1 7 Inspection and Maintenance of Flame Arresters 7.1. Need and Importance of Maintenance Inadequate maintenance of flame arresters can result in their failure to perform as required. Failure can result from enlargement of the apertures due to corrosion, erosion, shock waves, or mishandling during cleaning. This results in the inability to stop the breakthrough of flames from deflagrations and detonations. Another cause for failure is pluggage due to entrainment of solids from the process, polymer deposits, freezing of water and organic liquids, and nests built by birds and insects. In this case, the plugged flame arrester may prevent or diminish vapor inflow and outflow from vessels, which can lead to vessel failure due to overpressure or vacuum collapse. Fixed element dry type flame arresters, such as end-ofline deflagration arresters, are especially susceptible to these failures. However, hydraulic (liquid seal) flame arresters, and other types can also fail to operate as required if regularly scheduled maintenance is not provided Mechanical Integrity Issues This section discusses inspection and maintenance practices and procedures that affect the mechanical integrity of flame arrester installations. 147

2 Inspection and Maintenance of Flame Arresters Inspection It is critical to the integrity of flame arresters that they be inspected and serviced on a regularly scheduled basis (preventive maintenance program) so that they continue to be effective. The regularity of inspections and the time interval between inspections depends on the application and company practice. One flame arrester manufacturer recommends that inspection should be made a month after initial operation. Many companies perform inspection and maintenance at least once annually unless operating experience indicates that the inspection period should be changed. Some companies that continuously monitor the pressure drop do not inspect flame arresters until abnormal pressure drop is detected. However, pressure drop may not identify corrosion problems or absence of the element or gaskets. Even if pressure drop indicates no potential problem, it is recommended that all flame arresters be visually inspected on a scheduled basis. Plugging may not be readily detected by pressure drop where the normal vent flow is only a small fraction of the design basis flow. Some flame arrester designs allow in-place inspection (via a removable housing cover plate); however, others have to be removed from the vent nozzle or in-line piping to inspect the flame arrester element. There are some mechanical factors that sometimes hamper inspection. A flame arrester may be in a location that is not readily accessible or does not provide sufficient working space or mechanical aids. This is why, as was mentioned in Chapter 6, proper location and installation is very important. If removal of the flame arrester is required for inspection, then purging may be required before removal. This may be difficult to do easily because of the flame arrester construction or location. Also, some flame arresters may be constructed so that removal of the arrester element for inspection is not possible (i.e., the element is welded to the housing). Another problem is that the flame arrester is in a pipeline or directly attached to a vessel that is in constant use. In some cases, this might even be a problem during a period of a turnaround. In this situation it may be necessary to install two flame arresters in parallel with adequate valving to switch from one to the other and to provide for purging. Before performing any inspection or maintenance on a flame arrester, the associated process equipment and piping should be taken out of service or isolated. The work area must be proven by test to be free of any harmful gases or vapors. It should also be verified that all piping is clean and free of obstructions and debris. All plant, company, local, state, and federal safety and fire codes and standards should be followed.

3 7.2. Mechanical Integrity Issues Current Maintenance Practices Depending on the size of a flame arrester, the cleaning of the flame arrester element may be done in place or in the maintenance shop. Removal of the flame arrester from its location and transport to the maintenance shop may require heavy lifting equipment. Care is needed to ensure that the cleaning method is compatible with the flame arrester in terms of the materials of construction and the arresters overall robustness. Suitable cleaning methods include the use of solvents, water, steam, compressed air, or ultrasonics. For crimped metal ribbon elements, cleaning must be done carefully, because of the small and delicate flow channels involved. It is important not to clean the element with sharp objects that might open the flow channels or distort them, and thus disable the arrester. At the same time, the small flow channels may tenaciously hold solids filtered from the line. In this case it may be desirable to send the element to the flame arrester manufacturer for cleaning. It is advisable to stock spare elements for replacement of the element returned to the manufacturer for cleaning so that the flame arrester may be returned to service quickly. If the flame arrester element is of the parallel plate type some manufacturers caution against disassembling the grid assembly to clean it. This is because such handling may increase the gaps between the plates to larger than the original design rendering the flame arrester ineffective. It is critical upon reassembly to check that all gaskets are properly installed and that the element is correctly aligned in the housing to ensure that there is no bypassing of the element. Failure to do this may result in complete loss of protection. On-line cleaning may be desirable for very large flame arresters as the elements may not be readily removed. One such on-line cleaning installation is provided for a 72-inch-diameter flame arrester assembly, which weighs more than 15,000 pounds and is installed in a 36-inch-diameter piping system (Anon 1999, Dafft 1999). The flame arrester is located in a vent gas collection system, upstream of an incinerator. The vent gas contains sticky solids that could eventually plug the flame arrester if not removed. To remove the sticky solids a cleaning assembly with multiple spray nozzles is provided for on-line cleaning of the flame arrester element with a mixture of steam and hot deionized water while the process gas continues to flow to an incinerator. If a flame arrester element is damaged, its effectiveness will be impaired, and a replacement should be considered. It is important to ensure that the replacement meets all specifications and that it is installed correctly, per the manufacturer s recommendations. It is recommended

