1 Company Directive STANDARD TECHNIQUE : SD5P/2 Design of Un-metered Connections ST:SD5P/2 7 th December of 10 -
2 1.0 INTRODUCTION This document specifies the requirements for the design of un-metered connections and includes a number of standard arrangements. 2.0 POLICY 2.1 Load Acceptance The Electricity (Unmetered Supply) Regulations 2001 specify strict criteria for determining whether or not a connection can be un-metered. These criteria are described below: a) The load must be predictable. If the value of load or its duration cannot be readily predicted the connection must be metered. Standard electricity sockets may not be installed at an un-metered connection as equipment connected to the socket cannot be determined. b) The connected load at each exit point should be rated below 500W. In some limited circumstances, where it is not practical to install metering due to high costs, technical difficulties or legal reasons, it is acceptable for load in excess of 500W to be un-metered. All loads above 500W shall be submitted to the Un-metered Connection Team who will determine if the load can be un-metered. Appendix A includes a list of equipment that can normally be un-metered. Load data associated with different types of un-metered equipment is published by Elexon and is available from the following link: \\plodcs01\national\library\bsc\bscp\umso_operational_information.pdf 2.2 Standard Arrangements There are a number of standard arrangements for providing un-metered connections. In each case a connection will only be made to a fused cut-out / distribution board housed within a secure weather proof cubicle, pillar or street lighting column. Connections will not be provided to cut-outs located within traffic bollards or to compartments placed below ground. Where a connection is required for equipment located on a motorway (or equivalent dual carriageway) e.g. lighting, signs etc. the highway authority shall provide a pillar / enclosure remote from the motorway carriageway. Access to the pillar / enclosure shall be provided from land adjacent to the motorway and not from the hard shoulder. ST:SD5P/2 7 th December of 10 -
3 The minimum service cable sizes for new installations are 16mm 2 Copper Concentric or Split Concentric and 25mm 2 hybrid. The maximum cut-out fuse size for individual items of un-metered equipment is generally 25A. Cut-out fuses for new installations shall be cartridge type (e.g. to BS1361 or BS7654). Existing installations may utilise semi-enclosed fuses (e.g. to BS 3036) Arrangement 1 This is a commonly used arrangement and is applicable where the mains system is relatively close to the un-metered connections. A separate service is provided to each street lighting column or kiosk. Each un-metered connection has its own exit point. The PME earth electrode (where PME is available) must be installed at, or beyond, the last service joint that connects to an unmetered connection. ST:SD5P/2 7 th December of 10 -
4 2.2.2 Arrangement 2 This is similar to Arrangement 1 but in this case a service cable is looped from the bottom of the first cut-out to the next un-metered connection. This is repeated for each subsequent connection. Each un-metered connection has a separate exit point. A PME earth terminal is required at the last un-metered connection (where PME is available) Arrangement 3 This is a commonly used arrangement, where WPD provide a single phase cut-out and provide one exit point within the customer s pillar or enclosure. The customer (typically a street lighting authority) installs their own cables and distributes to individual items of equipment. Where PME is available a PME electrode must be installed at either the service joint which connects to the customer s pillar, or at a position along the mains circuit that is more remote from the source substation than that service joint. In addition the customer installs an earth electrode at their most remote installation (irrespective of whether they distribute with CNE or SNE cables). As only one exit point is provided the total load of the connected equipment must satisfy the criteria specified in 2.1 (i.e. it must be predictable and, in most circumstances, rated below 500W). Page Revised 29 th January 2010 ST:SD5P/2 7 th December of 10 -
5 2.2.4 Arrangement 4 This is similar to Arrangement 3 but in this case a 3 phase connection is provided and one exit point is provided per fuse-way. This arrangement may be applicable where the customer wishes to distribute to several items of equipment with a total load in excess of 500W. Where PME is available WPD shall install a PME electrode at the pillar. In addition, the customer installs an earth electrode at the most remote installation on each of their circuits (irrespective of whether they distribute with CNE or SNE cables). The total load of the connected equipment at each exit point must satisfy the criteria specified in 2.1 (i.e. it must be predictable and, in most circumstances, rated below 500W). Customer s Equipment Substation One exit point provided at the outgoing terminals of each fuse-way - Customer owns enclosure / pillar - WPD owns cut-out PME Earth Electrode Page Revised 30 th December 2009 ST:SD5P/2 7 th December of 10 -
