDER UNDER EXECUTION REMARK 5) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / or EN by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification, valid for a period of FIVE years from the date of validity of technical bid. Seal and Sign of Bidder Page 3 of 26

4 TECHNICAL SPECIFICATION FOR 11 KV INDOOR PANEL / SWITCH BOARD WITH VCB 1.1 SCOPE The 11 kv Switch boards shall fully meet with the technical, climatic, isoceraunic and system conditions given in this specification, for indoor installation. 1.2 CLIMATIC & ISOCERAUNIC CONDITIONS The climatic conditions at site under which the equipment shall operate satisfactorily are as follows: (a) Maximum ambient temperature 50 of the air in shade ( 0 C) (b) Minimum ambient temperature 4 of the air in shade ( 0 C) (c) Maximum daily average 40 ambient temperature ( 0 C) (d) Minimum yearly average 30 ambient temperature ( 0 C) (e) Maximum relative humidity (%) 95 (f) Average number of thunder-storm 15 days per annum (g) Average annual rainfall (cm) 115 (h) Maximum wind pressure (Kg/m 2 ) 150 (i) Earthquake acceleration (g) 0.08 x 2 g. (j) Height above mean sea level (m) Not exceeding The equipment offered shall be suitable for continuous operation at the full rated capacity under the above conditions Since the sub-stations are near the seashore or in an industrial area, the equipment offered shall be suitable, for heavily polluted atmosphere. 1.3 TECHNICAL AND SYSTEM CONDITIONS SYSTEM CONDITIONS 11 kv switchgear equipment and accessories shall comply with the following system conditions: (a) Nominal system voltage (kv) 11 (b) Highest system voltage (kv) 12 (c) System earthing Effectively earthed (d) Number of phases 3 (e) Rated Frequency (Hz) 50 (f) Basic Insulation level Seal and Sign of Bidder Page 4 of 26

5 (i) 1.2 x 50 micro second impulse 75 withstand voltage (in KV peak) (ii) One minute power frequency 28 withstand voltage (KV rms) TECHNICAL REQUIREMENT CIRCUIT BREAKERS The circuit breakers shall comply with the following technical requirements: (a) Type Indoor drawout (b) Insulating Medium Vacuum (c) Breaking capacity 500 MVA (d) Rated normal current of breakers (Amp) 1250/1600 (e) Bus-bar Rating (Amp) 1600 (f) (i) Rated short time current (KA RMS) 25 (ii) Rated time (Sec.) 3 (g) Operating duty cycle Sec - Co - 3 Min.-Co. (h) Method of closing (i) Normal Motor operated (ii) Emergency Manual (i) Auxiliary voltage for closing 110 V DC and tripping coils (j) Auxiliary voltage for spring 240 V, AC, 50 Hz charging motor with voltage variation +10% and 15% of normal value and frequency variation ± 3% (k) Size of bus bar 1500mm 2 (preferably 2x75x10mm) GERNERAL REQUIRMENTS OF C.B. The circuit breakers shall comply with the requirements of the latest edition of IS: 13118/1991 or IEC except where specified, otherwise in the specification. The circuit breakers shall be with vacuum insulating medium and shall be indoor, floor mounting, draw out type. They should be complete with raising and lowering mechanism, transportation truck, isolating plugs and spouts with automatic metallic gravity fall type safety shutters, padlocking arrangements and necessary mechanical interlocks. They shall be incorporated in panel boards described in clause of this specification The circuit breaker shall be capable of rapid and smooth interruption of currents under all conditions, completely suppressing all undesirable phenomena even under the most severe and persistent short circuit conditions or during capacitor switching operations. There shall be no re-striking, no abnormal voltage and Seal and Sign of Bidder Page 5 of 26

6 no high frequency current, generating consequent to switching of the capacitor banks. The details of any devices incorporated to limit or control the rate of rise of re-striking voltage across the circuit breaker contacts shall be stated. The over voltage caused by circuit breaker while switching inductive or capacitive loads shall not exceed 2.5 times the highest phase to neutral voltage. The actual make and break times of the circuit breakers throughout the ranges of their operating duties shall be stated in the tender and guaranteed The circuit breaker shall be trip free only The symmetrical breaking capacity of the breaker shall be 500 MVA, which shall remain constant within the limits of the two rated voltages specified in this specification. For voltages lower than the rated voltage, the breaking current shall remain constant The relation between current and time shall be maintained in accordance with the formula I 2 t = constant, when short circuit duration exceed one second The temperature rise and maximum temperature on any part of the circuit breaker, while in service under continuous full load conditions shall not exceed the permissible limits of temperature rise as specified in the IEC-694:1996 publication for alternating current circuit breakers with bolted type silver plated bus bars, jumpers & riser ends. Gaskets shall be of a material which will not deteriorate under service conditions. Metallic compression steps shall be provided for compressible gasket Main contacts shall have ample area and contacts pressure for carrying the rated current and the short time rated tripping current of the breakers without excessive temperature rise which may cause pitting or welding. Contacts shall be adjustable to allow for wear and shall be easily replaceable and shall have a minimum of moveable parts. The main contacts shall be the first to open and in the last to close so that there will be little burning and wear of the contacts. Acing contacts if provided shall be the first to close and last to open and shall be easily accessible for inspection and replacement. Tips of arcing and main contacts shall be suitably silver plated or have a tungsten alloy tipping. The moving contact shall have a permanent marking or scale other means shall be provided so that the extent of wear and tear of the tip can be measured The circuit breaker shall be suitable for rapid closing and tripping. The breaker opening and closing operations shall be obtained from compressed spring charging mechanism. The mechanism for spring charging shall be motor operated with facility for manual, charging when required. It shall be suitable for re-closing once. Spring Seal and Sign of Bidder Page 6 of 26

