2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3.

Size: px
Start display at page:

Download "2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3."

Transcription

1 18-22 June 2006, Montreal, Canada Paper 06GM0613 Fault Current Limiters - Report on the Activities of Cigre WG A3.16 presented by: Heino Schmitt, Siemens AG on behalf of Cigre WG A3.16 heino.schmitt@siemens.com June 2006, Montreal, Canada Heino Schmitt,

2 Content Overview Fault Current Limitation State of the Art Application Questionnaire Protection Conclusion June 2006, Montreal, Canada Heino Schmitt,

3 Overview CIGRE WG Fault Current Limiters Established in members from 9 different countries Reports in Electra 2001 and 2003 Technical Brochure No. 239, 2003 Work finished and WG disbanded in June 2006, Montreal, Canada Heino Schmitt,

4 Overview Further work WG A3.16: Fault current limiters impact of different fault current limiting technologies on existing protection and new protection schemes 12 members from 9 different countries Report scheduled for June 2006, Montreal, Canada Heino Schmitt,

5 Fault Current Limitation R s L s i f ~ U 0 CB Fault Unlimited peak short-circuit current Peak let-through current Peak let-through current Rated current (max. load current) Prospective fault current with current interrupting without current interrupting Normal operation Short-circuit June 2006, Montreal, Canada Heino Schmitt,

6 State of the Art of Fault Current Limiters Characterisation Passive Fault Current Limiting Measures Passive: Increase of Impedance at Nominal and Fault Conditions (Example: Fault Current Limiting Reactor) Active Fault Current Limiters Active: Fast Increase of Source Impedance at Fault Conditions (Example: Superconducting Fault Current Limiter) With Current Interruption Without Current Interruption Self-triggered External-triggered June 2006, Montreal, Canada Heino Schmitt,

7 1 2 Distribution network Potential Application 3 Transmission network Distribution network SC-Cable 9 9 Distribution network 1 Generator feeder 2 Power station auxiliaries 3 Network coupling 4,5 Busbar coupling 6 Shunting current limiting reactor 7 Transformer feeder 8 Busbar connection / feeder 9 Combination with other SC devices, especially SC cables 10 Coupling local generating units 11 Closing ring circuits June 2006, Montreal, Canada Heino Schmitt,

8 Potential Application L June 2006, Montreal, Canada Heino Schmitt,

9 Potential Application RWE, Germany 110 kv application Coupling of 110 kv subgrids 380 kv 380 kv 380 kv A 110 kv B 110 kv 220 kv 220 kv 220 kv 380 kv June 2006, Montreal, Canada Heino Schmitt,

10 Questionnaire need for CIGRE Questionnaire 1996 location of up to 145 kv 11% above 145 kv 2% F e e d e r 1 5 % I n c o m i n g T r a n s f o r m e r 1 8 % I n c o m i n g G e n e r a t o r 1 5 % up to 36 kv 87% B u s T i e 5 2 % June 2006, Montreal, Canada Heino Schmitt,

11 Questionnaire CIGRE Questionnaire need for 10 % need at MV with restrictions 47 % need at MV without restrictions 21 % need at HV without restrictions 6 % need at HV with restrictions 26 % no need at all June 2006, Montreal, Canada Heino Schmitt,

12 Protection Principles Overcurrent protection (protection number 50/51) Distance protection (protection number 21) Directional protection (protection number 67) Differential protection (protection number 87) June 2006, Montreal, Canada Heino Schmitt,

13 Influence on Protection Systems Sensing transmission errors causing a difference between primary and secondary signals Pick-up distinction between load and fault currents Processing evaluation of measured values regarding magnitude, phase angle, etc. Co-ordination considering selectivity, sensitivity and reliability June 2006, Montreal, Canada Heino Schmitt,

14 Influence on Protection Systems Hardw are Relay AC S 1 D/D D/A D/D B1 B2 B3 T1 L L R L CT PT SC RTDS Simulation T2 G June 2006, Montreal, Canada Heino Schmitt,

