Quick Term II. Cold Shrink Silicone Rubber Termination. Quick Term II. Instruction Sheet

Similar documents
Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

Cold Shrink QS T Trifurcating Transition Splice Kit

QT-III Cold Shrink Silicone Rubber

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

ELB ES. Product Installation Instructions

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

DISTRIBUTION CONNECTORS SECTION DF COMPRESSION TERMINALS. Aluminum Compression Lugs Aluminum Bi-Metal Pin Terminals Copper Compression Lugs

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

CP 600V Cable Protectors

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

ELB ELB

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

B T T T 2.11 MY29-11 (1) 4/0 AWG - MY29-11 (1) W30VT (2) U30RT (2) 300 kcmil 150 W30VT (2) YA30L-2TC W30RT (2) U28ART (2)

High Voltage Joints and Terminations up to 72,5 kv 145 kv

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Wind Energy Catalog Solutions for the Wind Industry

3M Cold Shrink Splice Kits, QS T Series

Lithium-Ion Battery-Powered Tools

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

Installation Instructions

BURNDY Compression. TWO HOLE HYLUG CODE CONDUCTOR STANDARD BARREL (Continued) Fig. 1 Fig. 2 Fig. 3. Conductor

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

Branch Splice QS-2001B

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

4 AWG to 2000 kcmil at 15 kv, 2 AWG to 1750 kcmil at 25 kv and 1 AWG to 1500 kcmil at 34.5 kv. Stress Control

Connector System Guide Compression Connectors Grounding Connectors Tools for Industrial Electrical Applications

Type Termination Cable Size Copper Aluminum 2 CP2C1-1/0 CP1/0C1-2/0 CP2/0C1-4/0 CP4/0C1 CP4/0A1. Cable 250kcmil CP250C3 CP250A3

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

3M Mechanical Shearbolt Connectors, QCI Series

Installation Instructions

A. General: Deliver, store and handle wire and cable in accordance with the manufacturer's instructions and as specified in Division 1.

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

(K),(M)430TB/G Up to 36 kv

CTN U-TYPE DIE COLOR INDEX QTY 7/374 8/346 11/375 12/ /298 18/324 19/470 20/299 22/472 24/473 CTN U-TYPE DIE COLOR INDEX QTY

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

Heavy Duty Copper Battery Terminals

HVS S 15kV Class

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

3M Cold Shrink QT-III Silicone Rubber Skirted and Inverted Skirted Termination Kits, 7640-S, 7650-S and 7660-S Series 5, 8, 15, 25/28 and 35 kv

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

HI-LINE UTILITY SUPPLY CO. Phone: Fax: WEJTAP TOOLS WEJTAP HOT STICK ACCESSORY KIT

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

600 A 35 kv class separable splices

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS

Easy-On II Terminations

DIE AND COLOR CODE INFORMATION -1 B ~ Fig. 1. Installation Tooling Stud Figure Mechanical Hvdraulic Wire ~ W8CVT (1) W8CVT (1)

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

SUBMERSIBLE SECONDARY CONNECTORS SSBC350-4LI. Cond. Range H W L

Loadbreak Apparatus Connectors

MR Gradient Cable Field Termination Training

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

INSTALLATION INSTRUCTION


Insulated Street and Highway Lighting Mechanical Connectors Insulated connectors for above-ground applications.

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations

(K),(M),(P)489TB/G Up to 42 kv

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

3 Reenterable Encapsulated PST Dome Closure

Company Switch Installation Instructions and User Manual

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

CTN QTY 7/374 8/346 11/375 12/ /298 18/324 19/470 20/299 22/472 24/473. Two-Hole NEMA CTN QTY

TBHD1 CRIMPING TOOL FOR THOMAS & BETTS TS DIES

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Transcription:

