(K),(M)430TB/G Up to 36 kv
|
|
- Lorena Mathews
- 5 years ago
- Views:
Transcription
1 IS90722-ENG - 430TB/G June Revision 8A - Supersedes edition of 25 November 2008 Page 1 of 10 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation instructions for separable tee connector - type C interface (K),(M)430TB/G Up to 36 kv Required components for the connector installation : 3 x Tee connector housing - 430BT 3 x Basic insulating plug+ cap - 300BIPR (up to 24 kv) + Silicone grease + wipers Only to be used on copper wire screened cable with extruded easy strip or bonded semi-conductive screen. or 3 x Cable reducer 430CA-W 3 x Basic insulating plug+ cap - 300BIPA (up to 36 kv) Installation instructions 3 x Clamping screw - 430TCS Water sealing mastic, type MWS (optional) or 3 x Conductor - TBC-X or TMBC-X Field control mastic, type MFC 1 x Installation rod (optional use for sizes 185 up to 300 mm²) Roll adhesive tape a Nexans company This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. These instructions are not intended as a substitute for adequate training or experience in such safety practices. These instructions do not attempt to provide for every possible contingency. Failure to follow these instructions could result in damage to the product and serious or fatal injury. IMPORTANT : Cable and associated apparatus must be de-energised, locked out, and tagged prior to product installation.
2 Page 2 of 10 EQUIPMENT equipment bushing (type C interface ) cut back point of outer sheath outer cable sheath M 250 necessary length of screen wire earth connection 1 Train the cable into the approximate finished position next to the equipment bushing. Be sure to allow enough extra length of concentric wires to connect to earth. 2 Mark centre line «M» of the bushing. 3 Remove the outer cable sheath to a point 250 mm from the centre line «M» of the bushing. For outdoor applications : one layer of water sealing mastic (type MWS) CUT HERE edge of the outer sheath tape marker outer cable sheath adhesive tape copper wires min Apply a tape marker around the outer sheath 40 mm from the edge. For indoor applications, bend the screen wires back over the outer sheath and proceed to step no. 5. For outdoor applications: - Wrap one layer of water sealing mastic (type MWS) around the outer sheath, flush with the end (25 mm minimum width). Completely encircle the cable. - Bend the screen wires back over the mastic and along the outer sheath, pressing them into the mastic. - Important: screen wires should not touch each other when pressed into the mastic to prevent water ingress. 5 Using adhesive tape, fix the screen wires at a distance of min 150 mm from the edge of the outer sheath. 6 Cut the cable to a point 205 mm from the outer sheath.
3 Page 3 of 10 CABLE PREPARATION For extruded easy strip semi-conductive screen easy strip semi-conductive screen 1 Check distance of 205 mm. 2 Remove the easy strip semi-conductive screen to a point 30 mm from the outer sheath. Cut squarely taking care not to cut the. outer sheath 30 For bonded extruded semi-conductive screen bonded semi-conductive screen Check distance of 205 mm. 2 Remove the bonded semi-conductive screen to a point 30 mm from the outer sheath. Use an appropriate pencilling tool. 3 Remove any traces of conductive residue from the.
4 Page 4 of 10 REMOVAL OF THE CORE INSULATION A. Compression type s (Type TBC-X) B. Mechanical type s (Type TMBC-X) A. Remove the from the for a distance «C» mm (C = depth of bore + 15 mm). field control mastic strip, type MFC 1 B. Remove the from the for a distance «C» mm (C = depth of bore + 5 mm). protective adhesive tape 2 Slightly bevel the edge of the. 3 Thoroughly clean. Always wipe towards the screen wires. 4 As a protection, wrap a few turns of adhesive tape around the end. 5 Remove field control mastic strip, type MFC, from coated paper. 6 Slightly stretch one end of the strip, making sure not to break it. 7 Apply the mastic on the cutback edge of the semi-conductive screen, covering approximately 5 mm of the extruded semi-conductive screen and 5 mm of the. 8 Push the mastic in place while stretching it progressively until both ends overlap and tear-off the excess mastic. 9 Using the coated side of the paper, squeeze the mastic tightly in place on the step of the semi-conductive screen. INSTALLATION OF THE CABLE REDUCER C 10 For sizes 35 up to 150 mm² bevel C protective adhesive tape 1 Lubricate* the indicated area :, mastic, semi-conductive screen and inner surface of the reducer. 2 Slide the reducer down the cable. 3 Remove protective adhesive tape from the.
