Installation Instructions

Size: px
Start display at page:

Download "Installation Instructions"

Transcription

1 517 Lyons Ave, Irvington, NJ Phone: Fax: Installation Instructions Series Cold Shrink R-800 Appli Ftener Type G Style Appli Housing Sizes O, P, & Q Appli Catalog Prefix Use With the Following Types 15kV Cls 25kV Cls ed Concentric Neutral (JCN) Longitudinally Corrugated Neutral (LC) Tape Neutral 61G 71G 91G 62G 72G 92G RP-II-G [C] Sheet 1 of 16

2 Appli Catalog Prefix WARNING System must be de-energized during installation or future operation of this product or its components. Do not touch or move energized connectors or components by hand. Excess distortion of the sembled connector may result in its failure. Failure to follow these instructions will result in damage to the connector and serious or fatal injury. This product should only be installed and/or operated by trained personnel in accordance with normal and safe work procedures. Variations in equipment or configuration or work procedures may not be covered in these instructions. Plee contact Richards Manufacturing for any additional questions. WARNING WARNING Guidelines for Installation in Cold Temperatures (<32 degrees F): 22 The cold shrink product must be kept and stored in a clean, dry manner. These high voltage accessories have internal phe to ground insulating interfaces which must be intact. Keep product within a warmer climate controlled environment long possible PRIOR to installation. This may be the cab of an operating vehicle if no other facility resources are available. If product h been inadvertently exposed and stored in freezing (or below) temperatures for an extended or unknown period of time: Product must warmed (41F or greater) and inspected prior to installation. If installing product in temperatures below freezing, and conducting post installation electrical testing it may be necessary to warm the interface of the accessory. This can incree the contact pressure between the accessory and the substrate. The heat should be applied primarily around the semicon shield cutback area. This can be accomplished via a space heater or hot air gun. The accessory should be gently heated so that the product becomes warm to the touch. Heat should not be concentrated but should be applied circumferentially around the product. If using a hot air gun, care must be taken not to apply the heat in a concentrated manner that could damage the or accessory. Check that proper ventilation is available if working in a confined space structure KIT CONTENTS KIT CONTENTS T KIT CONTENTS R Standard kits may include the following. Custom kits may vary. Check package contents to be sure they are complete, undamaged,and properly sized for the application. P N G Style Cold Shrink R-800 () (15kV or 25kV) M Insulating Cap 21LBICG (for 15kV Cls) 22LBICG (for 25kV Cls) L OR K J Shear Bolt Lug P6ALR-X-15/16 /16 Threaded Hole Lug P6AL-X-15/16 P7ALCU-X-15/16 P9CU-X-15/16 15 (1) Prep Pack containing: H G F Silicone Lubricant P6SL1 (1) Piece Sealing (1) Piece Stress Control (1) Piece Latex Gloves (1) Pair E Stud P625HIP-STUD P925HIP-STUD D UNLESS OTHERWISE SPECIFIED: DIMENSIONS ARE IN MILLIMETERS SURFACE FINISH: TOLERANCES: LINEAR: ANGULAR: C RP-II-G [C] DEBURR AND BREAK SHARP EDGES FINISH: SIGNATURE NAME N/A DATE CHK'D APPV'D MFG Q.A Sheet 2 of 16 MATERIAL: As Noted B DO NOT SCALE DRAWING TITLE: DRAWN WEIGHT: REVISION 15 kv Cold Shrink R800; F Style; (EXPANDED) TestA0 6FCN-01A Point - Size P DWG NO. SCALE:1:1 2 SHEET 1 OF 1 1