6 2.2.5 Arrangement 5 This is similar to Arrangement 4 but in this case a 3 phase multi-way distribution board is installed within the customer s enclosure. This allows several un-metered exit points to be provided (one per fuse-way). Where PME is available WPD shall install a PME electrode at the pillar. In addition, the customer installs an earth electrode at the most remote installation on each of their circuits (irrespective of whether they distribute with CNE or SNE cables). The total load of the connected equipment ay each exit point must satisfy the criteria specified in 2.1 (i.e. it must be predictable and, in most circumstances, rated below 500W). Customer s Equipment One exit point is provided at the outgoing terminals of each fuse-way Substation PME Earth Electrode Page Revised 30 th December 2009 ST:SD5P/2 7 th December of 10 -
7 2.3 Design Requirements Whichever arrangement is used the planner shall ensure: the voltage at each exit point is within statutory limits. equipment (cables overhead line etc.) are not overloaded. the earth fault level at each un-metered exit point is above the rating of the fuses that protect the incoming service. mains cable / overhead line shall be adequately protected by the source protection (i.e. the source fuses shall be capable of operating before the short circuit rating of the cable / overhead line is exceeded. the phase to neutral loop impedance at each exit point is less than 1.5 ohms. for Arrangement 1 and 2 the length of service (from the connection with the mains cable or overhead line to the most remote connection) shall not exceed 250m. The planner must also determine and agree earthing requirements for the exit point. Windebut can be used to check the voltage and circuit loading aspects described above and also to check that mains cables / lines are adequately protected. Windebut can also be used to provide earth fault levels and loop impedance values. Further guidance on Windebut is given ST:SD6K Earthing Earthing requirements are specified in ST:TP21D. Un-metered equipment is often installed in metal enclosures that are accessible to the public. These types of installations can create touch potential risks where PME connections are provided. Given this there are certain restrictions on the provision of PME Street Electrical Fixtures PME or SNE connections can be provided to street electrical fixtures, including, streetlights, traffic signals, advertising hoardings, bus shelters and public telephones etc. situated on or adjacent to roads, streets or footpaths. Where PME is made available to these installations a PME earth electrode must be provided at, or beyond, the service joint / connection to each unmetered installation. These requirements are shown in the previous drawings. In addition to this, earth electrodes are also required at the most remote customer installations where the customer installs their own infrastructure (see Arrangement 3, 4 and 5). Page revised 14 October 2011 ST:SD5P/2 7 th December of 10 -
8 Other Housings Accessible to the Public For other types of housing accessible to the public it is recommended that the installation has Class II insulation (as defined in the IET Wiring Regulations BS7671). Where this is the case a PME earth terminal is not is not required. Single phase installations that are not defined as Class II can be offered a PME earthing terminal as long as: Load connected at the housing is below 2kW. The customer installs and maintains an earth electrode system, bonded to the earth terminal with a resistance of 20 ohms or less. Three phase or split phase (single phase - three wire) installations that are not defined as Class II may only be offered a PME earth terminal if the load is well balanced across the phases. If PME cannot be provided then either an SNE (TN-S) earthing terminal shall be offered or, if this is not suitable, then direct earthing (TT type) will be provided. Where direct earthing is to be used WPD do not provide an earthing terminal and, if the installation is not defined as Class II, the customer must provide their own earth electrode and RCD. ST:SD5P/2 7 th December of 10 -
