Life Extension Testing of Electrical Penetration Assemblies
|
|
- Hannah Burke
- 5 years ago
- Views:
Transcription
1 Nuclear Division Life Extension Testing of Electrical Penetration Assemblies EQ Conference Oct 31 Nov 2, 2018 Steve Benesh, Curtiss-Wright Nuclear 1 October 22, 2018 Curtiss-Wright
2 Summary Life Extension Testing of EPAs Qualification Standards and Scope Testing Strategies Challenges Test Design Results 2 Feb, 2017 Proprietary 2014 Curtiss-Wright
3 Qualification Scope and Standards Qualification Standards: IEEE IEEE standard for Electric Penetration Assemblies in Containment Structures for Nuclear Power Generating Stations. Customer s implementing procedures/standards - follows IEEE 317 Qualification Scope Qualified-life testing for 24 EPA modules per above standards and customer approved test procedure including: o Initial tests continuity, IR, dielectric withstand, gas leak rate and visual o Pre-conditioning shipping and storage simulation, thermal cycling, thermal aging and radiation aging. o Short-circuit current and short-circuit thermal capacity tests o Seismic was not required by customer o DBE Simulations o Rated short-time overload current and duration during DBE environmental conditions o Rated short-circuit current and thermal capacity tests during DBE environmental conditions 3 Feb, 2017 Proprietary 2014 Curtiss-Wright
4 Testing Strategies Laboratory tests were designed to simulate the as installed configuration and minimize over-testing: DBE tests simulated EPA installation on the outboard end of the penetration nozzle. Prior to DBE simulations we performed trials with dummy specimens to set test LOCA system parameters (i.e. superheat temp, pressure regulators, etc.) to ensure minimal overshoot. Modules were aged in Nitrogen to maintain 2% to 10% Oxygen atmosphere along with a high humidity environment. Continuous current and fault current tests were based on the actual maximum current that could occur in the plant. Voltages were based on maximum actual voltage in the plant Pre-planning of test fixtures, resources and testing approach to meet customer schedule: Multiple test flanges that mimic the field configuration for gas leak rate testing Multiple DBE accident test chambers to allow for parallel testing Project staffed to meet customer schedule Test approach to gather required data for qualification in an efficient manner Test specimen selection Stock (inventory) samples and Field installed samples 4 Feb, 2017 Proprietary 2014 Curtiss-Wright
5 Challenges Challenges: Customer had compressed schedule how to reduce overall qualification time: 24 EPA modules under test, ~ 1800 conductors 18AWG-150C, 16 AWG-140C, 10 AWG -75C, 8 AWG-27C, 2/0 AWG-7C and Coaxial Thermal Aging for 60 years, acceleration factor 250, ~3 months aging time Four groups of modules with different radiation aging requirements, ~3 months aging time 2 customers, different DBE profiles H4 (LOCA), H5 (Severe Accident), Post-Fukushima (FOSH) Different profiles for Wet Well versus Lower Drywell modules Forsmark H4 and H5 DBEs were 30 days Large number conductors (150 to 350) to monitor during DBE Testing How to measure Insulation Resistance, Voltage & Current during DBE simulation Customer wanted modules aged in Nitrogen (maintaining a 2%-10% oxygen level) since containments are inert with Nitrogen during operation. Test specimens were to be aged for 20 days with 95% RH. Internal EPA module volumes, which is a variable in calculating leak rates by pressure decay method, were not known. 5 Feb, 2017 Proprietary 2014 Curtiss-Wright
6 Initial Electrical Testing IR, Dielectric, continuity and resistance testing. Used containers with copper BBs to test conductors to all other conductors. 6 Feb, 2017 Proprietary 2014 Curtiss-Wright
7 Gas leak rate testing by pressure decay method 3 EPA Header Plate Flanges fabricated with 6 feedthrough ports each. Test flange ports designed with same dimensions as ports in EPA header plates in the plant. Each port had individual monitoring connection for leak rate measurement of individual modules. Manifold to pressurize and leak test 6 modules at a time. 7 Feb, 2017 Proprietary 2014 Curtiss-Wright
8 Determining internal volume of EPA modules Gas leak rate by pressure decay was most efficient method for determining leak rate in acceptance range <1E-3 cm 3 /sec. Internal volume of modules were unknown and needed to be determined to calculate module leak rate by pressure decay method. Determined internal volume of modules by pressuring a known gas volume and releasing the pressure to the module internal space. Knowing the initial and final pressure we could calculate the internal volume of each type of module using the ideal gas laws. 8 Feb, 2017 Proprietary 2014 Curtiss-Wright
9 Thermal Aging in Nitrogen Oxygen sample Thermocouples Modules in Thermal Aging Oven 9 Feb, 2017 Proprietary 2014 Curtiss-Wright
10 Thermal Aging in Nitrogen Thermal aging chambers, data acquisition and oxygen concentration analyzer. Sealed chamber and inerted with Nitrogen. 10 Feb, 2017 Proprietary 2014 Curtiss-Wright