3 LCN/ LCN/ Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions TIP: 517 Lyons Lyons Ave. Ave. 517 Irvington, NJ NJ Irvington, 517 Lyons Ave. Phone (973) Phone (973) TIP: TIP: Irvington, NJ TIP: FaxTIP: (973) Fax (973) Phone (973) TIP: 0-Positioning FaxTIP: (973) the TIP: Use To-Scale Cutback Template aid to prepare. 0-Positioning 0-Positioning 0-Positioning 0-Positioning TIP: Use Use to-scale cutback template on lt page aid aid to to prepare prepare.. TIP: to-scale cutback template on lt page Certain items used, such PVC tape, may not be included. 1-Exposing 0-Positioning the the 1-Exposing 0-Positioning the the TIP: Use to-scale cutback template on lt page aid to prepare. Certain items used such mtic, PVC tape, shrink tube, etc. may not be includ Certain items used such mtic, PVC tape, shrink tube, etc. may not be includ ing the Metallic Tape /L Strap/Wire s ing Metallic /LC s the Positioning & Exposing Metallic Certain items used such mtic, PVC tape, shrink tube, etc.tape may not be includ 1 A. A. A. B. B. C. C. B. C. Straighten and and train train end. end. should should be be free free to to move move Straighten approximately 2"train either direction. approximately inin either direction. Straighten and2" end. should be free to move Cut to to dimensions dimensions Cut approximately 2" in either direction. Clean jacket approximately 24" from from end end of of.. Clean approximately Cut tojacket dimensions 24" Clean jacket approximately 24" from end of. 1-Exposing ing 1-Exposing 1-Exposing 1-Exposing 1-Exposing 1-Exposing ing 1-Exposing ing ing ing ing ing Metallic Tape /LC Sh Bushingor or Bushing Mating Part Mating Part Bushing or Metallic Metallic Tape/LC /LC Tape Mating Part Metallic MetallicTape Tape /LC /LC Metallic Tape /LC Metallic Tape /LC Metallic Metallic Tape/LC Tape/LC or Strap/Wire s Strap/Wire Strap/Wire s s s s Strap/Wire s s Strap/Wire Strap/Wire D. Strap/Wire Remove jacket to to dimensions dimensions D. Remove jacket E. Abrade area E. Abrade area D. Remove jacket to dimensions Strap/Wire s e s E. Abrade area REF. 111/1/22 REF. 1 1 /2 REF. 2 AbradedArea Area Abraded Abraded Area or Strap/Wire s 113/3/44 1 3/4 2-Applying Tape/LC 2-Applying D. Metallic Remove jacket jacket to dimensions dimensions D. Remove to E. Abrade Abrade area jacket E. D. Removearea to dimensions Metallic Tape /L Metallic Tape /LC E. Abrade area REF. 111/1/22 REF. 1 1 /2 REF /4 12 AbradedArea Area Abraded 2-Applying Abraded Area Metallic Tape /LC Shie Applying 2-Applying 2-Applying 2-Applying 2-Applying 2-Applying Metallic MetallicTape Tape/LC /LC 2-Applying Metallic Tape/LC Metallic MetallicTape Tape/LC /LC Metallic Tape /LC Strap/Wire Strap/Wire s s Strap/Wire s s Strap/Wire s s A. Apply one piece of jacket mtic at position shown by stretching and Go to Metallic Step 3 Tape /LC wrapping with light tension fully around outer jacket. mtic will be applied in Step /4 3- Exposing 3- Exposing Strap/Wire re s s 3 Exposing Strap/Wire A. B. Metallic Tape /LC Metallic Tape /LC 3- Exposing Metallic Tape/LC Fold back strap/wire shields and press firmly into jacket mtic. A. Wrap 2 layers 3- Exposing Exposing of PVC tape at dimension shown to secure metallic shield Exposing Exposing Secure strap/wire shields 3 back from jacket mtic with binding wire 3- Exposing B. Remove metallic shield up to PVC tape 3- Exposing or zip tie Strap/Wire s Binding Wire or Zip Tie Strap/Wire Strap/Wire s s s s ee Strap/Wire s e s mtic under strap/wire shield RP-II-G [C] Metallic Tape /LC 10 Metallic MetallicTape Tape/LC /LC Metallic MetallicTape Tape/LC /LC Metallic Tape /LC Metallic Tape /LC PVC Tape Metallic Sheet 3 of 16

4 4 Strap/Wire A. Remove semi-conductive shield to dimension Exposing Insulation Metallic Tape/LC A. Remove semi-conductive shield to dimension WARNING: Do not nick or cut the insulation. WARNING: Do not nick or cut the insulation. 9 3 / /4 Insulation Metallic Insulation 5 A. Remove insulation. Refer to instructions provided with lug for insulation cutback dimension. Cutback dimension should not exceed 4 3 /8". Exposing Conductor Insulation Cutback WARNING: Do not nick or cut the conductor strands. Insulation Conductor Confirm all dimensions with To-Scale Cutback Template before proceeding. 6 Installing Lug WARNING: Lug MUST have a 15 /16 hole. Confirm lug and hole dimension before installing lug. A. Clean conductor of any debris. aluminum conductor, wire brush and immediately insert lug onto conductor. Slide lug until the conductor is fully seated within the lug barrel. B. Rotate lug so that spade is parallel to the contact face of the bushing or mating part C. Shear Bolt Connectors: Install lug using separate instructions provided with lug. Crimp Connectors: Select correct tool and die using crimp chart supplied with lug. Crimp lug (min. number indicated in crimp chart) starting just below knurl line adjacent to pad Carefully wipe any excess inhibitor from lug and insulation. Lug Locate first crimp here Ensure surfaces are parallel before installing lug Bushing Knurl Line RP-II-G [C] Sheet 4 of 16

5 7 A. After installing lug, confirm distance from lug end to insulation cutback does not exceed dimension Checking Lug 7 1 /4 MAX WARNING: Do not exceed maximum dimension 8 Strap/Wire Applying Stress Control Metallic Tape/LC A. Clean insulation with approved cleaning wipes by wiping from lug to shielding. B. Apply supplied stress control mtic centered over edge of semiconductive shield cutback. Apply the mtic with light tension so it slightly stretches and completely wraps the. A. Clean insulation with approved cleaning wipes by wiping from lug to shielding. B. Remove PVC tape from Step 3. C. Apply supplied stress control mtic centered over edge of semiconductive shield cutback. Apply the mtic with light tension so it slightly stretches and completely wraps the. Applied Stress Control Stress Control Wipe Direction Applied Stress Control Stress Control Wipe Direction Cutback Insulation Cutback Insulation 9.1 Applying Gree A. Apply gree over exposed insulation and stress control mtic Use only supplied or approved silicone gree. Apply gree in this area RP-II-G [C] Sheet 5 of 16

