IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

Similar documents
(K),(M),(P)489TB/G Up to 42 kv

(K),(M)430TB/G Up to 36 kv

Nexans Network Solutions Div. Euromold

ELB ES. Product Installation Instructions

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

a Nexans company Catalogue 2008

ELB ELB

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

IS90750-ENG - 430TB/G-45/LCA 14 January 201 O - Revision 7 - Supersedes edition of 25 June 2009 Page 1 of 9

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

INTERFACE F MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

INSTALLATION INSTRUCTION

Installation instruction PEM1150ENG

INTERFACE E - 5/8" MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

a Nexans company Catalogue 2011

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

QT-III Cold Shrink Silicone Rubber

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

HVS S 15kV Class

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

Installation Instruction EPP /92

a Nexans company Medium voltage symmetrical separable connectors - Interface C -

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink QT-III Silicone Rubber Termination

Nexans Network Solutions Div. Euromold

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

a Nexans company Catalogue 2007

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

INTERFACE C MEDIUM VOLTAGE SYMMETRICAL SEPARABLE CONNECTORS CATALOGUE 2017

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

a Nexans company Catalogue 2007

Power cables accessories for use in potentially explosive atmospheres

Installation Instructions

INSTALLATION INSTRUCTION PEM1121ENG ENGLISH

a Nexans company Catalogue 2012

VITALink Taped Splice Pigtail Crimp

I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv

Nexans Network Solutions Div. Euromold

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH

a Nexans company Catalogue 2006

High Voltage Accessories up to 72.5 kv

OFFSHORE WIND FEASIBILITY STUDY APPENDICES Appendix C.2 Subsea Cable Data Sheets

MV TERMINATIONS. INDOOR SINGLE CORE TERMINATION - ELTI-1C for polymeric cables - Slip-on termination - Modular type APPLICATION STANDARDS

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink Splice Kit QS-III 5536A

Installation Instructions

a Nexans company Catalogue 2009

a Nexans company Catalogue 2015

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

a Nexans company Catalogue 2008

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

UNSIGNED HARDCOPY NOT CONTROLLED

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Caledonian Medium Voltage Cables Three Core Cables to VDE 0276-

THORNE & DERRICK UK TEL FAX TEL FAX

Cold-shrinkable Silicone 12 kv - 24 kv - 36 kv

Company Directive STANDARD TECHNIQUE: CA3V/3. Relating to Procedures for Making 33kV CableTerminations

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

C Power Connection Kit

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

Effective November 2016 Supersedes February 2012 (S )

INTERFACE A MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017

Caledonian Medium Voltage Cables

Caledonian Medium Voltage Cables

QUICKTERM TERMINATION KIT

a Nexans company Catalogue 2009

a Nexans company Catalogue 2015

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

a Nexans company Catalogue 2009

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Overhaul Special Tools Required

Connection kits for joining all types of DEVI self-limiting heating cables to cold tails

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

Installation Instructions

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

power cable accessories

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

Maintenance Information

3/ ABB cable accessories for PILC kv General accessories and Tools

Application Techniques for Reflective Pressure-Sensitive Films

PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors

Installation Guide The RSi brief overview:

MX Cable Connector Kit Manual Manual for Trimming the Cable and Connecting the Connector to an MX8031 Extension Cable

Transcription:

IS94012-ENG - AFN 20-45 5 February 2013 - Revision 6 - Supersedes edition of 28 January 2013 Page 1 of 7 CAUTION: Read instructions thoroughly and completely prior to beginning installation. Installation instructions for slip-on outdoor termination Contents : 3 x Termination housing Roll adhesive tape Wiper Optionally supplied : or 3 x Conductor 3 x Earthing AFN 20 U max. 24 kv For copper wire screened cable with : - extruded easy strip semi-conductive screen - bonded extruded semi-conductive screen Sealing silicone sleeves and / or Sealing silicone caps Emery cloth Installation instructions and / or 3 x Stress control, type MFC (Hi-K) Table 1 Termination size 1 35-70 2 3 4 3 x Earthing collar Silicone grease Conductor cross section (mm²) [for information only] 95-240 300-500 3 x Sealing Cable core diameter (mm) min. 18 22,5 31 Glove max. 23,5 33 41 400-630 34 46 a Nexans company This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. These instructions are not intended as a substitute for adequate training or experience in such safety practices. These instructions do not attempt to provide for every possible contingency. Failure to follow these instructions could result in damage to the product and serious or fatal injury. IMPORTANT : Cable and associated apparatus must be de-energised, locked out, and tagged prior to product installation.

Page 2 of 7 EQUIPMENT temporarily fixed 1 Temporarily install the on to the equipment and hold the cable next to it. Note : Foresee extra screen wire length if needed. L extra screen wire length if needed B A cable 2 Mark the bottom of the on the cable (reference point A). 3 Measure the depth of the bore (length L) and mark this distance above the reference point A on the cable (reference point B).

