1 Flotection: Building Main Shutoff System
2 Overview of System Retail stores have a requirement for night time monitoring of the Domestic Water Supply. When flow is detected, during the hours the store is closed, the system shuts off this supply and flood damage is thereby prevented. System operation: Tie-in to EMS controller : The store EMS signals the panel to go into Open/Day mode or Closed/Night Mode on a daily basis. Power to the EMS relay in the panel puts the system in Closed/Night Mode. No power to the EMS relay puts the system onto Open/Day Mode. Dry contacts on Relay 2 and 3 allow Flow Alarm monitoring and Valve Status monitoring back to the EMS. 1. Day/Occupied : On power being supplied to the 2 pole main breaker the panel will go into the Open/Day mode. This is the default mode. The EMS relay coil in the panel is not receiving power from the EMS at this point The Main valve in the main domestic water supply line to the store interior is powered open. A Bypass valve in the 1 ½ bypass line is un-powered and is spring driven to the closed position. A green light indicates the Main Valve is fully open and power to the panel is connected. The Valve Status contact is open to indicate to the EMS that the Main Valve is open. 2. Night/Unoccupied: After store hours the local EMS signals the panel to go into Close/Away mode. The EMS relay coil in the panel is now receiving power from the EMS. The Main Valve is powered closed. The Bypass valve in the 1 ½ bypass line is powered open. This bypass line allows low volume water flow to the store. A yellow light indicates the Main Valve is fully closed. The Valve Status contact is closed to indicate to the EMS that the Main Valve is closed. The panel employs electrical interlocking relays to prevent any over-riding signal to be sent to the main valve during Night/Away mode.
3 Overview of System, cont. 3. Alarm mode: The Flow Sensor detects water flowing through the bypass line. The Time Delay Relay times out and closes a on-delay contact (adjustable 0-60 sec.) The Bypass Valve is de-energized allowing it to spring closed. The Main Valve remains closed. The water is now shut off completely. A Red light indicates an alarm condition. The Flow Alarm Status contact closes and the Valve Status contact remains closed. A dry contact, available for an additional alarm circuit, has now closed 4. To Reset A qualified person must go to the control panel and reset the system via a single Red button on the panel door. No remote reset is permitted. After reset the system returns to the previous EMS selected mode, Open/Day or Closed/Night. 5. To Test A qualified person may operate a Test toggle switch in the panel. In Test mode (ON) the panel is forced into closed/night mode. the operator can observe that that the Main valve is closed and the Bypass valve is open. Indicators on each valve show the position of the valve. In the Day/Open Mode the indicators show the main has opened and the Bypass is closed. Regular testing ensures the system is operating normally
4 Example of Horizontal Supply Installation 12 cords (supplied) to prewired parts Flotection Control panel 120V 1 ½ Valve w/prewired 120V actuator 120V Supply and EMS connections 24V ac/dc EMS Relay (internal) 120V pre wired flow sensor Main Valve w/prewired 120V Actuator
5 Installing the Control Panel 1. Choose a suitable location to mount the panel. The connector cords are 12 long. 2. IMPORTANT SAFETY CAUTION: Pull the fuse holder open to disconnect panel from power source until ready to energize system. 3. Connect 120V supply voltage to the main 2 Pole fuse holder and install the fuses. To connect to the EMS system: 1. Connect 24Vac/dc power from the EMS to the blue terminals marked + and -. Power to these terminals will force the system into Night/Away mode. 2. Flow Alarm Indication connect to terminal 29 and 33 from EMS. A signal will flow to EMS when the relay operates, indicating there has been flow. 3. Valve Open/Close Status connect to terminal 35 and 39 from EMS. A signal will flow to EMS indicating open/closed position of main valve. 4. Second alarm signal connect to terminal 47 and 49. A signal will flow to an additional alarm indicator Notes: When the system is connected and energized (fuse holder closed) the Main Valve will open. When in the fully OPEN position the green light will serve to indicate the power is connected and the Open position of the Main valve. The Flow sensor switch is now powered but the bypass valve is closed, no flow detected.
