1 PowerIT PowerIT Current Limiting Fuses, Motor Circuits Fuses, CMF Catalogue 1YMB51-en Industrial IT enabled TM

2 High voltage current limiting fuse links type Rated voltage:,/7,- kv Rated current: - A Index 1. General.... Overvoltages.... Replacement of melted fuse links Nameplate Pre-arcing times Current limitation Indicator and striker pin Choice of fuse links Ordering table Data and dimensions Accessories...9. Data and dimensions... High voltage current limiting fuse link for MOTOR circuit applications type CMF Rated voltage: Rated current:, kv 0-15 A 7, kv -15 A kv - A Index 1. General Nameplate Indicator and striker pin Ordering table CMF Ordering table UCM.... Ordering table type CMF-BS Pre-arcing times Current limitation Overvoltages Choice of fuse links Replacement of melted fuse links The K-factor Data and dimensions CMF...15

3 High voltage current limiting fuse links type Rated voltage:,/7,- kv Rated current: - A 1. General The HRC generation of fuse link type are designed and tested according to IEC Publication 8-1. Dimensionally the fuse links are in accordance with DIN 4. 's high voltage fuse links have the following properties: Low minimum breaking current Low power losses Low arc-voltage High breaking capacity High current limitation. Low power losses permit installation of these fuse links in compact switchgear. fuses are of back-up type. They have a zone between the minimum melting current and the minimum breaking current where the fuse links may fail to interrupt. For fuse links this zone is very narrow. The minimum breaking current I for any type is specified in the table on p. 8. Other fuse types produced by can be found in the following catalogues: Fuses for Voltage Transformers WBP/BRT 1YMB0001-en Fuses for Railway DC Applications BWT/WBT 1YMB1-en. Overvoltages In order to be current limiting, the fuse link must generate an arc-voltage exceeding the instantaneous value of the operating voltage. The switching voltage generated by the fuse link is below the maximum permissible value acc. to IEC 8-1. The fuse link can safely be used if the system line voltage is -0% of the rated fuse link voltage.. Replacement of melted fuse links Cef fuse links cannot be regenerated. According to IEC Publication 8-1, all fuse links should be replaced, even if only 1 or of the fuse links in the threephase system have operated. Exceptions are allowed when it can be verified that the fuse link(s) have not experienced any over- current. STRIKER SCHLAGSTIFT TYPE IN A I I N UN kv I1 ka INDOOR INNENRAUM 4. Nameplate The symbols on the nameplate have the following meaning: I N = Rated current U N = Rated voltage I = Minimum breaking current I = Maximum short circuit current for which the fuse is tested 1 The arrowhead on the nameplate indicates in which end of the fuse link the indicator and striker pin appears. Additionally this end contact of the fuse link is specially marked. -U is outdoor type.

4 Fuse link type Minutes 8 4 Seconds 1min , 0,4 0, 0, 0,1 0,08 0,0 0, ,0 0, Pre-arcing times The characteristics are equal for all rated voltages and are recorded from cold condition. Dashed sections of the curves indicate the zone of uncertain interruption. 4

5 Fuse link type 0 ka ,1 0,01 0,1 1 Jp 0kA. Current limitation fuse links are current limiting. A large short circuit current will therefore not reach its full value. The diagram shows the relation between the prospective short circuit current and the peak value of the cut-off current. Substantial current limitation results in a considerable reduction of the thermal and mechanical stress on the high voltage installation. 7. Indicator and striker pin Force (N) The fuse link is equipped with a combined indicator- and striker system, which is activated immediately when the fuse element melts. The force diagram is in accordance with the requirements of IEC 8-1 and DIN 4. Travel (mm) 5

6 Fuse link type 8. Choice of fuse links Choice of rated voltage U N: The rated voltage of the fuse links must be equal to, or higher than the operating line voltage. By choosing the fuse link rated voltage considerably higher than the line voltage, the maximum arc voltage must not exceed the insulation level of the network. Choice of rated current I N: To obtain the best possible current limitation, and thereby also protection, IN must be chosen as low as possible compared to the rated current of the object to be protected. However, the following limitations must be taken into consideration: the largest load current must not exceed IN cooling conditions (e.g. in compact switchgear). inrush current of off load transformers. starting currents of motor circuits. (See page 14 with CMF, special motor fuses). For the choice of rated current of fuse links for protection of transformers, the relation between the power rating of the transformers, operating voltage and rated current of the fuse link is given in the table below. The same table indicates the highest rated current of the low voltage fuse link (on the low voltage side of the transformer) which gives discrimination with the high voltage fuse link. The low voltage fuse link is of the type gl (VDE) or gg / gm (IEC). For choice of fuse links for transformer protection in switchgear of type Safe Plus or Safering CTC-F, see SF Insulated Compact Switchgear and Ring Main Unit catalogue (NOPOWSR4GB). Choice of fuse links for protection of transformers Line voltage (kv) TRANSFORMER RATING (kva) HIGH VOLTAGE FUSE-LINK I n (A) * 0 15* 0* 15* 0* x x x x Low voltage LOW VOLTAGE FUSE-LINK I n (A) 0 V V V * CMF - fuse link