6 9.2 A. Install onto until the lug is fully seated inside the housing. Installing WARNING: Confirm the lug h fully seated into housing Housing Lug fully seated within housing 15 /16" Threaded Lug RP-II-G [C] Sheet 6 of 16

7 9.3 Inserting Hex Tool A. Insert Hex tool (P620AT or equivalent 5 /16" hex tool) through loadbreak interface and engage ftener. B. Slide ftener into forward position through lug hole ( shown in detail view). WARNING: Ftener is factory-installed in a retracted position. The Ftener must be stroked into forward position. The female threaded end of Ftener will then extend into the 15 /16" Threaded hole of the Lug. WARNING: Confirm that ftener goes through lug hole shown below. Ftener Ftener in the retracted position Ftener stroked into forward position through Lug Hole Hex Tool Push Ftener through Lug Hole Lug RP-II-G [C] Sheet 7 of 16

8 9.4 A. Hand-tighten stud into the appropriate mating part or bushing. Mounting WARNING: A standard threaded stud is included in the kit. If the use of an ymmetrical threaded stud is approved, it MUST be installed with longer threaded side facing AWAY from equipment shown below. Correct Incorrect B. Clean and lubricate (using supplied or approved silicone gree) deadbreak interface of and interface of mating part or bushing. C. Place one hand on the power directly below and one hand on the body of the. Lifting together, push onto mating part, lining up the hole in the lug with the stud on the mating part. D. Insert Hex tool (P620AT or equivalent 5 /16" hex tool) into loadbreak interface and engage fter. Rotate tool 2-3 turns to start thread engagement. CHECK: Tug on power to confirm stud is through hole in lug. Only a small amount of movement should be possible. If the moves more than a small amount repeat steps above. E. Continue rotating hex tool. Torque ftener to 20ft-lb (P620AT Tool h built in 20ft-lb torque limiter.) CHECK: As a final check, tug on power. This should result in no movement at all. Clean and Lubricate (Internal Cavity) Mating Part or Bushing Clean and Lubricate Stud Torque Grp and lift from here RP-II-G [C] Sheet 8 of 16

9 10.1 Removing Core A. Grp removal ring. Push ring against core flange and twist so that cutting teeth breaks tape on both sides. Check that tape is broken. B. To remove core by hand: Proceed to Step D. To remove core using P6AT-CS2 Tool: Insert one half of tool between removal ring and core flange. Pry core slightly away from housing. C. Insert second half of core removal tool between removal ring and core flange. Press handles inwards to eject core. D. Completely remove core from rubber housing by hand. DO NOT twist core while removing. E. Separate core into two halves and clip any pltic rings that remain on. A Removal Ring B C D 10.2 Strap/ Wire Go to Step 11 Metallic Tape/LC A. Install jacket mtic on jacket aligned with jacket cutback. B. Wrap tinned copper braid around exposed metallic shield. C. Align edge of solder block with jacket cutback. D. Secure copper braid 3 back from end of jacket mtic with zip tie or binding wire. E. Unwind constant force spring over wrapped copper braid F. Tighten constant force spring by hand and wrap two layers of PVC tape (in direction of spring) to secure. G. Press solder block into jacket mtic. Preparing Metallic Binding Wire or Zip Tie Solder Block Tinned copper braid wrapped around exposed tape shield Constant ce Spring Apply PVC tape here RP-II-G [C] Sheet 9 of 16

10 11 Strap/Wire Applying Sealing Metallic Tape/LC A. Apply sealing mtic close possible to folded back jacket seal while maintainting complete overlap of previously applied jacket mtic. sealing mtic may or may not overlap stress control mtic. A. Apply sealing mtic close possible to folded back jacket seal while maintainting complete overlap of previously applied jacket mtic. sealing mtic may or may not overlap stress control mtic. Sealing Sealing completely covered with Sealing completely covered with Sealing 12 Strap/Wire Applying Seal Metallic Tape/LC A. Apply gree over area Only use gree supplied with kit or approved silicone gree. B. Hold both tabs and pull out to completely cover sealing mtics shown below. Ensure sealing mtic is not dislodged when unfolding seal. A. Apply gree over area shown below. Only use gree supplied with kit or approved silicone gree. B. Hold both tabs and pull out to completely cover sealing mtics shown below. Ensure sealing mtic is not dislodged when unfolding seal. Lubricate Pull Pull Tab Lubricate Pull Pull Tab Pull Pull Pull Tab Pull Tab Seal Installed Seal Installed RP-II-G [C] Sheet 10 of 16