9 APPENDIX A TYPES OF UNMETERED EQUIPMENT The following list shows typical types of equipment which may be considered for unmetered connections, providing the load complies with the requirements in 2.1. The list is not exhaustive and is for illustration purposes only. Advertising Hoardings Alarm Systems Bus Shelters Cable Network Pillar Cathodic Protection Clocks Communication Cabinets Fire Warning System Flood Warning System Ice Detector Illuminated Bollards Illuminated Map Cabinets Information Signs Navigation Signal Pay & Display Machines Radio Transmitter Red Runner Camera Security Camera Sewage flow recorder Speed Camera Storm overflow Street Lighting Telephone Kiosk (lighting) Telephone Kiosk (phonecard) Ticket Machine TV Aerial TV Amplifier TV Camera TV Relay Traffic Counter Traffic Master Units Traffic Signs Traffic Signal/Pelican Crossing Warden call equipment ST:SD5P/2 7 th December of 10 -
10 APPENDIX B SUPERSEDED DOCUMENTS ST:SD5P/1 APPENDIX C ASSOCIATED DOCUMENTS ST:TP21D ST:SD5K ST:NC1N BS7671 HV and LV System Earthing Use of Windebut Software Procedure for Unmetered Connections and Disconnections Requirements for Electrical Installations (IET Wiring Regulations) ENA Engineering Recommendation G12/3, Requirements for the application of Protective Multiple Earthing to Low Voltage networks. POLICY IMPLEMENTATION APPENDIX D This Standard Technique shall be implemented on issue for all new and substantially modified connections. Managers shall brief relevant staff (including those involved with the design, construction, maintenance and replacement of un-metered connections) on the requirements of this document. IMPACT APPENDIX E 1) Earthing requirements have been added to clause 2.2.1, 2.2.2, 2.2.3, and The associated diagrams have been modified to illustrate these aspects. 2) Significant changes have been made to the design requirements specified in Section 2.3, including the requirement for a maximum earth fault loop impedance of 1.5 ohms and a maximum service length of 250m. 3) Earthing requirement in have been modified. 4) Design requirements are now checked using Windebut rather than the spreadsheet provided in the previous version of the document. KEYWORDS Un-metered, Un-metered Connection, Street Lamp, Street Light DOCUMENT LAST REVIEWED December 2009 APPENDIX G APPENDIX H ST:SD5P/2 7 th December of 10 -
Company Directive STANDARD TECHNIQUE: SD4O/1. Standard HV Connection Arrangements
Company Directive STANDARD TECHNIQUE: SD4O/1 Standard HV Connection Arrangements Policy Summary This document specifies the standard arrangements for HV metered connections. NOTE: The current version of
More informationCompany Directive STANDARD TECHNIQUE : TP4B/2. Relating to 11kV and 6.6kV Transformer Protection
Company Directive STANDARD TECHNIQUE : TP4B/2 Relating to 11kV and 6.6kV Protection Policy Summary This document describes the detailed requirements for 11kV/415V and 6.6kV/415V distribution transformer
More informationNPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations
Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification
More informationCLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001
CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS
More informationWIRING MATTERS SEPTEMBER 2018
WIRING MATTERS SEPTEMBER 2018 The 18 th Edition (BS 7671:2018) launch - revisited This is the second of two articles on the launch of the 18 th Edition (BS 7671:2018). The first article covered electric
More informationOn-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011)
(BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) Author: IET Publications (edited by Mark Coles) Book details Author: IET Publications (edited by Mark Coles) Year: 2011 Format: Paperback,
More informationIET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS
IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS 717.1 Scope The particular requirements of this section apply to a.c. and d.c. installations for mobile or transportable
More informationA guide for the connection of a low voltage installation to The Guernsey Electricity Network
A guide for the connection of a low voltage installation to The Guernsey Electricity Network Guernsey Electricity Limited (GEL) - January 2017 2 Contents Definitions 3 Introduction 5 Scope 6 Sections 1
More informationLevel 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( )
Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 (2382-18) March 2018 Version 1.0 FAQs 1 18 th Edition IET Wiring Regulations 2018 FAQs When will the 18 th Edition of BS 7671
More informationEDS CUSTOMER LV INSTALLATION EARTHING DESIGN
Document Number: EDS 06-0017 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN EPN, LPN, SPN This standard provides guidance on the earthing of customer
More informationEDS CUSTOMER LV INSTALLATION EARTHING DESIGN
Document Number: EDS 06-0017 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN EPN, LPN, SPN This standard provides guidance on the earthing of customer
More informationMajor changes within the New 18 th Edition Wiring Regulations announced by The IET