7 Fuse link type 9. Ordering table High-voltage HRC fuse links Other ratings and dimensions on request. When ordering outdoor version pls. indicate U. 7 19/5 19/5 19/5 19/5 19/5 19/5 19/5 19/5 19/5 9/5 9/5 9/5 9/5 9/5 9/5 9/5 9/87 9/87 9/5 9/5 9/5 9/5 9/87 9/87 9/87 /5 /5 /5 /5 /87 /87 /87 /87 /87 /87 /5 /5 /5 /5 /5 /87 /87 /87 /87 /87 /5 /5 /5 /87 /87 /87 /87 57/87 57/87 57/5 57/5 57/5 57/87 57/87 Type Rated voltage kv Rated current A e/d mm Old No. New No. Weight kg e/d mm Old No. New No. Weight kg ,5 1,5 1,5 1,5 1,5 1,5 1,5,,,,,,,,,,8,8,,,,,8,8,8 5, 5, 5, 5, 5, 5, 5, 5, 5, 5, 5, 5, 5,,,,1,1,1,, 9/5 9/5 9/5 9/5 9/5 9/5 9/5 9/87 9/87 9/87 9/87 9/87 /5 /5 /5 /5 /5 /5 /5 /87 /87 /87 /87 /87 7/5 7/5 7/5 7/5 7/87 7/87 7/87 57/87 57/87 57/87 NHPL0570R1 NHPL05719R1 NHPL0570R1 NHPL05704R1 NHPL0579R1 NHPL0570R1 NHPL0570R1 NHPL05748R1 NHPL05749R1 1YMB54M0001 1YMB54M000 1YMB54M000 1YMB54M0004 1YMB54M0005 1YMB54M000 1YMB54M0007 1YMB54M0008 1YMB54M0009 1YMB1M00 1YMB1M0011 1YMB1M00 1YMB55M0001 1YMB55M000 1YMB55M000 1YMB55M0004 1YMB55M0005 1YMB55M000 1YMB55M0007 1YMB55M0008 1YMB55M0009 1YMBM00 1YMBM0011 1YMBM00 1YMB5M0001 1YMB5M000 1YMB5M000 1YMB5M0004 1YMB5M0005 1YMB5M000 1YMB5M0007 1YMB4M0008 1YMB4M0009 1YMB4M00,,,,,,,,,,,, 5, 5, 5, 5, 5,,7,7,7,7 4,4 4,4 4,4,,, 1YMB1M0001 1YMB1M000 1YMB1M000 1YMB1M0004 1YMB1M0005 1YMB1M000 1YMB1M0007 1YMB1M0008 1YMB1M0009 1YMBM0001 1YMBM000 1YMBM000 1YMBM0004 1YMBM0005 1YMBM000 1YMBM0007 1YMBM0008 1YMBM0009 1YMBM0001 1YMBM000 1YMBM000 1YMBM0004 1YMBM0005 1YMBM000 1YMBM0007 1YMB57M0001 1YMB57M000 1YMB57M000 1YMB57M0004 1YMB57M0005 1YMB57M000 1YMB57M0007 1YMBM0008 1YMBM0009 1YMBM00 1YMB4M0001 1YMB4M000 1YMB4M000 1YMB4M0004 1YMB4M0005 1YMB4M000 1YMB4M0007 1YMB5M0001 1YMB5M000 1YMB5M000 1YMB5M0001 1YMB5M000 1YMB5M000 1YMB5M0004 1YMB5M0005 1YMB5M000 1YMB5M0007 1YMB5M0008 1YMB5M0009 1YMBM0001 1YMBM000 1YMBM000 1YMBM0004 1YMBM0005 NHPL05711R1 NHPL0571R1 NHPL05714R1 NHPL05715R1 NHPL057R1 NHP 5R NHPL05717R1 NHPL05701R1 NHPL05718R1 NHPL0571R1 NHPL057R1 NHPL057R1 NHPL057R1 NHPL057R1 NHP R NHPL0577R1 NHPL0570R1 NHPL0578R1 NHPL0571R1 NHPL057R1 NHPL0574R1 NHPL0575R1 NHPL057R1 NHP 7R11 NHPL0577R1 NHPL05705R1 NHPL0578R1 NHPL0579R1 NHPL05741R1 NHPL0574R1 NHPL05744R1 NHPL05745R1 NHPL0574R1 NHP 8R NHPL05747R1 NHP 47R NHP 47R1 NHP 47R NHP 14R7 NHP 14R8 NHP 14R9 NHP 14R1 NHP 14R NHP 14R5 NHP 14R NHP 14R NHP 14R4 NHPL057R1 NHPL0575R1 NHPL0575R1 NHPL05754R1 NHPL05755R1

8 Fuse link type. Data and dimensions UN IN e D I1 I PN RO kv A mm mm ka A W mω 19/ / / ,,/7, 19/ ,1 19/ , 19/ ,4 19/ ,8 19/ , 0 19/ , , , ,7 9/ / / / , 9/ 5 5 5,0 9/ ,9 9/ ,4 9/ , 0 9/ 87 75, , , ,7 9/7/ /7/ /7/ /7/ ,7 9/7/ ,5 9/7/ 87 90,1 9/7/ , , , , , 5 1 4, , , , , , , , , , , , , , ,1 I 1 = maximum short-circuit current tested I = minimum breaking current P N= power loss at rated current R 0= resistance at room temp. 8

9 Fuse link type 11. Accessories Fuse base type UCE Fuse clips 4.5 ±0.5 9 R4 ø. Old No. NHP078P1 New No. 1YMX078P0001 R R.5 R ø. 8.5 R R5 Ordering table Type Rated Current Fuse Dimensions in mm Weight Old No. New No. voltage ratings length kv A mm A A1 A H K K1 B kg UCE 7,,/7, ,4 NHPL1R1 1YMX01M001 UCE,/7, 1- NHPLR1 1YMX0M ,7-0 NHPLR1 1YMX0M001 UCE L , NHPL5R1 1YMX05M001 UCE ,7 HNPL7R1 1YMX07M001 UCE -1 NHPL9R1 1YMX09M ,9 NHPL9R1 1YMX09M001 UCE L ,4 NHPL511R1 1YMX0511M001 UCE , NHPL51R1 1YMX051M001 test fuse-link,/7,- kv for test of striker system. Old No. New No. * Adjustable. The striker has a force-travel characteristic as shown in the figure on page 5. Operating tong for fuse links,/7, KV Old No. New No. Test voltage Weight kv kg NHPL00R1 1YMX00M001 0, Dimensions in mm Weight kg NHP 000 1YMX000R001 1,4 L1 L A( Ø) Dimension in mm e* Total length Old No. NHP077P1 New No. 1YMX077P0001 9