15 Influence on Protection Systems Current (ka) 1 0 Trip Relay State Current (ka) 1 0 Trip Relay State Total Superconductor Shunt trip Normal Total Supe rconductor Shunt trip Normal in upstream of PT and CT in downstream of PT and CT June 2006, Montreal, Canada Heino Schmitt,

16 Protection Zones Case: inside 87 Protection zone Internal fault External fault Case: outside June 2006, Montreal, Canada Heino Schmitt,

17 Influence on Protection Systems June 2006, Montreal, Canada Heino Schmitt,

18 Conclusion characteristics introduce new system dynamics Standard testing procedures must be developed System protection must be investigated How to coordinate characteristic with existing protection schemes? New protection schemes are possible with for future systems Validated models for system simulation studies needed New materials for (e.g. Cryogenics) Utilities/users are not familiar with June 2006, Montreal, Canada Heino Schmitt,

19 Thank you for your attention Fault Current Limiters - Report on the Activities of Cigre WG A June 2006, Montreal, Canada Heino Schmitt,

CHAPTER 4 PROTECTION REQUIREMENTS

CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

Review paper on Fault analysis and its Limiting Techniques.

Review paper on Fault analysis and its Limiting Techniques. Review paper on Fault analysis and its Limiting Techniques. Milap Akbari 1, Hemal Chavda 2, Jay Chitroda 3, Neha Kothadiya 4 Guided by: - Mr.Gaurang Patel 5 ( 1234 Parul Institute of Engineering &Technology,

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

Tolerance-Based Time-Current Coordination

Tolerance-Based Time-Current Coordination S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background....

More information

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems Advanced Power Transmission Solutions Power Transmission and Distribution Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in Systems s Development of Power Markets Increasing

More information

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer Achieving Higher Short Circuit Current Ratings for Industrial Control Panels Standards & codes note 1 By Steve Hansen Sr. Field Engineer Introduction Articles 9.1 and. in the National Electrical Code require

More information

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Assembly Short-Circuit Current Ratings What Is A Short-Circuit

More information

Protective Device Coordination ETAP Star

Protective Device Coordination ETAP Star Protective Device Coordination ETAP Star Agenda Concepts & Applications Star Overview Features & Capabilities Protective Device Type TCC Curves STAR Short-circuit PD Sequence of Operation Normalized TCC

More information

Transformer Protection

Transformer Protection Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

EE042: Practical Power System Protection for Engineers & Technicians

EE042: Practical Power System Protection for Engineers & Technicians EE042: Practical Power System Protection for Engineers & Technicians EE042 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: This intensive course has been designed to give plant operators,

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

Item 1: Contents of the complete training & CV of the lecturer

Item 1: Contents of the complete training & CV of the lecturer Course DESIGN CONCEPTS + software SwitchgearDesign for SWITCHGEAR, SWITCHBOARDS, BUSDUCTS & SUBSTATIONS" Item 1: Contents of the complete training & CV of the lecturer Presented by Sergio Feitoza Costa

More information

Advanced Protective Relay Training

Advanced Protective Relay Training Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection

More information

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect

More information

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec Catalog HA 41.43 Edition 2018 Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear siemens.com/simosec Application Typical uses R-HA41-135.tif R-HA40-112.tif R-HA41-115.tif

More information

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction

More information

Switchgear and Distribution Systems for Engineers and Technicians

Switchgear and Distribution Systems for Engineers and Technicians Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Use of switch-fuse combinations at the medium-voltage level for the protection of distribution transformers siemens.com/tip-cs

Use of switch-fuse combinations at the medium-voltage level for the protection of distribution transformers siemens.com/tip-cs Technical Series Edition 2 Use of switch-fuse combinations at the medium-voltage level for the protection of distribution transformers siemens.com/tip-cs 1. Basis Medium-voltage distribution transformers

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E. MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E

More information

4. CIRCUIT BREAKERS (Continued)

4. CIRCUIT BREAKERS (Continued) 4. CIRCUIT BREAKERS (Continued) 4.3 Other Characteristics of a circuit breaker: Familiarity with the following less-important characteristics of LV circuit breakers is, however, often necessary when making