11 Test Chamber Design Designed portable chamber equivalent in size to the containment nozzle Three portable extension chambers that mount directly to the CWN LOCA chamber were fabricated. Chambers had immersion heater and temperature and pressure control system. Ports at the end of the nozzle allowed conductors to exit for electrical testing during the DBE simulation. Chamber was insulated Advantages: After the ramp and once the profile reached saturation or submergence conditions, chamber could be disconnected from LOCA system, blind flange added to back of chamber and remaining profile completed away from the LOCA chamber. LOCA system available to start the next accident simulation typically within 1 to two days vs. being tied up for the full 30 day test. Significant time savings during DBE testing. Immersion heater and compressed air/nitrogen supply able to accurately maintain profile temperature and pressure conditions. Temperature conditions during ramp and first couple plateaus were representative of conditions that the EPA would see in the plant with EPA installed on the outboard side of the nozzle. Temperature control with immersion heater and regulated pressure source provided tight temperature and pressure control. Chemical waste during submergence was significantly less than would be needed for large chamber. Conservatisms Chamber was insulated so that nozzle did not conduct heat as wells as nozzles in the containment structure. Testing did not take any credit for junction boxes that are installed in the containment and that would have provided an additional steam barrier during the DBE. 11 Feb, 2017 Proprietary 2014 Curtiss-Wright
12 Test Chamber Design Nozzle/ Extension Chamber Conductors exiting chamber. LOCA Chamber EPA 12 Feb, 2017 Proprietary 2014 Curtiss-Wright
13 Nozzle Extension Chamber 13 Feb, 2017 Proprietary 2014 Curtiss-Wright
14 DBE Trails Prior to performing the DBE Simulation with the test specimens, Technicians would perform several trials with dummy specimens or equivalent heat sink in the accident chamber to determine settings for superheat temperatures, over-boarding pressure, valve settings and etc. 14 Feb, 2017 Proprietary 2014 Curtiss-Wright
15 LOCA Chamber vs. Module Temperature plot Initially ~ 40 C to 50 C temperature difference from entrance to nozzle and at EPA flange on outboard end of nozzle. After about ~2 hrs. temperatures converged. Temperature in LOCA System Chamber Temperature in nozzle between modules in EPA flange 15 Feb, 2017 Proprietary 2014 Curtiss-Wright
16 Electrical Testing during H4 (LOCA) DBE Simulation Difficulties with IR testing: Customer wanted to capture insulation resistance (IR) readings on all conductors and specifically at the higher temperatures during the initial temperature plateaus. The first temperature plateau was 1 minute long and second was 10 minutes long. Tests had 150 to 350 conductors After taking IR readings needed to quickly transition to loading conductors with voltage and current. Test Set-up: Conductors inside the LOCA chamber were laid onto a grounded metal plate during LOCA testing to ensure a good ground plane. Conductors were wired in series for voltage and current. Conductors were broken down in groups of 20 or 30 conductors for IR testing. Voltage was applied to each group of conductors and insulation resistance measured. Single wire measurement was taken on each module for reference. Expected IR for the group if all conductors had the same insulation resistance as the single wire would be: 16 Feb, 2017 Proprietary 2014 Curtiss-Wright
17 Insulation Resistance Measurements IR Test Set-up Electrical Loading Voltage & Current 17 Feb, 2017 Proprietary 2014 Curtiss-Wright
18 Testing Strategies IR testing of conductor groups via Hipot testers 18 Feb, 2017 Proprietary 2014 Curtiss-Wright
19 Qualification Results Program started with the testing of 18 EPA modules from stock (inventory). Testing was extended to test an additional 6 modules removed from service at Forsmark Unit #2. Total project testing duration ~12 months. Test results after conditioned for 60 years life: Mechanically Testing results showed that modules generally did well in regards to pressure integrity and leak tightness requirements. Electrical Signal Integrity Some module types showed discontinuities or high resistance measurements during temperature aging and DBE testing. Customer was able to limit the modules requiring replacement based on test results for 40 to 60-year life extension. 19 Feb, 2017 Proprietary 2014 Curtiss-Wright
20 SUMMARY Overall joint project between two utilities provided considerable savings by sharing testing costs, resources and test samples. Position or location specific testing reduced risk of failure due to over-testing that would have occurred with enveloping DBE profiles but did required additional testing time and cost. Testing to the installed configuration with EPA on the outboard end of nozzle and at plant actual maximum currents and voltages reduced risk. Pre-planning with multiple header plate flanges and accident chambers significantly reduced project timeline. Planning of electrical testing method to monitor large quantity of electrical conductors during DBE was an important consideration including finding a suitable instrument that could measure lower IR values with grouped conductors. Standard IEC provided helpful information in regards to IR measurements during LOCA testing to avoid uncertainties during the test. Test approach resulted in limiting modules requiring replacement for plant life extension but did identify some electrical issues with certain module types. 20 Feb, 2017 Proprietary 2014 Curtiss-Wright