10 Fuse link type. Data and dimensions Data and dimensions acc. to EN 08-1: /5 07/5 07/5 07/5 07/5 07/5 07/5 07/5 07/5 7/87 7/87 7/87 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 557/5 557/5 557/5 557/5 557/5 557/5 557/5 05/5 07/5 07/5 07/5 07/5 07/5 07/5 07/5 07/5 419/87 7/87 7/87 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5 55/87 419/5 7/5 7/5 7/5 7/5 7/5 7/5 55/87 557/5 557/5 557/5 557/5 557/5 557/5 557/ NHP R1 NHP R NHP R NHP R4 NHP R5 NHP R NHP R7 NHP R8 NHP R9 NHP R NHP R11 NHP R NHP 81R1 NHP 81R NHP 81R NHP 81R4 NHP 81R5 NHP 81R NHP 81R7 NHP 81R8 NHP 81R9 NHP 81R NHP 81R11 NHP 81R NHP 8R1 NHP 8R NHP 8R NHP 8R4 NHP 8R5 NHP 8R NHP 8R NHP 8R7 NHP 8R8 NHP 8R9 NHP 8R1 NHP 8R NHP 8R NHP 8R4 NHP 8R5 NHP 8R7 NHP 8R NHPR1 NHPR NHPR NHPR NHPR NHPR NHPR7 NHPR8 NHPR9 NHPR0 NHPR1 NHPR NHP81R1 NHP81R NHP81R NHP81R NHP81R NHP81R NHP81R7 NHP81R8 NHP81R9 NHP81R0 NHP81R1 NHP81R NHP8R1 NHP8R NHP8R NHP8R NHP8R NHP8R NHP8R7 NHP8R8 NHP8R9 NHP8R0 NHP8R1 NHP8R NHP8R NHP8R NHP8R NHP8R NHP8R7 1YMB7M0001 1YMB7M000 1YMB7M000 1YMB7M0004 1YMB7M0005 1YMB7M000 1YMB7M0007 1YMB7M0008 1YMB7M0009 1YMB7M00 1YMB7M0011 1YMB7M00 1YMB8M0001 1YMB8M000 1YMB8M000 1YMB8M0004 1YMB8M0005 1YMB8M000 1YMB8M0007 1YMB8M0008 1YMB8M0009 1YMB8M00 1YMB8M0011 1YMB8M00 1YMB9M0001 1YMB9M000 1YMB9M000 1YMB9M0004 1YMB9M0005 1YMB9M000 1YMB9M0007 1YMB9M0008 1YMB9M0009 1YMB9M00 1YMB5M0001 1YMB5M000 1YMB5M000 1YMB5M0004 1YMB5M0005 1YMB5M000 1YMB5M0007 1YMB7M001 1YMB7M00 1YMB7M00 1YMB7M00 1YMB7M00 1YMB7M00 1YMB7M007 1YMB7M008 1YMB7M009 1YMB7M000 1YMB7M001 1YMB7M00 1YMB8M001 1YMB8M00 1YMB8M00 1YMB8M00 1YMB8M00 1YMB8M00 1YMB8M007 1YMB8M008 1YMB8M009 1YMB8M000 1YMB8M001 1YMB8M00 1YMB9M001 1YMB9M00 1YMB9M00 1YMB9M00 1YMB9M00 1YMB9M00 1YMB9M007 1YMB9M008 1YMB9M009 1YMB9M000 1YMB5M001 1YMB5M00 1YMB5M00 1YMB5M00 1YMB5M00 1YMB5M00 1YMB5M007 Type Type Rated voltage kv Rated voltage kv Rated current A Rated current A L/D mm L/D mm A mm A mm Old No. Old No. New No. New No.

11 High voltage current limiting fuse link for MOTOR circuit applications type CMF Rated voltage: Rated current:, kv 0-15 A 7, kv -15 A kv - A 1. General The fuse links type CMF are specially designed for motor circuit applications. They are tested according to the IEC Publication 8-1 and Publication 44. The IEC 44 applies to fuse links used with motors started direct-on-line on alternating current systems. High voltage fuses used in motor circuits must have the ability to withstand, without deterioration, the repeated surges associated with motor starting. The dimensions are in accordance with DIN 4, i.e. the, kv rating is realized in the normal kv length (e = 9 mm). The 7, kv and kv rating in the kv length (e = mm). Special connection elements can be delivered in cases where fuses have to be paralleled. s motor fuses have the following properties: higher current rating within single body dimensions tested according to IEC 44 which guaranties excellent ability to withstand repeated motor starting conditions low power losses low minimum-breaking-current high breaking capacity and excellent short circuit current limitation. Although a motor fuse is normally run at a stationary current which is much lower than the fuse rated current, the low-loss characteristics of the CMF fuses make them especially suitable in compact contactor compartments.. Nameplate STRIKER SCHLAGSTIFT I N = A TYPE CMF UN = 7,kV I1 = ka The symbols on the nameplate have the following meaning: I N = Rated current U N = Rated voltage I = Maximum short circuit current for which the fuse is tested 1 The arrowhead on the nameplate indicates in which end of the fuse link the indicator and striker pins appears. Additionally this end contact of the fuse links is specially marked. Force (N). Indicator and striker pin The CMF fuse links are equipped with a combined indicator and striker system, which is activated immediately when the fuse element melts. The force diagram is in accordance with the requirements of IEC 8-1 and DIN 4. Travel (mm) 11

12 Fuse link type CMF 4. Ordering table type CMF High voltage fuse links Type Rated Rated e Old No. New No. Weight voltage kv current A kg CMF, 0 9 NHPL0570R1 1YMB58M0001. CMF, 0 9 NHPL0571R1 1YMB58M000. CMF, 9 NHPL057R1 1YMB58M000. CMF, 0 9 NHPL057R1 1YMB58M CMF, 15 9 NHPL0574R1 1YMB58M CMF 7, NHPL05770R1 1YMB59M CMF 7, 0 NHPL05771R1 1YMB59M000.0 CMF 7, 0 NHPL0577R1 1YMB59M000.0 CMF 7, NHPL0577R1 1YMB59M CMF 7, 0 NHPL05774R1 1YMB59M CMF 7, 15 NHPL05775R1 1YMB59M CMF NHPL0577R1 1YMBM CMF 0 NHPL05777R1 1YMBM CMF 0 NHPL05778R1 1YMBM CMF NHPL05779R1 1YMBM FUSE BASE TYPE UCM 5. Ordering table UCM Rated Dimensions in mm Weight Type voltage Old No. New No. kv A A1 A H K K1 B kg UCM, ,7 NHP1907R1 1YMX1907R001 UCM 7,/ , NHP1907R 1YMX1907R00. Ordering table type CMF-BS Dimension CMF-BS kv, L A 48 7, Type Rated Rated e Old No. New No. Weight voltage kv current A kg CMF-BS, 0 9 NHPL147R1 1YMB51M0001. CMF-BS, 0 9 NHPL147R 1YMB51M000. CMF-BS, 9 NHPL147R 1YMB51M000. CMF-BS, 0 9 NHPL147R4 1YMB51M CMF-BS, 15 9 NHPL147R5 1YMB51M CMF-BS 7, NHPL147R 1YMB5M CMF-BS 7, 0 NHPL147R7 1YMB5M000.0 CMF-BS 7, 0 NHPL147R8 1YMB5M000.0 CMF-BS 7, NHPL147R9 1YMB5M CMF-BS 7, 0 NHPL147R 1YMB5M CMF-BS 7, 15 NHPL147R11 1YMB5M CMF-BS NHPL147R1 1YMB5M CMF-BS 0 NHPL147R14 1YMB5M CMF-BS 0 NHPL147R15 1YMB5M CMF-BS NHPL147R 1YMB5M

