OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

Size: px
Start display at page:

Download "OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS"

Transcription

1 OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

2 Abstract According to the standards, an overcurrent is a current which exceeds its rated value. Overcurrents can arise in different modalities, depending on whether they are the result of an overload or a short-circuit. While the former is a normal situation for an electrical circuit, the latter occurs after a negligible impedance fault between two points of the circuit where there is a voltage in ordinary operating conditions. One of the features that must be carefully evaluated when choosing a UPS is its capability to properly withstand a short circuit current on its output for a certain amount of time. This capability depends on whether the output short circuit current is withstood solely by the inverter or by the source through the static bypass. In the first case the capability strictly depends on the UPS design, while in the second it also depends on the source prospective short circuit current (named Icp). The Icp is independent of the UPS and, because of its electrodynamic and thermal effects on the components, in some cases it is appropriate to define its limits and/or to implement particular solutions which allow limiting its extent within the UPS or the entire site. However, in other cases limiting the prospective short circuit current is necessary in order to stay within the limits of the protective devices downstream the UPS. All the choices mentioned above risk negatively affecting the short circuit current that the electrical distribution downstream the UPS requires to guarantee the correct coordination between the various site protective devices. Therefore you need to take into consideration how the maximum source-icp can be mitigated by the UPS while operating in double conversion mode. The aims of this white paper are to clarify the concept of prospective short circuit current bearable by the UPS, to explain the role of fuses and to indicate the requirements of the international standard IEC

3 Devices run across by short circuit current and their sizing Throughout the current path, between the bypass input and the UPS output, there are various components and devices which are run across by short circuit current. Among these we can mention cables, switching devices, static devices (named SCR after the acronym of Silicon Controlled Rectifiers ) and possible fuses (Figure1). Their sizing indirectly fixes a limit to the maximum perspective short circuit current of the source. There are mainly two guidelines for this sizing: 1. Protect as many devices as possible while accepting to penalize the maximum output current; 2. Achieve the maximum output current possible while accepting that the fault may spread over more than one device, but still guaranteeing their insulation. Maintenance Bypass QS3 Static Switch U1, V1, W1 QS2 Rectifier Inverter U, V, W QS1 QS4 U2, V2, W2 Battery converter N Battery N Figure 1: UPS block diagram. Short-circuit current effects Short-circuit current effects are both electro-dynamic and thermal. The thermal effects consist of heat dissipation over the conductors by Joule effect and, as short-circuit currents are much higher than rated current, the component overheats and degrades. On the contrary, the electro-dynamic effects are attractant or repulsive mechanical actions between the components and are function of the square of the current peak. Depending on the prospective short-circuit current of the source (Icp), the current peak value must be evaluated according to Table 7 of the international standard CEI EN here below: Up to a Icp 10kArms, Ipk max = 1.7 x Icp Up to a Icp 20kArms, Ipk max = 2.0 x Icp Up to a Icp 50kArms, Ipk max = 2.1 x Icp Up to a Icp 100kArms, Ipk max = 2.2 x Icp 3

4 High speed fuses When there is the need for maximum device protection, it is necessary to use high speed fuses, which are capable of limiting the prospective short circuit current peak whenever it rises above a certain level. Figure 2 portrays the curve of some high speed fuses which show the feature mentioned above. For example, the 1000 A fuse does not limit the maximum current peak up to the prospective short-circuit current of 5 ka, while above 5 ka the value gradually reduces so that in case the prospective short circuit current value is 100 ka it becomes equal to 31 ka only. If a UPS with a rated current of 1000 A is paired with a 1000 A high speed fuse, the UPS itself could be compatible with a source prospective short-circuit current of 45 ka if the peak current limit of the static bypass devices is higher than 24 ka, while it could be compatible with 100 ka if the peak current limit of the static bypass devices is higher than 31 ka. If the same UPS was paired with a 1250 A high speed fuse and the maximum peak current limit was still 31 ka, it could be compatible with a source prospective shortcircuit current of about 50 ka maximum, and not 100 ka as in the case of the 1000 A fuse. The use of high speed fuses inevitably reduces the current peak and its duration (which is usually some ms long), therefore the selectivity downstream can be accomplished for the short-circuit only by using some more high speed fuses or electromechanical devices, which are also capable to open the circuit with characteristics dependent on the I 2 t value. In these two cases the current peak will be mainly limited by the high speed fuses downstream of the device. How to increase the short-circuit current As fuses are not resettable after they intervene and Service intervention to replace them is always required, a valid solution to achieve a higher short-circuit current is to increase the fuse size at the expense of SCR protection Im = 2.3 Ip 1400 A 1250 A 1100 A Max peak let trhu current (Im) (A) A 900 A 800 A 700 A 630 A 550 A 500 A e + 06 Available current in RMS symmetrical amperes (Ip)(A) Figure 2: Short-circuit current peak limitation of a typical commercial high speed fuse 4