21 21 Feb, 2017 Proprietary 2014 Curtiss-Wright
22 Nuclear Division QualTech NP Thank You 22 October 22, 2018 Curtiss-Wright
Aug07 Rev A All Paragraphs Revised
Qualification Test Report Universal MATE-N-LOK* Connector 110-213 28Aug07 Rev A All Paragraphs Revised 1. INTRODUCTION 1.1. Purpose 1.2. Scope Testing was performed on Universal MATE-N-LOK* connectors
More informationEnvironmental Qualification
Environmental Qualification Actuation Solutions for Nuclear Powerplants Environmental Qualification of Rotork nuclear electric actuators and gearboxes Redefining Flow Control Contents Section 1 Environmental
More informationJun 20,2014 Rev A
Product Specification 108-115067 Jun 20,2014 Rev A DDR4 DIMM Through-hole Memory Socket 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the TE Connectivity
More informationJun06 Rev D
Product Specification High Speed Serial Data 2 Connector 108-1965 27Jun06 Rev D 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the Tyco Electronics High
More informationProduct Specification Rev A
Product Specification 108-6116 1. Scope :.5 Signal DBL Lock Connector 18P 1.1 Contents This specification covers the requirements for product performance, test methods and quality assurance provisions
More informationReliability Test Report
Reliability Test Report Page 1 of 29 Reliability flow Chart: Page 2 of 29 Test Group 1 1.1 Dimensional Analysis: 1.1.1 Test Purpose: These measurements are to verify that the units meet the dimensional
More informationEQ tests of electrical equipment used in Japanese NPP
2017 EQ Technical Meeting @ Clear water beach Nov.8 th -10 th. 2017 EQ tests of electrical equipment used in Japanese NPP Nov.10 Th.2017 Yasutaka Eguchi Mitsubishi Heavy Industries, LTD 7IS-AZ-20170065
More informationPF Coil Fabrication Overview
PF Coil Fabrication Overview PF Coils Information Meeting Barcelona - 15 th October 2012 This presentation is intended for reference purposes only and is not a legally binding document PF Building Layout
More informationSEP 2016 Rev D2
Product Specification 108-2112 28 SEP 2016 Rev D2 VAL-U-LOK* Connectors 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for VAL-U-LOK* Connectors. 1.2. Qualification
More informationContent Modular terminals for high-temperature applications Nuclear power terminal blocks erminal Blocks T D.1
Content Modular terminals for high-temperature applications TS 32 / Ceramic.2 -.3 Nuclear power terminal blocks Overview.4 -.5.6 -.10 Terminal Blocks.1 Modular terminals for high-temperature applications
More informationPRODUCT SPECIFICATION
1.0mm Pitch ZIF FPC Page 1 Top Entry Side Entry 1.0mm Pitch ZIF FPC Page 2 1.0 SCOPE. This specification covers performance, tests and quality requirements for 1.0mm Pitch ZIF FPC Connector 2.0 APPLICABLE
More informationJAMES F. GLEASON, P.E. CHAIRMAN QUALIFICATION COMMITTEE
JAMES F. GLEASON, P.E. CHAIRMAN QUALIFICATION COMMITTEE Presented ese ted at NPEC C Ju July y 27, 7, 2011 0 NPEC Most Nuclear Power Countries Use IEEE NPEC Standards Administrative Qualification Operations,
More informationQSFP Copper Module Direct Attach Cable Assembly &Cage
Qualification Test Report 501-60067 12Mar. 2012 Rev. 1 QSFP Copper Module Direct Attach Cable Assembly& Qualification Test Report QSFP Copper Module Direct Attach Cable Assembly & Tyco Electronics. (Shanghai)
More informationPRODUCT SPECIFICATION
ML-XT COMMERCIAL VEHICLE CONNECTOR SERIES 1.0 SCOPE This Product Specification relates to the ML-XT Commercial Vehicle, (CV), Power and/or Signal wire-to-wire connector system. This system consists of
More informationVIA Platform Environmental Qualification Testing Standards
VIA Platform Environmental Qualification Testing Standards Revision: 1 Report Dated: September 7 th 2016 Report Prepared By: Noel Joyce Reliability Lab Manager Page 1 of 16 Table of Contents 1. Purpose...
More informationSerial Attached SCSI (SAS) Connector
Product 108-51053 Specification DR: Stanley Huang 24 Oct 2013 Rev G APVD: Vincent Peng Serial Attached SCSI (SAS) Connector 1.0 SCOPE This specification covers the requirements for product performance,
More informationTE 91 PRECISION ROTARY VACUUM TRIBOMETER
TE 91 PRECISION ROTARY VACUUM TRIBOMETER Description The TE 91 Precision Rotary Vacuum Tribometer is based on a bench mounted test chamber. A motor driven test spindle, in the form of standard rotary feedthrough,
More informationPRODUCT SPECIFICATION
288 Ckt Vertical Press Fit DDR4 DIMM 2.4mm Seating Plane 1.0 SCOPE This Product Specification covers the 0.85 mm centerline gold plated DDR4 DIMM edge card connector for 1.40 +/- 0.10 thick memory modules.
