Applications. Fuse range selection. Motors Power transformers. Voltage (kv)

Size: px
Start display at page:

Download "Applications. Fuse range selection. Motors Power transformers. Voltage (kv)"

Transcription

1 Presentation Applications Fuse range selection 0550N 05579N Public distribution Protection of motors Our Fusarc CF, Soléfuse, Tépéfuse and MGK fuses make up a broad, consistent and uniform range of high breaking capacity fuses and limiters. They are all of combined type and they are constructed so that they can be installed both indoors and outdoors (according to the type). Their main function is to protect medium distribution devices (from 3 to 3 kv) from both the dynamic and thermal effects of short circuit s greater than the fuse s minimum breaking. Considering their low cost and their lack of required maintenance, medium fuses are an excellent solution to protect various types of distribution devices: b medium consumers (transformers, motors, capacitors, etc.); b public and industrial electrical distribution networks. They offer dependable protection against major faults occuring either on medium or low circuits. This protection can be further enhanced by combining the fuses with low protection systems or an over relay. Selection table Depending on the equipment to be protected and its rating, the table below gives the range of fuses which are suited to the protection application. Voltage Motors Power transformers Capacitors Voltage transformers 3. Fusarc CF Fusarc CF Fusarc CF Fusarc CF MGK 7. Fusarc CF Fusarc CF Fusarc CF Fusarc CF MGK Soléfuse Soléfuse Fusarc CF Fusarc CF Fusarc CF Tépéfuse Soléfuse Soléfuse Fusarc CF 7.5 Fusarc CF Fusarc CF Tépéfuse Soléfuse Soléfuse Fusarc CF Fusarc CF Fusarc CF Tépéfuse Soléfuse Fusarc CF Soléfuse 3 Fusarc CF Fusarc CF Tépéfuse Soléfuse Soléfuse Fusarc CF Soléfuse (UTE standard; transformer protection) 0557N MGK (UTE standard; motor protection) Fusarc CF (DIN standard; transformer, motor and capacitor protection) Tépéfuse (UTE standard; transformer protection) Schneider Electric

2 Presentation Main characteristics 0553N Key characteristics The most significant features provided by our range of fuses are as follows: b high breaking capacity; b high limitation; b dependable interruption of critical s; b low breaking over; b low dissipated power; b no maintenance or ageing; b for indoor and outdoor; b with a striker for indication and tripping. Standards Our fuses are designed and manufactured according to the following standards: b IEC--, IEC-77 (Fusarc CF, Soléfuse,Tépéfuse, MGK); b DIN 35 (Fusarc CF); b VDE (Fusarc CF); b UTE C00, C (Soléfuse, Tépéfuse). Quality assurance system In addition to being tested in our own laboratories, as well as in official laboratories such as the CESI, Les Renardiers and Labein, with their own respective certificates, our fuses are manufactured according to quality guidelines within the framework of the ISO-900 and ISO- quality system certification awarded by the AENOR (IQ-NET) which provides additional guarantees for customers. Testing During manufacture, each fuse is subject to systematic routine testing with the aim of checking its quality and conformity: b dimensional control and weight control; b visual control of markings, labelling and external appearance; b electrical resistance measurement: a key point to ensure that the fuses have the required performance levels at the end of the production process and to check that no damage has occured during assembly. Measurement of the room temperature resistance of each fuse is therefore carried out in order to check that they are in line with values according to their rated and rated. Furthermore we carry out internal type-testing on our fuses in order to comply with our quality policy. Seal testing: in order to test the sealing of our Fusarc CF fuses, they are plunged into a hot water bath (0 C) for 5 minutes, according to standard IEC -. Quality certified to ISO 900 and ISO A major advantage Within each of its production units, Schneider Electric integrates a functional organisation whose main mission is to check quality and monitor compliance with standards. MESA, the only company within Schneider that makes fuses, is certified by AENOR (the Spanish Standards Association), and is certified to ISO 900 and ISO (IQ-NET). Schneider Electric 3

