1 INDUSTRIAL ONTROL TRANSORMRS PT, PH, PTD, PHD, SL, Q, M, VM, MV Series ontrol Transformers ontrol Transformer Quick Selection harts What Is A ontrol Transformer? ontrol Transformer Selection Guide PT Series Applications and Selection Tables PT Series Detailed Dimensions PH Series Applications and Selection Tables PTD and PHD Din Rail eatures & Selection Tables PT, PH, PTD and PHD Series using Options SL Series Applications SL Series Selection Tables & Dimensional Data SL Series using Options inger Safe Terminal overs Options Q Series Applications and Standard Specifications Q Series Selection harts VM Series Indoor/Outdoor Transformers M Series Indoor Molded urrent Transformers MV Series Medium ontrol Transformers MV Series Dimensional Drawings and use Kit... 89

2 INDUSTRIAL ONTROL TRANSORMRS ONTROL TRANSORMR QUIK SLTION HARTS PT Series ontrol Transformers PH Series ontrol Transformers Volts Sec. Volts Group Part No. Page 600, 480, 416, , 120, 99 JJ PT _MRMA , 460, , 95 PT _MMH , 415, , 120 QQ PT _MMD ,380,277,240, KK PT _MSG , 230, 208, , 115 NN PT _MHM , 230, PT _MLI , 400, /220 MM PT _MMX , 400, , 120 PP PT _MMD , 277, II PT _MGJ / /240 RR PT _QP /480,230/460,220/ , 115, 110 AA PT _MQMJ /480 12/24 LL PT _QR / PT _QG / /240 SS PT _PP / DD PT _PG 37 Pri. Volts Sec. Volts Group Part No. Page J PH _AM A PH _AJ /240 PH _AP K PH _AG /24 X PH _AR PH _J L PH _G /240 I PH _KP R PH _KG / /240 PH _QP PH _MJ M PH _MG / /240 H PH _SP D PH _LJ S PH _LG / /240 G PH _PP /240 12/24 P PH _PR Q PH _JJ N PH _JG O PH _J 57 PTD & PHD Series Transformers Pri. Volts Sec. Volts Group Part No. Page PHD-A PHD _AJ PHD-K PHD _AG /24 PHD-X PHD _AR / ,115,110 PTD-AA PTD _MQMJ / /240 PHD- PH _QP /480 12/24 PTD-LL PTD _QR / /240 PTD-SS PTD _PP / PTD-DD PTD _PG /240 12/24 PTD-TT PTD _PR PHD-N PHD _JG 68 Q Series ontrol Transformers Pri. Volts Sec. Volts Group Part No. Page / Q 9P /24 8 Q _PR_ / / Q 6P 86 30

3 STION 91 INDUSTRIAL ONTROL TRANSORMRS WHAT IS A ONTROL TRANSORMR? What is a ontrol Transformer? A control transformer is an isolation transformer designed to provide a high degree of secondary voltage stability (regulation) during a brief period of overload condition (also referred to as inrush current ). ontrol transformers are also known as Machine Tool Transformers, Industrial ontrol Transformers or ontrol Power Transformers. When you calculate the VA requirement of a Transformer, do you use the or the? When selecting the VA requirement, you use the. an you use a ontrol Transformer connected in reverse? Yes, a control transformer can be connected in reverse. However, keep in mind the output voltage will be less than its rating, due to the compensation factor of the windings. an a ontrol Transformer regulate the output voltage? A control transformer will not regulate the voltage. Output voltage is a function of the coil s turn ratio only, times the input voltage. What is the benefit of Vacuum Impregnation on a Transformer? All Hammond ontrol Transformers are vacuum impregnated with VT Polyester Resin and oven cured which seals the surface and eliminates moisture. Impregnating the entire unit provides a strong mechanical bond and offers protection from environmental conditions. xplain the VA or Volt Ampere Output Rating? The VA or volt ampere output rating designates the output which a transformer can deliver for a specifi ed time at its rated secondary voltage and rated frequency, without exceeding its specifi ed temperature rise. Insulating Materials, what are they made of and what is their purpose? Hammond Power Solutions utilizes Mylar, Nomex and other high quality insulating materials. Insulation is used to electrically insulate turn to turn windings, layer to layer windings, primary to secondary windings and ground. What is the effect of Overload? When a transformer is continually overloaded, excessive heat develops and the insulation system will begin to breakdown. As a result, the life expectancy of the transformer is shortened due to the heat exceeding the rating of the insulation system. 31

