1 National Seminar on New Generation High Performance Conductors 4 th Dec 14
2 Compulsion for alternative why? Limitation of power flow New line ROW Constraint Increasing urbanization left no inlet for critical S/S. EHV Cable cost still very high Use efficient conductor from day one Existing line (Overloaded/ Uprate the capacity) Replace/ Reconductoring with efficient conductor
3 What is efficient Conductor? ATTRIBUTES WHY 1) More current carrying capacity More power 2) High Conductivity (Low Resistance) Efficient power transfer 3) Temperature rise with current More I 2 R loss 4) Ultimate Tensile Strength Sag Tension compliance 5) Co-efficient of linear expansion limit Sag for ground clearance as per IE rules 6) Weight per meter Optimal loads for tower design 7) Cost Conductor contributes 40% of line cost
4 What GETCO is doing for new lines? Characteristics of various options: Options of conductor Benefits / Short comings Category Cost factor 1) ACSR Zebra (220 kv) 2) ACSR Moose (400 kv) Presently used Moderate Temp. Comparatively Low Presently used Moderate Temp. Comparatively Low 3) AAAC Lower weight, Higher Sag, Higher Resistance 4) TACSR / ZTACSR Higher Sag, Higher Resistance 5) ACSS Higher Sag, Higher Resistance 6) AL59 Higher Sag, Lower Resistance, Lower weight 7) CCC Lower Sag, Lower Resistance, Special T&P 8) Invar type Lower Sag, Higher Resistance 9) GAP type Lower Sag, Higher Resistance, Special T&P Moderately Higher Temp. (90 ⁰C) Higher Temperature ( ⁰C) Higher Temperature (250 ⁰C) Moderately Higher Temp. (95 ⁰C) HTLS (180 ⁰C) HTLS (230 ⁰C) HTLS ( ⁰C) Marginally High High High Marginally High Very High Very High High
5 What GETCO is doing for new lines? Adopted for 220 kv & 400 kv new lines. Options Available 1) Equal Diameter to ACSR 2) Equal Weight to ACSR Adopted - Equal Weight to ACSR Zebra (220 kv) - Equal Diameter to ACSR Moose (400 kv)
6 What GETCO is doing for new lines? (220 kv) Factors considered for decision making : 1) Current capacity required 170 to 200% of ACSR conductor 2) Project time Use of existing tower design, since new takes time. 3) Efficiency I 2 R loss 4) Satisfy Sag-Tension requirement with existing Tower Spotting Data 5) Dependency on supplier for hardware & accessories suitable for high temperature 6) Competency and T&P to handle erection of new conductor 7) Project cost (Deciding factor)
7 What GETCO is doing for new lines? (220 kv) How AL59 suited for decision making: Factors AL59 suitability Current capacity requirement Project time Efficiency Satisfy Sag-Tension with existing Tower Spotting Data Dependency for Hardware & Accessories Competency of erection Project cost Doubled with moderate Temperature rise (95 ⁰C) Suited to existing tower design Low I 2 R losses even@ 95⁰C Satisfied with 3 meter extension and by limiting the wind span Adequate Indigenous manufacturers Does not require special skill or T&P Increases by 10% appx.
8 What GETCO is doing for new lines? (220 kv) Comparison of options: PARAMETER AL59 (equal diameter to ACSR Zebra) AL59 (equal weight to ACSR Zebra) 1) Type 61/ /3.50 2) Diameter (mm.) ) Weight (kgs./km.) ) Cross section area (sq. mm.) 5) Resistance 20 0 c) (ohms/km.) ) UTS (KN) ) Wind Span (meters) ) Ampere Capacity
9 What GETCO is doing for new lines? (220 kv) Ultimate comparison with ACSR Zebra: PARAMETER ACSR Zebra AL59 (equal weight to ACSR Zebra) 1) Resistance 20 0 c) (ohms/km.) ) A.C. Resistance (@ maximum operating Temp.) 3) Ampere Capacity (AT 40 0 c) 4) Power Transfer capability in p.f per ckt. 5) Net Power Transfer for 100 km. line 0 c 0 c MW 373 MW 175 MW 350 MW
10 What GETCO is doing for new lines? (220 kv) Changes adopted to satisfy Tower Spotting Data: Options to counter higher sag at full temperature (95 0 c), 1) Reduction of Normal span 2) Use of extension permanently Practice adopted by GETCO 1) Use of extension permanently lesser cost & additional margin available for ground clearance. 2) Reduction in Maximum wind span to attend wind load increased due to diameter increase.