13 Fuse link type CMF Pre-arcing time Pre-arcing times Minutes / Minuten The characteristics are equal for all rated voltages and are recorded from cold condition. Dashed sections of the curves indicate the zone of uncertain interruption. 1 0 Seconds / Secunden 8 4 0,8 1 0, 0,4 0, , , Current / Strom in A Maximum cut of current ka (peak) 0 8. Current limitation CMF fuse links are current limiting. A large short circuit current will therefore not reach its full value. The diagram shows the relation between the prospective short circuit current and the peak value of the cut off current Overvoltages 1, Prospective current ka (rms) In order to be current limiting, the fuse links must generate an arc voltage exceeding the instantaneous value of the operating voltage. The overvoltage generated by the CMF fuse link is below the maximum permissible value acc to IEC 8-1. CMF fuse links can safely be used if the system line voltage is -0% of the rated fuse link voltage. 1

14 Fuse link type CMF Fuselink rating [A] 15 0 Motor run-up times not exceeding seconds 8 4 Number of starts per hour. Choice of fuse links Choice of rated voltage UN The rated voltage of the fuse links must be equal to, or higher than the operating line voltage. By choosing fuse link rated voltage considerably higher than the line voltage, the maximum arc voltage must not exceed the insulation level of the network motor starting current [A] Fuselink rating [A] Motor run-up times not exceeding 15 seconds 8 4 Number of starts per hour Choice of rated current I The minimum permissible current rating of the fuse link for motor protection may be determined from the selection charts I, II and III. The three different charts are for run-up times of, 15 and 0 seconds respectively. Each chart contains different characteristics, depending on the number of starts per hour. Of this specific number of starts per hour, the first two are in immediate succession, the rest being evenly spaced in the 1 hour period. The number of starts per hour indicates the time interval between separate starts. For example, 4 starts in 15 minutes are represented by starts per hour. N motor starting current [A] On the horizontal axis of the selection chart, the motor starting current is given, and along the vertical axis the current rating of the fuse link is found. Fuselink rating [A] Motor run-up times not exceeding 0 seconds 8 4 Number of starts per hour Selection procedure: Select the charts which are appropriate for the run-up time of the motor, select the starting current along the horizontal axis, depending on the number of starts per hour, select the correct characteristic (, 4, 8,, ), read of the correct rating of the fuse link on the vertical axis. Example: A B Starting current of the motor 8A 0A Run-up time sec. 15 sec. Number of starts per hour Chart number 1 Rated current of fuse link 0A 0A motor starting current [A] 14

15 Fuse link type CMF 11. Replacement of melted fuse links CMF fuse link cannot be regenerated. According to IEC, Publication 8-1, all fuse links should be replaced, even if only 1 or of the fuse links in the threephase system have operated. Exceptions are allowed when it can be verified that the fuse link(s) have not experienced any overcurrent.. The K-factor According to the IEC 44, the K-factor is a factor (less than unity) defining an overload characteristic to which the fuse link may be repeatedly subjected under specified motor starting conditions without deterioration. The overload characteristic is obtained by multiplying the current on the prearcing characteristic (melting time characteristics) by K.TheValue of K given in the data table is chosen at seconds melting time, and is valid for melting times between 5 and 0 seconds. 1. Data and dimensions CMF U I e D K* I I R P N N 1 O N Minimum Maximum kv A mm mm ka A mω Watt Pre-arc Interruption A s A s ,75 75, 49 1,4 17, ,7 0 1,94 75, ,7 0 1,4 75 7, , 70 1, , 900 0, , , 45 0,48, , ,9 7 1, 18 7, 0 5 0,7 0,9 119, ,7 0, , , 0 1, , 9 1, , , 77 0, ,75 75,7 1, ,7,04 155, ,7, , 91 *) The K-factor is referred to the average value of current. Legends: e = see figure D = see figure K = K-factor acc. to IEC 44 I 1 = max. short circuit current tested I = minimum breaking current R 0 = resistance at room temperature P N= power loss at rated current 15

16 is working to continuous improve the products. Therefore we reserve the right to change desig n, dimension and data without prior notice. TM This product has been certified by Group as Industrial IT Enabled - Information Level. All product information is supplied in interactive TM electronic format, based on Aspect Object technology. The Industrial IT commitment from ensures that every enterprise building block is equipped with the integral tools necessary to install, operate, and maintain it efficiently throughout the product lifecycle. 1YMB51-en Publication 04. Sp. z o.o. Power Technologies Division ul. Leszno Przasnysz, Poland Phone: (+48 ) , (+48 9) 75, 75 Fax: , export.plzwa@pl.abb.com

High voltage current limiting Fuse links type CEF

High voltage current limiting Fuse links type CEF High voltage current limiting Fuse links type CEF Index 1. General........................................... 9 2. Overvoltages...................................... 9 3. Pre-arcing times and cut-off characteristics..............

More information

Medium voltage products. Fuses

Medium voltage products. Fuses Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...

More information

Medium Voltage current limiting Fuse links

Medium Voltage current limiting Fuse links Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 200A 1. General information P&C Medium Voltage fuse-links named PCEF are designed

More information

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical

More information

Medium voltage products. Fuses

Medium voltage products. Fuses Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...