3 Presentation Main characteristics MT000 Key definitions Un: rated This is the highest between phases (expressed in kv) for the network on which the fuse might be installed. In the medium range, the preferred rated s have been set at: and 3 kv. In: rated This is the value that the fuse can withstand on a constant basis without abnormal temperature rise (generally 5 K for the contacts). Dependable operating range I3: minimum rated breaking This is the minimum value which causes the fuse to blow and break the. For our fuses, these values are of between 3 and 5 times the In value. Comment: it is not enough for a fuse to blow to interrupt the flow of. For values less than I3, the fuse will blow, but may not break. Arcing continues until an external event interrupts the. It is therefore essential to avoid using a fuse in the range between In and I3. I: critical s (s giving similar conditions to the maximum arc energy). The value of I varies between 0 and times the In value, depending on then design of the fuse element. If the fuse can break this, it can also break s between I3 and I. I: maximum rated breaking This is presumed fault that the fuse can interrupt. This value is very high for our fuses ranging from 0 to 3 ka. Comment: it is necessary to ensure that the network short circuit is at least equal to the I of the fuse that is used. Figure : definition of a fuse s operating zones. Information to provide on ordering The customer has to give certain key data when ordering to avoid any misunderstandings. This includes the following: b rated ; b operating ; b rated ; b transformer power (or motor power); b operating conditions (open air, cubicle, fuse chamber, etc.); b fuse length and cap diameter; b standards. For orders, please note the reference and characteristics of the fuses. Schneider Electric

4 Fusarc CF, Soléfuse, Tépéfuse, MGK Construction MT0009EN force (N) travel (mm) Figure : this graph shows the value of the force provided by the striker according to its length of travel. End contact caps () Together with the enclosure, they form an assembly which must remain intact before, during and after breaking the. This is why they have to withstand mechanical stresses and sealing stresses due to overpressure caused by arcing. They also have to provide the stability of the internal components over time. Enclosure () This part of the fuse must withstand certain specific stresses (related to what has already been mentioned): b thermal stresses: the enclosure has to withstand the rapid temperature rise that occurs when the arc is extinguished. b electrical stresses: the enclosure has to withstand the restoring of after breaking. b mechanical stresses: the enclosure has to withstand the increase in pressure caused by expansion of the sand when breaking occurs. Core (3) This is a cylinder surrounded by ceramic fins onto which the fuse element is wound. The striker control wire together with the latter are lodged within the cylinder. They are insulated from the fuse elements. Fuse element () This is the main component of the fuse. Materials with low resistivity and which do not suffer wear over time are used. Our fuses have fuse elements with a carefully chosen configuration, defined after a lot of testing. This allows us to achieve the required results. Extinction powder (5) The extinction powder is made up of high purity quarzite sand (over 99.7%), which is free from any metal components and moisture. When it vitrifies, the sand aborbs the energy produced by the arc and forms an insulating component called fulgurite with the fuse element. Striker () This is a mechanical device which indicates the correct functioning of the fuse. It also provides the energy required to actuate a combined breaking device. The striker is controlled by a heavy duty wire which, once the fuse element has blown, also melts and releases the striker. It is important that the control wire does not cause the premature tripping of the striker, nor must it interfere with the breaking process. The strikers used on our fuses are of medium type and their force/travel characteristics (approximately joule according to standard IEC-.) are illustrated in figure. - contact caps - enclosure 3 - core - fuse element 5 - extinction powder - striker MT Cross sectional diagram of a fuse Schneider Electric 5

5 Fusarc CF Characteristics and dimensions MT00 Dimensions Ø5 33 striker * The following page gives the diameter and length of the fuse according to its rating. L* Ø* 33 Ø 3 Fusarc CF This is Schneider Electric s DIN standard fuse range. When designing this range, we paid particular attention to minimise power dissipation. It is increasingly common to use RMU units with SF gas as the insulating material. In view of these operating conditions, in which the fuse is inserted inside a hermetically sealed fuse chamber virtually without any ventilation, these fuses avoid the premature ageing, both of themselves and of the whole device, which would be caused by a non-optimised fuse. The enclosure in the Fusarc CF range up to A (rated ) is made from crystallised brown porcelain, which withstands ultra violet radiation and can therefore be installed both outdoors as well as indoors. Fuses with rated values greater than A have glass fibre enclosures and are only for indoor installations. You will find the full list of the Fusarc CF range in the table given on the following page. With rated s ranging from 3 to 3 kv and rated s of up to 50 A, customers can meet their exact requirements in terms of switchgear short circuit protection. Time/ fuse curves These characteristic curves show the rms value for each type of fuse and how this correlates with the associated fusing duration or pre-arc duration. Careful selection and design of fuse elements, together with meticulous industrial control, ensures an accuracy limit of ±%, i.e. more demanding than that recommended in IEC standards. During the design of our Fusarc CF fuses, we focused on a relatively high fusing at 0. s in order to withstand transformer making s and at the same time a low fusing at s in order to achieve quick breaking in the case of a fault. See page for the time/ characteristics of Fusarc CF fuses. Current limitation curves The Fusarc CF fuse range is specially adapted to protecting transformers from short circuits. Short circuits will not reach their maximum value if you choose a Fusarc CF fuse with a correct rated. For example, as shown in the limitation curves on page, for a short circuit whose presumed is 5 ka in an unprotected installation, the maximum value would be 7 ka for symmetrical flow and 3 ka for an asymmetrical case. If we had used a Fusarc CF fuse with a rated of A, the maximum value reached would have been.5 ka. Fusarc CF fuses installed in an SM type fuse-switch Fusarc CF fuses installed in an RM distribution cubicle 055N 055N Schneider Electric