5 In this scenario, in the rare case of a short circuit taking place right at the UPS output, both fuses and SCR will need to be replaced. For example, if a 1400 A fuse is used then the maximum current peak becomes about 45 ka while the prospective short-circuit current is approximately equal to 100 ka; it is then clear that both the peak value and the I 2 t value are increased, but both values remain much lower than the maximum current peak value with no fuses, which is approximately equal to 220 ka in the worst case. Manual bypass short-circuit current The maximum current peak value without fuses, equal to 220 ka in the example above, is the value to be considered for any possible manual bypass, be it inside or outside the equipment, as a manual bypass is not typically protected by fuses. In this scenario it is the very switch, with its typical short-circuit withstand current (called Icw), to fix the limit of the maximum prospective short circuit current: when it is lower than the static bypass short circuit current It becomes the limit for the entire installation / site. In case of systems with a prospective current higher than the switch Icw, then one of the two following solutions is needed: yadding fuses on the manual bypass; yadding an inductance in series with the source whose value may be enough to lower the maximum prospective short-circuit current to the desired value. The inductances mentioned above are typically realized in the air, in order to avoid their saturation in short-circuit conditions. Their presence upstream of the UPS can give the opportunity to reconsider the static bypass fuse sizing as well. Short-circuit current in a parallel UPS system In those situations in which there are more UPS connected in parallel, once again considering just the short-circuit-tothe-output of the parallel system, the maximum prospective short-circuit current of the source may be considered equal to about 80% of that of the single UPS multiplied by the number of UPS in the parallel system (without considering any redundancy). 80% is a safety margin which takes into consideration that there can be a short-circuit current imperfect distribution due to asymmetries in the equipment connections both at the bypass input and at the system output. These asymmetries have always to be taken into consideration when balancing the UPS static bypasses in nominal operating conditions, in order to keep them within a 10% range. If the site layout does not allow symmetry between the bypass input and UPS output connections, solutions have to be implemented in order to compensate for these deviations. In case inductances are chosen as a solution, they must not saturate in a short circuit scenario. International standard IEC The international standard IEC :2008 (EN : ) was published in 2008 under the name Uninterruptible Power Systems (UPS) - Part 1: General and Safety Requirements for UPS. In September 2011 it replaced the first editions of IEC and IEC , published in This standard applies to UPS units which are movable, stationary, fixed or for building-in, for use in low-voltage distribution systems and intended to be installed in any operator accessible area or in restricted access locations as applicable. Amendment IEC :2008/A1:2013 (Date of publication, DOP) must be taken into consideration mandatorily by law, in addition to the original standard as of 14/02/2016 (Date of withdrawal, DOW) in order to assess UPS safety conformity through harmonized standards. This amendment introduces requirements to the UPS output short-circuit withstand current. In particular, it forces the manufacturers to guarantee a minimum value depending on the UPS rating. Important final note When talking about prospective short-circuit current, considering only the source can be penalizing because the softening action carried out by the impedance of the connection between source and bypass input would be left out. The above mentioned impedance depends both on the distance between source and UPS, and, above all, on the connection type, (i.e. if this is made with a low impedance busbar or with cables). In the latter scenario, the way in which cables are arranged into the support conduit is another factor to be taken into consideration because it could cause significant impedance depending on the specific solution implemented. Therefore, the declared UPS performance has to be intended as a prospective short-circuit current available to the bypass input. 5