More information

Medium Voltage current limiting Fuse links

Medium Voltage current limiting Fuse links Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 0A 1. General information P&C Medium Voltage fuse-links named PCEF are designed to

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A DISTRIBUTION SOLUTIONS Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A Superior performance versus standard fuses ensuring up to 40% faster protection in case of low

More information

PowerIT Indoor Voltage Transformer Fuses, WBP. Outdoor Voltage Transformer Fuses, BRT. Catalogue 1YMB en. Industrial IT.

PowerIT Indoor Voltage Transformer Fuses, WBP. Outdoor Voltage Transformer Fuses, BRT. Catalogue 1YMB en. Industrial IT. PowerIT PowerIT Indoor Voltage Transformer Fuses, WBP Outdoor Voltage Transformer Fuses, BRT Catalogue 1YMB612070-en Industrial IT enabled TM 1. FEATURES Unlimited breaking capacity Short circuit current

More information

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction. HHD HIGH VOLTAGE GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main

More information

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction. HHD High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After

More information

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents HHM High Voltage Fuses Motor Circuit Protection DIN and British Standard SIBA Motor Rated Fuses are available in - German DIN Standard and - British Standard Design The large variety in body sizes / mounting

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links imum cold resistance power dissipation pre-arcing I t value total I t value [kv] (mm) I n [A] (ka) [mω] [W] [A s] [A s] 1 580,1 57 A 0 370 9 17,3 1 A 5 00 10 3 30 10 A 55 7 11

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links [A] (ka) [mω] [W] [A 2 s] [A 2 s] 12 580 4 6,1 57 4 A 20 370 9 17,3 164 6 A 25 260 10 36 340 10 A 46 55 7 161 1 530 16 A 60 37 13 250 2 270 20 A 80 30 15 430 3 750 25 A 105 25

More information

Limitor -G General Purpose Fuses

Limitor -G General Purpose Fuses Limitor -G General Purpose Fuses HIGH VOLTAGE IEC FUSES DIN HV GENERAL PURPOSE FUSES FOR TRANSFORMERS FEATURES & BENEFITS Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear

More information

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV. DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

MEDIUM VOLTAGE DIN Fuse-Links

MEDIUM VOLTAGE DIN Fuse-Links Standards/Approvals: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) Catalogue Symbol: 24TDMEJ(amp) 24THMEJ(amp) 24TFMEJ(amp) 24TXMEJ(amp) Class of Operation: Back-up as IEC 60282-1

More information

MEDIUM VOLTAGE DIN Fuse-Links

MEDIUM VOLTAGE DIN Fuse-Links Standards/Approvals: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) Catalogue Symbol: 12TDLEJ(amp) 12THLEJ(amp) 12TKLEJ(amp) 12TXLEJ(amp) 12TFMSJ(amp) Class of Operation: Back-up

More information

High voltage high-breaking capacity VV fuse-links

High voltage high-breaking capacity VV fuse-links High fuse-links High fuse-links High high-breaking capacity VV fuse-links VV General information ET fuse-links named VV THERMO are designed to protect devices in switch-gears and other equipment (distribution

More information

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000

More information

Selection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection

Selection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection HHD-BPT Selection Guide HHD-BPT, DIN Style, Current-imiting,, Potential Transformer Protection Current ratings [A]; 0.5, 1, 2, 2.5, 3.15, 4, 5 E=192mm Page E=292mm Page E=367mm Page E=442mm Page E=537mm

More information

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH HH DRIESCHER - High-voltage high breaking capacity fuses from 1 kv up to 36 kv HH HH ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-866 MOOSBURG TEL. +9 87 61 6 81-0 FAX +9 87 61 68 11 37 http://www.driescher.com

More information

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017 HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION March 2017 HV FUSE-LINKS IN THE WORLD UL STANDARD E OR R RATED: AMERICAN STANDARD DIN STANDARD: GERMAN STANDARD FR STANDARD: FRENCH STANDARD BS STANDARD: BRITISH

More information

Medium voltage fuses - European Fuses

Medium voltage fuses - European Fuses HV Back-up Fuse-Links according to IEC 60 282- HV fuse-links have been used for reliable protection in medium-voltage switchgear and controlgear and systems for decades. They protect apparatus and equipment

More information

Applications. Fuse range selection. Motors Power transformers. Voltage (kv)

Applications. Fuse range selection. Motors Power transformers. Voltage (kv) Presentation Applications Fuse range selection 0550N 05579N Public distribution Protection of motors Our Fusarc CF, Soléfuse, Tépéfuse and MGK fuses make up a broad, consistent and uniform range of high

More information

RAPIDPLUS. high speed fuse links for semiconductors

RAPIDPLUS. high speed fuse links for semiconductors high speed fuse links for semiconductors RAPIDPLUS 2 PAGE04 ar HIGH SPEED FUSE LINKS FOR SEMICONDUCTORS PAGE05 gr HIGH SPEED FUSE LINKS FOR SEMICONDUCTORS PAGE06 gs NH HIGH SPEED FUSE LINKS FOR SEMICONDUCTORS

More information

new NH fuse-links (HRC) rated rated breaking type current voltage capacity size description price

new NH fuse-links (HRC) rated rated breaking type current voltage capacity size description price NH fuse-links (HRC) rated rated breaking type current voltage capacity size description price gg fuselinks 500V (IEC60269 - VDE0636 - DIN43620) with fuse blown indication NH Fuse links gg class with high

More information

IEC Standard Back-Up Fuse-Links

IEC Standard Back-Up Fuse-Links 3 / 7.2 kv 6 / 12 kv 10 / 17.5 kv 10 / 24 kv 20 / 36 kv Ferrule German DIN Standard Beyond our line of ANSI / IEEE current-limiting fuses, Mersen offers a full line of medium voltage fuse links according

More information

Fuse-Links according to VDE 0670 T 402. Hi gh-voltage

Fuse-Links according to VDE 0670 T 402. Hi gh-voltage High-Voltage Fuse-Links according to VDE 0670 T 402 Hi gh-voltage Limitor Notes 2 Ferraz Shawmut is global leader in fuse-based electrical protection solutions. Our brand is worldwide renowned for technical

More information

High-Voltage Fuse Links according to IEC

High-Voltage Fuse Links according to IEC High-Voltage Fuse Links according to IEC 60282- Limitor Ferraz Shawmut is global leader in fuse-based electrical protection solutions. Our brand is worldwide renowned for technical expertise, innovative