4 Inspection and Maintenance of Flame Arresters that a flame arrester be inspected after it stops a flame (see Sections and ). All flame arrester manufacturers have written instructions for installation, inspection, and maintenance, and these should be followed. Some flame arrester manufacturers require that maintenance be done at their facility to avoid invalidating the flame arrester warranty Documentation and Verification of Flame Arrester Maintenance It is important that the inspection and maintenance activities be documented as required per company practice and any process safety management regulatory requirements. Maintenance records should indicate the inspection results and the scope of maintenance work performed, if any. Before the flame arrester is reinstalled in the process, it should be visually inspected to make sure that reassembly conforms to the manufacturer s recommendations. Some companies affix a tag to the flame arrester indicating the inspection and maintenance date Training and Competence Issues for Operating and Maintenance Personnel Proper training on the operation and maintenance of flame arresters should be given to the appropriate personnel so that they will become competent with respect to the operating characteristics of the various types of flame arresters used in a plant, as well as their specific inspection and maintenance requirements. Many flame arrester manufacturers provide training courses on inspection and maintenance of flame arresters, either at their facilities or a client s plant. It is recommended that such courses be scheduled for operating and maintenance personnel. Also, the OSHA PSM standard, 29 CFR (j)(3), should be consulted for requirements for training for process maintenance activities On-Stream Isolation and Switching of Parallel Spares For vapor lines that cannot be shut down conveniently to remove and clean arrester elements, parallel flame arresters are sometimes installed. To be able to switch the flame arresters, suitable isolation valving must be installed upstream of the flame arresters, which will allow the switching to be done without interrupting operations. Care must be taken to assure that

5 7.6. References 151 monitoring instrumentation and/or interlocks remain functional at all times. Procedures or interlocks must ensure that the process system is protected at all times Check List for Inspection Flame Arrester Type Dry fixed element Hydraulic Packed bed What to Look For Plugging, corrosion, physical damage, correct bolt torque, contaminants, correct arrester orientation, functioning instrumentation Proper liquid level, seal fluid contaminants, foam, vessel corrosion, distributor pluggage, functioning instrumentation Packing attrition, corrosion, fouling or plugging, distributor condition (for wet type), functioning instrumentation 7.6. References Regulations, Codes of Practice, and Industry Standards 29 CFR Process Safety Management of Highly Hazardous Chemicals. U.S. Department of Labor, Washington, DC Specific References Anon New Detonation Arrester Stops Flamefronts. InTech, p. 26 (July 1999). Dafft, C. A Personal communication from C. A. Dafft, Rohm and Haas Company, Deer Park, TX to S. S. Grossel (August 1999). Howard, W. B Use Precaution in Selection, Installation, and Operation of Flame Arresters. Chemical Engineering Progress, 88(4),

INSTALLATION AND MAINTENANCE

INSTALLATION AND MAINTENANCE System Series SDB A.GENERAL The Deflagration- and Endurance burning Flame Arresters, Series SDB, are intended for use in Piping Systems handling flammable Gases / Vapours of Gas Group Ex. IIA / I. B. GUIDANCE

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Intelligent Flow Measurement Your Sole Source for Badger Differential Producers Worldwide 6 Blackstone Valley Place, Lincoln RI 02865-1162 Ph: 401 334 1170 Fx: 401 334 1173 Em: solutions@wyattflow. Installation,

More information

Installation, Operation and Maintenance Manual for Flame Check

Installation, Operation and Maintenance Manual for Flame Check Installation, Operation and Maintenance Manual for Flame Check Model 7622B 2014 Groth Corporation IOM-7622B Rev. C 12444 Ref. ID: 98172 Page 2 of 9 Table of Contents SECTION PAGE I. Introduction 3 II.

More information

KEEP FOR FUTURE REFERENCE DC VACUUM BACK-UP SYSTEM READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT

KEEP FOR FUTURE REFERENCE DC VACUUM BACK-UP SYSTEM READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT KEEP FOR FUTURE REFERENCE P.O. Box 368 908 West Main Laurel, MT USA 59044 phone 800-548-7341 phone 406-628-8231 fax 406-628-8354 INSTRUCTIONS International Version STOCK NUMBERS: SEE SPECIFICATIONS DC

More information

SERIES 670E End-of-Line Deflagration Flame Arrester

SERIES 670E End-of-Line Deflagration Flame Arrester SERIES 670E PROTECTOSEAL CAUTION: If any questions arise concerning the proper installation or maintenance of our products, please contact Protectoseal or one of our Authorized Representatives. When installing

More information

Fisher TBX Hydro Plug Fixture

Fisher TBX Hydro Plug Fixture Instruction Manual TBX Hydro-Plug Fixture Fisher TBX Hydro Plug Fixture Contents Introduction... 1 Scope of Manual... 1 Description... 2 Educational Services... 2 Principle of Operation... 2 Maintenance...