11 PROJECT COST (220 kv) ACSR Zebra conductor AL59 with +3 meter extension AL59 with reduced normal span Project Cost % %
12 What GETCO is doing for new lines? (220 kv) Conclusion: Double the Ampere Capacity & Net power transfer capacity by addition of appx. 10% to project cost and without operating line at excessive higher temperature. Low resistance compared to ACSR Zebra even at rated Temperature results in to lower loss for same power transfer & do not aggravate % Voltage Regulation. No special erection methodology, special tools tackles, special design Hardwares & Accessories required. Indigenous supply available for conductor and hardwares.
13 What GETCO is doing for new lines? (400 kv) Adopted AL59 for 400 kv New Lines. Options Available 1) Equal Diameter to ACSR Moose 2) Equal Weight to ACSR Moose Adopted - Equal Diameter to ACSR Moose.
14 What GETCO is doing for new lines? (400 kv) Comparison among options: PARAMETER AL59 (equal diameter to ACSR Moose) AL59 (equal weight to ACSR Moose) 1) Type 61/ /3.89 2) Diameter (mm.) ) Weight (kgs./km.) ) Cross section area(mm 2 ) ) Resistance 20 0 c) (ohms/km.) ) UTS (KN) ) Ruling Span(Sag-Tension) ) Wind Span
15 What GETCO is doing for new lines? (400 kv) Ultimate comparison with ACSR Moose: PARAMETER ACSR Moose AL59 (equal diameter) 1) Resistance 20 0 c) (ohms/km.) 2) A.C. Resistance (@ maximum operating Temp.) c 0 c 3) Ampere Capacity (AT 40 0 c) (130% higher) 4) Thermal Power Transfer capability in MW per ckt. (p.f. 0.95, factor 0.9) 936 MW 1220 MW (130% higher) 6) Project Cost 100% %
16 What GETCO is doing for new lines? (400 kv) How AL59 suited for decision making: Factors AL59 suitability Current capacity requirement Project time Efficiency Satisfy Sag-Tension with existing Tower Spotting Data Dependency for Hardware & Accessories Competency of erection Project cost Increased 30% with moderate Temperature rise (95 ⁰C) Suited to existing tower design Low I 2 R losses Satisfied with normal tower and by limiting the ruling span matching with actual field observation Adequate Indigenous manufacturers Does not require special skill or T&P Increases by 6-8% appx.
17 What GETCO is doing for new lines? (400 kv) Thermal capacity increased by 30% at increase of project cost 6-8% As the Sag at maximum operating temperature is increased, ruling span is reduced by appx. 7%. By retaining wind and weight span additional benefit of reduction in vertical load & longitudinal load added FOS for existing tower design.
18 CONDUCTOR COST Conductor Cost (Lac Rs./km.) Comparison ACSR Zebra ** ACSR Moose ** AL59 (61/3.50) % of Zebra 104.5% of Moose
19 GETCO Expectations Indigenous manufacturers conductor, hardware Availability of erection agencies Indigenous testing agencies Innovative erection technology e.g. live line Optimum cost
20 Thank You
OTAHUHU-MANGERE-ROSKILL- HEPBURN ROAD 110 KV CIRCUITS
NORTH AUCKLAND AND NORTHLAND GRID UPGRADE PROJECT ATTACHMENT J OTAHUHU-MANGERE-ROSKILL- HEPBURN ROAD 110 KV CIRCUITS UPGRADE WITH HIGH TEMPERATURE LOW SAG CONDUCTOR September 2007 Contents 1 INTRODUCTION
More informationEnhancement of Power Transfer Capability of Existing 400kV Transmission Lines
558 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 22 Enhancement of Power Transfer Capability of Existing 4kV Transmission Lines Rajiv Gandhi, Anish Anand, Y. K. Sehgal, M. Krishnakumar and Anand Mohan Abstract--The
More informationHow the choice of transmission conductor can reduce greenhouse gas emissions.
