Fab Efficiency. A new Power Quality and Energy Monitoring Technology for Fabs and Tools

Size: px
Start display at page:

Download "Fab Efficiency. A new Power Quality and Energy Monitoring Technology for Fabs and Tools"

Transcription

1 Fab Efficiency A new Power Quality and Energy Monitoring Technology for Fabs and Tools

2 Content Introduction of PSL (Power Standards Lab) What is SEMI F47 What is SEMI E6/S23 How to combine SEMI F47 (Power Quality) and SEMI E6 (Power Monitoring) to get a New Embedded Monitoring Technology

3 Power Standards Lab Go Green. Know your power. PSL located near San Francisco, California, USA. PSL staff speak English, German, French, Spanish, Japanese, Kiwi, Mandarin Chinese, Cantonese Chinese, and more. Customers in 45 countries world-wide. 3

4 Power Standards Lab Go Green. Know your power. PSL works with most of the major player in the semiconductor industry on solving interesting electric power problems, world-wide. Experts on electric power measurements. PSL designs and manufactures electric power instruments. PSL provides Testing and Certification Services. And we write IEEE, IEC, SEMI standards. 4

5 SEMI F47-Power Quality (1) Frequency Variation: The deviation of the power system fundamental frequency from its specified nominal value. Undervoltage: Decrease in the RMS AC voltage to less than 90 percent at the power frequency for a duration longer than 1 min. Voltage Sags (dips): Decrease between 10% to 90% in RMS voltage or current. Duration from 0.5 cycles to 1 min Interruption Temporary Interruption is the complete loss of voltage for a period from 3 seconds up to one minute. Sustained interruption is the complete loss of voltage for a greater than one minute.

6 SEMI F47-Power Quality (2) Overvoltage: Increase in the RMS AC voltage greater than 10% above nominal. Duration longer than 1 min. Voltage Swells (surges): Increase 10% in the RMS AC voltage or current Durations from 0.5 cycle to 1 min Described by RMS value and duration Impulsive Transient: Short duration, unidirectional in polarity. Characterized by their rise time, decay times and peak magnitude Typical causes: Lightning, ESD, Load switching

7 SEMI F47-Power Quality (3) Oscillatory Transient: Positive and negative polarity values. Described by peak magnitude, waveform, spectral content (predominate frequency.) Typical causes: Line switching, capacitor switching, load switching. Notching: Periodic, steady-state voltage disturbance. Caused by component switching (commutation) e.g. switch mode DC power supplies. During this period, there is a momentary short circuit between two phases pulling the voltage as close to zero as permitted by system impedances. And more

8 SEMI F47 Tool Failure Cause Tools are sensitive. Unexpected,intermittent failures What causes the failures? Software bug? Bad connection? Operator error? Temperature? Flaw in feed material? Humidity? Bubble in process cooling water? etc... Or power quality disturbance? 8

9 Why don t electric companies fix power quality? Because it is caused by faults... 9

10

11

12 SEMI F47 What is it about SEMI F47 Intent: Lead to improved selection criteria for subcomponents and improvements in equipment systems design. Not intended to proliferate the use of battery based UPS systems Requirement:..Equipment must continue to operate without interrupt during conditions identified in the area above the defined line...re-start without operator invention Equipment based standard, not a process quality standard Voltage Sag/Dip Performance - (Voltage Sag Immunity) (By far the majority of Power Quality Problems)

13 SEMI F47 The Famous Curve

14 SEMI F47-Typical Test Setup

15 SEMI F47 Why is it sucessful Lower maintenance cost No need for unnecessary and expensive power storage devices End-users don t want to deal with regular power problems More Fabs do SEMI F47 incoming inspections for new tools Reduces finger pointing at Facilities Mandatory requirement by more and more end-users Improvement of electrical tool design

16 SEMI E6 What is it about Describes how tool manufacturers must report electric power requirements Fixes Oversized breaker problem Gives idea to distinguish between loads (More loads) Requires graphs, numbers on kwh per wafer or process, kva, worst-case THD, and much more First step towards green semiconductor tools

17 SEMI E6 What is it about Gives every load a carbon emission value! Outlook 2015: Any product, machine, facility will come with a designated carbon emission value