4 INDUSTRIAL ONTROL TRANSORMRS ONTROL TRANSORMR SLTION Selecting a ontrol Transformer requires that you have fi rst hand knowledge of the application for the transformer, and that you understand some basic terms related to the selection process. y using the following information, you will be sure to select the Hammond ontrol Transformer which best meets your application. The Hammond PT Series machine tool control transformers are specifi cally designed for high inrush applications requiring reliable output voltage stability. Designed to meet industrial applications where electromagnetic devices such as relays, solenoids, etc. are used, the Hammond PT series transformers maximize inrush capability and output voltage regulation when electromagnetic devices are initially energized. To select the proper transformer, three characteristics of the load circuit must first be determined. They are total steady-state (sealed) VA, total inrush VA, and inrush load power factor. A. The total steady state sealed VA is the amount of VA that the transformer must supply to the load circuit for an extended length of time. Simply add the total steady-state VA of all devices in your control circuit. The operating VA data of these components is available from the manufacturers.. The total inrush VA is the amount of VA that the transformer must supply for all components in the control circuit which are energized together. Some consideration to the start-up sequence may be required. Inrush VA should be obtained from the device manufacturer.. The inrush load power factor is diffi cult to determine without detailed vector analysis of all the control circuit components. Such information is not generally available. Therefore, Hammond is recommending that a value of 40% power factor be utilized. Although some other control transformer manufacturers still recommend a power factor of only 20%, Hammond, through recent tests conducted on many popular brands of control devices has determined that the 40% power factor value is more accurate. Once the above circuit variables have been determined, transformer selection is a six (6) step process. SIX ASY STPS 1. Determine what your (supply) and (output) voltage requirements are, as well as your required frequency (i.e. 60 Hz) 2. alculate the Total Sealed VA of your circuit. (See Step A) 3. Now calculate the Inrush VA by adding the inrush VA of all components being energized together. Remember to add the sealed VA of all components that do not have inrush VA, (lamps, timers etc.) as they do however present a load to the transformer during maximum inrush. If the inrush for the components in your circuit are not known, assume a 40% Inrush Power actor. 4. alculate the Total Inrush VA using one of the two methods: A. Total Inrush VA = (VA sealed) 2 + (VA inrush) 2 OR. Total Inrush VA = VA Sealed + VA Inrush Note: method will result in a slightly larger transformer being selected. 5. If the nominal supply voltage does not fl uctuate more than 5%, then reference the 90% secondary voltage column in the Regulation Data Table for the correct VA rating. If the supply voltage varies upwards of 10%, the 95% secondary voltage column should be used to size the transformer. urrent standards require electromagnetic devices to operate reliably at a minimum of 85% of their rated voltage. However, contact life may be affected with continuous start-ups at that voltage level. Therefore, the minimum 85% secondary voltage column should only be used as a reference. 6. Using the regulation data tables below, select the appropriate VA rated transformer: A) with a continuous VA rating that is equal to or greater than the value in Step 2. ) with a maximum inrush VA equal to or greater than the value obtained in Step 4. To determine the correct Hammond Transformer and its atalog Number, just refer to the tables in this catalog for the voltage ratings, frequency and corresponding VA required. PT TRANSORMRS RGULATION DATA TAL ontinuous VA Inrush 40% Power actor Transformer 85% 90% 95% Nameplate Rating It is recommended that a ontrol Transformer be sized at a 40% Power actor. Some components in a circuit, such as electromagnetic devices, typically operate at that level due to their inherently lower power factor. Selecting a transformer at 40% Power actor will more than adequately size the unit for all the various loads in the circuit. 32

5 STION 91 PT SRIS ONTROL TRANSORMRS PT Series ontrol Transformer - Applications The Hammond PT series of machine tool transformers, now Marked, are specifi cally designed for high inrush applications requiring reliable output voltage stability. Designed to meet industrial applications where electromagnetic devices such as relays, solenoids, etc. are used, the Hammond PT series transformers maximize inrush capability and output voltage regulation when electromagnetic devices are initially energized. STANDARDS Hammond Industrial and Machine Tool ontrol and Instrument Transformers meet or exceeds the standards established by UL, SA, IR, ANSI, NMA. Standard ile # VA Size UL (ANSI/UL 506) All PT SA (22-2 No. 66) LR3902 All PT I 989 NMA (ST-1) All Molded PT s All PT At HAMMOND, we rate the VA capacity of our transformers at the output... where it counts. Other transformer manufacturers rate their capacity on the input side of the transformer, which can result in a 5% to 20% lower actual VA at the output. 33

6 PT SRIS ONTROL TRANSORMRS eatures enefits OR & OILS High quality, high permeability silicon steel laminations. All-welded construction. omputer designed copper wound coils with optimum turns ratio. INSULATION Mylar, Nomex and other insulating materials are used for phase to phase and layer to layer insulation. The PT series transformers have the following insulation systems: Up to 200 VA ; class A, 55 rise, 105 class. 250 to 1000 VA ; class, 80 rise, 130 class VA and up ; class, 115 rise, 180 class. VAUUM IMPRGNATION All Hammond ontrol Transformers are Vacuum Impregnated with VT (vinyl-toluene) Polyester Resin. Oven cured after vacuum impregnating. MOLDD ONSTRUTION All PT series transformers, up to 1000 VA, are molded in a UL 94 fl ame retardant polyester compound. These units have a thermal plastic, injection molded cover with distinctive cooling fi ns. TRMINAL LOKS abricated from molded high-impact resin, fi nished in black. ombination Phillips (#2) and Robertson (# 2) Red terminal screws with #9 head, 8-32 UN threads. Terminals are tinned brass and chrome plated, and all connections are soldered. Terminals are torque tested with automatic drivers. NAMPLAT lack letters on white background including terminal markings, schematic and mark. Polyester, non conductive material. MOUNTING PLAT Offers an unique Universal Plate made of heavy steel, welded to the core. INGR SA TRMINAL OVRS inger safe terminal covers for both fused and unfused terminals, in a clear, see through fi nish, are available for all molded PT series units. STANDARD SONDARY US LIPS ach PT series transformer, that has a single secondary, comes with a factory installed secondary fuse kit (fuses not included). OR & OILS Provides optimum performance and reliability. Rugged one-piece assembly with low noise. nhanced voltage regulation with excellent thermal characteristics. INSULATION Provides the best insulated control transformer in the industry. Insulation materials are of the highest rating available for the temperature class. Assures long life and reliable performance. VAUUM IMPRGNATION Impregnating the entire unit provides a strong mechanical bond and offers protection against environmental conditions. Seals the surface and eliminates moisture. MOLDD ONSTRUTION ompletes the protection process by sealing the core and coils against moisture, dirt and other airborne contaminants. Strong and durable, yet still dissipates heat quickly and effi ciently. TRMINAL LOKS asy access to terminals while separation barriers prevent unintentional contact. Versatile screw head with optimum torque and retention ability. Assures integrity and strength of connections and terminals Withstands any manual installation method. NAMPLAT ase of readability results in easier installation. Safe for other conductors, even in close proximity. MOUNTING PLAT Provides direct interchangeability with many other popular control transformers. INGR SA TRMINAL OVRS This ensures your protection against electric shock or accidental contact of any kind, and complies with I and requirements. STANDARD SONDARY US LIPS Accommodates 13/32 X 1 1/2 Midget use. 34

