1 Earth Leakage Current Measurement and ELCB (RCD) trip analysis & Chemical Factory Inverter AC_DC_Battery_Temp Case study Jaeshininformation Co., of Korea Distributor

2 Our Goal We can follow IEEE1100 perfectly! DC V & I? N-E V?

3 Phase 1 Semiconductor Tools

4 1. Scope Semiconductor Tools Electric Room ELB Type 0.2Sec/800mA D-Box1 MCCB Type D-Box2 MCCB Type CLS#1 MAIN 3ph ELB Type 0.1Sec/500mA FACTORY Main E-Room #3 MCCB Type CLS#7 MAIN ELB #1 Type 0.1Sec/500mA Trip Source? CLS #7 WALL HEATER 1ph ELB Type 0.1Sec/30mA Wall Heater #1 ~ #14

5 2. Diagram A. General diagram Why trip:? 3P4W 208/120V

6 2. Diagram B. Heater Diagram Why trip :?

7 3. Measuring by PQube3 A. PQube3 Measuring Method Leakage Current : 45mA Noise Filter Leakage Current : 960mA 250A x 3CT Magnetic Contactor Monitoring 1000 : N current : 5~8 Amp PT 220:24 PQube3 Voltage : 5 points Current : 7 points Leakage current : 1 point Sag Monitoring I7(5:0.333)

8 3. Measuring by PQube3 ZCT = 1,000mA : 0.333V For earth leakage current PT = 220V : 24V Split CT PSL Clamp on CT CP-1,000 = 1,000A : 0.333V

9 3. Measuring by PQube3 B. PQube3 Installation

10 4. Measuring Data A. Harmonics

11 5. Event Data A :15:18:36 ELB#1 Trip

12 5. Event Data B :15:18:36 ELB#1 Trip Earth Leakage Current : trip soruce Heater Current ( R, S, T - I6, I7, I8 ) Main ELCB Input L1-L2 V

13 5. Event Data I8 Heater Current

14 5. Event Data Trip tmie

15 5. Event Data Earth Leakage Current : 1,400mA Tripped within 0.1sec

16 5. Event Data ELCB Trip Threshold setting : 500mA, 0.1sec 500mA duration : 35msec

17 5. Event Data Earth Leakage Current sec sec

18 5. Event Data I6 Heater Current +0.01sec wave changed sec wave changed

19 5. Event Data I7 Heater Current sec - wavechange sec Wave changed

20 5. Event Data I8 Heater Current sec Wave changed

21 5. Event Data B :11:56 2 nd Trip

22 5. Event Data B :11:56 2 nd Trip Leakage Current Trip Curve Leakage Current Formula = 2 * π * 50Hz * 120V * C uf

23 5. Event Data ELCB Trip threshold setting : 500mA, 0.1sec 500mA duration : 40msec

24 5. Event Data L6 Heater Current

25 5. Event Data L1-N Voltage

26 6. Conclusion A. Fixed the imperfect heater connection line. B. Changed the process on-off time of heater. The process was changed so that the change of the current phase did not occur.

27 Phase 2. Telecommunication Device

28 1. Scope Proof of earth leakage of capacitive leakage current and proposal of improvement method Normal ELCB IGR ELCB ZCT SMPS Ground Fault

29 2. Analysis model tripping of ELCB by lightning Tripping analysis modeling of earth leakage breaker in case of lightning, power line grounding In the case of one phase ground fault, the earth leakage breaker trip occurs in unnecessary operation area due to the dynamic instant leakage current that momentarily increases the capacitive leakage current between the ground and power line. 22.9kV : 380V / 220V T R lightning arrester 3P 3set R, S, T, N Fault line Normal line Dynamic Capacitive Leakage Current Instantaneous Rise in Electrical Leakage Circuit Breaker on no-problem power line Analysis method! : If the distribution line is grounded by lightning or trees, the high voltage is grounded from the lightning arrester to ground to prevent surge voltage from reaching the customer directly. On the other hand, the surge protector is attached to the front of the earth leakage breaker for the purpose of preventing the internal surge and induction light from the customer side. However, in order to prevent tripping of the earth leakage breaker, it is necessary to install a surge protection device of 12kV or more inside the earth leakage breaker none. This is because the earth leakage breaker is not tripped by the surge but tripped due to the instantaneous capacitive leakage current rise between the ground, which causes tripping of most earth leakage breaker installed in the wireless mobile communication repeater and internet communication equipment.

