INSTALLATION CONNECTIONS. COMMUNICATION. COMMISSIONING AM ; AMC 150; DV 1000

Size: px
Start display at page:

Download "INSTALLATION CONNECTIONS. COMMUNICATION. COMMISSIONING AM ; AMC 150; DV 1000"

Transcription

1 INSTLLTION CONNECTIONS. COMMUNICTION. COMMISSIONING M ; MC 150; DV

2 safety instructions This Manual must be read before installing the irmaster air handling unit. Following this Manual will ensure this product is operated correctly. The manufacturer cannot be held liable for damage arising from use or installing in contravention of these instructions. The installation contractor is responsible for ensuring that the unit is installed according to current regulations and standards. The manufacturer reserves the right to make changes without notice. ll values stated are nominal values and can be affected by local conditions. When installing the air handling unit in a room with a fire or stove drawing air from the room, all applicable provisions must be observed. Failure to observe the warnings indicated by a danger symbol implies a risk of personal injury or damage to property. The unit should not be used in rooms with abrasive particles or flammable or corrosive gas in the air, in wet rooms (not CV-series) or explosion-protected rooms. This manual relates to the irmaster unit it accompanies plus all equipment, and must be given to and saved by the unit s owner. The unit should not be used without the filters specified in the Operator s Manual. ll necessary data and guides to network integration can be downloaded from www. airmaster-as.com. WRNINGS Service covers may not be opened without first disconnecting the unit s power supply and preventing use. The unit may not be started up until all service covers and grates on duct connections have been installed. Place of installation and serial numbers (S/N): Type: Delivery date: Place of installation: S/N of ir handling unit: S/N of Cooling Module:

3 Table of Contents 1. Technical Specifications Condensate Drain Heating Surfaces Water Heating Surface leeding Setting the Heat Retention Valve Setting the Kv value on the valves Check Heating Surface Electric Heating Surfaces Electrical Installation Supply Voltage Connection of Electrical Equipment Data Cable Shield Termination Control Panel Motion (PIR) Sensor Carbon Dioxide (CO 2 ) Sensor External Stop Function External Start oost nalogue MS Checking Electrical Installation irlinq MS Installation Connectors DIP Switch / Jumper Wiring-diagram for typical irlinq MS sytemes Junction ox for Group Control Panels System Programming Programming Units ID1 to ID Programming ID Programming Group Control Panels for Groups 1 to Programming Cooling Modules ID1 to ID Commissioning and Final Inspection

4 ppendix 1 Wiring Diagrams...23 Control ox QC-L (lack Control ox) for MC 150, M 150, M(L) 300, 500 and QC-P (Grey Control ox) for M(P) 500, 800, 900 and 1200, M(S) 1000 and DV QC-C (lack Control ox) for Cooling Modules and MC DIP Switch and Jumper Standard Connections MC 150 with QC-L (lack Control ox) Standard Connections M 150, 300, 500 and 800 with QC-L (lack Control ox) Standard Connections M 500, 800 and 900 with QC-P (Grey Control ox) Standard Connections M 1000 and 1200 with QC-P (Grey Control ox)...27 Connecting the M 1000 Sections Connecting the M 1200 Sections Standard Connections DV 1000 with QC-P (Grey Control ox) Wiring Diagram for Typical irlinq MS Systems Individual Units, One System Control Panel Individual Units with Cooling Module, One System Control Panel Individual Units with Cooling Module and Group Control Panels, One System Control Panel...31 Combined System MS Connections LON KNX Cnet TM /IP Cnet TM MS/TP MODUS RTU RS irmaster irlinq Online (Ethernet)...37 ppendix 2 Error Descriptions

5 1. Technical Specifications Max. flow rate with epm 10 75%/ePM 10 75% filters at 35 d() Max. flow rate with epm 10 75%/ePM 10 75% filters at 33 d() Max. flow rate with epm 10 75%/ePM 10 75% filters at 30 d() Throw, max. M MC M M M m 3 /h m 3 /h m 3 /h m 3,4 3,4 6,5 7,5 8,1 Condensate pump Flow rate, max. Pump head at flow rate 5 l/h Drain hose air handling unit, int./ext. diameter Drain hose cooling module, int./ext. diameter l/h m mm/mm 4/6 4/6 8/12 8/12 8/12 mm/mm - - 8/12 8/12 8/12 Electric heating surface Thermal cut-out, automatic reset Thermal cut-out, manual reset C C Water comfort heater Power at 60/40 C Delivery/Return Max. operating temperature Max. operating pressure Connections Material Motorised valve, opening and closing time W C bar /8 /DN10 1/2 /DN Copper / aluminium s Electrical connection (with N, PE) ir handling unit voltage Frequency Power consumption Nominal current Power factor Cooling module power consumption, max. Nominal current Power factor Cooling duty, nominal Cooling duty, min. Electric heating surface power consumption (VPH) Nominal current Electric comfort heater power consumption Nominal current Electric preheater power consumption Nominal current Max. leakage current on air handling unit Max. leakage current on cooling module Recommended fuse Max. fuse IP-Code V 1~230 1~230 1~230 1~230 1~230 Hz W ,3 0,4 0,6 1,1 1,1 0,55 0,52 0,56 0,58 0,56 W ,8 6,4 6,8-0,7 0,7 0,71 0,71 W W W / ,6 2,6 3,3/6,5 - - W ,6 4,4 W ,4 6,5 m 0,5 0, m - 1, IP VPH: Virtual Preheat 5

6 Max. flow rate with epm 10 75%/ePM 10 75% filters at 35 d() Max. flow rate with epm 10 75%/ePM 10 75% filters at 33 d() Max. flow rate with epm 10 75%/ePM 10 75% filters at 30 d() Nominal flow rate with epm 10 75%/ePM 10 75% filters Throw, max. M M M DV 900M (Mix.) m 3 /h m 3 /h m 3 /h m 3 /h m 12 10, Condensate pump Flow rate, max. Pump head at flow rate 5 l/h Drain hose air handling unit, int./ext. diameter Drain hose cooling module, int./ext. diameter l/h m mm/mm 4/6 4/6 8/12 5/8 mm/mm /12 Electric heating surface Thermal cut-out, automatic reset Thermal cut-out, manual reset C C Water heating surface Water comfort heater Water heating surface, VPH (Virtual Preheat) Power at 60/40 C Delivery/Return Max. operating temperature Max. operating pressure Connections Material Motorised valve, opening and closing time W C bar /2 /DN15 Copper / aluminium s Electrical connection (with N, PE) ir handling unit voltage Frequency Power consumption Nominal current Power factor Cooling module power consumption, max. Nominal current Power factor Cooling duty, nominal Cooling duty, min. Electric heating surface power consumption (VPH) Nominal current Electric comfort heater power consumption Nominal current Electric preheater power consumption Nominal current Max. leakage current on air handling unit Max. leakage current on cooling module Recommended fuse Max. fuse IP-Code V 1~230 3~230 3~230 3~230 Hz W ,8 2,2 1,4 2,6 0,6 0,6 0,6 0,6 W , ,71 W W W ,9 W ,4 6,5 7,3 - W , ,9 - m m x 13 3 x 13 3 x x 16 3 x 16 3 x 16 IP VPH: Virtual Preheat 6

7 irmaster s M series is delivered either with a black control box (QC-L) or with a grey control box (QC-P). The DV series is always delivered with a grey control box (CQ-P) 2. ir handling units without condensatpump (only possible for M 300, 500, 800 and 1200): HU (16/20 mm hose) M units with QC-L: M 150, MC 150 M 300 (specific designation: ML 300) M 500 (specific designation: ML 500) M 800 (specific designation: ML 800) M units with QC-P: M 500 (specific designation: MP 500) M 800 (specific designation: MP 800) M 900 (specific designation: MP 900) M 1000 (specific designation: MS 1000) M 1200 (specific designation: MP 1200) N! Fit a water lock to avoid unpleasant odours from the wastewater system. The dimensions for the drain hose position can be found under Dimensional Drawings and dditional Dimensions in the installation manuals. Optional installation of condensate drain: The hose can also be run through the outer wall. For this version, drill a hole of suitable diameter and with a 1-2% outward downward gradient. 2. Condensate Drain We recommend connecting the air handling unit s (HU)/ cooling module s (CC) condensate drain to a wastewater pipe from a condensate pump (1.) or directly from the condensate tray (2.) N! Remember to seal the gap between the hose and outer wall. N! The hose must be PROTECTED against formation of ice. 1. ll air handling units and cooling modules with a condensate pump: HU/CC N! Fit a water lock to avoid unpleasant odours from the wastewater system. HU/CC N! The drain hose must not be subjected to negative pressure or a downward incline of over 0.5 m. The dimensions for the drain hose position can be found under Dimensional Drawings and dditional Dimensions in the installation manuals. 7

8 3. Heating Surfaces 3.1. Water Heating Surface The irmaster air handling unit DV 1000 can be fitted with an external water heating surface. M 300, 500, 800, 900, 1000 and 1200 can be fitted with an internal water heating surface. The water heating surface for the DV 1000 is also used to protect against the formation of ice in the heat exchanger. The Virtual Preheat function is used for this purpose. Further details are available in the Operator s Manual. Internal construction: In the case of DV 1000, the internal assembly is installed on the inside of the external heating surface. In the case of M products, the unit must be opened for any connection work. 1 2 TC M For this option, a motorised valve and an automatic heat retention thermostat are fitted on the heating surface. The water heating surface is leakage tested and final inspection performed according to standards and rules in effect. The heating unit s delivery flow is connected to the connection fitting marked FREM ( DELIVERY ) and the return flow to the connection fitting marked RETUR ( RETURN ). N! The dimensioning of pipes and valves and connection of water to the unit must always be carried out by an authorised specialist in accordance with current legislation and regulations. N! There must be clean water in the installation for the internal valves in the water comfort heater to be able to function optimally without problems. It is recommended that shut-off valves, a dirt filter and a line regulating valve be fitted in accordance with the External connection block diagram. It may be necessary (e.g. in the case of a district heating unit) to install a pressure differential regulator if the pressure difference p exceeds 40 kpa (10 kpa = 0,1 bar). External connection: F TD E D C Δp 1 Return connection. (Delivery connection for the M 800.) 2 Delivery connection. (Return connection for the M 800.) 3 Thermostatic heat retention valve (Comap D3803S) with remote temperature sensor (Comap Senso RI). 4 Control valve (Comap D3803S) with electric On/Off valve (allerox ). 5 Water heating surface. 6 irflow leeding Open the water throughflow and bleed the system using the bleed valve (F). fter a short time any air noise in the water throughflow should cease. N! The unit must be bled with fully open valves (3 + 4) Setting the Heat Retention Valve The sensor element (3 - TC) ensures that the water comfort heater maintains a minimum temperature of approximately 8 C provided that there is hot water available. N! The heat supply or water flow must never be cut off or switched off in freezing temperatures, nor when the air handling unit should be out of operation. N! The flow temperature must never fall below 40 C during periods of frost. C D E F Internal assembly (supplied by irmaster). Shut-off valve (supplied by installation contractor). Dirt filter (supplied by installation contractor). Line regulating valve (supplied by installation contractor). Pressure differential regulator (supplied by installation contractor). leed valve (supplied by installation contractor). 8