How the choice of transmission conductor can reduce greenhouse gas emissions. What is the scope of the impact? Complete conversion of the US grid to efficient conductor would eliminate 44 million metric
More informationLine using HTLS Conductors to increase
Upgradation of 132kV Transmission Line using HTLS Conductors to increase the load transfer capacity. By Srikrushna S. Navlakhe Executive Engineer, EHV Construction cum Operation and Maintenance Zone, MSETCL,
More informationTransmission Corporation of Telangana, Jawaharlal Nehru Technological University Hyderabad
ENHANCEMENT OF POWER TRANSFER CAPABILITY OF TRANSMISSION LINES USING HTLS CONDUCTOR 1 M.SHESHAGIRI, 2 B.V.SANKER RAM Transmission Corporation of Telangana, Jawaharlal Nehru Technological University Hyderabad
More informationHigh-Temperature Low Sag (HTLS) conductors. for easy Upgrading of Overhead Transmission Lines
Gap-type conductor High-Temperature Low Sag (HTLS) conductors for easy Upgrading of Overhead Transmission Lines J-Power Systems (JPS) is a joint-venture of HITACHI CABLE and SUMITOMO ELECTRIC INDUSTRIES
More informationNEW TREND ON TRANSMISSION POWER LINES AND RELATED STRINGING EQUIPMENT DEVELOPMENT
NEW TREND ON TRANSMISSION POWER LINES AND RELATED STRINGING EQUIPMENT DEVELOPMENT Background Several regions of the world are facing severe pressure on transmission line infrastructure, while the trends
More informationEfficiency, Capacity, Reliability AND Cost-Effective Carbon Reductions: The Multiple Benefits of High Performance Transmission Conductors (HPTC)
Efficiency, Capacity, Reliability AND Cost-Effective Carbon Reductions: The Multiple Benefits of High Performance Transmission Conductors (HPTC) WHY ARE WE HERE? The Transmission System: The Backbone of
More informationUNIVERSITY OF NAIROBI
UNIVERSITY OF NAIROBI COLLEGE OF ARCHITECTURE AND ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING PROJECT TITLE: UPRATING OF TRANSMISSION LINES-A CASE STUDY OF 132KV DANDORA JUJA RD LINES
More informationTHE PROTEAN AND POC-MAST DESIGN
THE PROTEAN AND POC-MAST DESIGN Contents 1. The changing landscape of generation for power transmission and distribution. 2. The Holford rules and recommendations for OHL routing and design. 3. The current
More informationCONTENTS. iii. Foreword Preface Chapter 1- Design Parameters for Transmission Lines
CONTENTS Foreword Preface Chapter 1- Design Parameters for Transmission Lines 1.1 Introduction 1.2 Mechanical Design 1.2.1 Wind Speed 1.2.2 Maximum Temperature of Current Carrying Conductor 1.2.3 Span
More informationHow Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the Smart Grid
CIGRE US National Committee 2013 Grid of the Future Symposium Boston, Massachusetts October 2013 How Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the Smart Grid Dave Bryant,
More informationTECHNICAL BRIEF OKLAHOMA GAS & ELECTRIC (OG&E) FIVE TRIBES PECAN CREEK 161 KV LINE
Company: Oklahoma Gas & Electric (OG&E) is a regulated electric utility serving more than 800,000 retail customers in Oklahoma and western Arkansas, and a number of wholesale customers throughout the region.
More informationEngineering Considerations. Glenn Stapleton - Senior Electrical Design Engineer Lines
Engineering Considerations Glenn Stapleton - Senior Electrical Design Engineer Lines Overview Transmission line terminology and concepts Types of clearances Electrical safety considerations in co-use Underground
More informationStudy on Economic Partnership Projects. in Developing Countries in FY kV Lines in West Java, in Indonesia SUMMARY.