6 Fusarc CF References and characteristics Reference Rated Operating Rated (A) Max. breaking I (ka) Min. breaking I3 (A) Room temp. resistance* (mω) Dissipate of power (W) Length Diameter (mm) (mm) (kg) AR 3. 3/ M M M M M M M M0 7. 3/ M M Weight M M BN BP BQ BR M M M M M M M M0 / M M M M CN , CP CQ M M M M M M M M M0 7.5 / M M M M M M M M M M M M M M M0 / M M M M M M M M M M M0 3 0/ M M M M *Resistances are given at ±% for a temperature of 0 C. Schneider Electric 7

7 Fusarc CF Fuse and limitation curves Fuse curve kv Time (s) MT00 0 A.3 A A A 0 A 5 A 3.5 A 0 A 50 A 3 A 0 A A 5 A A 00 A 50 A Current (A) Limitation curve kv Maximum value of the limited broken (ka peak) The diagram shows the maximum limited broken value as a function of the rms value which could have occured in the absence of a fuse. MT003 Ia =. Ik Is = Ik 50 A 00 A A 5 A A 0 A 3 A 50 A 0 A 3.5 A 5 A 0 A A A.3 A A Rms value of the presumed broken (ka) Schneider Electric

8 Soléfuse References and characteristics The Soléfuse ranges of fuses is manufactured according to standard UTE C00. Their rated varies from 7. to 3 kv. they can be supplied with or without a striker and their weight is of around kg. They are mainly intended to protect power transformers and distribution networks, and are solely intended for indoor installations (glass fibre enclosure). Electrical characteristics Reference Rated Operating Rated Min. breaking Max. breaking Room temp. resistance* Room temp. resistance* (A) I3 (A) I (ka) with striker (mω) without striker (mω) reference 7573 BC BE BH 7. 3./ BK BN CM / DL / EC EC 7573 EE EE 7573 EH 3./ EH 7573 EJ EJ 7573 EK EK 7573 FC FD FE 3 30/ FF FG FH *Resistances are given at ±% for a temperature of 0 C. Dimensions striker MT00 50 Ø Ø max. Weight:.3 kg Schneider Electric 9

9 Soléfuse Fuse and limitation curves Fuse curve kv Time (s) MT A A A 0 5 A 3.5 A 3 A 3 A 0 A A 5 A Limitation curve kv Maximum value of limited broken (ka peak) Current (A) The diagram shows the maximum limited broken value as a function of the rms value which could have occured in the absence of a fuse. MT00 Ia =. Ik Is = Ik 5 A A 0 A 3 A 3 A 3.5 A 5 A 0 A A A.3 A Rms value of presumed broken (ka) Schneider Electric

10 Tépéfuse, Fusarc CF (metering transformer protection) References, characteristics and curves Type Reference Rated Operating We manufacture Tépéfuse and Fusarc CF type fuses intended for metering transformer protection which have the following references and characteristics: Characteristics Rated (A) Max. breaking I (ka) Min. breaking I3 (A) Length Diameter (mm) (mm) (kg) Tépéfuse 75 A < 75 B 3./ Fusarc CF MO 7. 3/ *Resistances are given at ±% for a temperature of 0 C. Tépéfuse fuses are made only in glass fibre when intended for indoor usage. Fuses for transformer protection are made without strikers. Weight MO / MO MO / MO MO 3 0/ Dimensions 33 MT005 Ø 5 Ø 50.5 MT007 Ø L Fusarc CF 5 Tépéfuse 30 Fuse curve kv Time (s) MT00 0 A 0.3 A.5 A Current (A) Schneider Electric

11 MGK References, characteristics and curves MGK fuses are intended to protect medium motors at 7. kv (indoor application). MT00 Dimensions Ø weight. kg 3 striker Electrical characteristics Reference Rated Operating rated (A) Min. breaking I3 (A) Max. breaking I (ka) Room temp. resistance* (mω) y *Resistances are given at ±% for a temperature of 0 C. Fuse curve 7. kv Time (s) MT000 0 A 5 A A 00 A 50 A Limitation curve 7. kv Maximum value of limited broken (ka peak) Current (A) The diagram shows the maximum limited broken value as a function of the rms value which could have occured in the absence of a fuse. MT00 Ia =. Ik Is = Ik 50 A 00 A A 5 A A Rms value of presumed broken (ka) Schneider Electric