More informationProduct Specification QSL RF Connectors
Product Specification QSL RF Connectors 108-2324 04Feb09 Rev A 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the Tyco Electronics QSL RF Connectors which
More informationHydrogen Station Equipment Performance Device (HyStEP Device) Specification
Hydrogen Station Equipment Performance Device (HyStEP Device) Specification Overview Policies and technology solutions need to be developed and implemented to help reduce the time from when a new hydrogen
More informationSummary of HALT, IPx7 & IP69K testing for AT Series connectors
S1-15227 Rev. A1 Corp. SINE Systems Corporation 44724 Morley Drive Clinton Twp, MI 48036 Summary of HALT, IPx7 & IP69K testing for AT Series connectors IPx7 (Submersion) PASS Requirements: Acceptance conditions
More informationPTC Thermistor for Automotive:TPM-C Series
Features 1. Qualification based on AEC-Q200 Rev-C 2. RoHS & Halogen-free compliant 3. EIA size 0603,0805 4. Fast and reliable response Recommended Applications 1. Automotive electronics Part Number Code
More informationWired for Power Generation
Instrumentation Cables Power Cables Control Cables Communications Cables Specialty Cables Wired for Power Generation Serving the Power Generation Market Wired for Power Generation Coax Low-Voltage Power
More informationSENSORS AND SYSTEMS FOR HUMIDITY AND TEMPERATURE MEASUREMENTS RELIABILITY REPORT. HS1100 / HS1101 Relative Humidity Capacitive Sensors
SENSORS AND SYSTEMS FOR HUMIDITY AND TEMPERATURE MEASUREMENTS RELIABILITY REPORT HS1100 / HS1101 Relative Humidity Capacitive Sensors Summary of the sensors resistance against various physical and chemical
More information25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:
25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.
More informationMEZALOK* Stacking Connector System
Product Specification 108-2411 25 FEB 16 Rev D MEZALOK* Stacking Connector System 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the MEZALOK* Stacking Connector
More informationPOLYFUSE Resettable PTCs Surface Mount > 2920L Series
Surface Mount > Description The device provides surface mount overcurrent protection for medium voltage ( 60V) applications where resettable protection is desired. Features Agency Approvals AGENCY AGENCY
More informationWhat Structural Engineers Should Know about Substation Rigid Bus Design
What Structural Engineers Should Know about Substation Rigid Bus Design Minnesota Power Systems Conference November 8, 2017 Paul Somboonyanon, P.E., P.Eng Agenda Substation Rigid Bus System Design Guide
More informationAccelerated Life Testing Final Report
Accelerated Life Testing Final Report November 6, 2006 Prepared by the, Project team: Lalith Jayasinghe, Conan O Rourke, Mariana Figueiro Background During the review process of the ENERGY STAR Light Fixture
More informationPTC Thermistor for Automotive:TPM-C Series
SMD PTC Thermistor for Features 1. Qualification based on AEC-Q200 Rev-C 2. RoHS & Halogen-free compliant 3. EIA size 0603,0805 4. Fast and reliable response Recommended Applications 1. Automotive electronics
More informationNTC Thermistor for Automotive: TSM-C Series
Features 1. Qualification based on AEC-Q200 Rev-C 2. Operating temperature range: -50 ~ +150 3. Superior stability in high-temperature and high-humidity environment 4. RoHS & Halogen Free (HF) compliant
More informationSPECIFICATION AND PERFORMANCE TABLE OF CONTENT. 1. Scope Reference Documents Material and Components... 2
TABLE OF CONTENT 1. Scope... 2 2. Reference Documents.. 2 3. Material and Components...... 2 4. Design and Construction..... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements
More informationWire & Cables for the Nuclear Market
Wire & Cables for the Nuclear Market AMS Informal CRP Meeting on Cables AMS Technology Center Knoxville, TN, USA 2011-08-02 Wire & Cable Solutions for the Nuclear Market Habia have provided wire and cable
More informationYour Super Pillar MCPCB Thermal Management Solution Supplier.
CofanUSA 46177 Warm Springs Blvd. Fremont CA 94539 1-877-228-3250 www.cofan-usa.com CofanCanada 2900 Langstaff Rd. #18 Vaughan, ON. L4K 4R9 Canada 1-877-228-3250 www.cofan-pcb.com Contents 1. Super Pillar
More informationQuick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description
Quick Splice II 5461 (CN) Cable (JCN) Cable 35 kv Molded Rubber Inline Splicing Kit Data Sheet Accessory Splice Jacket 1. Product Description The 3M 5461 Quick Splice II is a 35 kv class inline splice
More informationVPPC Terry Hosking, V.P. of Engineering SBE Inc.
VPPC 2009 Comparative Evaluation and Analysis of the 2008 Toyota Lexus, Camry and 2004 Prius DC Link Capacitor Assembly vs. the SBE Power Ring DC Link Capacitor --- Terry Hosking, V.P. of Engineering SBE
More informationCyclic Corrosion Chamber C.C.T AUTO Series
Cyclic Corrosion Chamber C.C.T AUTO Series CCT 5000 AUTO image merely illustrative Cooling system image merely illustrative Specifications/ Models CCT 1300 AUTO CCT 3000 AUTO CCT 5000 AUTO Allows 7 different
More informationA Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun
A Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun Robert MacGregor and Sikhanda Satapathy August, 2002 Institute for Advanced Technology The
More informationVEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY
VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY VEIKI-VNL Ltd. VEIKI-VNL Electric Large Laboratories Ltd. is an independent accredited testing member laboratory of
More informationAdvanced Techniques US Inc.
Information PRO 1600 Technology Series Reflow Solutions Ovens Product Overview Key Features Full Convection and Lead Free Compatible Reflow Oven Up to 10 individually programmable zones Small Footprint
More informationFEATURES AND BENEFITS
DESCRIPTION Honeywell Zephyr Digital Airflow Sensors: HAF Series-High Accuracy, provide a digital interface for reading airflow over the specified full scale flow span and temperature range. Their thermally
More informationMonitoring the combustion process directly on the grate of Municipal Solid Waste Incinerators Jean-Pierre Schosger & Jiri Martinec
II International Conference on W&B Combustion Oslo 17 Feb 10 1 Monitoring the combustion process directly on the grate of Municipal Solid Waste Incinerators Jean-Pierre Schosger & Jiri Martinec II International
More information3M Connector System 0.050" x 0.100" Pitch. 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810
1 of 9 3M Connector System 0.050" x 0.100" Pitch 3M Tripolarized Wiremount Socket - Series 820 3M 4-Wall, Tripolarized Header - Series 810 Product Specification 78-5110-0074-0 Released: 10-1-10 2 of 9
More informationMetal Alloy Low-Resistance Resistor Specifications
Page 1 of 14 Metal Alloy Low-Resistance Resistor Specifications March 2010 Specification Number:GCT-SPEC-011-11 Issued Date:2010/03/01 Page 2 of 14 1. Scope: 1.1 This specification is covered following
More informationHoneywell Zephyr TM Analog Airflow Sensors. HAF Series High Accuracy ±50 SCCM to ±750 SCCM
Honeywell Zephyr TM Analog Airflow Sensors HAF Series High Accuracy ±50 SCCM to ±750 SCCM Honeywell Zephyr TM Analog Airflow Sensors HAF Series - High Accuracy Honeywell Zephyr HAF Series sensors provide
More informationClass 1E LOCA Cabled Connectors
8NA Series Cabled Field Plugs Class 1E LOCA Cabled Connectors 8NA cabled field plugs are designed according to RCC-E 2005 and IEEE LOCA requirements and are suitable for safety equipments in the reactor
More informationCERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM
CP No.: CP9806 Page: 1 of 35 CERTIFIED TEST REPORT Cooper Power Systems 25 kv Class 200 Amp SEPARABLE CONNECTOR SYSTEM Includes Cooper POSI-BREAK Loadbreak Elbow and Insulated Protective Cap April 3, 1998
More information97311T. Features T Enclosed Burner with Touch Screen Control Panel. No visible flame. Touch Screen Control Panel
97311T Designed for complete automatic operation of the entire Burner System, the S&J 97311T Enclosed Flare and Touch Screen Control Panel is specifically designed to operate efficiently with low BTU anaerobic
More information2920L Series. POLY-FUSE Resettable PTCs. Surface Mount > 2920L Series. Description
RoHS Description The PTC provides surface mount overcurrent protection for medium voltage ( 60V) applications where resettable protection is desired. Features RoHS compliant, lead-free and halogen-free
More informationTABLE OF CONTENTS Page
TABLE OF CONTENTS Page Objective 3 Summary 3 Conclusion 3 Sample Preparation 4 Testing 4 Test Results 5 Summary of Test Results (Table 1) 6 Appendix I 7 Addendum 1 8 2 I. OBJECTIVE To evaluate the performance
More informationPOLYFUSE Resettable PTCs Surface Mount > 2920L Series
Surface Mount > Description The PTC provides surface mount overcurrent protection for medium voltage ( 60V) applications where resettable protection is desired. Features Agency Approvals AGENCY AGENCY
More informationPRODUCT SPECIFICATION
MultiCat TM In-line Power Connector System WIRE-TO-WIRE AND WIRE-TO-BOARD MALE CRIMP CONTACT (201845-00X0) FEMALE CRIMP CONTACT (201846-00X0) PLUG HOUSING (201840-00XX) RECEPTACLE HOUSING (201841-00XX)
More informationWM 07 Conference, February 25 March 1, 2007, Tucson, AZ. Evaluation of Glass Fiber Hepa Filters as a Function of Media Velocity
Evaluation of Glass Fiber Hepa Filters as a Function of Media Velocity S. L. Alderman, M.S. Parsons, K.U. Hogancamp, C.A. Waggoner Mississippi State University, Institute for Clean Energy Technology Starkville,
More informationSERVICE BULLETIN. Containment Atmosphere Monitoring System, CAMS
SERVICE BULLETIN Containment Atmosphere Monitoring System, CAMS 907374-01 Spare 120 VAC Solenoid Valve Sub-Assembly for 110C113-2, -5, and -6 Regulator Solenoid Assemblies 1 of 6 ANALYZER MODEL: CAMS INSITU
More informationNuclear. EGS Electrical Connection Product Catalog.