More information

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection ABB AG - EPDS Ultra-Fast Earthing Switch UFES active internal arc protection Agenda Arc fault Protection concepts Ultra-Fast Earthing Switch type UFES Principle Components Differentiation of protection

More information

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY WHAT IS SELECTIVITY? Selectivity in mean of protective devices is also called by other terms as discrimination or coordination of protective devices. To

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Multi-purpose percentage restraint differential protection

Multi-purpose percentage restraint differential protection Multi-purpose percentage restraint Page 1 Issued June 2002 Changed since June 1999 Data subject to change without notice (SE970169) Features Complete phase and earth fault protection for generators, motors,

More information

Industry Automation Control Components

Industry Automation Control Components Industry Automation Control Components SIRIUS 3RV2 Motor Starter Protectors SIRIUS 3RV21 Motor Starter Protectors can be easily and flexibly combined with other SIRIUS devices to reduce space requirements

More information

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000

More information

OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS Abstract According to the standards, an overcurrent is a current which exceeds its rated value. Overcurrents can arise in different modalities, depending

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

MITIGATE ARC EFFECTS WITHIN AN E-HOUSE

MITIGATE ARC EFFECTS WITHIN AN E-HOUSE MITIGATE ARC EFFECTS WITHIN AN E-HOUSE Jérôme DOUCHIN Anthony BROWN Juha RINTALA Schneider Electric France Schneider Electric Singapore Schneider Electric Finland Jerome.douchin@ Anthony.brown@ juha.rintala@

More information

Power Systems Trainer

Power Systems Trainer Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,

More information

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Robert P. Hansen, P.E., PhD GE Specification Engineer Introduction Switchboards are a widely used type of equipment

More information

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR FEBRUARY 14, 2001 REVISION 3 Publication: SE-125-M Document: S95-C125-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

XT IEC Power Control Manual Motor Protectors

XT IEC Power Control Manual Motor Protectors May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted

More information

That s how compact transformer protection is today. The customer newsletter of Kries-Energietechnik

That s how compact transformer protection is today. The customer newsletter of Kries-Energietechnik The customer newsletter of Kries-Energietechnik www.kries.com A change of paradigm in distribution network transformer protection: the self-powered and IEC 60255-compliant IKI-35 protection relay 05 17

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

MESG 12 / 17.5 / 24 / 36 KV

MESG 12 / 17.5 / 24 / 36 KV MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL

More information

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable www.siemens.com/medium-voltage-switchgear Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.43 2012 Answers for infrastructure and cities. Neue Bilder

More information

B4 Load Break Switch CONTENTS

B4 Load Break Switch CONTENTS B4 Load Break Switch CONTENTS B4-02 Load Break Switch LBS Load Break Switch B4-03 VITZROTECH Load Break Switch is a product developed from the previous model E3-Class and manufactured based on the 100A

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Motor settings using the SIPROTEC Compact motor protection relay 7SK80 is explained below. Information is given on how to

More information

Superconducting Fault Current Limiters as New Devices for Distribution Installations

Superconducting Fault Current Limiters as New Devices for Distribution Installations 1/6 Title Superconducting Fault Current Limiters as New Devices for Distribution Installations Registration Nº: (Abstract) Summary Superconducting fault current limiters (SFCLs) as versatile devices are

More information

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram:

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram: Question Set(2017) Switch Gear & protection(5 th SEm) 1. What is fault in power system? Classify the fault. What are the bad effects of fault? 2. Define with example: Symmetrical fault and unsymmetrical

More information

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A) M6 24kV Medium Voltage Switchgear MetalEnclosed (LSC2A) GENERAL FEATURES GENERAL DESCRIPTION The structure of the cubicles, of considerable strength, has selfsupporting structure and is made of steel sheet

More information

SF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1

SF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1 SF 6 gas insulated RMU SafePlus 24 kv 25.03.2010 SafePlus 24 kv SF6 gas insulated RMU 1 Secondary distribution 400 kv Transmission substation Transformer 40-70 kv 130 kv Main Substation Secondary distribution

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Evaluating Selective Coordination Between

Evaluating Selective Coordination Between Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current- Limiting Circuit Breakers selective coordination note 1 By Steve Hansen Sr. Field Engineer and Robert Lyons Jr. Product

More information

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

OVERALL LENGTH (B)  ( mm)  ( mm)  ( mm)  ( mm) 1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165

More information

Recommended Procedures

Recommended Procedures Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that

More information

AutoLink Frequently Asked Questions

AutoLink Frequently Asked Questions Rev. 3 October 2013 Page 1 of 8 AutoLink Frequently Asked Questions October 2013 1 Rev. 3 October 2013 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the AutoLink Single Phase Electronic Sectionalizer?...