6 Field Connections to Numbered Terminal Blocks Line N R2 R3 R2 R4 Terminal# L1 L IN OUT IN OUT (+) (-) Function Power EMS - Flow Alarm status EMS - Valve status OPEN/CLOSE Alarm Contact EMS Relay Power 24V ac/dc For wiring schematic, see Drwg. ST4-M006
7 Kit with Main Valve, Bypass Valve, Flow Sensor (all prewired) Order by size of main domestic water line Part# Size FLO120V1.5NP 1.5 FLO120V2.0NP 2 FLO120V2.5NP 2.5 FLO120V3.0NP 3 FLO120V4.0NP 4 FLO120V5.0NP 5 FLO120V6.0NP 6 These prewired parts plug directly into the control panel
8 Installing the Main Valve, Bypass Valve and Flow Sensor Install main valve in line with main water supply. Follow instructions provided with main valve. Install Belimo ball valve in 1 ½ bypass line. Install the flow sensor in the bypass line. A street fitting (1 ) and a Tee (1 1/2x1 ) are provided. This ensures the correct depth of the sensor into the bypass line. Plug the cords from the control panel into the main valve, bypass valve and flow sensor. These parts have been prewired to ensure the correct functioning of the system. These kits plug into the control panel on the previous page
9 Testing/Operating the System
10 Test Toggle Switch 1. The toggle switch mounted on the standoff plate must be in the OFF (normal mode) position for daytime operation, 2. The toggle switch in the ON position forces the system into Close/Night mode 3. Toggle to the ON position and observe the Main Valve and Bypass valve indicators. The Main Valve will close and the indicator will rotate to show Closed, the Bypass valve will rotate to position Toggle to the Off position and observe that the Main Valve opens and the Bypass valve closes. 5. The system is now in the Open/Day mode. Toggle switch shown in ON (Test) position
11 Day or Occupied Mode Condition: No Faults The Energy Management System sends a signal that the store is open for the day. 1. An open signal is sent to the Control Panel that commands the opening of the Main Valve. 2. As the Main valve totally opens a micro-switch inside of the Main valve energizes the OPEN/DAY Pilot Light. 3. Power is removed from the bypass valve and the valve closes (exercising the valve daily) 4. The Flow sensor switch is now powered but the bypass valve is closed, no flow detected.
12 Night or Unoccupied Mode Condition: No Faults The Energy Management System sends a signal that the store is closed for the night. 1. A close signal is sent to the Valve Controller that commands the closing of the Main Valve. 2. As the Main valve totally closes a micro-switch inside of the Main valve energizes the close indicator 3. A yellow pilot light illuminates. 4. The Bypass Valve is opened by the 120V actuator. 5. The flow sensing device monitors the Bypass Piping for any water flow. 6. A relay contact for the external monitoring of the Main Valve closes, indicating to the EMS that the Main Valve is closed.
13 Night or Unoccupied Mode Condition: Fault with Main Valve closed 1. The Sensing device detects water flow through the Bypass piping 2. This detection energizes a Time Delay Relay, and after 60 seconds (adjustable) of water flow the Time Delay Relay activates a lockout relay. 3. The lockout relay immediately signals a Fault Condition, closing both the Main Valve and the Bypass Valve and removes all external signals controlling both of the valves. 4. The EMS received a Fault indication.
14 Reset Condition: Fault with Main Valve closed Reset Button 1. After an on-site visual Inspection of the water piping has been confirmed, the fault has been corrected or there is no problems or breaks. 2. The reset button must be activated by a person on-site, to restore the normal operation of the Valve Controller. 3. When reset the bypass valve will re-open, if there is less than fault condition water flow.
15 Status Outputs Flow Alarm Indication connect to terminal 29 and 33 from EMS A signal will flow to EMS indicating there has been water flow. Valve Open/Close Status connect to terminal 35 and 39 from EMS. A signal will flow to EMS indicating open or closed position of main valve. Second alarm signal connect to terminal 47 and 49 A signal will flow to an additional alarm indicator.