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

HHB. Medium Voltage Fuses British Standard. Introduction. Fuse-links for oil insulated switchgear

HHB. Medium Voltage Fuses British Standard. Introduction. Fuse-links for oil insulated switchgear HHB Medium Voltage Fuses British Standard For Oil Insulated Switchgears Introduction Medium voltage fuse-links according to British Standard are back-up fuse-links for the protection of substations up

More information

Thermal system protection of switchgear through high voltage fuse links with integrated temperature limiter under consideration of IEC 420:1990

Thermal system protection of switchgear through high voltage fuse links with integrated temperature limiter under consideration of IEC 420:1990 66 Thermal system protection of switchgear through high voltage fuse links with integrated temperature limiter under consideration of IEC 420:1990 Dipl.-Ing. U. Haas SIBA, Sicherungen-Bau GmbH, Lünen,

More information

Special Purpose Fuses

Special Purpose Fuses Special Purpose Fuses Fuses for DC voltage applications www.eti.si ETI Elektroelement d.d. Obrezija 5, SI - 111 Izlake Slovenija Tel. + 38 03 5 57 570 Faks + 38 03 5 7 077 eti@eti.si NH DC 80 V - Telecom

More information

CYLINDRICAL FUSES. 8x32. 10x38. 14x51. In REFERENCE U BREAKING CAPACITY REFERENCE U BREAKING CAPACITY PACKING (A) IEC /95/EC

CYLINDRICAL FUSES. 8x32. 10x38. 14x51. In REFERENCE U BREAKING CAPACITY REFERENCE U BREAKING CAPACITY PACKING (A) IEC /95/EC fuses 02 gg 04 am gg Cylindrical fuse links gg class for use as general protection against overloads and short circuits, intended as protection of cables, power lines and equipment. Made of ceramic tube

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

RAPIDPLUS. high speed fuse links for semiconductors

RAPIDPLUS. high speed fuse links for semiconductors high speed fuse links for semiconductors RAPIDPLUS 2 PAGE04 ar PAGE05 gr PAGE06 gs NH ar RAPIDPLUS ar fuse links are intended to clearing short-circuits and have been designed and manufactured to have

More information

Paramount HRC Cartridge

Paramount HRC Cartridge Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing

More information

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30 Characteristics TeSys contactors Mini-contactors TeSys LC SK and LP SK Environment Rated insulation voltage (Ui) Conforming to 0, VDE 00 gr C,BS, CSA - n, UL 0 V 0 Conforming to standards IEC 0, NF C -0,

More information

gi-gl-gg, am gi-gl-gg gi-gl-gg NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories

gi-gl-gg, am gi-gl-gg gi-gl-gg NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories ,, FUSE BASES, AND ACCESSORIES Ferraz Shawmut NH Fuse-links, sizes 00, 0, 1, 2, 3 and 4 are rated 500 or 690 Volts AC with breaking capacities of 80kA or 120kA. All fuse-links include an indicator or striker

More information

gg, am NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories NH DIMENSION KNIFE-BLADE FUSE-LINKS, FUSE BASES, AND ACCESSORIES

gg, am NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories NH DIMENSION KNIFE-BLADE FUSE-LINKS, FUSE BASES, AND ACCESSORIES , am, FUSE BASES, AND ACCESSORIES Ferraz Shawmut NH Fuse-links, sizes 000, 00, 0, 1, 2, 3, 4 and 4a are rated 500 or 690 Volts AC with breaking capacities of 80kA or 120kA. All fuse-links include an indicator

More information

INDUSTRIAL CYLINDRICAL FUSE LINKS

INDUSTRIAL CYLINDRICAL FUSE LINKS gg Cylindrical gg class for use as general protection against overloads and short circuits, intended as protection of cables, power lines and equipment. Made of ceramic tube with high withstand to internal

More information

Low-Peak 600V Class RK1

Low-Peak 600V Class RK1 LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:

More information

NH fuse-links am VAC with striker, size 0, 1, 2, 3, 4

NH fuse-links am VAC with striker, size 0, 1, 2, 3, 4 NH fuse-links am 500-690VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions according to DIN 43 620 Parts 1 to 4 Lead free contact blades 0% cadmium APPLICATIONS am: Partial purpose,

More information

Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES

Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES TECHNICAL SPECIFICATIONS L.V- HRC KNIFE (NH TYPE) FUSE-LINKS ( V.AC) HRC knife fuse-links (NH Type) must have a rated breaking capacity current of

More information

Low Voltage Industrial Type T Fuse Links

Low Voltage Industrial Type T Fuse Links Low Voltage Industrial Type T Fuse Links Type T HRC Fuse Links for Industrial and General Application Contents Introduction 2 Performance Data 3 List Numbers and Dimensions 4 Utilisation Categories 8 Application

More information

LG HRC Power Fuses ISO 9001 ISO 14001

LG HRC Power Fuses ISO 9001 ISO 14001 LG HRC Power Fuses ISO 900 ISO Current without Power Fuse (ka ms) Ipeak Let through Below 0.5 Cycle voltage(kv) Initiation of 3. 7. 5.5 3 arcing(degree) Ipeak(kA) Power Factor 5 5 90 5 70 9 0 7 7 7 5 5

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Semiconductor Fuses European Fuses

Semiconductor Fuses European Fuses 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos

More information

onlinecomponents.com

onlinecomponents.com 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current

More information

Low voltage NH knife-blade fuse-links

Low voltage NH knife-blade fuse-links Low voltage NH knife-blade fuse-links NV KOMBI advantages ETI is introducing a new generation of low-voltage fuse-links from size NV00C up to NV3 with new, dual indication of fuse-link operation, called

More information

General information on current-limiting fuse-links. The main characteristics of the CNC fuse-links. Construction. Operating.