11 13 Installing Mating Component A. Clean and lubricate (using supplied or approved silicone gree) loadbreak interface of and interface of insulating cap or mating part. B. Install mating component per manufacturer instructions. Loadbreak Cap shown reference. Clean and Lubricate (Internal Cavity) Clean and Lubricate RP-II-G [C] Sheet 11 of 16

12 14 Strap/Wire Connecting Drain Wires to A. Insert one end of a piece of wire (#14 AWG copper or larger) through one of the available grounding eyes and twist to make a small loop. Be sure not to damage grounding eye. B. Connect other end of wire to shield wires. C. Ground the shield according to appropriate/approved practice. To Ground Metallic Tape/LC Ground Eye Drain Wire A. Insert one end of a piece of wire (#14 AWG copper or larger) through one of the available grounding eyes and twist to make a small loop. Be sure not to damage grounding eye. B. Connect other end of wire to copper braid. C. Ground the shield according to appropriate/approved practice. To Ground Ground Eye Drain Wire Installation Complete RP-II-G [C] Sheet 12 of 16

13 RP-II-G [C] Sheet 13 of 16

14 Strap/Wire 9 3 /4 11 Cutback Template SCALE 1:1 Conductor Conductor intentionally not shown exposed. Multiple insulation cutback lengths exist depending on lug being installed. Locate appropriate dimension within instructions (dimension should not exceed 4 3 /8"). Insulation 11 3 /4 10 Metallic Tape/LC 8 3 /4

15 RP-II-G [C] Metallic Sheet 15 of 16

16 RP-II-G [C] Sheet 16 of 16

Installation Instructions

Installation Instructions 517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Deadbreak Elbow Applicable Current Ratings 600A (Aluminum) 900A (Copper) Applicable Catalog Prefix 35kV

More information

ELB ES. Product Installation Instructions

ELB ES. Product Installation Instructions ELB-25-210-ES 200A 25kV Class Loadbreak Elbow with Integral Jacket Seal for Copper Tape (CT) and Jacketed Concentric Neutral (JCN) cables Product Installation Instructions Safety Instructions When installing

More information

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions Raychem CSJA 1521 Cold-Shrinkable Splice for single core polymeric insulated (XLPE-EPR) cables up to 15kV for tape, wire, Unishield, LC shield, JCN, and flat strap neutral cable UniShield is a trademark

More information

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits 3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits With High-K Stress Relief For 3-Conductor Type G (Ground Wire), Copper Tape Shield, Armored Cables 7600-S-3G Series Instructions IEEE Std.

More information

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination 3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working around energized electrical systems may

More information

ELB ELB

ELB ELB ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical

More information

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 3M Cold Shrink QT-III Silicone Rubber Termination For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable 7673-S-8(S)-TOW/WOT Instructions IEEE Std. No. 48 Class 1 Termination 69 kv Class, 350

More information

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series 3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series For 3-Conductor Copper Tape Shield Cables without Ground Wires Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC For Tape Shield or Longitudinally Corrugated (LC) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350

More information

Cold Shrink QS T Trifurcating Transition Splice Kit

Cold Shrink QS T Trifurcating Transition Splice Kit Cold Shrink QS2012-13-3T Trifurcating Transition Splice Kit Instructions IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice Cable Size Range Requirements PILC 500 kcmil Conductor Size (240 mm 2

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350

More information

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles IS---K656CY,CH,I Page 1 of 6 CONTENTS: Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars,

More information

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Class I Indoor Termination Voltage Designation: 12/20(24) kv Kit Contents: 1 HeatShrinkBreakoutBootAssembly 3 HeatShrinkBindingSleeves

More information

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink Splice Kit QS-III 5536A 3M Cold Shrink Splice Kit QS-III 5536A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric

More information

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN 3 Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class 350 kv BIL IEC 60840 72,5 kv Kit Contents: 1 Silicone Rubber Lug Seal Insulator

More information

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit 3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit With High-K Stress Relief For 3-Conductor Copper Tape Shield Cables with or without Ground Wires 7600-T-3RJS Series Instructions

More information

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF

More information

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254. 3 Loadbreak Elbows 200 Amp 5-15 kv Industrial pg. 252 Loadbreak Elbows 200 Amp 25 kv Industrial pg. 254 Loadbreak Elbows 200 Amp Industrial pg. 255 Loadbreak Elbows Accessories 3 Loadbreak Elbows 3M 200

More information

QT-III Cold Shrink Silicone Rubber

QT-III Cold Shrink Silicone Rubber QT-III Cold Shrink Silicone Rubber 7600-T-3RJS Series 3/C Cabinet Termination Instructions Kit Contents: 3ÑSilicone Rubber Phase Re-jacketing Sleeve Assembly 3ÑCold Shrink Silicone Rubber Termination Assembly

More information

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) 3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) for Tape Over Wire and Wire Over Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN For Jacketed Concentric Neutral (JCN) Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350 kv BIL IEC 60840 72,5

More information

HVS S 15kV Class

HVS S 15kV Class Product HVS-3-1580S 15kV Class Transition Splice for 3/C to 3/C Extruded Dielectric (Poly/EPR) Power Cables Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 PII-54864, Rev