30 3. Analysis model tripping of ELCB by Elevator 4 Elevator distributor panel of Apartment Normal load current 4.5A and replace with IGR-32, 20A with patent earth leakage breaker. IGCgenerator

31 3. Analysis model tripping of ELCB by Elevator 4 Elevator distributor panel of Apartment Breaker trip does not occur even if leakage current 40mA or more occurs arbitrarily after replacing IGR breaker. Rise of leakage current

32 3. Analysis model tripping of ELCB by compressor motor s ground fault 114 #1 Air conditioner frequently Tripping ELCB PQube3 monitoring for earth leakage current

33 3. Analysis model tripping of ELCB by compressor motor s ground fault normally R, S, T, N 380V, 220V between the normal status. N-G is maintained below 1 volt. Abnormal state 2V between S-G and 220V between N-G.

34 4 3. Analysis model tripping of ELCB by compressor motor s ground fault Daily trend of PQube3 S phase : Mobile device power line Periodically, T-phase grounded equipment is tracked and communicated at the start of air conditioner # 1. When the compressor of the air conditioner is grounded, the leakage breaker for the power source of the S phase is tripped.

35 3. Analysis model tripping of ELCB by compressor motor s ground fault 90kHz Noise Track equipment that periodically changes voltage. Noise level is measured, but not at a large level, but the periodic noise of 90 khz is revealed by the air conditioner # 1 compressor motor.

36 3. Analysis model tripping of ELCB by compressor motor s 114 ground fault Mobile device S ph V Sph current Mobile leakage current T ph V T ph current N-G V

37 Analysis model tripping of ELCB by compressor motor s ground fault Events that occur when changing waveforms If a ground fault occurs on the T phase, the circuit breaker for mobile device is tripped.

38 3. Analysis model tripping of ELCB by compressor motor s ground fault In the real time measurement graph of the instantaneous leakage current rise of the circuit after replacing the frequent trip breaker with the IGR breaker, a leakage current of 15 ma maximum was confirmed in connection with the N-G potential rise in the graph. Based on this, it is estimated that the circuit breaker may trip due to the motor start when the cooling load operation in summer is started..

39 4. Conclusion A. LG U+ decided to install 6,000 sets of IGR ELCB in their mobile and internet device power lines.

40 Phase 3. Chemical Factory Inverter AC_DC_Battery_ENV1 Analysis Case Study

41 1. Why did the battery cells temperature increase highly? Temperature increased : why?

42 2. PQube3 Connection PT/TR PT 440V : 24V PQube3 AN-3 : Analog - V E I6 A : Analog - A L1 - A Chemical Factory Inverter L1 - V N INPUT 440V 3P AC OUTPUT 120V AC Power Quality 130V DC DC current Hall Sensor ATT2 AN-1 (V) AN-2 (V) Analog (A) Temperature : Battery 2V x 60 cells ENV-1 Lte Modem

43 3. PQube3 Connection and Installation pictures

44 3. PQube3 Connection and Installation pictures

45 3. PQube3 Connection and Installation pictures ENV1 receiving through Lte modem

46 4. Monitorin g & Analyzing Inverter out : 120V AC Inverter out current : 28 ~36A Inverter input current : 20A Charging volt : 0.13kV Battery Charging current:0~20a Inverter input volt : 440V

47 4. Monitorin g & Analyzing Inverter output volt : 120V Inverter output current Inverter input current :? Charging volt : 130V DC Charging current Charging input volt

48 4. Monitorin g & Analyzing Charging volt Charging current

49 4. Monitorin g & Analyzing Battery Temperature and Humidity : No problems.