Major changes within the New 18 th Edition Wiring Regulations announced by The IET BS 7671:2018 Requirements for Electrical Installations will be issued on 2 nd July 2018 and is intended to come into effect
More informationEARTHING YOUR QUESTIONS ANSWERED
18 EARTHING YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing
More informationGuidance for Low Voltage Electrical Installations
Guidance for Low Voltage Electrical Synopsis This document provides information in support of GI/RT7007 Low Voltage Electrical. Signatures removed from electronic version Submitted by Anne E Blakeney Standards
More informationEDS ELECTRIC VEHICLE CONNECTIONS
Document Number: EDS 08-5050 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-5050 ELECTRIC VEHICLE CONNECTIONS EPN, LPN, SPN This standard outlines the design requirements for the connection of
More information33kV Connection up to 90MVA
Electricity Specification 217 Issue 2 December 2007 33kV Connection up to 90MVA Contents 1 Scope 2 General 3 Connection Arrangements 4 Equipment Records 5 Documentation 6 Documents Referenced 7 Keywords
More informationCompany Directive STANDARD TECHNIQUE: TP21E/1. Relating to Provision of WPD Earth Terminals to Customer LV Installations
Company Directive STANDARD TECHNIQUE: TP21E/1 Relating to Provision of WPD Earth Terminals to Customer LV Installations This Standard Technique defines requirements regarding the provision of WPD Earth
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements
More informationEffective discrimination of protective devices
Effective discrimination of protective devices In the event of a fault occurring on an electrical installation only the protective device nearest to the fault should operate,leaving other healthy circuits
More informationDocument reference: IMP/001/107 Document Type: Code of Practice Version:- 3.0 Date of Issue:- August 2017 Page 1 of 27
Version:- 3.0 Date of Issue:- August 2017 Page 1 of 27 IMP/001/107 Code of Practice for Point of Connection assessment using Standard Design Rules for Low Voltage s up to 60kVA 1 Purpose The purpose of
More information3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show.
1 PAPER 7 Sample Questions - C&G 2382 17th Edition paper C 1 o/c 1 - BS 7671 relates to permanent and temporary installations for equipment on: a marinas. b ships. c equipment on aircraft. d railway traction
More informationThe Impact of the 18 th edition (BS 7671:2018)
The Impact of the 18 th edition (BS 7671:2018) In this article, Geoff Cronshaw looks at some of the proposed changes in the DPC (draft for public comment) for electrical installations, focusing on Section
More informationLow Voltage Power Supplies in Electrified Areas
Low Voltage Power Supplies in Electrified Areas Synopsis This document mandates requirements for control of return and stray currents and the management of earthing for low voltage power supplies in electrified
More informationEDS FUSE RATINGS AT DISTRIBUTION SUBSTATIONS
Document Number: EDS 05-4001 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 05-4001 FUSE RATINGS AT DISTRIBUTION SUBSTATIONS EPN, LPN, SPN This design standard details the HV and LV fuse ratings
More informationGT/TDINT100 Issue: 1 Date: SEP 1993 Page 1 of 11
British Railways Board Group Standard Page 1 of 11 Part A Synopsis This Directive gives the general requirements of telecommunications earthing systems, and encompasses the requirements for the earthing
More informationElectrical Installation Lecture No.14 Dr.Mohammed Tawfeeq Alzuhairi
Earthing systems What is earthing? The whole of the world may be considered as a vast conductor which is at reference (zero) potential. In the UK it is referred to this as 'earth' whilst in the USA it
More informationElectrical Awareness and Considerations
Electrical Awareness and Considerations By David Taylor FIHE MIET IEng Objectives Awareness of specifications. Awareness of Distribution Network Operators (DNO) earthing arrangements. Awareness of basic
More informationThe Management of Electrical Safety in Quarries, Associated Plant and Equipment
Quarries National Joint Advisory Committee (QNJAC) Plant Information Sheet 1 (Version 1, November 2015, review date: 2020) The Management of Electrical Safety in Quarries, Associated Plant and Equipment
More informationEDS POLE-MOUNTED EQUIPMENT EARTHING DESIGN
Document Number: EDS 06-0015 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 06-0015 POLE-MOUNTED EQUIPMENT EARTHING DESIGN EPN, SPN This standard details the design requirements for the earthing
More informationThe Licensed Distribution Network Operators of Great Britain
DCRP_12_04_07 The Licensed Distribution Network Operators of Great Britain A review of Engineering Recommendation G12/3 Requirements for the Application of Protective Multiple Earthing to Low Voltage Networks.