12 Selection and usage guide General Transformer protection MT00 I cc Short circuit General According to their specific characteristics, the various types of fuses (Fusarc CF, Soléfuse, Tépéfuse and MGK) provide real protection for a wide variety of medium and high equipment (transformers, motors, capacitors). It is of the utmost importance to always remember the following points: b Un of a fuse must be greater than or equal to the network. b I of a fuse must be greater than or equal to the network short circuit. b the characteristics of the equipment to be protected must always be taken into consideration. Even if only one fuse blows, it is recommended to change all three since the two others may have been subject to damage. Important: even if only one of the three fuses is in service, it is recommended to change them all because the two others may also have been subject to damage. I 3 I n Fuse () Transformer Closing () In this zone, any overloads must be eliminated by LV protection devices or by an MV switch equipped with an over relay. I n I Transformer protection A transformer imposes three main stresses on a fuse. This is why then fuses must be capable of: b withstanding the peak start up which accompanies transformer closing without spurious fusing. The fuse s fusing at 0. s must be higher than times the transformer s rated. If(0. s) > x In transfo. b breaking fault s across the terminals of the transformer secondary A fuse intended to protect a transformer has to break the circuit in order to prevent the transformer s rated short circuit level (Isc) from damaging the latter. Isc > If( s) b... withstanding the continuous operating together with possible overloads In order to achieve this, the fuse s rated must be more than. times the transformer s rated.. In transfo. < In fuse Choice of rating In order to correctly choose the fuse s rated s to protect a transformer, we have to know and take account of: b the transformer characteristics: v power (P in kva), v short circuit (Usc in %), v rated. b the fuse characteristics: v time/ characteristics (If 0.s and If s), v the minimum rated breaking (I3). b the installation and operating conditions: v open air, cubicle or fuse chamber, v presence or otherwise of permanent overload. Comment: whether used with Schneider Electric s SM or RM or in a device from another manufacturer, the equipment manufacturers own user s instructions must be referred to when choosing the fuse. Schneider Electric 3

13 Selection and usage guide Transformer protection Selection tables Fusarc CF fuses/din standard for transformer protection (rating in A) () () (3) Operating Rated Transformer power (kva) Soléfuse fuses/ute standard for transformer protection (rating in A) () () (3) Operating Rated Transformer power (kva) / / () Fuse ratings correspond to open air installation with a transformer overload of 30%, or to an indoor installation without transformer overload. () If the fuses are incorporated in a distribution switchboard, please refer to the selection table provided by the manufacturer of this device. (3) Although the ratings shown in bold type are the most appropriate, the others also protect transformers in a satisfactory manner. Schneider Electric

14 Selection and usage guide Motor protection Capacitor bank protection Fusarc CF fuse selection for motor protection Max. Start-up Start-up duration (s) operating 5 0 (A) No. of start-ups per hour Motor protection When combined with a contactor, the fuse provides a particularly effective protection system for an MV motor. The specific stresses that the fuses have to withstand are due to: b the motor to be protected; b the network on which it is placed. Stresses due to the motor b the start up (Id). b the start up duration (Td). b the number of successive start ups. b when the motor is energised, and throughout the start up period, the impedance of a motor is such that is consumes a Id which is significantly greater than the rated load In. Normally this Id is around times the rated (Id/In = ). b the start up duration Td depends on the type of load that is being driven by the motor. It is of around seconds. b we also have to take account of the possibility of several successive start ups in choosing the fuse rating. Stresses related to the network b the rated : the rated for MV motors is at most equal to kv. b the limited broken : networks with MV motors are generally high installed power networks with very high short circuit s. Choice of rating The fuse rating chosen depends on 3 parameters: b the start up ; b the duration; b the start up frequency. Capacitor bank protection Fuses intended to protect capacitor banks have to withstand special s: b when the bank is energised, the inrush is very high and can lead to premature ageing or fusing of the fuse element. b in service, the presence of harmonics can lead to excessive temperature rise. Choice of rating A common rule applied to any switchgear in the presence of capacitor banks is to derate the rated by 30 to 0% due to the harmonics which cause additional temperature rise. It is recommended to apply a co-efficient of between.7 and.9 to the capacitive in order to obtain the appropriate fuse rating, i.e..7 or.9 times the rated capacitor. As for transformers, it is necessary to know the rms inrush value and its duration. Schneider Electric 5

