Electrical and Control Aspects of Offshore Wind Farms II (Erao II)
|
|
- Myles Baker
- 5 years ago
- Views:
Transcription
1 ECN-C Electrical and Control Aspects of Offshore Wind Farms II (Erao II) Volume : Offshore wind farm case studies J.T.G. Pierik (ECN) J. Morren (TUD) E.J. Wiggelinkhuizen (ECN) S.W.H. de Haan (TUD) T.G. van Engelen (ECN) J. Bozelie (Neg-Micon) March 4 ECN-C- -4-5
2 Erao II, Volume : Offshore wind farm case studies Distribution Novem: J. t Hooft 5 TUD: J. Morren 6 S.W.H. de Haan 7 P. Bauer TenneT: W. Kling 3 J. Bozelie 4 Kema: R. de Groot 5 P. Vaessen 6 Essent: H. Slootweg 7 C. Houben 8 Continuon: M. Bongaerts 9 Nuon: M. van Riet Neg-Micon: A. Winnemuller ICE: J.C. Montero R. Jimenez 3 Sintef: J.O. Tande 4 Chalmers: O. Carlson 5 T. Thiringer 6 Risoe: P. Soerensen 7 VTT: B. Lemstrom 8 NREL: Y-H. Wan 9 E. Muljadi 3 Ineti: A. Lopez Estanquero 3 University College Dublin: A. Mullane 3 M. O Malley 33 UMIST: N. Jenkins 34 O. Anaya-Lara 35 Hydro Quebec: R. Gagnon 36 ECN: A.B.M. Hoff 37 C.A.M. van der Klein 38 W.C. Sinke 39 G.J.H. van Nes 4 G. Peppink 4 H.J.M. Beurskens 4 L.W.M.M. Rademakers 43 H. Snel 44 B.H. Hendriks 45 G.P. Corten 46 E.J. Wiggelinkhuizen 47 B.H. Bulder 48 P. Schaak 49 P. Heskes 5 P. Lako 5 T.J. de Lange 5 T.G. van Engelen 53 E.L. van der Hooft 54 J.T.G. Pierik 55 ECN Wind Energy Archive ECN Central Archive 7 ECN-C- -4-5
3 ABSTRT To investigate dynamic interaction of wind farms and the electrical grid, dynamic models of wind farms are needed. These models are not available however. The objective of the Erao- project has been () to develop these models, () to demonstrate their use by evaluating wind farms with different types of electrical systems and (3) to design and demonstrate controllers that can cope with grid code requirements. Four types of wind farm models have been developed based on different types of turbines: Constant Speed Stall turbine with directly coupled Induction Generator (CSS-IG); Constant Speed Stall turbine with Cluster Controlled induction generator operating in variable speed mode (CSS-CC); Variable Speed Pitch turbine with Doubly-Fed Induction Generator (VSP-DFIG); Variable Speed Pitch turbine with Permanent Magnet generator and full converter (VSP-PM). For each type of wind farm, three cases have been evaluated: normal operation including flicker production; response to a grid frequency dip; response to a grid voltage dip. For the wind farms which are able to support grid voltage or grid frequency, controllers for these purposes have been developed and demonstrated. Results and conclusions The response of a wind farm to a grid frequency dip strongly depends on the presence of a converter. A full converter, in the CSS-CC and VSP-PM wind farms, decouples the turbines from the disturbance. But also the system with a partial converter (VSP-DFIG) is hardly affected by the frequency dip. The constant speed wind farm (CSS-IG) on the other hand has serious problems with a frequency dip and the corresponding voltage dip. The constant speed wind farm can stay connected during the voltage dips that have been applied. The high amount of reactive power that is required by this wind farm during a voltage disturbances can be problematic. The Cluster Controlled wind farm (CSS-CC) can handle voltage dips if a resistor is placed in parallel to the dc-link capacitor and the surplus of energy during the voltage dip is dissipated. Wind farms using doubly-fed induction machines (VSP-DFIG) are the most problematic concept when voltage dips are considered. A solution is to provide a controlled by-pass for the high currents in the rotor. In the variable speed pitch wind farm with permanent magnet generators (VSP-PM) good voltage dip ride-through is achieved. The constant speed stall controlled wind farm (CSS-IG) can not assist in grid frequency control. The cluster controlled wind farm in the Erao- study is based on a stall controlled turbine (CSS-CC). Therefore it can not assist in grid frequency support either. Both variable speed pitch wind farms (VSP-DFIG and VSP-PM) can support grid frequency, which has been demonstrated by simulations. Only systems with converters are suitable for grid voltage control. The simulations demonstrate the feasibility of voltage control for wind farms with doubly-fed induction generators. There is no large difference between voltage control by wind farms with doubly-fed induction generators and voltage control by the other wind farms with IGBT converters: CSS-CC and VSP-PM. Recommendation With the completion of the wind farm models based on individual turbines, verification of models should now have a high priority. ECN-C
4 Erao II, Volume : Offshore wind farm case studies Keywords: wind farm models, wind farm dynamics, electrical systems, fault ride through, grid support Acknowledgement Erao- is a continuation of the Erao- project, in which a steady state (load flow) and economic model for offshore wind farms has been developed [9]. The Erao projects have been supported by the Dutch Agency for Energy and Environment (NOVEM) in the "Programma Duurzame Energie" of the Netherlands, executed by Novem by order of the Ministry of Economic Affairs. Novem project number: ECN project number: ECN-C- -4-5
5 EXECUTIVE SUMMARY In The Netherlands offshore wind power is on the brink of implementation. Plans exist for two offshore wind farms of about MW, located and 5 km from the coast of the province of North Holland. In 3 an investigation has been started to quantify the effect of 6 MW offshore wind power on the high voltage grid. Only the steady state behaviour has been considered, resulting in suggestions for grid reinforcement. This investigation needs to be complemented by a study on the dynamic interaction of wind power and the electrical grid. Objective of Erao- To investigate dynamic interaction of wind farms and the electrical grid, dynamic models of wind farms are needed. These models will be of great help in the evaluation of the behaviour of wind power during normal grid operation as well as during grid faults and in the design of controllers that enable wind farms to support the grid. Dynamic models of wind farms, including the relevant electrical components and sections of the grid, are not available however. The objective of the Erao- project is () to develop these models, () to demonstrate their use by evaluating wind farms with different types of electrical systems and (3) to design and demonstrate controllers that can cope with grid code requirements. Part : Model development The wind farm models are based on models of electrical components and controllers developed in this project and already existing models of wind, rotor, tower, mechanical drive train and pitch controller. The modelled electrical components and controllers are: induction generator doubly-fed induction generator permanent magnet generator IGBT converter and converter controller transformer cable synchronous generator consumer load wind farm controller for grid frequency support converter controller for grid voltage support A simple grid model and a model of the flicker meter has also been developed. An important aspect of dynamic models of electrical systems is computational speed. Electrical transients have very small time constants, resulting in small time steps and long computation time. In Erao- special attention has been paid to computational speed. An important increase in speed can be realised by the use of the dq-transformation, which has been applied to all models of electrical components in the Erao- component library. Volume of this report gives a mathematical derivation of the electrical component models, followed by the implementation of the models in Simulink, a computer program suitable for dynamic simulation. Turbines are modelled by connecting the electrical component models to ECN-C
6 Erao II, Volume : Offshore wind farm case studies the models of the rotor, tower, mechanical drive train and pitch controller. In the second step, individual turbine models are connected by cable models to produce the wind farm model. Results and conclusions from model development Dynamic models of wind farms based on individual turbine models are large and complicated. The number of state variables is high and some of the time constants are small, leading to a relatively long simulation time. The level of detail is high however, which makes these models suitable for the evaluation of wind farm dynamics and wind farm-grid interaction as well as for the design of controllers. The application of the dq-transformation significantly reduces the simulation time during normal operation of the wind farm, when transients from electrical switching operation have died out. Part : Model demonstration The second part of the Erao- project demonstrates the use of the developed wind farm models. In a number of case studies, four types of wind farms have been compared. The wind farm types use different turbines and different control methods, viz.: Constant Speed Stall turbine with directly coupled Induction Generator (CSS-IG, reference case); Constant Speed Stall turbine with Cluster Controlled induction generator operating in variable speed mode (CSS-CC); Variable Speed Pitch turbine with Doubly Fed Induction Generator (VSP-DFIG); Variable Speed Pitch turbine with Permanent Magnet generator and full converter (VSP- PM). The layout of a proposed offshore wind farm, the Near Shore Wind farm (NSW), has been taken as reference. The Near Shore Wind Farm is planned in the North Sea near the town of Egmond in The Netherlands. One string of turbines has been modelled with each of the four types of turbines. A simplified grid model has been included to enable simulation of wind farm-grid interaction. For each type of wind farm, three cases have been evaluated: normal operation including flicker production; response to a grid frequency dip; response to a grid voltage dip. For the wind farms which are able to support grid voltage or grid frequency, a converter controller or a wind farm controller suitable for this purpose has been developed and demonstrated. Volume of this report describes the case study results. Results and conclusions from case studies Normal operation of the wind farms has been simulated by the response to a wind gust. The simulations demonstrated proper operation of the generator and converter models, the converter controllers and proper overall behaviour of the wind farm. A limited flicker evaluation has been executed. Instantaneous flicker values have been determined over the complete range of operating conditions for the four types of wind farms. Flicker 6 ECN-C- -4-5
7 values of a single turbine have been compared to the values of a string of twelve turbines under the same operating conditions and fictitious grid parameters. The constant speed stall wind farm generates the highest flicker, the flicker production of the wind farms with partial and full converter is lower. Wind farm response to grid frequency and grid voltage dips The response of a wind farm to a grid frequency dip (5 Hz, sec) strongly depends on the presence of a converter. A full converter, in the case of the CSS-CC and VSP-PM wind farms decouples the turbines from the disturbance. But also the system with a partial converter (VSP- DFIG) is hardly affected by the frequency dip due to the effective adjustment of the rotor currents by the rotor converter. The constant speed system on the other hand has serious problems with a frequency dip and the corresponding voltage dip: depending on the depth and the conditions at the start of the dip, current, power and reactive power peaks may exceed rated values and may lead to a wind farm shut down. The farm with constant speed stall turbines and directly connected induction generators (CSS- IG) can stay connected during the voltage dips that have been applied (3%- sec, 5%-.5 sec and 85%-. sec). High currents are flowing during the voltage drop. Due to the high thermal capacity of the induction machine these currents will be no problem. The currents may trigger protective devices in the grid. The high amount of reactive power that is required by the wind farm during a voltage disturbances can be more problematic. When the dip lasts too long this may lead to voltage collapse. The Cluster Controlled wind farm (CSS-CC) can handle voltage dips if a resistor is placed in parallel to the dc-link capacitor and the surplus of energy during the voltage dip is dissipated. Wind farms using doubly-fed induction machines (VSP-DFIG) are the most problematic concept when voltage dips are considered. Large currents will flow in the rotor circuits and in the converters. Due to the limited thermal capacity of the power electronic devices in the converters, these currents may destroy the converters. A possible solution is to limit the high currents in the rotor by providing a by-pass over a set of resistors connected to the rotor windings. With these resistors it is possible to survive grid faults without disconnecting the turbine from the grid. One of the case studies demonstrates this solution. Manufacturers of DFIG systems are working on this solution and are making progress in meeting the voltage ride-through requirement. In the variable speed pitch wind farm with permanent magnet generators (VSP-PM), all the essential parameters can be controlled. Therefore good voltage dip ride-through can be achieved. The power supplied by the generator is reduced by the controllers during the dip. This is required because otherwise the current in the converters or the dc-link voltage becomes too high. To avoid overspeeding the pitch controller is activated. Wind farms assisting grid frequency or grid voltage The constant speed stall controlled wind farm (CSS-IG) can not assist in grid frequency control. The cluster controlled wind farm in the Erao- study is based on a stall controlled turbine (CSS-CC). It can not control aerodynamic power directly and therefore it can not assist in grid frequency support either. Both variable speed pitch wind farms (VSP-DFIG and VSP-PM) can be controlled to support grid frequency, which has been demonstrated by simulations. The controller consists of two parts: delta-control to realise a power margin and frequency feed-back to act on a frequency deviation. Since frequency control capability for wind farms implies maintaining a power margin, this feature may not be cost-efficient. Only systems with converters are suitable for grid voltage control. Different voltage and reac- ECN-C
8 Erao II, Volume : Offshore wind farm case studies tive power control strategies have been investigated for the VSP-DFIG wind farm. It has been shown that it is possible to control the power factor and that the wind farm can follow reactive power setpoints. Two voltage control options have been investigated. In the first option each turbine controls the voltage at its own terminal, in the second option the voltage at the grid connection point is controlled. Droop control has been implemented on each turbine. With this type of control, the wind farm behaviour during voltage deviations is similar to conventional power plant behaviour. The results depend on the X/R ratio of the grid: low X/R ratios require large amounts of reactive power to control the voltage and the wind farm converters are limited in current and thus in reactive power. Nonetheless, the simulations demonstrate the feasibility of voltage control for wind farms with doubly-fed induction generators. There is no large difference between voltage control by wind farms with doubly-fed induction generators and voltage control by the other wind farms with IGBT converters: CSS-CC and VSP-PM. This has been demonstrated by simulations with a cluster of CSS-CC turbines and a string of VSP-PM turbines. The results are similar to those of the VSP-DFIG wind farm. Economic evaluation The load flow program and the database with electrical and economic parameters developed in the Erao- project has been used in an economic evaluation of the four wind farm electrical systems. For a wind regime representative of the North Sea, the power production including the electrical losses, has been determined for the layout of the Near Shore Wind farm. This results in the contribution of the electrical system to the Levelised Production Costs (LPC). The VSP-DFIG farm performs best:.4 Eurocent/kWh. The CSS-IG farm is of the same magnitude:.6 Eurocent/kWh, while the other two farms have relatively expensive electrical systems:.6 Eurocent/kWh (VSP-PM) and 4.57 Eurocent/kWh (CSS-CC). The high price for the Cluster Controlled system is caused by the expensive converters. Recommendations With the completion of the wind farm models based on individual turbines, verification of models should now have a high priority. The Erao-3 project has been started with model validation as one of the objectives. For the incorporation of dynamic models of wind farms in models of national grids, the complexity of the wind farm models has to be reduced. Aggregated wind farm models, in which all turbines are represented by a single equivalent model are more suitable for this purpose. However, aggregated models loose the wide range of applicability of the wind farm models based on individual turbine models. It is recommended to develop aggregated wind farm models, tailored to application in power system models. The wind farm models developed in Erao- can serve as reference in the development of these aggregated models. Systems with cables to shore have not been included in the Erao- case studies. The Erao- component library includes all models necessary to investigate connections, with the exception of the thyristor converter. This converter however, is a less likely option for the connection of offshore wind farms than the IGBT converter, due to its limited controllability and large footprint. connections are currently more expensive than, but may offer a number of advantages. It is recommended to include these systems in a future study and for comparison purpose also develop a thyristor converter model. 8 ECN-C- -4-5
9 Nomenclature volume Symbols Subscripts C capacitance a aerodynamic f frequency conv converter i current dc dc-link L inductance e electrical P (active) power g grid Q reactive power m mechanical R resistance r rotor T torque s stator u voltage v voltage V Velocity w angular velocity Z impedance Table : Base values for per unit calculation CSS-IG CSS-CC VSP-DFIG VSP-PM Parameter Value Parameter Value Parameter Value Parameter Value Ps.75 MW Pconv, Pg 3*Ps Pconv, Pr 75 kw Ps, Pconv.5 MW Vs 96 V Udc 39 V Vconv, Vr 67 V Vs, Vconv 4 V wm *pi Udc V Udc 45 V Pg *Ps Vg 34 kv Parameters for CSS-CC, VSP-DFIG and VSP-PM are equal to that of CSS-IG, unless otherwise stated. ECN-C
10 Erao II, Volume : Offshore wind farm case studies. ECN-C- -4-5
11 CONTENTS Introduction 5 Reference wind farm NSW 6 3 Normal operation 9 3. Constant speed stall wind farm Cluster controlled wind farm Variable speed pitch controlled wind farm with DFIG Variable speed pitch controlled wind farm with PM Conclusion Flicker evaluation Constant speed stall wind farm Cluster controlled wind farm Variable speed pitch controlled wind farm with DFIG Variable speed pitch controlled wind farm with PM Conclusion Frequency dip response of wind farms Constant speed stall wind farm Cluster controlled wind farm Variable speed pitch controlled wind farm with DFIG Variable speed pitch controlled wind farm with PM Conclusion Voltage dip behaviour of wind turbines Introduction Voltage dips Simulation setup Constant speed stall wind turbine Introduction Dip of 3% - seconds Dip of 5% -.5 seconds Dip of 85% -. seconds Final remarks Cluster controlled wind turbine Introduction Dip of 3% - seconds ECN-C- -4-5
12 Erao II, Volume : Offshore wind farm case studies Dip of 5% -.5 seconds Dip of 85% -. seconds Discussion Variable speed pitch controlled wind turbine with DFIG Introduction Dip of 3% - seconds Dip of 5% -.5 seconds Dip of 85% -. seconds Discussion Variable speed pitch controlled wind turbine with PM Introduction Dip of 3% - seconds Dip of 5% -.5 seconds Dip of 85% -. seconds Discussion Conclusions and recommendations Grid frequency support by wind farms 9 7. Introduction Constant speed stall wind farm Cluster controlled wind farm Variable speed pitch controlled turbine with PM Delta control Grid frequency control support Variable speed pitch controlled turbine with DFIG Conclusion Grid voltage control by wind farms Introduction Voltage control strategies Simulation setup Introduction Doubly-Fed Induction generator Permanent magnet generator Cluster coupled induction machines Constant power factor control Reactive power setpoint Voltage control per turbine Voltage control at connection point ECN-C- -4-5
13 CONTENTS 8.8 Droop control Permanent magnet generator and cluster coupled induction machines Discussion Weak and strong grids X/R ratio Maximum current rating of wind turbines Distributed versus centralised control Conclusion and recommendations Economic analysis 9 Conclusions and remarks. Conclusions Remarks and recommendations A EeFarm load flow results 7 B Data for dynamic modelling of wind turbines 3 ECN-C
14 Erao II, Volume : Offshore wind farm case studies. 4 ECN-C- -4-5
15 INTRODUCTION For the problem description and the objectives of the Erao- project is referred to the introduction of Volume of this report. Volume of the Erao- report focuses on the dynamic behaviour of the four types of wind farm models in a number of a case studies. The four types of wind farm that have been considered are: Constant Speed Stall turbine with directly coupled induction generator (CSS-IG, reference case); Constant Speed Stall turbine with Cluster Controlled induction generator operating in variable speed mode (CSS-CC); Variable Speed Pitch turbine with Doubly Fed Induction Generator (VSP-DFIG); Variable Speed Pitch turbine with Permanent Magnet Generator with full converter (VSP- PM). The dynamic models of the wind farms have been used to: investigate wind farm behaviour during normal operation (for instance to evaluate flicker production or to examine dynamic interaction between interconnected turbines and between the wind farm and the grid); investigate wind farm response to deviations of the grid voltage and frequency; develop wind farm controllers. These applications are demonstrated in case studies in which the layout of a proposed Dutch offshore wind farm, the Near Shore Wind farm (NSW), has been taken as reference. The Near Shore Wind Farm is planned in the North Sea near the town of Egmond in The Netherlands. One string of the farm, consisting of turbines has been modelled with the four types of turbines. For each type of wind farm, three cases are evaluated: () normal operation including flicker production, () the behaviour during a grid frequency and (3) grid voltage dip. For those systems that are able to support grid voltage or grid frequency, a wind farm controller suitable for these purposes has been developed and demonstrated. Table gives an overview of all evaluations. Table : Erao- case study evaluations CSS-IG VSP-DFIG VSP-PM CSS-CC Normal operation X X X X Flicker X X X X Frequency dip X X X X Voltage dip X X X X Frequency support - X X X Voltage support - X X X ECN-C
16 REFERENCE WIND FARM NSW The Near Shore Wind Farm (NSW), planned near Egmond (see figure ), has been chosen as reference system for the Erao- evaluations. Figure gives the NSW layout. The farm consists of three sets of twelve NM9.75MW turbines connected by three cables to the 5 kv substation in IJmuiden. The cables in the farm and to shore are rated at 34 kv. In the farm two types of cables are used, depending on the loading at a given location. For the connection from the wind farm to the transformer in the substation also two types of cables are used, one for the submarine section of the route and a second type for the on-land route. Between the two sections, a relay station is located (see bottom part of figure ). Figure 3 gives the steady state characteristics of the NM9 turbine, a variable speed pitch controlled turbine. Based on the data of this turbine (including a design of the pitch control by ECN), the cable and transformer data, the ECN-TUD program EeFarm has been used to calculate the load flow over the full range of wind speeds: see figure 4. The load flow results (voltage, current, active and reactive power at all nodes) for full load for the four types of wind farms are listed in appendix A. NSWP ECN Figure : Near Shore Wind Park (NSWP) location 6 ECN-C- -4-5
17 REFERENCE WIND FARM NSW R.S. Figure : Near Shore Wind Fark layout ECN-C
18 Erao II, Volume : Offshore wind farm case studies Pel (kw) Vw (m/s) Pel (kw) N (rpm) Torque (knm) 5 5 Torque (knm) Vw (m/s) N (rpm) Figure 3: NM9 power and torque curves EeFarm ver.. 7 NSW Egmond WF Pel (MW) Vw (m/s) Ploss (MW) Vw (m/s) 95 Eff (%) Vw (m/s) Figure 4: NSW total power, electrical losses and efficiency calculated by EeFarm ( ECN- TUD) 8 ECN-C- -4-5
19 3 NORMAL OPERATION The first step in the case study will be to illustrate the response of the four types of wind farms during normal operation. To characterize the wind farm dynamic behaviour, a wind gust has been chosen from cut-in to rated wind speed and back again. To all turbines in the farm the same gust is applied, but with a small time delay. The total time simulated will be sec. The wind farm is connected to a grid model which consists of a MW synchronous generator with frequency and voltage control, two consumer loads (5 and 65 MW) and a 5 km 4 kv cable connecting to the 5 kv grid. A detailed description of the models can be found in Volume of this report. 3. Constant speed stall wind farm 96 V 34 kv 5 kv Figure 5: CSS-IG wind farm: electrical layout of a string of CSS turbines Figure 6 shows the response of turbine, 6 and of the CSS-IG farm to a wind speed increase from 4 to 5 m/s and back again. The reactive power demand of the turbines increases during the gust and is not supplied by capacitors but by the cables connecting the farm to the HV grid and the HV grid. It can be profitable to absorb (part of) the reactive power production of the cables by the wind farm. The total active and reactive power of the string, as well as current and voltage at the 5 kv side of the wind farm transformer are plotted in figure 7. ECN-C
20 Erao II, Volume : Offshore wind farm case studies 5 Turbine, 6, 3 plot CSSout Vw (m/s) 5 Paero (MW) Q tur (MVA) slip ( ) x Figure 6: Response of first turbine in CSS-IG wind farm to wind gust 3 Park plot CSSout Pel park (MW) Q park (MVA) I park (A) 5 V park (kv) Figure 7: Power, reactive power, current and voltage at the 5 kv side of the CSS-IG wind farm transformer ECN-C- -4-5
21 3 NORMAL OPERATION Grid plot CSSout Pel grid (MW) P cons, (MW) freq (Hz) 5 V exc (V) Figure 8: Response of grid to wind gust in CSS-IG wind farm Figure 8 shows how the changes in wind power ( to 5 MW) are compensated by the frequency controller of the synchronous machine representing the HV grid. The frequency stays within a band of.5 Hz around the 5 Hz setpoint. The voltage regulator on the synchronous machine compensates for the reactive power changes, the voltage at the HV side of the park transformer is kept within a band near 5 kv (Figure 7). ECN-C- -4-5
22 Erao II, Volume : Offshore wind farm case studies 3. Cluster controlled wind farm ω 34 kv ω3 34 kv ω 34 kv ω4 34 kv 34 kv 5 kv Figure 9: CC wind farm: electrical layout of four strings of 3 cluster controlled turbines Figure 9 shows the layout of a string of the near shore wind in cluster controlled mode. The string is divided into four clusters of three wind turbines each, connected to a single back-toback converter. The converters are connected through 34 kv submarine cables to the 34/5 kv transformer in the transformer station on shore. In the Simulink model, the cluster controlled wind farm consists of one cluster, the 34 kv cable to the transformer, the 5 kv transformer and a simplified grid model. For the details of the component models is referred to Volume of this report. For the cluster controlled wind turbine, power limitation by either stall or pitch control can be chosen. In principle, both options are technically feasible. The effect of cluster controlled operation on the aerodynamic power of both options is illustrated in figure. On the left the power-wind speed curves for -6 Hz operation of a constant speed stall turbine are plotted. 6 Hz operation postpones stall and can lead to tripping of the turbine due to excess power. Therefore, 5 Hz will mark the upper speed limit for the cluster controlled stall turbines. On the right hand side of figure the power-wind speed curves for -6 Hz operation of a variable speed pitch turbine are plotted for pitch angle zero. Exceeding the rated aerodynamic power will be prevented by pitching the blades and the rotational speed of the cluster generators does not need to be limited to 5 Hz. ECN-C- -4-5
23 3 NORMAL OPERATION 6 Power speed curves CSS turbine 6 Power speed curves VSP turbine (Bladhoek gr.) 6 Hz Hz 4 4 Paero (MW) 3 5 Hz Paero (MW) 3 5 Hz 4 Hz 4 Hz 3 Hz 3 Hz Hz Vw (m/s) Hz Vw (m/s) Figure : CCS (left) and VSP (right) turbine steady state power curves At low wind speed, decreasing rotational speed below rated will increase aerodynamic efficiency compared to constant speed operation: the, 3 and 4 Hz curves are above the 5 Hz power curve. The combination of high wind speed and low rotational speed reduces the aerodynamic power compared to constant speed operation. For a turbine with pitch control, this effect can be reduced by pitching at below rated wind speeds. Since individual wind speeds at the individual turbines in a cluster will differ, there will always be some mismatch, leading to a lower overall aerodynamic efficiency compared to individual variable speed. This reduction in energy yield has been estimated at.4% [7]. Hopefully, this is compensated by a cost reduction due to a smaller number of converters. A second aspect to consider for cluster control is the effect on turbine power and torque variations. The question is whether these variations will decrease or increase compared to constant speed operation. Individual turbine values as well as overall cluster behaviour can be compared. The cluster controlled wind farm in this evaluation will be based on a constant speed stall turbine (CSS-CC). If a variable speed turbine is chosen, a modification of the pitch control is required, especially if an attempt is made to increase efficiency by blade pitching below rated speed wind speed. This modification is outside the scope of this study. Speed control of a cluster will be based on measured wind speed(s). In the simulations, the wind speed at turbine has been chosen, but a different choice may prove to be more efficient. The speed of the turbines in a cluster is controlled for constant lambda operation compared to this wind speed, between an upper and a lower limit. The turbine speed is dictated by the frequency of the rectifier (turbine side converter). Since this results in a reduced frequency in the stator of the induction machine, the amplitude of the stator voltage is reduced proportionally to this frequency. This is necessary since the stator impedance is proportional to the stator frequency and a decrease in frequency would otherwise lead to high currents and possibly the activation of the thermal protection. The stator voltage is determined by a feed forward controller on the turbine side converter, which directly sets the amplitude of the voltage (see for details the Simulink blocks for the CSS-CC system in Volume ). Therefore, the control strategy of the turbine side converter in the cluster controlled system is completely different from the converters in the DFIG and PM systems, which control the current. ECN-C
24 Erao II, Volume : Offshore wind farm case studies Figure illustrates the combined effect of reduced frequency and voltage: the power-slip and torque-slip curves are similar in shape, only the pull-out power is reduced. The reactive power consumption is reduced. = 5 Hz, 96 V, = 4 Hz, 768 V x 4 amstat6 5.5 Pel (MW) ids (A) Slip ( ) 5 5 iqs (A) 3 x 4 Tel (Nm) Slip ( ) Reactive Power (MVAr) Slip ( ) Figure : Steady state curves for an induction machine at 5Hz, 96V and 4Hz, 768V 4 ECN-C- -4-5
25 3 NORMAL OPERATION vw, vw, vw3 (m/s) 5 5 CC turb,, 3 n, n, n3 (rpm) CC normal oper Pa, Pa, Pa3 (MW) plot CC a.m 9 Jan vs, vs, vs3 (V) 4 8 is, is, is3 (A) s, s, s3 (%) Figure : Cluster controlled wind farm: normal operation, turbines, and 3 Figure demonstrates normal operating conditions of a wind farm with one cluster of 3 turbines. A gust from 4 to 5 m/s passes the turbines with a small delay. The wind speed at turbine determines the rotor speed setpoint. Rotor speed and stator voltage vary proportionally. Power and slip vary accordingly. The turbine speed controller attempts to maintain a tip speed ratio of 5 below rated wind speed, compared to the wind speed at turbine. Figure 3 shows the total power of the cluster, the reactive power, the currents, voltages, current and the cluster frequency. The response of the grid to the changing operating conditions of the cluster can be seen in figure 4. ECN-C
26 Erao II, Volume : Offshore wind farm case studies CC converter CC normal oper plot CC a.m 9 Jan 4 P cluster (WM) Q cluster (kva) 5 5 idg, iqg (A) vdg, vqg (kv) udc (kv) f cluster (Hz) Figure 3: Cluster controlled wind farm: normal operation, converter values Grid plot CSSout 8 8 P SM (MW) 6 4 P cons (MW) freq (Hz) 5 V exc (V) Figure 4: Cluster controlled wind farm: normal operation, grid values 6 ECN-C- -4-5
27 3.3 Variable speed pitch controlled wind farm with DFIG 3 NORMAL OPERATION 96 V 34 kv 69 V 5 kv Figure 5: DFIG wind farm: electrical layout of a string of DFIG turbines Figure 5 gives the layout of a string of turbines equiped with doubly fed induction generators. Normal operation of this wind farm is demonstrated by the response to a wind gust passing through the farm. Figure 6 gives the rotor effective wind speed at turbine, 6 and in the string. The aerodynamic powers P a, P a6 and P a and slip of the turbines s, s6 and s follow the wind speed changes. The - converter on the generator rotor controls the generator torque and the reactive power of the stator (reactive power setpoint zero) by adjusting the d- and q-current in the rotor (for the details see Volume ). The grid side - converter controls the -voltage and the reactive power to the grid (i d setpoint zero, corresponding to a practically zero reactive power) by adjusting the d- and q-current to the grid. The total reactive powers Q, Q6 and Q (stator plus grid side converter) are plotted in the upper right part of figure 6. ECN-C
28 Erao II, Volume : Offshore wind farm case studies DFIG turb, 6,. plot DFIG norm op.m vw, vw6, vw (m/s) Q, Q6, Q (MW) Pa, Pa6, Pa (MW) s, s6, s (%) Figure 6: DFIG wind farm, normal operation, turbines, and 3 5 DFIG normal oper plot DFIG norm op.m.5 P park (MW) 5 Q park (MVA) idp, iqp (A) vdp, vqp (kv) Figure 7: DFIG wind farm, normal operation, string of turbines The total electric power produced by the string of turbines is plotted in figure 7. A peak 8 ECN-C- -4-5
29 3 NORMAL OPERATION power of about MW is reached. The park reactive power at the low voltage side of the 34kV-5kV transformer fluctuates between -.5 and.5 MVA, inversely proportional to the produced electric power. The fluctuations are caused by the inductivity of the turbine transformers and the cables inside the wind farm. The d-component of the 34kV voltage is relatively small, the q-component of the string current is therefore almost proportional to the string power, and the d-component to the reactive power. In chapter 8 is demonstrated how the converter can be controlled to realise zero reactive power at the point of common coupling. 75 Grid 7 plot DFIG norm op.m P SM (MW) P cons (MW) freq (Hz) dv exc (V) Figure 8: DFIG wind farm, normal operation, grid values In figure 8 the response of the grid model to the changing wind power is illustrated. The synchronous machine adjusts the power to maintain the grid frequency. The frequency deviations are small, in spite of the relatively small rotating mass in the grid. Consumer load is constant and the synchronous machine adjust the exciter voltage to keep the grid voltage constant. ECN-C
30 Erao II, Volume : Offshore wind farm case studies 3.4 Variable speed pitch controlled wind farm with PM 34 kv 5 kv Figure 9: VSP-PM wind farm: electrical layout of a string of PM turbines Figure 9 gives the layout of a string of turbines equipped with permanent magnet generators. Normal operation of this wind farm is demonstrated by the response to a wind gust passing through the farm. Figure gives the rotor effective wind speed at turbine, 6 and in the string. The aerodynamic powers P a, P a6 and P a and rotational speeds of the turbines s, s6 and s follow the wind speed changes. The - converter on the generator controls the generator torque and the reactive power of the stator (reactive power setpoint zero) by adjusting the d- and q-current in the stator. The grid side - converter controls the -voltage and the reactive power to the grid (reactive power setpoint zero) by adjusting the d- and q-current to the grid. The reactive power of turbine, 6 and (Q, Q6 and Q) is plotted in the upper right part of figure. 3 ECN-C- -4-5
31 3 NORMAL OPERATION 6 PM turb, 6,. PM norm oper vw, vw6, vw (m/s) Q, Q6, Q (MW) Pa, Pa6, Pa (MW) plot PM norm op.m s, s (%) Figure : PM wind farm: normal operation, turbines, 6 and 3 PM norm oper plot PM norm op.m 5 P park (WM) 5 Q park (kva) idp, iqp (A) 5 vdp, vqp (kv) Figure : PM wind farm: normal operation, string of turbines The total electric power produced by the string of turbines is plotted in figure. A peak ECN-C
32 Erao II, Volume : Offshore wind farm case studies power of 3 MW is reached. The park reactive power at the low voltage side of the 34kV- 5kV transformer fluctuates between - and.5 MVA, inversely proportional to the produced electric power. The range is wider that of the farm equipped with DFIG. The fluctuation is caused by the inductivity of the turbine transformers and the cables inside the wind farm. 7 Grid 7 plot PM norm op.m 65 6 P SM (MW) P cons (MW) freq (Hz) 5 dv exc (V) Figure : PM wind farm: normal operation, grid values In figure the response of the grid model to the changing wind power is illustrated. The synchronous machine adjusts the power to maintain the grid frequency. The frequency deviations are small. Consumer load is constant and the synchronous machine adjusts the exciter voltage to keep the grid voltage constant. 3.5 Conclusion Normal operation of four types of wind farms has been demonstrated by their response to a wind gust. The cluster controlled system has been equiped with a different machine side converter control strategy than the VSP-DFIG and VSP-PM system due to different requirements. The simulation showed proper operation of the generator and converter models and the converter controllers. 3 ECN-C- -4-5
33 4 FLICKER EVALUATION The currents and voltages calculated in the previous chapter during the first s of normal operation have been used to calculate instantaneous flicker values for a single turbine, cluster or the wind farm. For the details of the flicker calculation is referred to Volume of the Erao- report. The short circuit power for the flicker calculation is adapted to the case, i.e. 5 times the rated power of the turbine, the cluster or string (farm). A fictitious grid angle of 3 o has been chosen. The sample frequency in the wind farm calculations was 4 Hz. Flicker values are binned during intervals of 6 s, resulting in 4 values per binning period, except for the final interval. 4. Constant speed stall wind farm 5 CSS, normal operation, Turbine, grid angle 3 o Nr. of samples per bin Instantaneous flicker ( ) Figure 3: Binned instantaneous flicker values for a CSS-IG turbine Binned instantaneous flicker values for the CSS turbine and for a string of CSS turbines are plotted in figure 3 and 4. In this example, turbine rotors are synchronized, due to identical initial values and the relatively short simulated time span. The flicker level of the farm is lower than the level of the individual turbine, caused by averaging effects. Although, the complete operating range of the turbine is included in the s normal operation, a full flicker evaluation requires a longer simulation. For a similar constant speed stall turbine, the NW46, the flicker levels were measured: a Pst between.5 and.5 was found for below rated operation and.5 to.45 for rated operation. The calculated values for the CSS turbine correspond well to the below rated operation, calculated rated operation values are lower and may be caused by differences in turbine properties. ECN-C
34 Erao II, Volume : Offshore wind farm case studies 5 CSS, normal operation, turb, grid angle 3 o Nr. of samples per bin Instantaneous flicker ( ) Figure 4: Binned instantaneous flicker values for a wind farm of CSS-IG turbines 4. Cluster controlled wind farm 5 CC, normal operation, one cluster Nr. of samples per bin Pst ( ) Figure 5: Binned instantaneous flicker values for a wind farm of three cluster controlled turbines The flicker level of a variable speed turbine is expected to be lower than the level of a constant speed turbine, if the turbine control is well tuned. Cluster control is a special case of variable speed operation; all turbines in a cluster have the same speed. A flicker calculation for individual turbines is not possible because the voltage is not intended to be constant but changes in a wide band in relation to the speed. Therefore, only the flicker produced by the cluster is calculated, over the same period and in the same way as for the CSS-IG wind farm. Comparable values require taking the rated power of both cases into account: the cluster only consists of 3 34 ECN-C- -4-5
35 4 FLICKER EVALUATION turbines while the CSS-IG farm contains turbines. Binned instantaneous flicker values for a CSS-CC cluster are plotted in figure 5. The flicker level of the CSS-CC farm is below the CSS-IG farm level. The variation in flicker level of the CSS-CC farm is small. 4.3 Variable speed pitch controlled wind farm with DFIG 5 DFIG, normal operation, Turbine, grid angle 3 o Nr. of samples per bin Instantaneous flicker ( ) Figure 6: Binned instantaneous flicker values for a DFIG turbine 5 DFIG, normal operation, turb, grid angle 3 o Nr. of samples per bin Instantaneous flicker ( ) Figure 7: Binned instantaneous flicker values for a farm of DFIG turbine In the turbine equipped with doubly fed induction generator, the stator is connected to the grid and the rotor to a converter. The control of the rotor side converter will to a large extent determine the turbine short term dynamics as well as the flicker level. In the simulated DFIG ECN-C
36 Erao II, Volume : Offshore wind farm case studies turbine flux oriented control is applied, which should be able to accurately control stator power and reactive power. The flicker level of this system is expected to be low. This is confirmed by figures 6 and 7. Farm flicker level shows a small reduction with respect to the individual turbine level. 4.4 Variable speed pitch controlled wind farm with PM 5 PM, normal operation, Turbine, grid angle 3 o Nr. of samples per bin Instantaneous flicker ( ) Figure 8: Binned instantaneous flicker values for a PM turbine 5 PM, normal operation, turb, grid angle 3 o Nr. of samples per bin Instantaneous flicker ( ) Figure 9: Binned instantaneous flicker values for a farm of PM turbine The wind turbine with permanent magnet generator incorporates a full converter connected to the stator of the generator. Turbine and grid are largely decoupled and, if well controlled, low 36 ECN-C- -4-5
37 flicker levels result. This is confirmed by the results in figure 8 and 9. 4 FLICKER EVALUATION 4.5 Conclusion Only a limited flicker evaluation could be executed within the framework of the Erao- project. In a relatively short simulation instantaneous flicker values were determined over the complete range of operating conditions for the four types of wind farms. Flicker values of a single turbine were compared to the values of a string of twelve turbines under the same operating conditions and fictitious grid parameters. As could be expected, the directly connected constant speed stall turbine (CSS-IG) generates the highest flicker, while the systems with partial and full converter perform better and similar. As expected, increasing the number of turbines reduces the flicker level. ECN-C
38 5 FREQUENCY DIP RESPONSE OF WIND FARMS 5. Constant speed stall wind farm A frequency dip has been simulated by a change of the frequency setpoint of the synchronous machine which simulates the grid (figure 3). At t= s the setpoint is decreased to 45 Hz and at s it is changed to the normal value of 5 Hz. This change is frequency is far beond any expected change, in magnitude as well as rate, but has been chosen to demonstrate the wind farm behaviour more clearly. In reality, grid frequency deviations take time due to inertia in the electric system and immediately action by grid primary control. 8 Grid 4 plot CSSout 6 Pel (MW) Pcons, (MW) freq (Hz) V exc (V) Figure 3: CSS-IG wind farm: Frequency dip response of the grid The simulated frequency dip results in a voltage dip (V park in figure 3), which is corrected by the synchronous machine voltage controller V exc. The initial voltage dip is of the same magnitude as the freqency dip: about %. The total consumer load P cons and P cons is about MW, which is supplied partly by the synchronous machine and partly by the wind farm. During the frequency dip all turbines operate at an average wind speed V w of m/s and the aerodynamic power P aero is about.5 MW (see figure 3). The aerodynamic power does not change significantly due to the change in frequency. The reactive power consumption oscillates, corresponding to a current peak (figure 3). The slip oscillates as well and the sign of the slip reverses. After a few seconds a new steady state is reached. The turbines have decreased in speed and the slip is back to its original value. The park power (P el in figure 3) strongly oscillated and includes a power reversal, corresponding to the oscillating slip. The frequency and voltage changes also change the power consumption of the grid. The turbine and park currents show large peaks and these could result in wind farm shut down, depending on the settings of the protection equipment. Protection measures are not included in the wind 38 ECN-C- -4-5
STEADY STATE ELECTRICAL DESIGN, POWER PERFORMANCE AND ECONOMIC MODELING OF OFFSHORE WIND FARMS
STEADY STATE ELECTRICAL DESIGN, POWER PERFORMANCE AND ECONOMIC MODELING OF OFFSHORE WIND FARMS J.T.G. Pierik 1, M.E.C. Damen 2, P. Bauer 2, S.W.H. de Haan 2 1 Energy research Centre of the Netherlands
More informationFuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators
Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Abstract: G. Thrisandhya M.Tech Student, (Electrical Power systems), Electrical and Electronics Department,
More informationCHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM
106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,
More informationA Variable Speed Wind Generation System Based on Doubly Fed Induction Generator
Buletin Teknik Elektro dan Informatika (Bulletin of Electrical Engineering and Informatics) Vol. 2, No. 4, December 2013, pp. 272~277 ISSN: 2089-3191 272 A Variable Speed Wind Generation System Based on
More informationCHAPTER 4 MODELING OF PERMANENT MAGNET SYNCHRONOUS GENERATOR BASED WIND ENERGY CONVERSION SYSTEM
47 CHAPTER 4 MODELING OF PERMANENT MAGNET SYNCHRONOUS GENERATOR BASED WIND ENERGY CONVERSION SYSTEM 4.1 INTRODUCTION Wind energy has been the subject of much recent research and development. The only negative
More informationEE 742 Chap. 7: Wind Power Generation. Y. Baghzouz
EE 742 Chap. 7: Wind Power Generation Y. Baghzouz Wind Energy 101: See Video Link Below http://energy.gov/eere/videos/energy-101- wind-turbines-2014-update Wind Power Inland and Offshore Growth in Wind
More informationPossibilities of Distributed Generation Simulations Using by MATLAB
Possibilities of Distributed Generation Simulations Using by MATLAB Martin Kanálik, František Lizák ABSTRACT Distributed sources such as wind generators are becoming very imported part of power system
More informationEE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011
EE 742 Chap. 7: Wind Power Generation Y. Baghzouz Fall 2011 Overview Environmental pressures have led many countries to set ambitious goals of renewable energy generation. Wind energy is the dominant renewable
More informationCHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL
123 CHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL 5.1 INTRODUCTION Wind energy generation has attracted much interest
More informationABB POWER SYSTEMS CONSULTING
ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February
More informationDesign and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim
Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim Dept. of Electrical Engineering Kwangwoon University, Korea Summary
More informationFault Rid Through Protection of DFIG Based Wind Generation System
Research Journal of Applied Sciences, Engineering and Technology 4(5): 428-432, 212 ISSN: 24-7467 Maxwell Scientific Organization, 212 Submitted: September 14, 211 Accepted: October 15, 211 Published:
More informationCONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS
CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS Lucian Mihet-Popa "POLITEHNICA" University of Timisoara Blvd. V. Parvan nr.2, RO-300223Timisoara mihetz@yahoo.com Abstract.
More informationPumped storage for balancing wind power fluctuations in an isolated grid
Wind Power to the Grid EPE Wind Energy Chapter 1 st seminar Delft University of Technology, 8-9 March 008 Pumped storage for balancing wind power fluctuations in an isolated grid Jon Are Suul, Professor
More informationWorkshop on Grid Integration of Variable Renewable Energy: Part 1
Workshop on Grid Integration of Variable Renewable Energy: Part 1 System Impact Studies March 13, 2018 Agenda Introduction Methodology Introduction to Generators 2 Introduction All new generators have
More informationIntegration of Large Wind Farms into Electric Grids
Integration of Large Wind Farms into Electric Grids Dr Mohammad AlZoubi Introduction Development WHAT IS NEXT!! Over the next 12 years, Europe must build new power capacity equal to half the current total.
More informationBattery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1
Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 CONTENTS Introduction Types of WECS PQ problems in grid connected WECS Battery
More informationExperience on Technical Solutions for Grid Integration of Offshore Windfarms
Experience on Technical Solutions for Grid Integration of Offshore Windfarms Liangzhong Yao Programme Manager AREVA T&D Technology Centre 18 June 2007, DTI Conference Centre, London Agenda The 90MW Barrow
More informationFaults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC
SPEEDAM 2010 International Symposium on Power Electronics, Electrical Drives, Automation and Motion Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations
More informationWind Generation and its Grid Conection
Wind Generation and its Grid Conection J.B. Ekanayake PhD, FIET, SMIEEE Department of Electrical and Electronic Eng., University of Peradeniya Content Wind turbine basics Wind generators Why variable speed?
More informationAbstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application
Issue #WP102: Technical Information from Cummins Generator Technologies Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application White Paper Ram Pillai
More informationModelling and Simulation of DFIG with Fault Rid Through Protection
Australian Journal of Basic and Applied Sciences, 5(6): 858-862, 2011 ISSN 1991-8178 Modelling and Simulation of DFIG with Fault Rid Through Protection F. Gharedaghi, H. Jamali, M. Deisi, A. Khalili Dashtestan
More informationWind Farm Evaluation and Control
International society of academic and industrial research www.isair.org IJARAS International Journal of Academic Research in Applied Science (2): 2-28, 202 ijaras.isair.org Wind Farm Evaluation and Control
More informationCHAPTER 5 ROTOR RESISTANCE CONTROL OF WIND TURBINE GENERATORS
88 CHAPTER 5 ROTOR RESISTANCE CONTROL OF WIND TURBINE GENERATORS 5.1 INTRODUCTION The advances in power electronics technology have enabled the use of variable speed induction generators for wind energy
More informationEPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION
EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy*** *Swiss Federal Institute of Technology, Electrical
More informationJ.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***
EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy*** *Swiss Federal Institute of Technology, Electrical
More informationCHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM
61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this
More informationEvaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection
Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba
More informationJournal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E
Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity
More informationUNC-Charlotte's Power Engineering Teaching lab
1 UNC-Charlotte's Power Engineering Teaching lab B. Chowdhury Panel Session Title: Existing and Proposed Power Systems Laboratories for the Undergraduate Curriculum PES GM 2015 2 Outline Background - Energy
More informationControl of Grid Voltage and Power of Doubly Fed Induction Generator wind turbines during grid faults
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 4 Ver. V (Jul Aug. 2014), PP 12-21 Control of Grid Voltage and Power of Doubly Fed
More informationGreen energy conversion
Green energy conversion Prof. Dr.-Ing. habil. Andreas Binder Department of Electrical Energy Conversion Darmstadt University of Technology abinder@ew.tu-darmstadt.de Prof. A. Binder 1.1/1 Contents of lecture
More informationSquirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student
Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid Lluís Trilla PhD student Current topology of wind farm Turbines are controlled individually Wind
More informationResearch on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC
Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,
More informationLow-Voltage Ride-Through Capability Improvement of DFIG-Based Wind Turbines
Low-Voltage Ride-Through Capability Improvement of DFIG-Based Wind Turbines Mehran Zamanifar, Behzad Fayyaz Dept. of Electrical Eng., Islamic Azad university of Najaf Abad, mehran_zamanifar@yahoo.com Dept.
More informationCHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR
100 CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR 6.1 INTRODUCTION Conventional energy resources are not sufficient to meet the increasing electrical power demand. The usages of
More informationLaboratory Tests, Modeling and the Study of a Small Doubly-Fed Induction Generator (DFIG) in Autonomous and Grid-Connected Scenarios
Trivent Publishing The Authors, 2016 Available online at http://trivent-publishing.eu/ Engineering and Industry Series Volume Power Systems, Energy Markets and Renewable Energy Sources in South-Eastern
More informationCOMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE
COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE Richa jain 1, Tripti shahi 2, K.P.Singh 3 Department of Electrical Engineering, M.M.M. University of Technology, Gorakhpur, India 1 Department
More informationPrinciples of Doubly-Fed Induction Generators (DFIG)
Renewable Energy Principles of Doubly-Fed Induction Generators (DFIG) Courseware Sample 86376-F0 A RENEWABLE ENERGY PRINCIPLES OF DOUBLY-FED INDUCTION GENERATORS (DFIG) Courseware Sample by the staff
More informationFrequency Control of Isolated Network with Wind and Diesel Generators by Using Frequency Regulator
Frequency Control of Isolated Network with Wind and Diesel Generators by Using Frequency Regulator Dr.Meenakshi mataray,ap Department of Electrical Engineering Inderprastha Engineering college (IPEC) Abstract
More informationEffect of crowbar resistance on fault ride through capability of doubly fed induction generator
ISSN: 2347-3215 Volume 2 Number 1 (January, 2014) pp. 88-101 www.ijcrar.com Effect of crowbar resistance on fault ride through capability of doubly fed induction generator V.Vanitha* and K.Santhosh Amrita
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationComparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 124-129 www.iosrjournals.org Comparative Analysis
More informationIMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR
IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR Uttam Kumar 1, Sandeep Kumar Pal 2, Harshit Kumar Yagyasaini 3, Bharat 4, Siddharth Jain 5 1, 2,3,4 Students, Electrical Engineering
More informationSynchronous Generators I. Spring 2013
Synchronous Generators I Spring 2013 Construction of synchronous machines In a synchronous generator, a DC current is applied to the rotor winding producing a rotor magnetic field. The rotor is then turned
More informationDoubly fed electric machine
Doubly fed electric machine Doubly fed electric machines are electric motors or electric generators that have windings on both stationary and rotating parts, where both windings transfer significant power
More informationENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG
ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG C.Nikhitha 1, C.Prasanth Sai 2, Dr.M.Vijaya Kumar 3 1 PG Student, Department of EEE, JNTUCE Anantapur, Andhra Pradesh, India.
More informationFACTS FOR GRID INTEGRATION OF LARGE OFFSHORE WIND FARMS BY MEANS OF AC
FACTS FOR GRID INTEGRATION OF LARGE OFFSHORE WIND FARMS BY MEANS OF AC Rolf Grünbaum, Per Halvarsson ABB Power Technologies AB Introduction After decades in the starting block, wind power is finally taking
More informationBrochure. Wind turbine generators Reliable technology for all turbine applications
Brochure Wind turbine generators Reliable technology for all turbine applications 2 ABB Wind turbine generators We provide motors and generators, services and expertise to save energy and improve customers
More informationFAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE
FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The
More informationEnhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor
> 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper
More informationAnupam *1, Prof. S.U Kulkarni 2 1 ABSTRACT I. INTRODUCTION II. MODELLING OF WIND SPEED
2017 IJSRSET Volume 3 Issue 3 Print ISSN: 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology PMSG Based Wind Farm Analysis in ETAP Software Anupam *1, Prof. S.U Kulkarni 2 1 Department
More informationMatlab Modeling and Simulation of Grid Connected Wind Power Generation Using Doubly Fed Induction Generator
ISSN (e): 2250 3005 Vol, 04 Issue, 7 July 2014 International Journal of Computational Engineering Research (IJCER) Matlab Modeling and Simulation of Grid Connected Wind Power Generation Using Doubly Fed
More informationSynchronous Generators I. EE 340 Spring 2011
Synchronous Generators I EE 340 Spring 2011 Construction of synchronous machines In a synchronous generator, a DC current is applied to the rotor winding producing a rotor magnetic field. The rotor is
More informationELECTROMECHANICAL OPTIMIZATION AGAINST TORSIONAL VIBRATIONS IN O&G ELECTRIFIED TRAINS MICHELE GUIDI [GE O&G] ALESSANDRO PESCIONI [GE O&G]
ELECTROMECHANICAL OPTIMIZATION AGAINST TORSIONAL VIBRATIONS IN O&G ELECTRIFIED TRAINS MICHELE GUIDI [GE O&G] ALESSANDRO PESCIONI [GE O&G] Topics INTRODUCTION - Mechanical vibrations in electrified trains
More informationAsian Journal on Energy and Environment ISSN Available online at
As. J. Energy Env. 2005, 6(02), 125-132 Asian Journal on Energy and Environment ISSN 1513-4121 Available online at www.asian-energy-journal.info Dynamic Behaviour of a Doubly Fed Induction Machine with
More informationPublished by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201
Study And Analysis Of Fixed Speed Induction Generator Based Wind Farm Grid Fault Control Using Static Compensator Abstract 1 Nazia Zameer, 2 Mohd Shahid 1 M.Tech(Power System) Scholar, Department of EEE,
More informationUkujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances
Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances 29 Juli 2014 Page 1 Characteristics of the Project Parameter Detail
More informationSimulated Switching Transients in the External Grid of Walney Offshore Wind Farm
Downloaded from orbit.dtu.dk on: Apr 07, 2019 Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm Arana Aristi, Iván; Johnsen, D. T.; Soerensen, T.; Holbøll, Joachim Published
More informationPOWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION
International Journal of Latest Research in Science and Technology Volume 3, Issue 1: Page No.68-74,January-February 2014 http://www.mnkjournals.com/ijlrst.htm ISSN (Online):2278-5299 POWER QUALITY IMPROVEMENT
More informationGOLDWIND 2.5MW PERMANENT MAGNET DIRECT-DRIVE (PMDD) WIND TURBINE
Rotor Blade Rotor/Generator Bearing Cast Hub Auxiliary Crane Wind Measurement Equipment Pitch System Heat Exchanger Yaw System Base Frame PMDD Generator GOLDWIND 2.5MW PERMANENT MAGNET DIRECT-DRIVE (PMDD)
More informationTechnical Guide No. 7. Dimensioning of a Drive system
Technical Guide No. 7 Dimensioning of a Drive system 2 Technical Guide No.7 - Dimensioning of a Drive system Contents 1. Introduction... 5 2. Drive system... 6 3. General description of a dimensioning
More informationGrid voltage control by using DFIG during grid faults
IOSR Journal of Engineering (IOSRJEN) e-issn: 2250-3021, p-issn: 2278-8719 Vol. 3, Issue 1 (Jan. 2013), V1 PP 25-32 Grid voltage control by using DFIG during grid faults Prof. Sushil Kumar 1, Shilpa Manoj
More informationGenerator Efficiency Optimization at Remote Sites
Generator Efficiency Optimization at Remote Sites Alex Creviston Chief Engineer, April 10, 2015 Generator Efficiency Optimization at Remote Sites Summary Remote generation is used extensively to power
More informationModeling of doubly fed induction generator (DFIG) equipped wind turbine for dynamic studies
Modeling of doubly fed induction generator (DFIG) equipped wind turbine for dynamic studies Mattia Marinelli, Andrea Morini, Andrea Pitto, Federico Silvestro Department of Electric Engineering, University
More informationPERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM
Volume II, Issue XI, November 13 IJLTEMAS ISSN 78-54 PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING K.B. Porate, Assistant Professor, Department of Electrical Engineering, Priyadarshini
More informationElectrical grid stability with high wind energy penetration
ECOWAS Regional Workshop on WIND ENERGY Praia, Cape Verde. November 4 5, 2013 Electrical grid stability with high wind energy penetration Fernando CASTELLANO HERNÁNDEZ Head of Wind Energy Section Renewable
More informationAsia Pacific Research Initiative for Sustainable Energy Systems 2011 (APRISES11)
Asia Pacific Research Initiative for Sustainable Energy Systems 2011 (APRISES11) Office of Naval Research Grant Award Number N0014-12-1-0496 Hydrogen Energy System Simulation Model for Grid Management
More informationDYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID
DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID J.Ramachandran 1 G.A. Putrus 2 1 Faculty of Engineering and Computing, Coventry University, UK j.ramachandran@coventry.ac.uk
More informationLECTURE 19 WIND POWER SYSTEMS. ECE 371 Sustainable Energy Systems
LECTURE 19 WIND POWER SYSTEMS ECE 371 Sustainable Energy Systems 1 GENERATORS Blades convert the wind kinetic energy to a shaft power to spin a generator and produce electricity A generator has two parts
More informationModel Predictive Control of Back-to-Back Converter in PMSG Based Wind Energy System
Model Predictive Control of Back-to-Back Converter in PMSG Based Wind Energy System Sugali Shankar Naik 1, R.Kiranmayi 2, M.Rathaiah 3 1P.G Student, Dept. of EEE, JNTUA College of Engineering, 2Professor,
More informationTargeted Application of STATCOM Technology in the Distribution Zone
Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric
More informationGuide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.
Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...
More informationStatcom Operation for Wind Power Generator with Improved Transient Stability
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 3 (2014), pp. 259-264 Research India Publications http://www.ripublication.com/aeee.htm Statcom Operation for Wind Power
More information2014 ELECTRICAL TECHNOLOGY
SET - 1 II B. Tech I Semester Regular Examinations, March 2014 ELECTRICAL TECHNOLOGY (Com. to ECE, EIE, BME) Time: 3 hours Max. Marks: 75 Answer any FIVE Questions All Questions carry Equal Marks ~~~~~~~~~~~~~~~~~~~~~~~~~~
More informationABB FACTS Grid connection of Wind Farms
Christian PAYERL ABB FACTS Grid connection of Wind Farms May 28, 2010 Slide 1 ABB Power of Wind May 28, 2010 Slide 2 ABB FACTS 300 engineers, highly skilled in the following disciplines: Development Marketing
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationField Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems
Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems Farid Katiraei *, Barry Mather **, Ahmadreza Momeni *, Li Yu *, and Gerardo Sanchez * * Quanta Technology, Raleigh,
More informationCHAPTER 5 ANALYSIS OF COGGING TORQUE
95 CHAPTER 5 ANALYSIS OF COGGING TORQUE 5.1 INTRODUCTION In modern era of technology, permanent magnet AC and DC motors are widely used in many industrial applications. For such motors, it has been a challenge
More informationCombined Input Voltage and Slip Power Control of low power Wind-Driven WoundRotor Induction Generators
Combined Input Voltage and Slip Control of low power Wind-Driven Woundotor Induction Generators M. Munawaar Shees a, FarhadIlahi Bakhsh b a Singhania University, ajasthan, India b Aligarh Muslim University,
More informationWind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment
2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in
More informationConfiguration of large offshore wind farms
Configuration of large offshore wind farms Randi Aardal Flo Master of Science in Energy and Environment Submission date: June 2009 Supervisor: Terje Gjengedal, ELKRAFT Norwegian University of Science and
More informationTemporary Rotor Inertial Control of Wind Turbine to Support the Grid Frequency Regulation
Temporary Rotor Inertial Control of Wind Turbine to Support the Grid Frequency Regulation Bing Liu, Kjetil Uhlen, Tore Undeland Department of Electric Power Engineering, NTNU The 9th Deep Sea Offshore
More informationAnalysis of Low Voltage Ride through Capability of FSIG Based Wind Farm Using STATCOM
Analysis of Low Voltage Ride through Capability of FSIG Based Wind Farm Using STATCOM Roshan Kumar Gupta 1, Varun Kumar 2 1(P.G Scholar) EE Department KNIT Sultanpur, U.P (INDIA)-228118 2 (Assistant Professor)
More informationControl of a wind turbine equipped with a variable rotor resistance
Control of a wind turbine equipped with a variable rotor resistance HÉCTOR A. LÓPEZ CARBALLIDO Department of Computer Science and Engineering CHALMERS UNIVERSITY OF TECHNOLOGY UNIVERSITY OF GOTHENBURG
More informationPOWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS
Available Online at www.ijcsmc.com International Journal of Computer Science and Mobile Computing A Monthly Journal of Computer Science and Information Technology IJCSMC, Vol. 3, Issue. 10, October 2014,
More informationDynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK
International Journal Of Engineering Research And Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 14, Issue 1 (January 2018), PP.59-63 Dynamic Behaviour of Asynchronous Generator
More informationAdvance Electronic Load Controller for Micro Hydro Power Plant
Journal of Energy and Power Engineering 8 (2014) 1802-1810 D DAVID PUBLISHING Advance Electronic Load Controller for Micro Hydro Power Plant Dipesh Shrestha, Ankit Babu Rajbanshi, Kushal Shrestha and Indraman
More informationGenerator Interconnection System Impact Study For
Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...
More informationControl of a wind turbine equipped with a variable rotor resistance
Control of a wind turbine equipped with a variable rotor resistance HÉCTOR A. LÓPEZ CARBALLIDO Department of Computer Science and Engineering CHALMERS UNIVERSITY OF TECHNOLOGY UNIVERSITY OF GOTHENBURG
More informationCHAPTER 6 POWER QUALITY IMPROVEMENT OF SCIG IN WIND FARM USING STATCOM WITH SUPERCAPACITOR
120 CHAPTER 6 POWER QUALITY IMPROVEMENT OF SCIG IN WIND FARM USING STATCOM WITH SUPERCAPACITOR 6.1 INTRODUCTION For a long time, SCIG has been the most used generator type for wind turbines because of
More informationImplementation of FC-TCR for Reactive Power Control
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 5, Issue 5 (May. - Jun. 2013), PP 01-05 Implementation of FC-TCR for Reactive Power Control
More informationA Case Study on Aggregate Load Modeling in Transient Stability Studies
A Case Study on Aggregate Load Modeling in Transient Stability Studies Presented by: Daniel Feltes Siemens PTI Coauthors: Carlos Grande-Moran, Bernardo Fernandes, James Feltes, Ming Wu and Robert Wells
More informationStudy of DFIG based Wind Turbine for Reactive Power Generation Capability
Study of DFIG based Wind Turbine for Reactive Power Generation Capability Janarthanan.S Assistant Professor, Department of EEE-M, AMET University, Chennai Abstract: In this paper to enhance the ability
More informationWind Turbine Emulation Experiment
Wind Turbine Emulation Experiment Aim: Study of static and dynamic characteristics of wind turbine (WT) by emulating the wind turbine behavior by means of a separately-excited DC motor using LabVIEW and
More informationPOWER QUALITY ISSUES IN WIND DIESEL HYBRID POWER GENERATION SYSTEMS
POWER QUALITY ISSUES IN WIND DIESEL HYBRID POWER GENERATION SYSTEMS BUNDA Ș. *University of Oradea, Universităţii no.1, Oradea, sbunda@uoradea.ro Abstract The purpose of this paper is to present main power
More informationDiversifying into Marine Energy. ABB March 2015
Diversifying into Marine Energy ABB March 2015 Structure Integrity, Construction and Manufacturing Solutions for the Process & Marine markets Process & Equipment Marine & Logistics Equipment Manufacturing
More informationVENSYS. Vensys 62 The next Generation of Gearless Wind Turbines goes into Production
Vensys 62 The next Generation of Gearless Wind Turbines goes into Production F. Klinger, INNOWIND GmbH J. Rinck, Vensys GmbH S. Balzert, FG Windenergie S. Jöckel, INNOWIND GmbH S. Jöckel: Vensys 62 Next
More informationRegenerative Utility Simulator for Grid-Tied Inverters
Regenerative Utility Simulator for Grid-Tied Inverters AMETEK s RS & MX Series with the SNK Option provides the solution Testing of grid-tied inverters used in solar energy systems is emerging as a major
More informationDynamic Study of Bonaire Island Power System: Model Validation and Project Experience
Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Y. Sun 1, 2,*, W. G. Kuijpers 3, E. C. W. de Jong 1,2, and H. Pustjens 3 1 Electrical Energy System, Eindhoven University
More information