More information

back to main page Type: Butterfly valves Instructions and Operation Manual Warning! Warning! Danger for life! 1. Intended use Danger for life!

back to main page Type: Butterfly valves Instructions and Operation Manual Warning! Warning! Danger for life! 1. Intended use Danger for life! Instructions and operation manual for butterfly valves This manual is intended to support the users of Herberholz butterfly valves type HRD/HRA, RD/RA, LDKE/LDKF for installation, operation and maintenance

More information

Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual

Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual Orifice Flange Union Assembly and Orifice Run Installation and Operation Manual 354-EN Please read and save these instructions. Installation Procedures Orifice Flange Union Assembly Installing Orifice

More information

Installation in Process Systems

Installation in Process Systems 6 Installation in Process Systems 6.1. Design Considerations with Respect to Other System Components When a flame arrester is installed in a system, consideration must be given to how it may adversely

More information

GT-200 GATE VALVES PN16, Screwed end

GT-200 GATE VALVES PN16, Screwed end Document No. : MD-QO-04-281 Date : 2009/07 /17 Version : 1.0 GT-200 GATE VALVES PN16, Screwed end USER MANUAL Modentic Industrial Corporation 14F-1,No.57Taya Rd.,Taichung,Taiwan,R.O.C. Email:modentic@ms9.hinet.net

More information

Operating & Maintenance Manual For Steam Conditioning Valve

Operating & Maintenance Manual For Steam Conditioning Valve For Steam Conditioning Valve 1 Table of Contents 1.0 Introduction 3 2.0 Product description 3 3.0 Safety Instruction 4 4.0 Installation and Commissioning 5 5.0 Valve Disassembly 6 6.0 Maintenance 6 7.0

More information

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004 U00X ULTRASONIC LEVEL SWITCH INSTALLATION AND OPERATIONS MANUAL Ultrasonic Liquid Level Switches For Non-Hazardous Locations For Models: U002, U003 & U004 READ THIS MANUAL PRIOR TO INSTALLATION This manual

More information

FABER BURNER ROUTINE MAINTENANCE

FABER BURNER ROUTINE MAINTENANCE FABER BURNER ROUTINE MAINTENANCE Version 2016 The Faber burner is designed for minimal maintenance; however, the frequency and quantity of maintenance that is required depends upon many factors which vary

More information

F8/FB8 Series Ball Valves IOM-F8/FB8

F8/FB8 Series Ball Valves IOM-F8/FB8 !!!CAUTION! Safety Precautions!!! Before removing valve from pipeline NOTE that: Media flowing through a valve may be corrosive, toxic, flammable, or a contaminant of harmful nature. Where there is evidence

More information

ROOTS Meters Series B3 Meter Models 8C175-56M175

ROOTS Meters Series B3 Meter Models 8C175-56M175 ROOTS Meters Series B3 Meter Models 8C175-56M175 Refer to IOM-B3 for Complete Instructions IS:B3 3.03 RECEIVING, HANDLING AND STORAGE ROOTS rotary positive displacement gas meters are precision measurement

More information

Steam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions

Steam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-8-002-US October 2016 Steam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions These instructions should be read by the Company

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER INJECTION PUMP

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER INJECTION PUMP INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER INJECTION PUMP MODEL SSO-8 DRAWING NUMBERS AD148CF AD148CG AD148CO AD148CQ AD500CA MANUAL NUMBER IOM-065 REVISION Rev. A, 8/17/2016 TABLE OF CONTENTS

More information

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor

The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor OPERATIONS MANUAL The Combustex Pilot Pro 800 Pilot Burner Assembly with Ignition & Flame Failure Monitor Safe, reliable ignition and flame failure protection combined with a proven, completely self-powered

More information

Welker Adjustable Probe with Check Valve and Welker Automatic Insertion Probe with Check Valve

Welker Adjustable Probe with Check Valve and Welker Automatic Insertion Probe with Check Valve a Installation, Operation, & Maintenance Manual Welker Adjustable Probe with Check Valve and Welker Automatic Insertion Probe with Check Valve Models AP-3MI & AIP-3MI The information in this manual has

More information

Fisher CVX Hydro Plug Fixture

Fisher CVX Hydro Plug Fixture Instruction Manual CVX Hydro-Plug Fixture Fisher CVX Hydro Plug Fixture Contents Introduction... 1 Scope of Manual... 1 Description... 1 Educational Services... 2 Principle of Operation... 2 Maintenance...