15 Selection and usage guide Motor protection Selection charts The 3 charts given below enable the fuse rating to be determined when we know the motor power (P in kw) and its rated (in kv). Chart : this gives the rated In (A) according to P (kw) and Un. Chart : this gives the start-up Id (A) according to In (A). Chart 3: indicates the appropriate rating according to Id (A) and the start-up duration time Td (s). Comments b chart is plotted for a power factor (cos ϕ) of 0.9 and an efficiency of 0.9. For values different to this, use the following equation: P In = h 3Uacosϕ b chart 3 is given in the case of start-ups spread over an hour or successive start-ups. For n spread start-ups (n > ), multiply Td by n --. For p successive start-ups (p > ), multiply Td by p -- (see selection table). In the absence of any information, take Td = s. b if the motor start up is not direct, the rating obtained using the charts below may be less than the full load of the motor. In this case we have to choose a rating of 0% over the value of this to take account of the cubicle installation. MT003EN Example A 50 kw motor powered at. kv (point A, chart ) has a of 7 A (point B). The start-up, times greater than the rated = 0 A (point C, chart ). For a start-up time of s, chart 3 shows a rating of 50 A (point D). P (kw) 50 kw 0 A 00 Td (s) 3A 3A 0A 5A A C 00 50A 0 x00a 50A 00A D x50a Id (A) Td (s) In (A) kv kv.kv kv 5.5kV.kV A 3.3kV 3kV B 7 A x x x x x 0 A In (A) 0 P (kw) Id (A) 00 Schneider Electric

Medium Voltage Distribution. Fuses. from 3.6 to 36 kv. Catalogue 2012

Medium Voltage Distribution. Fuses. from 3.6 to 36 kv. Catalogue 2012 Medium Voltage Distribution Fuses from 3. to 3 kv Catalogue 01 Medium voltage fuses from 3. kv to 3 kv Contents Applications Fuse range selection Main characteristics Fusarc CF, Soléfuse, Tépéfuse, MGK

More information

MV SWITCHGEAR 511. CF / SOLEFUSE / TEPEFUSE / MGK MV current limiting fuses With thermally operated striker From 3.6 to 36 kv

MV SWITCHGEAR 511. CF / SOLEFUSE / TEPEFUSE / MGK MV current limiting fuses With thermally operated striker From 3.6 to 36 kv MV SWITCHGEAR 5 MV current limiting fuses With thermally operated striker From 3. to 3 kv In line with our customers and their needs. In a sector like energy, which requires the maximum collaboration between

More information

Medium Voltage Distribution Catalogue I Fuses from 3.6 to 36 kv

Medium Voltage Distribution Catalogue I Fuses from 3.6 to 36 kv Medium Voltage Distribution Catalogue I 01 Fuses from 3. to 3 kv Medium voltage fuses from 3. kv to 3 kv Contents Applications Fuse range selection Main characteristics 3 Fusarc CF, Soléfuse, Tépéfuse,

More information

2016 Catalog. Fuses. From 3.6 to 36kV. Medium Voltage Distribution. schneider-electric.com/mv-distribution

2016 Catalog. Fuses. From 3.6 to 36kV. Medium Voltage Distribution. schneider-electric.com/mv-distribution 01 Catalog Fuses From 3. to 3kV Medium Voltage Distribution schneider-electric.com/mv-distribution Fuses are the one of the first device to ensure the protection of your equipment and your installations.

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

High voltage high-breaking capacity VV fuse-links

High voltage high-breaking capacity VV fuse-links High fuse-links High fuse-links High high-breaking capacity VV fuse-links VV General information ET fuse-links named VV THERMO are designed to protect devices in switch-gears and other equipment (distribution

More information

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV. DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them

More information

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction. HHD High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After

More information

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction.

HHD HIGH VOLTAGE FUSES GERMAN DIN STANDARD. The temperature limiting function of the fuse striker pin. Design and construction. HHD HIGH VOLTAGE GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main

More information

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000

More information

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents HHM High Voltage Fuses Motor Circuit Protection DIN and British Standard SIBA Motor Rated Fuses are available in - German DIN Standard and - British Standard Design The large variety in body sizes / mounting

More information

EUROPEAN HIGH VOLTAGE FUSES

EUROPEAN HIGH VOLTAGE FUSES EUROPEAN HIGH VOLTAGE FUSES AS PER IEC 60282 EDUPACK TRAINING MODULE 2012 HH DIN NF MEDIUM OR HIGH VOLTAGE FUSE? High Voltage is the official definition provided by the standard. High Voltage starts just