50 4. Monitorin g & Analyzing Daily. Problem! Charging current : 90A During 14 hours

51 4. Monitorin g & Analyzing Problem! Charging current : 90A During 14 hours

52 5. Conclusion A. The inverter had some problems in charging circuit. Battery had no problems.

53 Phase 4. IGR ELCB & Leakage Current Analysis Technology Introduction made by Jaeshin s patent

54

55

56

57

58

59 The capacitive leakage current(igc) occurred in LED Sensor Lamp Line. The IGR ELCB can be only installed in this case.

60 We want to share our technology with PSL s partners!

61 Many thanks! CEO : Han, Jeong-kyu ( ) jasshininfo@korea.com / ceo@jsdata.co.kr

Technical Journal September 2012

Technical Journal September 2012 Technical Journal September 2012 Earth leakage protection in polluted low voltage network In present day irrespective of the application be it in process industry or in IT industry, Pollution of electrical

More information

Fab Efficiency. A new Power Quality and Energy Monitoring Technology for Fabs and Tools

Fab Efficiency. A new Power Quality and Energy Monitoring Technology for Fabs and Tools Fab Efficiency A new Power Quality and Energy Monitoring Technology for Fabs and Tools Content Introduction of PSL (Power Standards Lab) What is SEMI F47 What is SEMI E6/S23 How to combine SEMI F47 (Power

More information

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors Eilis M. Logan UPRR Marvin J. Frazier Corr. Comp Co. Electromagnetic Interference Magnet and Paper Clip

More information

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES PROK DEVICES PRIVATE LIMITED B-80, 2 nd & 3 rd Floor, KSSIDC Industrial estate, 4 th Main Road, 6 th Block, Rajaji Nagar, Bengaluru -560010 Ph no: 080-41480777, 080-41157700, Email:,, www.prokdvs.in DIP

More information

DC Microgrids and Distribution Systems for Residences

DC Microgrids and Distribution Systems for Residences Microgrids and Distribution Systems for Residences Toshifumi ISE, Hiroaki KAKIGANO (Osaka University, JAPAN) Outline of the Presentation 1. Introduction 2. System Configuration and Control Scheme 3. System

More information

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100

More information

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction

More information

PQube 3 Modbus Interface

PQube 3 Modbus Interface PQube 3 Modbus Interface Reference manual Revision 1.9 Modbus Interface Reference Manual 1.9- Page 1 Table of Contents 1. Background... 3 2. Basics... 3 2.1 Registers and Coils... 3 2.2 Address Space...

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

W SERIES IMPULSE VOLTAGE TEST SYSTEM APPLICATION FEATURES

W SERIES IMPULSE VOLTAGE TEST SYSTEM APPLICATION FEATURES W SERIES IMPULSE VOLTAGE TEST SYSTEM Impulse Voltage Test System is used to generate impulse voltages from 100 KV to 2400 KV simulating lightning strokes and switching surges with energies up to 240 KJ.

More information

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD) Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD) Schneider Electric RCBO Earth Leakage Circuit Breaker (ELCB) An Earth Leakage Circuit Breaker (ELCB) is a device

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

Electric Vehicle Supply Equipment EVSE Vehicle Simulator

Electric Vehicle Supply Equipment EVSE Vehicle Simulator Electric Vehicle Supply Equipment EVSE Vehicle Simulator Equipment design and Operating Instructions GS1007 A Technicians Service Tool to enable the functional, safety and operation of an installed EVSE

More information

Marine Solutions. June 20, Author : Siemens Energy & Automation, Thomas Orberger Your Success is Our Goal

Marine Solutions. June 20, Author : Siemens Energy & Automation, Thomas Orberger Your Success is Our Goal Marine Solutions June 20, 2003 Author : Siemens Energy & Automation, Thomas Orberger Your Success is Our Goal System Overview Water Cooling Unit 1 Control Unit 1/2 DUO-Inverter G G CAN System Bus Gateway

More information

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device Australian Journal of Basic and Applied Sciences, 5(9): 1180-1187, 2011 ISSN 1991-8178 Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

Circuit Breaker Prepared By :