Study on Economic Partnership Projects in Developing Countries in FY2007 Study on Upgrading Transmission Capacity of Existing 500kV Lines in West Java, in Indonesia SUMMARY March 2008 Tokyo Electric Power
More informationMINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates
MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment
More informationDistribution lines Overload Control to Increase Reliability and Power Loss Reduction
Distribution lines Overload Control to Increase Reliability and Power Loss Reduction SHRIRANG KARANDIKAR Vice President (Business Development) Kalpataru Power Transmission Ltd. Santacruz (East), Mumbai-400055
More informationACCC. Aluminum Conductor Composite Core. High Tension Low Sag Conductors
RELATIVE TO CONVENTIONAL CONDUCTORS Up to Twice the Current Carrying Capacity Greater & Reduced Sag Reduced Line Losses by 25% to 40% or more Increased Spans on Fewer & Shorter Structures High Resistance
More informationMETRO NORTH TRANSMISSION STUDY ELECTRIC AND MAGNETIC FIELD PROFILES (VILLAGE OF ANMORE)
METRO NORTH TRANSMISSION STUDY ELECTRIC AND MAGNETIC FIELD PROFILES (VILLAGE OF ANMORE) File: T2016-6004 METRO NORTH TRANSMISSION STUDY ELECTRIC AND MAGNETIC FIELD PROFILES METRO NORTH TRANSMISSION STUDY
More informationPower System Analysis I TRANSMISSION LINE PARAMETERS
Power System Analysis I TRANSMISSION LINE PARAMETERS Components of Overhead Lines Transmission Line Parameters An overhead transmission line consists of conductors, insulators, support structures, and,
More information2 Pole 1222MVA Turbo-Generator & 4 Pole 1690MVA Turbo-Generator
2 Pole 1222MVA Turbo-Generator & 4 Pole 1690MVA Turbo-Generator 27. August, 2008 Generator Design Team Chong Whie Cho 2008 CIGRE SESSION 42, Paris CONTENTS Introduction 2-Pole 1222MVA Generator - Specifications
More informationUnderground Cable Thermal Analysis Case Study
Underground Cable Thermal Analysis Case Study Authors - Chulanga Niriella - B.Sc (Eng) Hons, AMIESL chulanga.niriella@gmail.com Nadeera Wijesinghe - M.Sc., B.Sc (Eng) Hons, PMP, AMIESL nadeerawije@gmail.com
More informationHIGH PERFORMANCE OVERHEAD LINE CONDUCTORS TO UPGRADE YOUR SYSTEM
HIGH PERFORMANCE OVERHEAD LINE CONDUCTORS TO UPGRADE YOUR SYSTEM ACPR LO-SAG CONDUCTOR UPGRADE YOUR INTERNAL BACKBONE AND CROSS-BORDER CAPACITY The innovative ACPR LO-SAG is much lighter & stronger, dispatching
More informationProtecting. Grid. Integrity. More amps, more confidence. 3M Aluminum Conductor Composite Reinforced (ACCR) High-capacity transmission conductor
3M Aluminum Conductor Composite Reinforced (ACCR) High-capacity transmission conductor Metric Units Protecting Grid Integrity More amps, more confidence 3 3M Aluminum Conductor Composite Reinforced In
More informationSERTP rd Quarter Meeting
2015 SERTP SERTP 2015 3 rd Quarter Meeting 2nd RPSG Meeting September 24 th, 2015 APC Headquarters Birmingham, AL 2015 SERTP Process Information The SERTP process is a transmission planning process. Please
More informationSmart initiatives in Transmission System. Dr Shekhar Kelapure PRDC, Bangalore
Smart initiatives in Transmission System Dr Shekhar Kelapure PRDC, Bangalore Overview Introduction Objectives Challenges Technologies Conclusions Page #2 Why Smart Transmission Grids (STG)? Improve grid
More informationSPIRAL VIBRATION DAMPERS FOR AAC, AAAC, ACSR, COPPER, SC/AC & SC/GZ CONDUCTORS. Part Number
SPIRAL VIBRATION DAMPERS FOR AAC, AAAC, ACSR, COPPER, SC/AC & SC/GZ CONDUCTORS Made from high impact, UV resistant, polyvinyl chloride (PVC), they are non-corrosive and do not abrade the conductor or require
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES TWIN AL59 CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES TWIN AL59 CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS
More informationCONFERENCE ON TRANSMISSION & DISTRIBUTON MR N C VENUGOPAL TRANSMISSION SECTOR GROWTH & CHALLENGES. DATE 2 ND NOVEMBER 2012
CONFERENCE ON TRANSMISSION & DISTRIBUTON MR N C VENUGOPAL TRANSMISSION SECTOR GROWTH & CHALLENGES. DATE 2 ND NOVEMBER 2012 TRANSMISSION SECTOR GROWTH HIGHLIGHTS Source - POWERLINE Transmission line length
More informationHigh Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK
High Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK Definitions Transmission Line Arresters Backflashover Occurs when lightning strikes the tower structure or overhead
More informationOHL AC Cable DC Cable Submarine
OHL AC Cable DC Cable Submarine HVAC Innovative Applications Focus on reliability and safety From high energy city links to regional reinforcements John Owen Business Development Manager Nexans - Land
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES-AL 59 CONDUCTOR FOR 220 KV TRANSMISSION LINE GETCO/E/TS
More informationValmont India - Utility UTILITY POLES
Valmont India - Utility 1 UTILITY POLES Introduction to Utility Poles 2 Traditionally lattice towers common for high voltage transmission lines. Use of steel poles started in late 1960s in US with extensive
More informationELECTROMONTAJ S.A. 68 years in Power Transmission
ELECTROMONTAJ S.A. 68 years in Power Transmission 1, Candiano Popescu street, district 4, Bucharest, 040581 elmbuc@electromontaj.ro www.electromontaj.ro ELECTROMONTAJ S.A. Bucharest ELECTROMONTAJ S.A.
More informationArmor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS
Transmission: Section 1 NOMENCLATURE Single Support and Double Support : Identified by S and D appearing in the length column on the catalog page. Should the maximum distance between tied supports exceed
More informationQuintas & Quintas Group
Electric Conductors Quintas & Quintas Group Index Quintas & Quintas and Solidal 2 Bare Conductors l uminium Conductors for overhead lines 3 l uminium loy Conductors for overhead lines 4 uminium Conductors
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More information026-2 : 1996 CEB STANDARD
026-2 : 1996 CEB STANDARD COMPRESSION CONNECTORS & TERMINATIONS FOR OVERHEAD LINE CONDUCTORS CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does
More informationHow Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the Smart Grid. D.C. BRYANT 1 CTC Global Corporation United States
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium How Aerospace Technology is Improving the Efficiency, Capacity and Reliability of the
More informationWisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power
Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that
More informationARMOR-GRIP Suspension: Double
: Double For Line Angles Between 30 and 60 ACSR, All-Aluminum, Aluminum Alloy, AWAC Compacted All-Aluminum Compacted ACSR, ACSS, ACSS/TW Range AGS s AGS AGS s & Min. Max. Nominal Conductor Size s Per Set
More informationDesign considerations and performance evaluation of EHVtransmission lines in India
Journal of Scientific & Industrial Research Vol. 74, February 2015, pp. 117-122 Design considerations and performance evaluation of EHVtransmission lines in India T S Kishore* and S K Singal Alternate
More informationHigh Voltage Surge Arresters Buyer s Guide Section Line Surge Arrester PEXLINK
High Voltage Surge Arresters Buyer s Guide Section Line Surge Arrester PEXLINK Line surge arresters PEXLINK The concept Both large and small public/private utility owners of transmission systems face a
More informationOverhead transmission lines Spacers
= SVENSKA KRAFTNÄT SWEDISH NATIONAL GRID UNIT, BUSINESS AREA AEL, Asset Management Lines OUR REFERENCE TR05-08E DATE 2016-06-09 CONSU12TATIONS TECHNICAL GUIDELINE REVISION 3 APPROVED Overhead transmission
More informationModification Method of Back-up Roll Bearing by Replacing Oil Film Bearing with Rolling Bearing
TECHNICAL REPORT Modification Method of Back-up Roll Bearing by Replacing Oil Film Bearing with Rolling Bearing J. KUBO N. SUZUKI As back-up roll s in rolling mills must support several thousand tons of
More informationBolt resistances: Class 10.9 Csk TCB: Non-preloaded using S275
Non-preloaded using S275 Single shear Double shear d A s F t,rd F v,rd 2 x F v,rd mm mm 2 kn kn kn 12 84.3 42.5 28.7 57.3 16 157 79 62.8 125.6 20 245 123 98 196 22 303 153 121 242 24 353 178 141 282 27
More informationAAAC - ASTM - B All Aluminium Alloy Conductor
AAAC - ASTM - B All Aluminium Alloy Conductor Eland Product Group: A4A APPLICATION AAAC is used as a bare overhead conductor for power transmission and distribution lines, on aerial circuits that require