7 STION 91 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. D A D A IGUR A IGUR Group AA 240/480, 230/460, 220/ , 115, /60 Hertz H1 X2 H3 H2 120V 115V 110V X H4 X1 240 H1, H4 H1-H3, H2-H4 230 H1, H4 H1-H3, H2-H4 220 H1, H4 H1-H3, H2-H4 480 H1, H4 H3-H2 460 H1, H4 H3-H2 440 H1, H4 H3-H2 120 X2, X 115 X2, X 110 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MQMJ A X PT50MQMJ A X PT75MQMJ A X PT100MQMJ A X PT150MQMJ A / X PT200MQMJ A / X PT250MQMJ A / X PT300MQMJ A / x PT350MQMJ A / X PT500MQMJ A / X PT750MQMJ A / X PT1000MQMJ A / X PT1500MQMJ / x PT2000MQMJ / x PT3000MQMJ / x PT5000MQMJ / x Height dimension () does not include fuse clip (applicable up to 1000VA jumpers are included. fuse clips for 13/32 X 1 1/2 fuse included up to 1000VA. Open style units (1500VA to 5000VA) do not carry the mark. The output amps listed above are based on a 115V secondary. 35

8 PT SRIS ONTROL TRANSORMRS Group 575, 460, , 95 50/60 Hertz jumpers and fuse clips are not applicable. jumpers are included. Open style units (1500VA to 5000VA) do not carry the mark. H1 X3 575V 460V H3 230V H2 X2 95V 115V H4 X1 575 H1, H4 460 H1, H3 230 H1, H2 115 X1, X3 95 X1, X2 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MMH X PT50MMH X PT75MMH X PT100MMH X PT150MMH / X PT200MMH / X PT250MMH / X PT300MMH / x PT350MMH / X PT500MMH / X PT750MMH / X PT1000MMH / X PT1500MMH / x PT2000MMH / x PT3000MMH / x PT5000MMH / x The output amps listed above are based on a 115V secondary. Group 240/ /60 Hertz H1 X2 H3 H2 24V X H4 X1 480 H1, H4 H2-H3 240 H1, H4 H1-H3, H2-H4 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25QG A X PT50QG A X PT75QG A X PT100QG A X PT150QG A / X PT200QG A / X PT250QG A / X PT300QG A / x PT350QG A / X PT500QG A / X PT750QG A / X Height dimension () does not include secondary fuse clip. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. 36

9 STION 91 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. D A D A IGUR A IGUR D A IGUR Group DD 120/ /60 Hertz H1 X2 H3 H2 24V X H4 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H2-H3 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25PG A X PT50PG A X PT75PG A X PT100PG A X PT150PG A / X PT200PG A / X PT250PG A / X PT300PG A / x PT350PG A / X PT500PG A / X PT750PG A / X Height dimension () does not include secondary fuse clip. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. 37

10 PT SRIS ONTROL TRANSORMRS Group 460, 230, /60 Hertz H1 X2 460V 230V H3 208V H2 115V X H4 X1 460 H1, H4 230 H1, H3 208 H1, H2 115 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MLI A X PT50MLI A X PT75MLI A X PT100MLI A X PT150MLI A / X PT200MLI A / X PT250MLI A / X PT300MLI A / x PT350MLI A / X PT500MLI A / X PT750MLI A / X PT1000MLI A / X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse are included. jumpers not applicable. Group II 380, 277, /60 Hertz H1 X2 380V 277V H3 208V H2 120V X H4 X1 380 H1, H4 277 H1, H3 208 H1, H2 120 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MGJ A X PT50MGJ A X PT75MGJ A X PT100MGJ A X PT150MGJ A / X PT200MGJ A / X PT250MGJ A / X PT300MGJ A / x PT350MGJ A / X PT500MGJ A / X PT750MGJ A / X PT1000MGJ A / X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse are included. jumpers not applicable. 38

11 STION 91 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. Group LL 240/480 12/24 D A 50/60 Hertz IGUR A H1 H3 H2 H4 X4 X2 X3 X1 D A IGUR 480 H1, H4 H2-H3 240 H1,H4 H1-H3, H2-H4 12 X1, X4 X1-X3, X2-X4 24 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25QR 2.08/ X PT50QR 4.17/ X PT75QR 6.25/ X PT100QR 8.33/ X PT150QR 12.5/ / X PT200QR 16.7/ / X PT250QR 20.8/ / X and jumpers are included. fuse clips are not applicable. Group MM 415, 400, /220 50/60 Hertz H1 H2 H3 H4 0V 380V 400V X4 X2 X3 X1 415V 415V H1, H4 400V H1, H3 380V H1, H2 110V X1, X4 X1-X3, X2-X4 220V X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MMX 1.04/ x PT50MMX 2.08/ x PT75MMX 3.13/ x PT100MMX 4.17/ x PT150MMX 6.25/ / x PT200MMX 8.33/ / x PT250MMX 10.42/ / x PT350MMX 14.58/ / x PT500MMX 20.83/ / x PT750MMX 31.25/ / x PT1000MMX 41.67/ / x jumpers and fuse clips are not applicable. jumpers are included. All dimensions are inches unless otherwise specifi ed. *Hammond does not offer uropean style metric fuse clips. 39

12 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. D A IGUR D D A IGUR Group JJ (Universal, Open Style Transformer) 600, 480, 416, , 120, 99 50/60 Hertz H1 H2 H3 H4 H5 0V 130V 120V 240V 99V 416V 480V X4 X3 X2 X1 600V 0V 600 H1, H5 480 H1, H4 416 H1, H3 240 H1, H2 130 X1, X4 120 X1, X3 99 X1, X2 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 50 PT50MRMA D X PT75MRMA D X PT100MRMA D X PT150MRMA D / X PT200MRMA D / X PT250MRMA D / X PT350MRMA D / X PT500MRMA D / X and jumpers, and fuse clips are not applicable. Group JJ open style units from (50VA to 500VA) do not carry the mark. The output amps listed above are based on a 120V secondary. Group KK (Universal, Open Style Transformer) 480, 380, 277, 240, /60 Hertz H1 H2 H3 H4 H5 H6 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 50 PT50MSG X PT75MSG X PT100MSG X PT150MSG / X PT200MSG / X PT250MSG / X PT350MSG / X PT500MSG / X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse are included. jumpers not applicable. Group KK open style units (50VA to 500VA) do not carry the mark. 0V X2 208V 240V 24V 277V 380V 480V X X1 480 H1, H6 380 H1, H5 277 H1, H4 240 H1, H3 208 H1, H2 24 X2, X 40

13 STION 91 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. D A IGUR A Group NN 460, 230, 208, , /60 Hertz H1 H2 H3 H4 0V 115V 200V 208V 24V 230V 460V 0V X3 X2 X X1 460V H1, H4 230V H1, H3 208V H1, H2 200V H1, H2 115 X1, X3 24 X1, X2 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MHM A 1.04/ x PT50MHM A 2.08/ x PT75MHM A 3.13/ x PT100MHM A 4.17/ x PT150MHM A 6.25/ / x PT200MHM A 8.33/ / x PT250MHM A 10.42/ / x PT350MHM A 14.58/ / x PT500MHM A 20.83/ / x Height dimension () does not include secondary fuse clip. fuse clips for 13/32 x 1 1/2 fuse included. jumpers not applicable. All dimensions are inches unless otherwise specifi ed. *Hammond does not offer uropean style metric fuse clips. 41

14 PT SRIS ONTROL TRANSORMRS Group PP 415, 400, , /60 Hertz Height dimension () does not include secondary fuse clip. fuse clips for 13/32 x 1 1/2 fuse included. jumpers not applicable. H1 H2 H3 H4 0V 120V 240V 24V 400V 415V 0V X3 X2 X X1 415V H1, H4 400V H1, H3 240V H1, H2 120V X1, X3 24 X1, X2 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MMD A 1.04/ x PT50MMD A 2.08/ x PT75MMD A 3.13/ x PT100MMD A 4.17/ x PT150MMD A 6.25/ / x PT200MMD A 8.33/ / x PT250MMD A 10.42/ / x PT350MMD A 14.58/ / x PT500MMD A 20.83/ / x All dimensions are inches unless otherwise specifi ed. *Hammond does not offer uropean style metric fuse clips. Group QQ 480, 415, , /60 Hertz H1 H2 H3 H4 0V 400V 415V 480V 120V 24V 0V X3 X2 X X1 400V H1, H4 415V H1, H3 480V H1, H2 120V X1, X3 24 X1, X2 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25MMD A 1.04/ x PT50MMD A 2.08/ x PT75MMD A 3.13/ x PT100MMD A 4.17/ x PT150MMD A 6.25/ / x PT200MMD A 8.33/ / x PT250MMD A 10.42/ / x PT350MMD A 14.58/ / x PT500MMD A 20.83/ / x Height dimension () does not include secondary fuse clip. fuse clips for 13/32 x 1 1/2 fuse included. jumpers not applicable. All dimensions are inches unless otherwise specifi ed. *Hammond does not offer uropean style metric fuse clips. 42

15 STION 91 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. D A D A IGUR A IGUR Group RR 240/ /240 50/60 Hertz H1 H3 H2 H4 X4 X2 X3 X1 240 H1, H4 H1-H3, H2-H4 480 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25QP 0.21/ x PT50QP 0.42/ x PT75QP 0.63/ x PT100QP 0.83/ X PT150QP 1.25/ / x PT200QP 1.67/ / x PT250QP 2.08/ / x PT300QP 2.50/ / x PT350QP 2.92/ / x PT500QP 4.17/ / x PT750QP 6.25/ / x PT1000QP 8.33/ / x and jumpers are included. fuse clips are not applicable. 43

16 PT SRIS ONTROL TRANSORMRS or detailed mounting dimensions by VA size, please refer to diagrams on Page 45. D A IGUR Group SS 120/ /240 50/60 Hertz H1 H3 H2 H4 X4 X2 X3 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PT25PP 0.21/ x PT50PP 0.42/ x PT75PP 0.63/ x PT100PP 0.83/ X PT150PP 1.25/ / x PT200PP 1.67/ / x PT250PP 2.08/ / x PT300PP 2.50/ / x PT350PP 2.92/ / x PT500PP 4.17/ / x PT750PP 6.25/ / x PT1000PP 8.33/ / x and jumpers are included. fuse clips are not applicable. 44

17 STION 91 PT SRIS ONTROL TRANSORMRS Detailed Dimensions VA VA X 0.44 Slots (4) 0.22 X 0.75 Slots (4) VA, 100 VA 150 VA, 200 VA, 250 VA L A 0.22 X 0.50 Slots (4) 0.22 X 0.75 Slots (8) VA, 500 VA 750 VA, 1000 VA A L D D A 0.22 X 0.75 Slots (8) G X H Slots (8) plates for units larger than 1000VA are not illustrated. Please consult customer service for any information you require. 45

18 PH SRIS ONTROL TRANSORMRS PH Series ontrol Transformer - Applications The Hammond PH series of machine tool transformers are specifi cally designed for high inrush applications requiring reliable output voltage stability. Designed to meet industrial applications where electromagnetic devices such as relays, solenoids, etc. are used, the Hammond PH series transformers maximize inrush capability and output voltage regulation when electromagnetic devices are initially energized. STANDARDS Hammond Industrial and Machine Tool ontrol and Instrument Transformers meet or exceeds the standards established by UL, SA, IR, ANSI, NMA. Standard ile # VA Size UL (ANSI/UL 506) All PH SA (22-2 No. 66) LR3902 All PH NMA (ST-1) All PH At HAMMOND, we rate the VA capacity of our transformers at the output... where it counts. Other transformer manufacturers rate their capacity on the input side of the transformer, which can result in a 5% to 20% lower actual VA at the output. 46