More information

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW) 3M Cold Shrink Skirted Termination Kit QT-III 7672-S-8-TS (RW) for Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325 kv BIL CAUTION Working around energized systems

More information

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN Deadbreak Apparatus Connectors MN650004EN Effective February 2015 Supersedes S600-15-3 July 2014 COOPER POWER SERIES 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions DISCLAIMER

More information

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN Deadbreak Apparatus Connectors MN650003EN Effective February 2015 Supersedes S600-55-1 July 2014 COOPER POWER SERIES 600 A 35 kv class BT-TAP connector system installation instructions DISCLAIMER OF WARRANTIES

More information

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits 3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Instructions IEEE Std. No. 48 Class 1 Termination 8 kv Class, 95 kv BIL:

More information

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Instructions Kit Contents 3 Lug Covers 3 Cold Shrink Terminations 12

More information

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions Deadbreak Apparatus Connectors MN650005EN Effective February 2015 Supersedes S600-10-2 July 2014 COOPER POWER SERIES 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

More information

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit Instructions for Shielded and Belted PILC Cable IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice UniShield Wire Shielded Longitudinally

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

(K),(M),(P)489TB/G Up to 42 kv

(K),(M),(P)489TB/G Up to 42 kv IS91374-ENG - 489TB/G-45/S 22 October 2012 - Revision 1 - Supersedes edition of 4 May 2012 Page 1 of 9 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 7642-S-2, 7642-S-2(L) For Jacketed Concentric Neutral (JCN) and Concentric Neutral (CN) Cable Instructions IEEE Std.

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable 7685-S-8 Instructions IEEE Std. No. 48 Class 1 Termination 35

More information

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K) IS94012-ENG - AFN 20-45 5 February 2013 - Revision 6 - Supersedes edition of 28 January 2013 Page 1 of 7 CAUTION: Read instructions thoroughly and completely prior to beginning installation. Installation

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal Loadbreak Connectors Catalog Data CA650062EN Supersedes June 2015 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal General Eaton s Cooper Power series

More information

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief 3M Cold Shrink QTlll Silicone Rubber Indoor Tubular Termination Kits With HighK Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7693T150, 7695T150, 7696T150 Instructions IEEE Std. No. 48

More information

Loadbreak Apparatus Connectors

Loadbreak Apparatus Connectors Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector

More information

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL Loadbreak Apparatus Connectors 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal Electrical Apparatus 500-10-7 GENERAL The Cooper Power Systems Loadbreak Elbow Connector is

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits With High Ampacity Ground Connection and High-K Stress Relief For Tape Shield, Wire-Over-Tape Shield and Longitudinally Corrugated (LC) Shield

More information

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination Instructions Quick Term II Silicone Rubber Termination IEEE Std. No. 48 1990 Class 1 Termination 46 kv Class 250 kv BIL ÁÁ ÁÁ Kit Contents 1 High-K, 8 Skirted Silicone Rubber Termination 1 4 Skirt Silicone

More information

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connector CA650099EN Supersedes 500-28-7C November 2011 COOPER POWER SERIES 200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General Eaton

More information

Assembly Instruction. EL OCHITO BLUE CONTACTS SuperSpeed USB TYPE I: PIN /SKT CABLE:

Assembly Instruction. EL OCHITO BLUE CONTACTS SuperSpeed USB TYPE I: PIN /SKT CABLE: AI85114-02 Assembly Instruction EL OCHITO BLUE CONTACTS SuperSpeed USB TYPE I: PIN 858-028-01/SKT 858-029-01 CABLE: 963-118 Revision History Rev Date Initiated By Approved 1 07/16/18 WLL GH 1.0 Tools Tools

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit 3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7622-T-110, 7624-T-110, 7625-T-110, 7626-T-110 Instructions

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief 3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7621-T-95, 7622-T-95, 7624-T-95, 7625-T-95 Instructions IEEE Std.

More information

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable Instructions

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief For Jacketed Concentric Neutral

More information

(K),(M)430TB/G Up to 36 kv

(K),(M)430TB/G Up to 36 kv IS90722-ENG - 430TB/G-45 25 June 2009 - Revision 8A - Supersedes edition of 25 November 2008 Page 1 of 10 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation

More information

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 5/8.7 kv Class 95 kv BIL Kit Contents: 3 Hi K, Tracking Resistant,

More information

High Voltage Joints and Terminations up to 72,5 kv 145 kv

High Voltage Joints and Terminations up to 72,5 kv 145 kv High Voltage Joints and Terminations up to 72,5 kv 145 kv 3M Cold Shrink Termination Kits QT-III and Joint Kits are designed to provide high reliability and save you time and money. They install quickly

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connectors Catalog Data CA650063EN Supersedes 500-10-7C November 2011 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General

More information

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP

Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN /SKT CABLE: S/FTP AI85112-02 Assembly Instruction EL OCHITO WHITE CONTACTS 1000BASE-T/10GBASE-T TYPE I: PIN 858-003-02/SKT 858-032-02 CABLE: 963-033-26 S/FTP Revision History Rev Date Initiated By Approved 1 07/05/18 WLL