Circuit Breaker Prepared By : Circuit Breaker Prepared By : Eng : Ayman Soliman Selmy Circuit Breaker Specification of circuit Breaker:- [1] Operating voltage of C.B [2] Rated current of C.B (Ir or In) Amp. [3] Instantaneous short

More information

Introduction to Power Electronics - A Tutorial. Burak Ozpineci Power Electronics and Electrical Power Systems Research Center

Introduction to Power Electronics - A Tutorial. Burak Ozpineci Power Electronics and Electrical Power Systems Research Center Introduction to Power Electronics - A Tutorial Burak Ozpineci Power Electronics and Electrical Power Systems Research Center Agenda 1. The definition of power electronics 2. Power semiconductors 3. Power

More information

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units Universal and Multi Split Units If there is a fault on any LG Universal or Multi unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller

More information

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS Prof. Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology Bombay OUTLINE Intoduction Grid

More information

Welcome to our company with many thanks!

Welcome to our company with many thanks! Company Introduction Welcome to our company with many thanks! Our company was established in June. 1991 and have been committed to the distribution and research and development of the processing technology

More information

Interruption Technology of Breakers for High-voltage Direct Current

Interruption Technology of Breakers for High-voltage Direct Current Interruption Technology of Breakers for High-voltage Direct MORIAI Hiroshi ABSTRT Applications for direct current () electric distribution have been spreading along with the increase of data centers and

More information

OFF GRID SOLAR INVERTER

OFF GRID SOLAR INVERTER OFF GRID SOLAR INVERTER Summarize series inverter is one of the most advanced DC to AC conversion products in the world, it has the main advantages of high quality sine wave AC output, microcomputer control,

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

QUALITY ASSURANCE & DOCUMENTATION

QUALITY ASSURANCE & DOCUMENTATION QUALITY ASSURANCE & DOCUMENTATION RTECK IMPORTED PRODUCT STATEMENT Rteck has sourced most product from a large and reputable Chinese product manufacturer who specialise in the manufacture of modular electrical

More information

P.1 CONTENTS. Industrial Earth Leakage Protection. Page

P.1 CONTENTS. Industrial Earth Leakage Protection. Page Industrial earth leakage protection P 1 P.1.01 GB CONTENTS Page Introduction 3 Earth leakage protection 4 Immunized earth leakage protection 5 Measurement in TRMS and Class A 6 Immunity against transient

More information

ic60h (6kA) single module combined RCD/MCB units ic60h (10kA) single module combined RCD/MCB units ild residual current circuit breakers idpn N Vigi

ic60h (6kA) single module combined RCD/MCB units ic60h (10kA) single module combined RCD/MCB units ild residual current circuit breakers idpn N Vigi Contents Miniature circuit breakers ic60n miniature circuit breakers 6kA, C curve, 6-63A ic60h miniature circuit breakers 10kA, C curve, 6-63A ic60n miniature circuit breakers 6kA, B curve, 6-63A ic60h

More information

Pure Sine Wave Power Inverter SSW A SSW A SSW A SSW A SSW A

Pure Sine Wave Power Inverter SSW A SSW A SSW A SSW A SSW A Pure Sine Wave Power Inverter SSW-350-12A SSW-600-12A SSW-1000-12A SSW-1500-12A SSW-2000-12A Owner's Manual Please read this manual before installing your inverter 1 IMPORTANT SAFETY INSTRUCTIONS THIS

More information

New DX 3 High rating & breaking capacity

New DX 3 High rating & breaking capacity New High rating & breaking capacity a new range OF MOduLar CirCuiT BrEakErs up TO 125 a T new dx³ MCBs AN ENHANCED range for HIgH-pErforMANCE INstALLAtIoNs DX³ : the new Legrand MCBs with dx³, Legrand

More information

GB60S 60W Single Output General Purpose Series

GB60S 60W Single Output General Purpose Series Features 2 x 3 x 1.0 Package Operates to 80 C Ambient For 1U Applications 60W convection cooled Universal Input 90-264Vac Optional Power ON LED Approved to CSA/EN/IEC/UL60950-1, 2 nd Edition Efficiency