19 STION 91 PH SRIS ONTROL TRANSORMRS eatures enefits OR & OILS High quality, high permeability silicon steel laminations. All-welded construction. omputer designed copper wound coils with optimum turns ratio. INSULATION Mylar, Nomex and other insulating materials are used for phase to phase and layer to layer insulation. The PH series transformers have the following insulation systems: Up to 200 VA ; class A, 55 rise, 105 class. 250 to 1500 VA ; class, 80 rise, 130 class VA and up ; class, 115 rise, 180 class. VAUUM IMPRGNATION All Hammond ontrol Transformers are Vacuum Impregnated with VT (vinyl-toluene) Polyester Resin. Oven cured after vacuum impregnating. MOLDD ONSTRUTION All PH series transformers, up to 1000 VA, are molded in a UL 94 fl ame retardant polyester compound. These units have a thermal plastic, injection molded cover with distinctive cooling fi ns. TRMINAL LOKS abricated from molded high-impact resin, fi nished in black. ombination Phillips (#2) and Robertson (# 2) Red terminal screws with #9 head, 8-32 UN threads. Terminals are tinned brass and chrome plated, and all connections are soldered. Terminals are torque tested with automatic drivers. NAMPLAT lack letters on white background including terminal markings, schematic and SA and UL logos. Polyester, nonconductive material. MOUNTING PLAT Offers the traditional Hammond plate made of heavy steel, and welded to the core. INGR SA TRMINAL OVRS inger safe terminal covers for both fused and unfused terminals, in a clear, see through fi nish, are available for all molded PH series units. STANDARD SONDARY US LIPS ach PH series transformer, that has a single secondary, comes with a factory installed secondary fuse kit (fuses not included). OR & OILS Provides optimum performance and reliability. Rugged one-piece assembly with low noise. nhanced voltage regulation with excellent thermal characteristics. INSULATION Provides the best insulated control transformer in the industry. Insulation materials are of the highest rating available for the temperature class. Assures long life and reliable performance. VAUUM IMPRGNATION Impregnating the entire unit provides a strong mechanical bond and offers protection against environmental conditions. Seals the surface and eliminates moisture. MOLDD ONSTRUTION ompletes the protection process by sealing the core and coils against moisture, dirt and other airborne contaminants. Strong and durable, yet still dissipates heat quickly and effi ciently. TRMINAL LOKS asy access to terminals while separation barriers prevent unintentional contact. Versatile screw head with optimum torque and retention ability. Assures integrity and strength of connections and terminals Withstands any manual installation method. NAMPLAT ase of readability results in easier installation. Safe for other conductors, even in close proximity. MOUNTING PLAT Provides direct interchangeability with many other popular control transformers. INGR SA TRMINAL OVRS This ensures your protection against electric shock or accidental contact of any kind. STANDARD SONDARY US LIPS Accommodates 13/32 X 1 1/2 Midget use. 47

20 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR Group A 600 H1 600V H2 600 H1, H Hertz X2 120V X X1 120 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25AJ A X PH50AJ A X PH75AJ A X PH100AJ A X PH150AJ A X PH200AJ A X PH250AJ A X PH350AJ A X PH500AJ A X PH750AJ A X PH1000AJ A X PH1500AJ / X PH2000AJ / X PH3000AJ / X Height dimension () does not include secondary fuse clip (applicable up to 1000VA). fuse clips for 13/32 X 1 1/2 fuse included up to 1000VA. jumpers not applicable. 48

21 STION 91 PH SRIS ONTROL TRANSORMRS Group Hertz H1 X2 480V 120V X H2 X1 480 H1, H2 120 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25J A X PH50J A X PH75J A X PH100J A X PH150J A X PH200J A X PH250J A X PH350J A X PH500J A X PH750J A X PH1000J A X PH1500J / X PH2000J / X Height dimension () does not include secondary fuse clip (applicable up to 1000VA). fuse clips for 13/32 X 1 1/2 fuse included up to 1000VA. jumpers not applicable. Group Hertz H1 X2 240V 120V X H2 X1 240 H1, H2 120 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25MJ A X PH50MJ A X PH75MJ A X PH100MJ A X PH150MJ A X PH200MJ A X PH250MJ A X PH350MJ A X PH500MJ A X PH750MJ A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. 49

22 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR D A IGUR Group D Hertz H1 X2 208V 120V X H2 X1 208 H1, H2 120 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25LJ A X PH50LJ A X PH75LJ A X PH100LJ A X PH150LJ A X PH200LJ A X PH250LJ A X PH350LJ A X PH500LJ A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. 50

23 STION 91 PH SRIS ONTROL TRANSORMRS Group / Hertz jumpers and fuse clips are not applicable. jumpers are included. H1 600V H2 X4 X2 X3 X1 600 H1, H2 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25AP.21/ X PH50AP.42/ X PH75AP.63/ X PH100AP.83/ X PH150AP 1.25/ X PH200AP 1.67/ X PH250AP 2.08/ X PH350AP 2.92/ X PH500AP 4.17/ X PH750AP 6.25/ X PH1000AP 8.33/ X PH1500AP 12.5/ / X PH2000AP 16.7/ / X PH3000AP 25.0/ / X PH5000AP 41.7/ / X PH7500AP 62.5/ / X Group 240/ / Hertz H1 H3 H2 H4 X4 X2 X3 X1 240 H1, H4 H1-H3, H2-H4 480 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25QP.21/ X PH50QP.42/ X PH75QP.63/ X PH100QP.83/ X PH150QP 1.25/ X PH200QP 1.67/ X PH250QP 2.08/ X PH350QP 2.92/ X PH500QP 4.17/ X PH750QP 6.25/ X PH1000QP 8.33/ X PH1500QP 12.5/ X PH2000QP 16.7/ X PH3000QP 25.0/ X PH5000QP 41.7/ X PH7500QP 62.5/ X and jumpers are included. fuse clips are not applicable. 51