9 Setting the Kv value on the valves The heating surface is supplied with a heat retention valve (3) and a regulating valve (4) set to 10 (fully open valve). The valves are set according to the calculation and diagram below in order to ensure the necessary flow at the desired differential pressure ( p). N! The system must be bled before it is adjusted. N! It is important to set the valves so that maximum water flow is not exceeded. N! If the differential pressure above the valves is greater than 40 kpa, there is a risk of flow noise from the valves. In this case, a pressure difference regulator should be installed. Example calculation N! This calculation should be performed for each unit setup, to set the valves (3 + 4). The calculation parameters are specific to each unit. The calculation is based on a critical operating situation. Typical water quantity for a delivery/return temperature of 60/40 C: Max. power (W) Water quantity (l/h) M M M M M M DV Use the diagram to find the setting point for the valves (3 + 4). (C) [kpa] [kv] Parameters used in example: OT Lowest outside temperature ( C) RT mbient temperature ( C) n Minimum efficiency of heat exchanger (%) IT Desired inlet temperature ( C) V L Inlet airflow (m 3 /h) t F Water temperature DELIVERY ( C) t R Water temperature RETURN ( C) p Desired differential pressure: kpa (10 kpa = 0.1 bar) 1. Calculate temperature (t) according to heat exchanger. [ C] 2. Calculate heating requirement (Q) for heating the air to the desired inlet temperature. [W] () () [l/h] Plot the calculated water quantity () on the diagram. (Here VV = 125 l/h) Plot the desired differential pressure for the control valve () on the diagram. Here, p = 10 kpa. (The optimal value for the valves is between 10 and 40 kpa.) Use the diagonal lines to read off the value (C) for the valve setting. Set the valve to the calculated value using the presetting key. (In this example the control valve is set to 6.) 3. Calculate the desired water quantity (V V ). [l/h] 9

10 Check Heating Surface Water pipes connected to heating unit Heating surface is bled Valves set Heating surface is waterproof Name of installation engineer: Comment: yes no 4. Electrical Installation N! ll electrical connections to the unit must be carried out by an authorised specialist in accordance with current legislation and regulations. N! The length of all leads used in the installation must be adjusted to fit. N! The power supply must be switched off for all connection work Electric Heating Surfaces irmaster units can be supplied with one or two built-in electric heating surfaces. In such cases, the safety thermostats are installed inside the unit. Electric heating surfaces for MC 150, M 150, M 300 and DV 1000 are installed as comfort heaters but are also used to protect against the formation of ice in the heat exchanger. The Virtual Preheat function is used for this purpose. See the Operator s Manual. N! Electric heating surfaces consume more power. For further details, see Technical Specifications. Safety functions on an electric heating surfaces: The electric heating surfaces are protected against overheating by two safety thermostats for each heating surface, which disconnect the heating surfaces in the event of overheating. The safety thermostats are installed in the heating surface. One of the thermostats disconnects the heating surface and is equipped with an automatic reset. For further details, see Technical Specifications. The second thermostat also disconnects the heating surface but is equipped with a manual reset. For further details, see Technical Specifications Supply Voltage N! pre-fuse and safety switch disconnector must be fitted as part of the permanent installation for the unit in accordance with current legislation and regulations. Pre-fuse and safety switch disconnector are supplied by the installation contractor. N! The supply cable must be dimensioned in accordance with current rules and regulations, taking into account the conditions at the installation location. N! Depending on the unit s power consumption and the existing electrical system, it may be necessary to set up at least one new power circuit. N! When a number of units are installed, the permitted leakage current per unit must be taken into consideration. For further details, see Technical Specifications. N! The control panel, as well as any sensors, switches and optional items, must be fitted before the supply voltage is connected. N! Electrical equipment must be connected in accordance with ppendix 1 Wiring Diagrams. Only M 1000, M 1200 and DV 1000: The units must be connected to the power supply using a 5-wire power supply cable (supplied by the installation contractor) for 3-phase operation (L1, L2, L3, N, PE). 10

11 4.2. Connection of Electrical Equipment Electrical equipment is connected at the control box: In the case of MC 150, M 150, 300, 500, 800 and 1000, under the base plate. In the case of M 900, behind the front cover. In the case of M 1200, under a service panel on the top of the unit s motor section. In the case of DV 1000, under the service panel on the side of the unit. N! ll connection work must be carried out with the power supply switched off in accordance with ppendix 3, Wiring Diagrams. MC 150, M 150, 300, 500 and 800 with QC-L (black control box) The QC-L has 3 analogue inputs available. Input I#1 (J17-5) is programmed as standard for a movement sensor ( PIR ), I#2 (J17-7) for overriding the flow by means of a CO 2 sensor ( CO2 Sensor 1 ) and I#3 (J17-11) for external start ( Ext start ). M 500, 800, 900, 1000 and 1200 and DV 1000 with QC-P (grey control box) The QC-P has 3 digital and 3 analogue inputs. Input DI#1 (J1-7) is programmed as standard for a movement sensor ( PIR ), DI#2 (J1-6) for external start ( Ext start ), DI#3 (J1-5) for start via an -MS ( -MS Start ), I#1 (J1-14) for flow control via -MS ( -MS Flow ), I#2 (J1-13) for inlet temperature control via -MS ( -MS Temp ) and I#3 (J1-12) for overriding the flow by means of a CO 2 sensor ( CO2 Sensor 1 ) Data Cable The connection cable for the control panel is a shielded twisted pair (STP) 2x2x0.6 data cable. Sensors can also be connected with a non-twisted pair but shielded data cable. The following instructions apply when preparing the cable for the terminals in the panel/sensor: Strip the insulation from the sheathing and shielding as closely to the connection terminations as possible for reasons of EMC noise. When stripping the insulation, take care to ensure that the leads are not damaged and do not break. Maintain the twisted pairing of the leads right up to the terminals. The following instructions apply when connecting the cable to the unit s optional plug: Strip the insulation as closely to the connection terminals as possible for reasons of EMC noise. When stripping the insulation, take care to ensure that the leads are not damaged and do not break. Maintain the twisted pairing of the leads right up to the terminals. Terminate the shield (see Shield Termination ). Electrical equipment must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams. N! The length of all leads used in the installation must be adjusted to fit Shield Termination Inputs on all units can be programmed for other signal sources. N! Other settings in the control system software must be performed using a PC running the irlinq Service Tool. The program can be downloaded from The following instructions apply to termination of the shield for both the control panel and all sensors next to the control box inside the air handling unit. Connect drain wire to ground (), cut away shielding foil. N! The shield must be removed at the control panel and sensors. Do not over-tighten the screws. 11

12 Control Panel Carbon Dioxide (CO 2 ) Sensor The delivery usually includes a control panel (loose) and a pre-fitted, 6,5-metre cable. Mount the control panel at a suitable height on the wall, usually in the same room as the air handling unit. It may, however, be placed in an adjacent room. N! Leads for / and 12 V/ must be twisted pair. The screen must be carefully removed to prevent short-circuiting. Electrical equipment must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams Motion (PIR) Sensor The irmaster air handling unit is also available with a CO 2 sensor. This sensor is available as an internally wired and fitted sensor or as an external sensor (shown here). The CO 2 sensors have a sensor range of ppm CO 2. On delivery, the sensor is unconnected and without a lead. If possible, the sensor should be installed 2 m above the ground at a distance of 1 m from the unit s extract air duct. Further details are available under Positioning the unit in the installation manual. ll M and DV units must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams. The connection cable for the PIR sensor is a shielded data cable. On delivery, the sensor is unconnected and without a lead. If possible, the sensor should be installed 2,25 m (1,8-2,5 m) above the ground. Further details are available under Positioning the unit in the installation manual. Electrical equipment must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams. 12

13 External Stop Function The External Emergency Stop function can shut down the unitindependently of other start signals, e.g. in an emergency. The unit is supplied with its own low voltage signal, e.g. by means of a smoke detector via a normally open (NO) contact for as long as the unit is in operation. The unit is started by the programmed start signals. If the function signal is disrupted (contact opens), the unit will stop immediately, regardless of status. MC 150, M 150, 300, 500 and 800 with QC-L (black control box) J J17-5 / 7 / 11 Connect a 13.5 VDC signal, e.g. using a smoke detector via a contact (1) from terminal J17-1 to terminal J17-5 (I#1), J17-7 (I#2) or J17-11 (I#3). Input I#1, I#2 or I#3 must be set to External Emergency Stop using a PC running the irlinq Service Tool. M 500, 800, 900, 1000 and 1200, DV 1000 with QC-P (grey control box) J1-8 J1-5 / 6 / 7 Connect a 12 VDC signal, e.g. using a smoke detector via a contact (1) from terminal J1-8 to terminal J1-5 (DI#3), J1-6 (DI#2) or J1-7 (DI#1). Input DI#3, DI#2 or DI#1 must be set to External Emergency Stop using a PC running the irlinq Service Tool External Start The unit is supplied with its own low voltage signal, e.g. via an external contact (e.g. a circuit breaker or a hygrostat). The unit starts when the contact closes. If the signal is disrupted, the unit will stop oost The boost function can be used to adjust the airflow temporarily. The function is programmed with fixed control voltages for both the supply and the exhaust fan and, if applicable, with afterflow time. It is possible to adjust the control voltages for the fans independently of each other if unbalanced ventilation is required. The unit is supplied with its own low voltage signal, e.g. via an external contact (e.g. a switch) (1). The air handling unit stops normal operation and activates the boost function when the contact closes. If the signal is disrupted, the unit will return to the previous operating mode. If the air handling unit has stopped, the boost function will start the unit. MC 150, M 150, 300, 500 and 800 with QC-L (black control box) J J17-5 / 7 / 11 Connect a 13.5 VDC signal via an external contact (e.g. a switch) (1) from terminal J17-1 to terminal J17-5 (I#1), J17-7 (I#2) or J17-11 (I#3). Input I#1, I#2 or I#3 must be set to oost using a PC running the irlinq Service Tool. The control voltages and, if applicable, after run time for the function must be programmed. M 500, 800, 900, 1000 and 1200, DV 1000 with QC-P (grey control box) J1-8 J1-5 / 6 / 7 Connect a 12 VDC output signal from terminal J1-8 via an external contact (e.g. a switch) (1) to terminal J1-5 (DI#3), J1-6 (DI#2) or J1-7 (DI#1). Input DI#1, DI#2 or DI#3 must be set to oost using a PC running the irlinq Service Tool. The control voltages and, if applicable, after run time for the function must be programmed. 1 Electrical equipment must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams. 13