5 Page 5 of 10 For sizes 185 mm² up to 300 mm² installation rod 1 Slide the installation rod on to the until it butts against the. installation rod protective adhesive tape 2 Thoroughly clean installation rod and. Always wipe towards the screen wires. 3 Lubricate* the indicated area : installation rod,, mastic, semi-conductive screen and inner surface of the reducer. 4 Slide the reducer on to the installation rod. 5 Slide the reducer down the cable. Take care to slide the reducer without hesitation and in one smooth move. 6 Remove installation rod and protective adhesive tape from the. * USE ONLY THE SILICONE LUBRICANT SUPPLIED
6 Page 6 of 10 CRIMPING/TIGHTENING OF THE CONTACT A Compression type s (Type TBC-X) Please refer to the crimp chart supplied with the. equipment bushing 1 For aluminium s : before installing the, wire brush the. 2 Fit the on to the. 3 Position the crimp taking care that the hole aligns with the bushing hole. 4 Prior to crimping distance «Z» must be between 150 and 160 mm. 5 Crimp the. Please refer to the crimp chart for crimp sequence. 6 After crimping distance «Z» must be between 155 and 165 mm. If necessary, adjust the position of the until distance «Z» is within the tolerance range. 7 Remove any burrs left after crimping and wipe-off excess inhibitor. Z deep indent crimping palm DIN crimping
7 B Mechanical type s (Type TMBC-X) Page 7 of 10 Before tightening Z = & é holding tool palm 1 For aluminium s : before installing the, wire brush the. equipment bushing 2 Insert, if necessary, the centre ring into the barrel according to table 1. 3 Position the so that the hole aligns with the bushing hole. 4 Before tightening, distance «Z» must be between 155 and 165 mm. 5 Tighten the screws slowly and alternately, with the tool according to table 2, until the heads shear off. It is recommended to use the holding tool for ease of installation. Tighten first screw & then é. 6 When the screws do not shear off flush with the barrel surface, apply one layer of vinyl tape around the barrel in order to protect the inside surface of the connector body during installation. TMBC LV TMBC LV TMBC LV TMBC grey grey red mm² mm² Small bore Table 1 yellow Large bore 50 mm² mm² mm² Small bore Small bore mm² mm² blue Table 1 yellow Large bore Table 1 Table 1 No centre ring necessary 95 mm² mm² mm² brown Large bore No centre ring necessary No centre ring necessary Al : mm² Cu : mm² 17mm Al : mm² Cu : mm² 17mm Al : mm² Cu : mm² 19mm Al : mm² Cu : mm² 22mm Table 2 Al : mm² Cu : mm² SW 6 Table 2 SW 6 Table 2 SW 6 Table 2 6mm L > 15 mm Al : 240 mm² Cu : mm² SW 6 Al : 150 mm² Cu : 120 mm² 6mm 6mm L > 19 mm Al : 300 mm² Cu : 300 mm² 6mm L > 15 mm L > 19 mm After tightening Z = After tightening, distance «Z» must be between 155 and 165 mm. If necessary, adjust the position of the until distance «Z» is within the tolerance range. 8 Wipe-off excess inhibitor and remove any burrs resulting from tightening.
8 Page 8 of 10 CONNECTOR INSTALLATION ON CABLE clean connector housing CONNECTOR INSTALLATION ON BUSHING equipment bushing locking ridge connector housing 1 Clean, and. 2 Lightly * the inside surface of the connector housing and outer surface of the. 3 Check if the angle of the tee connector housing is correct relative to the palm of the crimp and the longer interface is pointed towards the bushing. Whilst preventing the from further movement down the cable, gently slide the housing on the cable until it cannot advance any further. 4 For mechanical type s : make sure the spade locks into the connector's housing. Check correct installation by trying to pull back the connector. It is correctly installed when it stays in its locked position. 5 The must stay in place during installation. * USE ONLY THE SILICONE LUBRICANT SUPPLIED 1 Clean and lightly * both connector and bushing interface. 2 Push connector on to the bushing.