More informationShunt reactors Proven history for future success
P OW E R T R A N S FO R M E R S Shunt reactors Proven history for future success 2 SHUNT REACTORS PROVEN HISTORY FOR FUTURE SUCCESS 3 Shunt reactors an investment for today and for the future Improving
More informationField Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI
Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and
More informationWorld s Largest Air-cooled Turbogenerator in operation
Titre de la diapositive! Paragraphe World s Largest Air-cooled Turbogenerator in operation Yves Sabater Table of content! Turbogenerators cooling technologies State of the art! 400 MVA air-cooled generator
More informationChristian Ohler, ABB Switzerland Corporate Research Physics of Electric Power Systems. ABB Group August 1, 2012 Slide 1
Christian Ohler, ABB Switzerland Corporate Research Physics of Electric Power Systems ABB Group August 1, 2012 Slide 1 Purpose of this Presentation Describe power systems from a physicists point of view
More informationElectrical Power Distribution (CDEE)
Lecturer: Ing. Martin Paar, Ph.D. paar@feec.vutbr.cz,www.ueen.feec.vutbr.cz Transmission and distribution networks in the Czech Republic Electrical Power Distribution (CDEE) e-power - Inovace výuky elektroenergetiky
More informationTHERMOLIGN Products for 3M Aluminum Conductor Composite Reinforced (3M ACCR)
Products for 3M Aluminum Conductor Composite Reinforced (3M ACCR) July 2015 History of Hardware at PLP Preformed Line Products has been involved with the design, testing and production of hardware and
More informationGSA Series Formed Wire Suspension
GSA Series Formed Wire Suspension Formed Wire Suspension Unit AFL is a renowned manufacturer of aluminum conductor accessories, manufacturing numerous products for the electric utility industry since the
More informationImpacts of MISO DPP-2016-February (West, ATC, MI, South) Projects on PJM Facilities
Impacts of MISO DPP-2016-February (West, ATC, MI, South) 1. MISO generators studied: Projects on PJM Facilities Net MW size (Summer) Net MW size (Winter) Service DPP Project Type Region Fuel Type POI J432
More information477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength
3M 477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength Principal Investigator: Dr. Kamal Amin Reviewed by: Dr. Colin McCullough Date of Report: June 1, 2003
More informationWheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation
Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction
More informationSSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL. Estimation and Costing & Utilization of Electrical Energy
1 SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL Estimation and Costing & Utilization of Electrical Energy Estimation and Costing & Utilization of electrical Energy Estimation
More informationSYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test)
ANNEXURE I SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) Paper I & Paper II for General Category of S.C.C. Examination Paper I & Paper
More informationLegal Statement. M E T A L S Research and Consulting
Legal Statement The purpose of this presentation is to guide ICA programs and provide members information to make independent business decisions. Copyright by MetalsPlus Research & Consulting. All rights
More informationFalcon-Midway 115 kv Line Uprate Project Report
Falcon-Midway 115 kv Line Uprate Project Report 12/1/2008 1 Background The function of this project is to uprate the 26.7 miles of Tri-State s 115 kv line between Midway and Falcon substations from 50
More informationVolume-III : Section-I 370 Technical Specifications
Volume-III : Section-I 370 TECHNICAL SPECIFICATION-PIERCING INSULATOR 5.1 Insulation Piercing Connectors (IPC) 5.1.1 Insulation Piercing Connectors (IPC) are used for making Tee/Tap-off/Service connectors
More informationSUBSTATION DESIGN TRAINING
2017 SUBSTATION DESIGN TRAINING ADVANCE ELECTRICAL DESIGN & ENGINEERING INSITUTE (Registered under MSME& An ISO 9001:2008 CERTIFIED) Training Centre: Advance Group of Institutions C-1, Second Floor Near
More informationKey-Words : Eddy Current Testing, Garter Spring, Coolant Channels, Eddy Current Test Coil Design etc.