14 nalogue MS n irmaster air handling unit can be connected to an nalogue uilding Management System (-MS). MC 150, M 150, 300, 500 and 800 with QC-L (black control box) J17-4 J17-5 J17-7 J17-8 J17-11 J V 0-10V The MS system passes the 13.5 VDC output signal via contact (NO) (3) from terminal J17-4 on terminal J17-5 (I#1). Consequently, the ventilation unit will start and stop according to the MS system s programming Checking Electrical Installation yes no Control panel installed PIR sensor installed CO 2 sensor installed External stop installed External start installed oost installed -MS installed Power supply installed Inputs programmed Name of installation engineer: Comment: The airflow volume (4) and inlet temperature (5) are controlled by a potential-free 0-10 volt signal on terminal J17-7 (I#2), on terminal J17-11 (I#3) and on terminal j17-8 of the -MS (4, 5). Input I#1 must be set to -MS Start, input I#2 to -MS Flow and input I#3 to -MS Temp using a PC running the irlinq Service Tool. If you simply wish to stop or start the unit using -MS, and otherwise let it assume the airflow volume and inlet temperature set on the control panel or set by, e.g. a CO2 sensor, the start signal only should be connected to Ext start. Electrical equipment must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams. M 500, 800, 900, 1000 and 1200, DV 1000 with QC-P (grey control box) For all irmaster air handling units with QC-P, the -MS connection is programmed ex works. Electrical equipment must be connected according to the wiring diagrams shown in ppendix 1 Wiring Diagrams. 14

15 5. irlinq MS Installation The irlinq MS (Master/Slave) installation allows up to 20 irmaster air handling units (Unit) and 20 cooling modules (CC Unit) to be controlled from one system control panel and up to 19 group control panels. Please note that all units must have an identical software version. If units purchased at different times are connected together the software will most probably have to be updated in all units. Contact the manufacturer with regard to this. Connect the units (control panel, units and cooling modules) as shown on the diagram. Maximum system cable length is 1000 m. N! Use a shielded twisted pair STP 2x2x0.6 data cable from the control panel to the unit and a shielded twisted pair data cable (PTS 2x0.6) from unit to unit! The shield at each cable must only be connected at one end! N! If over 100 m of data cable needs to be installed on a control panel, please contact irmaster before connecting the cable. N! The first and last unit must be terminated in a DIP Switch (control panel) or a jumper (control box). None of the other units may be terminated. The control panel can be connected as the first or last unit in the chain. N! The system is programmed using a PC running the irlinq Service Tool. System: CC Unit (101) Junction ox (2) CC Unit (y) max. 21cm System Control Panel MSTER, Unit (0) SLVE, Unit (1) Group Control Panel (2) SLVE, Unit (2) SLVE, Unit (x) Wiring Diagram Data Cable: max. 100 m PTS 2x2x0,6 CC Unit (101) (ID101) Junction ox 2 max. 21 cm PTS 2x2x0,6 PTS 2x2x0,6 CC Unit (y) (IDy) Jumper ON System Control Panel (ID179) MSTER Unit (0) (ID0) SLVE Unit (1) (ID1) Group Control Panel 2 (ID162) SLVE Unit (2) (ID2) SLVE Unit (x) (IDx) DIP Switch ON DIP Switch / Jumper OFF Jumper OFF max m 5.1. Connectors See ppendix 1 Wiring Diagrams DIP Switch / Jumper See ppendix 1 Wiring Diagrams Junction ox for Group Control Panels N! The junction box must be installed in the immediate vicinity of the control panel. Cables longer than 21 cm are not permitted and may lead to communication errors Wiring-diagram for typical irlinq MS sytemes See ppendix 1 Wiring Diagrams. 15

16 5.5. System Programming N! ll programming is carried out using the irlinq Service Tool program that is running on the unit to be programmed, i.e. on the unit s control box or cooling module, or on the control panel. Units in an irlinq MS system must be grouped in the building, according to the customer s requirements. This physical grouping is programmed in the master (system 0, unit 0, ID0) using a PC running the irlinq Service Tool program. group could, for example, be room 102 with unit 2 (unit 2, ID2) and unit 3 (unit 3, ID3). In each group, one unit is programmed to be the unit that determines the group s operations (Group Master). ll units must be programmed with the group identity (group ID) to which the unit in question must belong as well as their own identity (Communication ID). cooling module must be paired with the unit on which the cooling module is installed. The cooling module s identity must be programmed. Further details are available in the programming instructions below and in the pairing table to the right. Pairing of units with cooling modules: Unit identity Cooling module identity (Communication ID) (Communication ID) ID0 ID100 ID1 ID101 ID2 ID ID18 ID118 ID19 ID119 n irlinq Viva control panel, which is used as a group control panel, must be programmed with its allocation to a specific group (Group ID) and its own identity (Communication ID). Further details are available in the programming instructions below and in the pairing table to the right. N! The maximum number of group control panels per system is 19. system must always be supplied with an irlinq Orbit control panel as the system control panel. Pairing of irlinq Viva with groups: Group identity Viva identity (Group ID) (Communication ID) G0 ID160 G1 ID161 G2 ID G17 ID177 G18 ID178 The irlinq Orbit control panel is programmed with the following identity ex works: ID179 (Communication ID). This setting should not be changed. When all programming has been completed, the entire system can be put into operation. Further details are available under Commissioning and final inspection. 16

17 Programming Units ID1 to ID19 egin with the unit that will be given the designation ID1. 1. Switch off the unit s power supply. 2. Open the unit and connect a US to mini US cable to the mini US port on the control box. 3. Switch on the power supply to the unit. Wait for 30 seconds. 4. Connect the US to mini US cable to the PC. Start the irlinq Service Tool. 5. Press Connect. The Please select your device window opens. 6. Select Direct Mode and press Enter on the keyboard of the PC. The program establishes communication with the control box. The Please select your device window closes. 7. Select MS - irlinq - Group ID = 0 and press Enter. The Set new value window opens. 8. Enter the group number you wish to allocate to the unit, e.g Press Enter. The Set new value window closes. 10. Select MS - irlinq - Communication ID = 0 and press Enter. The Set new value window opens. 11. Enter 1 for ID Press Enter. The Reboot required window opens. 13. Press Enter. The control box will restart. The Reboot required window closes. 14. Wait for 60 seconds. 15. Switch off the power supply to the unit. 16. Remove the US to mini US cable from the control box. 17. Close the unit. 18. Switch on the power supply to the unit. Repeat the procedure for the rest of the units (ID2, ID3, ID4,... ID19) in numerical order. 17

18 Programming ID0. 1. Disconnect the power supply from the unit. 2. Open the unit and connect a US to mini US cable to the mini US port on the control box. 3. Switch on the power supply to the unit. Wait for 30 seconds. 4. Connect the US to mini US cable to the PC. Start the irlinq Service Tool. 5. Press Connect. The Please select your device window opens. 6. Select Direct Mode and press Enter on the keyboard of the PC. The program establishes communication with the ID0 control box. The Please select your device window closes. 7. Select MS - irlinq - ir Handling Units = 1 and press Enter. The Set new value window opens. 8. Enter the number of air handling units in the system, e.g. 12 for a total of 12 units. 9. Press Enter. The Set new value window closes. 10. Select MS - irlinq - Group 1 Master = 0 and press Enter. The Set new value window opens. 11. Enter the identity ( communication ID ) of the unit that determines operations in, e.g., group 1 and, consequently, must be programmed as Group Master, e.g. 1 for ID1. (Group Master in group 0 is usually ID0; Group 0 Master = 0 ) 12. Press Enter. The Set new value window closes. (ll units belonging to Group 1 will now be controlled by ID1.) Repeat steps 10 to 12 for all groups to be programmed in the system ( Group 0 Master = 0, Group 1 Master = 0, Group 2 Master = 0,... Group 19 Master =0 ) until all necessary Group Masters have been programmed. 13. Switch off the power supply to the unit. 14. Remove the US to mini US cable from the control box. 15. Close the unit. 16. Switch on the power supply to the unit. 18

19 Programming Group Control Panels for Groups 1 to 19 egin with group Connect a US to mini US cable to the control panel s mini US port. Start the irlinq Service Tool. 2. Press Connect. The Please select your device window opens. 3. Select Direct Mode and press Enter on the keyboard of the PC. The program establishes communication with the control panel. The Please select your device window closes. 4. Select Group Settings - Group ID = 0 and press Enter. The Set new value window opens. 5. Enter the group number to which you wish to connect the control panel, e.g. 1 for group Press Enter. The Set new value window closes. 7. Select Group Settings - Communication ID = 160 and press Enter. The Set new value window opens. 8. Enter 161 for ID161. N! The control panel s identity is dependent on the identity of the group to which the control panel is connected. Further details are available in the System programming section. Pairing of irlinq Viva with groups: Group identity Viva identity (Group ID) (Communication ID) G0 ID160 G1 ID161 G2 ID G17 ID177 G18 ID Press Enter. The Reboot required window opens. 10. Press Enter. The control panel restarts. The Reboot required window closes. 11. Remove the US to mini US cable from the control panel. Repeat the procedure for the rest of the group control panels (ID162, ID163, ID164,... ID178). 19

20 Programming Cooling Modules ID1 to ID19 N! cooling module installed on the unit with communication identity ID0 does not need to be programmed. 1. Disconnect the power supply to the air handling unit and the cooling module. 2. Open the cooling module and connect a US to mini US cable to the mini US port on the control box. 3. Switch on the power supply to the unit. Wait for 30 seconds. 4. Connect the US to mini US cable to the PC. 5. Press Connect. The Please select your device window opens. 6. Select Direct Mode and press Enter on the keyboard of the PC. The program establishes communication with the control box from the cooling module. The Please select your device window closes. 7. Select Settings - Communication ID = 100 and press Enter. The Set new value window opens. 8. Enter the cooling module s identity, e.g. 101 for ID101. N! The cooling module s identity is dependent on the identity of the unit installed together with the cooling module. Further details are available in the System programming section. Pairing of units with cooling modules: Unit identity Cooling module identity (Communication ID) (Communication ID) ID0 ID100 ID1 ID101 ID2 ID ID18 ID118 ID19 ID Press Enter. The Reboot required window opens. 10. Press Enter. The control box restarts The Reboot required window closes. 11. Remove the US to mini US cable from the PC. 12. Wait for 60 seconds. 13. Disconnect the power supply to the unit and the cooling module. 14. Remove the US to mini US cable from the control box. 15. Close the cooling module. 16. Switch on the power supply to the unit and the cooling module. Repeat the procedure for the rest of the cooling modules (ID102, ID103, ID104,... ID119). 20