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links [A] (ka) [mω] [W] [A 2 s] [A 2 s] 12 580 4 6,1 57 4 A 20 370 9 17,3 164 6 A 25 260 10 36 340 10 A 46 55 7 161 1 530 16 A 60 37 13 250 2 270 20 A 80 30 15 430 3 750 25 A 105 25

More information

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017 HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION March 2017 HV FUSE-LINKS IN THE WORLD UL STANDARD E OR R RATED: AMERICAN STANDARD DIN STANDARD: GERMAN STANDARD FR STANDARD: FRENCH STANDARD BS STANDARD: BRITISH

More information

M.V. LIMITING FUSE WITH THERMAL PROTECTION

M.V. LIMITING FUSE WITH THERMAL PROTECTION M.V. LIMITING FUSE WITH THERMAL PROTECTION 1 INDEX 1.- Why Limiting Fuses? 2.- When does those situations happen? 3.- Market Solutions 4.- MERLIN GERIN Thermal Protection 5.- Technical, economical and

More information

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH HH DRIESCHER - High-voltage high breaking capacity fuses from 1 kv up to 36 kv HH HH ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-866 MOOSBURG TEL. +9 87 61 6 81-0 FAX +9 87 61 68 11 37 http://www.driescher.com

More information

High-Voltage Fuse Links according to IEC

High-Voltage Fuse Links according to IEC High-Voltage Fuse Links according to IEC 60282- Limitor Ferraz Shawmut is global leader in fuse-based electrical protection solutions. Our brand is worldwide renowned for technical expertise, innovative

More information

Medium Voltage current limiting Fuse links

Medium Voltage current limiting Fuse links Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 200A 1. General information P&C Medium Voltage fuse-links named PCEF are designed

More information

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A DISTRIBUTION SOLUTIONS Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A Superior performance versus standard fuses ensuring up to 40% faster protection in case of low

More information

Medium Voltage current limiting Fuse links

Medium Voltage current limiting Fuse links Medium Voltage current limiting Fuse links Type PCEF for indoor and outdoor use Rated Voltage 12-24 kv Current Rating 6 0A 1. General information P&C Medium Voltage fuse-links named PCEF are designed to

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

HIGH VOLTAGE FUSE-LINKS HIGH VOLTAGE FUSE-LINKS WITH THERMAL STRIKER HIGH VOLTAGE FUSES POWER NEEDS CONTROL

HIGH VOLTAGE FUSE-LINKS HIGH VOLTAGE FUSE-LINKS WITH THERMAL STRIKER HIGH VOLTAGE FUSES POWER NEEDS CONTROL HIGH VOLTAGE FUSE-LINKS HIGH VOLTAGE FUSE-LINKS WITH THERMAL STRIKER HIGH VOLTAGE FUSES POWER NEEDS ONTROL HIGH VOLTAGE FUSE-LINKS 1. General information High voltage fuse-links (hereinafter called HV

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links imum cold resistance power dissipation pre-arcing I t value total I t value [kv] (mm) I n [A] (ka) [mω] [W] [A s] [A s] 1 580,1 57 A 0 370 9 17,3 1 A 5 00 10 3 30 10 A 55 7 11

More information

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Fuse-Links according to VDE 0670 T 402. Hi gh-voltage

Fuse-Links according to VDE 0670 T 402. Hi gh-voltage High-Voltage Fuse-Links according to VDE 0670 T 402 Hi gh-voltage Limitor Notes 2 Ferraz Shawmut is global leader in fuse-based electrical protection solutions. Our brand is worldwide renowned for technical

More information

Medium voltage products. Fuses

Medium voltage products. Fuses Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...

More information

Current Limiting Fuses, CEF Motor Circuits Fuses, CMF. Catalogue 1YMB en. Industrial IT. enabled

Current Limiting Fuses, CEF Motor Circuits Fuses, CMF. Catalogue 1YMB en. Industrial IT. enabled PowerIT PowerIT Current Limiting Fuses, Motor Circuits Fuses, CMF Catalogue 1YMB51-en Industrial IT enabled TM High voltage current limiting fuse links type Rated voltage:,/7,- kv Rated current: - A Index

More information

Limitor -G General Purpose Fuses

Limitor -G General Purpose Fuses Limitor -G General Purpose Fuses HIGH VOLTAGE IEC FUSES DIN HV GENERAL PURPOSE FUSES FOR TRANSFORMERS FEATURES & BENEFITS Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear

More information

Medium voltage products. Fuses

Medium voltage products. Fuses Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...