Page 3 of 7 CABLE PREPARATION Table 2 Termination size 1 2 3 4 ref point B copper screen wires counter helix copper tape abrade cable outer sheath Cable core diameter (mm) 18-20,5 20,5-23,5 X (mm) 165 160 22,5-26 165 26-29,5 160 29,5-33 155 31-36 165 36-41 160 34-40 165 40-46 160 X + L + 30 1 Remove the outer cable sheath for a distance X + L + 30 mm from the reference point B. L L = depth of the bore X = see table 2 2 Remove the counter helix copper tape(s). Make sure to remove all sharp edges. 3 Abrade the outer sheath over a distance of 50 mm. 4 20 mm below the outer cable sheath apply one layer of around outer cable sheath. Bend all the copper screen wires downwards, around the outer sheath, pressing them equally spaced into the. Using adhesive tape, secure the screen wires approx. 60 mm below the edge of the outer sheath. 5 Cut the cable to a point X + L + 30 mm from the outer sheath. remove sharp edges CUT HERE 20 50 copper screen wires securing tape X + L + 30 approx. 60

Page 4 of 7 6 Remove the semi-conductive screen up to 25-30 mm above the cut edge of the outer sheath. Check if the cable diameter is in accordance with the termination range. See table 2. 7 Bare the conductor for a distance L + 30 mm. IMPORTANT : To ensure the termination slips on easily, the edge of the core should be rounded and slightly roughened using the supplied emery cloth. For cables with extruded easy strip semi-conductive screen (see detail) : - Apply one layer of field control, type MFC (Hi-K), on the core, flush with the extruded semiconductive screen. - Squeeze it tightly in place using the coated side of the paper. X conductor bevelled and rounded core extruded semiconductive screen remove all sharp edges For cables with extruded easy strip semi-conductive screen Detail 25-30 25-30 L 30 core field control, type MFC (Hi-K) easy strip semiconductive screen

Page 5 of 7 INSTALLATION OF THE TERMINATION HOUSING AND CABLE LUG Hexagonal deep indent bolted protective adhesive tape termination housing internal step 1 Remove burrs from the conductor and as a protection, wrap a few turns of adhesive tape around the conductor end. 2 Remove any traces of conductive residue from the core. 3 Lubricate core and the inner surface of the termination (use only the silicone lubricant supplied). 4 Push the termination on the cable, until the internal step in the bottom part of the termination butts against the cable outer sheath. Remove protective tape from the conductor. 5 - Crimp contacts : crimp according specification. - Bolted contacts : tighten the screws, refer to the installation instruction included with the contact. 6 Remove any burrs after crimping/tightening and wipe off excess inhibitor. 7 Using, fill the gap between the top of the termination and. - For deep indent crimping, fill the holes of the indents with. - For bolted s, cover the screws with.

Page 6 of 7 SEALING OF THE TERMINATION 1 Select a combination of sleeve(s) and/or cap to waterseal the top of the termination. 2 - Crimp contacts : at least half of the contact barrel must be covered. - Bolted contacts : the whole contact barrel (screws) must be covered. silicone sleeve silicone cap Case : combination of two elements overlap ±20 mm - Use a first sleeve to build up the contact diameter, this sleeve must tight-fit on the contact barrel. - Cut the sleeve to the same length as the lug barrel. - Lubricate* inside surface of the sleeve. Slide the sleeve over the until it butts against the top part of the termination. - Lubricate* inside surface of the cap (or the second sleeve). - Slide the cap (or the second sleeve) over the first sleeve until it overlaps the top part of the termination (±20 mm). silicone sleeve Case : one element overlap ±20 mm - Lubricate* the inside surface of the sleeve or cap. - Slide the sleeve or cap over the until it overlaps both the top part of the termination (±20 mm), and the contact barrel. * USE ONLY THE SILICONE LUBRICANT SUPPLIED

Page 7 of 7 CABLE SCREEN EARTHING earthing collar cable clamp 1 Install the earthing collar 5 mm above termination base. Press three wires of the copper screen under the earthing collar (Hand tighten earthing collar, it has no water function but is only used to drain the surface currents). Pull these three and the other screen wires to one side of the termination and twist them together to form a pigtail and fit in the earthing. Crimp the. 2 Connect screen wires to the system earth. 3 copper screen wires earthing to the system earth 3 Clamp the cable as close as possible to the termination. 5 a Nexans company Nexans Network Solutions NV - div. EUROMOLD Zuid III - Industrielaan 12 B-9320 EREMBODEGEM-AALST BELGIUM Tel: +32 (0)53/85 02 11 Telefax: +32 (0)53/83 10 13 sales.euromold@nexans.com