21 6. Commissioning and Final Inspection Once installation of the irmaster unit is complete, the basic operating functions must be checked. Once this has been done, all parameters and the unit s equipment must be programmed in accordance with the customer s operational requirements. N! Initial adjustments must be made to the ducting systems of units before they are started up. N! In the case of irlinq MS systems, general settings can be made for the whole system or for whole groups. However, unit-specific settings must be set on each unit individually, using the irlinq Service Tool. N! During startup of M 1000, it is important that structural noise and vibration is not present (i.e. using drills or hammers on surrounding walls and ceiling), when the power supply is switched on. The calibration of the active noise cancelling (NC) system during startup may fail if excessive structural noise is present. For irlinq Viva and irlinq Orbit: For irlinq Viva and irlinq Orbit: Check that extract air and supply air draw and blow, respectively. Perform other settings using a PC running the irlinq Service Tool. Enter all data required by the Operators Manual and the instructions in the program. ll units (M 500, 800, 900, 1000, 1200 and DV 1000) with QC-P (grey control box): Connect a PC running the irlinq Service Tool to the mini US port at the bottom of the control panel and start the program. Press Connect. Select the unit s communication ID under ddress Mode - Device ddress, e.g. 0 for ID0 or 1 for ID1. Close the unit and the cooling module if they are open. sk the customer about requirements for unit operation. Switch on the power supply to the unit. Only for irlinq Viva: Connect a PC running the irlinq User Tool to the mini US port at the bottom of the control panel. Perform filter calibration from Settings - Process Settings - Filter - Settings. Start the irlinq User Tool. The Startup Guide starts automatically. Or start the Startup Guide from the Settings - Startup Guide menu item in the program. Further details are available on page 20 of the instruction manual supplied with the unit. Follow all instructions in thestartup Guide closely, finishing with start up of the unit. Only for irlinq Viva: The control panel s Startup Guide will start automatically when the unit is started for the first time. Otherwise, it can be activated manually from the Settings - Startup Guide menu item. Further details are available on page 20 of the instruction manual supplied with the unit. Follow all instructions in the Startup Guide closely, finishing with start up of the unit. Highlight the Run filter calibration parameter and press Enter on the keyboard. The Set new value window opens. Set Yes and press Enter on the keyboard. The Set new value window closes. N! Filter calibration must be performed for each individual unit in an irlinq MS system. If filter calibration is not performed when the unit is started up, it will be performed automatically after 25 hours of operation. 21

22 For irlinq Viva and irlinq Orbit: Once the settings have been made according to the customer s requirements, stop the unit temporarily. Restart the unit. Check the inlet flow pattern in the room at max. airflow. djust the inlet flow pattern according to the guide in the Operator s Manual if necessary. Only M 1000: The setting of daptive irflow TM with automatic throw length adjustment is carried out using a PC with the program, irlinq Service Tool. Final inspection: yes no The unit starts correctly ll parameters are programmed Installation engineer s name: N: Remove labels/protective cardboard from the base plate. Inform the customer that installation is complete. Hand over all manuals to the customer. 22

23 ppendix 1 Wiring Diagrams Control ox QC-L (lack Control ox) for MC 150, M 150, M(L) 300, 500 and 800 Connection of databus RS485 (J16) and signal sources (J17): Connection of digital MS/Ethernet (J18) and PC communication (J19); jumper setting: J18 Digital MS J16 J17 Jumper J19 mini- US QC-P (Grey Control ox) for M(P) 500, 800, 900 and 1200, M(S) 1000 and DV 1000 Connection of digital MS/Ethernet (J5), signal sources(j1), connection of the CC300D (J2), databus RS485 (J3) and PC communication (J4): J5 Digital MS mini- US J1 J2 J3 J4 The jumper is set inside the control box. QC-C (lack Control ox) for Cooling Modules and MC 150 Connection of PC communication (J15), jumper setting: Connection of databus RS485 (J6): ON OFF Jumper mini- US J J6 DIP Switch and Jumper DIP Switch next to a control panel. Closed ( ON, standard): Open ( OFF ): jumper in a control box is open as standard ( OFF ). ON ON QC-P and QC-C: QC-L: OFF: OFF: ON: ON: ppendix 1-23

24 Standard Connections MC 150 with QC-L (lack Control ox) L N PE J6- J6- U U/K U U/K J16- J16- J16- J16- OR OR/K U U/K P1 (*1) K: lack U: lue GN: Green OR: Orange YE: Yellow 2 J 15 S1 EM (*1) X1 J 18 J OR U YE/ GN 3 L N PE TR(*1) 24V 0V 3 1 J17-1 J17-11 J17-4 J17-6 J17-1 J17-5 J17-8 J17-7 J larm larm 24V 0-10V External start 1 (*1) 2 (*1) J6 J6- J6- J16 J16- J16- J16- J16- Plug, RS485 + RS485 () - RS485 () Plug, control panel 12 VDC output + RS485 () - RS485 () J17 Plug, option connection J VDC output J17-3 J VDC output J17-5 PIR (I#1) or External Emergency Stop/analogue MS Start (input 0-10VDC or 13,5VDC) J17-6 J Volt CO 2 signal (I#2) or analogue MS flow or analogue MS temperature/external Emergency Stop (input 0-10VDC or 13,5VDC) J17-8 J17-11 External start (I#3) or External Emergency Stop/ analogue MS Start (input 0-10VDC or 13,5VDC) J17-12 J18 MS plug (LON, KNX, MODUS, Cnet TM ), Ethernet J15/J19 Mini- US plug (PC connection) (*1) Option 1 ir handling unit 2 QC-C Cooling module 1 Movement sensor (PIR) (*1) 2 Internal/external CO 2 sensor (*1) EM Energy meter (*1) P1 Control panel (*1) S1 Supply separator (not supplied by irmaster) TR Power supply 24 Volt DC (*1) X1 Terminal clamps, power supply External Emergency Stop, oost, analogue MS start - see section Connection of electrical equipment. N! ll digital and analogue inputs can be programmed using the irlinq Service Tool. ppendix 1-24

25 Standard Connections M 150, 300, 500 and 800 with QC-L (lack Control ox) L N PE S1 J6- J6- U U U/K U/K J16- J16- J16- J16- OR OR/K U U/K P1 (*1) K: lack U: lue GN: Green OR: Orange YE: Yellow X1 OR U YE/ GN (*1) EM (*1) L N PE J 15 1 J17-1 J17-11 J17-4 J17-6 J17-1 J larm larm External start 1 (*1) J 18 J 19 X1 OR U YE/ GN 3 L N PE 7 9 TR(*1) 24V 0V 3 1 J17-8 J17-7 J V 0-10V 2 (*1) J6 J6- J6- J16 J16- J16- J16- J16- Plug, RS485 + RS485 () - RS485 () Plug, control panel 12 VDC output + RS485 () - RS485 () J17 Plug, option connection J VDC output J17-3 J VDC output J17-5 PIR (I#1) or External Emergency Stop/analogue MS Start (input 0-10VDC or 13,5VDC) J17-6 J Volt CO 2 signal (I#2) or analogue MS flow or analogue MS temperature/external Emergency Stop (input 0-10VDC or 13,5VDC) J17-8 J17-11 External start (I#3) or External Emergency Stop/ analogue MS Start (input 0-10VDC or 13,5VDC) J17-12 J18 MS plug (LON, KNX, MODUS, Cnet TM ), Ethernet J15/J19 Mini- US plug (PC connection) (*1) Option 1 ir handling unit 2 Cooling module (*1; M 300, 500 and 800) 1 Movement sensor (PIR) (*1) 2 Internal/external CO 2 sensor (*1) EM Energy meter (*1) P1 Control panel (*1) S1 Supply separator (not supplied by irmaster) TR Power supply 24 Volt DC (*1) X1 Terminal clamps, power supply External Emergency Stop, oost, analogue MS start - see section Connection of electrical equipment. N! ll digital and analogue inputs can be programmed using the irlinq Service Tool. ppendix 1-25

26 Standard Connections M 500, 800 and 900 with QC-P (Grey Control ox) L N J3- OR PE J3- OR/K S1 P1 (*1) U U J3- U J6- U/K J3- U/K J6- U/K K: lack U: lue GN: Green OR: Orange YE: Yellow X1 EM (*1) J 4 J 5 OR U YE/ GN X1 L N PE 1 2 OR 3 4 U YE/ GN L N PE 2 (*1) J 15 1 S2 NO COM J1-9 J1-10 J1-9 J1-7 J1-1 J1-2 J1-11 J1-12 J1-8 J1-6 J1-8 J1-5 J1-14 J1 Plug, option connection J V (DC) output, one sensor J1-2 (24 V) J1-3 larm terminal clamp 1 (NO) J1-4 larm terminal clamp 2 J1-5 nalogue MS Start/External Emergency Stop, digital input (DI#3) J1-6 External start, digital input (DI#2) J1-7 PIR signal, digital input (DI#1) J V (DC) output J V (DC) output J1-10 PIR J1-11 (CO 2 signal, analogue MS flow signal, analogue MS temperature signal) J Volt CO 2 signal input (I#3) J Volt analogue MS temperature signal input (I#2) J Volt analogue MS flow signal input (linear) (I#1) J3 Plug, control panel J3-12 V (DC) output J3- (12 V) J3- + RS485 () J3- - RS485 () larm larm 24V 0-10V 0-10V 1 (*1) 2 (*1) External start -MS start J1-11 -MS flow J V J1-11 -MS temp. J1-3 J1-4 < 24V/100m/2V larm COM J5 MS plug (LON, KNX, MODUS, Cnet TM ), Ethernet J6 J6- J6- Plug, RS485 + RS485 () - RS485 () (*1) Option 1 ir handling unit 2 Cooling module (*1; M 500 and 800) 1 Movement sensor (PIR) (*1) 2 External CO 2 sensor (*1) EM Energy meter (*1) P1 Control panel (*1) S1 Supply separator (not supplied by irmaster) S2 larm contact X1 Terminal clamps, power supply External Emergency Stop, oost - see section Connection of electrical equipment. N! ll digital and analogue inputs can be programmed using a PC with the irlinq Service Tool. J4/J15 Mini- US plug (PC connection) ppendix 1-26