More informationGuideline for Parallel Grid Exit Point Connection 28/10/2010
Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationRequirements for Secondary Voltage Revenue Metering (750 V and less)
Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.
More informationAccess Management Standards
Access Management Standards This section replaces Access Control Standards on Page number 300-4 of the Engineering Standards passed February 11, 2002 and is an abridged version of the Access Management
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to
More informationAudi A4 Current Flow Diagram No. 111 / 1
Page 1 of 9 Audi A4 Current Flow Diagram No. 111 / 1 CAN bus wiring from model year 2006 Notes: For information concerning Edition 10.2006 Position of relays and fuses Multi-pin connections Control units
More informationELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016
UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department
More informationUnderground Distribution Construction Manual
Underground Distribution Construction Manual Section E7 Earthing Approved by: A Smith de Perez Energex Limited 2014 ABN 40 078 849 055 MANUAL 00305 1. INSTALLATION Detailed earthing information may be
More informationE-12 Low-voltage Switchboard
Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationRenewable sources of electricity a brief overview
Micro generation 11 Renewable sources of electricity a brief overview THE SCOPE of the 17th Edition is wider and contains many new requirements, including additional requirements to ensure the safe connection
More informationAFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationOn_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.
1 PAPER 4 Sample Questions - C&G 2382 17th Edition full paper D 1 o/c 1 - A recommendation for the interval to the first periodic inspection shall be made by: a the installation electrician. b the main
More informationElectrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2
Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL
More informationECS CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS
Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 03-0054 CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS EPN, LPN, SPN This standard details the procedures to be undertaken
More informationSteve Summers Region Sales Manager
Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control
More informationEngineering Recommendation P26
Engineering Recommendation P26 The Estimation of the Maximum Prospective Short-Circuit Current for Three Phase 415V Supplies Document originally produced by the Electricity Association. 2003 Energy Networks
More informationInitial and Periodic Inspection and Testing of Electrical Installations ( ) Sample Test
Initial and Periodic Inspection and Testing of Electrical Installations (2391-052) Sample Test Version 1.1 January 2018 Please note this is not a complete sample theory exam, this document consists of
More informationResearch Brief. Impact of higher 25kV fault currents. T873 - October Background. Aims
Research Brief Impact of higher 25kV fault currents Background Increasing the maximum fault levels at traction feeder stations has the potential to reduce the costs of electrification schemes. The potential
More informationContents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers
DISTRIBUTION CODE Contents 1 Introduction 2. Advisory and Information Systems 3. Supply 3.1 Quality of Electric Supply 3.2 Interference with other Customers 3.3 Application for the Supply of Electricity
More informationSPRINGFIELD UTILITY BOARD ELECTRIC RATE SCHEDULES RESIDENTIAL SCHEDULE R-1
AVAILABLE Available to residential services in all territory served by the Springfield Utility Board (SUB) except where special rates are in effect. CHARACTER OF SERVICEE 60 Hertz alternating current of
More informationTitle High Voltage and 1500 System Earthing References and Definitions. Reference Number PDS 02 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title High Voltage and 1500 System Earthing References and Definitions Reference Number PDS 02 (RIC Standard: EP 12 00 00 01 SP) Document Control
More informationSection 6 Electric Metering: Residential
Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationResident Permit and Visitor Permit Guidelines
OPERATING GUIDELINES Resident Permit and Visitor Permit Guidelines Approved by: GM, City Services May 2003 Subsequent Amendments: 9 September 2016 Associate Director (Vanessa Godden) Amended to reflect
More informationThe following lighting types are NOT compatible with the TT- 402Wireless Inline Dimmers:
TT402 (300W) Incandescent Wireless receiver Inline Dimmer Product Description The TT- 402is a 40-300W dimmable wireless receiver. It can be paired with only circuits 1 and 2 (keys 4 or 5) on the Taptile
More informationN-03 STEERING GEAR CONTROL SYSTEMS
Guideline No.: N-03(201510) N-03 STEERING GEAR CONTROL SYSTEMS Issued date: October 20,2015 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements,
More informationBS : C&G 2382 Outcomes 4
BS7671 2008: C&G 2382 Outcomes 4 Outcome 4 Protection for safety The candidate will be able to: 4.1 Identify the differences between basic and fault protection 4.2 State means of protection against electrical
More informationConstruction and Connection of Street Light Assets
Construction and Connection of Street Light Assets 1. INTRODUCTION... 2 2. FURTHER INFORMATION... 3 3. DEFINITIONS... 3 3.1 Designer... 3 3.2 Street Light Asset Owner... 3 3.3 Road Owner... 4 3.4 Developer...