16 Manifold Suggestions Overall length 60 Non grooved pipe at both ends
17 Technical Support Call: Sam Cordaro
Quick Start Guide TS 910
Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible
More informationQuick Start Guide TS 910 & TS 920
Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer
More informationMANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450
MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION
More informationThe X, Y, and Z of Circuit Breaker Control
The X, Y, and Z of Circuit Breaker Control BRENT L. CARPER, P.E. Principal Engineer Presented at the 35th Annual Hands-On Relay School March 12-16, 2018 Agenda Importance of Breaker Control The IEEE C37.11
More informationSOLAR SMART. 12/24V 20Amp MPPT Solar Charge controller with Ethernet
SOLAR SMART 12/24V 20Amp MPPT Solar Charge controller with Ethernet Embedded web pages, SNMP support, output port for external Relay board and GSM SMS unit port USER MANUAL PLEASE READ THIS MANUAL CAREFULLY
More information1-3 MANUAL STARTERS EXERCISE OBJECTIVE. Examine and describe the operation of manual motor starters. DISCUSSION
1-3 MANUAL STARTERS EXERCISE OBJECTIVE Examine and describe the operation of manual motor starters. DISCUSSION Motor starters are made out of power switches and overload protection devices. They can be
More informationOptimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version
Optimal Series Automatic Transfer Switch Installation and User Manual for the OPT2225 Automatic Transfer Switch Full Version File: OPT2225 Rev2.5.doc November, 2004 2 Thank You For Purchasing This DynaGen
More informationPower Inverter. User s Manual. Diamond Series CPD1200EILCD
Power Inverter Diamond Series CPD1200EILCD User s Manual 2 TABLE OF CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS..4 2 INSTALLATION....5 2-1 Unpacking...5 2-2 Product Overview & Outlook..5 2-3 Power Requirements
More informationSECTION Instrument Cluster and Panel Illumination
413-00-i Instrument Cluster and Panel Illumination 413-00-i SECTION 413-00 Instrument Cluster and Panel Illumination CONTENTS PAGE DIAGNOSIS AND TESTING Instrument Cluster and Panel Illumination... 413-00-2
More informationAdvantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.
Advantage-D Series 3 Central Vacuum Systems (Expandable/Modular Models) (Ver. 8/05) Operating Instructions and Maintenance Manual DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems
More informationTCM D Single Zone, 24 Volt DC Timer Control Module User s Manual D-M-E Company
TCM-03-024D Single Zone, 24 Volt DC Timer Control Module User s Manual D-M-E Company D-M-E Company TCM-03-024D Page 1 SAFETY D-M-E Company products have been designed to be safe and simple to operate.
More informationInstallation Instructions
Smart Start Assist Kit For use with Single-Phase Residential Geothermal Heat Pumps 8-733-934-497 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY
More informationPower Sliding Door (PSD) Diagnostic Approach. Fixing Intermittent Malfunctions. Power Sliding Door (PSD) Diagnostic Information
Power Sliding Door (PSD) Diagnostic Information Power Sliding Door (PSD) The power sliding door (PSD) provides built-in diagnostics. This assists the service technicians during troubleshooting. The PSD
More informationE.S.P. Embedded Sensing Probes for Motor Brushes
E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com
More informationExercise 1-3. Manual Starters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Direct-on-line (DOL) starters. Reversing starters
Exercise 1-3 Manual Starters EXERCISE OBJECTIVE Examine and describe the operation of manual motor starters. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Direct-on-line
More informationDesigned for ease of integration with automation systems
BAS, 200 ~ 600V, 1/2-30HP BUILDING AUTOMATION STARTER SMARTER AND MORE VERSATILE THAN EVER Smartstart Equipped with advanced I/O including Fireman s Override and damper control, the BAS was designed from
More informationELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243
ELECTRIC SCHEMATICS NOTES: (Unless otherwise specified). Switch S BASE/PLATFORM makes contact from the CENTER to the LEFT position when placed in BASE.. Switch S UP/DOWN makes contact from the CENTER to
More informationTIME REQUIREMENT GUIDE (TRG)
CAT SWITCHGEAR TIME REQUIREMENT GUIDE (TRG) This warranty repair time requirement guide is designed to: Provide detailed guidance on troubleshooting Determine possible solutions Guide the technician to
More informationHGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology
HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951
More information1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.
RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to
More informationAUTO-EC-3-E-PLC Electric Filter Backwash Controller Operation & Maintenance Manual
AUTOEC3EPLC Electric Filter Backwash Controller Operation & Maintenance Manual Contents Contents Controller Basics 3 Controller Components 4 Screen Flow Diagram Controller Functions 6 Installation 7 Warranty
More informationControls and Instruments
CHAPTER 9 Controls and Instruments A complex set of controls and instruments monitors the operation of an electric generator set. Equipment operators must understand what these controls and instruments
More informationHGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic
HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 4 3. SPECIFICATIONS... 5 4. OPERATION... 6 5. PROTECTION...
More informationDoor Lock System Controls
2017 Chevy Truck Suburban HD 4WD V8-6.0L Vehicle > Body and Frame > Locks > Description and Operation > Components POWER DOOR LOCKS Door Lock System Components The power door lock system consists of the
More informationControls Manual Standard 1 Fan Control Panel
Controls Manual Standard 1 Fan Control Panel >> Operation >> Sequence of Operation >> Schematic >> Troubleshooting >> Preventitive Maintenance >> Parts List >> Certifications 888-452-6684 www.colmetsb.com
More informationEMIU 720W Mini Inverter
THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using
More informationHGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...
CONTENT 1. SUMMARY...4 2. PERFORMANCE AND CHARACTERISTICS...4 3. SPECIFICATION...5 4. OPERATION...6 4.1. DISPLAY PANEL...6 4.2. LCD ICON INSTRUCTION...7 4.3. DISPLAY INSTRUCTIONS...7 4.4. DISPLAY DESCRIPTION...8
More informationOnCommand Troubleshooting Guide Hayward Industries
OnCommand Troubleshooting Guide 2010 Hayward Industries Table of Contents Safety Precautions Page 1 Overview Pages 2-5 Software Troubleshooting Page 6 Local Display Pages 7-8 Relays Pages 9-10 Heaters
More informationPOWERLINE 2000 Energy Management System TM
Display Panel TM The PowerLine 00 EMS is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed in the standard main distribution
More informationJ1 Plug Pin Identification
D5 D8 D7 D4 D5 D ART_8 J 4 8 D D0 7 R R R R4 TB 80 D D D D4 D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 4 8 INPUT
More informationControl System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)
Part B, Section 1 This section covers the following unit configurations. Model 3100 3400 3500 Voltage 1, 2 Pump Piston (E, F, or G) Manifold 4-Port (A) 6-Port (B or C) Control UniScan (1) B 1-0 B 1-1 Section
More informationExterior Lighting Systems Description and Operation. Exterior Lamps. The exterior lighting system consists of the following lamps: The headlamps
Exterior Lighting Systems Description and Operation Exterior Lamps The exterior lighting system consists of the following lamps: The headlamps The daytime running lamps (DRL) The front fog lamps The park,
More informationDESCRIPTION AND OPERATION ICE DETECTION SYSTEM
ICE DETECTION SYSTEM 2.23. ICE DETECTION SYSTEM The ice detection system consists of an ice detector located on the right side of the airplane nose and two ICE amber caution lighted pushbuttons on both
More informationSECTION Interior Lighting
417-02-i Interior Lighting 417-02-i SECTION 417-02 Interior Lighting CONTENTS PAGE DIAGNOSIS AND TESTING Interior Lighting... 417-02-2 Principles of Operation... 417-02-2 Inspection and Verification...