18 SEMI E6 A Typical Recipe

19 SEMI E6-Measure energy use First, any tool consumes energy in two different ways 1. Direct Way Tool hooked up to power 2. Indirect Way The tool is hooked up to a variety of other utilities, such as process cooling water, clean dry air, vacuum, each of which requires energy to produce. So reducing the electric power consumption of a tool can have a multiplier effect by reducing the indirect power as well. Second, any tool energy consumption is influenced and controlled in part by the recipe design, and in part by the tool design (Not a high priority at the moment)

20 SEMI E6-Conversion Factors Example of indirect energy consumption: SEMI S23 provides useful conversion factors that inform process designers of the energy costs of all the important utilities: for example, de-ionized water at room temperature costs 9 kwh per cubic meter, and at 85ºC it costs 92 kwh per cubic meter, while the cooling load for the fab air conditioning is roughly 0.3 kwh for each kwh used by the tool. These conversion factors are especially useful because they are expressed in kilowatt-hours, allowing their results to be directly added to the direct energy consumption of the tool.

21 New Monitoring Technology You have to monitor before you can improve! Where? As close to loads as possible

22 Embedded Monitoring

23 New Technology Driving Factors Price Size Ease of Use Add Benefit to Fabs and Tools

24 The digital camera for electric power As easy to use as a digital camera removable SD card, Windows picture files 24

25 What is New Friendly data and absolute no Software Easy-to-understand pictures, straight from your PQube (no software). If you can use a digital camera, you can use a PQube. Don t want pictures? Excel -compatible files, too! 25

26 Go Green. Know your power. What is New Patent-pending CO 2 meters and trends. Accurately converts power measurements to CO 2 emissions generated or avoided! Graph is straight from PQube no software! 26

27 What is New Works right out of the box. Patent-pending power configuration just connect it to the tool s power, and it automatically figures out what you ve got at this fab, and immediately starts recording disturbances, trends, and statistics. (Want a special power configuration? Just edit text in the setup.ini file on your PQube s SD card.) 27

28 What is New Works with or without a network. No network? No problem! Your PQube gives you all its data on an SD card, just like a digital camera. You can get started today. Network available? Great! With its ETH1 module, your PQube will send you an every time it has interesting data. IT department willing to help you with firewalls and setup? Even better! Use your PQube s built-in web server and FTP server for easy access. Or start today without a network. Add network later. 28

29 Integrated WebServer, , FTP Live real time meters, events, trends see from any browser in the world. Web pages are straight from PQube no software! 29

30 What is New Tiny. Smallest 690-volt-rated power monitor ever made. Snaps onto a DIN-rail almost anywhere. Perfect for embedding in semiconductor tools and sensitive Fab locations. Snaps into standard DIN circuit-breaker box, too. Low cost. One-fifth the cost of comparable instruments. Payback time measured in weeks. 30

31 Final Conclusion - Benefit Separating intermittent equipment problems caused by power quality events from intermittent problems caused by other events Accurate, at-the-equipment-terminal statistics about power quality, it will be particularly interesting to learn how much worse power quality is at equipment terminals, compared with power quality at the main meter Now the equipment can be programmed to respond intelligently to power quality events Finally, obtaining all energy usage and carbon (Co2) emissions information for particular systems or parts of Fabs, helping to reduce and conserve energy and lead to a more green environment in the semi industry

32 Thank You Andreas Eberhard

Jaeshininformation Co., of Korea Distributor

Jaeshininformation Co., of Korea Distributor Earth Leakage Current Measurement and ELCB (RCD) trip analysis & Chemical Factory Inverter AC_DC_Battery_Temp Case study 2017. 09 Jaeshininformation Co., of Korea Distributor Our Goal We can follow IEEE1100

More information

PQube 3 Modbus Interface

PQube 3 Modbus Interface PQube 3 Modbus Interface Reference manual Revision 1.9 Modbus Interface Reference Manual 1.9- Page 1 Table of Contents 1. Background... 3 2. Basics... 3 2.1 Registers and Coils... 3 2.2 Address Space...