EGS Electrical Connection Product Catalog www.cwnuclear.com EGS Electrical Connection Product Catalog About Curtiss-Wright supplies safety-related and environmentally qualified electrical interconnection
More informationLV Bushing Oil to Air Dry Insulation PTAB-SLV832
LV Bushing Oil to Air Dry Insulation PTAB-SLV832 Technical Guide 600 V, 30 kv BIL, 600-2500 A 5/8" Integral Flange Bushing 1.0" Integral Flange Bushing 1.25" Bushing General Description The ABB low voltage
More informationProduct Specification
AFI Jack, Straight Orientation, Mixed Technology AFI Plug, Straight Orientation, Cable Terminated Other configurations available for: Vertical cable-to-board applications Floating Adaptor, Surface mount,
More information100 / 110 DRYWELL FUSE SPECIFICATION
100 / 110 DRYWELL FUSE SPECIFICATION 15KV & 25KV SUBMERSIBLE VACUUM LOAD INTERRUPTERS AND DRYWELL FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED SUBMERSIBLE SWITCHGEAR WITH LOAD INTERRUPTING SWITCHES
More informationPOLY-FUSE Resettable PTCs. 2920L Series. Surface Mount > 2920L Series E R RoHS. Description
2920L Series RoHS Description The 2920L Series PTC provides surface mount overcurrent protection for medium voltage ( 60V applications where resettable protection is desired. Features RoHS compliant, lead-free
More informationSCOPE OF ACCREDITATION TO ISO/IEC 17025:2005
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 ELEMENT MATERIALS TECHNOLOGY MINNEAPOLIS LLC (A subsidiary of Element Materials Technology Minneapolis Inc.) 9725 Girard Avenue South Minneapolis, MN 55431
More informationQuick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications
Quick Splice II 5451R (CN) Cable (JCN) Cable Accessory Splice Jacket 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet 1. Product Description The 3M 5451R Quick Splice II is a 25/28 kv class
More informationFeatures. V max (Vdc) I max (A) typ. (W) P d
2016L Series RoHS Description The 2016L Series PTC provides surface mount overcurrent protection for low voltage ( 60V applications where resettable protection is desired. Features RoHS compliant, lead-free
More informationQualification Test Report. DRCP 86 Pin Inline DTR # /6/2012
Qualification Test Report DRCP 86 Pin Inline DTR #120313-01 7/6/2012 1.0 SPECIFICATION REFERENCES Industrial 1.1 DCPM 2000 Deutsch Calibration Procedures Manual 2.0 TEST CONDITIONS AND EQUIPMENT 3.1 Test
More informationAutoclave Thermocouples (Type 9) and Pt100 Sensors (Type 69)
Autoclave Thermocouples (Type 9) and Pt100 Sensors (Type 69) A range of thermocouple sensors specifically designed to withstand the harsh conditions within autoclaves. Autoclave Load and Drain thermocouples
More informationHuntsville- Aerospace Testing & Engineering Services Highway 20 West Huntsville, AL 35806
Huntsville- Aerospace Testing & Engineering Services 7800 Highway 20 West Huntsville, AL 35806 Facility Overview Huntsville Facility Overview Site: Total Square Footage: 92 Acres 160,000 sq. ft. of Laboratory
More informationMay2015 Rev A
Product Specification 108-60104 15May2015 Rev A ANGLED ENTRY JACK FOR CATEGORY 6 APPLICATIONS 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the TE Connectivity
More informationTHERMAL SHOCK TEST REPORT
Report No. :DH1509300024A Version:A THERMAL SHOCK TEST REPORT Company :FLIP CHIP OPTO. INC. Address :No.185, Kewang Rd., Longtan Dist., Taoyuan City 325, Taiwan (R.O.C.) Model Name :Apollo 600-B Lot Number
More informationALD3 Diaphragm Valve Technical Report
ALD Diaphragm Valve Technical Report Scope This technical report provides data on Swagelok ALD normally closed diaphragm valves. The report covers: helium seat leak testing valve flow consistency analysis
More informationAP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface. September 2017
AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface September 2017 Randy C. Ivey Director Supplier Quality Oversight Westinghouse Electric Company AP1000 is a trademark or registered
More informationProduct Specification AMP Mini CT DC Drawer Connector, 1.5 mm Pitch Lead Free Version