6 Conclusion With this whitepaper the concept of prospective short-circuit current withstand capability has been clarified for both a single UPS and a parallel system, by illustrating the role of fuses and by giving an indication about what the IEC international standard requirements are. All the topics above are important because one of the features to be carefully evaluated when choosing a UPS is its capability to bear a short circuit current to its output properly for a certain amount of time. 6

7 Notes: 7

8 VertivCo.com Emerson Network Power Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB Vertiv Co. All rights reserved. Vertiv, the Vertiv logo, and Vertiv Liebert UPS are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

ACTIVE ECO MODE IN SINGLE-PHASE UPS. Miguel Rascon AC Power Senior Product Manager

ACTIVE ECO MODE IN SINGLE-PHASE UPS. Miguel Rascon AC Power Senior Product Manager ACTIVE ECO MODE IN SINGLE-PHASE UPS Miguel Rascon AC Power Senior Product Manager Abstract Environmental protection, high efficiency and energy savings are nowadays popular topics of discussion and, as

More information

HIGH EFFICIENCY MODES OF OPERATION. Path toward highest energy efficiency without load availability trade-off

HIGH EFFICIENCY MODES OF OPERATION. Path toward highest energy efficiency without load availability trade-off HIGH EFFICIENCY MODES OF OPERATION Path toward highest energy without load availability trade-off Valerio Zerillo, Large Power Offering Manager Stephen Major, Large Power Offering Manager TWO STAGE POWER

More information

Active ECO Mode in Single-Phase UPS. By Miguel Rascon AC Power Senior Product Manager

Active ECO Mode in Single-Phase UPS. By Miguel Rascon AC Power Senior Product Manager Active ECO Mode in Single-Phase UPS By Miguel Rascon AC Power Senior Product Manager Abstract Environmental protection, high efficiency and energy savings are nowadays popular topics of discussion and,

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT

SITE PLANNING DATA LIEBERT EXM 3-PHASE UPS: KVA/KW, 60HZ, VAC, SINGLE INPUT SITE PLANNING DATA LIEBERT EXM 3-PHASE : 10-100KVA/K, 60HZ, 208-480VAC, SINGLE INPUT MAINTENANCE BYPASS CABINET Busbar * System 3 ire + GND BIB MBB MIB Note 6 AC 208V 4 ire + GND Static Bypass Local Grounding

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer Achieving Higher Short Circuit Current Ratings for Industrial Control Panels Standards & codes note 1 By Steve Hansen Sr. Field Engineer Introduction Articles 9.1 and. in the National Electrical Code require

More information

Protistor size 14x51 ar 690VAC (IEC) / 700VAC (UL)

Protistor size 14x51 ar 690VAC (IEC) / 700VAC (UL) 690VAC (IEC) / VAC (UL) Protistor size 14x51 ar 690VAC (IEC) / VAC (UL) SEMICONDUCTOR PROTECTION FUSES IEC HIGH-SPEED CYLINDRICAL FUSE-LINKS AC PROTECTION FEATURES & BENEFITS Low l²t for improved semiconductor

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/ Galaxy VX Technical Specifications 12/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this

More information

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS Transformer-free. High Efficiency, Scalable On-line UPS LIEBERT Liebert NX NX TM TM UPS 250-250kVA 1000-1000kVA Facility managers continue to face the increasing outlay of energy consumption and the call

More information

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration

More information

Protistor size 70 gr 690VAC (IEC)

Protistor size 70 gr 690VAC (IEC) Protistor size 70 gr SEMICONDUCTOR PROTECTION FUSES SQUARE BODY HIGH-SPEED FUSE-LINKS AC PROTECTION FEATURES & BENEFITS Excellent cycling capability Multiple body sizes and terminals or blades combination

More information

BS : C&G 2382 Outcomes 4

BS : C&G 2382 Outcomes 4 BS7671 2008: C&G 2382 Outcomes 4 Outcome 4 Protection for safety The candidate will be able to: 4.1 Identify the differences between basic and fault protection 4.2 State means of protection against electrical

More information

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E. MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E

More information

Leadership in fusible circuit protection

Leadership in fusible circuit protection Bussmann series High speed fuse application guide Leadership in fusible circuit protection SERIES Eaton is the leading source of fusible circuit protection solutions in the global marketplace. Eaton s

More information

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery Application Guide Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery Bulletin Numbers 280, 281, 284, 290, 291 Topic Introduction 2 Background 2 ArmorStart