More Info at Open Access Database www.ndt.net/?id=15054 Development of Eddy Current Test Technique for Detection of Garter Springs in 540 and 700 MWe Pressurized Heavy Water Reactors Arbind Kumar AFD,
More informationPAC TRAINING PUMP MOTORS
PAC TRAINING PUMP MOTORS 1 Basics Magnet supported from above N S N S Since unlike poles repel each other, the magnet will rotate Stationary Magnet 2 Basics N S Stationary Magnet 3 Basics N N S S Stationary
More informationNatural Ester Transformer Fluid Overview. Cargill India Pvt Ltd Naveen Jain
Natural Ester Transformer Fluid Overview Cargill India Pvt Ltd Naveen Jain 1 Global producer of natural and synthetic ester transformer fluids Examples of how utilities worldwide are using FR3 fluid to
More informationItem L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.)
Village Hydro Specifications Line Distribution Description of Requirement Item L.1 Voltages 1. The consumer voltage must be between +10% and -10% of the nominal national voltage (nnv.) Recommendation 2.
More informationTENSION CLAMPS AND JOINTS. General Wedge tension clamp without jumper guide, for aluminium based conductors... 79
73 Contents General.................................................................................................. 74 Wedge tension clamp without jumper guide, for aluminium based conductors...........................
More informationHealth Monitoring of Overhead Power Transmission Line:
Vienna 26-27 January, 2004 Health Monitoring of Overhead Power Transmission Line: User Needs Dmitri SNEGOVSKI (Mech. Eng., PhD student) Transmission and Distribution of Electrical Energy University of
More informationODISHA POWER TRANSMISSION CORPORATION LIMITED VOL-II (PART-II)
ODISHA POWER TRANSMISSION CORPORATION LIMITED VOL-II (PART-II) Package CPC-79/2014-15: Construction of 220kV Double Circuit Transission line on DC tower fro 400/220 KV Grid S/S, Pandiabil (Benapanjari)
More informationDynamic Line Rating as a Means to Enhance Transmission Grid Resilience
Dynamic Line Rating as a Means to Enhance Transmission Grid Resilience McCall, J. Goodwin, T. Lindsey Manufacturing Tip Goodwin Consulting LLC USA Canada CIGRE US National Committee 2015 Grid of the Future
More informationSystem Impact Study Report
Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS
More informationTotal Ex. Tax/VAT. (Rs.) (if any) in Rs. (Bought out/direct) length 587M 226M
ORISSA POWER TRANSMISSION CORPORATION LIMITED Supply & Laying of 132 KV XLPE Double Circuit (4 cable per Circuit including one spare) underground 1000 Sq. mm annealed Copper XLPE EHV Cable with Associated
More informationCurrent collecting characteristics of catenary with non-tension contact wires
Current collecting characteristics of catenary with non-tension contact wires T. Hamada, A. Suzuki & T. Shimada Railway Technical Research Institute, Japan Abstract Feeder cables are additionally installed
More informationGrid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom
Grid code Compliance and Renewable Energy Projects Mick Barlow, Business Development Director, S&C Electric, United Kingdom Why Grid Codes? Permit the development of and operation of an efficient and economical
More informationAdvice Pertaining to ERC Resolution No.16 and the Role of Hybrid Generation Advice with respect to specific questions from PIPPA
Advice Pertaining to ERC Resolution No.16 and the Role of Hybrid Generation Advice with respect to specific questions from PIPPA George Horvath george.horvath@aecom.com Month Day, Year Part A Introduction
More informationFull-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA
Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA Philippe Maibach, Alexander Faulstich, Markus Eichler, Stephen Dewar ABB Switzerland Ltd CH-5300 Turgi, Switzerland Phone: +41
More informationNext Generation Drive Train Superconductivity for Large-Scale Wind Turbines*
Next Generation Drive Train Superconductivity for Large-Scale Wind Turbines* Applied Superconductivity Conference, Portland, Oregon October 11th, 2012 R. Fair, W. Stautner, M. Douglass, R. Rajput-Ghoshal,
More informationTECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF HARDWARE & ACCESSORIES ACSR MOOSE CONDUCTOR FOR TRANSMISSION LINE GETCO/E/TS
More information/ I S S : / S T S I
Agenda Electrical Transformers (Quality Control) Order Obtaining BIS Licence Requirements of Guidelines / IS 1180-1: 1: 2014 / STI Concerns in Getting BIS Licence Experience with BEE Regulations Recommendations
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationLive-line transmission lines upgrade projects. First-in-Africa project
Live-line transmission lines upgrade projects First-in-Africa project Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract This paper covers live-line
More informationDO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.
DO-III DO-III Fuse Holder TPL 44-835, May 2000, Page 1 of 4 General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder ABB Inc. General Description The ABB DO-III fuse holder is a draw
More informationFeasibility Study Report
Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Chester County, SC Total Output Requested By Customer: 74.5 MW Commercial Operation Date Requested By Customer: 1/7/2019 Feasibility
More informationGENERAL ATOMICS ITER CEnTRal SolEnoId ModulE FabRICaTIon September 2018
GENERAL ATOMICS ITER Central Solenoid Module Fabrication September 2018 ITER Central Solenoid The heart of the international fusion energy device The Central Solenoid (CS) is the heart of ITER. The 5-story,
More informationS840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en
Snap-action switches S80, S85, S86 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D0.en Snap-action switches, S80, S85, S86 Series Single-break
More informationREDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION
REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi
More informationELECTRICIANS REGULATIONS EXAMINATION 25 June 2011
ER42 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 Int QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationTECHNICAL SPECIFICATION FOR SHACKLE HARDWARE FITTINGS SUITABLE FOR TENSION STRING TO BE USED FOR 11KV LINE
TECHNICAL SPECIFICATION FOR SHACKLE HARDWARE FITTINGS SUITABLE FOR TENSION STRING TO BE USED FOR 11KV LINE The hardware fittings suitable for tension string to be used for 11KV consisting of following
More informationACSR- ROPES Aluminium wire steel reinforced (ACSR conductor)
ACSR- ROPES Aluminium wire steel reinforced (ACSR conductor) The steel reinforced aluminium conductor consists of seven or more aluminium wires applied in concentric layers over a steel core made of one
More informationImproving Power System s Performance with Line Arresters
Arr ArresterWorks Improving Power System s Performance with Line Arresters Jonathan Woodworth April 208 Copyright 208 ArresterWorks ArresterFacts 043 Improving Power System s Performance with Line Arresters
More informationLV Capacitor CLMD03 Power Module Instruction manual
LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...
More information25 kv Apparatus Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More information477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength
3M 477-kcmil, 3M Brand Composite Conductor Compression Dead End Evaluation Mechanical Holding Strength Principal Investigator: Dr. Kamal Amin Reviewed by: Dr. Colin McCullough Date of Report: June 1, 2003
More informationJDR PRODUCT APPLICATIONS. MCE Deepwater Development 2017
Innovative 72 kv Wet-Design Cables for Dynamic Deepwater Power Umbilicals James Young, Chief Technology Officer JDR Cable Systems Ltd NH GRAND HOTEL KRASNAPOLSKY AMSTERDAM 3-5 APRIL 2017 JDR PRODUCT APPLICATIONS
More informationGENERAL ATOMICS ITER CENTRAL SOLENOID MODULE FABRICATION
GENERAL ATOMICS ITER CENTRAL SOLENOID MODULE FABRICATION January 2018 ITER Central Solenoid The heart of the international fusion energy device The Central Solenoid (CS) is the heart of ITER. The 5-story,
More informationNew Frontier in Energy, Engineering, Environment & Science (NFEEES-2018 ) Feb
RESEARCH ARTICLE OPEN ACCESS DESIGN AND IMPACT ANALYSIS OF A ROLLCAGE FOR FORMULA HYBRID VEHICLE Aayush Bohra 1, Ajay Sharma 2 1(Mechanical department, Arya College of Engineering & I.T.,kukas, Jaipur)
More informationVORTX Vibration Damper
Product Identification 1 2 3 5 4 NOMENLTURE 1. lamp & Keeper: The lamp has an extruded hook shaped profile to hang onto the cable or conductor while tightening the keeper. Together, the aluminum keeper
More informationArcelorMittal Europe - Long products Sections and Merchant Bars HISTAR. Innovative high strength steels for economical steel structures
ArcelorMittal Europe - Long products Sections and Merchant Bars HISTAR Innovative high strength steels for economical steel structures Shanghai World Finance Center, P.R. China Innovative high strength
More information