27 Standard Connections M 1000 and 1200 with QC-P (Grey Control ox) L1 J3- OR L2 J3- OR/K L3 P1 J3- U N J3- U/K PE K: lack U: lue GN: Green GY: Grey OR: Orange YE: Yellow S1 J1-9 J1-10 J1-9 J1-7 + larm larm 1(*1) EM (*1) J1-1 J1-2 J1-11 J V 0-10V 2 (*1) J1 1 X1 J 4 J 5 OR GY K U L1 L2 L3 N PE S2 Plug, option connection YE/ GN NO COM J1-8 J1-6 J1-8 J1-5 J V External start -MS start J1-11 -MS flow J1-13 J V (DC) output, one sensor J1-2 (24 V) J1-3 larm terminal clamp 1 (NO) J1-4 larm terminal clamp 2 J1-5 nalogue MS Start/External Emergency Stop, digital input (DI#3) J1-6 External start, digital input (DI#2) J1-7 PIR signal, digital input (DI#1) J V (DC) output J V (DC) output J1-10 PIR J1-11 (CO 2 signal, analogue MS flow signal, analogue MS temperature signal) J Volt CO 2 signal input (I#3) J Volt analogue MS temperature signal input (I#2) J Volt analogue MS flow signal input (linear) (I#1) J3 Plug, control panel J3-12 V (DC) output J3- (12 V) 0-10V J1-11 -MS temp. J1-3 J1-4 < 24V/100m/2V COM J3- + RS485 () J3- - RS485 () J4 larm Mini- US plug (PC connection) J5 MS plug (LON, KNX, MODUS, Cnet TM ), Ethernet (*1) Option 1 ir handling unit 1 Movement sensor (PIR) (*1) 2 External CO 2 sensor (*1) EM Energy meter (*1) P1 Control panel S1 Supply separator (not supplied by irmaster) S2 larm contact X1 Terminal clamps, power supply External Emergency Stop, oost - see section Connection of electrical equipment. N! ll digital and analogue inputs can be programmed using a PC with the irlinq Service Tool. ppendix 1-27

28 Connecting the M 1000 Sections Connecting the M 1200 Sections J20 J21 "J20" "J21" J 7 J 8 J 9 (*2) "IT" (*2) "RT" (*2) "ETV" IT Sensor RT Sensor ETV Sensor J22 J23 J24 J25 J26 CR (*1) "J22" (*1) "J23" (*1) "J24" "J25" (*1) "J26" "" X1-L1 X1-N X1-PE J15 10 J15 11 J15 26 J15 27 J15 28 N (*2) "X2" U 3x0,75 YE/GN K (*2) "X2" U 2x0,25 N K (*2) "CO2" (*1) RD N CP (*1) FT ICO (*1) K2T1 U (*2) "CH" X1-N7 CH (*1) 3x1,5*1 YE/GN X1-PE 7 SKM230-T-12 Output 1 "CR-ED" (*1) J16 X1-N 5 12 K U (*2) "X3" (*1) 2x0,75 M WCH (*1) Output 2 "CR-SD" (*1) J16 2 X1-N 11 N U (*2) "MD" M MD Spring-return K: lack N: rown U: lue GN: Green RD: Red YE: Yellow J20 Plug 1 left section J21 Plug right section J22 Plug 1 front section (internal motion sensor) (IPIR) (*1) J23 Plug 2 front section (I) (*1) J24 Plug 3 front section to plug 2 left section (NC) J25 Plug 3 left section (WCH) (*1) J26 Plug 4 front section (IT) CR Capacitive Return (*1) CR-ED Exhaust ir Damper Capacitive Return (*1) CR-SD Supply ir Damper Capacitive Return (*1) SKM Capacity Unit Capacitive Return (*1) Ground (*1) Option X1 Terminal clamps, power supply (L1 Phase 1, N Neutral, PE Earth) X2 J7 J8 J9 Terminal clamps, condensate pump (CP) and condensate float (FT) Plug, inlet temperature sensor (IT) Plug, room temperature sensor (RT) Plug, exhaust temperature sensor (ETV) J15-10 Input 1 Condensate float (FT) J15-11 Input 2 Condensate float (FT) J15-26 Signal input, Internal CO 2 sensor (ICO) (I#4) J15-27 Output Internal CO 2 sensor (ICO) J15-28 Output 24 V Internal CO 2 sensor (ICO) J16-2 Power supply (230 V) Main damper (MD) (Connection only for models with roof ducts) J16-5 Power supply (230 V) Water comfort heater (WCH) K2 Relay for electrical comfort heater (CH) (*1) Option (*2) Wire label ppendix 1-28

29 Standard Connections DV 1000 with QC-P (Grey Control ox) L1 L2 L3 N PE S1 1 EM (*1) 3 J 4 J 5 X N 2 (*1) J6- U J6- U/K X1 1 OR GY K YE/ U GN L1 L2 L3 N PE 3 L OR 3 U N U YE/GN PE YE/ GN 3 J 15 S2 1 NO COM J16-2 X1-N9 J16-2 X1-N8 J16-5 X1-N7 J3- J3- U J3- U/K J3- J1-9 J1-10 J1-9 J1-7 J1-1 J1-2 J1-11 J1-12 J1-8 J1-6 J1-8 J1-5 J1-14 J1 Plug, option connection J V (DC) output, one sensor J1-2 (24 V) J1-3 larm terminal clamp 1 (NO) J1-4 larm terminal clamp 2 (COM) J1-5 nalogue MS Start/External Emergency Stop, digital input DI#3 J1-6 External start, digital input DI#2 J1-7 PIR signal, digital input DI#1 J V (DC) output J V (DC) output J1-10 PIR J1-11 (CO 2 signal, analogue MS flow signal, analogue MS temperature signal) J Volt CO 2 signal input, I#3 J Volt analogue MS temperature signal input, I#2 J Volt analogue MS flow signal input (linear), I#1 J3 Plug, control panel J3-12 V (DC) output J3- (12 V) J3- + RS485 () J3- - RS485 () N U N U N U 0-10V External start -MS start J1-11 -MS flow J V J1-11 -MS temp. J1-3 larm J1-4 < 24V/100m/2V M M ED(*1) Spring-Return SD(*1) Spring-Return M J6 J6- J6- WCH (*1) (VPH) OR OR/K U U/K J16-1 N J16-2 WH X1-N9 U J16-1 N J16-2 WH X1-N8 U + larm larm 24V 0-10V COM Plug, RS485 + RS485 () - RS485 () P1 1 (*1) 2 (*1) J16 Plug 230 V (C) relays J V (C) output J V (C) output J V (C) output M M ED(*1) no Spring-Return SD(*1) no Spring-Return (*1) Option 1 Ventilation unit 2 Cooling module (*1) 1 PIR sensor (*1) 2 External CO 2 sensor (*1) ED External exhaust air damper (*1) EM Energy meter (*1) P1 Control panel SD External supply air damper (*1) S1 Supply separator (not supplied by irmaster) S2 larm contact WCH External water comfort heater (*1) X1 Terminal clamps, power supply N7 Neutral pin 7 N8 Neutral pin 8 N9 Neutral pin 9 K: lack N: rown U: lue GN: Green GY: Grey OR: Orange WH: White YE: Yellow J4/J15 J5 Mini- US plug (PC connection) MS plug (LON, KNX, MODUS, Cnet TM ), Ethernet oost, External Emergency Stop - see section Connection of electrical equipment. N! ll digital and analogue inputs can be programmed using the irlinq Service Tool. ppendix 1-29

30 Wiring Diagram for Typical irlinq MS Systems Individual Units, One System Control Panel System Control Panel MSTER SLVE SLVE SLVE SLVE Unit (0) Unit (1) Unit (2) Unit (3) Unit (x) PTS 2x2x0,6 System Control Panel (ID179) MSTER SLVE SLVE SLVE SLVE Unit (0) (ID0) Unit (1) (ID1) Unit (2) (ID2) Unit (3) (ID3) Unit (x) (IDx) DIP Switch ON Jumper OFF Jumper ON Individual Units with Cooling Module, One System Control Panel CC Unit (100) CC Unit (101) CC Unit (102) CC Unit (103) CC Unit (y) System Control Panel MSTER, Unit (0) SLVE, Unit (1) SLVE, Unit (2) SLVE, Unit (3) SLVE, Unit (x) PTS 2x2x0,6 CC Unit (100) (ID100) CC Unit (101) (ID101) CC Unit (102) (ID102) CC Unit (103) (ID103) CC Unit (y) (IDy) System Control Panel (ID179) MSTER Unit (0) (ID0) SLVE Unit (1) (ID1) SLVE Unit (2) (ID2) SLVE Unit (3) (ID3) SLVE Unit (x) (IDx) DIP Switch ON Jumper OFF Jumper OFF Jumper ON ppendix 1-30

31 Individual Units with Cooling Module and Group Control Panels, One System Control Panel Junction ox (0) Junction ox (1) Junction ox (18) CC Unit (100) CC Unit (101) CC Unit (118) max. 21cm max. 21cm max. 21cm MSTER, Unit (0) SLVE,Unit (1) SLVE, Unit (18) System Control Panel Group Control Panel (0) Group Control Panel (1) Group Control Panel (18) PTS 2x2x0,6 Junction ox(0) PTS 2x2x0,6 Junction ox(1) PTS 2x2x0,6 Junction ox(18) PTS 2x2x0,6 System Control Panel (ID179) max. 21 cm PTS 2x2x0,6 Group Control Panel (0)(ID160) CC Unit (100) (ID100) max. 21 cm CC Unit (101) (ID101) MSTER SLVE SLVE Unit (0) (ID0) Unit (1) (ID1) Unit (18) (ID18) Group Control Group Control Panel (1)(ID161) Panel (18)(ID178) PTS 2x2x0,6 max. 21 cm PTS 2x2x0,6 CC Unit (118) (ID118) DIP Switch ON DIP Switch / Jumper OFF N! The junction box must be installed in the immediate vicinity of the control panel. Cables longer than 21 cm are not permitted and may lead to communication errors. Jumper OFF Jumper ON ppendix 1-31

32 Combined System Junction ox (4) CC Unit (102) Junction ox (2) CC Unit (105) CC Unit (103) PTS 2x2x0,6 PTS 2x2x0,6 System Control Panel (ID179) MSTER Unit (0) (ID0) PTS 2x2x0,6 DIP Switch ON PTS 2x2x0,6 PTS 2x2x0,6 max. 21 cm max. 21 cm CC Unit (105) (ID105) CC Unit (102) (ID102) SLVE SLVE SLVE Unit (2) (ID2) Unit (3) (ID3) Unit (5) (ID5) SLVE SLVE Group Control Unit (4) (ID4) Unit (x) (IDx) Panel (ID164) Group Control Panel (ID162) Jumper ON DIP Switch / Jumper OFF System Control Panel max. 21cm max. 21cm MSTER, Unit (0) SLVE, Unit (1) SLVE, Unit (2) SLVE, Unit (3) SLVE, Unit (4) SLVE, Unit (5) SLVE, Unit (x) Group Control Panel (4) Group Control Panel (2) Junction ox (4) Junction ox (2) CC Unit (103) (ID103) SLVE Unit (1) (ID1) N! The junction box must be installed in the immediate vicinity of the control panel. Cables longer than 21 cm are not permitted and may lead to communication errors. ppendix 1-32