7 operated mechanism shall be complete with opening spring, closing spring and all necessary accessories to make the mechanism a complete unit. Each mechanism shall be designed to have a continuous sequence of circuit breaker opening and closing operations, to be obtained by control switch. Operating mechanism shall be operated by local electrical control. A conveniently located manual tripping lever push button shall also be provided for tripping the breaker and simultaneously opening the circuit. The manual closing device to be provided should be at a convenient height so that it can easily be operated The auxiliary voltage of spring charging motor shall be stated under clause (j) The closing release shall operate correctly at all values of voltage between 85% and 110% of the rated voltage. The shunt trip shall operate correctly under all conditions of the circuit breaker upto the rated breaking capacity of the circuit breaker and at all values of supply voltage between 70% and 110% of the rated voltage Mechanical indicators to show the close or open position of the contacts shall be provided. Operating handle shall be provided for charging the operating mechanism All MS parts of breakers and ferrous parts such as hangers, supports, bolts & nuts shall be hot dip galvanized as per IS:2629 (latest edition) with zinc platting & olive green passivation. The material for spring shall be rust proof The circuit breaker along with the operating mechanism shall be mounted on a telescopic rail, to facilitate withdrawal, whenever required Working parts of the operating mechanism shall be of corrosion resisting material, bearing which requires grease shall be equipped with pressure type grease fittings. Bearings pins, bolts, nuts and other parts shall be adequately pinned or locked to prevent loosening or changing adjustment with repeated operation of breaker. Breaker wheels shall be provided with ball bearings. Manufacturer shall indicate or mark the critical settings and gaps to be maintained undisturbed for satisfactory operation of breaker by RED marks and shall mention it on name / rating plate CIRCUIT BREAKER The circuit breakers shall be vacuum circuit breaker (a) The circuit breaker shall comprise of three independent poles, fitted with a common operating mechanism. Seal and Sign of Bidder Page 7 of 26

8 (b) The breaker along with its operating mechanism shall be mounted inside a weather proof sheet steel cabinet described under clause no (c) Each pole of circuit breaker shall constitute a separate breaking chamber. These three breaking chambers shall be mounted on a common chassis and connected together for operation by common operating mechanism (d) The following interlocks between the withdrawable/drawout circuit breaker and cubicle shall be provided. i) The circuit breaker can not be inserted into service position, when it is in closed position. ii) The circuit breaker can not be withdrawal from the service position, unless it is in open position. iii) The circuit breaker can be closed only in test and in service position. iv) VCB of lower rating cannot be inserted into the panel with VCB of higher rating. v) VCB cannot be put in service unless the multiple plug is in position. vi) Multiple plug cannot be removed, when VCB is in service position. vii) The door can only be opened when breaker is in OFF condition & vice versa. viii) The operation shall be possible only with closed-door ix) condition. Racking in/out operation should be possible only when front panel door is closed. x) In case of feeder panel, when rear panel cover of cable compartment is opened the breaker shall open instantly. Similarly, for incomer panel along with its own breaker the HV side breaker shall also get trip command instantly (e) The details and ratings of vacuum interrupters shall be indicated in GTP and on the Name plate of the VCB panel. The speed of operation of shall be indicated in the bid and in rating plate of VCB itself. The rating of vacuum interrupter shall be 12 kv having short time current rating of 25 ka for 3 sec and BIL of 28 kv rms & 75 kvp. The current rating for Outgoing VCB shall be 1250 Amp and for Incomer 1250 or 1600 Amp as per specified in the tender inquiry. The bidder shall submit the following test report for offered type rating vacuum interrupter OR shall offer these tests during acceptance. i) LIGHTING IMPULSE VOLTAGE WITHSTAND TEST ii) SHORT TIME CURRENT WITHSTAND TEST iii) TEMPERATURE RISE TEST The vacuum interrupter shall be encapsulated for protection against explosion. Seal and Sign of Bidder Page 8 of 26

9 (f) Live part indicators shall be provided on panel to conform that there is no malfunction. Each pole CLOSE POSITION indication shall be provided on the front panel door EARTHING Earthing switch shall be provided (as optional - extra on per breaker basis and alternatively common earthing trolley (as optional extra)) shall be offered NAME PLATE The name plate / rating plate shall be provided and shall also indicate all required details of breaker, panel, CT, PT, support insulator, vacuum interrupters, and any other required details CURRENT TRANSFORMERS The cast resin insulated current transformers shall comply with the requirements of IS:2705 (latest edition) and technical requirements furnished below. (1) CT Ratio (a) / Amp For transformer control (with 1250 Amp VCB) (b) / Amp For transformer control (with 1600 Amp VCB) (c) /5-5 Amp For feeder control Core 1 Core 2 Core 3 (2) Rated Burden 15 VA 10 VA - (3) Class of Accuracy (0.5) 5P PS (4) Rated Instrument 10 (ISF) 20 (ALF) - Security Accuracy Limit Factor (5) Purpose Metering Protection Differential Protection Matching differential current transformers on 11 KV side shall be provided for differential protection. Necessary details of HV side current transformers will be furnished to successful bidders The current transformers shall be mounted on incoming/outgoing feeder side only POTENTIAL TRANSFORMERS The potential transformers shall comply with the following requirements, (a) Rated Burden : 100 VA Seal and Sign of Bidder Page 9 of 26