More informationInstallation Instructions & Users Manual
Installation Instructions & Users Manual UTILITY/ BUILDING INPUT 120 VAC ( OPTION) 15-20A N L CONTROL BOARD G SECURITY LIGHTING POWER SUPPLY (OPTION) CHARGER- POWER SUPPLY ASSBY XFMR (OPTION) CBM MODEL
More informationSERVICE MANUAL (DOMESTIC & INTERNATIONAL)
SERVICE MANUAL (DOMESTIC & INTERNATIONAL) DUAL TECHNOLOGY FINISHER MODEL 1960 & 1980 SERIES Lincoln Foodservice Products, LLC 1111 North Hadley Road Fort Wayne, Indiana 46804 United States of America Telephone:
More informationGENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).
Technical Data Sheet GENSET CONTROL MODULE LEVEL 0 A120A Features: One model for both spark ignition and diesel engines. 4-alarm light outputs with automatic lamp-test provision. Overspeed adjustment not
More informationPhenix Technologies Inc. 75 Speicher Drive Accident, Maryland 21520
USER S MANUAL PORTABLE HIGH CURRENT TEST SET MODEL NUMBER HC2 Version 4.0 Phenix Technologies Inc. 75 Speicher Drive Accident, Maryland 21520 Copyright Phenix Technologies, Inc. Rev 11/20/2014 nab TABLE
More informationMANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600
MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION
More informationIMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS
THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. IMPORTANT SAFEGUARDS INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL When using
More informationInstruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.
Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored
More informationTekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL
AUTOMATIC FILTERS, INC. 67 S. LA CIENEGA BLVD. LOS ANGELES, CA 90034 30 839 88 800 336 94 FAX 30 839 6878 www.tekleen.com info@tekleen.com Tekleen GB6 & GB7 USERS MANUAL GB6 & GB7 USERS MANUAL AUTOMATIC
More informationIMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE LMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS
THIS UNIT CONTAINS A RECHARGEABLE VALVE-REGULATED LEAD ACID BATTERY. PLEASE RECYCLE OR DISPOSE OF PROPERLY. IMPORTANT SAFEGUARDS INTERRUPTIBLE EMERGENCY LIGHTING UNIT INVERTER INSTRUCTION MANUAL When using
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationFlight Systems. Replacement for KASSEC DESCRIPTION
DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most
More informationInstruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.
www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure
More informationWARNING. Murphy W-Series Engine Panels General Installation Instructions. Installation Accessories
Murphy W-Series Engine Panels General Installation Instructions WS-93002N Revised 04-06 Section 30 (00-02-0191) Read the following information before installing. These installation instructions are typical
More informationWARNING. Murphy W-Series Engine Panels General Installation Instructions. Installation Accessories
Murphy W-Series Engine Panels General Installation Instructions WS-93002N Revised 08-02 Section 30 (00-02-0191) Read the following information before installing. These installation instructions are typical
More informationWiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents.
1 10/2014 REV 7 !!Attention!! Before performing diagnostics: Wiring diagrams on page 29 are for reference only. For detailed vehicle wiring refer to Navistar documents. Check for Fault Codes using the
More informationGENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.