More information

MEDIUM VOLTAGE DIN Fuse-Links

MEDIUM VOLTAGE DIN Fuse-Links Standards/Approvals: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) Catalogue Symbol: 24TDMEJ(amp) 24THMEJ(amp) 24TFMEJ(amp) 24TXMEJ(amp) Class of Operation: Back-up as IEC 60282-1

More information

Medium voltage fuses - European Fuses

Medium voltage fuses - European Fuses HV Back-up Fuse-Links according to IEC 60 282- HV fuse-links have been used for reliable protection in medium-voltage switchgear and controlgear and systems for decades. They protect apparatus and equipment

More information

High voltage current limiting Fuse links type CEF

High voltage current limiting Fuse links type CEF High voltage current limiting Fuse links type CEF Index 1. General........................................... 9 2. Overvoltages...................................... 9 3. Pre-arcing times and cut-off characteristics..............

More information

Fuses are the most effective and economic ways of protection against short circuits in m.v. installations.

Fuses are the most effective and economic ways of protection against short circuits in m.v. installations. HIGH VOLTAGE FUSES CURRENT LIMITING TYPE HIGH BREAKING CAPACITY BACK-UP CLASS Standarts: TS EN 60282-1, VDE 0670/4, DIN 43625 İNTER TEKNİK fuse links are automatic, selectively acting medium voltage switching

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

MEDIUM VOLTAGE DIN Fuse-Links

MEDIUM VOLTAGE DIN Fuse-Links Standards/Approvals: DIN 43625, VDE 0670 part 4, VDE 0670 part 402 and IEC 60282-1 (2005) Catalogue Symbol: 12TDLEJ(amp) 12THLEJ(amp) 12TKLEJ(amp) 12TXLEJ(amp) 12TFMSJ(amp) Class of Operation: Back-up

More information

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air) Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear ETS12-01-02 Specification ETS12-01-02 Ver 3 Contents 1. Purpose

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system. MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

HD4. Gas insulated MV circuit-breakers kv A ka

HD4. Gas insulated MV circuit-breakers kv A ka HD4 Gas insulated MV circuit-breakers 12... 40.5 kv - 630... 3600 A - 16... 50 ka 1 DESCRIPTION Autopuffer breaking technique Electric arc extinction without chopped current No restriking after breaking

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

NEXT STEP B) SAFETY :

NEXT STEP B) SAFETY : SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Medium voltage fuses Medium voltage fuses

Medium voltage fuses Medium voltage fuses European Fuses DIN Fuses 7.2kV - 36kV IBD 7.2 UP TO 36 KV HIGH-VOLTAGE FUSES DESIGNED FOR POWER TRANSFORMER PROTECTION INTERIOR/EXTERIOR USE CERAMIC HOUSING MEDIUM CLASS TRIP-INDICATOR COMBINED WITH A

More information

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers

More information

General information on current-limiting fuse-links. The main characteristics of the CNC fuse-links. Construction. Operating.

General information on current-limiting fuse-links. The main characteristics of the CNC fuse-links. Construction. Operating. General information on current-limiting fuse-links The high-voltage back-up current-limiting fuse-links are designed for protection of systems which include transformers, against the destructive results

More information

Product Catalog Medium Voltage Fuses. Circuit Protection

Product Catalog Medium Voltage Fuses. Circuit Protection Product Catalog General Catalog Contents (Con t.) Page R-Rated Fuses 2.75 to 5.5kV........................................0 E-Rated Fuses 5.5kV MV055.......................................05 8.25kV.............................................09

More information

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical

More information

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders ETS12-01-01 Specification ETS12-01-01 Ver 3 Contents 1. Purpose and Scope... 1 2. References...

More information

IEC Standard Back-Up Fuse-Links

IEC Standard Back-Up Fuse-Links 3 / 7.2 kv 6 / 12 kv 10 / 17.5 kv 10 / 24 kv 20 / 36 kv Ferrule German DIN Standard Beyond our line of ANSI / IEEE current-limiting fuses, Mersen offers a full line of medium voltage fuse links according

More information

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect

More information

Visual comparison of Plain & Hazy PP Film

Visual comparison of Plain & Hazy PP Film ECOVAR High Voltage Power Capacitors are manufactured at our Sinnar Plant in India which is an ISO 9001 accredited facility & houses a computer aided design manufacturing processing and testing infrastructure

More information

X-Limiter full-range current-limiting fuse

X-Limiter full-range current-limiting fuse Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting

More information

Product Selection Guide

Product Selection Guide Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Mica Element Support. Compacted Quartz Sand. Length B