More information

INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS

INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS INSTALLATION AND OPERATING INSTRUCTIONS FOR CONCRETE VAULT TYPE UNITS CONTENTS Introduction Safety Operating Principle System Installation Initial Startup System Operations Troubleshooting Maintenance

More information

Installation, Operation & Maintenance. Model 7678 End of Line Deflagration Flame Arrester ATEX Certified

Installation, Operation & Maintenance. Model 7678 End of Line Deflagration Flame Arrester ATEX Certified Installation, Operation & Maintenance Model 7678 End of Line Deflagration Flame Arrester ATEX Certified January 2, 2012 IOM-7678 Rev. A 12187 Ref. 97290 Table of Contents Section Page Introduction 2 Certification

More information

Welker Heated Instrument Regulator

Welker Heated Instrument Regulator Installation, Operation, and Maintenance Manual Welker Heated Instrument Regulator Model The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for

More information

Model Ton Hand Carry Axle Jack P/N: CJ67D0250-1

Model Ton Hand Carry Axle Jack P/N: CJ67D0250-1 Model 1504-50 15 Ton Hand Carry Axle Jack P/N: CJ67D0250-1 Operation and Maintenance Manual with Illustrated Parts List 2222 South Third Street Columbus, Ohio 43207-2402 Phone (614) 443-7492 FAX (614)

More information

An Explosive Situation. Definitions

An Explosive Situation. Definitions An Explosive Situation Explosions due to flame arrester failures are destructive, expensive and potentially deadly. Prior to 1989, no arrester provided protection against all types of flame propagation.

More information

2. Disconnect the accelerator control cable and the cruise control cable from the throttle body. 3. Disconnect the vacuum hose from the throttle body.

2. Disconnect the accelerator control cable and the cruise control cable from the throttle body. 3. Disconnect the vacuum hose from the throttle body. 2002 Silverado K 4WD Applies to: 4.8L, 5.3L, and 6.0L Report a problem with this article Removal Procedure 1. Remove the air intake duct. Refer to Air Cleaner Resonator Outlet Duct Replacement. 2. Disconnect

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER PROBE MOUNTED LIQUID ELIMINATOR

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER PROBE MOUNTED LIQUID ELIMINATOR INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER PROBE MOUNTED LIQUID ELIMINATOR MODEL LE-2SSKO DRAWING NUMBERS AD691BG AD691BGSYS.3 AD691BGSYS.4 AD691CC AD691CD AD691CG AD691CI MANUAL NUMBER IOM-069

More information

EJECTORS GENERAL OPERATION & MAINTENANCE MANUAL

EJECTORS GENERAL OPERATION & MAINTENANCE MANUAL EJECTORS GENERAL OPERATION & MAINTENANCE MANUAL The information contained in this manual was current at the time of printing. The most current versions of all Hydro Instruments manuals can be found on

More information

LVDT/HC PILOT BURNER. External raw gas pilot burner

LVDT/HC PILOT BURNER. External raw gas pilot burner 4-22.4-1 LVDT/HC PILOT URNER External raw gas pilot burner Stable pilot flame in combination with MXON IRFLO LV, HC, DELT-TE and COMUSTIFUME burners Rugged design urns natural gas, propane and LPG Suitable

More information

Flame-transmission-proof KITO devices for storing and transporting combustible fluids, vapours and gases

Flame-transmission-proof KITO devices for storing and transporting combustible fluids, vapours and gases Flame-transmission-proof KITO devices for storing and transporting combustible fluids, vapours and gases Typical KITO flame arrester elements, which prevent the propagation of flames and explosions (both

More information

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual ACRIS PFA LINED BALL VALVES WWW.AMRESIST.COM Table of Contents Safety Instructions - Definition of Terms............................................2 Introduction..............................................................2

More information

Drilling Series SC Series Cellular Suction Stabilizers Instruction, Operating & Maintenance Manual

Drilling Series SC Series Cellular Suction Stabilizers Instruction, Operating & Maintenance Manual Drilling Series SC Series Cellular Suction Stabilizers Instruction, Operating & Maintenance Manual Manufacturer of Pulsation Control Products 3309 Essex Dr. Suite 200, Richardson, Texas 75082 Phone: 972.699.8600

More information

PENBERTHY MODELS GL AND GH GAS OPERATED JET PUMPS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

PENBERTHY MODELS GL AND GH GAS OPERATED JET PUMPS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Before installation, these instructions must be read carefully and understood. PRODUCT WARRANTY Emerson warrants its Penberthy products as designed and manufactured to be free of defects in the material

More information

KEYSTONE. Butterfly valves Figure 9 Installation & Maintenance Instructions. Please read these instructions carefully

KEYSTONE. Butterfly valves Figure 9 Installation & Maintenance Instructions.  Please read these instructions carefully KEYSTONE Please read these instructions carefully This symbol indicates important messages and safety instructions. Hazard potentials: disregarding of instructions improper use of product insufficiently

More information

Typical Machine Tool Coolant Purification Unit Installation and Operating Manual Note: MSR provides a custom manual for every application

Typical Machine Tool Coolant Purification Unit Installation and Operating Manual Note: MSR provides a custom manual for every application Typical Machine Tool Coolant Purification Unit Installation and Operating Manual Note: MSR provides a custom manual for every application Mohr Separations Research Model MSR-33 S Separator Customer: Background