More information

Selective Coordination Enforcement:

Selective Coordination Enforcement: Selective Coordination Enforcement: Overcurrent Protective Device Basics by Tim Crnko The Basics of Selective Coordination Merely having a higher ampere overcurrent protective device (OCPD) feeding a lower

More information

Liebert. APS UPS 5-20 kva Flexible, efficient scalable UPS for room or row-based applications

Liebert. APS UPS 5-20 kva Flexible, efficient scalable UPS for room or row-based applications Liebert APS UPS 5-20 kva Flexible, efficient scalable UPS for room or row-based applications LIEBERT APS, 5-20 KVA UPS A Scalable Power Solution for Dynamic Demands Provide mission-critical availability

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics 450 TO 700VAC / 63 TO 2800A Recognized Exceptionally low I 2 T, Watt losses. Non-magnetic construction, Highly reliable low voltage Trip-indicator system, conformity to UL, IEC, DIN

More information

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect

More information

Earthing Principles. Symmetra PX 250/500 kw

Earthing Principles. Symmetra PX 250/500 kw Earthing Principles Symmetra PX 250/500 kw Table of Contents Earthing Principles... 1 Decoding the Earthing Types... 1 TN Systems... 2 Characteristics... 2 Reference to IEC/EN 60364-4-41 413.1.3... 2

More information

High Speed Fuses. Section Contents Page

High Speed Fuses. Section Contents Page Section Contents Page General pplications.......................1-13 North merican fuses & accessories...........1-11 DFJ - High speed Class J fuse.................. 15 Square ody fuses & accessories............

More information

NetSure 5100 ORDERING GUIDE. 48V & 24V DC Power System (40 A to 600 A)

NetSure 5100 ORDERING GUIDE. 48V & 24V DC Power System (40 A to 600 A) NetSure 5100 ORDERING GUIDE 48V & 24V DC Power System (40 A to 600 A) NETSURE 5100 ORDERING GUIDE Description The NetSure 5100 Series, a compact -48 volt 600 A DC power solution, features an advanced control

More information

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers 250-800kVA Liebert NX Enterprise-Scale UPS Protection For Medium And Large Data Centers Efficiency. Availability. Capacity. Control. Facility managers continue to face the increasing cost of energy consumption

More information

Semiconductor Fuses European Fuses

Semiconductor Fuses European Fuses 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos

More information

onlinecomponents.com

onlinecomponents.com 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers 1.General The design of rectifier equipment requires specific provisions in the switchgear for the protection of power semiconductor

More information

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF Manuel d installation Installation manual Part. LE05733AA-07/12-01 GF Index 1 Introduction 18 2 Conditions for use 19 3 Installation 20 4 Visual and acoustic warning signals 22 5 ups diagnostic software

More information

Est DCM Double Conversion Module 400kVA - 800kVA

Est DCM Double Conversion Module 400kVA - 800kVA Est.1968 DCM Double Conversion Module 400kVA - 800kVA The parallel operation of converters for increased output power or redundancy is commonplace but poses problems for large systems. A new approach is

More information

2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3.

2006 IEEE PES General Meeting June 2006, Montreal, Canada Paper 06GM0613. Fault Current Limiters - Report on the Activities of Cigre WG A3. 18-22 June 2006, Montreal, Canada Paper 06GM0613 Fault Current Limiters - Report on the Activities of Cigre WG A3.16 presented by: Heino Schmitt, Siemens AG on behalf of Cigre WG A3.16 heino.schmitt@siemens.com

More information

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw DELPHYS GP Green Power 2.0 range 160 to 1000 kva/kw OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application.