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

Installation and Operation Manual Back-UPS BR800/1100CI-IN

Installation and Operation Manual Back-UPS BR800/1100CI-IN Installation and Operation Manual Back-UPS BR800/1100CI-IN Safety and General Information There are no serviceable parts in the Back-UPS. Do not attempt to open or repair the Back-UPS as this will void

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A Gas-Insulated Switchgear Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A siemens.com/energy-management Table of content Gas-insulated switchgear Product portfolio 72.5 550 kv Vacuum interrupters for switching

More information

Harmonic current emissions as EN Harmonic Test Value in Amps % of fund Limit value in Amps

Harmonic current emissions as EN Harmonic Test Value in Amps % of fund Limit value in Amps POWER QUALITY Harmonic current emissions as EN 61000-3-2 Harmonic Test Value in Amps % of fund Limit value in Amps 2 0.014 0.143 1.080 3 0.106 1.108 2.300 4 0.003 0.036 0.430 5 0.044 0.463 1.140 6 0.008

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP Phoenix DX Sensorless AC Vector Drive 3 HP to 3500 HP Standard Features: * PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR) * EASY TO USE, SIMPLE SETUP * POWER

More information

Power System Solutions (PSS)

Power System Solutions (PSS) About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91

More information

Technologies & Products Press Conference LeaXield Active filter for leakage current minimization

Technologies & Products Press Conference LeaXield Active filter for leakage current minimization Technologies & Products Press Conference 2014 LeaXield Active filter for leakage current minimization Andrew Tucker Automotive & Power Conversion Solutions Magnetics Business Group November 12, 2014 Leakage

More information

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric

More information

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA) Back-UPS 650 VA 230 V with AVR (BX650CI-ZA) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

SURE-TRIP OEM RELACEMENT TRIP UNIT

SURE-TRIP OEM RELACEMENT TRIP UNIT RMS CURRENT MEASUREMENT with SURE-TRIP OEM RELACEMENT TRIP UNIT Update Circuit Breaker Solid State Controls with SURE-TRIP LOGIC The SURE-TRIP Solid State Tripping Systems Have Been Designed, Tested And

More information

DEVELOPMENT OF AUTO RE-CLOSER EARTH LEAKAGE CIRCUIT BREAKER (AR-ELCB) AHMAD KHAIRUL AZWAN BIN JANTAN ANUA JAH

DEVELOPMENT OF AUTO RE-CLOSER EARTH LEAKAGE CIRCUIT BREAKER (AR-ELCB) AHMAD KHAIRUL AZWAN BIN JANTAN ANUA JAH DEVELOPMENT OF AUTO RE-CLOSER EARTH LEAKAGE CIRCUIT BREAKER (AR-ELCB) AHMAD KHAIRUL AZWAN BIN JANTAN ANUA JAH A thesis submitted in fulfillment of the requirements for the award of the degree of Bachelor

More information

The reason for higher electric bills

The reason for higher electric bills The reason for higher electric bills William S. Bathgate, BS EE bill.bathgate@gmail.com 1 The new AMI electric meter block diagram The Switched Mode Power Supply, (SMPS) which injects high frequency Oscillations/Harmonics

More information

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code: Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah

More information

PSNH INTERCONNECTION REQUEST

PSNH INTERCONNECTION REQUEST PSNH INTERCONNECTION REQUEST Send the completed Interconnection Request and required attachments to: Public Service of New Hampshire Attn: Michael Motta, Senior Engineer Supplemental Energy Sources P.