General information on current-limiting fuse-links. The main characteristics of the CNC fuse-links. Construction. Operating. General information on current-limiting fuse-links The high-voltage back-up current-limiting fuse-links are designed for protection of systems which include transformers, against the destructive results

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics 450 TO 700VAC / 63 TO 2800A Recognized Exceptionally low I 2 T, Watt losses. Non-magnetic construction, Highly reliable low voltage Trip-indicator system, conformity to UL, IEC, DIN

More information

FUSE-LINKS FOR PHOTOVOLTAIC APPLICATIONS

FUSE-LINKS FOR PHOTOVOLTAIC APPLICATIONS 1 2 06 PML 10/14x85 1500V FUSE HOLDERS 08 CLIP CONTACT FOR φ10 FUSE LINKS 05 PMX & 14x51 FUSE HOLDERS 02 gpv & 14x51 600 &/1100 FUSE LINKS 03 gpv 1200 & 1500V FUSE LINKS 04 gpv NH1, NH2 & NH3 FUSE LINKS

More information

Bussmann 7.2 kv Medium voltage fuse links

Bussmann 7.2 kv Medium voltage fuse links Supersedes November 2008 Product description s range of 7.2 kv DIN Medium voltage fuse links are suitable for transformer protection. These fuse links can be used even where there is no secondary LV protection,

More information

CI-TI Contactors and motor starters Types CI 61 - CI 98

CI-TI Contactors and motor starters Types CI 61 - CI 98 Data sheet CI-TI Contactors and motor starters s CI 6 - CI 98 Contactors CI 6, CI 7, CI 86 and CI 98 switch powers of up to 0 kw, 7 kw, 45 kw and 55 kw respectively under 80 V - loads. Accessories include

More information

Medium Voltage Distribution. Fuses. from 3.6 to 36 kv. Catalogue 2012

Medium Voltage Distribution. Fuses. from 3.6 to 36 kv. Catalogue 2012 Medium Voltage Distribution Fuses from 3. to 3 kv Catalogue 01 Medium voltage fuses from 3. kv to 3 kv Contents Applications Fuse range selection Main characteristics Fusarc CF, Soléfuse, Tépéfuse, MGK

More information

HV-Fuse-links SSK type SSK 10/02

HV-Fuse-links SSK type SSK 10/02 HV-Fuse-links SSK type SSK 10/0 Reg.-Nr. 0/QM/07.00 QM-System-Audit DIN EN ISO 9001 UMWELTMANAGEMENTSYSTEM DQS - zertifiziert nach DIN EN ISO 1001 Reg.-Nr. 1-0 SICHERUNGEN/FUSES SIBA Sicherungen-Bau GmbH

More information

Contactor-Fuse Combination 3TL62 / 63 / 66

Contactor-Fuse Combination 3TL62 / 63 / 66 Contactor-Fuse Combination TL6 / 6 / 66 Medium-Voltage Equipment Selection and Ordering Data Catalog HG. 00 Answer for energy. Contactor-Fuse Combination TL6 / 6 / 66 R-HG-.tif Siemens HG. 00 Contactor-Fuse

More information

Special Purpose Fuses

Special Purpose Fuses Special Purpose Fuses Multimeter fuses Metering Fuses Telecom fuses NH 80V Fuses for DC voltage applications NH am 00V a.c. NH gg 0V a.c. Safe work fuses SWF Fuses for protection of forklift batteries

More information

Short Circuit. Sizes 0, 1, 2, and 690 Volt ratings - 32A through 630A All ratings include striker. 0% Lead

Short Circuit. Sizes 0, 1, 2, and 690 Volt ratings - 32A through 630A All ratings include striker. 0% Lead , am nh dimension knife-blade fuse-links, fuse bases, and accessories Ferraz Shawmut NH Fuse-links, sizes 000, 00, 0, 1, 2, 3, 4 and 4a are rated 500 or 690 Volts AC with breaking capacities of 80kA or

More information

Practical and completely safe

Practical and completely safe FUSE RRIERS >>> Practical and completely safe Isolating fuse carriers 058 06 058 28 Dimensions (p. 0) onform to standard IE 60269-2/2. and to NF 63-2. Isolators conform to IE 60947-3. Icc: - 20 k with

More information

fuses fuse holders CYLINDRICAL

fuses fuse holders CYLINDRICAL fuses fuse holders 02 gg FUSES 04 am FUSES FUSES 09 PMC COMPACT 09 -CC FOR CC CLASS FUSE-LINKS 11 PMB PLUG CONNECTION 11 CLIP CONTACT FOR φ10 FUSE-LINKS 10 PMF 11 BAC OPEN FUSE BASES 06 gg FUSES FUSES

More information

Bussmann series NH catalogue. Leadership in circuit protection

Bussmann series NH catalogue. Leadership in circuit protection Bussmann series NH catalogue Leadership in circuit protection Energizing a world that demands more. We deliver: Electrical solutions that use less energy, improve power reliability and make the places

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

MV SWITCHGEAR 511. CF / SOLEFUSE / TEPEFUSE / MGK MV current limiting fuses With thermally operated striker From 3.6 to 36 kv

MV SWITCHGEAR 511. CF / SOLEFUSE / TEPEFUSE / MGK MV current limiting fuses With thermally operated striker From 3.6 to 36 kv MV SWITCHGEAR 5 MV current limiting fuses With thermally operated striker From 3. to 3 kv In line with our customers and their needs. In a sector like energy, which requires the maximum collaboration between

More information

Mica Element Support. Compacted Quartz Sand. Length B

Mica Element Support. Compacted Quartz Sand. Length B Construction A Tin-Plated Brass Caps Dimensional Information for Trans-Guard s NOMINAL 5.5 Resin-Rich Filament Wound Glass/Epoxy Body 3 75 80 200 3 50 5 80 5 125 3 50 5 5 100 23.0 50 Low Current Interruption

More information

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products Hi-Tech SX Full-Range Current-Limiting Fuses Provides both overload and fault current protection for distribution equipment in a single fuse body. Trans-Guard SX Full-Range Current-Limiting Fuse As a full-range

More information

Medium voltage fuses Medium voltage fuses

Medium voltage fuses Medium voltage fuses European Fuses DIN Fuses 7.2kV - 36kV IBD 7.2 UP TO 36 KV HIGH-VOLTAGE FUSES DESIGNED FOR POWER TRANSFORMER PROTECTION INTERIOR/EXTERIOR USE CERAMIC HOUSING MEDIUM CLASS TRIP-INDICATOR COMBINED WITH A

More information

GE Power Controls. Low Voltage HBC Fuselinks. For more information, please contact: MAJESTIC GLOBAL LTD.