More information

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents HHM High Voltage Fuses Motor Circuit Protection DIN and British Standard SIBA Motor Rated Fuses are available in - German DIN Standard and - British Standard Design The large variety in body sizes / mounting

More information

GBPC15,25,35- Series. Features: Page <1> 10/08/10 V1.1

GBPC15,25,35- Series. Features: Page <1> 10/08/10 V1.1 Features: Plastic material. Integrally moulded heatsink provide very low thermal resistance for maximum heat dissipation. Surge overload ratings from 300 to 400 amperes. Terminals solderable per MIL-STD-202,

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers Evaluating Selective Coordination Between And Non Current-Limiting Circuit Breakers Tech Topics: Selective Coordination Note 1, Issue 1 Steve Hansen Sr. Field Engineer Robert Lyons Jr. Product Manager

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

Application Guide Effective June Protecting semiconductors with high speed fuses

Application Guide Effective June Protecting semiconductors with high speed fuses pplication Guide 10507 Effective June 2016 Protecting semiconductors with high speed fuses Contents : Introduction 3 bout this guide 3 Background 3 Typical fuse construction 3 Fuse operation 4 Power semiconductors

More information

Electrical Measuring Instruments

Electrical Measuring Instruments UNIT 12 Electrical Measuring Instruments Learning Objectives After studying this unit, the student will be able Understand different measuring instruments used in electricity Understand the working of

More information

Features. Figure 1. EFIL-28 Connection Diagram

Features. Figure 1. EFIL-28 Connection Diagram Description The EFIL-28 Module is an EMI Filter designed for use with Calex DC/DC Converters. Built in a 1/2 brick package for systems with 24VDC and 28VDC nominal input, the EFIL-28 module can provide

More information

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY

NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY WHAT IS SELECTIVITY? Selectivity in mean of protective devices is also called by other terms as discrimination or coordination of protective devices. To

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN APPLICATION The KNK capacitors are used for power - factor correction of inductive consumers (transformers, electric motors, rectifiers) in industrial networks for voltages of up to 660 V. DESIGN Cylindrical

More information

Miniature & Moulded Case

Miniature & Moulded Case Miniature & Moulded Case MCB OPERATION MAGNETIC OPERATION The short time protection (typically less than 1 second after energising) of the MCB is defined as the magnetic operation. 1 2 3 THERMAL OPERATION

More information

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC Manufacturer s declaration in accordance with 8- Frame Model catalogue reference 93PS-XX(20)-YY- 93PS-XX(40)-YY- Number of power modules (UPM) 1 1 or 2 Number of internal batteries 0 to 2 x 32 blocks 0

More information

Evaluating Selective Coordination Between

Evaluating Selective Coordination Between Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current- Limiting Circuit Breakers selective coordination note 1 By Steve Hansen Sr. Field Engineer and Robert Lyons Jr. Product

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

Limitor -G General Purpose Fuses

Limitor -G General Purpose Fuses Limitor -G General Purpose Fuses HIGH VOLTAGE IEC FUSES DIN HV GENERAL PURPOSE FUSES FOR TRANSFORMERS FEATURES & BENEFITS Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear

More information

Selective Coordination

Selective Coordination Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings

More information

Green Power 2.0 MASTERYS GP

Green Power 2.0 MASTERYS GP Green Power 2.0 MASTERYS GP 60 to 120 kva/kw OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application.

More information

Liebert Hipulse E The High-ECO-Availability UPS. AC Power Systems

Liebert Hipulse E The High-ECO-Availability UPS. AC Power Systems Liebert Hipulse E The High-ECO-Availability UPS AC Power Systems We re Emerson Network Power, backed by Emerson, a global company that brings technology and engineering together to provide innovative solutions

More information

Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors.

Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors. Date: 30.05.2005 Page 1 Surge Current, I 2 t Value and Short - Circuit Protection of High Power Semiconductors. According to DIN IEC 60747 the maximum rated surge current is the maximum allowable non periodical,

More information

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake Data sheet CI-tronic Soft Start Motor Controller Type MCI 25B with Brake MCI 25B motor controller with brake is designed for soft starting and braking of 3 phase AC motors. The digital controlled soft

More information

Technical Section: Miniature Circuit Breakers

Technical Section: Miniature Circuit Breakers MCBs and Accessories Data. Calibration With CBI Hydraulic- Magnetic Miniature Circuit Breakers, there is no effect on the fixed trip point at ambient temperature ranges from -5 C to +60 C. 2. Products

More information

NH fuse-links am 690VAC top indicator/live tags size 4, 4a

NH fuse-links am 690VAC top indicator/live tags size 4, 4a NH fuse-links am 69VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions according to DIN 43 62 parts 1 to 4 Non-isolated gripping lugs Double indicator Lead free contact blades %