More information

PQC - STATCON The ultra fast Power Quality Compensator

PQC - STATCON The ultra fast Power Quality Compensator PQC - STATCON The ultra fast Power Quality Compensator PQC - STATCON The ultra fast power quality compensator PQC - STATCON is based on IGBT voltage source inverter technology. It is a shunt connected

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

1. Electronic Stabilizer and Technical Development. 2. Electronic Stabilizer General

1. Electronic Stabilizer and Technical Development. 2. Electronic Stabilizer General SPW TPW6B series SCR Electronic Voltage Stabilizer/Power Conditioner for Industries Use Applications: Printing Specific /Medical Specific /Control Numerical Machine/Elevator Specific /Testing Specific/UPS

More information

Metering Products Protection Units Current Transformers. April 1, 2015

Metering Products Protection Units Current Transformers. April 1, 2015 Metering Products Protection Units Current Transformers April, 0 With Effect From April, 0 Sr.No Description Model No. Multifunction LED Meters POWER ANALYZER - LED VIPS 80P 00 POWER ANALYZER - LED 0-

More information

ISTEK-C A 750V DC Contactor

ISTEK-C A 750V DC Contactor ISTEK-C105 200A 750V DC Contactor Part-A: Areas of applications This model of high voltage contactor can be used in many different areas, which include: battery charger, pre-charging of inverter capacitor,

More information

MEDIUM VOLTAGE DRIVE STARTER TYPE MV-SVFD-ML1

MEDIUM VOLTAGE DRIVE STARTER TYPE MV-SVFD-ML1 EDIU VOLTAGE DRIVE STARTER TYPE V-S-L1 UP TO 20 W UP TO 12 KV UP TO 520/2500 A OCOTECH PRESENTS THE VARIABLE FREQUENCY DRIVE STARTER TYPE V-S & The V- is based on multi level voltage source inverter technology

More information

4-Day Power System Analysis, Coordination, System Studies

4-Day Power System Analysis, Coordination, System Studies 4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our

More information

Safe, fast HV circuit breaker testing with DualGround technology

Safe, fast HV circuit breaker testing with DualGround technology Safe, fast HV circuit breaker testing with DualGround technology Substation personnel safety From the earliest days of circuit breaker testing, safety of personnel has been the highest priority. The best

More information

Technical Explanation for Inverters

Technical Explanation for Inverters CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor

More information

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc. ASHRAE - Variable Speed Drives By Dan Watkins, LEED BD+C Bornquist, Inc. Adjustable Frequency Drive Fundamentals How does a VFD actually work VS Pumping Analysis VS Pumping Features Harmonics VFDs and

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

POWERSOURCEPURE INSTRUCTIONS. Pure Sine Wave Inverter. RINV1200P REINV1200P RINV2200P REINV2200P

POWERSOURCEPURE INSTRUCTIONS. Pure Sine Wave Inverter.  RINV1200P REINV1200P RINV2200P REINV2200P POWERSOURCEPURE Pure Sine Wave Inverter RINV1200P REINV1200P RINV2200P REINV2200P INSTRUCTIONS Retain these instructions for future reference www.ringautomotive.co.uk OVERVIEW The Ring Pure Sine Wave (PSW)

More information

KEWTECH. KT56 digital multi function tester. Instruction manual

KEWTECH. KT56 digital multi function tester. Instruction manual KEWTECH KT56 digital multi function tester Instruction manual Contents 1 Safety Notice 1 2 Features and Principles of Measurement 3 3 Introduction 6 4 Specifications 7 5 Instrument layout 9 6 Operating

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01

More information

SURE TRIP RETRO KITS

SURE TRIP RETRO KITS RMS CURRENT MEASUREMENT with SURE TRIP RETRO KITS Circuit Breaker Solid State Controls with SURE TRIP LOGIC The Sure Trip Solid State Tripping Systems Have Been Designed, Tested And Produced To all Applicable

More information

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. 1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse

More information

Series Motor Protection

Series Motor Protection 320-327 Series Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za

More information

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MANUFACTURED IN THE EU EUROPEAN QUALITY 1, 2 & 3 POLE MCB s TRIPPING CURVES C & D CURRENT RATINGS 1AMP TO 63AMPS 10KA BREAKING CAPACITY

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation

More information

BREAKER. Molded Case Circuit Breaker/Earth Leakage Circuit Breaker

BREAKER. Molded Case Circuit Breaker/Earth Leakage Circuit Breaker BREAKER Molded Case Circuit Breaker/Earth Leakage Circuit Breaker 2 BREAKER With an improved technology and agressive invesment in R&D, DAERYUK create differentiated value for each customer in order to

More information

Residual Current Circuit-breaker (RCCB) FH 200 Series

Residual Current Circuit-breaker (RCCB) FH 200 Series Residual Current Circuit-breaker (RCCB) FH 200 Series Bi-directional cylindrical terminal ensure higher safety of connecting operations, making them easier. Test pushbutton to verify the correct functioning

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

Ancol. Ancol Electronics Co.,Ltd Non-Linear Resistor (mm) Element Diameter Packaging K ±10% Varistor Voltage

Ancol. Ancol Electronics Co.,Ltd Non-Linear Resistor (mm) Element Diameter Packaging K ±10% Varistor Voltage FEATURES: Widely voltage range 1 8v-1.8kv Fast response to the rapidly increase Voltage (Mu sec.) Excellent non-linearity voltage Symmetric V-I characteristics Great withstanding surge current (200 0A/c

More information

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL Dual Rating NRTL/C CERTIFIED Technologies Inc. mgitech.com Sensor/Sensorless Vector Control Dual current rated for constant and variable torque Auto

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4)

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4) CP9817 PAGE: 1 of 16 CERTIFIED TEST REPORT VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC 60099-4 (99-4) 0711 Supersedes 0601 Cooper Industries. All Rights Reserved. CP9817 PAGE:

More information

CIRCUIT PROTECTORS LOW VOLTAGE FUSES AIR CIRCUIT BREAKERS

CIRCUIT PROTECTORS LOW VOLTAGE FUSES AIR CIRCUIT BREAKERS CIRCUIT PROTECTORS LOW VOLTAGE FUSES AIR CIRCUIT BREAKERS Circuit protectors Circuit protectors Air circuit breakers Air circuit breakers AFaC and BaC types HRC fuses BLC, CR and CS types Super Rapid Fuses

More information

TPAK Series COOLANT PUMP

TPAK Series COOLANT PUMP TPAK Series COOLANT PUMP Instruction Manual ISO 9001 Certified WALRUS PUMP CO., LTD. EC Declaration of Conformity Manufacturer: Walrus Pump Co., Ltd. Address: No.83-14, Dapiantou, Sanzhi Dist., New Taipei

More information

w.s e c.c o m.t w AUTOMATIC TRANSFER SWITCHES Instructions (MCCB TYPE) BREAKER & SWITCHGEAR SYSTEM

w.s e c.c o m.t w AUTOMATIC TRANSFER SWITCHES Instructions (MCCB TYPE) BREAKER & SWITCHGEAR SYSTEM w.s e c.c o m.t w 2010 AUTOMATIC TRANSFER SWITCHES Instructions (MCCB TYPE) BREAKER & SWITCHGEAR SYSTEM Index ATS Instructions A. General description B. MCCB TYPE Specification C. The main structure analysis

More information

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY Sheet 1 of 5 Order Number Serial Number PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY Issue Date Level B 27/05/1999 Initial issue. Summary of changes Due to RMS continuous product improvement policy

More information

Transforming Energy.. For Advanced Technology

Transforming Energy.. For Advanced Technology Transforming Energy.. Manufacturers of CE approved Transformers & Reactors Five Decades of Manufacturing Experience Manufacturers of Quality Reliable Transformers. Auto C 201,4 th Cross Peenya Induatrial

More information

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

User Manual Back-UPS BX650CI-MS 230 Vac with AVR User Manual Back-UPS BX650CI-MS 230 Vac with AVR Overview Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. Read the Safety

More information

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements. Datasheet Single- and three-phase switched-mode power supply units NEW The new power supplies offer a wide range of robust solutions for demanding application requirements. C SEMI F47 US Designed for high

More information

Table of contents NLE 2 x 36 W T8, 230 V, 4 Ah, 1.5 h 4

Table of contents NLE 2 x 36 W T8, 230 V, 4 Ah, 1.5 h 4 Data sheet Integrated emergency converter for fluorescent lamps zone 2 Ex 100,000 h suitable for zone 2 hazardous areas For mains and battery supply Integrated battery management inear V inear V Emergency