More information

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS) white paper ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS) Electricity, flowing continuously through the grid, is something that most of today s amenities rely on. For any electrical device to

More information

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues Designing and Maintaining a Pollution-Resilient Electric Power System Tom McDermott IEEE/PES T&D Conference April 21-24, 2008 Chicago, IL Managing Pollution Issues Define the metrics, and measure them

More information

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100

More information

Grounding systems for power supply facilities

Grounding systems for power supply facilities MATEC Web of Conferences 141, 01052 (2017) Grounding systems for power supply facilities Vladimir Konusarov 1,*, and Ekaterina Tarasova 2 1 National Research Tomsk Polytechnic University, 634050 Tomsk,

More information

Regenerative Utility Simulator for Grid-Tied Inverters

Regenerative Utility Simulator for Grid-Tied Inverters Regenerative Utility Simulator for Grid-Tied Inverters AMETEK s RS & MX Series with the SNK Option provides the solution Testing of grid-tied inverters used in solar energy systems is emerging as a major

More information

Titelgrau belassen! Leere Vorlage

Titelgrau belassen! Leere Vorlage Titelgrau belassen! Leere Vorlage MAVOWATT 20 Energy Platform Energy and Power Analyzer MAVOWATT 20 The new Energy and Power Analyzer 2 Klaus-Peter Richter Product Management 10.3.2010 Page 2 Applications

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT20K Highlights On-line double-conversion topology, VFI operation

More information

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS. SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS Róbert Riedlmajer TRNAVA 2007 Unit 14 - Fundamentals of power system protection

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation

More information

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery AC/DC Battery Controller Power Supply TSPC-240UPS Series Compact universal 24 VDC power supply with integrated battery controller module Battery protection for over voltage, deep discharge, short circuit

More information

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers

Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers Ultra-Rapid Fuse Links for the Protection of Semiconductor Rectifiers 1.General The design of rectifier equipment requires specific provisions in the switchgear for the protection of power semiconductor

More information

Sources, Effect, and melioration. Power Quality Problems. Asnil Elektro FT UNP

Sources, Effect, and melioration. Power Quality Problems. Asnil Elektro FT UNP Sources, Effect, and melioration of Power Quality Problems Asnil Elektro FT UNP Sources of Power Quality Problems Power Electrinic Devices Arcing Devices Load Switching Large Motor Starting Embedded Generation

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

HIGH EFFICIENCY MODES OF OPERATION. Path toward highest energy efficiency without load availability trade-off

HIGH EFFICIENCY MODES OF OPERATION. Path toward highest energy efficiency without load availability trade-off HIGH EFFICIENCY MODES OF OPERATION Path toward highest energy without load availability trade-off Valerio Zerillo, Large Power Offering Manager Stephen Major, Large Power Offering Manager TWO STAGE POWER

More information

FUSE TECHNOLOGY Ambient temperature

FUSE TECHNOLOGY Ambient temperature This fuse technology guide will discuss basic fuse operating, application, and selection criteria concepts. The intended purpose of this section is to aid designers with the operation and characteristics

More information

TECHNICAL DATA SHEET KVA UPS Systemss

TECHNICAL DATA SHEET KVA UPS Systemss Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800

More information

Overview Overvoltage protection

Overview Overvoltage protection A P P L I C AT I O N N OT E 1.0 Overview Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge

More information

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Mining The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Reprint Authors: Kurt Tischler Siemens AG, Mining Technologies, Erlangen, Germany Reprint: WORKSHOP SAG

More information

Optimization of Total Operating Costs Using Electric Linear Drives

Optimization of Total Operating Costs Using Electric Linear Drives Optimization of Total Operating Costs Using Electric Linear Drives TCO analysis demonstrates high potential for savings, even for simple applications, by replacing pneumatic drives Electric linear drives

More information

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous

More information

C.E.S. Solution Presentation CSDP C.E.S. Smart Distribution Panel CMCS C.E.S. Monitoring & Control Software

C.E.S. Solution Presentation CSDP C.E.S. Smart Distribution Panel CMCS C.E.S. Monitoring & Control Software C.E.S. Solution Presentation CSDP C.E.S. Smart Distribution Panel CMCS C.E.S. Monitoring & Control Software White Paper Version US-090701 Table of Contents COMPUTERIZED ELECTRICITY SYSTEMS LTD. - COMPANY

More information

MKN-DSP SERIES - THREE PHASE

MKN-DSP SERIES - THREE PHASE Output Power Factor 0.9 MKN-DSP SERIES - THREE PHASE Double conversion True On-Line UPS 3 Phase Input - 3 Phase Output 10 KVA 15 KVA 20 KVA 30 KVA 40 KVA 50 KVA 60 KVA Model for: 208/120 V 220/127 V /

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING 1 DEPARTMENT OF ELECTRICAL ENGINEERING Introduction to High Voltage Testing It is essential to ensure that the electrical equipment is capable of withstanding the overvoltages that are met within the service.