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

C&D VRLA Batteries Extended Run Time for Small UPS Machines

C&D VRLA Batteries Extended Run Time for Small UPS Machines TECHNICAL BULLETIN 41-7954 C&D VRLA Batteries Extended Run Time for Small UPS Machines 41-7954/0112/CD www.cdtechno.com Small UPS machines, in the range of 400 to 2500 VA, are typically used to provide

More information

Implementation of low inductive strip line concept for symmetric switching in a new high power module

Implementation of low inductive strip line concept for symmetric switching in a new high power module Implementation of low inductive strip line concept for symmetric switching in a new high power module Georg Borghoff, Infineon Technologies AG, Germany Abstract The low inductive strip line concept offers

More information

Adapted from presentation developed by Scott Fausneaucht

Adapted from presentation developed by Scott Fausneaucht Adapted from presentation developed by Scott Fausneaucht Definition of Electricity Electrical Fundamentals Generation & Transmission Transformers Fuses & Circuit Breakers Motors Motor Controls Safety Not

More information

CI-TI Contactors - VLT Frequency Converters

CI-TI Contactors - VLT Frequency Converters MN.90.K1.02 - VLT is a registered Danfoss trademark 1 Description This data sheet is based on tests made in co-operation with Contactor Business from Danfoss Automatic Division and Danfoss Drives A/S.

More information

Lab Electrical Power Engineering I

Lab Electrical Power Engineering I INSTITUT FÜR ELEKTRISCHE MASCHINEN RHEINISCH-WESTFÄLISCHE TECHNISCHE HOCHSCHULE AACHEN Lab Electrical Power Engineering I Test 3: Induction machine with squirrel cage rotor and slip ring rotor 1 Experiment

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090529 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW Line/Load Reactors are components designed to improve the

More information

NEOZED D0 fuse-links gg 400/440VAC

NEOZED D0 fuse-links gg 400/440VAC NEOZED D0 fuse-links gg 400/440VAC LOW VOLTAGE IEC FUSES DIN LV FUSE-LINKS D0 FEATURES & BENEFITS The D0 fuse-system is installed in low voltage distribution units, where fuse-links are accessible to non

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

FUSE: SAFE & RELIABLE

FUSE: SAFE & RELIABLE FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Common Bus and Line Regeneration

Common Bus and Line Regeneration Common Bus and Line Regeneration Addressing VFD applications when Regenerative Energy is Present Steve Petersen, Drives Technical Training Yaskawa America, Inc. Variable frequency drives (VFDs) are implemented

More information

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems FUSERBLOC CD The universal Fuse Combination Switch FROM 20 TO 1250 A SOCOMEC GROUP SWITCHING PROTECTION & UPS Industrial Switching & Protection Systems SWITCHING FUSERBLOC CD THE UNIVERSAL FUSE COMBINATION

More information

FUSE TECHNOLOGY Ambient temperature

FUSE TECHNOLOGY Ambient temperature This fuse technology guide will discuss basic fuse operating, application, and selection criteria concepts. The intended purpose of this section is to aid designers with the operation and characteristics

More information

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors Fuse monitoring possible throughout Busbar supports can be

More information

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph

10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph VEGA INDUSTRIAL UNINTERRUPTIBLE POWER SUPPLY 10 20KVA 3Ph/1Ph 10 120KVA 3Ph / 3Ph - 6 pulse SCR rectifier - IGBT inverter - Power output transformer - Low and stable ripple on battery for the highest battery

More information

NH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3

NH fuse-links gg 400VAC double indicator/live gripping-lugs size 000, 00, 1, 2, 3 NH fuse-links gg 4VAC double indicator/live gripping-lugs size,, 1, 2, 3 NH fuse-links gg 4VAC double indicator/live gripping-lugs size,, 1, 2, 3 LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS

More information

Recommended Procedures

Recommended Procedures Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that

More information

NH Solid Blades 690 VAC sizes 000 to 3

NH Solid Blades 690 VAC sizes 000 to 3 NH Solid Blades 6 VAC sizes 000 to gs-class Protistor NH 6 VAC fuse-links provide maximum flexibility in equipment design and ultimate protection for today s power conversion equipment. This range is a