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

4-Day Power System Analysis, Coordination, System Studies

4-Day Power System Analysis, Coordination, System Studies 4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our

More information

Protection and control VIP30, VIP35. Relays technical manual

Protection and control VIP30, VIP35. Relays technical manual Protection and control VIP30, VIP35 Relays technical manual contents 1. presentation of the VIP30 and VIP35...3 2. use and settings...4 3. sensors and operating ranges... 4. connection scheme...9 5. assembly

More information

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing

More information

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Totally Integrated Power SIMOSEC Catalog HA 41.43 Edition Sept. 2014 Answers for infrastructure and cities. Neue

More information

Motor Protection Circuit Breakers 3VU13 and 3VU16

Motor Protection Circuit Breakers 3VU13 and 3VU16 Motor Protection Circuit Breakers 3VU13 and 3VU16 3VU13/3VU16 is suitable for use in fuseless motor feeders upto 11KW/22KW (25A/63A) respectively. 3VU motor protection circuit breakers are used for protection

More information

Source-Side Fuse/Load-Side Recloser Coordination

Source-Side Fuse/Load-Side Recloser Coordination How to Coordinate ransformer Primary-Side Fuses with Feeder Reclosers Using Coordinaide M he S&C Protection and Coordination Assistant Part I: Conservative Method his is the first in a series of articles

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

Selective Coordination Enforcement:

Selective Coordination Enforcement: Selective Coordination Enforcement: Overcurrent Protective Device Basics by Tim Crnko The Basics of Selective Coordination Merely having a higher ampere overcurrent protective device (OCPD) feeding a lower

More information

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are

More information

Noxon Rapids Reactor Project. Scott Wilson June 9, 2016 Tracy Rolstad

Noxon Rapids Reactor Project. Scott Wilson June 9, 2016 Tracy Rolstad Noxon Rapids Reactor Project Scott Wilson June 9, 2016 Tracy Rolstad Voltage Performance at Noxon (ALIS) 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear ENGINEERING SERVICES 809 Gleneagles Court, Suite 309; Towson, MD 21286 Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear Prepared by: Keith Robertson, PE Staff Power

More information

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Mining The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Reprint Authors: Kurt Tischler Siemens AG, Mining Technologies, Erlangen, Germany Reprint: WORKSHOP SAG

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristic Rated currents I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SX2

More information

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). FUSE CATALOG 2 Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). TYPE DESCRIPTION CAT PAGE 15K-1 UNIVERSAL TYPE FUSE LINK 2066A1 38K-1 UNIVERSAL TYPE FUSE LINK 2070A1 15K-2 UNIVERSAL

More information

ABB Automation & Power World: April 18-21, 2011 WPO MV outdoor products for smart grid demands. ABB Inc. April 19, 2011 Slide 1

ABB Automation & Power World: April 18-21, 2011 WPO MV outdoor products for smart grid demands. ABB Inc. April 19, 2011 Slide 1 ABB Automation & Power World: April 18-21, 2011 WPO-123-1 MV outdoor products for smart grid demands ABB Inc. April 19, 2011 Slide 1 WP0-123-1 MV outdoor products for smart grid demands Speaker name: Speaker

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: SIEMENS AG DF CP R&D VC 2 WERNER-VON-SIEMENS-STRASSE 48 92224 AMBERG, GERMANY This is to certify that representative samples of Combination Motor Controllers (See following pages for additional

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

Targeted Application of STATCOM Technology in the Distribution Zone

Targeted Application of STATCOM Technology in the Distribution Zone Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric

More information

Superconducting Cable Systems for Urban Areas AmpaCity Project - Germany

Superconducting Cable Systems for Urban Areas AmpaCity Project - Germany Superconducting Cable Systems for Urban Areas AmpaCity Project - Germany Frank Schmidt Frank.Schmidt@Nexans.com 2016 IEEE PES General Meeting Agenda Project overview Motivation for HTS cables Components

More information

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers Evaluating Selective Coordination Between And Non Current-Limiting Circuit Breakers Tech Topics: Selective Coordination Note 1, Issue 1 Steve Hansen Sr. Field Engineer Robert Lyons Jr. Product Manager

More information

Technical data for manual motor starters Type MS325

Technical data for manual motor starters Type MS325 for manual mor starters Type MS325 General data Rated voltage 600 V Rated current 25 A (14 setting ranges, 0.1 25A) Rated frequency 50-60 Hz Electrical and mechanical life endurance 100,000 operations

More information

Shippensburg University

Shippensburg University Shippensburg University 1871 Old Main Drive Shippensburg, PA 17257 SUPPLEMENT 1 Electrical Coordination Study Professional: Entech Engineering, Inc. 4 South Fourth Street P.O. Box 32 Reading, PA 19603

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

PROTECTION AND CONTROL

PROTECTION AND CONTROL B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter

More information

Cascading & Discrimination

Cascading & Discrimination Cascading & Discrimination Typical LV System Level 1 ACBs - 6300A General LV Switchboard Level 2 ACB - 3200A MCCB 3200A Level 3 MCCB 1250A Fuses 630A Switchboard, Panelboard or MCC Level 4 MCBs - 100A

More information

Circumstances affecting the protection against electrode potential rise (EPR)

Circumstances affecting the protection against electrode potential rise (EPR) Ŕ periodica polytechnica Electrical Engineering 53/1-2 (2009) 79 83 doi: 10.3311/pp.ee.2009-1-2.10 web: http:// www.pp.bme.hu/ ee c Periodica Polytechnica 2009 Circumstances affecting the protection against

More information

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489 MINIATURE CIRCUIT BREAKERS SU200M Datasheet Branch protection acc. to CSA C22.2 No.5 / UL 489 The miniature circuit breaker SU200 M is ABB s solution for UL 489 branch circuit protection up to 480 Y/277

More information

What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018

What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018 What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018 Before we start A Penny for Your Thoughts At the end of the session, share your feedback via

More information

Catalogue March InLine II - ZLBM/ZHBM Fuse Switch Disconnector

Catalogue March InLine II - ZLBM/ZHBM Fuse Switch Disconnector Catalogue March 2015 InLine II - ZLBM/ZHBM Fuse Switch Disconnector 2 1SEC312022B0202 ABB Catalogue Contents Introduction 1 Apparatus 2 Accessories 3 Technical Data 4 Cable terminations and cable shrouds

More information

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues Designing and Maintaining a Pollution-Resilient Electric Power System Tom McDermott IEEE/PES T&D Conference April 21-24, 2008 Chicago, IL Managing Pollution Issues Define the metrics, and measure them

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Solar Power Switchgear & Energy Storage Renewable Energy Systems 7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH

More information

Modular medium-voltage switchgear. NorMax

Modular medium-voltage switchgear. NorMax Modular medium-voltage switchgear NorMax NorMax MODULAR MEDIUM-VOLTAGE SWITCHGEAR 2 NorMax Modular medium-voltage switchgear Contents Subject Page Table of contents 2 Introduction and main features 2 Technical

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J Protection Equipment Siemens AG 2015 Click on the Article No. in the catalog PDF to access it in the Industry Mall and get all related information. Article-No. 3RA1943-2C 3RA1943-2B 3RA1953-2B 3RA1953-2N

More information

Manual motor starters Overview and benefits

Manual motor starters Overview and benefits Manual motor starters Overview and benefits ABB offers a complete standard motor-protection concept for the world market IEC motor branch protection UL type E/F Motor applications with fuseless protection

More information

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT Fusing Equipment Kearney Fuse Links Electrical Apparatus K-SEC 030 GENERAL Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment.

More information