More informationUPPER CUMBERLAND ELECTRIC MEMBERSHIP CORPORATION. RESIDENTIAL RATE--SCHEDULE RS (March 2019) Availability. Character of Service.
UPPER CUMBERLAND ELECTRIC MEMBERSHIP CORPORATION RESIDENTIAL RATE--SCHEDULE RS () Availability This rate shall apply only to electric service to a single-family dwelling (including its appurtenances if
More informationToledo 2005 Current Flow Diagram No. 651 / 1 Edition
Page 1 of 6 Toledo 2005 Current Flow Diagram No. 651 / 1 Edition 12.2005 CAN bus network, drive train and diagnosis, LIN bus network from May 2005 Notes: For information concerning Position of relays and
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationTransmission & Distribution Glossary of Electrical Terms
Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The
More informationSELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting
The Electrical Contractors Association SELECT MEMBERSHIP NUMBER 15019 ELECTRICAL INSTALLATION CERTIFICATE (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IET WIRING REGULATIONS]) EI Copyright The
More informationSNZ TR 6120:2014. New Zealand Technical Report. Low voltage supply earthing systems SNZ TR 6120:2014
New Zealand Technical Report Low voltage supply earthing systems SNZ TR 6120:2014 COMMITTEE REPRESENTATION This technical report was prepared under the supervision of the LV Supply Earthing Systems Review
More informationLIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016
No Description/ Specification Amendment 1 EDD 1 :2008 11/0.415 kv Distribution Transformer, Oil Filled - 2 ED 2 :1987 The Galvanization of Iron and Steel, Articles Other Than Steel Wire - 3 ED 3 :1979
More information9. Non-Residential Services (Commercial, Industrial, and Agricultural)
Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect
More informationCHAPTER 4 PROTECTION REQUIREMENTS
CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.
More informationCHAPTER 7 ELECTRIC VEHICLE CHARGING FACILITIES
CHAPTER 7 ELECTRIC VEHICLE CHARGING FACILITIES CHAPTER 7 ELECTRIC VEHICLE CHARGING FACILITIES 7.1 Introduction 1. Electric Vehicles ( EVs ) have zero emission and help improve roadside air quality. Moreover,
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationTechnical Specification 43-8 Issue Amendment
PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 43-8 Issue 4 2015 + Amendment 1 2016 Overhead line clearances www.energynetworks.org PUBLISHING AND COPYRIGHT
More informationEarthing Principles. Symmetra PX 250/500 kw
Earthing Principles Symmetra PX 250/500 kw Table of Contents Earthing Principles... 1 Decoding the Earthing Types... 1 TN Systems... 2 Characteristics... 2 Reference to IEC/EN 60364-4-41 413.1.3... 2
More informationNPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links
Version:- 7.0 Date of Issue:- July 2017 Page 1 of 19 NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links 1. Purpose The purpose of this document is to detail
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationTrack Circuit Assister Configuration for Rail Vehicles
Track Circuit Assister Configuration for Rail Synopsis This Standard mandates where TCAs shall be fitted onto a vehicle and how they shall be set up. It also contains the requirements for testing a TCA.
More informationCentral battery system ZB-S with STAR technology
Central battery system ZB-S with STAR technology As well as providing a dependable supply of power (30V AC/0 V DC) to safety and exit luminaires, the central battery system ZB-S tests itself automatically
More informationFINAL-ER 42 Electrician Regulations Answer Schedule
FINAL-ER 42 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.