More information

Installation and Operating Manual

Installation and Operating Manual Model u002 & u003 Installation and Operating Manual Ultrasonic Level Switch 60 Great Hill Road Naugatuck, CT 06770 ph: 203-729-6434 fax: 203-729-6696 www.innovativesensing.com Read this Manual Before Installing

More information

Venturi Flow Meter Installation and Operation Manual

Venturi Flow Meter Installation and Operation Manual Venturi Flow Meter Installation and Operation Manual 357-EN Please read and save these instructions. Installation Procedures The Proper Method of Installing a Venturi Meter Caution: - This is a high quality

More information

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions 4034450/9 IM-P403-15 AB Issue 9 BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions 1. Safety information 2. Application 3. Technical data 4. Operation 5. Installation 6. Rotating

More information

Delayed Coking. Process Overview

Delayed Coking. Process Overview Process Overview Page 1 of 6 History of the Delayed Coking Process Petroleum coke was first made by the pioneer oil refineries in Northwestern Pennsylvania in the 1860 s. Primitive distillation techniques

More information

JOB AID INTRODUCTION TOOLS REQUIRED: GC160 GC190 GS190 GCV160 GCV190 GSV160 GSV190 CARBURETOR CLEANING

JOB AID INTRODUCTION TOOLS REQUIRED: GC160 GC190 GS190 GCV160 GCV190 GSV160 GSV190 CARBURETOR CLEANING JOB AID GC160 GC190 GS190 GCV160 GCV190 GSV160 GSV190 CARBURETOR CLEANING INTRODUCTION Service engineering has discovered that many GCV carburetors returned for warranty were improperly cleaned. Eighty

More information

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood HAZARD POTENTIALS disregarding of instructions improper use of product insufficiently qualified personnel Valve application to be

More information

Fisher RSS Lined Globe Valve

Fisher RSS Lined Globe Valve Instruction Manual D0990 RSS Valve July 07 Fisher RSS Lined Globe Valve Contents Introduction... Scope of Manual... Description... Educational Services... Specifications... Installation... Maintenance...

More information

TECHNICAL DATA 1-1/2 (dn40)

TECHNICAL DATA 1-1/2 (dn40) July 1, 2011 Deluge Valves 209a DESCRIPTION The Viking Model E-3 1-1/2 Deluge Valve is a quick-opening, differential type flood valve with a rolling diaphragm clapper. The deluge valve is used to control

More information

Maintenance Information

Maintenance Information (Dwg. MHP1539) 16600470 Edition 1 May 2007 Z Rail Aluminum and Steel Overhead Rail System Maintenance Information Save these Instructions The minimum maintenance required for a rail system requires inspection

More information

Rental Industry Safety Tester Safe Check 5s

Rental Industry Safety Tester Safe Check 5s Rental Industry Safety Tester Safe Check 5s Feb 2006 2006 Clare Instruments Inc. Issue 2.0 Firmware Version : 1.2a Limited Warranty & Limitation of Liability Clare Instruments Inc, guarantees this product

More information

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL S003 LIQUID LEVEL FLOAT SWITCH INSTALLATION AND OPERATIONS MANUAL Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information

More information

Amerigear SL Spindle

Amerigear SL Spindle Amerigear SL Spindle Installation and Maintenance Manual Form No. 378-SH, 6/97 Spindle Installation and Maintenance Manual TABLE OF CONTENTS SECTION TITLE PAGE 1 Introduction...: 3 2 General Information...:

More information

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 4. Ozone: storage rooms should not contain any equipment generating ozone. E.g. lamps, electric motors. IMPORTANT Before valves

More information

HTX-HTH SEPARATORS I&O MANUAL

HTX-HTH SEPARATORS I&O MANUAL INSTALLATION OPERATIONS AND MAINTENANCE HTX-HTH SEPARATORS I&O MANUAL 1365 N. Clovis Avenue Fresno, California 93727 (559) 255-1601 www.lakos.com LS-714B (Rev. 11/17) TABLE OF CONTENTS Table of Contents...

More information

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been

More information

To ensure proper installation, digital pictures with contact information to before startup.

To ensure proper installation,  digital pictures with contact information to before startup. Check List for Optimal Filter Performance? There should be no back-pressure on the flush line. A 1 valve should have a 2 waste line, and 2 valve should have a 3 waste line. Do not use rubber hosing or

More information

Operating instructions. Skyline Beam Clamp Bypass

Operating instructions. Skyline Beam Clamp Bypass Operating instructions for Skyline Beam Clamp Bypass Model # 3091 Reliance Industries, LLC PO Box 140008 Denver, CO 80214 Ph. (800) 488-5751 Ph. (303) 424-8650 Fax (303) 424-8670 User Instructions 3091

More information

Installation, Operation & Maintenance. Model 7688 In Line Deflagration Flame Arrester. ATEX Certified

Installation, Operation & Maintenance. Model 7688 In Line Deflagration Flame Arrester. ATEX Certified Installation, Operation & Maintenance Model 7688 In Line Deflagration Flame Arrester ATEX Certified January 2, 2012 IOM-7688 Rev. A 12188 Ref. 97291 1 Section Table of Contents Page Introduction 2 Certification