More information

Zenith ZTGSE/ZTGDSE. GE Energy Digital Energy. Service Entrance Rated Automatic Transfer Switches. Introduction. Features and Benefits

Zenith ZTGSE/ZTGDSE. GE Energy Digital Energy. Service Entrance Rated Automatic Transfer Switches. Introduction. Features and Benefits GE Energy Digital Energy Zenith ZTGSE/ZTGDSE Service Entrance Rated Automatic Transfer Switches Introduction While providing the functionality of an automatic transfer switch (ATS), GE s Zenith ZTGSE Series

More information

SINAMICS SM150. Siemens product performance features. Competitor product profile. Components. Power, transport units. Service friendliness

SINAMICS SM150. Siemens product performance features. Competitor product profile. Components. Power, transport units. Service friendliness SINAMICS SM150 B.Rasch A&D LD IB mail to: bjoern.rasch@siemens.com Slides: 1 SINAMICS SM150 Product overview Voltage: Power: Motor: Operation: Output frequency: Topology: Technology: Cooling: Closed-loop

More information

Power Solutions Manager Generac Power Systems, Inc.

Power Solutions Manager Generac Power Systems, Inc. Engine Generator Paralleling Concepts Gen. #1 Gen. #2 Gen. #3 Gen. #4 Gen. #5 Presenter: Daniel Barbersek Power Solutions Manager Generac Power Systems, Inc. RUNNING HEADLINE What Topics Will Be Covered

More information

UPS Ratings-Not so Apparent

UPS Ratings-Not so Apparent App Notes ~ Outdoor Power System Design and Cost Considerations Application Notes Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Jason Marckx Chief

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT20K Highlights On-line double-conversion topology, VFI operation

More information

Model #: APS V DC or 120V AC input; 120V AC output (hardwired) Auto Transfer Switching option for battery backup / UPS operation

Model #: APS V DC or 120V AC input; 120V AC output (hardwired) Auto Transfer Switching option for battery backup / UPS operation PowerVerter APS Inverter/Charger with Auto-Transfer Switching Model #: APS2012 12V DC or 120V AC input; 120V AC output (hardwired) 2000 watts continuous, 3000 watts OverPower and 4000 watts DoubleBoost

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

Domae. The right solution for distribution boards

Domae. The right solution for distribution boards Domae The right solution for distribution boards Guaranteed quality and adapted solutions Domae : SIRIM approved The quality marks prove product conformity to their reference standard. They guarantee:

More information

GENSET CONTROL MODULE A121A / A241A

GENSET CONTROL MODULE A121A / A241A Technical Data Sheet GENSET CONTROL MODULE A121A / A241A Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 4-alarm light outputs with lamp-test provisions.

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.

More information

Novel Charging Protocols in Lithium Ion Battery

Novel Charging Protocols in Lithium Ion Battery Novel Charging Protocols in Lithium Ion Battery Objective:-: To develop a protocol which could optimize the charging time and the capacity fade. Approach: The Constant voltage charging process yields to

More information

StorEdge Solar and Energy Storage System Review

StorEdge Solar and Energy Storage System Review StorEdge Solar and Energy Storage System Review About this Review Barry Cinnamon and his team at Cinnamon Solar and Spice Solar have scheduled a series of hands-on reviews of commercially available residential

More information

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

Extra-High-Voltage SF 6 Gas-Insulated Switchgear Extra-High-Voltage SF 6 Gas-Insulated Switchgear Shuichi Sugiyama Masahiko Fujita Takahiro Shinohara 1. Introduction Due to location criteria and toughened restrictions on transportation, it has become

More information

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out) TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power

More information

DZ47LE C45LE Residual Current Circuit Breaker with Over Current Protection

DZ47LE C45LE Residual Current Circuit Breaker with Over Current Protection DZ47LE 1P+ DZ47LE C45LE Residual Current Circuit Breaker with Over Current Protection DZ47LE C45LE RCBO is used for the protection against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage

More information