Mica Element Support. Compacted Quartz Sand. Length B Construction A Tin-Plated Brass Caps Dimensional Information for Trans-Guard s NOMINAL 5.5 Resin-Rich Filament Wound Glass/Epoxy Body 3 75 80 200 3 50 5 80 5 125 3 50 5 5 100 23.0 50 Low Current Interruption

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

NX indoor current-limiting fuses

NX indoor current-limiting fuses Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground

More information

Selection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection

Selection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection HHD-BPT Selection Guide HHD-BPT, DIN Style, Current-imiting,, Potential Transformer Protection Current ratings [A]; 0.5, 1, 2, 2.5, 3.15, 4, 5 E=192mm Page E=292mm Page E=367mm Page E=442mm Page E=537mm

More information

Semiconductor Fuses European Fuses

Semiconductor Fuses European Fuses 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos

More information

onlinecomponents.com

onlinecomponents.com 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

LV Capacitor CLMD03 Power Module Instruction manual

LV Capacitor CLMD03 Power Module Instruction manual LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...

More information

FX Full-Range Current-Limiting Fuse

FX Full-Range Current-Limiting Fuse Hi-Tech FX Full-Range Current-Limiting Fuses Trans-Guard FX Full-Range Current-Limiting Fuse Patented damage sensor significantly reduces the risk of fuse failure should the fuse be subjected to an element-damaging

More information

Medium Voltage Distribution. Rollarc R400-R400D contactor 1 to 12 kv

Medium Voltage Distribution. Rollarc R400-R400D contactor 1 to 12 kv Medium Voltage Distribution Rollarc R400-R400D contactor to kv Description ield of application and utilisation range Description The Rollarc three-pole indoor contactor uses sulphur hexafluoride (S) gas

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker DR-6/DT-6 COMPACT AND EXTENSIBLE RING MAIN UNIT BUILT TO LAST! DR-6/DT-6 Compact and/or extensible SF 6 insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker SAFETY, RELIABILITY,

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use QMB cubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual

More information

FUSE: SAFE & RELIABLE

FUSE: SAFE & RELIABLE FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

DISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales

DISTRIBUTION SOLUTIONS HA Breaker Retrofit. Medium Voltage Service Marketing and Sales DISTRIBUTION SOLUTIONS HA Breaker Retrofit Medium Voltage Service Marketing and Sales Table of contents Retrofit concept General description Technical specification Necessary details for standard retrofit

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

Contents. The RM6 range

Contents. The RM6 range Ring Main Unit RM6 24 kv Catalogue 2009 The RM6 range Contents Presentation Applications 2 Range advantages 4 Experience of a world leader 6 Protecting the environment 7 Quality - Standards 8 The RM6 range

More information

Protistor size 70 gr 690VAC (IEC)

Protistor size 70 gr 690VAC (IEC) Protistor size 70 gr SEMICONDUCTOR PROTECTION FUSES SQUARE BODY HIGH-SPEED FUSE-LINKS AC PROTECTION FEATURES & BENEFITS Excellent cycling capability Multiple body sizes and terminals or blades combination

More information

Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES

Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES Section ( VI ) TECHNICAL SPECIFICATIONS AND SCHEDULES TECHNICAL SPECIFICATIONS L.V- HRC KNIFE (NH TYPE) FUSE-LINKS ( V.AC) HRC knife fuse-links (NH Type) must have a rated breaking capacity current of

More information

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration

More information

DRIWISA HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE

DRIWISA HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE HIGH VOLTAGE CURRENT-LIMITING FUSE CATALOG ! DRIWISA trademark is registered by and is protected by national and international law. The use of this trademark without written authorization by is a crime

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

fuses fuse holders CYLINDRICAL

fuses fuse holders CYLINDRICAL fuses fuse holders 02 gg FUSES 04 am FUSES FUSES 09 PMC COMPACT 09 -CC FOR CC CLASS FUSE-LINKS 11 PMB PLUG CONNECTION 11 CLIP CONTACT FOR φ10 FUSE-LINKS 10 PMF 11 BAC OPEN FUSE BASES 06 gg FUSES FUSES

More information

Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications

Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications ETS12-01-04 Specification ETS12-01-04 Ver 3 Contents 1. Purpose and Scope...

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

PhaseCap Premium PFC Capacitors Gas-impregnated n Dry type n Concentric winding n Wavy cut n Triple safety system

PhaseCap Premium PFC Capacitors Gas-impregnated n Dry type n Concentric winding n Wavy cut n Triple safety system Premium PFC Capacitors General capacitors in cylindrical aluminum cases have been designed for power factor correction in low-voltage plant. Loads like motors and transformers consume active power as well

More information

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two

More information

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element

More information