Quick Term II Cold Shrink Silicone Rubber Termination Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 15 kv Class 110 kv BIL Kit Contents: 1 Hi K Silicone Rubber Termination 2 Scotch 70 Silicone Rubber Tape Strip(s) 1 Neutral Wire Ground Clip 1 Pack of Silicone Grease (clear 5cc tube with green letters) 1 Instruction Sheet ÁÁ ÁÁ 15 kv Kit Selection Chart NOTE: Cross reference conductor size with insulation O.D. range. Kit Number Cable Insulation O.D. Range 5601 0.637 1.12 in. (16 28 mm) 5602 0.84 1.38 in. (21 35 mm) 5603 1.08 1.80 in. (27 46 mm) Conductor Range (AWG & kcmil) 15 kv 4 Stranded or 2 Solid 4/0 (35 100 mm 2 ) 250 500 (125 250 mm 2 ) 500 1250 (300 600 mm 2 ) Table 1 Quick Term II Cold Shrink Silicone Rubber Termination Kits for use on Concentric Neutral (CN) Cable Concentric Neutral Cable 5601 5602 5603 DR.: D Tracy APP.: P. McDonough NUMBER OF PAGES: 8 SCALE: Not to scale ISSUE DATE: 2/3/97 ISSUE: B 78 8114 1039 4

A. Prepare Cable 1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page). 2. Train cable into position and cut to length required for installation. Allow sufficient neutral wire length for neutral connection. 3. Bind neutral wires with a piece of wire or vinyl tape at dimension [A] + [B] ❶ (Table 2 and Figure 1). 4. Bend the neutral wires over the binding wire or vinyl tape ❷ (Figure 1). 5. Remove cable semi-conductive insulation shield (semi-con) for a distance of [C] plus [B] ❸ (Table 2 and Figure 1). 6. Remove cable insulation ❹ (Figure 1) from end of conductor ❺ for distance [B] ❺ (Table 2 and Figure 1). 7. Place a marker tape 2 back from semi-con cut edge as shown ❻ (Figure 1). * add 1 to [A] and [C] for short lug barrels (1 or less). Kit Number Dimension 5601 5602 5603 [A] 9 9 9 1/2 [B] Depth of Terminal Lug Barrel [C] 5 1/2 5 1/2 6 Table 2 Conductor 2 Solid 1, 2 1/0 2/0 3/0 4/0 3M Stem Connector Number SC0002 SC0001 SC0010 SC0020 SC0030 SC0040 For 3M SC Series Stem Connector. Table 3 B 1 3/4 (44,5 mm) 2 3/8 (60,3 mm) Figure 1 2 [A] [C] [B] ❷ Neutral Wire ❶ Binding Wire or Vinyl Tape ❹ Cable Insulation ❸ Semi-Con Insulation Shield ❻ Marker Tape ❺ Conductor DO NOT LOOP NEUTRAL WIRES BEYOND MARKER TAPE 2

B. Install Lug or Connector 1. If lug ❶ will not fit through the core of the termination, slide termination on cable before installing lug. Do not remove core at this time. Figure 2 ❶ 2. When using 3M type lugs or connectors, refer to the tooling index (Pages 5 and 6) for crimping information. 3. Position lug or connector and crimp according to manufacturer s directions. Remove excess contact aid and sharp crimp flash. C. Clean Cable Insulation and Lug Barrel Using Standard Practice 1. Wipe the cable insulation with an approved solvent. Do not allow solvent to touch semi-con insulation shield! 2. If abrasive must be used: a. Use on insulation only. Do not use abrasive on semi-con insulation shield! b. Use only aluminum oxide abrasive; grit 120 or finer or Scotch A 3 Electrician s Abrasive Roll. c. Be careful not to reduce the cable insulation diameter below that allowed by the kit. D. Install Termination 1. Important: A track resistant seal must be made between the silicone termination insulator and connector using one of two gray Scotch 70 Silicone Rubber Electrical Tape Strips (contained in kit) ❶ (Figure 3). If the lug barrel is smaller than the cable insulation, wrap the bottom end of the lug with gray silicone tape to the approximate diameter of the cable insulation ❶ (Figure 3). 2. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease ❷ (Figure 3).On this product the silicone grease does not serve as a lubricant. It must be used to fill the step at the semi-con cutoff. Figure 3 IMPORTANT Do Not Forget Silicone Grease ÁÁÁ ÁÁÁ ❷ Silicone Grease ❶ Gray Silicone Tape 3