GE Power Controls. Low Voltage HBC Fuselinks. For more information, please contact: MAJESTIC GLOBAL LTD. GE Power Controls Low Voltage HBC Fuselinks For more information, please contact: MAJESTIC GLOBAL LTD. www.mgl.hk GE Power Controls type NS/T/TS range of High Breaking Capacity (HBC) fuselinks are extensively

More information

Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors

Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors 90 Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors Environment characteristics Conforming to standards IEC 60947, NF C 63-110, VDE 0660, BS 5424 Product certifications LCp

More information

EUROPEAN HIGH VOLTAGE FUSES

EUROPEAN HIGH VOLTAGE FUSES EUROPEAN HIGH VOLTAGE FUSES AS PER IEC 60282 EDUPACK TRAINING MODULE 2012 HH DIN NF MEDIUM OR HIGH VOLTAGE FUSE? High Voltage is the official definition provided by the standard. High Voltage starts just

More information

3.6kV 36kV High Voltage DIN Distribution Fuses

3.6kV 36kV High Voltage DIN Distribution Fuses 3.6kV 36kV High Voltage DIN Distribution Fuses DIN Dimension Fuses To Specification DIN 43.625 This product group covers current limiting fuses with dimensions to DIN 43.625 and performance in compliance

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air) Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear ETS12-01-02 Specification ETS12-01-02 Ver 3 Contents 1. Purpose

More information

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders ETS12-01-01 Specification ETS12-01-01 Ver 3 Contents 1. Purpose and Scope... 1 2. References...

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

Low Voltage A GE Power Controls Company. General catalogue

Low Voltage A GE Power Controls Company. General catalogue Low Voltage A GE Power Controls Company General catalogue this is a blanc page Miniature circuit breakers A Miniature circuit breakers AC miniature circuit breakers Benefits of the new MCB s A 3 The AEG

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Fuses for Semiconductor Protection - European Standard. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits

Fuses for Semiconductor Protection - European Standard. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits Fuses for Semiconductor Protection - European Standard Class: ar Voltage ratings: 660V AC to 1000V AC Current ratings: 16 A to 400 A Standards: UL 248-13 IEC 60269-1 & 4 DIN VDE 0636-40 DIN 43653 Approvals:

More information

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX File: PCUP-09-002_EX Outdoor Use Indoor Use The Trans-Guard EX full-range current-limiting capacitor fuse provides both low and high current fault protection in a single, compact fuse body. As a full-range

More information

BUSSMANN. Leadership in fusible circuit protection solutions SERIES. Bussmann series Medium voltage fuse links catalogue

BUSSMANN. Leadership in fusible circuit protection solutions SERIES. Bussmann series Medium voltage fuse links catalogue Bussmann series Medium voltage fuse links catalogue BUSSMANN SERIES Leadership in fusible circuit protection solutions Energizing a world that demands more. Discover today s Eaton. Powering business worldwide

More information

British BS 88 Fuses. High Speed Fuses. Introduction. General Information

British BS 88 Fuses. High Speed Fuses. Introduction. General Information British BS 88 Fuses Introduction British BS 88 Contents Fuse Volts Amp Range Page 0-900 15-17 90-78-1 Accessories Indicator System & Fuse Bases British BS 88 Fuse Ranges Amps Vac Vdc -900 0 150-710 90

More information

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

Approved Standards. Ordering Information. Thermal Overload Relay J7TKN. Model Number Legend. Thermal Overload Relay. Accessories

Approved Standards. Ordering Information. Thermal Overload Relay J7TKN. Model Number Legend. Thermal Overload Relay. Accessories Thermal Overload Relay J7TKN ) Thermal Overload Relay Direct and separate mounting Single phasing sensivity according to IEC 60947-4-1 Finger proof (BGV A2) Accessories Set for single mounting Approved

More information

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification 543 technical hotline +44 ()1268 56372 Standards and approvals Sentry MCBs are designed to fully comply with the relevant requirements of BS EN 6898: 23. They all feature positive contact status indication

More information

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a NH fuse-links gg 69VAC NH fuse-links gg 69VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions in accordance with DIN 43 62 Live tags Top indicator Lead free contact blades % cadmium

More information

Voltage and Auxiliary Transformer Fuse Links

Voltage and Auxiliary Transformer Fuse Links British Standard VT Fuse Links. A range of voltage transformer primary Fuse Links to BS9- and IEC-. Wide range of ratings from kv to kv. Amp industry standard current ratings. CAV range with ratings from.kv

More information

Product Catalog Medium Voltage Fuses. Circuit Protection

Product Catalog Medium Voltage Fuses. Circuit Protection Product Catalog General Catalog Contents (Con t.) Page R-Rated Fuses 2.75 to 5.5kV........................................0 E-Rated Fuses 5.5kV MV055.......................................05 8.25kV.............................................09

More information

NH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3

NH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3 NH fuse-links gg 4VAC double indicator/live gripping-lugs size,, 1, 2, 3 NH fuse-links gg 4VAC double indicator/live gripping-lugs size,, 1, 2, 3 LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS

More information

Accessories. For product data sheets, visit

Accessories. For product data sheets, visit British BS 88 Introduction British BS 88 Contents Fuse Volts Amp Range Page 0-900 188-190 90-791-19 Accessories Indicator System & Fuse Bases 195 British BS 88 Fuse Ranges Amps Vac Vdc -900 0 150-710 90

More information

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil)

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil) Ergon Energy Corporation Limited Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear ETS12-01-03 Specification ETS12-01-03 Ver 3 Contents 1. Purpose and Scope...

More information

FX Full-Range Current-Limiting Fuse

FX Full-Range Current-Limiting Fuse Hi-Tech FX Full-Range Current-Limiting Fuses Trans-Guard FX Full-Range Current-Limiting Fuse Patented damage sensor significantly reduces the risk of fuse failure should the fuse be subjected to an element-damaging

More information

Medium Voltage Fuse Links Full Line Catalogue

Medium Voltage Fuse Links Full Line Catalogue Medium Voltage Fuse Links Full Line Catalogue Medium Voltage Fuse Links Full Line Catalogue Cooper Bussmann, a division of Cooper Industries, is the leading source of circuit protection solutions in the

More information

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements. Datasheet Single- and three-phase switched-mode power supply units NEW The new power supplies offer a wide range of robust solutions for demanding application requirements. C SEMI F47 US Designed for high

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated