A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

Size: px
Start display at page:

Download "A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution"

Transcription

1 A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical.1_ UFSS#p A:_. DAVID/ IC, L re Mechanical Civil Protection & Control an LAND& 4^ Transmission & Distribution Telecontrol System Planning REPLACE 230 KV CIRCUIT BREAKER Sunnyside Terminal Station April 2010 newfoundland labrador h dro a nalcor energy company

2 Table of Contents 1 INTRODUCTION 1 2 PROJECT DESCRIPTION 3 3 EXISTING SYSTEM : Age of Equipment or System : : Major Work and/or Upgrades Anticipated Useful life Maintenance History Outage Statistics Industry Experience Maintenance or Support Arrangements Vendor Recommendations Availability of Replacement Parts Safety Performance Environmental Performance Operating Regime 8 4 JUSTIFICATION Net Present Value Levelized Cost of Energy Cost Benefit Analysis Legislative or Regulatory Requirements Historical Information Forecast Customer Growth Energy Efficiency Benefits Losses during Construction Status Quo Alternatives 10 5 CONCLUSION Budget Estimate Project Schedule 13 Newfoundland and Labrador Hydro

3 1 INTRODUCTION Newfoundland and Labrador Hydro (Hydro) owns and operates 54 terminal stations in the Island Interconnected System. A critical element in a terminal station is the circuit breaker. The circuit breakers protect the transformers and transmission lines from overloading. They operate automatically in the same way as circuit breakers or fuses operate to protect the circuits in a normal household electrical system. The circuit breaker senses excessive current and uses a compressed spring arrangement to open the breaker contacts and cut off the power flow to the circuit. This protects the electrical equipment from damage caused by high currents that occur during an electrical fault. The circuit breakers that operate at 230 kv interrupt currents up to 4,000 Amperes. In the Island Interconnected System, Hydro owns and operates kV circuit breakers of which 53 are air blast circuit breakers. Figure 1 shows a picture of a typical 230 kv air blast circuit breaker in use on the Island Interconnected System. When the Island Interconnected System was originally constructed, the standard technology for circuit breaker design was air blast technology. As the electrical utility industry developed, advances in circuit breaker technology changed from air blast technology to Sulphur Hexafloride (SF 6) technology. The main difference in the two technologies is that air blast circuit breakers use a compressed air system to operate whereas SF6 circuit breakers use an inert gas. An inert gas is a chemically stable gas that can be used to extinguish electrical arcing at high temperatures. Since the mid 1980's, SF6 gas technology has been used. The SF6 gas is contained inside the sealed chamber of the breaker. This inert gas extinguishes the arc across the breaker contacts when the circuit is being interrupted. The advancement to SF6 gas means that breakers can be self contained and do not need a centralized compressed air supply to operate as required by air blast breakers. Also, SF6 circuit breakers have the ability to Newfoundland and Labrador Hydro Page 1

4 interrupt larger currents and withstand higher voltages than the air blast circuit breakers. The utility industry is switching to SF6 technology. The 230 kv circuit breakers that required replacement on the Hydro system over the last twenty years have been replaced by SF6 gas breakers. Figure 1: Typical 230 kv Air Blast Circuit Breaker Newfoundland and Labrador Hydro Page 2

5 2 PROJECT DESCRIPTION This project consists of the replacement of the existing 230 kv air blast circuit breaker L03L06 at the Sunnyside Terminal Station with a new 230 kv SF6 circuit breaker. The scope of the work involves the following: Removal and retirement of the existing breaker Purchase and installation of a new breaker Supervision of the factory acceptance test of the new breaker Construction of a new foundation for the circuit breaker structure Installation of new protection equipment and control cables Commissioning of the new breaker. Newfoundland and Labrador Hydro Page 3

6 3 EXISTING SYSTEM The Sunnyside Terminal Station (Sunnyside) is located just off the Trans Canada Highway near the junction to the community of Sunnyside. The terminal station is approximately 20 kilometers east of Clarenville. Sunnyside is one of Hydro's major terminal stations. It is the termination point for the 230 kv transmission lines TL-202 and TL-206 from Bay d'espoir. It is the focal point for transmission of power to the Avalon Peninsula. The 230 kv transmission line TL-203 originates at Sun nyside and transmits power to the Western Avalon Terminal Station. Also, the 230 kv transmission line TL-207 transmits power from Sunnyside to the Come By Chance oil refinery. Electrical power to the Burin Peninsula is supplied from the Sunnyside Terminal Station via 138 kv transmission lines TL-212 and TL Also, Sunnyside supplies power to Clarenville and surrounding area via Newfoundland Power's transmission system. Figure 1 shows part of the Island Interconnected System and indicates the location of Sunnyside. CLARENVILLE M MILTON \ Figure 2: Portion of the Island Interconnected System showing Sunnyside At Sunnyside, there are five 230 kv air blast circuit breakers. L03L06 is a 230 kv circuit breaker used as part of the protection scheme at the terminal station for transmission lines Newfoundland and Labrador Hydro Page 4

7 TL-203 and TL-206. This breaker has deteriorated and requires replacement in order for Sunnyside to continue its vital role as part of the Island Interconnected System. Figure 3 shows some of the deterioration of L03L06. Figure 3: Corrosion on Breaker at Sunnyside 3.1 Age of Equipment or System Circuit breaker L03L06 was manufactured by Brown Boveri and was installed in It is 44 years old. Newfoundland and Labrador Hydro Page 5

8 3.2 Major Work and/or Upgrades An overhaul of this breaker was done in 2000 at a cost of $115,800. A complete relubrication was done on the breaker in 2007 at a cost of $19, Anticipated Useful Life The anticipated useful life of a power circuit breaker is 30 years. 3.4 Maintenance History The maintenance history for Breaker L03L06 is shown in the following Table 1. Table 1: Maintenance History Preventive Maintenance Corrective Maintenance Total Maintenance Year ($000) ($000) ($ 000) Outage Statistics Table 2 below lists the previous 5 year average for the performance of 230 kv Air Blast Breaker. A comparison is made between Hydro's last 5 year performance to the latest CEA five year average ( ). There has been one forced outage of the Sunnyside L0306 circuit breaker in the last 15 years. There have been 25 forced outages due to problems with the air blast breakers over Newfoundland and Labrador Hydro Page 6

9 the last 15 years, throughout the Hydro system. 230 kv Air-Blast Breakers ( ) CEA 230 kv Air-Blast Breakers ( ) Table 2: Outage Statistics Number of Forced Frequency Outages (per a) 1 Unavailability (percent) Frequency (per a) is the number of failures per year. 2 Unavailability is the percent of time per year the unit is unavailable. 3.6 Industry Experience Through consultations with other Canadian utilities, Hydro has confirmed that the 230 kv air blast circuit breakers of other utilities present similar operational problems as those on the Hydro system. Such problems are corrosion, leaking seals, porcelain failures, malfunctioning valves and unreliable controls. These operational problems begin to occur when the breakers have reached between 20 and 30 years of service. In addition, Hydro consulted with the manufacturer, Asea Brown Boveri who confirmed the existence of the above mentioned problems are typical among utilities using these breakers. Other utilities are either replacing or upgrading the air blast circuit breakers. 3.7 Maintenance or Support Arrangements Normal operation and maintenance work is performed by Hydro Operations personnel. 3.8 Vendor Recommendations The vendor, Asea Brown Boveri, recommends replacing the breaker because of the condition of the tank. If the tank was in a better condition the breaker could be upgraded. Newfoundland and Labrador Hydra Page 7

10 3.9 Availability of Replacement Parts Replacement parts for the existing breaker are generally readily available Safety Performance Regular maintenance inspections of the circuit breaker indicate that the compressed air tanks no longer meet current safety codes. The minimum tank wall thickness for this type of breaker under ASME Section VIII Division 1, UG-27 is 3.84 mm. The minimum measured thickness of the tank wall is 2.94 mm Environmental Performance There are no specific environmental issues regarding the air blast breakers Operating Regime Circuit breaker L03L06 is in continuous operation. Newfoundland and Labrador Hydro Page 8

11 4 JUSTIFICATION This project is justified on the requirement to replace failing or deteriorated infrastructure in order for Hydro to provide safe, reliable electrical service. Because of corrosion, the tank walls for circuit breaker L03L06 are not up to industry standards. This creates the risk of a tank rupture which is a major safety and reliability concern. Also, the circuit breaker is 44 years old and beyond its anticipated useful life of 30 years. The only practical option is to replace the breaker. 4.1 Net Present Value A net present value calculation was not required for this project as there is only one viable alternative. 4.2 Levelized Cost of Energy This project does not affect the levelized cost of energy because it does not involve any new sources of generation. 4.3 Cost Benefit Analysis A cost benefit analysis is not required because there are no quantifiable benefits. 4.4 Legislative or Regulatory Requirements There are no legislative and regulatory requirements for this project. Newfoundland and Labrador Hydro Page 9

12 4.5 Historical Information Hydro has not replaced any 230 kv circuit breakers within the past five years. 4.6 Forecast Customer Growth The forecast customer load growth has no affect on this project. 4.7 Energy Efficiency Benefits There are no energy efficiency benefits associated with this project. 4.8 Losses during Construction There are no losses during construction associated with this project. 4.9 Status Quo The status quo is not an option because the circuit breaker has safety and reliability problems Alternatives A repair of the corroded sections on the compressed air tank was considered. This was not possible because the existing tanks are glass lined and any attempt to weld them would damage the lining and further damage the breaker. As well, any attempt to repair the tanks would require a complete disassembly and reassembly of the breaker. The labour and materials costs for this option, plus the outage time required for the work, is expected to Newfound/and and Labrador Hydro Page 10

13 exceed the costs for a replacement by approximately $200,000. Because the major deficiency is in the tanks, it is not cost effective to try to repair the breaker. The most effective means to correct the problem is to completely replace the breaker. Hydro's air blast breaker upgrade program which has been ongoing for the last five years involves upgrade of the interrupters, resistors and capacitors. This type of upgrade is possible only if the breaker tank is in good condition. If the breaker tanks are damaged or corroded then the upgrade option is not practical or feasible. Thus, there are no viable alternatives to correcting the problem described in this proposal other than to replace the breaker completely. Newfoundland and Labrador Hydro Page 11

14 5 CONCLUSION This project is necessary to address the reliability and safety concerns identified on Breaker L03L06 in the Sunnyside Terminal Station. Maintenance inspections have shown that the compressed air tank on the breaker is corroded and the tank walls no longer meet industry standards. Because of the corrosion there is a risk of the tank rupturing and causing a safety hazard. Repair of the breaker is not practical or feasible. The only viable alternative is a complete replacement of the breaker. 5.1 Budget Estimate The budget estimate for this project is shown in Table 3. Table 3: Budget Estimate Project Cost:($ x1,000) Beyond Total Material Supply Labour Consultant Contract Work Other Direct Costs O/H, AFUDC & Escln Contingency TOTAL Newfoundland and Labrador Hydro Page 12

15 5.2 Project Schedule The project schedule is shown in Table 4. Activity Table 4: Project Schedule Milestone Project Start April 2011 Initial Planning and Equipment Tendering August 2011 Equipment Delivery May 2012 Equipment Installation July 2012 Commissioning July 2012 Project In Service August 2012 Project Completion and Close Out December 2012 Newfoundland and Labrador Hydro Page 13

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical vo1e.5s 0j 44, AMY., CK NI r. SIGNATURE Mechanical Civil Protection & Control t^ /DATE 1 o Transmission & Distribution AND Telecontrol

More information

Insulator Replacements

Insulator Replacements A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Insulator Replacements Electrical Mechanical. Civil Protection & Control Transmission & Distribution Telecontrol System Planning HYDRO THE POWER

More information

A REPORT TO. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution. Telecontrol. System Planning

A REPORT TO. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution. Telecontrol. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical 4v ^c 0:01'1 S0^O c.. ^ '^ W E. G. PIERCY i^ x zoto/off/zq,.'ftrif4^#ft^^,' r Mechanical Civil Protection & Control Transmission &

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical 4a >estro Mechanical re *.i Civil f ::^:s '1 E 1 t i^.l. al1.i 2 Or Protection & Control Transmission & Distribution Telecontrol System

More information

A REPORT TO. Electrical. Mechanical. Civil. Transmission & Distribution. System Planning REPLACE UNIT 2 STEAM SEAL REGULATOR

A REPORT TO. Electrical. Mechanical. Civil. Transmission & Distribution. System Planning REPLACE UNIT 2 STEAM SEAL REGULATOR A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical ^ ^^ t wiessio PBG n ^, wl I,,dn,w l.n Mechanical Civil T I.C LINS Protection & Control 41 41 4-01 "i"""11'"" ii. cl u Z`^ M 1K ' ^""

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical Civil Protection & Control S1GNATLJL 2oü 4 "DAT Transmission & Distribution Telecontrol - System Planning OVERHAUL DIESEL

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. - Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. - Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Muskrat Falls Project - Exhibit 114 Page 1 of 47 Electrical Mechanical /''.., Civil Protection & Control - Transmission & Distribution Telecontrol

More information

A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. System Planning. Overhaul Diesel Engines.

A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. System Planning. Overhaul Diesel Engines. A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical ( Protection Civil & Control & Distribution System Planning Overhaul Diesel Engines Various Locations July 2012 newfoundland

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Q^sss^ - Mechanical Civil SIONATURI Zo \r or o', Protection & Control Transmission & Distribution Telecontrol System Planning ARC FLASH

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Transmission & Distribution. Telecontrol.

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Transmission & Distribution. Telecontrol. A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical Civil Protecti on & Contro l MAV1PJ1 Transmission & Distribution Telecontrol System Planning Upgrade Circuit Breakers July

More information

Director Corporate Services & Board Secretary. Newfoundland and Labrador Hydro 2015 Capital Budget Application

Director Corporate Services & Board Secretary. Newfoundland and Labrador Hydro 2015 Capital Budget Application \ I newfoundland labrador k_hy dro a nalcor energy company Hydro Place. 500 Columbus Drive. P.O. Box 12400. St. John's. NL Canada A1B 4K7 t. 709.737.1400 f. 709.737.1800 www.n1h.nl.ca September 12, 2014

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

The Energy Queensland Group Notice of no non-network options

The Energy Queensland Group Notice of no non-network options The Energy Queensland Group Notice of no non-network options 24 September 2018 MCE Mount Crosby East Establish new substation to replace Mount Crosby Substation (SSMTC) Page 1 of 1 DISCLAIMER While care

More information

Experiences in a Motor Protection Retrofit

Experiences in a Motor Protection Retrofit Special Feature by Kyle Craig, Ontario Power Generation Amy Sinclair, Schweitzer Engineering Laboratories, Inc. Experiences in a Motor Protection Retrofit Introduction The initial stage of any project

More information

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned.

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned. \ newfoundland labrador hydro a nalcor energy company Hydro Place. 00 Columbus Drive. P.O. Box 00. St. John's. NL Canada AB K t. 0..00 f. 0..00 www.nh.nl.ca December, 0 The Board of Commissioners of Public

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027)

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) February 2013 Contents I. Introduction 1 II. Status of Electricity Supply and Demand 2 1. Electricity Demand 2 2. Electricity

More information

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 1 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 2 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC

More information

OCTOBER 17, Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC Engineering LLC

OCTOBER 17, Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC Engineering LLC OCTOBER 17, 2018 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC

More information

FORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5

FORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5 ALANNA GILLIS ACTING COMMISSION SECRETARY Commission.Secretary@bcuc.com web site: http://www.bcuc.com SIXTH FLOOR, 900 HOWE STREET, BOX 250 VANCOUVER, BC CANADA V6Z 2N3 TELEPHONE: (604) 660 4700 BC TOLL

More information

Seabrook Substation Reliability Improvement Project

Seabrook Substation Reliability Improvement Project New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability

More information

West Station-West Cañon 115 kv Transmission Project

West Station-West Cañon 115 kv Transmission Project West Station-West Cañon 115 kv Transmission Project Project Sponsor: Additional Project Participants: Project Description: Black Hills Colorado Electric New 115 kv line from West Station to West Cañon

More information

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids Author Company Email Presenter T.A. Messinger BC Hydro toly.messinger@bchydro.com E. Burt BC Hydro ed.burt@bchydro.com P.Glaubitz Siemens

More information

EMERGING REQUIREMENTS

EMERGING REQUIREMENTS Page of 0 EMERGING REQUIREMENTS EXTERNALLY INITIATED PLANT RELOCATIONS THESL distributes electricity to residential, commercial, and industrial customers via overhead and underground infrastructure. This

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

Memorandum. This memorandum requires Board action. EXECUTIVE SUMMARY

Memorandum. This memorandum requires Board action. EXECUTIVE SUMMARY California Independent System Operator Memorandum To: ISO Operations (MRTU) Committee From: Armando J. Perez, Director of Grid Planning cc: ISO Board of Governors ISO Officers Date: April 29, 2005 Re:

More information

Transmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202

Transmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202 Transmission and Distribution Substation Projects Operating Company: Entergy Gulf States - Texas Customer: PID # 202 Funding Project Number: F4PPGS0386 Facility Study for PID # 202: Study for 146 MW Revision

More information

DFO STATEMENT OF NEED REPORT

DFO STATEMENT OF NEED REPORT APPENDIX E DFO STATEMENT OF NEED REPORT Table of Contents 1.0 Executive Summary... 1 2.0 Description of the Area... 2 2.1 Geographic Study Area... 2 2.2 2016 System Configuration... 2 3.0 Area Loading

More information

Ms. Tracey Pennell Senior Counsel Newfoundland and Labrador Hydro P.O. Box St. John's, NL A1B 4K7

Ms. Tracey Pennell Senior Counsel Newfoundland and Labrador Hydro P.O. Box St. John's, NL A1B 4K7 NEWFOUNDLAND AND LABRADOR BOARD OF COMMISSIONERS OF PUBLIC UTILITIES 120 Torbay Road, P.O. Box 21040, St. John's, Newfoundland and Labrador, Canada, AIA 5B2 E-mail: TraceyPennell@nlh.nl.ca 2017-01-27 Ms.

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

June Substation Refurbishment and Modernization. Prepared by: Substatiort Refu14bislrment and Modernization NP 2012 CBA

June Substation Refurbishment and Modernization. Prepared by: Substatiort Refu14bislrment and Modernization NP 2012 CBA 2.1 2012 Substatiort Refu14bislrment and Modernization NP 2012 CBA 2012 Substation Refurbishment and Modernization June 2011 Prepared by: Peter Feehan, P.Eng. A FORTIS COMPANY 2.1 2012 Substation Refurbishment

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2018-04-24 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants Breaking new ground A circuit breaker with the capacity to switch 15 large power plants Helmut Heiermeier, Reto Karrer The power networks that span the landscape and bring electrical energy to cities and

More information

Cromby Units 1 and 2 and Eddystone Units 1 and 2. Deactivation Study

Cromby Units 1 and 2 and Eddystone Units 1 and 2. Deactivation Study Cromby Units 1 and 2 and Eddystone Units 1 and 2 Deactivation Study Original Posting Date: March 2, 2010 Updated May 10, 2010 Updated June 7, 2010 Updated September 7, 2010 General PJM received notice

More information

2011 Substation Refurbishment and Modernization. June 2010

2011 Substation Refurbishment and Modernization. June 2010 Z,1 Substatiort Refurbish~nent and Modernization NP 2011 CBA 2011 Substation Refurbishment and Modernization June 2010 Prepared by: Peter Feehan, P.Eng. 2.1 2011 Substation Refurbishment and Modernization

More information

Supplemental Report on the NCTPC Collaborative Transmission Plan

Supplemental Report on the NCTPC Collaborative Transmission Plan Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for

More information

PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report

PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report 155697 September 2001 Table of Contents DESCRIPTION PAGE 1.0 Introduction 3 2.0 Description of Facilities Included

More information

Upgrade Power Transformers

Upgrade Power Transformers - A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Upgrade Power Transformers Electrical Mechanical I SIGATUREJ Protection & Control / Transmission & Distribution Civil Telecontrol System Planning

More information

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC OCTOBER 22, 2015 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting Emera Maine Representative: Jeffrey Fenn, P.E., SGC

More information

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1 Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland

More information

Umatilla Electric Cooperative Net Metering Rules

Umatilla Electric Cooperative Net Metering Rules Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through

More information

PUD ELECTRIC SYSTEM INTERCONNECTION

PUD ELECTRIC SYSTEM INTERCONNECTION APPENDIX A PROCEDURES & REQUIREMENTS for OKANOGAN PUD ELECTRIC SYSTEM INTERCONNECTION Version 4.0 December 2011 Version 4.0 12/28/2011 Page 1 of 15 TABLE OF CONTENTS DEFINITIONS 1.0 Introduction 2.0 Procedures

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic July 26, 2016 Reliability Analysis Update MetEd Transmission Zone N-1 First Energy Planning Criteria (FERC Form 715): The North Boyertown West Boyertown 69 kv is

More information

REQUEST FOR PROPOSALS FOR THE ESTABLISHMENT OF SOLAR PV POWER PLANT ON BUILD, OWN AND OPERATE BASIS. International Competitive Bidding (ICB)

REQUEST FOR PROPOSALS FOR THE ESTABLISHMENT OF SOLAR PV POWER PLANT ON BUILD, OWN AND OPERATE BASIS. International Competitive Bidding (ICB) REQUEST FOR PROPOSALS FOR THE ESTABLISHMENT OF SOLAR PV POWER PLANT ON BUILD, OWN AND OPERATE BASIS International Competitive Bidding (ICB) Polonnaruwa Solar PV Power Project (10 MWp) Tender No: CEB/EPT/SP/RFP1

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

STAFF REPORT ACTION REQUIRED

STAFF REPORT ACTION REQUIRED STAFF REPORT ACTION REQUIRED Procurement Authorization Amendment Purchase of 18 Forty Foot Low Floor Clean Diesel City Buses Date: July 29, 215 To: From: TTC Board Chief Executive Officer Summary This

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC OCTOBER 22, 2014 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting E M i R t ti Emera Maine Representative: Jeffrey Fenn,

More information

FINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010

FINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010 FINAL FACILITY STUDY 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1 September 10, 2010 I. Introduction This is a revised facility study performed for Transmission Queue Request 2009

More information

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba

More information

Appendix D Black Hills Project Summary

Appendix D Black Hills Project Summary Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain

More information

2016 Load & Capacity Data Report

2016 Load & Capacity Data Report Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation, accuracy, completeness

More information

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In

More information

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008 NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0

More information

NEWFOUNDLAND AND LABRADOR HYDRO. Glossary of Terms

NEWFOUNDLAND AND LABRADOR HYDRO. Glossary of Terms NEWFOUNDLAND AND LABRADOR HYDRO AC See Alternating Current Alternating Current (AC) A continuous electric current that regularly reverses direction, usually sinusoidally. Alternating current is used in

More information

CI Number: ACE CI Page 1 of 9. Title: Metro Voltage Support - Add Capacitor Bank

CI Number: ACE CI Page 1 of 9. Title: Metro Voltage Support - Add Capacitor Bank 216 ACE CI 46587 Page 1 of 9 CI Number: 46587 Title: Metro Voltage Support Add Capacitor Bank Start Date: 215/6 InService Date: 216/12 Final Cost Date: 217/6 Function: Transmission Forecast Amount: 3,373,511

More information

Reliability Analysis Update

Reliability Analysis Update Reliability Analysis Update Transmission Expansion Advisory Committee February 8, 2018 2018 RTEP Analysis Update 2 PSE&G Transmission Zone Transmission Service Update 3 Linden VFT Previous agreements:

More information

Refurbishment and Life Extension of Existing Facilities in Vermont

Refurbishment and Life Extension of Existing Facilities in Vermont Refurbishment and Life Extension of Existing Facilities in Vermont Prepared by Joshua Burroughs, Joanne Hu & Jeff Carrara 2015 Grid of Future Symposium Life Extension Projects in Vermont Highgate Converter

More information

City of Palo Alto (ID # 6416) City Council Staff Report

City of Palo Alto (ID # 6416) City Council Staff Report City of Palo Alto (ID # 6416) City Council Staff Report Report Type: Informational Report Meeting Date: 1/25/2016 Summary Title: Update on Second Transmission Line Title: Update on Progress Towards Building

More information

Selling PFIFFNER in the UK. Paul Haines

Selling PFIFFNER in the UK. Paul Haines Selling PFIFFNER in the UK. Paul Haines Contents Introduction, Country & Market Overview UK. Accessing the Market Critical Success Factors. Developing the Business Together. Proposed Pfiffner Support.

More information

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

Maritime Link. MITC Canada Day March 2015

Maritime Link. MITC Canada Day March 2015 Maritime Link MITC Canada Day March 2015 About Emera $9.85 billion of assets in Canada, United States and Caribbean Algonquin (21.0%) 2 Emera Maine 154,000 customers in Northern, Central and Downeast Maine

More information

Network. ENMAX Power Corporation Network Planning & Design November 4, 2011

Network. ENMAX Power Corporation Network Planning & Design November 4, 2011 Network ENMAX Power Corporation Network Planning & Design November 4, 2011 ENMAX Fast Facts Service area of 1,044 square kilometers 1,738MVA Peak load (2009) Transmission System 266 km overhead 15km underground

More information

TORONTO TRANSIT COMMISSION REPORT NO.

TORONTO TRANSIT COMMISSION REPORT NO. Form Revised: February 2005 TORONTO TRANSIT COMMISSION REPORT NO. MEETING DATE: September 27, 2012 SUBJECT: NOTICE OF AWARD PROCUREMENT AUTHORIZATION - ARTICULATED BUSES INFORMATION ITEM RECOMMENDATION

More information

Impact of Distributed Energy Resources on Transmission System Reliability

Impact of Distributed Energy Resources on Transmission System Reliability S E P T E M B E R 1 3, 2 0 1 8 W E B I N A R Impact of Distributed Energy Resources on Transmission System Reliability National Council on Electricity Policy (NCEP) Alan McBride D I R E C T O R, T R A

More information

Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation

Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction

More information

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element

More information

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study ` Dunvegan Hydroelectric Project For Glacier Power Limited Preliminary Interconnection Study Prepared by Pung Toy, P. Eng. and Ata Rehman, P. Eng. September 24, 2004 Table of Contents Table of Contents...

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E2: Circuit Breaker Condition Assessment E2.1 GENERAL Circuit breakers are key components in the power train at hydroelectric powerplants and are

More information

Transformer Protection

Transformer Protection Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

Pump Station 7 Improvements

Pump Station 7 Improvements Project Business Case ID: C04 2/18/2017 Pump Station 7 Project Purpose: The purpose of this project is to ensure that Pump Station 7 continues to operate in an efficient and effective manner following

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring ABB is a leader in power and automation technologies that enable utility and industry customers to

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

New 115 kv Disconnect Switches at Bloomsburg MTS

New 115 kv Disconnect Switches at Bloomsburg MTS 115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115

More information

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2 Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2 Table of Contents 1 Introduction... 4 2 Description of retrofit circuit-breaker 8DN8... 5 3 Technical data for retrofit circuit-breaker

More information

Net Metering Interconnection Requirements

Net Metering Interconnection Requirements Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

off-grid Solutions Security of supply Basics: Off-grid energy supply

off-grid Solutions Security of supply Basics: Off-grid energy supply RENEWABLE OFF-GRID ENERGY COMPLETE off-grid POWER solutions off-grid Power with AEG Power Solutions Security of supply Getting renewable energy to two billion people living in the world s poorest countries

More information

PROFITABILITY THRESHOLDS OF RESILIENT MICROGRIDS (and how to exceed them) Baltimore, MD October 27th, 2018

PROFITABILITY THRESHOLDS OF RESILIENT MICROGRIDS (and how to exceed them) Baltimore, MD October 27th, 2018 PROFITABILITY THRESHOLDS OF RESILIENT MICROGRIDS (and how to exceed them) Baltimore, MD October 27th, 2018 Agenda About HARC Resilience and microgrids Microgrid Design Considerations with Uncertainty HARC

More information

Raising the bar. UHV switchgear and components

Raising the bar. UHV switchgear and components Raising the bar UHV switchgear and components Walter Holaus, Michael Lane, Richard Thomas The reliable supply of electrical energy is a backbone of the modern economy. Its ability to operate safely and

More information

Western Alberta Transmission Line (WATL) HVDC Project

Western Alberta Transmission Line (WATL) HVDC Project Submission for the ACEC Canada Canadian Consulting Engineering Awards 2016 Western Alberta Transmission Line (WATL) HVDC Project Submitted by Teshmont Consultants LP as a Consultant to AltaLink Attachment

More information

Illinois State Report

Illinois State Report July 2016 Illinois State Report Table of Contents 1. Planning Generation Portfolio Analysis Transmission Analysis Load Forecast Gas Pipeline Information 2 Executive Summary (July 2016) Existing Capacity:

More information

BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER. Exhibit Accompanying Rebuttal Testimony of Dana M.

BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER. Exhibit Accompanying Rebuttal Testimony of Dana M. Exhibit RMP (DMR-1R) BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER Exhibit Accompanying Rebuttal Testimony of Dana M. Ralston Lakeside U12 Combustion Turbine Exhaust Cylinder

More information

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

OVERALL LENGTH (B)  ( mm)  ( mm)  ( mm)  ( mm) 1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165

More information

Sub Regional RTEP Committee Western Region ATSI

Sub Regional RTEP Committee Western Region ATSI Sub Regional RTEP Committee Western Region ATSI February 20, 2019 1 ATSI Needs Stakeholders must submit any comments within 10 days of this meeting in order to provide time necessary to consider these

More information

PRESS RELEASE June 25, 2004

PRESS RELEASE June 25, 2004 120 Torbay Road, Suite E-210, P.O. Box 21040, St. John=s, NL. A1A 5B2 Tel: (709) 726-8600 - Fax: (709) 726-9604 PRESS RELEASE June 25, 2004 The Newfoundland and Labrador Board of Commissioners of Public

More information

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV December, 1975 New nformation and Supersedes DB 38-131 Pages 1-4, dated May 1972, and 38-121 D WE A, Pages 1-4, dated April1974 E, D, C/1981/ DB Westinghouse Electric Corporation Distribution Apparatus

More information

BC HYDRO SUPPLY CHAIN APPLICATIONS PROJECT EXHIBIT A-8

BC HYDRO SUPPLY CHAIN APPLICATIONS PROJECT EXHIBIT A-8 Patrick Wruck Commission Secretary Commission.Secretary@bcuc.com Website: www.bcuc.com Sixth Floor, 900 Howe Street Vancouver, BC Canada V6Z 2N3 TEL: (604) 660-4700 BC Toll Free: 1-800-663-1385 FAX: (604)

More information

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR #

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR # Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #75669514, under the SaskPower Open Access Transmission Tariff (OATT). The TSR consists

More information

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two

More information

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Project #148. Generation Interconnection System Impact Study Report

Project #148. Generation Interconnection System Impact Study Report Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information