10 (b) Type and Connections : One unit - 3 phase, 11 KV/110 Volt, Class (0.5) accuracy PTs or alternatively three nos. - 1 phase 11KV V PTs connected in star-star 3 with neutral grounded The drawout cast resin insulated potential transformers shall be provided in/over the 11 KV panels, with necessary plug and socket type connections to enable easy withdrawal of PTs. The secondary lead shall be brought out to a terminal board. Fuses shall be provided at both HV and LV sides and limiting resistors were required, shall be provided. The PTs shall be easily withdrawable independently of the breaker ENERGY METERS (KWH METERS) The static energy meter of high precision of accuracy 0.5, capable of performing functions of recording and storing in the memory half hourly units sent out to HV/EHV consumers. The meter shall be 3- phase 4-wire balance load type for HT applications as per attached technical specifications. The Energy Meter should have appropriate hardware and software to communicate with existing SCADA system & should be capable to provide data on polling cycle PANEL BOARDS The 11 KV panel with accessories and fittings shall be indoor, floor mounting, extensible sheet steel cubicle type switch boards for controlling 11 KV side of transformers, 11 KV feeders, for various sub stations. The breaker, CTs and PTs described under clauses , and , above and the panel board shall be so constructed as to form independent 11KV indoor switch board panel. All the panels shall be completely dust and vermin proof. The panels shall remain vermin proof, even when the breaker is taken out for maintenance. The transformer control panel and feeder control panels as well as there withdrawable breaker portions of same voltages shall be interchangeable. Overall dimensions of the panel shall be furnished to check up the suitability with the existing panels. The exterior as well as interior of panel shall be painted with two coats of stoved enamel paint, with zinc phosphate treatment, after application of single coat of anti-rusting paint. The exterior shall be painted with light gray paint shade 631 of IS: 5. The interior shall be painted with glossy white paint shade. The manufacturer shall have in-house painting facility. The panels shall be provided with MS sheet on all sides and shall be sent as individual panels but shall be suitable for assembly at site to form a switchboard. The Seal and Sign of Bidder Page 10 of 26

11 panel shall be provided with not less than 2 mm thick MS sheet for all sides. Suitable blanking plates shall be provided to facilitate extensions of bus bars. Suitable barriers for the bus-bars breakers shall be provided, so that damage to other healthy panels is minimized in case of damage in one of the panels. Lifting arrangement shall be provided for the panel. Breaker, Busbar, cable/ct chamber shall be individual. Pressure release flaps shall be provided for breaker chamber, bus bar chamber, CT & Cable chamber. The flaps should be gravity fall type with suitable size wire mesh provided bellow it, to maintain vermin proofing. The rear door shall have wire mesh provided behind it, so that the person opening the door shall not have access to live parts of the panel. The nuts shall be welded with rear door cover so that all the bolts of the rear door cover shall be in position, there by effecting complete closing of the door. The panels shall be vermin proof for degree of protection of IP5X. The manufacturer shall submit type test report for offered panel along with material, size, thickness of metal sheet and gaskets provided. All the front doors shall be latch type only (a) Dimensions of panel shall be provided as mentioned below: Depth : 1750 mm to 2300 mm Height : 2200 mm to 2450 mm Width : 600 mm to 800 mm BUS BARS A set of 3-phase bus-bars of 1600 A current rating, having size of preferably 2 x 75 x 10mm = 1500 mm 2, suitably insulated by heat shrinkable tubes shall be provided. The bus bars shall be made of electrolytic high-grade copper and shall be rectangular bars of sufficient current rating. PVC sleeves/tap of suitable thickness shall be provided on bus bars and jumpers except at the joints. The joints shall be covered with suitable shrouds. Suitable shutters shall be provided in addition and separate from interlocks, with padlocking arrangements, so that bus bars become inaccessible, when the breaker is drawn out for maintenance. Phase and inter panel barriers shall be of FRP/UL994 material POWER TRANSFORMER CONTROL SWITCHBOARD PANEL The circuit breakers (vacuum) switchboard panels shall be complete with the following equipments: 1. Vacuum circuit breaker of 11 KV, 500 MVA, 1250 Amp/1600 Amp current rating and having S.T.C. rating and B.I.L. as per clause (f) and 1.3.1(f) respectively of the specifications. Seal and Sign of Bidder Page 11 of 26

12 2. 1-true trip free manually charged, manually released spring closing mechanism fitted with 110 V DC shunt trip coil and a hand trip device set of vertically horizontally isolated secondary plugs and sockets with automatic safety shutters with locking arrangement nos., epoxy cast resin type cable termination kits, suitable for 3 core 300 mm 2 /240 mm 2 XLPE aluminum power cable, with complete accessories i.e. lugs, glands etc. The cable entry shall be from the bottom (300 mm 2 cable for 1600 Amp VCB and 240 mm 2 cable for 1250 Amp VCB) cast resin insulated current transformer having ratio / Amp or / Amp for instrumentation, protection and differential as per detailed technical particulars, furnished under clause no of this specification voltage transformer, cast resin insulated, withdrawable carriage type independent of breaker 3-phase and having ratio 11000/110 volts, class I accuracy to IS:3156, complete with current limiting resistors and HT and LT fuses. Alternatively 3 nos. 1-phase 11KV V PTs connected in star-star may be offered watts/230 volt AC tubular heater, with thermostat set at required setting (One each in breaker and cable chamber) 8. 1-instrument panel mounted on the front comprising: (a) 1-Ammeter, 144 mm 2 flush pattern case, with selector switch and scaled suitably. (b) 1-Voltmeter, 144 mm 2 flush pattern case, with selector switch and scaled suitably. (c) 1-KW meter, suitable for 3-phase unbalanced load. (d) 1-KWH meter, suitable for 3-phase unbalanced load as per detailed at clause (e) 1-Double element auxiliary relay for buchholz alarm and trip housed in non-drawout flush pattern case. (f) 1-Power factor meter suitable for 3-phase unbalance load. (g) 1-Triple pole IDMT over current and earth fault Numerical relay as per annexure B attached. (h) 1-alarm cancellation relay (i) 1-set of potential selection relays of EE make or equivalent shall be provided for automatic selection of voltage supplied to a voltmeter, KW and KWH meters in a definite sequence (provision shall also be made for two future transformer connection sets at each sub-stations). (j) (1) 1-CB TNC control switch. (2) One each local manual close and trip push buttons. (k) 2-Indicating lamp working on 110 V DC supply to indicate (l) circuit breaker ON/OFF position. 1-Trip circuit healthy umber lamp with push button and working on 110 V DC supply. (m) 1-Mechanical ON/OFF indicator. (n) 1 Set of suitable mechanical interlocks. Seal and Sign of Bidder Page 12 of 26