9 Page 9 of 10 22mm clamping screw 22 mm socket L 90 mm extension 1/2" - 12,7 mm torque wrench 1/2" - 12,7 mm torque wrench 3 Insert clamping screw into the threaded hole of the bushing. 4 Use torque wrench with a socket wrench 22 and tighten exerting 50 Nm (5 kgm or 36,9 foot-pounds) of torque. In order to achieve the correct applied torque ensure that there is no lubricant on the threaded parts. basic insulating plug 22mm 22 mm socket 5 Clean and * the insulating plug for the opposite side of the connector. 6 Insert the plug in the connector and tighten assembly : use torque wrench with socket of 22 and tighten exerting 30 Nm (3 kgm or 22,1 foot-pounds) of torque. In order to achieve the correct applied torque ensure that there is no lubricant on the threaded parts. * USE ONLY THE SILICONE LUBRICANT SUPPLIED
10 Page 10 of 10 INSTALLATION OF THE CAP CONNECTOR EARTHING AND CABLE CLAMPING protective cap A. Installation on insulating plug BIPR without voltage detection point (for applications up to 24 kv only) : Clean inside of the cap and outside surface of connector and insulating plug. Push cap over the connector and on to the insulating plug. Slightly pull up the edge of the cap to exhaust the air during assembly. Position the cap with the pulling tab pointing downwards. protective cap B. Installation on insulating plug BIPA with voltage detection point (for applications up to 36 kv) : Clean inside of the cap and outside surface of connector and insulating plug. Push cap over the connector and on to the insulating plug. Slightly pull up the edge of the cap to exhaust the air during assembly and while pressing the centre of the cap on to the locking point until it snaps in place. Position the cap with the pulling tab pointing downwards. system earth screen wires cable clamp 1 Bend back the screen wires along the outer sheath to form a pig tail. 2 Connect the earthing lead and screen wires to the system earth. NOTE : A connector/bushing mated combination should not be allowed to carry the full weight of the cable. Therefore clamp the cable as close as possible to the connector. IMPORTANT NOTES : - Never disconnect the connector from energised equipment nor energise a disconnected connector without previously installing on its appropriate corresponding mating part. - Do not allow hydrocarbon oils or solvents to contaminate the E.P.D.M. rubber. In the event of contamination, wipe the surface clean with a dry cloth. a Nexans company locking point earthing lead Nexans Network Solutions NV - div. EUROMOLD Zuid III - Industrielaan 12 B-9320 EREMBODEGEM-AALST BELGIUM Tel: +32 (0)53/ Telefax: +32 (0)53/ sales.euromold@nexans.com
(K),(M),(P)489TB/G Up to 42 kv
IS91374-ENG - 489TB/G-45/S 22 October 2012 - Revision 1 - Supersedes edition of 4 May 2012 Page 1 of 9 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation
More informationIS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)
IS94012-ENG - AFN 20-45 5 February 2013 - Revision 6 - Supersedes edition of 28 January 2013 Page 1 of 7 CAUTION: Read instructions thoroughly and completely prior to beginning installation. Installation
More informationIS90750-ENG - 430TB/G-45/LCA 14 January 201 O - Revision 7 - Supersedes edition of 25 June 2009 Page 1 of 9
IS90750-ENG - 430TB/G-45/LCA 14 January 201 O - Revision 7 - Supersedes edition of 25 June 2009 Page 1 of 9 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation
More informationINTERFACE F MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017
INTERFACE F MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017 NEXANS NETWORK SOLUTIONS DIV. EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer,
More informationINTERFACE E - 5/8" MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017
INTERFACE E - 5/8" MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017 NEXANS NETWORK SOLUTIONS DIV. EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer,
More informationa Nexans company Catalogue 2007
a Nexans company Catalogue 2007 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationa Nexans company Catalogue 2011
a Nexans company Catalogue 2011 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationELB ELB
ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical
More informationInstallation Instructions K656CY, K656CH and K656I Deadbreak Receptacles
Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles IS---K656CY,CH,I Page 1 of 6 CONTENTS: Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars,
More informationa Nexans company Medium voltage symmetrical separable connectors - Interface C -
a Nexans company Medium voltage symmetrical separable connectors - Interface C - Catalogue 2011 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised
More informationNexans Network Solutions Div. Euromold
a Nexans company Catalogue 2011 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationa Nexans company Catalogue 2009
a Nexans company Catalogue 2009 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable
More informationTHORNE & DERRICK UK TEL FAX TEL FAX