D. Install Termination (continued) 1. Slide the termination body onto the cable and remove core by unwinding, counter-clockwise ❸ (Figure 4), starting with the loose end. Make sure the termination body is butted up to the edge of the marker tape ❹ (Figure 4). Tip: An occasional tug of the strand while unwinding will aid in core removal. Figure 4 ❹ Marker Tape ❸ ÁÁÁ Gray Silicone Tape NOTE: The material being removed at this step is mixed polymers and can be recycled with waste. 2. Complete the lug seal using the second gray silicone tape strip. Overlap insulator by one inch and extend tape wrapping onto lug barrel as shown in ❺ (Figure 5). Figure 5 ÁÁÁÁ ÁÁÁÁ ❺ Gray Silicone Tape E. Install Ground Connection 1. Snap stainless steel grounding clip onto base of termination ❶ (Figure 6). Clip must be applied to the base of the termination, between the bottom two rings. 2. Loop one neutral strand around ground clip ends, pulling clip tight onto the termination ❷ (Figure 6). 3. Bundle all neutral wires together and connect to ground ❸ (Figure 6). Figure 6 ❷ ❸ ❶ Stainless Steel Grounding Clip 4

Binding Wire or Vinyl Tape Correct Installation of Termination ÁÁÁÁÁÁ ÁÁÁÁÁÁ Ridge at End of Cable Insulation Shield (Semi-Con) Ridge at End of High-K Tube Semi-Con Insulation Shield Cable Insulation Conductor High-K Stress Relief 5

Tooling Index Crimping Information for 3M Stem Connectors Copper/Aluminum Conductor CRIMPING TABLE FOR 3M STEM TYPE CONNECTOR Recommended Crimping Tools 3M Connector No. Manufacturer Mech. Tool Die (No. Crimps) Hydraulic Tool Die (No. Crimps) Burndy MD6 BG(4), W243(4) Y35, Y39, Y45** U25ART, U243 #2 Sol. #1, #2 1/0 SC0002 SC0001 SC0010 Kearny T & B 0 51, 0 52 TBM 8 5/8 1(4) Olive 12, 20, 40, Ton TBM 15 5/8 1(4) 50* Anderson VC 6 Universal Burndy MD6 W669(0) 840(5)* Y35, Y39, Y45** U28ART 2/0 3/0 4/0 SC0020 SC0030 SC0040 Kearny T & B 0 51, 0 52 TBM 8 840(5)* White(4) WH 1, WH 2 TBM 15 840 66 Anderson VC 6 Universal Lug and Crimping Information for Scotchlok Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 Two hole Cable AWG/ kcmil Stud (in.) Scotchlok Lug Number Burndy Corporation MD6 MY29 Y34A Y35, 39, 45*, 46* CRIMPING TOOL-DIE SETS (NO. OF CRIMPS) Thomas & Betts Corporation ** Y1000 TBM 5 TBM 8 TBM 12 TBM 15 Square D Co. Anderson Div. VC6 3** VC6 FT** VC8C** ITT Blackburn Co. OD58 Kearne Nat l Div. TYPE 0 6 40016 W161 6 AWG A6CAB U6CABT Grey Grey 29 BY19 J 4 40020 W162 4 AWG A4CAB U4CABT Green Green 37 BY53 P 2 40024 W163 40025 W163 2 AWG 2 AWG A2CAB A2CAB U2CABT U2CABT Pink Pink Pink Pink 42H 42H BY23 BY23 1 40028 40029 W163 W163 1 AWG 1 AWG A1CAR A1CAR U1CART U1CART Gold Gold Gold Gold 45 45 BY23 BY23 1/0 40032 40033 40132 W241 W241 W241 1/0 1/0 1/0 A25AR A25AR A25AR U25ART U25ART U25ART Tan Tan Tan Tan Tan Tan 50 50 50 BY25 BY25 BY25 1 1 1 2/0 40037 BG(4) 2/0 40137 BG(4) 2/0 A26AR A26AR U26ART U26ART Olive Olive Olive Olive 54H 54H BY31C BY31C 5 /8 1 5 /8 1 3/0 40041 W166(4) 3/0 A27AR 40141 W166(4) 3/0 A27AR U27ART U27ART Ruby Ruby Ruby Ruby 60 60 737 737 4/0 40045 40046 40145 W660(4) W660(4) W660(4) 4/0 4/0 4/0 A28AR A28AR A28AR U28ART U28ART U28ART White(4) White(4) White(4) 66(4) 66(4) 66(4) BY35C(4) BY35C(4) BY35C(4) 840(4) 840(4) 840(4) 250 40049 40050 40149 W249 W249 W249 A29AR A29AR A29AR U29ART U29ART U29ART 71H(4) 71H(4) 71H(4) 71H 71H 71H 300 40053 40153 A30AR A30AR U30ART U30ART 76H(4) 76H(4) 76 76 350 40056 40057 40156 U31ART U31ART U31ART 87H(4) 87H(4) 87H(4) 87H 87H 87H 400 40160 U32ART(4) 94H(4) 94H(4) 500 40067 40166 U34ART(4) U34ART(4) 106H(4) 106H(4) 106H 106H 600 40170 U36ART(4) 115H 750 40073 40172 U39ART(4) U39ART(4) 125H(5) 125H(5) 1000 40079 40178 S44ART(4) S44ART(4) 140H(4) 140H(4) * Y45 and Y46 accept all Y35 dies ( U series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter. ** Anderson VC6 3, VC6 FT, VC8C and Burndy Y1000 require no die set. 6