More information

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH

INSTALLATION INSTRUCTION PEM1093ENG ENGLISH INSTALLATION INSTRUCTION PEM1093ENG 2017-04 ENGLISH HEAT SHRINK TERMINATIONS FOR SINGLE CORE CABLES INDOOR TERMINATIONS HIT1.12, HIT1.24 AND HIT1.36 OUTDOOR TERMINATIONS HOT1.12, HOT1.24 AND HOT1.36 2/12

More information

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connectors CA650101EN Supersedes 500-29-7C November 2011 COOPER POWER SERIES 200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

More information

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 Product HVS Series Cable Splice Shim Kit for 1/C Extruded Dielectric (Poly/EPR) Power Cables: Metallic Tape, Wire Shield, UniShield, LC Shield, Lead Sheath or Concentric Neutral URD Cables UniShield is

More information

600 A 35 kv class BT-TAP deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector Supersedes 600-55 July 2014 600 A 35 kv class BT-TAP deadbreak connector General Eaton's Cooper Power Systems 600 A 35 kv Class BT-TAP deadbreak connector is used to terminate high-voltage underground

More information

Installation Instructions LINK---C

Installation Instructions LINK---C IS---LINK---C Page 1 of 10 Installation Instructions LINK---C DEADBREAK CAM LINK OPERABLE CONNECTOR SYSTEM The is a 600 amp, connector designed to: 1.) provide a fully shielded, fully submersible hot stick

More information

Installation instruction PEM1150ENG

Installation instruction PEM1150ENG Installation instruction PEM1150ENG 2008-08 USHJ630 SCREENED SEPARABLE BACK CONNECTOR 630 A FOR 1 CORE PLASTIC CABLES 12-24 kv ENGLISH 2/8 USHJ630 PEM1150ENG 2008-08 GENERAL INFORMAT ION - Check that the

More information

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M Terminations Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M Cold Shrink QT-III Silicone Rubber Terminations 265 3M Cold Shrink Termination QT-III 69 kv/72,5 kv 270 3M Cold Shrink

More information

3M Cold Shrink Splice Kits, QS T Series

3M Cold Shrink Splice Kits, QS T Series 3M Cold Shrink Splice Kits, QS-2000-3T Series For 15 kv Trifurcating Transition Splice Kits Data Sheet October 2011 Description 3M Cold Shrink Splice Kits, QS-2000-3T Series for 15 kv Trifurcating Transition

More information

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet Quick Term II Cold Shrink Silicone Rubber Termination Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 15 kv Class 110 kv BIL Kit Contents: 1 Hi K Silicone Rubber Termination 2 Scotch 70 Silicone

More information

600 A 25 kv class BT-TAP deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector Deadbreak Connectors Catalog Data CA650001EN Supersedes January 2015 600 A 25 kv class BT-TAP deadbreak connector COOPER POWER SERIES General Eaton terminates high-voltage underground cable to transformers,

More information

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50 Deadbreak Apparatus Connectors 600 A 35 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-50 General The Cooper Power Systems 600 A, 35 kv Class Bol-T Deadbreak Connector is used to terminate

More information

Rejuvenation Instructions

Rejuvenation Instructions Rejuvenation Instructions #541 200A Live-Front Terminations UPR This NRI covers the following: How to prepare 200amp live-front terminations for injection. How to install the two approved live-front termination

More information

Installation Instructions 15/25/35kV, 600/900 AMPERE

Installation Instructions 15/25/35kV, 600/900 AMPERE Installation Instructions 15/25/35kV, 600/900 AMPERE Two---, Three--- and Four---Point Deadbreak Junctions IS---600/900A J2,J3,J4 Page 1 of 7 CONTENTS: The contents always include: 1---Deadbreak Junction,

More information

WRSS Wraparound Repair Sleeve Installation Instructions

WRSS Wraparound Repair Sleeve Installation Instructions WRSS Wraparound Repair Sleeve Installation Instructions TECP-30-263. Issue 1. 4/2016 1.0 General Product Information This practice provides information regarding the description and use of Raychem s WRSS

More information

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN Loadbreak Apparatus Connectors MN650014EN Effective January 2016 Supersedes S500-110-1 April 2015 COOPER POWER SERIES Fused loadbreak elbow connector installation instructions DISCLAIMER OF WARRANTIES

More information

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate

More information

INSTALLATION PRODUCTION TESTS

INSTALLATION PRODUCTION TESTS Deadbreak Apparatus Connectors 600 A 15/25 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-10 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class Bol-T Deadbreak Connector is used to terminate

More information

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series 3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series Data Sheet 1. Product Description 3M Cold Shrink Termination Kit QT-III 7672-S-8 Series contains one silicone rubber termination

More information

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series 3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series Data Sheet March 2011 Description 3M Cold Shrink 1/C Transition Splice Kits QS-III, 5510A-1T-PILC Series (which includes 5513A-1T-PILC,