Technical Data Sheet GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 5-alarm light outputs with lamp-test
More information100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE
100% OUTSIDE AIR MAKE-UP UNITS WITH DISCHARGE TEMPERATURE CONTROL & c.pco DIRECT DIGITAL CONTROL MODULE Start-up must be performed by a trained, experienced service person. The following general start-up
More informationAdvanced Instructions
Advanced Instructions Detailed wiring and installation instructions Monitor Battery #1 (and power the device) Connect the long red (positive) and black (negative) leads to the main battery. Many vehicles
More informationWasher Extractor. Balancing Systems
Washer Extractor Balancing Systems Why is it Necessary Out of Balance conditions can cause a tremendous level of force. 1 G machine that is out of balance 1 lb is 1lbf 300 G machine that is 40 lbs out
More informationJ1 Plug Pin Identification
D D8 D D D D ART_8 J 8 D D0 R R R R TB 80 D D D D D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 8 INPUT Steer Left
More informationBombardier Challenger Auxiliary Power Unit
GENERAL A Honeywell 36 150(CL) constant-speed gas turbine auxiliary power unit (APU) is installed within a fire-resistant compartment in the aft equipment bay. The APU drives a generator, providing AC
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax
Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES
More informationJ1 Plug Pin Identification
D5 D D D D5 D ART_ J D D0 R R R R TB 0 D D D D D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal INPUT Steer Left 5 OUTPUT
More informationX4 Installation and Operation Manual - POWER FLAME INCORPORATED
7.13.2 Set the burner s combustion air inlet damper to the approximate setting as shown in this manual for the desired firing rate. Also, verify that the correct main orifice is installed in the main orifice
More informationTABLE OF CONTENTS. Understanding the Troubleshooting Instructions...2 Signal Light...2 Harness Connections...2 Inspection...2
TRIPP Model B ELECTRICAL TABLE OF CONTENTS Understanding the Troubleshooting Instructions...2 Signal Light...2 Harness Connections...2 Inspection...2 LVDT Setup/Adjustments...2 Basic Troubleshooting...3
More informationArch HTH Water Chemicals Commercial Equipment Trouble Shooting Guide
Arch HTH Water Chemicals Commercial Equipment Trouble Shooting Guide 8/28/00 TROUBLESHOOTER S GUIDE PROBLEM CAUSE SOLUTION Insufficient water flow to chlorinator Check water flow through Flow Controller
More informationELECTRICAL SYSTEM RP-7
ELECTRICAL SYSTEM RP-7 This section of the manual does not include integral electrical components of the engine. Refer to section Engine RP-1 for details. This section of the manual is divided into three
More informationDocument Version Abbra_
Congratulations on your purchase of the Abbra Professional Series home security system! With an Abbra system installed in your home, you can rest secure in the knowledge that your home and family are protected.
More informationUtility Distribution Systems Installation, Operation, and Maintenance Manual
Utility Distribution Systems Installation, Operation, and Maintenance Manual RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately
More informationCDI series Model TW. Residential Water to Water Heat Pump. Engineering Submittal Sheet. Standard Features. Overview and Certifications
CDI series Model TW Residential to Pump Engineering Submittal Sheet Overview and Certifications Standard Features, Factory Installed Options and Control Options Standard Features White Pre-Painted Sheet
More information5. OVERCURRENT RELEASE (OCR)
5. OVERCURRENT RELEASE (OCR) Options available for the type AR ACBs include a highly reliable, multi-functional overcurrent release (OCR) with a built-in 8- bit microprocessor. This OCR is supplied with
More informationEXTREME R MOTOR OWNER'S MANUAL
EXTREME R MOTOR OWNER'S MANUAL 2 HP, 3 HP & 5 HP WITH SELF-ENGAGING CHAIN HOIST FOR TECHNICAL SUPPORT PLEASE CALL 1-(855) 594-4969 3137B(0) ECN 1313 BY JM 7/9/15 OPERATOR SERIAL# PRO-FDG MOTOR OPERATORS
More informationMODUL-CONNECT 1.2. Owner s Manual. Modular, digital wiring and control system. Document Part Number MSMC Rev 9 (04/18)
MODUL-CONNECT 1.2 Modular, digital wiring and control system Owner s Manual Document Part Number MSMC Rev 9 (04/18) Service Contact Information E-mail: info@modul-system.com Phone: +46 31 746 87 00 Web:
More informationP144F REQUESTED INFORMATION P144F EGR COOLER BYPASS STATUS LINE CIRCUIT HIGH RAM Pickup 6.7L Eng /12/2014 Printer Friendly View
P144F 2012 RAM Pickup 6.7L Eng 2500 REQUESTED INFORMATION P144F EGR COOLER BYPASS STATUS LINE CIRCUIT HIGH http://www1.prodemand.com/print/index?content=tabs&module=true&tab=true&terms=true&ymms=false&classname=
More informationTwo Channel Remote Shutdown Device
Installation & Operation Standard Features: Two Channel Remote Shutdown Device I. Introduction Latched shutdown for increased safety Powerful transmitter with 300 feet range Waterproof sealed transmitter
More informationInstallation, Operation and Maintenance Manual
Document 47681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
More informationIMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE
USER MANUAL IMI vibration switch INSTALLATION - OPERATION - MAINTENANCE Z0929039_A ISSUED 03/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. contents Overview General
More informationSeries. idrive 300. Installation and User s Guide INTELLIGENT ENVIRONMENTAL CONTROL. March 2014 v1.1 Edition Copyright 2014 Corporation
idrive 300 Series INTELLIGENT ENVIRONMENTAL CONTROL Installation and User s Guide March 2014 v1.1 Edition Copyright 2014 Corporation Table of Contents Introduction... 1 Customer Service... 2 Contact Us...