24 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR D A IGUR Group G 120/ / Hertz H1 H3 H2 H4 X4 X2 X3 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25PP.21/ X PH50PP.42/ X PH75PP.63/ X PH100PP.83/ X PH150PP 1.25/ X PH200PP 1.67/ X PH250PP 2.08/ X PH350PP 2.92/ X PH500PP 4.17/ X PH750PP 6.25/ X PH1000PP 8.33/ X PH1500PP 12.5/ / X PH2000PP 16.7/ / X and jumpers are included. fuse clips are not applicable. 52

25 STION 91 PH SRIS ONTROL TRANSORMRS Group H 208/ / Hertz H1 H3 H2 H4 X4 X2 X3 X1 208 H1, H4 H1-H3, H2-H4 416 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25SP.21/ X PH50SP.42/ X PH75SP.63/ X PH100SP.83/ X PH150SP 1.25/ X PH200SP 1.67/ X PH250SP 2.08/ X PH350SP 2.92/ X PH500SP 4.17/ X PH750SP 6.25/ X PH1000SP 8.33/ X PH1500SP 12.5/ / X PH2000SP 16.7/ / X PH3000SP 25.0/ / X PH5000SP 41.7/ / X and jumpers are included. fuse clips are not applicable. Group I / Hertz H1 347V H2 X4 X2 X3 X1 347 H1, H2 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25KP.21/ X PH50KP.42/ X PH75KP.63/ X PH100KP.83/ X PH150KP 1.25/ X PH200KP 1.67/ X PH250KP 2.08/ X PH350KP 2.92/ X PH500KP 4.17/ X PH750KP 6.25/ X PH1000KP 8.33/ X PH1500KP 12.5/ / X PH2000KP 16.7/ / X PH3000KP 25.0/ / X and jumpers are included. fuse clips are not applicable. 53

26 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR Group J 600 H1 600V H2 600 H1, H Hertz X2 240V X X1 240 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25AM A X PH50AM A X PH75AM A X PH100AM A X PH150AM A X PH200AM A X PH250AM A X PH350AM A X PH500AM A X PH750AM A X PH1000AM A X PH1500AM / X Height dimension () does not include secondary fuse clip (applicable up to 1000VA). fuse clips for 13/32 X 1 1/2 fuse included up to 1000VA. jumpers not applicable. 54

27 STION 91 PH SRIS ONTROL TRANSORMRS Group K Hertz H1 X2 600V 24V X H2 X1 600 H1, H2 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25AG A X PH50AG A X PH75AG A X PH100AG A X PH150AG A X PH200AG A X PH250AG A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. Group L Hertz H1 X2 480V 24V X H2 X1 480 H1, H2 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25G A X PH50G A X PH75G A X PH100G A X PH150G A X PH200G A X PH250G A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. 55

28 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR Group M 240 H1 240V H2 240 H1, H Hertz X2 24V X X1 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25MG A X PH50MG A X PH75MG A X PH100MG A X PH150MG A X PH200MG A X PH250MG A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. 56

29 STION 91 PH SRIS ONTROL TRANSORMRS Group N Hertz H1 X2 120V 24V X H2 X1 120 H1, H2 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25JG A X PH50JG A X PH75JG A X PH100JG A X PH150JG A X PH200JG A X PH250JG A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. Group O Hertz H1 X2 120V 12V X H2 X1 120 H1, H2 12 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25J A X PH50J A X PH75J A X PH100J A X PH150J A X PH200J A X PH250J A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. 57

30 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR Group P D A IGUR 120/240 12/24 60 Hertz H1 H3 H2 H4 X4 X2 X3 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H1-H3 12 X1, X4 X1-X3, X2-X4 24 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25PR 2.08/ X PH50PR 4.17/ X PH75PR 6.25/ X PH100PR 8.33/ X PH150PR 12.5/ X PH200PR 16.7/ X PH250PR 20.8/ X PH350PR 29.2/ X PH500PR 41.7/ X PH750PR 62.5/ X PH1000PR 83.3/ X PH1500PR 125/ / X PH2000PR 167/ / X PH3000PR 250/ / X and jumpers are included. fuse clips are not applicable. 58

31 STION 91 PH SRIS ONTROL TRANSORMRS Group Q Hertz H1 X2 120V 120V X H2 X1 120 H1, H2 120 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25JJ A X PH50JJ A X PH75JJ A X PH100JJ A X PH150JJ A X PH250JJ A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. Group R Hertz H1 X2 347V 24V X H2 X1 347 H1, H2 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25KG A X PH50KG A X PH75KG A X PH100KG A X PH150KG A X PH200KG A X PH250KG A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. 59

32 PH SRIS ONTROL TRANSORMRS D A D A IGUR A IGUR Group S 208 H1 208V H2 208 H1, H Hertz X2 24V X X1 24 X2, X VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25LG A X PH50LG A X PH75LG A X PH100LG A X PH150LG A X PH200LG A X PH250LG A X Height dimension () does not include secondary fuse clip. fuse clips for 13/32 X 1 1/2 fuse included. jumpers not applicable. Group X /24 60 Hertz H1 600V H2 X4 X2 X3 X1 600 H1, H2 12 X1, X4 X1-X3, X2-X4 24 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions enters Mtg. Slot Shipping Rating Number ig. Amps A D G X H Wt/Lbs 25 PH25AR 2.08/ X PH50AR 4.17/ X PH75AR 6.25/ X PH100AR 8.33/ X PH150AR 12.5/ X PH200AR 16.67/ X PH250AR 20.83/ X jumpers and fuse clips are not applicable. jumpers are included. 60