More information

4. SHIELDS. 4.1 Power Cable. 4.2 Electronic Cable Conductor Shield (Strand Shield) Outer Shield (Insulation Shield) 60

4. SHIELDS. 4.1 Power Cable. 4.2 Electronic Cable Conductor Shield (Strand Shield) Outer Shield (Insulation Shield) 60 4. SHIELDS 4.1 Power Cable 4.1.1 Conductor Shield (Strand Shield) 60 4.1.2 Outer Shield (Insulation Shield) 60 4.2 Electronic Cable 4.2.1 Foil Shield 62 4.2.2 Copper Braid Shield 63 4.2.3 Spiral (Serve)

More information

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH

INSTALLATION INSTRUCTION PEM1367ENG ENGLISH INSTALLATION INSTRUCTION PEM1367ENG 2012-06 ENGLISH COLD SHRINK JOINT CJE11.42 FOR SINGLE CORE CABLES WITH Cu WIRE SHIELD Uo/U = 20.8/36 kv, Um = 42 kv 2/10 CJE11.42 PEM1367ENG 2012-06 GENERAL INFORMATION

More information

MY F150 SuperCab 1. Tools Required. Page 1 of 12 9L3J-19A014-BA Copyright Ford 2013 FoMoCo

MY F150 SuperCab 1. Tools Required. Page 1 of 12 9L3J-19A014-BA Copyright Ford 2013 FoMoCo 2009-2014MY F150 SuperCab 1 Tools Required A B C D E F G 3X 6X 3X H I J 2X 3X 3X K L M N 3X Page 1 of 12 9L3J-19A014-BA Copyright Ford 2013 FoMoCo 2009-2014MY F150 SuperCab 2 Subwoofer Power Wire Routing

More information

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications. QS-III 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits Data Sheet Tape Shield Wire Shield UniShield Kit Contents: 1 Cold Shrink Silicone Rubber Splice Body 1 Cold Shrink Adapter Tube

More information

Application Specification Circular Plastic Connector (CPC) Series 45 System 05 AUG 14 Rev D

Application Specification Circular Plastic Connector (CPC) Series 45 System 05 AUG 14 Rev D Application Specification Circular Plastic Connector (CPC) 114-13137 Series 45 System 05 AUG 14 Rev D NOTE i All numerical values are in metric units [with U.S. customary units in brackets]. Dimensions

More information

Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc.

Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc. Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc. DIN EN 60529 General characteristics and technical data Series

More information

Splicing Procedures 4. 2 Insert the new wire between the parted strands. If more than one wire is being spliced, wrap them in opposite directions. Use

Splicing Procedures 4. 2 Insert the new wire between the parted strands. If more than one wire is being spliced, wrap them in opposite directions. Use Splicing Procedures 1 Splicing Procedures Refer to applicable wiring diagrams for circuit information. This procedure contains multiple splicing techniques. Review splicing procedures prior to performing

More information

3M Electrical Markets Division Loadbreaks Deadbreaks Junctions Surge Arresters Disconnectable Joints 3 3M is the exclusive distributor for Richards Medium Voltage cable accessories in Canada. www.richards-mfg.com

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION HEAT SHRINKABLE TERMINATION FOR 11kV, 3 CORE, XLPE/PVC COPPER WIRE SCREEN UNARMOURED CABLE. INDOOR & OUTDOOR. Cable Dielectric INDOOR INSTRUCTION No PJT001-14A XLPE/EPR OUTDOOR Tested to IEC60502-4 (TDT

More information

600 A 15 kv class T-OP II deadbreak connector

600 A 15 kv class T-OP II deadbreak connector Deadbreak Apparatus Connectors CA650017EN Supersedes 600-12 February 2010 COOPER POWER SERIES 600 A 15 kv class T-OP II deadbreak connector General Eaton terminates high-voltage underground cable to transformers,

More information

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.) Molded Rub ber Products 600 A 35 kv Class Separable Splices Electrical Ap pa ra tus 700-31 General Cooper Power Systems 600 A, 35 kv Class Deadbreak Separable Splices are used to splice two, three or four

More information

VITALink Taped Splice Pigtail Crimp

VITALink Taped Splice Pigtail Crimp A Marmon Wire & Cable Berkshire Hathaway Company VITALink Taped Splice Pigtail Crimp 1 Hour Fire-Rated Splice VITALink MC Cables, UL FHIT 120 Installation Instructions Description The VITALink Taped Splice

More information

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV

Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV Installation Instruction Heatshrink Termination For 3 Core Polymeric Cables 7.2kV to 36kV * PLEASE READ INSTRUCTIONS THOROUGHLY BEFORE PROCEEDING * INDOOR OUTDOOR Download free QR code scanning software

More information

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts Deadbreak Connectors Catalog Data CA650007EN Supersedes March 2015 COOPER POWER SERIES 600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts General Eaton connects and assembles

More information

MY F150 CrewCab 1. Tools Required E F G. Page 1 of 10 9L3J-19A014-AA Copyright Ford 2013 FoMoCo