33 MS Connections The network plug for M 500, 800, 900, 1000 and 1200, DV 1000 with QC-P (grey control box) is named J5. The network plug for MC 150, M 150 and 300 with QC-L (black control box) is named J18. N! Wiring must be connected according to the MS standard. N! Further information on the D-MS documentation is available on irmaster s website: KNX Connection grey KNX red KNX + D1 KNX status LED, green SW2 KNX key, test button Test Status LED is green during programming. ddressing LON Connection Each individual network module is supplied with the same address: J5/J18 D1 S1 us- input and us- input (polarity irrelevant) LON status LED, red Service Pin (test button) Press the test button on the network module to identify the units and establish communication. The test button puts the units into programming mode, enabling among other things change of address to a unique address in the system. Test Status LED flashes. Identification Each individual network module has a Neuron ID. The ID number is located on a label delivered with the module/ glued onto the control box in the unit. For example: QC LON When programming, you can press the test button on the network module to identify the units. Cable Recommendation KNX -registered, certified data cable (Twisted Pair (TP) or Shielded Twisted Pair (STP). list is available on the internet athttps:// Connection of Units 2 twisted-pair wires (1 pair) for KNX and KNX + ccording to KNX ssociation guidelines [KNX TP1 Installation, KNX ssociation] it is not usually necessary to connect the shield to the data cable if a typical standard KNX cable (e.g. KNX TP1) is used in the installation. Cable Recommendation list of cables that comply with Echelon wire guidelines is available at ( Junction ox and Wiring Guidelines engineering bulletin ). ppendix 1-33

34 Cnet TM /IP Connection Port 1 INPUT (3) Port 2 OUTPUT (4) NS Network Status LED (1) MS Module Status LED (2) Link/ctivity Port 1 (5) og Port 2 (6) Identification Each individual network module has a unique unit ID. The ID number is located on a label delivered with the module/ glued onto the control box in the unit. For example: QC CNET The identification number can be read from the status window, using the irlinq Service Tool. Cable Recommendation Test Scanning of the network (e.g. using the nybus IPconfig program, which is available on irmaster s website) using a PC connected directly to the network module or control of MS LED (green light). t least one WG 24 CT 5e STP (Shielded Twisted Pair)data cable with RJ45 connector. The maximum recommended length for an IP segment with WG 24 cables is 70 metres. Connection of Units With QC-L (black control box): D-MS TM Cnet IP Network Connection Unit 1 J18 TM P1 Cnet IP Input P2 Cnet TM IP Output Unit 2 J18 TM P1 Cnet IP Input P2 Cnet TM IP Output Unit X J18 TM P1 Cnet IP Input P2 Cnet TM IP Output With QC-P (grey control box): D-MS TM Cnet IP Network Connection Unit 1 J5 TM P1 Cnet IP Input P2 Cnet TM IP Output Unit 2 J5 TM P1 Cnet IP Input P2 Cnet TM IP Output Unit X J5 TM P1 Cnet IP Input P2 Cnet TM IP Output ppendix 1-34

35 Cnet TM MS/TP Connection 1 NS: Network Status LED 2 MS: Module Status LED 3 Cnet TM plug Pin 1 Signal common / Pin 2 Data - / us- Pin 3 Shield Pin 4 Data + /us- Pin 5./. ddressing Index Parameter Name Value 128 ID405 acnet MS/TP dress ID406 acnet MS/TP aud Rate 9600 ddressing can be performed using the irlinq Service Tool or directly via the network. N! Cnet TM MS/TP systems must be terminated according to the system s standard. Cable Recommendation Shielded Twisted Pair (STP) data cable (2+1 or 2x2) according to NSI/SHRE ddendum to NSI/SHRE Standard Test MS LED is green. Characteristic impedance between 100 and 130 ohms. Capacitance between the wires must be less than 100 pf per metre. Maximum recommended length in an MS/ TP segment with an WG 18 cable is 1200 m. The shield is placed on the frame according to the drawing below. Connection Each individual network module has a unique unit ID. The ID number is located on a label delivered with the module/ glued onto the control box in the unit. For example: QC CNET The identification number can be read from the status window, using the irlinq Service Tool. Connection of Units With QC-L (black control box): D-MS Signal common / Data - / us- Data + / us- 1 Signal common 2 Data - / us- 3 Shield 4 Data + / us- 5. /. Unit 1 J18 Unit 2 J18 1 Signal common 2 Data - / us- 3 Shield 4 Data + / us- 5. /. 1 Signal common 2 Data - / us- 3 Shield 4 Data + / us- 5. /. Unit X J18 J17-10 () J17-10 () J17-10 () With QC-P (grey control box): D-MS Signal common / Data - / us- Data + / us- 1 Signal common 2 Data - / us- 3 Shield 4 Data + / us- 5. /. Unit 1 J5 Unit 2 J5 1 Signal common 2 Data - / us- 3 Shield 4 Data + / us- 5. /. 1 Signal common 2 Data - / us- 3 Shield 4 Data + / us- 5. /. Unit X J5 J1-11 () J1-11 () J1-11 () ppendix 1-35

Ventilation in balance

Ventilation in balance Ventilation in balance AIRLINQ - DIGITAL BMS PARAMETERS FOR BACNET TM /IP. BACNET TM MS/TP BASIC INFORMATION The present document is only valid for air handling units with firmware version 6. or newer.

More information

Ventilation in balance

Ventilation in balance Ventilation in balance AIRLINQ - DIGITAL BMS PARAMETERS FOR MODBUS RTU RS485 BASIC INFORMATION The present document is only valid for air handling units with firmware version 6. or newer. The firmware

More information

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ZIP Economizer Fault Detection and Diagnostics (FDD) Table Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns

More information

CX-SERIES ADVANCED BATTERY CHARGER

CX-SERIES ADVANCED BATTERY CHARGER CX-SERIES ADVANCED BATTERY CHARGER Table of Content 1. IMPORTANT SAFETY INFORMATION... 2 1-1 General Safety Precautions... 2 1-2 Battery Precautions... 2 2. FEATURES... 3 2-1 Battery Charging Curve...

More information

A 601 A B C. 1. How it works

A 601 A B C. 1. How it works 601 W4 DXN6P25 Variable flow-control 6-way valve, series DXN6_ For 4-pipes climate ceilings with change-over Pressure independent variable flow-control Integrated flow measurement Power supply U v : 24Volt

More information

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18 Zone Sensors Submittal Data English Language/IP Units SD1582EW 06/18 ZS Series RNet Zone Sensors ZS Series RNet Sensor Overview The ZS Series line of intelligent zone sensors provides the function and

More information

INTECH Micro 2300-RTD6

INTECH Micro 2300-RTD6 INTECH Micro 2300-RTD6 6 Channel RTD Input Station Overview. The Intech Micro 2300 Series is a system of modular I/O Remote Stations, that add an even lower cost option to Intech s already extensive intelligent

More information

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when

More information

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

How to Order. Nil. W Water-cooled refrigerator type. Temperature: 5 to 40 C, Humidity: 30 to 70%RH Clean water 5 to /1.

How to Order. Nil. W Water-cooled refrigerator type. Temperature: 5 to 40 C, Humidity: 30 to 70%RH Clean water 5 to /1. Thermo-cooler Series HRGC Specifications HRGC//5 Cooling method Refrigerant Control method Ambient temperature/humidity Circulating fluid Note ) Temperature range setting Note ) C Cooling capacity Note

More information

REMOTE POWERING Central Energy System ( HUB )

REMOTE POWERING Central Energy System ( HUB ) / 0 REMOTE POWERING Central Energy System ( HUB ) User Guide Mitra E&I SCA Wavre Belgium 009 Subject to modifications without notice / 0 Content RECTIFIER SYSTEM - USER MANUAL The information and pictures

More information

TECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00

TECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00 TECHNICAL MANUAL EN Inverter / Charger Combi Combi SW 12V 1600VA Réf : PF.16088 Combi SW 24V 3800VA Réf : PF.16089 SAFETY PRECAUTIONS TO PREVENT ANY RISK OF ELECTRIC SHOCK OR FIRE, READ THIS MANUAL CAREFULLY

More information

TA-6-way valve. NPT threads. Standard control valves 6-way valve for change-over systems

TA-6-way valve. NPT threads. Standard control valves 6-way valve for change-over systems T-6-way valve NPT threads Standard control valves 6-way valve for change-over systems IMI T / Control valves / T-6-way valve NPT threads T-6-way valve NPT threads The 6-way valve solution enables various

More information

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem / Series Characterized Control Valve, Spring ctuator Two-way and Three-way Valves with Chrome Plated rass all and rass Stem, NPT Female Ends Service: Flow Characteristic: Media Temp Range: mbient Temp

More information

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

SERVICE MANUAL (DOMESTIC & INTERNATIONAL) SERVICE MANUAL (DOMESTIC & INTERNATIONAL) DUAL TECHNOLOGY FINISHER MODEL 1960 & 1980 SERIES Lincoln Foodservice Products, LLC 1111 North Hadley Road Fort Wayne, Indiana 46804 United States of America Telephone:

More information

Accessories STRA Room Controller

Accessories STRA Room Controller Accessories STRA Room Controller External temperature sensor, STRZ-5-b Technical data room sensor: STRZ-5-5 C PT, DIN class B IP Technical data external sensor: STRZ-5-2 - +7 C PT, DIN class B Technical

More information

RVD125/109 RVD145/109

RVD125/109 RVD145/109 G2511 en Installation Instructions District heating and d.h.w. controller RVD125/109 RVD145/109 Installation without base Place of installation Compact station front or control panel front Permissible

More information

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0 APP EOLE4 Applicable to program versions TAC5 Version DT 2.8.2 & DG 2.7.0 2 THE APP EOLE4 INTERFACE This interface can be used on Android, IOS and PC. Download the app from the App Store/Google Play or

More information

Phoenix Inverter

Phoenix Inverter Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC

More information

EC200 ELECTRONIC CONTROL SYSTEM

EC200 ELECTRONIC CONTROL SYSTEM 1 INTRODUCING THE EC200 ELECTRONIC CONTROL SYSTEM With the use of new technology and an innovative approach to user interfacing, the EC200 Power Control System provides a complete control solution for

More information

Accessories. Series REC

Accessories. Series REC Accessories Series REC 5-7-9 ACCESSORIES REC Series RBA BAF RBE CV3 PC3 SRE PSD CSA GIU TPA O. REC 5 REC 5-6 - 5BT11 5BT6 1CO71 1CO73 1SE96 5PR 1KR6 5SU137 5TE1 REC 5-12 5BT12 5BT122 5BT121 1CO71 1CO73

More information

User manual Temperature Calibrator JOFRA CTC-140/320/650 A/B JOFRA CTC-1200 A Copyright 2005 AMETEK DENMARK A/S ( UK)

User manual Temperature Calibrator JOFRA CTC-140/320/650 A/B JOFRA CTC-1200 A Copyright 2005 AMETEK DENMARK A/S ( UK) User manual Temperature Calibrator JOFRA CTC-140/320/650 A/B JOFRA CTC-1200 A Copyright 2005 AMETEK DENMARK A/S (123199-UK) FIG. 1 1 2 3 4 5 CALI BRAT ION I NSTRUM ENTS 6 + - Switch Test RS232 7 8 11

More information

Sturdy Truck Body Poultry Shipping Truck - Operations Manual August 2003

Sturdy Truck Body Poultry Shipping Truck - Operations Manual August 2003 1.0 Introduction The Sturdy ventilation controller is designed to automatically control indoor air quality including: temperature, relative humidity, carbon dioxide and oxygen in the interior of the vehicle

More information

Induction Power Supplies

Induction Power Supplies Induction Power Supplies 7.5kW; 135 400kHz 480V version (Integral Heat Station) User s Guide Model 7.5-135/400-3-480 SMD Control Brds Rev. D 5/08 Table of Contents 1. Specifications and features...3 2.