13 (o) 1-Test terminal block having 1100 grade insulation, duly wired for testing of relays and meters. (p) Complete internal wiring with 1100 volt grade single core multi-stranded wires conforming to modern standard practice. All necessary cable glands and minor accessories shall be supplied. (q) Internal earthing of all parts of the panel as per standard practice and providing for earthing of panel. (r) 1-Circuit breaker operating handle, if applicable (two for each panel board set or 1 no. for each single phase transformer or O/G feeder panel). (s) 1-Truck or trolley for easy drawl of the breaker from its panel, if applicable (two for each panel board set). (t) Alarm scheme consisting of 1-Trip bell (on DC supply) 1-Hooter for DC failure (on AC supply) 1-Bell for AC failure (on DC supply) (u) 1-Panel label set FEEDER CONTROL SWITCHBOARD PANELS These panels will be similar to the transformer control switchboard panels, but with the following changes: (1) Item Nos. 6, 8(b), 8(e), 8(f), 8(h), 8(i), 8(t) shall not be provided. (2) 3 Cast resin insulated current transformer having ratio /5-5 A for instrumentation as per detailed technical particulars furnished in clause of this specification. (3) The set of indicating lamps shall work on 240 V AC supply instead of 110 V DC supply, as in item 8(k). (4) 2 Nos. epoxy resin type, cable termination kits suitable for three core 150 mm 2 /185 mm 2 XLPE aluminum power cable, with complete accessories i.e. lugs etc. The cable entry shall be from bottom BUS SECTIONALIZING PANEL Outwardly this panel will be similar to the feeder switchboard. No metering arrangement is to be provided on this panel. Single core CTs required for protection only shall be provided. The panel shall have 11 KV bus connections with adjoining panels on both sides, instead of cable box at bottom TESTS & TEST REPORTS (i) The indoor switchgear panels with VCB shall be of proven design and should have been type tested as per IEC / IS:13118 for the following type tests, carried out in Government approved laboratory, within last five years prior to date of bid opening. a) Dielectric test Seal and Sign of Bidder Page 13 of 26

14 b) Temperature Rise test c) Measurement of resistance of main circuit. d) Short time current and peak withstand current test e) Mechanical endurance test f) Duty cycle test g) Internal Arc test at 25kA for 0.1 sec in breaker, busbar and CT/Cable compartment. h) Cable charging current switching test i) Capacitor bank current switching test j) Single phase making and breaking test k) BIL test on support insulators l) Degree of protection (IP5X) m) Humidity test n) Type tests reports for numerical relays and major bought out items as per relevant IS/IEC. Type test reports for above tests shall be submitted with the offer. In case of non-submission of the type test reports with the offer, the bid shall be liable to be rejected. (ii) (iii) (iv) Routine tests/acceptance tests as per the latest edition of IS: for circuit breakers and also as indicated below shall be carried out on each VCB panels (in presence of purchaser s representative if desired by the purchaser.) a) Paper test to be carried out for panel with gaskets provided for vermin proofing. The test reports for type tests and routine tests in respect of associated equipment such as compressor air receivers, motors, instrument, pressure switches, relays etc. as per the latest edition of the relevant IS shall be supplied by the bidder. All tests reports for acceptance / routine rests shall be submitted and got approved from the purchaser before dispatching the breaker. 1.4 EARTH QUAKE AND WIND DESIGN LOADS Equipment shall be designed to withstand repeated earth quake accelerations of 0.08 x 2g. and wind loads of 150 kg/m2 on the project area (non simultaneous) without damage to component parts and without impairment of operation. 1.5 AUXILIARY POWER SUPPLY Power supply for auxiliary will be available at 240 V, single phase and 415 V, three phase, AC 50 Hz. The frequency can vary between 97% and 103% and voltage would vary from 110% to 85% of the normal value. Seal and Sign of Bidder Page 14 of 26

15 1.5.2 DC supply at 110 Volt, two wires will be available from the station battery for trip coils and closing coils of panels. DC supply will be available for indicating lamp in case of power transformer control panel only. DC supply is subject to variation between 85% and 110 % of the normal value. 1.6 Details shall be furnished in the appended schedule-a (guaranteed particulars). In the absence of these details, offer shall be treated as incomplete and is liable to be ignored. 1.7 Detailed schedule of requirements is appended herewith. 1.8 All the required operation & maintenance manuals incorporating Field Quality Plans (2 sets) shall be supplied along with each panel board. Seal and Sign of Bidder Page 15 of 26

16 SCHEDLE A SCHEDULE OF GUARANTEED TECHNICAL PERTICULARS (To be filled in and signed by the Bidder) [I] CIRCUIT BREAKERS (1) Maker s name and country of manufacturer (2) Manufacturer s type designation (3) Applicable technical standards (4) Rated voltage (KV) (5) Service voltage (KV) (6) Type of circuit breakers (7) Ambient temperatures used for design (a) Maximum ( 0 C) (b) Maximum daily average ( 0 C) (8) Continuous current (a) Under site condition (Amp) (b) Rated (Amp) (9) (a) Rated short time current (KA rms) (b) Rated time (Secs) (10) Maximum rise of temperature over ambient for current rating under clause 9 above ( 0 C) (11) Rated operating duty cycle (12) Interrupting capacity based on duty cycle in clause 11 above (a) Symmetrical at rated voltage in KA and MVA (b) Assymmetrical at rated voltage (KA) (c) Symmetrical at service voltage (KA) (13) Rated restriking voltage (a) Amplitude factor (b) Rate of rise of natural frequency (c) Type devices, if any used to limit the rate of rise of restriking voltage (14) Rated continuous voltage for rated MVA (KV) (15) Making capacity (KA peak) (a) At higher rated voltage (b) At lower rated voltage (16) Type of devices, if any used to obtain uniform voltage distribution between breaks Seal and Sign of Bidder Page 16 of 26