More information

NO-BREAK KS. Dynamic UPS system PRESENTATION

NO-BREAK KS. Dynamic UPS system PRESENTATION NO-BREAK KS Dynamic UPS system PRESENTATION Contents Chapter 1: Description of No-Break KS System...3 Chapter 2: Operation when mains power is available...4 Chapter 3: Operation when mains supply is disrupted...6

More information

Symmetra PX 100 kw. Scalable from 10 kw to 100 kw Modular, scalable, high-efficiency power protection for data centers

Symmetra PX 100 kw. Scalable from 10 kw to 100 kw Modular, scalable, high-efficiency power protection for data centers Symmetra PX 100 kw Scalable from 10 kw to 100 kw Modular, scalable, high-efficiency power protection for data centers High-performance, right-sized, 3-phase power protection with high efficiency and availability

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION! INSTALLATION INSTRUCTIONS FOR SYMCOM S MOTORSAVER MODEL 460 BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

More information

DPX30-xxSxx DC-DC Converter Module 9.5 ~ 18 VDC and 18 ~ 36 VDC and 36~ 75 VDC input; 3.3 to 28 VDC Single Output; 30 Watts Output Power

DPX30-xxSxx DC-DC Converter Module 9.5 ~ 18 VDC and 18 ~ 36 VDC and 36~ 75 VDC input; 3.3 to 28 VDC Single Output; 30 Watts Output Power DC-DC Converter Module 9.5 ~ 18 VDC and 18 ~ 36 VDC and 36~ 75 VDC input; 3.3 to 28 VDC Single Output; 30 Watts Output Power FEATURES NO MINIMUM LOAD REQUIRED 1600VDC INPUT TO OUTPUT ISOLATION SCREW TERMINALS

More information

DPX30-xxDxx DC-DC Converter Module 9.5 ~ 18 VDC and 18 ~ 36 VDC and 36~ 75 VDC input; ±12 to ±15 VDC Dual Output; 30 Watts Output Power

DPX30-xxDxx DC-DC Converter Module 9.5 ~ 18 VDC and 18 ~ 36 VDC and 36~ 75 VDC input; ±12 to ±15 VDC Dual Output; 30 Watts Output Power DC-DC Converter Module 9.5 ~ 18 VDC and 18 ~ 36 VDC and 36~ 75 VDC input; ±12 to ±15 VDC Dual Output; 30 Watts Output Power FEATURES NO MINIMUM LOAD REQUIRED 1600VDC INPUT TO OUTPUT ISOLATION SCREW TERMINALS

More information

THE SEMI CONDUCTOR INDUSTRY VERSUS VOLTAGE SAGS. Power. Made Perfect. SM THE CASE FOR AGGRESSIVE INTERVENTION

THE SEMI CONDUCTOR INDUSTRY VERSUS VOLTAGE SAGS. Power. Made Perfect. SM THE CASE FOR AGGRESSIVE INTERVENTION Power. Made Perfect. SM THE SEMI CONDUCTOR INDUSTRY VERSUS VOLTAGE SAGS THE CASE FOR AGGRESSIVE INTERVENTION 2018 Utility Systems Technologies ustpower.com SITUATION TRUE STORY: A California semiconductor

More information

DPX30-xxWDxx DC-DC Converter Module 10 ~ 40VDC, 18 ~ 75VDC input; ±12 to ±15 VDC Dual Output; 30 Watts Output Power

DPX30-xxWDxx DC-DC Converter Module 10 ~ 40VDC, 18 ~ 75VDC input; ±12 to ±15 VDC Dual Output; 30 Watts Output Power DC-DC Converter Module 10 ~ 40VDC, 18 ~ 75VDC input; ±12 to ±15 VDC Dual Output; 30 Watts Output Power FEATURES NO MINIMUM LOAD REQUIRED 1600VDC INPUT TO OUTPUT ISOLATION SCREW TERMINALS FOR INPUT AND

More information

DPX30-xxWSxx DC-DC Converter Module 10 ~ 40VDC, 18 ~ 75VDC input; 3.3 to 28VDC Single Output 30 Watts Output Power

DPX30-xxWSxx DC-DC Converter Module 10 ~ 40VDC, 18 ~ 75VDC input; 3.3 to 28VDC Single Output 30 Watts Output Power DC-DC Converter Module 10 ~ 40VDC, 18 ~ 75VDC input; 3.3 to 28VDC Single Output 30 Watts Output Power FEATURES NO MINIMUM LOAD REQUIRED 1600VDC INPUT TO OUTPUT ISOLATION SCREW TERMINALS FOR INPUT AND OUTPUT

More information

Features. Description. Table of Contents

Features. Description. Table of Contents Features Very low profile Very high efficiency (typically 90%) Single and dual output versions Input voltages from 24V to 110VDC nominal voltages from 5V to 48VDC -40 C to +71 C operation without de-rating

More information

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

A21M. Introduction: Functional Overview: Key Protection & Control Functions: Introduction: ASHIDA has designed economical & reliable Multifunction A21M Protection & Control System. The simple and compact construction of A21 series, A21M relay provides integrated Protection, Control

More information

SmartOnline 3-Phase In/Out 120/208V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, DB9 Serial, Hardwired

SmartOnline 3-Phase In/Out 120/208V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, DB9 Serial, Hardwired SmartOnline 3-Phase In/Out 120/208V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, DB9 Serial, Hardwired MODEL NUMBER: SU20K3/3 Description Tripp Lite's SU20K3/3 20kVA SmartOnline

More information

HBC DC-DC Series Data Sheet 300-Watt Half-Brick Converters

HBC DC-DC Series Data Sheet 300-Watt Half-Brick Converters Applications Intermediate Bus architectures Telecommunications equipment LAN/WAN applications Data processing applications Features RoHS lead solder exemption compliant High efficiency up to 94% High power

More information

Questions Section: Do you have questions that aren't covered? Please contact us!

Questions Section: Do you have questions that aren't covered? Please contact us! Questions Section: 1. What are the screw terminals on the back of my XP600 for? 2. How do I hook up a remote turn-on switch for my XP250 / XP600 / XP1100/ MX series inverter? 3. Can I sell power back to

More information

THIS PAGE WAS INTENTIONALLY LEFT BLANK.

THIS PAGE WAS INTENTIONALLY LEFT BLANK. THIS PAGE WAS INTENTIONALLY LEFT BLANK. Table of Contents Features... 2 Applications... 2 Approvals... 2 Part Marking... 3 System... 4 Absolute Ratings... 4 Fuse Configuration and Dimensions... 5 Specifications...

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

DPX15-xxWDxx Dual Output: DC-DC Converter Module 9.5 ~ 36VDC, 18 ~ 75VDC input; ±5 to ±15 VDC Dual Output; 15 Watts Output Power

DPX15-xxWDxx Dual Output: DC-DC Converter Module 9.5 ~ 36VDC, 18 ~ 75VDC input; ±5 to ±15 VDC Dual Output; 15 Watts Output Power DPX15-xxWDxx Dual Output: DC-DC Converter Module 9.5 ~ 36VDC, 18 ~ 75VDC input; ±5 to ±15 VDC Dual Output; 15 Watts Output Power FEATURES NO MINIMUM LOAD REQUIRED 1600VDC INPUT TO OUTPUT ISOLATION SCREW

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS

Liebert NX TM. 250kVA kVA Transformer-free. High Efficiency, Scalable On-line UPS Transformer-free. High Efficiency, Scalable On-line UPS LIEBERT Liebert NX NX TM TM UPS 250-250kVA 1000-1000kVA Facility managers continue to face the increasing outlay of energy consumption and the call

More information

SolarMax MT series. The power pack for maximum yields.

SolarMax MT series. The power pack for maximum yields. SolarMax MT series The power pack for maximum yields. All good things come in three phases. We have been developing and producing transformerless inverters for over 20 years. Our engineers have effectively

More information

Frequently Asked Questions. ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp

Frequently Asked Questions. ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp Copyright 2009, ABB Inc. All Rights Reserved Specifications subject to change without notice Contact ABB Inc, Low Voltage Drives ABB Inc - Low

More information

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

User Manual Back-UPS BX650CI-MS 230 Vac with AVR User Manual Back-UPS BX650CI-MS 230 Vac with AVR Overview Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. Read the Safety

More information

HYBRID POWER FOR TELECOM SITES

HYBRID POWER FOR TELECOM SITES HYBRID POWER FOR TELECOM SITES ARE YOU MAKING THE MOST OF YOUR ENERGY TO REDUCE OPEX? Energy costs can amount to 55-65% of total operating expenditure for mobile operators, yet many lack the tools they

More information

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation agenda Fundamentals Compelling value Product line overview VerSaVac (VSV) Product features and benefits Design Ratings Applications

More information

Liebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL

Liebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL GXT4 5000 & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY This specification shall define the electrical and mechanical characteristics and requirements for a continuousduty,

More information

Technical Data. Low Voltage Regulation System LVRSys. Flexible solution for power utilities. Voltage stabilization for industrial grids

Technical Data. Low Voltage Regulation System LVRSys. Flexible solution for power utilities. Voltage stabilization for industrial grids Technical Data Low Voltage Regulation System LVRSys 1 Power range: 7.5 kva up to 3150 kva 1 Regulation: single- or three-phase 1 Regulation ranges: ± 6 % to ± 24 % 1 Overall efficiency: 99.4 % to 99.8

More information

Feed-in management with Solar-Log

Feed-in management with Solar-Log Feed-in management with Solar-Log 1 Publisher: Solare Datensysteme GmbH Fuhrmannstr. 9 72351 Geislingen-Binsdorf Germany International Support Tel.:+49 7428 9418-640 Fax:+49 7428 9418-280 E-mail: support@solar-log.com

More information

Sunny Tripower. Can do everything that we can

Sunny Tripower. Can do everything that we can Sunny Tripower Can do everything that we can New Features Optiflex Flexible Plant Design Optiprotect Electronic String Fuse Optiprotect Integrable Type II Overvoltage Protection Optiprotect Intelligent

More information

Ampd Silo. Energy Storage System. Maintenance-free Li-ion energy storage for mission critical backup. Power to Empower

Ampd Silo. Energy Storage System. Maintenance-free Li-ion energy storage for mission critical backup. Power to Empower Energy Storage System Maintenance-free Li-ion energy storage for mission critical backup Power to Empower State-of-the-art Energy Storage Backup for mission critical applications Ampd Silo is an ultra-compact,

More information

OFF-GRID PV INVERTERS EssenSolar & Expert series. 1kW-5kW. Solution on Unstable or Remote Area without Utility

OFF-GRID PV INVERTERS EssenSolar & Expert series. 1kW-5kW. Solution on Unstable or Remote Area without Utility OFF-GRID PV IVERTERS EssenSolar & Expert series Solution on Unstable or Remote Area without 1kW-5kW FSP Off-Gird Inverters: EssenSolar & Expert series An ideal Off-Grid inverter for households, FSP Off-Grid

More information

SolarMax MT series The all-rounder for trade and industry

SolarMax MT series The all-rounder for trade and industry SolarMax MT series The all-rounder for trade and industry All good things come in three phases. We have been developing and producing transformerless inverters for over 20 years. Our engineers have effectively

More information

Model Number Structure

Model Number Structure Solid State Relays (Single-phase) G3PB New Single-phase Solid State Relays with Compact Size for Heater Control Slim models with a thickness of only 22.5 mm are also available. Compact design achieved

More information

Galaxy VM. From 160 kva to 1000 kva Three-phase power protection. apc.com/products

Galaxy VM. From 160 kva to 1000 kva Three-phase power protection. apc.com/products From 160 kva to 1000 kva Three-phase power protection 2 3 trusted partner for your business continuity Highly efficient, easy-to-deploy, three-phase power protection that seamlessly integrates into the

More information

This manual is to be given to the end user. Optional RFI filter. Drive. Stop. Thermal protection device. Start / Reset +DC.

This manual is to be given to the end user. Optional RFI filter. Drive. Stop. Thermal protection device. Start / Reset +DC. 3943 en - 2013.12 / c Optional RFI filter This manual is to be given to the end user Main contactor power supply Start / Reset Stop Thermal protection device Drive +DC BR Braking resistor DIGIDRIVE SK

More information

Suppression Products. Overvoltage Suppression Products: Introduction Industrial Varistor Products 173

Suppression Products.  Overvoltage Suppression Products: Introduction Industrial Varistor Products 173 : Introduction 171-172 Industrial aristor Products 173 Surge Fuses 174 www.littelfuse.com 2005 Littelfuse POWR-GAR Products Catalog Courtesy of Steven ngineering, Inc.-230 Ryan Way, South San Francisco,

More information

Technical information No. 01. IT systems. The basis for reliable power supply

Technical information No. 01. IT systems. The basis for reliable power supply IT systems The basis for reliable power supply FA01en/01.2004 IT systems The basis for reliable power supply in critical areas The advantages of sophisticated industrial systems can only be of use, if

More information

ELECTRICAL POWER and POWER ELECTRONICS

ELECTRICAL POWER and POWER ELECTRONICS Introduction to ELECTRICAL POWER and POWER ELECTRONICS MUKUND R PATEL (cj* CRC Press Taylor & Francis Group Boca Raton London New York CRC Press is an imprint of the Taylor & Francis Croup, an informa

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

DYNACOMP. The top-class reactive power compensator

DYNACOMP. The top-class reactive power compensator DYNACOMP The top-class reactive power compensator Dynacomp vs Electromechanical switching of capacitors Electromechanical switching of capacitors The Dynacomp : the top-class dynamic compensator Transients

More information

Overcurrent protection

Overcurrent protection Overcurrent protection This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT40K Highlights On-line double-conversion topology, VFI operation

More information

Pipe gasket range. Designed to make a difference. Designed to make a difference 1

Pipe gasket range. Designed to make a difference. Designed to make a difference 1 Pipe gasket range Designed to make a difference Designed to make a difference 1 How Gulf gaskets can make a difference to you Water, drainage, sewerage - when it comes to sealing pipes, it s clear that

More information

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report Test report Type VRLTC load tap changer VRLTC 1500A Type test summary report Date: 10 October 2012 Type Test Summary Report Type VRLTC Vacuum/Reactance Load Tap Changer ABB has tested the Type VRLTC, vacuum

More information

ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS

ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS MIL-STD-1539 (USAF) 1 AUGUST 1973 MILITARY STANDARD ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS FSC 1810 Electrical Power, Direct Current, Space Vehicle Design Requirements MIL-STD-1539

More information

Impulse Voltage Test System, Q Structure, kV

Impulse Voltage Test System, Q Structure, kV TCDYQ Series Impulse Voltage Test System, Q Structure, 200-3600kV Applications: Shunt reactors Power transformers Distribution transformer Instrument transformers Cables (type tests) Bushings Arresters

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

Reading on meter (set to ohms) when the leads are NOT touching

Reading on meter (set to ohms) when the leads are NOT touching Industrial Electricity Name Due next week (your lab time) Lab 1: Continuity, Resistance Voltage and Measurements Objectives: Become familiar with the terminology used with the DMM Be able to identify the

More information

Energy Management Through Peak Shaving and Demand Response: New Opportunities for Energy Savings at Manufacturing and Distribution Facilities

Energy Management Through Peak Shaving and Demand Response: New Opportunities for Energy Savings at Manufacturing and Distribution Facilities Energy Management Through Peak Shaving and Demand Response: New Opportunities for Energy Savings at Manufacturing and Distribution Facilities By: Nasser Kutkut, PhD, DBA Advanced Charging Technologies

More information

Fluke 438-II Power Quality and Motor Analyzer

Fluke 438-II Power Quality and Motor Analyzer Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com TECHNICAL DATA Fluke 438-II Power Quality and Motor Analyzer Quickly and easily discover electrical and

More information

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2 Solid-state Contactor (New Heat Sink Construction) G3PB Space and working time saved with new heat sink construction. Series now includes 480-VAC models to allow use in a greater range of applications.

More information

A permanent supply in any environment today and in the future High performance power supplies fit for digitisation Let s connect.

A permanent supply in any environment today and in the future High performance power supplies fit for digitisation Let s connect. A permanent supply in any environment today and in the future High performance power supplies fit for digitisation Let s connect. Power supply Supplying power even under difficult environmental conditions

More information

On-line, Single Phase, Double Conversion UPS

On-line, Single Phase, Double Conversion UPS V Series Standard Universal Tower/Rack Mount 1, 2, 3 kva On-line, Single Phase, Double Conversion UPS The UniStar V features a field-proven Digital Signal Processor (DSP) achieving high reliability, while

More information

T2 Tester. Calibration Information. Introduction. Safety Information

T2 Tester. Calibration Information. Introduction. Safety Information T2 Calibration Information Introduction This calibration information sheet provides the following information for the T2 (hereafter referred to as "the tester"): Safety information Parts and service information

More information

Active Isolation System AIS

Active Isolation System AIS Active Isolation System AIS Active electronic-pneumatic vibration insulation system with powerful real-time control for the highest demands on effective insulation, deflection and constant level. n Active

More information

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA) Back-UPS 650 VA 230 V with AVR (BX650CI-ZA) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit

More information

SDM320D / SDM320A. Single phase din rail meter SDM320D / SDM320A user manual

SDM320D / SDM320A. Single phase din rail meter SDM320D / SDM320A user manual SDM320D / SDM320A DIN Rail Single Phase Two Wire Energy Meter with S0 Pulse Output (Four modular) User Manual ------------------- 1.1 Safety instruction 1.2 Introductions 1.3 Performance criteria 1.4 Specifications

More information

+86(571) (571) (V4)

+86(571) (571) (V4) +86(571)-56260011 +86(571)-56075753 5 (V4) THE SOLAX INVERTER The solar inverter is a critical technological component that is the heart of any PV plant. A solar inverter or PV inverter, converts the variable

More information

When Grids Get Smart - ABB s Vision for the Power System of the Future

When Grids Get Smart - ABB s Vision for the Power System of the Future When Grids Get Smart - ABB s Vision for the Power System of the Future When Grids Get Smart ABB s Vision for the Power System of the Future There is a convergence occurring between the business realities

More information

TECHNICAL CATALOGUE. PCS100 AVC-40 Active Voltage Conditioner for sag correction

TECHNICAL CATALOGUE. PCS100 AVC-40 Active Voltage Conditioner for sag correction TECHNICAL CATALOGUE PCS100 AVC-40 Active Voltage Conditioner for sag correction ABB Power Conditioning Leading the industry in innovation and technology, ABB provides power conditioning for many of the

More information

Electrical Test of STATCOM Valves

Electrical Test of STATCOM Valves 21, rue d Artois, F-75008 PARIS 619 CIGRE 2016 http : //www.cigre.org Electrical Test of STATCOM Valves Baoliang SHENG 1, Christer DANIELSSON 1, Rolf NEUBERT 2, Juha TURUNEN 3, Yuanliang LAN 4, Fan XU

More information

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration

More information

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Breaker Technology Operational Advantages Development Schedule Dave Richardson, Ph.D.,P.E. Powell Power Electronic

More information

Power Supplies. SDN-C Compact DIN Rail Series

Power Supplies. SDN-C Compact DIN Rail Series SDN-C Compact DIN Rail Series The SDN-C DIN rail power supplies are the next generation of the popular SDN series. These models combine high effi ciency and compact size with new visual diagnostic LEDs

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91

More information

Net Metering Interconnection Requirements

Net Metering Interconnection Requirements Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual Operating & Service Instructions Sola Minicomputer Regulators UL White Card Listed Power Supply Classification CSA Certified Transformer Classification General Description and Specifications The Sola Micro/Minicomputer

More information

Electrical Power Electric power electrical electric power Electric power electric electric

Electrical Power Electric power electrical electric power Electric power electric electric Power Calculations Electrical Power Electric power is the rate at which electrical energy is transferred by an electric circuit. The SI unit of power is the watt, one joule per second. Electric power is

More information

UCI224F - Technical Data Sheet

UCI224F - Technical Data Sheet UCI224F - Technical Data Sheet UCI224F SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

ABB Data Center Solutions Day 5 July 2013 by Kelvin Sim Myths or Truths: Achieving 99% Efficiency with Single Conversion Backup Power System

ABB Data Center Solutions Day 5 July 2013 by Kelvin Sim Myths or Truths: Achieving 99% Efficiency with Single Conversion Backup Power System ABB Data Center Solutions Day 5 July 2013 by Kelvin Sim Myths or Truths: Achieving 99% Efficiency with Single Conversion Backup Power System Striking the right balance The Data Centre Backup Power / UPS

More information

White Paper: Pervasive Power: Integrated Energy Storage for POL Delivery

White Paper: Pervasive Power: Integrated Energy Storage for POL Delivery Pervasive Power: Integrated Energy Storage for POL Delivery Pervasive Power Overview This paper introduces several new concepts for micro-power electronic system design. These concepts are based on the

More information

MultiCal. Operation Manual for MultiCal mmhga/psia Pressure Module

MultiCal. Operation Manual for MultiCal mmhga/psia Pressure Module MultiCal Operation Manual for MultiCal mmhga/psia Pressure Module Contents Overview.... 1 Introduction... 1 Operation.... 2 Functions.... 2 Pressure Measurement... 2 Battery Replacement... 3 Calibration....

More information

UCDI274K - Technical Data Sheet

UCDI274K - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000,

More information