More information

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management Ductable units NEW Eco-Design Filter Air handling unit with high available static pressure V3000 control Fresh air management The range of air handling units is designed for suspended ceiling heating and

More information

Overview of types. Technical data

Overview of types. Technical data Technical data sheet 6..S+NVFT24-MFT-E Globe valves, 2-way, with flange PN 16, actuator with emergency control function for closed hot water systems up to 150 C in district heating applications approved

More information

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator /3 Series Characterized Control Valve, Non-Spring ctuator Two-way and Three-way Valves with Chrome Plated rass all and rass Stem, NPT Female Ends Service: Flow characteristic: Media Temp Range: mbient

More information

EC400 Power Control System

EC400 Power Control System 1 Introduction This section of the handbook will guide you through the operation of the electrical system. Further technical details are contained in section 3 or in the supporting technical manual available

More information

Section 3 Technical Information

Section 3 Technical Information Section 3 Technical Information In this Module: Engine identification Modes of operation Battery charging and heat manage operation Service and repair procedures Maintenance requirements Engine Identification

More information

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside

More information

Advanced Battery Charger. 3 - stage charging capability (IUoU) 25A

Advanced Battery Charger. 3 - stage charging capability (IUoU) 25A Cxx Features: Universal AC input with active PFC Compatible with Lead Acid, Li-ion, Gel and AGM batteries Support optional remote controller (CR-) Voltage / temperature compensation with battery temp.

More information

Products Tde Macno. User s Manual BRAKING UNIT. Cod. MP00401E00 V_1.0

Products Tde Macno. User s Manual BRAKING UNIT. Cod. MP00401E00 V_1.0 Products Tde Macno User s Manual BRAKING UNIT Cod. MP00401E00 V_1.0 SUMMARY 1 GENERAL DESCRIPTION... 2 2 USE LIMITATIONS... 2 2.1 Climatic Class... 2 2.2 Resistance To Chemically Active Substances...

More information

B2 Series Characterized Control Valve, Non-Spring Return Actuator

B2 Series Characterized Control Valve, Non-Spring Return Actuator 2 Series Characterized Control Valve, Non-Spring ctuator Two-way Valve with Stainless Steel all and Stem, NPT Female Ends Service: Flow Characteristic: Media Temp Range: Maximum Differential: Pressure

More information

ECONOMISER SERIES E2T USER MANUAL

ECONOMISER SERIES E2T USER MANUAL TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014

More information

CBQ Multiservice chilled beam platform for suspended installation

CBQ Multiservice chilled beam platform for suspended installation CBQ Multiservice chilled beam platform for suspended installation Factory-fitted and tested CBQ-units are supplied to site as a single-fix device satisfying comfort cooling, heating and lighting needs.

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

REVISION HISTORY REVISION HISTORY

REVISION HISTORY REVISION HISTORY FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim

More information

BAS Construction Checklist

BAS Construction Checklist BAS Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist items

More information

The Traveler Series: Wanderer

The Traveler Series: Wanderer The Traveler Series: Wanderer RENOGY 30A Charge Controller Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version: 2.0 Important Safety Instructions Please save these instructions. This

More information

Proportional pressure reducing valves type DHRZO direct operated, ISO 4401 size 06

Proportional pressure reducing valves type DHRZO direct operated, ISO 4401 size 06 www.atos.com Table TF040-4/E Proportional pressure reducing valves type DHRZO direct operated, ISO 440 size 06 A DHRZO are 3 way, proportional pressure reducing valves, direct operated, with standard ISO

More information

Issue 2.0 December EPAS Midi User Manual EPAS35

Issue 2.0 December EPAS Midi User Manual EPAS35 Issue 2.0 December 2017 EPAS Midi EPAS35 CONTENTS 1 Introduction 4 1.1 What is EPAS Desktop Pro? 4 1.2 About This Manual 4 1.3 Typographical Conventions 5 1.4 Getting Technical Support 5 2 Getting Started

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

Digital Room Thermostats with Touch Screen LCD

Digital Room Thermostats with Touch Screen LCD TC40 Touch Series Digital Room Thermostats with Touch Screen LCD Revision Date February 22, 2013 Features Wall-mount Display Control to match any decor Extra large easy-to-read Liquid Crystal Display (LCD),

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

Solar Controller SUNGO S

Solar Controller SUNGO S OPERATING INSTRUCTIONS, Issue SW1201/ 2.01/ HW2.4 Solar Controller SUNGO S Wagner& Co Figure 1 Solar Controller SUNGO S. The benefits at a glance Large display to indicate temperature, balance values and

More information

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features. Page of 7 Application control unit, in conjunction with the associated hydraulic set provides a complete pressure independent balancing and control group for efficient and effective individual room or

More information

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Quick guide. Plug-in fans GPPM with FC101_106 August 2014 Quick guide Plug-in fans GPPM with FC101_106 August 2014 Fläkt Woods permanent magnet motors and speed controllers for plug fans GPPM 1. General Fläkt Woods offers a wide range of permanent magnet motors

More information

Centriflow Plus EC. Technical data

Centriflow Plus EC. Technical data Technical data Centriflow Plus CTLOGUE Contents General description...3 General survey chart...4 Design description Fan Impeller...5 Inlet cone and supporting frame...5 EC motor...5 ir flow sensor...6

More information

Zonestar Installation Manual

Zonestar Installation Manual Zonestar Installation Manual National Sales Ph: 1300 306 125 sales@ias.net.au Product Support Freecall: 1800 354 434 support@ias.net.au Designed and Manufactured in Australia by: Innovative Air Systems

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin LowNOx Commercial Gas Electronic Spark Ignition Sequence The Universal TM gas LowNOx series water heaters contain an electronic spark ignition system. The heater is connected to a 120VAC power source required by the transformer. The transformer steps down the

More information

V1.0. Showven Technologies Co.,Ltd.

V1.0. Showven Technologies Co.,Ltd. V1.0 Showven Technologies Co.,Ltd. SONICBOOM TM SMOKEJET USER MANUAL Foreword Thanks for choosing SHOWVEN SONICBOOM TM SMOKEJET. Please read following manual carefully and completely before operating this

More information

MODEL FA1 Mini Air Filtration System. Operations Manual

MODEL FA1 Mini Air Filtration System. Operations Manual MODEL FA1 Mini Air Filtration System Operations Manual READ AND SAVE THESE INSTRUCTIONS WARNING: Disconnect from power supply before performing maintenance procedures such as cabinet cleaning, changing

More information

EC225 Power Control System

EC225 Power Control System 1 Key Features 200W (~16A) combined Power Converter / Battery Charger - Converts the 230V mains supply into 12v DC power to run the leisure equipment and charge the battery using an intelligent two-stage

More information

7 Services Control and monitoring

7 Services Control and monitoring Control and monitoring 7 Services We are the only manufacturer of laboratory equipment who offers you fume cupboards and variable fume cupboard control all from one supplier. Benefit from our know-how

More information

ADAPTTM. Free. Active communicative, supply air diffuser for the WISE system, ADAPT F

ADAPTTM. Free. Active communicative, supply air diffuser for the WISE system, ADAPT F ADAPTTM Free Active communicative, supply air diffuser for the WISE system, ADAPT F Quick facts Supply air diffuser with an active damper Pressure-dependent and cleanable Integrated sensor module Simple

More information

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14 Zone Sensors Submittal Data English Language/IP Units SD1582EW 10/14 ZS Series RNet Zone Sensors ZS Series RNet Sensor Overview The ZS Series line of intelligent zone sensors provides the function and

More information

Advanced Battery Charger 0 ~ 15A 0 ~ 25A 0 ~ 35A 0 ~ 50A 0 ~ 80A. 3 - stage charging capability (IUOU) 90 ~ 264VAC (refer to de-rating curve)

Advanced Battery Charger 0 ~ 15A 0 ~ 25A 0 ~ 35A 0 ~ 50A 0 ~ 80A. 3 - stage charging capability (IUOU) 90 ~ 264VAC (refer to de-rating curve) Cxx Features: Universal AC input with active PFC Compatible with Lead Acid, Li-ion, Gel and AGM batteries Support optional remote controller (CR-) Voltage / temperature compensation with battery temp.