33 STION 91 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS DIN Rail Mount PT & PH Series ontrol Transformers The Hammond DIN rail mount PT and PH series of machine tool transformers are designed to meet the requirements for panel mounted industrial control applications. This line offers the same features as our standard PT and PH units except the base has been confi gured for mounting on DIN rail. Hammond is pleased to introduce the NW PTD and PHD series... the fi rst DIN rail mountable industrial control transformers offered in the market. The benefi ts of the DIN rail mounting includes: No incorrect back-plate holes. lexibility in locating the transformer virtually anywhere in the panel. No drilling necessary. No metal shavings to dispose. Substitute or replace any transformer quickly and effi ciently. All products installed in the control panel can now be bench work assembled. All the same great features of the PT and PH series with the ease of DIN rail mounting. Optional anti-vibration bracket for high vibration applications and long range shipments. Shows 3 sizes of PTD DIN rail units mounted in panel. Shows a PTD DIN rail unit mounted in a panel complete with both primary and secondary fusing options installed. The transformer hooks on to the top edge of the DIN rail. The clamping plate is tightened up under the bottom edge of the rail. STANDARDS Hammond Industrial and Machine Tool ontrol and Instrument Transformers meet or exceeds the standards established by UL, SA, IR, ANSI, NMA. Standard ile # VA Size ixed Plate UL (ANSI/UL 506) All PTD & PHD SA (22-2 No. 66) LR3902 All PTD & PHD I 989 All Molded PTD s lamp Plate NMA (ST-1) All PTD & PHD 61

34 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS eatures enefits OR & OILS High quality, high permeability silicon steel laminations. All-welded construction. omputer designed copper wound coils with optimum turns ratio. INSULATION Mylar, Nomex and other insulating materials are used for phase to phase and layer to layer insulation. The PTD and the PHD series transformers have the following insulation systems: Up to 200 VA ; class A, 55 rise, 105 class. 250 to 500 VA ; class, 80 rise, 130 class. VAUUM IMPRGNATION All Hammond ontrol Transformers are Vacuum Impregnated with VT (vinyl-toluene) Polyester Resin. Oven cured after vacuum impregnating. MOLDD ONSTRUTION All PTD and PHD series transformers, up to 1000 VA, are molded in a UL 94 fl ame retardant polyester compound. These units have a thermal plastic, injection molded cover with distinctive cooling fi ns. TRMINAL LOKS abricated from molded high-impact resin, fi nished in black. ombination Phillips (#2) and Robertson (# 2) Red terminal screws with #9 head, 8-32 UN threads. Terminals are tinned brass and chrome plated, and all connections are soldered. Terminals are torque tested with automatic drivers. NAMPLAT lack letters on white background including terminal markings, schematic and mark (PTD series only). Polyester, nonconductive material. DIN RAIL MOUNTING Offers a 2-way Din Rail mounting system. A welded mounting plate and an adjustable clamping plate. INGR SA TRMINAL OVRS inger safe terminal covers for both fused and unfused terminals, in a clear, see through fi nish, are available for all molded PTD and PHD units. STANDARD SONDARY US LIPS ach PTD and PHD series transformer, that has a single secondary, comes with a factory installed secondary fuse kit (fuses not included). OR & OILS Provides optimum performance and reliability. Rugged one-piece assembly with low noise. nhanced voltage regulation with excellent thermal characteristics. INSULATION Provides the best insulated control transformer in the industry. Insulation materials are of the highest rating available for the temperature class. Assures long life and reliable performance. VAUUM IMPRGNATION Impregnating the entire unit provides a strong mechanical bond and offers protection against environmental conditions. Seals the surface and eliminates moisture. MOLDD ONSTRUTION ompletes the protection process by sealing the core and coils against moisture, dirt and other airborne contaminants. Strong and durable, yet still dissipates heat quickly and effi ciently. TRMINAL LOKS asy access to terminals while separation barriers prevent unintentional contact. Versatile screw head with optimum torque and retention ability. Assures integrity and strength of connections and terminals Withstands any manual installation method. NAMPLAT ase of readability results in easier installation. Safe for other conductors, even in close proximity. DIN RAIL MOUNTING Provides for easy and quick installation onto standard DIN rail systems with no drilling and few tools. INGR SA TRMINAL OVRS This ensures your protection against electric shock or accidental contact of any kind, and complies with I and requirements. STANDARD SONDARY US LIPS Accommodates 13/32 X 1 1/2 Midget use. 62

35 STION 91 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS A IGUR A Group PTD-AA 240/480, 230/460, 220/ , 115, /60 Hertz H1 X2 H3 H2 120V 115V 110V X H4 X1 240 H1, H4 H1-H3, H2-H4 230 H1, H4 H1-H3, H2-H4 220 H1, H4 H1-H3, H2-H4 480 H1, H4 H3-H2 460 H1, H4 H3-H2 440 H1, H4 H3-H2 120 X2, X 115 X2, X 110 X2, X VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PTD25MQMJ A PTD50MQMJ A PTD75MQMJ A PTD100MQMJ A PTD150MQMJ A PTD200MQMJ A PTD250MQMJ A PTD300MQMJ A PTD350MQMJ A PTD500MQMJ A Height dimension () does not include secondary fuse clips. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. The output amps are based on a 115V secondary. Note: Other DIN rail voltage units are available upon request. 63

36 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS Group PTD-DD 120/ /60 Hertz H1 X2 H3 24V H2 X H4 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H2-H3 24 X2, X VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PTD25PG A PTD50PG A PTD75PG A PTD100PG A PTD150PG A PTD200PG A PTD250PG A PTD300PG A PTD350PG A PTD500PG A Height dimension () does not include secondary fuse clips. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. Group PTD-LL 240/480 12/24 50/60 Hertz H1 H3 H2 H4 X4 X2 X3 X1 240 H1, H4 H1-H3, H2-H4 480 H1, H4 H2-H3 12 X1, X4 X1-X3, X2-X4 24 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PTD25QR 2.08/ PTD50QR 4.17/ PTD75QR 6.25/ PTD100QR 8.33/ PTD150QR 12.5/ PTD200QR 16.7/ PTD250QR 20.8/ and jumpers are included. fuse clips are not applicable. Note: Other DIN rail voltage units are available upon request. 64