More informationEquipotential Bonding of Rail Vehicles to Running Rail Potential
Railway Group Standard Equipotential Bonding of Rail Vehicles to Running Rail Potential Synopsis This standard mandates the requirements for equipotenial bonding of rail vehicles to comply with the Electricity
More informationControl, Safe Use and Operation of Excavators, Loaders and Earth Moving Equipment
Control, Safe Use and Operation of Excavators, Loaders and Earth Moving Equipment Page 1 of 14 Part A Synopsis A standard detailing the requirements for the control, safe use and operation of excavators,
More informationMCST LIGHTING AND POWER DESIGN AND CONSTRUCTION
Engineering Standard- Design Structures & Facilities MCST 000002-01 Version: 3 Issued: May 2016 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT MAY NOT BE UP-TO-DATE; REFER
More informationRapid Response. Lineside Signal Spacing. Railway Group Standard GK/RT0034 Issue Three Date September 1998
Rapid Response Railway Group Standard Lineside Signal Spacing Synopsis This Standard specifies the minimum distance that must be provided between the first signal displaying a cautionary aspect and the
More informationGuidelines for connection of generators:
Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...
More informationTitle Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category General Title Reference Number PMP 01 (RIC Standard: EP 00 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards and
More informationControl, Safe Use and Operation of Road-Rail Plant
Control, Safe Use and Operation of Page 1 of 13 Part A Synopsis A Standard detailing the requirements for the control, safe use and operation of road-rail plant in the railway environment. Approval and
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationSPRINGFIELD UTILITY BOARD ELECTRIC RATE SCHEDULES
AVAILABLE RESIDENTIAL SCHEDULE R-1 Available to residential services in all territory served by the Springfield Utility Board (SUB) except where special rates are in effect. CHARACTER OF SERVICE 60 Hertz
More informationWORKING PAPER. International TWENTY-F Edition. (Presented SUMMARY. paragraph (DGP/24-WP/3)). to amend shown in. Appendix B. 1.1 biennium.
International Civil Aviation Organization DGP/24-WP/65 20/8/13 WORKING PAPER DANGEROUS GOODS PANEL (DGP) SUMMARY TWENTY-F FOURTH MEETING Montréal, 28 October to 8 November 2013 Agenda Item 2: Development
More informationTechnical Guidance for Customer Export Limiting Schemes
PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation G100 Technical Guidance for Customer Export Limiting Schemes www.energynetworks.org PUBLISHING AND COPYRIGHT
More information2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00
DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations
More informationNZQA unit standard version 8 Page 1 of 5. Apply and remove earths from conductors on electricity supply networks
Page 1 of 5 Title Apply and remove earths from conductors on electricity supply networks Level 4 Credits 4 Purpose People credited with this unit standard are able to: demonstrate knowledge of earthing
More informationHANDBOOK FOR THE. ST700 TfL CONTROLLER
Siemens Traffic Controls Limited Sopers Lane Poole Dorset BH17 7ER HANDBOOK FOR THE ST700 TfL CONTROLLER (SMALL) PREPARED: FUNCTION: Dave Martin Engineering Manager DATE: January 2002 Siemens plc. 2002
More informationMATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****
Page 1 of 8 ****Supercedes BECo Standard E2.12-2.12 and ComElectric Spec 6-0895**** 1.0 General Requirements SINGLE PHASE PAD-MOUNTED DISTRIBUTION TRANSFORMERS 1.1 These specifications cover single-phase
More informationGUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES
MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:
More informationME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position
LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble
More informationSECTION 3 CUSTOMER CLASS SPECIFIC
SECTION 3 CUSTOMER CLASS SPECIFIC 3.0 General PowerStream shall recover costs associated with the installation of Connection Assets, by customer class, via a Basic Connection Charge and a Variable Connection
More informationAn advisory circular may also include technical information that is relevant to the rule standards or requirements.
Revision 0 Electrical Load Analysis 2 August 2016 General Civil Aviation Authority advisory circulars contain guidance and information about standards, practices, and procedures that the Director has found
More informationLocal Highway Panels Members Guide. 8 Passenger Transport Improvements
Local Highway Panels Members Guide 8 Passenger Transport Improvements 2 Local Highway Panels (LHP) Members Guide 2016/17 1. Introduction Bus Services The bus services outside London were deregulated in
More information31-SDMS-01 REV. 03 SPECIFICATIONS FOR
31-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE DISTRIBUTION PANEL This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1.0 SCOPE
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More information