More informationElectromagnetic Industries LLP
GROUND FAULT CURRENT DETECTION GFM Relay (Model 252 & 262) The GFM system is designed for electrical protection, not for personnel protection Application: These Class 1 (Model GFM) Ground Fault protection
More informationTHAWZALL Manufactured by THAWZALL, Inc. MODEL 2M SPECIFICATIONS AND PERFORMANCE SPECIFICATIONS: MODEL 2M
THAWZALL Manufactured by THAWZALL, Inc. MODEL 2M SPECIFICATIONS AND PERFORMANCE SPECIFICATIONS: MODEL 2M Height 78 Inches Width 74 Inches Length 144 Inches Weight (Including Fuel) 3,006 Lbs. Fuel Capacity
More informationCircuit breaker interlocking and operation requirements SIEMENS
Circuit breaker interlocking and operation requirements SIEMENS When manufacturers and specifiers discuss circuit breaker operational and interlocking requirements, several terms are used repeatedly. Despite
More informationCALTRAP INSTALLATION AND OPERATIONS MANUAL
INSTALLATION AND OPERATIONS MANUAL NOTE Please read this entire installation and operations manual before energizing the. Safety Considerations: Installing and servicing capacitor equipment can be hazardous.
More informationGENSET CONTROL MODULE A121A / A241A
Technical Data Sheet GENSET CONTROL MODULE A121A / A241A Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 4-alarm light outputs with lamp-test provisions.
More informationHGM501 Gen-set Controller USER MANUAL. Smartgen Technology
HGM501 Gen-set Controller USER MANUAL Smartgen Technology Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. OVERVIEW... 4 PERFORMANCE AND CHARACTERISTICS... 4 TECHNICAL DATA... 5 OPERATION... 6 4.1. BUTTON DESCRIPTION...
More informationREVISION HISTORY REVISION HISTORY
FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim
More informationElectrical. The following slide shows the entire electrical overview. Take a moment to study the overview and become familiar with the components.
Electrical The electrical system is the most simple of any proven automated collection unit in the industry. It takes an ignition supply from the chassis, through a switch normally mounted by the body
More informationCS-865RKE Series II REMOTE KEYLESS ENTRY SYSTEM
INTRODUCTION: CS-865RKE Series II REMOTE KEYLESS ENTRY SYSTEM INSTALLATION & OPERATING INSTRUCTIONS CONGRATULATIONS on your choice of a Remote Keyless Entry System by Crimestopper Security Products Inc.
More informationSAFE & SECURE ACTUATOR PRODUCT MANUAL
INDELAC CONTROLS SAFE & SECURE ACTUATOR PRODUCT MANUAL Product Description: The Safe & Secure Series Actuator is a quarter turn Open/Close Actuator with Battery Backup Power ALL IN ONE! No more mounting
More informationUSER MANUAL. IPS home inverters with UPS function. IPS home inverter manual
USER MANUAL IPS home inverters with UPS function Suitable for UPS: - IPS300-SIN - IPS300-SIN-WM - IPS300-SIN-DC - IPS600-SIN - IPS600-SIN-WM - IPS600-SIN-DC - IPS1000-SIN - IPS1000-SIN-DC - IPS1600-SIN
More information! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.