More information

GUIDELINES FOR THE MAINTENANCE AND INSPECTIONS OF FIXED CARBON DIOXIDE FIRE-EXTINGUISHING SYSTEMS

GUIDELINES FOR THE MAINTENANCE AND INSPECTIONS OF FIXED CARBON DIOXIDE FIRE-EXTINGUISHING SYSTEMS INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 IMO E Ref: T4/4.01 11 June 2009 GUIDELINES FOR THE MAINTENANCE AND INSPECTIONS OF FIXED

More information

METERING VALVE 2" STEM GUIDED

METERING VALVE 2 STEM GUIDED 2" STEM GUIDED All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been made to ensure their accuracy, they are not to be construed

More information

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED DIAPHRAGM BALANCED All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been made to ensure their accuracy, they are not to

More information

KITO explosion and endurance burning flame arrester devices

KITO explosion and endurance burning flame arrester devices KITO flame arresters and fittings for the storage and transportation of inflammable liquids, vapours and gases. Designed to prevent fire penetration, explosions and detonations in tank installations of

More information

2" - 24" OS Series Butterfly Valves. Operation and Maintenance Manual. Job Name: Contractor: Date:

2 - 24 OS Series Butterfly Valves. Operation and Maintenance Manual. Job Name: Contractor: Date: s Operation and Maintenance Manual Job Name: Contractor: Date: Document #: IOM Revision Date: 10/2/2016 SAFETY MESSAGES All safety messages in the instructions are flagged with an exclamation symbol and

More information

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils

Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Standard Service / Installation / Operation Manual Type W & P Water / Glycol Heat Transfer Coils Please consult your local representative or the factory for warranty issues. July 2017 DRS Marlo Coil Customer

More information

Picking Dry-Type Flame Arresters

Picking Dry-Type Flame Arresters Fluids/Solids Handling Don t Get Burned Picking Dry-Type Flame Arresters Stanley S. Grossel, Process Safety & Design, Inc. Flame arresters prevent the propagation of a flame front from outside of a storage

More information

Tool-less Hinged Closure Installation, Operation, & Maintenance

Tool-less Hinged Closure Installation, Operation, & Maintenance 2612 Howard Street Louisville, KY 40211 USA Phone 502-774-6011 Fax 502-774-6300 Website: www.tubeturns.com For genuine Tube Turns Closure parts please contact factory: ttaftermarket@sypris.com Bulletin

More information

Volumetric Measuring Devices Issued: Revision Number: 2

Volumetric Measuring Devices Issued: Revision Number: 2 Field Inspection Manual Part: 4-STP Section: 29 Page: 1 of 5 APPLICATION This procedure is used when performing accuracy tests on any measuring systems that incorporate an air eliminator or deaerator of

More information

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822 Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822 Statements: NIBCO High Performance Butterfly Valves, Series 6822 and 7822, have been designed

More information

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16 USER INSTRUCTIONS NAF Setball SF Ball Sector Valves FCD NFENIM4156-00 A4 09/16 Installation Operation Maintenance Experience In Motion Contents SAFETY 3 1 General 3 2 Lifting 4 3 Receiving Inspection 4

More information

SERIES PC INSTRUCTION AND OPERATION MANUAL

SERIES PC INSTRUCTION AND OPERATION MANUAL MEGGA SERIES PC INSTRUCTION AND OPERATION MANUAL Models PCT and PCF Close-coupled and frame-mounted single-stage horizontal end-suction pumps. WARNING: Read this manual before installing or operating this

More information

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING

ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING 1.0 General 1.1 The work covered by this section consists of providing all labor, equipment, material and supplies, insurance, accessories, tools, transportation,

More information

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com I000-7000-D0447-A 4/7/05 1 SAFETY PRECAUTIONS CAUTION Please read this entire document prior to operating the gear drive. Gear drive failure and / or injury to operators may be caused by improper installation,

More information

OPERATION & MAINTENANCE INSTRUCTION MANUAL

OPERATION & MAINTENANCE INSTRUCTION MANUAL Last Updated 12-11-2017 OPERATION & MAINTENANCE INSTRUCTION MANUAL TABLE OF CONTENTS GENERAL Page 2 TANKS FOR FOOD APPLICATION Page 2 AFTER THE TANK IS PUT INTO SERVICE Page 3 TANK USAGE Page 3 AIR LOADING

More information

Installation and Service Manual for SRC25, SRC252, SRC50, SRC502, SRC75, SRC752

Installation and Service Manual for SRC25, SRC252, SRC50, SRC502, SRC75, SRC752 Rocking Piston Compressors Installation and Service Manual for SRC25, SRC252, SRC50, SRC502, SRC75, SRC752 Thank you for purchasing the Stratus SRC series rocking piston compressor. This instruction manual

More information

Handling Precautions, Prohibitions and General Supply Notices for VARTA Microbattery GmbH CoinPower Lithium-Ion Batteries