17 (17) Recovery voltage distribution between breaks in percentage of rated voltage (a) Switching OFF capacitor banks (b) Switching OFF on an unloaded transformer (18) Details of main contacts (a) Material (b) Whether contacts are silver plated (c) Thickness of silver coating (d) Contact pressure (kg/mm 2 ) (19) Insulation level of the breaker (a) One minute dry withstand voltage (KV rms) (b) One minute wet withstand voltage (KV rms) (c) Impulse withstand test voltage (KV peak) (20) Minimum clearance in air/vacuum (a) Between phase (live parts) (mm) (b) Between live part and earth (mm) (c) Centre distance between phases (mm) (20A) Details for circuit breaker V.I. (a) (i) quantity of vacuum per circuit breaker, if (ii) applicable (bars) Standard to which the Vacuum confirms (iii) details of vacuum interrupters, indicate (Make/Type/Rating) (iv) Speed of operation of V.I. (b) Weight of complete circuit breaker with insulating medium (kg) (c) Pressure of insulation media in the chamber, if applicable (21) Whether circuit breaker is Fixed Trip or Trip Free (22) Method of closing (a) Normal (b) Emergency (23) Type of closing mechanism (a) (i) Normal voltage of motor for closing mechanism (AC Volt) Seal and Sign of Bidder Page 17 of 26

18 (ii) Pick up range (AC Volt) (b) Power at normal voltage of closing coil (Watt) (c) Power at 85% of normal 110 V DC (Watt) (d) Details of electric motor for operating mechanism (complete name plate details) (24) Type of tripping mechanism (a) Normal voltage of tripping coils (Volt) (b) Power at normal voltage for tripping coils (Watt) (c) Power at 70% of normal 110 V DC for tripping coils (25) Arc duration at 100% interrupting capacity (a) Opening (i) Arcing time (cycle) (ii) Total time measured from instant of trip coil energisation to arc extinction (cycle) (b) Closing time measured from instant of application of power to closing device upto arcing contacts touching (cycle) (26) (a) Recovery voltage when circuit breaker is tested at 100% rated breaking capacity (HV inst.) (b) Rate of rise of restriking voltage at breaking (i) For 30% breaking capacity (KV/micro secs.) (ii) For 60% breaking capacity (KV/micro secs.) (iii) For 100% breaking capacity (KV/micro secs.) (c) Maximum over voltage factor of the circuit breaker, when switching OFF (i) Capacitor banks (ii) Unloaded transformers (iii) Loaded transformers (27) When switching OFF a synchronous system (a) Maximum current (b) Minimum recovery voltage between contacts of one pole (KV) Seal and Sign of Bidder Page 18 of 26

19 (28) Nos. of operations, the circuit breaker is capable of performing without replacing/reconditioning oil (a) At 50% rated current (b) At 100% rated current (c) At 50% breaking capacity (d) At 100% breaking capacity (29) Overall dimensions of panels (a) Breadth (mm) (b) Width (mm) (c) Length (mm) (30) Gaskets a) Material b) Size c) Type [II] CURRENT TRANSFORMERS (1) Rated primary current (Amp) (2) Rated secondary current (Amp) (3) Rated output (VA) and accuracy class (4) Rated continuous thermal current (5) Insulation level (lightening impulse withstand voltage & with PF withstand voltage) (6) Magnetising curve characteristics (7) Overall dimensions and mounting details (8) Applicable standard and type of CT [III] POTENTIAL TRANSFORMERS (1) Rated primary current (Amp) (2) Over voltage factor and capacity offered (3) Rated output (VA) and accuracy class (4) Over voltage factor and capacity as per ISS (5) Total weight (kg) (6) Insulation level (lightening impulse withstand voltage & with PF withstand voltage) (7) Overall dimensions and mounting details (8) Applicable standard and type of PT Seal and Sign of Bidder Page 19 of 26

20 [IV] INSTRUMENTS AND METERS PF Am- Volt Watt- KWH Meter meter meter meter Meter (1) Make (2) Type (3) Accuracy class (4) Burden (VA) (5) Scale details (6) Short time overload capacity (7) Limits of error in effective range (8) Applicable IS [V] SWITCHES (1) Make (2) Type (3) Making capacity of contacts (4) Breaking capacity of contacts (5) No. of positions (6) No. of contacts in each positions (i) Open (ii) Close (7) No. of spare contacts Breaker control Ammeter Voltmeter Switch (T.N.C.) selector switch selector switch [VI] RELAY Main relay Auxiliary relay 1 2 (1) Make (2) Type (3) Current coil rating (4) Tap range (5) VA burden (i) Highest tap (ii) Lowest tap (7) Type of characteristic Seal and Sign of Bidder Page 20 of 26