Product Specification 108-60026 MP Mini CT DC Drawer Connector, 1.5 mm Pitch Lead Free Version 1. 1.1 Scope: Contents: This specification covers the requirements for product performance, test methods and
More informationHIGH SPEED MEZZANINE PRODUCT SPECIFICATION
OARD TO OARD CONNECTOR 75005 Receptacle Assembly 75003 Plug Assembly Table of Contents 1.0 Scope 2.0 Product Description 3.0 Applicable Documents and Specifications 4.0 Ratings 5.0 Performance 5.1 Qualification
More informationComparison of IG Testing Standard. IGMA Summer Meeting August 8, 2004
Comparison of IG Testing Standard IGMA Summer Meeting August 8, 2004 1 The Task Compare the new Harmonized standards to: Old ASTM stds. Canadian stds. CEN stds. (Europe) ISO std. (proposed) 2 The Standards
More informationCERTIFICATE of QUALITY TEST
Test lab CERTIFICATE of QUALITY TEST according to DIN 55 350-18 - 4.3.4. DAP-PL-3439.00 Test report - No. 7564 / 09 Client FALCOM Wireless Communications GmbH Gewerbering 6 98704 Langenwiesen Equipment
More informationFeatures Enclosed Burner. Enclosed Burner. No visible flame. Controlled Combustion environment with natural draft design
97311 The S&J 97311 Enclosed burner incinerates harmful emissions from waste gas streams. Typical applications include fermentation off gas piping systems such as anaerobic digesters or landfill gas. This
More informationDATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General purpose Class 1, NP0
Product Specification March 7, 2017 V.16 DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General purpose Class 1, 16 V TO 50 V 0.22 pf to 100 nf RoHS compliant & Halogen Free Product specification
More informationCIRCULATION HEATERS SPECIFICATIONS DESCRIPTION FEATURES CH & CHP SERIES HEAT EXCHANGE AND TRANSFER, INC. 6 to 480 kw and higher. Flanged construction
SPECIFICATIONS 6 to 480 kw and higher CIRCULATION HEATERS CH & CHP SERIES Flanged construction 208 volt through 575 volt, 3 phase 5 to 40 watts/in 2 and higher NEMA 4/12 Terminal housing DESCRIPTION Type
More informationPRODUCT SPECIFICATION
of 3 C Section : For the 200222, 2002323, 2002444, 20025, 200252, 200252, 20026, 200262, 200262, 20028, 200283, 200284, 2002822, 2002824, 200283, 2002832, 2002833, 2002834 and 2002835 series parts..0 GENERAL
More informationTest Group Description. Total Number. Figure 1. Unless otherwise stated, the following environmental conditions prevailed during testing:
Qualification Test Report 26 November 12 Rev A1 SL Series Jacks, Category 6 1. INTRODUCTION 1.1. Purpose 1.2. Scope Testing was performed on AMP NETCONNECT* SL Series Category 6 Jacks to determine their
More informationIgnition energy enough for igniting the mixture is available, such as sparkles generated by friction and impaction, electric arc or hot surfaces.
Elementary knowledge of safety and explosion protection 1.1 Characteristics of explosion A phenomenon, in which substances are converted from one state into another and massive energy and sounds are instantaneously
More informationAUG 16 Rev C2
Product Specification 23 AUG 16 Rev C2 025 Series Connector 1Row 1. SCOPE 1.1 Contents This specification covers the requirements for product performance, test methods and quality assurance provisions
More informationEXPERIMENTAL STUDY OF DYNAMIC THERMAL BEHAVIOUR OF AN 11 KV DISTRIBUTION TRANSFORMER
Paper 110 EXPERIMENTAL STUDY OF DYNAMIC THERMAL BEHAVIOUR OF AN 11 KV DISTRIBUTION TRANSFORMER Rafael VILLARROEL Qiang LIU Zhongdong WANG The University of Manchester - UK The University of Manchester
More informationCOLD PLATE SOFTWARE PROGRAM ANALYZES AIRCRAFT
COLD PLATE SOFTWARE PROGRAM ANALYZES AIRCRAFT DISPLAY T. Renaud Sanders, a Lockheed Martin Co. Nov, 2000 Introduction Finned heat exchangers, called cold plates, have been used for many years to cool military
More informationIEC SYSTEM FOR CONFORMITY TESTING AND COMMITTEE OF TESTING LABORATORIES CERTIFICATION OF ELECTRICAL EQUIPMENT
IEC SYSTEM FO CONFOMITY TESTING AND CETIFICATION OF ELECTICAL EQUIPMENT COMMITTEE OF TESTING LABOATOIES =equired by Lab S=May be subcontracted TESTING AND MEASUING EQUIPMENT/ALLOWED SUBCONTACTING Power
More information3.1 Air Pollution Control Officer (APCO): as defined in Rule 1020 (Definitions).