Tooling Index Lug and Crimping Information for Scotchlok Copper Lugs 30014 thru 30045 One hole 31036 thru 31068 One hole long barrel 31145 thru 31178 Two hole Cable AWG/ kcmil Stud (in.) Scotchlok Copper Lug Number Burndy Corporation MD6 MY29 Y34A CRIMPING TOOL-DIE SETS (NO. OF CRIMPS) Thomas & Betts Corporation Y35, Y39 Y45*, Y46* TBM 5 TBM 8 TBM 15 Square D Co. Anderson Div. VC6 3, VC6 FT** 6 10 1 / 4 30014 30015 30016 6 AWG U5CRT Blue Blue Universal 4 10 1 / 4 30018 30019 30021 W161 4 AWG A4CR U4CRT Grey Grey Universal 2 1 / 4 30022 30023 30024 W162 2 AWG A2CR U2CRT Brown Brown 33 Universal 1 30027 30028 1 AWG A1CR U1CRT Green Green 37 Universal 1/0 30031 30032 W163 1/0 A25R U25RT Pink Pink 42H Universal 2/0 30036 31036 W241 W241 2/0 2/0 A26R A26R U26RT U26RT Black Black Black Black 45 45 Universal Universal 3/0 30041 W243 3/0 A27R U27RT Orange Orange 31041 W243 3/0 A27R U27RT Orange Orange 50 50 Universal Universal 4/0 30045 31045 31145 BG BG(4) BG(4) 4/0 4/0 4/0 A28R U28RT U28RT U28RT Purple Purple Purple Purple Purple Purple 54H 54H 54H Universal Universal Universal 250 31049 31149 W166(4) 250 A29R U29RT Yellow Yellow 62 Universal 300 31053 31153 A30R U30RT White 66 Universal 350 31056 31156 A31R U31RT Red(4) 71H(4) 400 31060 31160 A32R U32RT Blue(4) 76H(4) 500 31066 31067 31166 A34R U34RT Brown(4) 87H(4) 600 31068 1 U36RT Green(4) 94H(4) / 2 31168 750 31172 Y39, Y45, Y46: U39RT(5) 106H(4) 1000 31178 Y45: S44RT(6) Y46: P44RT(6) 125H(4) 7

Important Notice to Purchaser: Electrical Products Division 6801 River Place Blvd. Austin, TX 78726-9000 Recycled paper 40% pre-consumer 10% post-consumer