Handling Precautions, Prohibitions and General Supply Notices for VARTA Microbattery GmbH CoinPower Lithium-Ion Batteries Handling Precautions, Prohibitions and General Supply Notices for VARTA Microbattery GmbH CoinPower Lithium-Ion Batteries Current version available under www.coinpower.de Preface Lithium batteries provide

More information

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual Before installation these instructions must be fully read and understood Important Before valves are installed or used the following actions are recommended. 1. Valves/parts have to be inspected and thoroughly

More information

TC Series Cooling Systems

TC Series Cooling Systems TC Series Cooling Systems Table of Contents Table of Contents...1 List of Figures...1 Safety...2 Introduction...2 General Specifications...2 Types of Coolant...2 Routine Maintenance...2 Surge Tank Coolant

More information

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE Page 1 of 13 1.1 General CHAPTER 1 - GENERAL INFORMATION This manual contains maintenance instructions with pertinent

More information

GL Ludemann Y-Strainers

GL Ludemann Y-Strainers GL Ludemann Y-Strainers Installation, Operation and Maintenance Manual English Issue 1-03/2014 - Page 1/7 GENERAL These instructions are for installing, operation and maintenance of Y-strainers fabricated

More information

Operating manual Separator

Operating manual Separator Operating manual Separator Sheet no. AS/4.1.141.1.1 issue 20.08.2014 Contents Section Title Page 0 Introduction... 1 1 Intended use......1 2 Marking of the fitting... 1 3 Safety instructions... 2 4 Transport

More information

IOM-CleanFLOW TM. CleanFLOW Series Ball Valves. SV F Flow Controls I N C O R P O R A T E D

IOM-CleanFLOW TM. CleanFLOW Series Ball Valves. SV F Flow Controls I N C O R P O R A T E D !!!CAUTION! Safety Precautions!!! Before removing valve from pipeline NOTE that: Media flowing through a valve may be corrosive, toxic, flammable, a contaminant or harmful nature. Where there is evidence

More information

Index. D Davy, Humphrey, 5, 84 Decomposition flames, flame propagation, 59

Index. D Davy, Humphrey, 5, 84 Decomposition flames, flame propagation, 59 Deflagration and Detonation Flame Arresters by Stanley S. Grossel Copyright 2002 American Institute of Chemical Engineers A Acetylene, flame arrester selectioddesign criteria, 130-1 31 Alumina (ceramic)

More information

DURAFire Oil Igniter User Manual. Publication Rev H

DURAFire Oil Igniter User Manual. Publication Rev H DURAFire Oil Igniter User Manual Publication INTRODUCTION This manual contains information for the DuraFire Oil Igniter from Forney Corporation, 16479 North Dallas Parkway, Suite 600 Addison, TX 75001.

More information

Installation, Operation and Maintenance Manual for Model 7758A Deflagration and Detonation Flame Arrester

Installation, Operation and Maintenance Manual for Model 7758A Deflagration and Detonation Flame Arrester Installation, Operation and Maintenance Manual for Model 7758A Deflagration and Detonation Flame Arrester 2010 Groth Corporation IOM-7758A Rev. B 12015 Ref. ID: 95618 TABLE OF CONTENTS: INTRODUCTION 2

More information

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP Installation, Operation, & Maintenance Manual Welker Sampler Model GSS-4HP The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor

The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor OPERATIONS MANUAL The Combustex Pilot Pro 500 Ignition System with Pilot Tip and Flame Sensor The CSA approved alternative ignition system delivering safety, reliability and versatility. KEY FEATURES Unique

More information

Top Drive System Installation and Commissioning Manual

Top Drive System Installation and Commissioning Manual TDS-1000A Top Drive System Installation and Commissioning Manual SM01040 General Information Conventions.............................. 1-3 Notes, Cautions, and Warnings......................... 1-3 Illustrations.........................................

More information

Diaphragm Valves Type 15

Diaphragm Valves Type 15 Serial No. H-V031-E-8 Diaphragm Valves Type 15 User s Manual Contents (1) Be sure to read the following warranty clauses of our product 1 (2) General operating instructions 2 (3) General instructions for

More information

SERIES G3DB/AG3DB ELEVATOR

SERIES G3DB/AG3DB ELEVATOR TM INSTRUCTIONS AND PARTS LIST SERIES G3DB/AG3DB ELEVATOR WARNING This manual, and GENERAL INSTRUCTIONS MANUAL, CA-1, should be read thoroughly prior to pump installation, operation or maintenance. SRM00059

More information

RULE 448 GASOLINE TRANSFER INTO STATIONARY STORAGE CONTAINERS Adopted (Amended , , , , , ) INDEX

RULE 448 GASOLINE TRANSFER INTO STATIONARY STORAGE CONTAINERS Adopted (Amended , , , , , ) INDEX RULE 448 GASOLINE TRANSFER INTO STATIONARY STORAGE CONTAINERS Adopted 2-5-75 (Amended 9-15-75, 8-3-77, 9-2-80, 12-17-91, 2-2-95, 02-26-09) INDEX 100 GENERAL 101 PURPOSE 102 APPLICABILITY 110 EXEMPTION:

More information

Technology. The OILMISER Vapor Guard

Technology.   The OILMISER Vapor Guard The OILMISER Vapor Guard An air breather is used to vent the enclosed air space on the Drive End and Non-Drive End bearings on a Boiler Feed Pump. Increasing heat and thermal expansion, cause inside oil

More information

TITAN FLOW CONTROL, INC.