21 (8) Time of operation of maximum dial setting at (i) 5 times tap setting current (ii) 10 times tap setting current [VII] INDICATING LAMP (1) Make (2) Type (3) Operating voltage (4) Lamp wattages (5) Colour of shade Suitable for Suitable for 240 V AC 110 V DC 1 2 [VIII] SWITCHBOARD WIRING (1) Insulation of wire (2) Size of wire (mm 2 ) (3) Grade of wire (Volt) (4) Whether conductor is of (i) Copper (ii) Stranded (5) Whether wire ends provided with rosecoutnany/lug type arrangements (6) Make and voltage grade of terminal blocks used [IX] CONFIRMATION POINTS (To be confirmed against each points) (1) Discharge flap with wire mesh provided. (2) Speed of operation of VI shall be indicated on rating/ nameplate of VCB. (3) The following test report for offered type rating vacuum interrupter shall be submitted OR shall be offered during acceptance, on any one unit. a. Lighting Impulse Voltage Withstand Test b. Short Time Current Withstand Test c. Temperature Rise Test (4) The vacuum interrupter shall be encapsulated for protection against explosion. (5) Live part indicators (2 nos for I/C and 1 for feeder) shall be provided on panel along with each pole CLOSE POSITION indication on the front panel door. Details & drawing is submitted. Seal and Sign of Bidder Page 21 of 26

22 (6) All the critical settings and gaps to be maintained undisturbed for satisfactory operation of breaker shall be given by RED marks and mentioned on name / rating plate as well as manuals. (7) The operation shall be possible only with closed-door condition. (8) Racking in/out operation should be possible only when front panel door is closed. (9) Tripping of VCB when rear door is open. (10) All the required O & M manuals incorporating FQP (2 sets) shall be supplied along with each panel board. (11) Vermin proofing as per IP5X and details of material, size, thickness of metal sheet and gaskets provided. (12) All the front doors shall be latch type only. (13) Type test report for Humidity test. (14) As a routine test, Paper test will be carried out on offered panel. (15) Heater with thermostat one each in cable & breaker compartment. (16) The joints shall be covered with suitable shrouds, instead of paraplast. Seal of Firm Signature of Bidder Note: Instead of giving reference of drawing nos./is/literatures etc. actual values/figures must be furnished, where ever required, otherwise the said details in G.T.P. of the Technical Bid, will be evaluated accordingly. Seal and Sign of Bidder Page 22 of 26

23 Sr. No. GETCO / E / TS HTPB 5401 / R0 Dt Details of Material Make BILL OF MATERIALS APPENDIX IV Type/ Desig- -nation Catiogu e if Any Single Transf. Quantity Per Each Panel/Panel Board 7 Bus 6 Pane Single Coulp Panel l Feeder er Board Boar d Ammeter 144 mm 2 flush pattern case, with selector switch 2 Voltmeter 144 mm 2 flush pattern case, with selector switch 3 KWH meter 4 KW meter 5 Power-factor meter 6 Triple pole IDMT Over-current and Earth-fault Numerical relay 7 Double element auxiliary relay for Buchholz alarm and trip 8 Alarm cancellation relay 9 Set of Potential selection relays 10 Circuit breaker trip - Neutral - Close control switch 11 Local manual push button 12 Local manual trip push button 13 Mechanical ON/OFF indicator 14 Test terminal block 15 Epoxy cast resin type cable termination kits, with complete accessories, suitable for 3 core XLPE aluminum power cable, (i) Size 300 mm 2 (ii) Size 240 mm 2 (iii) Size 150 mm 2 (iv) Size 185 mm 2 16 Circuit breaker operating handle 17 Circuit breaker ON/OFF position indicating lamps working on 240V AC supply 18 Circuit breaker ON/OFF position indicating lamps working on 110V DC supply 19 Spring charged indicator lamp 20 Auto trip indicator lamp with suitable relay 21 Trip circuit healthy lamp 22 Trip circuit healthy push button 23 Alarm schemes 24 Trip bell (on DC supply) 25 Hooter for DC failure (on AC supply) 26 Bell for AC failure (on DC supply) watts, 240 V AC tubular heater with thermostat (One each in breaker & Cable chamber) 28 Cast resin insulated current transformers as per specification 29 Cast resin insulated withdrawable carriage type, voltage transformer, as per specification Signature of Bidder(With seal of Firm) Note: The Bidder should state various makes for bought out items, wherever required in BOM instead of indicating or or equivalent. Any other materials required other than above, for successful operation shall be indicated in a separate sheet. 8 Panel Board Seal and Sign of Bidder Page 23 of 26

24 PRINCIPAL TECHNICAL PARAMETERS OF O/C AND E/F RELAY SR. Item NO. 1 NON- DIRECTIONAL O/C AND E/F PROTECTION RELAY. Specification (A) Features: a) Shall be Numerical type. b) Shall have 2 over current and 1 Earth Fault element. c) TRUE RMS Measurement. d) Have selectable and front panel programmable normal, inverse, very inverse & IDMT Characteristic. e) Selectable CT Secondary. I.e. 1A / 5A f) High set over current with selectable time delay. g) High set Earth fault with selectable time delay h) Shall have Breaker Failure Protection as in built feature. i) Include hand reset Flag/LED indicators for phase identification for all faults. j) Readable Human Machine Interface with LED/ LCD display. k) Should be able to store at least last 3 events with fault data viz. Fault current, Faulty Phase etc. l) Shall have Self monitoring feature. m) Relay offered shall be communicable type. (B) Technical Parameters: 1. Rating: 1A / 5A, 50 Hz ±2.5 Hz 2. Auxiliary Supply: 110 V DC ±15 % (C) Relay settings: 1. Over Current: 50% - 200% (In steps of 5%) 2. Earth Fault: 5% - 80% (In steps of 5%) 3. High set O/C: times In or more. 4. High set E/F: times In or more. 5. Time multiplier for: (In steps of 0.025) (Independent for O/C & E/F) 6. Time delay for high set element : 0.02 to 2 sec (in steps of 0.01 sec) 7. Pick up: Within 1.1 times of set current value. 8. Reset current: 95% to 90% of pick-up current. 9. Operating Time: As per selectable characteristic. For Inst. Element < 40 ms for 2xIn. (D) Other Features: 1. Provide sufficient number of potential free contacts to cater the needs of connection to alarm annunciation. Output contacts: Minimum 2 N/O contacts with Seal and Sign of Bidder Page 24 of 26