Technical Information Double Oven Electric Range MER6555AAB/Q/W MER6751AAB/Q/S/W MER6755AAB/Q/S/W MER6775AAB/F/N/Q/S/W Due to possibility of personal injury or property damage, always contact an authorized
More informationInstruction Manual. What s In The Box? CANsmart Controller DNL.WHS BMW K1600 Series. Kit Contents DENALIELECTRONICS.COM
Instruction Manual Instruction Rev0 Thank you for choosing DENALI We know you would rather be riding your bike than wrenching on it, so we go the extra mile to make sure our instructions are clear and
More informationApplication Engineering
Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor
More informationFuel System (Central SFI)
Page 1 of 6 1997 GMC Truck GMC K Pickup - 4WD Chevy Pickup, GMC Pickup, Suburban, Tahoe, Yukon (VIN C/K) Service Manual Engine Engine Controls - 5.0L, 5.7L, and 7.4L Description and Operation Document
More informationPROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER
PROFIRE 1100i IGNITION FLAME SAFETY CONTROLLER Cautions WARNING: EXPLOSION HAZARD- -DO NOT SERVICE UNLESS AREA IS KNOWN TO BE NON- HAZARDOUS -DO NOT OPEN WHEN ENERGIZED EXPLOSION HAZARD- -SUBSTITUTION
More informationApplication Engineering
Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the
More informationSECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS
SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationZ1 B1 B2 Z2 B3 B4. Steuerteil + 24 V. Leistungsteil K1 K2 K1 K2. Practice for Professionals Electropneumatics Trainee s manual. Version 1.
04 Z1 B1 B2 04 Z2 B3 B4 31 14 Y1 12 4 2 5 3 1 15 31 14 Y2 12 4 2 5 3 1 15 Steuerteil + 24 V B1 S0 K1 B2 K2 B4 K3 B3 Leistungsteil 1 2 3 4 5 6 7 8 9 K4 K1 K2 0V K1 K2 K1 K3 K2 K4 K3 Y1 K3 Y2 Practice for
More information6500DC Dual Motor Wireless Controller Kits
6500DC Dual Motor Wireless Controller Kits READ ALL DIRECTIONS FIRST BEFORE PROCEEDING NOTE: SEE THE QUICK PROGRAM INSTRUCTIONS BEFORE OPERATING THE FIRST TIME. DO NOT REMOVE THE TRANSMITTER BATTERY Please
More informationValcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual
Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS
More informationCHAPTER ICE AND RAIN PROTECTION SYSTEM
15--00--1 ICE AND RAIN PROTECTION SYSTEM Table of Contents REV 3, May 03/05 CHAPTER 15 --- ICE AND RAIN PROTECTION SYSTEM Page TABLE OF CONTENTS 15-00 Table of Contents 15--00--1 INTRODUCTION 15-10 Introduction
More information"Engineered to Ride, Built to Last "
Congratulations on your purchase of an Arnott air suspension product. We at Arnott Incorporated are proud to offer a high quality product at the industry s most competitive pricing. Thank you for your
More informationSAFE AND SECURE EXTREME R MOTOR OWNER'S MANUAL MODEL PRO-FDG FOR TECHNICAL SUPPORT PLEASE CALL 1-(855) OPERATOR SERIAL#
SAFE AND SECURE EXTREME R MOTOR OWNER'S MANUAL MODEL PRO-FDG FOR TECHNICAL SUPPORT PLEASE CALL 1-(855) 594-4969 3121B(4) ECN 1288 BY TG 2/6/15 OPERATOR SERIAL# PRO-FDG MOTOR OPERATORS MOTOR OWNER'S MANUAL
More informationEngineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)
Engineering Bulletin IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Issued By: Clarksville Marketing and Sales Support Order No. UN-PRB001-EN
More informationOPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets
Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599
More informationLanding Gear & Brakes
EMBRAER 135/145 Landing Gear & Brakes GENERAL The EMB-145 landing gear incorporates braking and steering capabilities. The extension/retraction, steering and braking functions are hydraulically assisted,
More information