TITAN FLOW CONTROL, INC. PREFACE: TITAN FLOW This manual contains information concerning the installation, operation, and maintenance of Titan Flow Control (Titan FCI)Full Body Swing Check Valves. To ensure efficient and safe

More information

CAST STEEL FLANGED GATE, GLOBE, & CHECK VALVES

CAST STEEL FLANGED GATE, GLOBE, & CHECK VALVES INTRODUCTION This instruction manual includes storage, installation, operation and maintenance information for cast steel flanged gate, globe, and check valves. This manual addresses class 150 and 300

More information

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804

Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP804 Worldwide Contacts www.tyco-fire.com Type D3S PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The Type D3S Protectospray Nozzles are open (non-automatic) directional

More information

Amerigear SF Spindle

Amerigear SF Spindle Amerigear SF Spindle Installation and Maintenance Manual Form No. 381-SH, 4/01 Spindle Installation and Maintenance Manual TABLE OF CONTENTS SECTION TITLE PAGE 1 Introduction...: 3 2 General Information...:

More information

Butterfly valves Figure 56 Installation & Maintenance Instructions

Butterfly valves Figure 56 Installation & Maintenance Instructions KEYSTONE Please read these instructions carefully This symbol indicates important messages and safety instructions. Hazard potentials: disregarding of instructions improper use of product insufficiently

More information

Geo-Prime Tank. Table of Contents. Installation, Operation & Maintenance Instructions AFCG1PT Revision: 7/3/14. Replacing a Pump 12

Geo-Prime Tank. Table of Contents. Installation, Operation & Maintenance Instructions AFCG1PT Revision: 7/3/14. Replacing a Pump 12 Geo-Prime Tank Installation, Operation & Maintenance Instructions AFCG1PT Revision: 7/3/14 Table of Contents General Description 3 Installation 4 Flushing and Purging 7 Initial Start-up 9 Replacing a Pump

More information

AEROMOTIVE Part # & Stealth Fuel Tank Sump INSTALLATION INSTRUCTIONS

AEROMOTIVE Part # & Stealth Fuel Tank Sump INSTALLATION INSTRUCTIONS AEROMOTIVE Part # 18651 & 18652 Stealth Fuel Tank Sump INSTALLATION INSTRUCTIONS CAUTION: Installation of this product requires detailed knowledge of automotive systems and repair procedures. We recommend

More information

1 of 7 12/18/2016 9:15 PM

1 of 7 12/18/2016 9:15 PM 1 of 7 12/18/2016 9:15 PM P0456-EVAP SYSTEM SMALL LEAK Special Tools: For a complete wiring diagram, refer to the Wiring Information. 2 of 7 12/18/2016 9:15 PM Theory of Operation 3 of 7 12/18/2016 9:15

More information

SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63

SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63 SPILL PREVENTION CONTROL AND COUNTERMEASURES PLAN (SPCCP) FOR FUELING AT STATION 63 The attached SPCC Plan contains introductory information, a description of facilities and practices employed to prevent

More information

PN9000 Series Pneumatic Actuators Installation and Maintenance Instructions

PN9000 Series Pneumatic Actuators Installation and Maintenance Instructions 3579049/14 IM-P357-29 CTLS Issue 14 PN9000 Series Pneumatic Actuators Installation and Maintenance Instructions PN9100 PN9200 1. Safety information 2. General product information PN9300 3. Installation

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Stay-put scuff guard helps to protect the dispensers from scratches and the breakaway during a drive-off event

Stay-put scuff guard helps to protect the dispensers from scratches and the breakaway during a drive-off event Product Bulletin UPDATE: Executive Orders VR-201 and VR-202 Revision Q Field Reattachable EVR Vapor Assist Healy-Style Safety Breakaway 09.24.14 The release of Executive Orders VR-201 and VR-202 Revision

More information

Model DF269 Control Valve

Model DF269 Control Valve Figure 1 DF269 Control Valve TABLE OF CONTENTS Introduction 2 Fail Open Actuator Disassembly 6 General 2 Body and Packing Reassembly 7 Scope 2 Fail Closed Actuator Resassembly 8 Specifications 3 Fail Open

More information

Filter. Table of Contents. Section 10. Filter NOTE: This section applies to applicators with an out-in filter.

Filter. Table of Contents. Section 10. Filter NOTE: This section applies to applicators with an out-in filter. Filter 10-1 Section 10 Filter NOTE: This section applies to applicators with an out-in filter. Table of Contents Filter...................................................... 10-1 Introduction................................................

More information