a Nexans company Catalogue 2006 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationINTERFACE C MEDIUM VOLTAGE SYMMETRICAL SEPARABLE CONNECTORS CATALOGUE 2017
INTERFACE C MEDIUM VOLTAGE SYMMETRICAL SEPARABLE CONNECTORS CATALOGUE 2017 NEXANS NETWORK SOLUTIONS DIV. EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer
More informationNexans Network Solutions Div. Euromold
Catalogue 2012 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories
More informationCold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions
Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Class I Indoor Termination Voltage Designation: 12/20(24) kv Kit Contents: 1 HeatShrinkBreakoutBootAssembly 3 HeatShrinkBindingSleeves
More informationa Nexans company Catalogue 2015
a Nexans company Catalogue 2015 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper
More information3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination
3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working around energized electrical systems may
More informationa Nexans company Catalogue 2007
a Nexans company Catalogue 2007 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationa Nexans company Catalogue 2009
a Nexans company Catalogue 2009 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More informationa Nexans company Catalogue 2012
a Nexans company Catalogue 2012 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationa Nexans company Catalogue 2006
a Nexans company Catalogue 2006 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More information3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series
3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series For 3-Conductor Copper Tape Shield Cables without Ground Wires Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working
More informationRaychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions
Raychem CSJA 1521 Cold-Shrinkable Splice for single core polymeric insulated (XLPE-EPR) cables up to 15kV for tape, wire, Unishield, LC shield, JCN, and flat strap neutral cable UniShield is a trademark
More informationNexans Network Solutions Div. Euromold
a Nexans company Catalogue 2011 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationELB ES. Product Installation Instructions
ELB-25-210-ES 200A 25kV Class Loadbreak Elbow with Integral Jacket Seal for Copper Tape (CT) and Jacketed Concentric Neutral (JCN) cables Product Installation Instructions Safety Instructions When installing
More informationPower cables accessories for use in potentially explosive atmospheres
Power cables accessories for use in potentially explosive atmospheres Catalogue 2013 NEXANS POWER ACCESSORIES EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor
More information3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits
3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits With High-K Stress Relief For 3-Conductor Type G (Ground Wire), Copper Tape Shield, Armored Cables 7600-S-3G Series Instructions IEEE Std.
More informationCompany Directive STANDARD TECHNIQUE: CA3V/3. Relating to Procedures for Making 33kV CableTerminations
Serving the Midlands, South West and Wales Gwasanaethu Canolbarth a De Orllewin Lloegr a Chymru Company Directive STANDARD TECHNIQUE: CA3V/3 Relating to Procedures for Making 33kV CableTerminations Policy
More information3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit
3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit With High-K Stress Relief For 3-Conductor Copper Tape Shield Cables with or without Ground Wires 7600-T-3RJS Series Instructions
More informationTHORNE & DERRICK UK TEL FAX TEL FAX
WWW.CABLEJOINTS.CO.UK THORNE & DERRICK UK TEL 0044 191 490 1547 FAX 0044 477 5371 TEL 0044 117 977 4647 FAX 0044 977 5582 WWW.THORNEANDDERRICK.CO.UK a Nexans company Catalogue 2006 EUROMOLD COMPANY PRESENTATION
More informationCOOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN
Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF
More informationInstallation Instructions
517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Deadbreak Elbow Applicable Current Ratings 600A (Aluminum) 900A (Copper) Applicable Catalog Prefix 35kV
More informationCOOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions
Deadbreak Apparatus Connectors MN650005EN Effective February 2015 Supersedes S600-10-2 July 2014 COOPER POWER SERIES 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions
More informationa Nexans company Catalogue 2008
a Nexans company Catalogue 008 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage
More informationInstallation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV
Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV * PLEASE READ INSTRUCTIONS THOROUGHLY BEFORE PROCEEDING * INDOOR OUTDOOR Download free QR code scanning software
More informationNexans Network Solutions Div. Euromold
Catalogue 2012 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories
More informationQT-III Cold Shrink Silicone Rubber
QT-III Cold Shrink Silicone Rubber 7600-T-3RJS Series 3/C Cabinet Termination Instructions Kit Contents: 3ÑSilicone Rubber Phase Re-jacketing Sleeve Assembly 3ÑCold Shrink Silicone Rubber Termination Assembly