25 - Continuous carry 5 A - Make & Carry for 0.5 s 30 A - Make & Carry for 3.0 s 15 A Signaling contact: Minimum 4 Nos for following signals - Relay Faulty - Relay Operated - High set operation - IDMT operation 2. Local PC Communication: RS232/RS Housing Flush Mounting Screw Terminals ( O Lug for CT Connection) Degree of Protection IP51 4. Temperature and humidity (a) Ambient temp -10 to 55 o C (b) Relative humidity 10% to 90% Non Condensing (c) Operate range 0-95% (d) Storage temp. -40 to 70 o C Seal and Sign of Bidder Page 25 of 26

26 SCHEDULE B GUARANTEED TECHNICAL PARTICULARS (TO BE FILLED IN BY THE BIDDER AND FURNISH WITH TECHNICAL BID) The GTP is to be filled up in this format and, in the page of Bid Specification only, to be submitted in duplicate along with the offer. This is intended for speedy comparison of various bidders GTP. The Bidder shall fill in the particulars against appropriate items in respect of each rating and type of Protective Relays offered in the broad categories listed below: (1) NUMERICAL NON-DIRECTIONAL OVERCURRENT AND EARTH FAULT RELAY WITH HIGH SET 1 Make 2 Type 3 Rating 4 Auxiliary Supply settings 5 Over Current 6 Earth Fault 7 High set O/C 8 High set E/F 9 Time multiplier 10 Whether independent for O/C and E/F or not 11 Time delay for high set element 12 Pick up value 13 Reset current 14 Operating Time For Inst. Element 15 No. of tripping contact 16 Tripping contacts rating Continuous carry Make & Carry for 0.5 s Make & Carry for 3.0 s 17 No. of Signaling contact 18 Communication ports and protocol 19 Housing 20 Temperature and Humidity 21 Relay burden 22 In built Breaker Failure Protection Seal and Sign of Bidder Page 26 of 26

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date: 10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information

66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED)

66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED) GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATION FOR 66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED) GETCO/E/06TS CB/R3 May12 Page

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax

More information

Technical Specification No.- S-168/DD KV Switchgear Panel. Vacuum Type

Technical Specification No.- S-168/DD KV Switchgear Panel. Vacuum Type DAKSHIN HARYANA BIJLI VITRAN NIGAM Office of the Chief General Manager/P&D, Vidyut Sadan, Vidyut Nagar, Hisar-125005 Tel: 01662-221285, 221830 (GM/P&D) Fax: 01662-220481 Technical Specification No.- S-168/DD-177

More information

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A Technical Specification Of 12KV, 400A, 18.4 KA Floor Mounted totally enclosed Ring Main Unit consisting of 2 nos. Vacuum Interrupting Incoming Unit and one no. Series Trip Metering Switchgear with Vacuum

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR SELECTIVE LEVEL METER GETCO/E/TS- PACC SLM 03504/R0, Dt: 2.04.2008 Page

More information

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT 33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

TECHNICAL SPECIFICATIONS OF PCC PANEL

TECHNICAL SPECIFICATIONS OF PCC PANEL S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB Annexure-V (Under Two Part Bid System) Tender No: NFV/ PUR/ BEC 160546 K for VCB Technical specification for NIT SL NO 1 S.No. Description NFL requirement as per NIT Vendors Comment [Agreed / If not agreed,

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

D.C. DISTRIBUTION BOARD

D.C. DISTRIBUTION BOARD PRAMBL: The TC is maintaining 50-volt battery backup system for the PLCC communication. The 50-volt D.C. supply from the Float cum Boost charger is brought to D.C. Distribution Board from where supply

More information

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011 Page 1 of 6 STANDARD SPECIFICATION FOR LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By 0 15.07.2008 6 Issued for FEED MSJ VDV VDV

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GETCO / E / TS- BCHR 3202 / R2 Oct 15 Seal & Sign

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR GETCO/E/TS-50V BCHR(SCADA)

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Metal Clad Air Insulated Switchgear

Metal Clad Air Insulated Switchgear Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system

More information

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay DG 14 drawn out from the case The type DG 14 relay is a heavily damped

More information

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application)

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application) GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (100A) & BOOST CHARGER (60A) FOR WITH REQUIREMENT FOR SCADA

More information

Metal Clad VCBs ~ Mk1

Metal Clad VCBs ~ Mk1 Metal Clad VCBs ~ Mk1 DUVI 150/40 ROLL ON FLOOR VCBs Range: 6kV, 00A, 1.5kA, 12kV, 150A, 40kA ( 4A000A Bus-Bars ) ` Widest range for MV (up to 6kV) Distribution Networks Megawin make metal clad VCB Panels

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

HARYANA VIDYUT PRASARAN NIGAM LTD.

HARYANA VIDYUT PRASARAN NIGAM LTD. HARYANA VIDYUT PRASARAN NIGAM LTD. TECHNICAL SPECIFICATION SSD/S-03/R-1/DGM-605 TECHNICAL SPECIFICATION FOR 33 KV CAPACITOR BANKS CHIEF ENGINEER/MM HVPNL, PANCHKULA TELEPHONE & FAX: 0172-2583724 MARCH-2017-0

More information

TECHNICAL SPECIFICATIONS FOR HARDWARE & ACCESSORIES -ACSR DOG CONDUCTOR FOR TRANSMISSION LINE

TECHNICAL SPECIFICATIONS FOR HARDWARE & ACCESSORIES -ACSR DOG CONDUCTOR FOR TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS FOR HARDWARE & ACCESSORIES -ACSR DOG CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV).

Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Amendments in Technical Specification No. S-137/DD-177 July 2007 for 11KVAutomatic Switched Capacitor bank at Sub-Stations (33/11KV). Sr. No. Clause No Existing Proposed 1 8.0 Dischar ge device 2 15.0

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

32-SDMS-03 SPECIFICATIONS FOR

32-SDMS-03 SPECIFICATIONS FOR SPECIFICATIONS FOR EXTENSIBLE SF6 INSULATED RING MAIN UNIT, 17.5 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

West Bengal State Electricity Distribution Co. Ltd.

West Bengal State Electricity Distribution Co. Ltd. West Bengal State Electricity Distribution Co. Ltd. TECHNICAL SPECIFICATIONS FOR D. C. DISTRIBUTION BOARD (FOR 33 KV SUB STATIONS) Page 1 of 14 1.0 SCOPE: This specification covers the design, manufacturing,

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable

More information

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES 1 TABLE OF CONTENTS 1. SCOPE 2. GENERAL 2.1 STANDARDS AND REGULATIONS 2.2 OPERATING CONDITIONS 2.3 DOCUMENTATION

More information

32-SDMS-02 SPECIFICATIONS FOR

32-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV METERED RING MAIN UNIT UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES 3

More information

TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-ACSR PANTHER CONDUCTOR FOR TRANSMISSION LINE

TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-ACSR PANTHER CONDUCTOR FOR TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-ACSR PANTHER CONDUCTOR FOR TRANSMISSION LINE GETCO/ENGG/TECH.

More information

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: (1) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 110 V, 100 Ah / 250 Ah & 220 V, 250 Ah / 350Ah TUBULAR LEAD ACID BATTERY SETS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 110 V, 100 Ah / 250 Ah & 220 V, 250 Ah / 350Ah TUBULAR LEAD ACID BATTERY SETS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 110 V, 100 Ah / 250 Ah & 220 V, 250 Ah / 350Ah TUBULAR LEAD ACID BATTERY

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- 01) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in 50Hz, 11KV distribution

More information

0.3 This standard is generally based on the following standards:

0.3 This standard is generally based on the following standards: IPSS GENERAL TECHNICAL SPECIFICATION FOR INDOOR HIGH VOLTAGE SWITCHGEAR (FIRST REVISION) BASED ON IS 12729:2004, IEC60694:2002, IEC62271-1:2007, -100:2008, -200:2003 IPSS:1-04-030-15 Formerly: IPSS:1-04-030-97

More information

Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make

Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch 1. Scope:- This specification covers manufacturing, testing and supply of 11KV 200Amp. 50Hz Air Break switches for outdoor installation

More information

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES:

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES: TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES: 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

31-SDMS-01 REV. 03 SPECIFICATIONS FOR

31-SDMS-01 REV. 03 SPECIFICATIONS FOR 31-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE DISTRIBUTION PANEL This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1.0 SCOPE

More information

TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE

TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE GETCO/E/TS

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

SPECIFICATIONS FOR 50 V, 600 AH LEAD ACID BATTERY

SPECIFICATIONS FOR 50 V, 600 AH LEAD ACID BATTERY (I) INTRODUCTION: Power Line Carrier Communication (PLCC) System is being used by Gujarat Energy Transmission Corporation Ltd. for Speech, Data, Protection and Teleprinter signal transmission purpose throughout

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents

More information

TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE

TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS.

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. DRAFT SPECIFICATION NO : RDSO/PE/SPEC/D/PS/0010-99 (REV. 0 ) SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. 0. FOREWORD 0.1 This specification covers manufacturing and

More information

TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY.

TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY. TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY. 1.0 SCOPE: This specification covers the design, manufacturing and testing of LT Distribution

More information

32-SDMS-01 REV. 02 SPECIFICATIONS FOR

32-SDMS-01 REV. 02 SPECIFICATIONS FOR 32-SDMS-01 REV. 02 SPECIFICATIONS FOR NON-EXTENSIBLE SF6 INSULATED RING MAIN UNIT, 17.5 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.0 008 Answers for energy. R-HG11-17.tif Siemens HG 11.0 008 Contents Contents Page SION Vacuum Circuit-Breakers Description General Construction

More information

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2 Sl. No. WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO GUARANTEED TECHNICAL PARTICULARS 1 of 2 REQUIREMENTS 11 Kv, 200 Amps, A.B Switches. Particulars 1 Maker's name and Country of origin. 2 Type

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

AN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR

AN ISO 9001 & COMPANY TENDER DOCUMENT. TENDER No: DLI/CON/696/411 FOR AN ISO 9001 & 14001 COMPANY TENDER DOCUMENT TENDER No: DLI/CON/696/411 FOR SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF 11/0.433KV INDOOR/OUTDOOR ELECTRIC SUBSTATION AND OTHER ASSOCIATED EXTERNAL ELECTRICAL

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance M E T A L - C L A D S W I T C H G E A R Safe and Reliable Flexible, Compact Design Easy Installation and Maintenance We build a better future! Hyundai HMS medium-voltage metal-clad switchgears and control-gears,

More information

TECHNICAL SPECIFICATION. UP TO 36 kv METAL-CLAD. With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

TECHNICAL SPECIFICATION. UP TO 36 kv METAL-CLAD. With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES TECHNICAL SPECIFICATION UP TO 36 kv METAL-CLAD With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES 1 TABLE OF CONTENTS 1. SCOPE 2. GENERAL 2.1 STANDARDS AND REGULATIONS 2.2 OPERATING CONDITIONS

More information

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura Modular-C\Standardized Motor Control Centres\ M600204.15 PT Guna Era Manufaktura Catalogue 2015 GAE MCC Modular-C Standardized Motor Control Centres General Definition Type-tested low-voltage switchgear

More information

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A. SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad

More information

Technical Specification of GECOL. Packaged Transformers

Technical Specification of GECOL. Packaged Transformers GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...

More information

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information