MY F150 CrewCab 1. Tools Required E F G. Page 1 of 10 9L3J-19A014-AA Copyright Ford 2013 FoMoCo 2009-2014MY F150 CrewCab 1 Tools Required A B C D 3X E F G H 2X I 6X 3X Page 1 of 10 9L3J-19A014-AA Copyright Ford 2013 FoMoCo 2009-2014MY F150 CrewCab 2 Subwoofer Power Wire Routing All Vehicles WARNING:

More information

Porsche 911/996/997 Carrera Do-It-Yourself Convertible Top Hydraulic Cylinder Inspection, Removal and Shipping Instructions

Porsche 911/996/997 Carrera Do-It-Yourself Convertible Top Hydraulic Cylinder Inspection, Removal and Shipping Instructions Porsche 911/996/997 Carrera Do-It-Yourself Convertible Top Hydraulic Cylinder Inspection, Removal and Shipping Instructions Disclaimer: These instructions are intended as a guide. Cabriolet Hydraulics

More information

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A 3M Cold Shrink QS-III Inline Splice Kits 15 kv Data Sheet June 2014! CAUTION Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel

More information

600 A 35 kv class separable splices

600 A 35 kv class separable splices Splices Catalog Data CA650050EN Supersedes 700-31 March 2009 COOPER POWER SERIES General Eaton s Cooper Power series 600 A, 35 kv Class deadbreak separable splices are used to splice two, three or four

More information

25 kv class fused loadbreak elbow connector

25 kv class fused loadbreak elbow connector Loadbreak Connectors Catalog Data CA650070EN Supersedes 500-111 July 2012 COOPER POWER SERIES 25 kv class fused loadbreak elbow connector General Eaton combines a fully-shielded and insulated plug-in termination

More information

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief) Instructions Quick Term II Silicone Rubber Termination (with High-K Stress Relief) IEEE Std. No. 48 990 Class Termination 5 kv Class 50 kv BIL Kit Contents Hi K Silicone Rubber Termination Scotch 70 Silicone

More information

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS The original TOMMY GATE hydraulic lift Assembling the Auxiliary Battery Box 1. Remove the cover from the auxiliary battery box by removing the two nuts and

More information

Coaxial Snap-Lock Connectors

Coaxial Snap-Lock Connectors Coaxial Snap-Lock Connectors Application Specification 114-13010 11 APR 13 NOTE NOTE i All numerical values are in metric units [with U.S. customary units in brackets]. Dimensions are in millimeters [and

More information

General characteristics and technical data Series MCS

General characteristics and technical data Series MCS MOD M MC MCS VP 100 S Operating voltage up to 5 kvdc Operating current up to 4,5 A 2-6 high voltage contacts Quick and easy assembling Protection class IP68 acc. DIN EN 60529 General characteristics and

More information

Product Number

Product Number Sealing and Grounding Cold Shrink cable accessory sealing kits are designed to seal the end of JCN cable. Use these kits when installing elbows or other cable accessories that do not include a jacket seal.

More information

LCT Shielded Primary UD EPR LCT Shielded Primary UD EPR Cable

LCT Shielded Primary UD EPR LCT Shielded Primary UD EPR Cable ed Primary UD EPR ed Primary UD EPR Cable Aluminum or Copper Conductor. EPR Insulation. Copper Longitudinal Corrugated Tape (). Low Density Polyethylene Jacket. APPLICATIONS Predominantly used for primary

More information

INSTALLATION INSTRUCTION PEM1121ENG ENGLISH

INSTALLATION INSTRUCTION PEM1121ENG ENGLISH INSTALLATION INSTRUCTION PEM1121ENG 2016-06 ENGLISH SJK JOINT KIT FOR PLASTIC CABLE WITHOUT ARMOURING 1 kv SJKR JOINT KIT FOR PLASTIC CABLE WITH ARMOURING 1 kv 2/8 PEM1121ENG 2016-06 GENERAL INFORMAT ION

More information

650 Series Cargo Van Lift Mounting Instructions Ford Transit (Standard Roof) 2015-Present

650 Series Cargo Van Lift Mounting Instructions Ford Transit (Standard Roof) 2015-Present TOMMY GATE OWNER'S / OPERATOR'S MANUAL 650 Series 650 LB Capacity 650 Series Cargo Van Lift Mounting Instructions Ford Transit (Standard Roof) 2015-Present Installing the Base Plate 1. Examine the interior

More information

Application Specification Pin&3Pin Miniature waterproof connector 28July2016 REV: C

Application Specification Pin&3Pin Miniature waterproof connector 28July2016 REV: C Application Specification 114-137093 2Pin&3Pin Miniature waterproof connector 28July2016 REV: C 1. INTRODUCTION This specification covers the requirements for application of 2Pin&3Pin Miniature waterproof

More information

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents Temporary Connections CA325004EN Supersedes November 2016 Grounding equipment COOPER POWER SERIES Contents Description Page Grounding elbow products... 2 Grounding elbow and kit product ratings... 5 200

More information