More informationINSTALLATION INSTRUCTION
HEAT SHRINKABLE TERMINATION FOR 11kV, 3 CORE, XLPE/PVC COPPER WIRE SCREEN UNARMOURED CABLE. INDOOR & OUTDOOR. Cable Dielectric INDOOR INSTRUCTION No PJT001-14A XLPE/EPR OUTDOOR Tested to IEC60502-4 (TDT
More information3M Cold Shrink Splice Kit QS-III 5536A
3M Cold Shrink Splice Kit QS-III 5536A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric
More informationa Nexans company Catalogue 2008
a Nexans company Catalogue 2008 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium
More information3M Cold Shrink QT-III Silicone Rubber Termination
3M Cold Shrink QT-III Silicone Rubber Termination For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable 7673-S-8(S)-TOW/WOT Instructions IEEE Std. No. 48 Class 1 Termination 69 kv Class, 350
More information3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN
3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN For Jacketed Concentric Neutral (JCN) Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350 kv BIL IEC 60840 72,5
More informationCOOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN
Deadbreak Apparatus Connectors MN650004EN Effective February 2015 Supersedes S600-15-3 July 2014 COOPER POWER SERIES 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions DISCLAIMER
More informationCOOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN
Deadbreak Apparatus Connectors MN650003EN Effective February 2015 Supersedes S600-55-1 July 2014 COOPER POWER SERIES 600 A 35 kv class BT-TAP connector system installation instructions DISCLAIMER OF WARRANTIES
More informationI nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv
I nstallation I nstruction Heatshrink Term ination For 3 Core Polym eric Cables 7.2 kv to 3 6 kv I NDOOR OUTDOOR ISSUE DATE: 05.01.11 General Fitting I nstructions * I t is highly recom m ended that a
More informationINTERFACE A MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 2017
INTERFACE A MEDIUM VOLTAGE SEPARABLE CONNECTORS AND BUSHINGS CATALOGUE 07 NEXANS NETWORK SOLUTIONS DIV. EUROMOLD COMPANY PRESENTATION EUROMOLD Nexans is the leading European specialised designer, manufacturer
More information3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)
3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) for Tape Over Wire and Wire Over Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325
More informationa Nexans company Catalogue 2015
a Nexans company Catalogue 05 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
More informationa Nexans company Catalogue 2009
a Nexans company Catalogue 009 EUROMOLD COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage
More informationInstallation Instruction EPP /92
E L E C T R I C A L P R O D U C T S. D I V I S I O N Installation Instruction EPP 0275 8/92 Terminations for Screened Single Core Plastic and Rubber Insulated Cables 7.2 kv to 36 kv without Armour Before
More information3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit
3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable 7685-S-8 Instructions IEEE Std. No. 48 Class 1 Termination 35
More information3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT
3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350
More informationCold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN
3 Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class 350 kv BIL IEC 60840 72,5 kv Kit Contents: 1 Silicone Rubber Lug Seal Insulator
More information3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit
3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7622-T-110, 7624-T-110, 7625-T-110, 7626-T-110 Instructions
More information3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC
3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC For Tape Shield or Longitudinally Corrugated (LC) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350
More informationCold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)
Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 5/8.7 kv Class 95 kv BIL Kit Contents: 3 Hi K, Tracking Resistant,
More information3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4
3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable Instructions
More information3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)
3M Cold Shrink Skirted Termination Kit QT-III 7672-S-8-TS (RW) for Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325 kv BIL CAUTION Working around energized systems
More informationHigh Voltage Accessories up to 72.5 kv
High Voltage Accessories up to 72.5 kv Technical instructions and application information The data given were determined diligently, but do not release our customers of the duty to carry out tests themselves
More informationINSTALLATION INSTRUCTION PEM1093ENG ENGLISH
INSTALLATION INSTRUCTION PEM1093ENG 2017-04 ENGLISH HEAT SHRINK TERMINATIONS FOR SINGLE CORE CABLES INDOOR TERMINATIONS HIT1.12, HIT1.24 AND HIT1.36 OUTDOOR TERMINATIONS HOT1.12, HOT1.24 AND HOT1.36 2/12
More information3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief
3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7621-T-95, 7622-T-95, 7624-T-95, 7625-T-95 Instructions IEEE Std.