More information

PN [ ] D7150NL/BAC D7200WL/BAC D7250WL/BAC D7300WL/BAC [ ]

PN [ ] D7150NL/BAC D7200WL/BAC D7250WL/BAC D7300WL/BAC [ ] Technical data sheet D7../C utterfly valve with actuator, Flange, P 16 Torque motor 160 m ominal voltage C 24...240 V / DC 24...125 V Control Open-close, modulating, communicative for mixing and diverting

More information

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

Pure Sine Wave Inverter GP-HS1500. Owner s Manual Pure Sine Wave Inverter GP-HS1500 Owner s Manual 2 Table of Contents Introduction 3 Specifications 4 Name and Main Function 5 Installation 7 Operation 9 Operating Limits 13 Troubleshooting 13 Maintenance

More information

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER KEW6201A CONTENTS 1. Safe testing 1 2. Procedure of removing cover. 3 2.1 Method of removing the cover. 3 2.2 Method of storing the cover. 3 3. Product summary

More information

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes Instructions for the BASIC BCVA Rotary heat exchanger, Sizes 080 120 1. General The BCVA heat recovery unit is a rotary heat exchanger that offers high temperature efficiency. The heat exchanger operates

More information

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With

More information

GSL Electronics Modified Sine Wave Power Inverters

GSL Electronics Modified Sine Wave Power Inverters GSL Electronics Modified Sine Wave Power Inverters Congratulations on choosing one of our Modified Sine Wave Inverters for your application. There are 6 models in the range, which will meet most of your

More information

RVP-R- VAV controller. In explosion-proof version

RVP-R- VAV controller. In explosion-proof version VAV controller In explosion-proof version RVP-R- SMAY LLC / 29 Ciep³ownicza St. / 31-587 Cracow / Poland tel. +48 12 378 18 00 / fax. +48 12 378 18 88 / e-mail: info@smay.eu Intended use VAV control units

More information

Specification of Battery Charger

Specification of Battery Charger Revision No.: 02 Specification of Battery Charger MODEL: 2460SR-1 24V / 30A IP-54 LEAD ACID BATTERY CHARGER Page 1 of 11 Contents 1. General--------------------------------------------------------------------------3

More information

VALVE CONTROLLERS Controllers for Dust Extr 2010 / 2011 action Technology

VALVE CONTROLLERS Controllers for Dust Extr 2010 / 2011 action Technology VALVE CONTROLLERS Controllers for Dust Extraction 2010 Technology / 2011 Valve controllers for all cases HESCH has the skills and technology to tackle any control task for dedusting of filter and dust

More information

ADAPTTM. Extract. Extract air diffuser for the WISE system. Quick Selection

ADAPTTM. Extract. Extract air diffuser for the WISE system. Quick Selection ADAPTTM Extract Extract air diffuser for the WISE system Quick facts Active damper Pressure-dependent and cleanable Integrated sensor module Simple wiring, Plug & Play Communication via Modbus RTU Supplied

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

Advanced Battery Charger. 3 - stage charging capability (IUOU) 4.1 A / 100VAC 1.8A / 240VAC

Advanced Battery Charger. 3 - stage charging capability (IUOU) 4.1 A / 100VAC 1.8A / 240VAC Cxx Features: Universal AC input with active PFC Compatible with Lead Acid, Li-ion, Gel and AGM batteries Support optional remote controller (CR-) Voltage / temperature compensation with battery temp.

More information

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

INLINE Flow sensor for hazardous area II 1 G/D - II 2 D - II 3 GD - I M1

INLINE Flow sensor for hazardous area II 1 G/D - II 2 D - II 3 GD - I M1 INLINE Flow sensor for hazardous area II G/D - II D - II GD - I M Type SE0 Ex can be combined with... Flow meter with NAMUR or NPN/PNP output signal Mounting, dismounting of electronics by a Quarter-Turn

More information

Manual. BlueSolar Grid Inverter 1500 / / / / / 230

Manual. BlueSolar Grid Inverter 1500 / / / / / 230 Manual EN BlueSolar Grid Inverter 1500 / 230 2000 / 230 2800 / 230 4000 / 230 5000 / 230 Before you start This manual contains important information regarding installation and safe operation of this unit.

More information

RVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths

RVD120 RVD G2510. Installation. Place of installation. Electrical installation. Permissible cable lengths en Installation Instructions District heating and d.h.w. controller 74 39 68 G25 RVD2 RVD4 Keep these instructions with the controller! Installation Place of installation In a dry room, e.g. the heat exchanger

More information

ADAPTTM. Sphere. Active communicative, supply air diffuser for the WISE system. Quick Selection

ADAPTTM. Sphere. Active communicative, supply air diffuser for the WISE system. Quick Selection ADAPTTM Sphere Active communicative, supply air diffuser for the WISE system Quick facts Supply air diffuser with an active damper Pressure-dependent and cleanable Integrated sensor module Simple wiring,

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

HRH. High efficiency heat recovery units. from 300 to m³/h >70 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR

HRH. High efficiency heat recovery units. from 300 to m³/h >70 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR 4 Lmf Clima 6 HRH High efficiency heat recovery units WITH HIGH EFFICIENCY HEAT RECOUPERATOR from 3 to 4.3 m³/h The HRH units have been designed for non-residential applications for which a forced and

More information

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL 1. INTRODUCTION VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down 24V to 12V DC-DC Converter has a programmable 12.0 to 15.0V output in

More information

VE-S_15-32 Pressure Independent Balancing & Control Valves

VE-S_15-32 Pressure Independent Balancing & Control Valves Page 1 of 9 VE-S_15-32 Pressure Independent Balancing & Control Valves (PIBCV) is used in heating and cooling systems in applications with Fan Coil Units, Chilled Beams or other terminal unit applications.

More information

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw TWA 212-1102 S/K/P Incorporating R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw The complete solution to all your cooling needs TWA 212-1102 S/K/P Index

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

1. SPECIFICATION. Altitude of motor installation. Information: Resistance and temperature specifications of the PTC thermistor / posistor/.

1. SPECIFICATION. Altitude of motor installation. Information: Resistance and temperature specifications of the PTC thermistor / posistor/. 1. SPECIFICATION 5 GENERAL INFORMATION Motors with parameters according to the data sheet comply with the requirements of the IEC 60034-1 standard, and IEC 60034-30 class efficiency IE2 Motor versions:

More information

Safety Precautions Product Contents Product PIN Diagram LED indicators Product Dimensions Installation of Panel with Casing Wire Legend Power Wiring

Safety Precautions Product Contents Product PIN Diagram LED indicators Product Dimensions Installation of Panel with Casing Wire Legend Power Wiring www.zkteco.com Safety Precautions Product Contents Product PIN Diagram LED indicators Product Dimensions Installation of Panel with Casing Wire Legend Power Wiring Diagram FR1200 Connection Weigand Connection

More information

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System POWER TROLLEY 8 Model: SINE 1548 Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System Version 07 CONTENTS Page 1. INTRODUCTION... 1 2. USING THE POWER TROLLEY.... 2 3. BATTERY BACKUP

More information

TA-6-way valve. Standard control valves 6-way valve for change-over systems

TA-6-way valve. Standard control valves 6-way valve for change-over systems TA-6-way valve Standard control valves 6-way valve for change-over systems IMI TA / Control valves and Actuators / TA-6-way valve TA-6-way valve The 6-way valve solution enables various control set-ups

More information

HRS. Very high efficiency heat recovery units. from 300 to m³/h >90 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR

HRS. Very high efficiency heat recovery units. from 300 to m³/h >90 % WITH HIGH EFFICIENCY HEAT RECOUPERATOR 4 Lmf Clima 6 FERRARO GROUP HRS Very high efficiency heat recovery units WITH HIGH EFFICIENCY HEAT RECOUPERATOR from 3 to 4. m³/h Air-handling unit designed and manufactured for nonresidential applications,

More information

Instruction of Solar Charge Controller. User s Manual

Instruction of Solar Charge Controller. User s Manual Instruction of Solar Charge Controller User s Manual 12V/24V 30A Dear Users: Thank you for selecting our product. Please read this manual carefully before you use this product. The controller is for off-grid

More information

Silvertel. Ag Features. 2. Description. Power-Over-Ethernet Module. IEEE802.3af compliant. Small SIL and SMT package available

Silvertel. Ag Features. 2. Description. Power-Over-Ethernet Module. IEEE802.3af compliant. Small SIL and SMT package available Silvertel V2.2 Jan 2015 Datasheet Ag9700 Pb 1. Features IEEE802.3af compliant Small SIL and SMT package available Low cost, with minimal external components required Input voltage range 36V to 57V Short-circuit

More information

INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS SD UK/IE (2010/04)

INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS SD UK/IE (2010/04) INSTALLATION AND OPERATING INSTRUCTIONS SOLAR HEATING PROGRAMMER TDS 300 6720613720-00.1 SD UK/IE CONTENTS Contents Contents 2 1 Safety instructions and explanation of symbols 5 1.1 General safety instructions

More information

C RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

C RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS C RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION Thermoscreens Ltd St. Mary s Road Nuneaton Warwickshire England

More information

EPS/ELA-Series User Manual EPS/ELA 250W

EPS/ELA-Series User Manual EPS/ELA 250W EPS/ELA-Series User Manual EPS/ELA 250W EPS Stromversorgung GmbH Tel: +49 (0)821 570451 0 Index 3 Page: 1 Table of contents: Page 1. Features of ELA-Series... 3 1.1 Basic Functions... 3 1.2 Options...

More information

MODEL NUMBER: MEDIUM DUTY ONBOARD AIR SYSTEM

MODEL NUMBER: MEDIUM DUTY ONBOARD AIR SYSTEM MODEL NUMBER: 10003 MEDIUM DUTY ONBOARD AIR SYSTEM IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using

More information

VEX140 Horizontal. with Electric heating coil HCE VEX100. Original instructions. Product information... Section 1 + 8

VEX140 Horizontal. with Electric heating coil HCE VEX100. Original instructions. Product information... Section 1 + 8 Product Instruction VEX140 Horizontal with Electric heating coil HCE VEX100 R A N G E CROSS FLOW HEAT EXCHANGER Unit supplied with (factory fitted): Airflow control Icing detector Electric heating coil

More information

Silvertel. Ag Features. 2 Description. Power-Over-Ethernet Module. IEEE802.3af compliant. Small SIL package size - 56mm (L) x 14mm (H) Low cost

Silvertel. Ag Features. 2 Description. Power-Over-Ethernet Module. IEEE802.3af compliant. Small SIL package size - 56mm (L) x 14mm (H) Low cost Silvertel V2.5 Feb 2014 Datasheet Pb 1 Features IEEE802.3af compliant Small SIL package size - 56mm (L) x 14mm (H) Low cost Input voltage range 36V to 57V Minimal (low cost) external components required

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A

ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE A ELIOS 25 DIGITAL CONTROL UNIT WITH LCD DISPLAY FOR THERMAL SOLAR SYSTEMS TDS 006 M00 0SE 012945A0 040906 1 MAIN FEATURES Power supply 230V~ ±10% 50Hz Backlit alphanumeric LCD display Management of 5 output

More information

EMERGENCY VEHICLE BATTERY MANAGER PS2024

EMERGENCY VEHICLE BATTERY MANAGER PS2024 EMERGENCY VEHICLE BATTERY MANAGER PS2024 2 The PS2024 (Fig. 1) is designed as a on-vehicle battery charger / battery charge state monitor. While the vehicle is at its base or station, the charger is connected

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

7/S6 FIRE DAMPER FDC40. v 2.9 (en) 7/S6 v.9 (en) FIRE DAMPER FDC0 www.klimaoprema.hr 8 TABLE OF CONTENTS FIRE DAMPER FDC0 87 FIRE CLASSIFICATION 87 SELECTION DIAGRAM 88 ORDERING KEY 88 DAMPER MODELS 89 FDC0-M cylindrical fire damper with

More information