RULE 4352 SOLID FUEL FIRED BOILERS, STEAM GENERATORS AND PROCESS HEATERS (Adopted September 14, 1994; Amended October 19, 1995; Amended May 18, 2006; Amended December 15, 2011) 1.0 Purpose The purpose
More informationEnsuring the Safety Of Medical Electronics
Chroma Systems Solutions, Inc. Ensuring the Safety Of Medical Electronics James Richards, Marketing Engineer Keywords: 19032 Safety Analyzer, Medical Products, Ground Bond/Continuity Testing, Hipot Testing,
More informationSPECIFICATION 宏致電子股份有限公司 桃園縣中壢市東園路 13 號. No.13, Dongyuan Rd., Jhongli City, Taoyuan County 320, Taiwan (R.O.C.)
SPECIFICATION 宏致電子股份有限公司 桃園縣中壢市東園路 13 號 No.13, Dongyuan Rd., Jhongli City, Taoyuan County 320, Taiwan (R.O.C.) TEL: +886-3-463-2808 FAX: +886-3-463-1800 SPEC. NO.: PS - 87151-XXX9 REVISION: D PRODUCT NAME:
More informationE/ECE/324/Rev.1/Add.15/Rev.7/Corr.1 E/ECE/TRANS/505/Rev.1/Add.15/Rev.7/Corr.1
E/ECE/34/Rev.1/Add.15/Rev.7/Corr.1 5 November 01 Agreement Concerning the Adoption of Uniform Technical Prescriptions for Wheeled Vehicles, Equipment and Parts which can be fitted and/or be used on Wheeled
More informationNFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH
NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH Contego Latex Fire Barrier Intumescent (Also marketed in Canada by Pyrologistics,
More information3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series
3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series Data Sheet 1. Product Description 3M Cold Shrink Termination Kit QT-III 7672-S-8 Series contains one silicone rubber termination
More informationCopyright Statement FPC International, Inc
Copyright Statement All rights reserved. All material in this document is, unless otherwise stated, the property of FPC International, Inc. Copyright and other intellectual property laws protect these
More informationYARWAY NARVIK STANDARD DUTY A.T.-TEMP DESUPERHEATER MODEL 38/48
Yarway covers requirements for Desuperheaters, pneumatic actuators, strainers with a wide range of models, sizes and materials to satisfy all the specifications of the power-pulp and paper industry and
More informationRULE 4352 SOLID FUEL FIRED BOILERS, STEAM GENERATORS AND PROCESS HEATERS (Adopted September 14, 1994; Amended October 19, 1995; Amended May 18, 2006)
RULE 4352 SOLID FUEL FIRED BOILERS, STEAM GENERATORS AND PROCESS HEATERS (Adopted September 14, 1994; Amended October 19, 1995; Amended May 18, 2006) 1.0 Purpose The purpose of this rule is to limit emissions
More informationDVFL2800S Series HIGH RELIABILITY HYBRID DC-DC CONVERTERS DESCRIPTION FEATURES
HIGH RELIABILITY HYBRID DC-DC CONVERTERS DESCRIPTION The DVFL series of high reliability DC-DC converters is operable over the full military (-55 C to +125 C) temperature range with no power derating.
More information3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv
3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv Data Sheet September 2014 Description 3M Cold Shrink QT-III Silicone Rubber Termination Kits, 7640-T
More informationDATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General Purpose & High Capacitance Class 2, X7R
Product Specification October 27, 16 V.15 DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General Purpose & High Capacitance Class 2, 6.3 V TO 50 V 100 pf to 22 µf RoHS compliant & Halogen Free
More informationContent (RF Inductors) Multi-Layer High Frequency Inductors (IQ & HI Series) Cautions... 18
Content (RF Inductors) Multi-Layer High Inductors (IQ & HI Series)... 2 Ordering Code... 2 Standard External Dimensions... 3 High Q Type (IQ Series)... 4 Standard Type (HI Series)... 5 Testing Condition
More informationEffects of Fuel Weathering on RVP, Distillation and Oxygen Content of Ethanol and iso-butanol Blends
Effects of Fuel Weathering on RVP, Distillation and Oxygen Content of Ethanol and iso-butanol Blends Thomas Wallner Argonne National Laboratory Jeff Wasil Bombardier Recreational Products Engine Manufacturers
More informationCyclic Corrosion Test CORR Series
Cyclic Corrosion Test CORR Series CCT 1300 CORR image merely illustrative Specifications/Model CCT 1300 CORR CCT 3000 CORR CCT 5000 CORR - Mode: SALT SPRAY / SALT FOG - Mode: WATER CONDENSATION HUMIDITY
More informationIMX-104 High Explosive (HE) Loading of 60/81/120mm Mortars
IMX-104 High Explosive (HE) Loading of 60/81/120mm Mortars Joint U S Army & U S Marine Corps Department of the Army Pilot Plant Melt Pour/Cast Cure Loading Facility Attn: Mr. Erik Boykin Tel 973-724-4391
More information