More information

NH fuse-links am VAC with striker, size 0, 1, 2, 3, 4

NH fuse-links am VAC with striker, size 0, 1, 2, 3, 4 NH fuse-links am 500-690VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions according to DIN 43 620 Parts 1 to 4 Lead free contact blades 0% cadmium APPLICATIONS am: Partial purpose,

More information

NH fuse-links gg 500VAC top indicator/live gripping-lugs size 4, 4a

NH fuse-links gg 500VAC top indicator/live gripping-lugs size 4, 4a LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions in accordance with DIN 43 62 Live tags Top indicator Lead free contact blades % cadmium APPLICATIONS gg: General purpose (protection

More information

TERMS AND DEFINITIONS

TERMS AND DEFINITIONS Application Guide Adjustable Alarm Level A setting on a protection relay at which an LED or an output contact operates to activate a visual or audible alarm. Adjustable Delay A setting on a protection

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links [A] (ka) [mω] [W] [A 2 s] [A 2 s] 12 580 4 6,1 57 4 A 20 370 9 17,3 164 6 A 25 260 10 36 340 10 A 46 55 7 161 1 530 16 A 60 37 13 250 2 270 20 A 80 30 15 430 3 750 25 A 105 25

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

Protection and Connection Motorized and automatic transfer switches IEC Technical guide Protection and Connection Motorized and automatic transfer switches IEC 61439 Technical guide Motorized change-over switches Uninterrupted power supply with motorized functionality ABB offers a wide variety

More information

Protection of Power Electronic Multi Converter Systems in AC and DC Applications

Protection of Power Electronic Multi Converter Systems in AC and DC Applications Protection of Power Electronic Multi Converter Systems in AC and DC Applications Prof. Norbert Grass Technische Hochschule Nürnberg, Institute for Power Electronic Systems, Nuremberg, Germany, Norbert.Grass@th-nuernberg.de

More information

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 2 August 2015 ISSN (online): 2349-784X Power System Stability Analysis on System Connected to Wind Power Generation with

More information

Optimizing Drive Systems for Energy Savings

Optimizing Drive Systems for Energy Savings Optimizing Drive Systems for Energy Savings Richard Messer Siemens AG, Industry Sector, Drive Technologies, Motion Control Systems Erlangen, Germany AIMCAL Web Handling Conference 2012 Prague, Czech Republic

More information

POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE

POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE POWR-SPEED FUSES TECHNICAL APPLICATIONS GUIDE TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 POWER SEMICONDUCTOR DEVICES... 4 2.1 Power Semiconductor Device Classification... 4 3.0 OVERCURRENT PROTECTION

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR Assembly Short-Circuit Current Ratings What Is A Short-Circuit

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components

More information

EPS Technical Specifications 06/2015.

EPS Technical Specifications 06/2015. EPS 8000 555 1125 kva Technical Specifications 06/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a NH fuse-links gg 69VAC NH fuse-links gg 69VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions in accordance with DIN 43 62 Live tags Top indicator Lead free contact blades % cadmium

More information

MASTERYS IP+ 10 to 80 kva

MASTERYS IP+ 10 to 80 kva MASTERYS IP+ 10 to 80 kva OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application. the information

More information

the National PhotoVoltaic protection note 5 I rated Introduction points of interest When to Fuse, When Not to Fuse

the National PhotoVoltaic protection note 5 I rated Introduction points of interest When to Fuse, When Not to Fuse Sizing Fuses for Photovoltaic Systems per the National Electrical Code PhotoVoltaic protection note 5 By Robert Lyons, Jr. Product Manager Introduction Properly sizing fuses for photovoltaic (PV) systems

More information

Page 2 of 39 Report No. CTI PA Testing location:

Page 2 of 39 Report No. CTI PA Testing location: age 2 of 39 Report No. CTI A 2841-2 Tests performed (name of test and test clause): according to :2009: 5 - Interface characteristics, 6 Information, 7 - Service conditions, 10.2.3.3 - Verification of

More information

ABB UPS 3. November 2014

ABB UPS 3. November 2014 ABB UPS 3. November 2014 Modular Architectures Centralized Parallel Architecture (CPA) In a Centralized Parallel Architectures the system is composed of common system building blocks: MAINS 1 MAINS 2 CENTRAL

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information