More informationMotor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)
Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Instructions Kit Contents 3 Lug Covers 3 Cold Shrink Terminations 12
More information3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits
3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Instructions IEEE Std. No. 48 Class 1 Termination 8 kv Class, 95 kv BIL:
More information3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief
3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 7642-S-2, 7642-S-2(L) For Jacketed Concentric Neutral (JCN) and Concentric Neutral (CN) Cable Instructions IEEE Std.
More informationINSTALLATION INSTRUCTION PEM1367ENG ENGLISH
INSTALLATION INSTRUCTION PEM1367ENG 2012-06 ENGLISH COLD SHRINK JOINT CJE11.42 FOR SINGLE CORE CABLES WITH Cu WIRE SHIELD Uo/U = 20.8/36 kv, Um = 42 kv 2/10 CJE11.42 PEM1367ENG 2012-06 GENERAL INFORMATION
More informationINSTALLATION INSTRUCTION PEM1121ENG ENGLISH
INSTALLATION INSTRUCTION PEM1121ENG 2016-06 ENGLISH SJK JOINT KIT FOR PLASTIC CABLE WITHOUT ARMOURING 1 kv SJKR JOINT KIT FOR PLASTIC CABLE WITH ARMOURING 1 kv 2/8 PEM1121ENG 2016-06 GENERAL INFORMAT ION
More informationCold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit
Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit Instructions for Shielded and Belted PILC Cable IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice UniShield Wire Shielded Longitudinally
More informationInstallation instruction PEM1150ENG
Installation instruction PEM1150ENG 2008-08 USHJ630 SCREENED SEPARABLE BACK CONNECTOR 630 A FOR 1 CORE PLASTIC CABLES 12-24 kv ENGLISH 2/8 USHJ630 PEM1150ENG 2008-08 GENERAL INFORMAT ION - Check that the
More information3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief
3M Cold Shrink QTlll Silicone Rubber Indoor Tubular Termination Kits With HighK Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7693T150, 7695T150, 7696T150 Instructions IEEE Std. No. 48
More informationInstallation Instructions
517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Series Cold Shrink R-800 Appli Ftener Type G Style Appli Housing Sizes O, P, & Q Appli Catalog Prefix
More informationInstructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination
Instructions Quick Term II Silicone Rubber Termination IEEE Std. No. 48 1990 Class 1 Termination 46 kv Class 250 kv BIL ÁÁ ÁÁ Kit Contents 1 High-K, 8 Skirted Silicone Rubber Termination 1 4 Skirt Silicone
More informationCold Shrink QS T Trifurcating Transition Splice Kit
Cold Shrink QS2012-13-3T Trifurcating Transition Splice Kit Instructions IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice Cable Size Range Requirements PILC 500 kcmil Conductor Size (240 mm 2
More informationDisassembly and Reassembly for CBB (Double Acting) Series Pneumatic Actuators
MECATORK S.A.S Release: May 2012 Disassembly and Reassembly for CBB (Double Acting) Series Pneumatic Actuators MECATORK S.A.S Table of Contents May 2012 Table of Contents Section 1: Introduction 1.1 General
More informationNexans Network Solutions Div. Euromold
Catalogue 0 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for
More informationCOOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN
Loadbreak Apparatus Connectors MN650014EN Effective January 2016 Supersedes S500-110-1 April 2015 COOPER POWER SERIES Fused loadbreak elbow connector installation instructions DISCLAIMER OF WARRANTIES
More informationInstallation Instruction EPP /02. Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour
R Installation Instruction EPP-0778-11/02 Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour Type: IXSU-F / OXSU-F Tyco Electronics Raychem GmbH Energy Division
More information3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit
3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief For Jacketed Concentric Neutral
More information3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits
3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits With High Ampacity Ground Connection and High-K Stress Relief For Tape Shield, Wire-Over-Tape Shield and Longitudinally Corrugated (LC) Shield
More informationQUICKTERM TERMINATION KIT
PYROTENAX QUICKTERM TERMINATION KIT INSTALLATION INSTRUCTIONS FOR TERMINATING SINGLE CONDUCTOR COPPER SHEATHED MINERAL INSULATED CABLE DESCRIPTION This termination kit is used to terminate #6 AWG and larger
More informationOverhaul Special Tools Required
1 of 31 Overhaul - Special Tools Required - Cylinder end seal remover attachment, 07NAD-SR3020A - Pilot collar, 07GAF-PH70100 - Valve seal ring sizing tool, 07NAG-SR3090A - Ball joint boot clip guide,
More informationHVS S 15kV Class
Product HVS-3-1580S 15kV Class Transition Splice for 3/C to 3/C Extruded Dielectric (Poly/EPR) Power Cables Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 PII-54864, Rev
More informationCold-shrinkable Silicone 12 kv - 24 kv - 36 kv
EUROMOD NV 0/00 www.think-media.be Accessories for medium voltage power cables Terminations Cold-shrinkable Silicone kv - kv - 6 kv Catalogue 0/00 TERMINATIONS TABE OF CONTENTS COD-SHRINKABE SIICONE TERMINATIONS
More informationOperating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc.
Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc. DIN EN 60529 General characteristics and technical data Series
More informationCaledonian Medium Voltage Cables Three Core Cables to VDE 0276-
Three Core Cables to VDE 0276 APPLICATIONS The three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6.6KV to 19/33KV and frequency 50Hz. They are
More informationPLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors
MARCH 2017 PLP Compression Dead-end & Jumper Terminal for ACSR & ACSS Conductors Be sure to read and completely understand this procedure before applying product. Be sure to select the proper PREFORMED
More informationEffective November 2016 Supersedes February 2012 (S )
Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling
More informationCOOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN
Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationQuick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet
Quick Term II Cold Shrink Silicone Rubber Termination Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 15 kv Class 110 kv BIL Kit Contents: 1 Hi K Silicone Rubber Termination 2 Scotch 70 Silicone
More informationProduct Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526
Product HVS Series Cable Splice Shim Kit for 1/C Extruded Dielectric (Poly/EPR) Power Cables: Metallic Tape, Wire Shield, UniShield, LC Shield, Lead Sheath or Concentric Neutral URD Cables UniShield is
More informationASSEMBLY, INSTALLATION, AND REMOVAL OF CONTACTS AND MODULES
ASSEMBLY, INSTALLATION, AND REMOVAL OF CONTACTS AND MODULES FOR THERMOCOUPLE CONTACTS AND MODULES Table of Contents SECTION 1 RECEIVER CONTACT ASSEMBLY INSTRUCTIONS SECTION 2 ITA CONTACT ASSEMBLY INSTRUCTIONS
More informationApplication Specification Pin&3Pin Miniature waterproof connector 28July2016 REV: C
Application Specification 114-137093 2Pin&3Pin Miniature waterproof connector 28July2016 REV: C 1. INTRODUCTION This specification covers the requirements for application of 2Pin&3Pin Miniature waterproof
More informationInstructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)
Instructions Quick Term II Silicone Rubber Termination (with High-K Stress Relief) IEEE Std. No. 48 990 Class Termination 5 kv Class 50 kv BIL Kit Contents Hi K Silicone Rubber Termination Scotch 70 Silicone
More informationVITALink Taped Splice Pigtail Crimp
A Marmon Wire & Cable Berkshire Hathaway Company VITALink Taped Splice Pigtail Crimp 1 Hour Fire-Rated Splice VITALink MC Cables, UL FHIT 120 Installation Instructions Description The VITALink Taped Splice
More informationEMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions
EMK-XP ElectroMelt Power Connection and End Seal Kit Installation Instructions Description The ElectroMelt EMK-XP Power Connection and End Seal Kit is for use with ElectroMelt EM2-XR and EM3-XR heating
More informationGeneral characteristics and technical data Series MCS
MOD M MC MCS VP 100 S Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc. DIN EN 60529 General characteristics and
More informationShielded surge arresters
Shielded surge arresters Nexans, worldwide leader for the cable industry Total sales of billion euros in 2009 The most complete range of cables and cabling systems Plants in 39 countries 22,700 employees
More informationCS Fiber Optic Splice Case. Instruction
3 2179-CS Fiber Optic Splice Case Instruction 2179-CS Fiber Optic Splice Case Description 1.0 General 1.1 The 3M 2179-CS Fiber Optic Splice Cases are closures that can be used in buried, underground, aerial,
More information