37 STION 91 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS A A IGUR A IGUR Group PTD-SS 120/ /240 50/60 Hertz H1 H3 H2 H4 X4 X2 X3 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PTD25PP 0.21/ PTD50PP 0.42/ PTD75PP 0.63/ PTD100PP 0.83/ PTD150PP 1.25/ PTD200PP 1.67/ PTD250PP 2.08/ PTD300PP 2.50/ PTD350PP 2.92/ PTD500PP 4.17/ and jumpers are included. fuse clips are not applicable. Note: Other DIN rail voltage units are available upon request. 65

38 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS Group PTD-TT 120/240 12/24 50/60 Hertz H1 H3 H2 H4 X4 X2 X3 X1 120 H1, H4 H1-H3, H2-H4 240 H1, H4 H2-H3 12 X1, X4 X1-X3, X2-X4 24 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PTD25PR 2.08/ PTD50PR 4.17/ PTD75PR 6.25/ PTD100PR 8.33/ PTD150PR 12.5/ PTD200PR 16.7/ PTD250PR 20.8/ PTD300PR 29.2/ PTD350PR 41.7/ PTD500PR 62.5/ and jumpers are included. fuse clips are not applicable. Group PHD-A Hertz H1 X2 600V 120V X H2 X1 600 H1, H2 120 X2, X VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PHD25AJ A PHD50AJ A PHD75AJ A PHD100AJ A PHD150AJ A PHD200AJ A PHD250AJ A PHD350AJ A PHD500AJ A Height dimension () does not include secondary fuse clips. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. Note: Other DIN rail voltage units are available upon request. 66

39 STION 91 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS A A IGUR A IGUR Group PHD- 240/ / Hertz H1 H3 H2 H4 X4 X2 X3 X1 240 H1, H4 H1-H3, H2-H4 480 H1, H4 H2-H3 120 X1, X4 X1-X3, X2-X4 240 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PHD25QP 0.21/ PHD50QP 0.42/ PHD75QP 0.63/ PHD100QP 0.83/ PHD150QP 1.25/ PHD200QP 1.67/ PHD250QP 2.08/ PHD350QP 2.92/ PHD500QP 4.17/ and jumpers are included. fuse clips are not applicable. Note: Other DIN rail voltage units are available upon request. 67

40 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS Group PHD-K Hertz H1 X2 600V 24V X H2 X1 600 H1, H2 24 X2, X VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PHD25AG A PHD50AG A PHD75AG A PHD100AG A PHD150AG A PHD200AG A PHD250AG A Height dimension () does not include secondary fuse clips. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. Group PHD-N Hertz H1 X2 120V 24V X H2 X1 120 H1, H2 24 X2, X VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PHD25JG A PHD50JG A PHD75JG A PHD100JG A PHD150JG A PHD200JG A PHD250JG A Height dimension () does not include secondary fuse clips. jumpers and fuse clips for 13/32 X 1 1/2 fuse are included. Note: Other DIN rail voltage units are available upon request. 68

41 STION 91 DIN RAIL MOUNT PT & PH SRIS ONTROL TRANSORMRS A A IGUR A IGUR Group PHD-X /24 60 Hertz H1 600V H2 X4 X2 X3 X1 600 H1, H2 12 X1, X4 X1-X3, X2-X4 24 X1, X4 X2-X3 VA atalog Mtg. Output Overall Dimensions Shipping Rating Number ig. Amps A Wt/Lbs 25 PHD25AR 2.08/ PHD50AR 4.17/ PHD75AR 6.25/ PHD100AR 8.33/ PHD150AR 12.5/ PHD200AR 16.67/ PHD250AR 20.83/ jumpers are included. jumpers and fuse clips are not applicable. Note: Other DIN rail voltage units are available upon request. 69

42 PT, PH, PTD and PHD SRIS USING OPTIONS PT, PH, PTD and PHD Series using Options The PT, PH, PTD and PHD ontrol Transformers, with terminal covers installed comply with I requirements for a fi nger safe device. These control units can be sized directly to meet both North American and I Standards. All PT, PH, PTD and PHD series control transformers with a single secondary, come standard with 13/32 X 1 1/2 midget fuse clips on the secondary. using options are available on all PT, PH, PTD and PHD series control transformers, up to 5000VA on factory installed fuse kits, and 1000VA on all fi eld installed fuse kits. ILD INSTALLD USING OPTIONS ield Installed use Kits Maximum Applicable VA use Kit Minimum (block mounted) (clip mounted) atalog No. Quantity 12 V 24 V 120V & up (Refer to Note 1) Purchase (none) 1/4" x 1 1/4" glass K kit (of 10) (none) 13/32" x 1 1/2" midget K kit (of 10) Dual Rejection 13/32" x 1 1/2" midget K-3 1 box Dual Rejection 1/4" x 1 1/4" glass K-6 1 box Single Rejection 1/4" x 1 1/4" glass K-9 1 box Single Rejection 13/32" x 1 1/2" midget K-10 1 box Dual Rejection Not Included K-11 1 box Dual Midget Not Included K-12 1 box Dual Rejection Single Midget (block mount) K-14 (Note 2) 1 box Notes: (1) fuse clips for 13/32 x 11/2" midget fuse are standard on all single secondary voltages. (2) Uses one triple pole fuse block containing: two rejection clips for the primary and one single midget (13/32" X 1 1/2") fuse clip for the secondary. This will allow for the fusing of most transformers containing multiple secondary voltages. ield and actory Installed use Kit Height Dimension Adders or PT and PH ontrol Transformers VA Size urrent PT urrent PH ield Installed Kit actory Installed Kit Dim. Height Dim. Height Dim. Height Adder Dim. Height Adder " " 1.50" " " 1.50" " " 1.50" " " 1.33" " " 1.33" " " 1.45" " " 1.45" " " 1.50" " " 1.50" " " 1.50" " " 1.50" " 6.25 N/A 1.50" " 6.25 N/A 1.50" " 6.25 N/A 1.50" " 7.50 N/A 1.50" 7500 NA 7.50 N/A N/A 70

43 STION 91 PT, PH, PTD and PHD SRIS USING OPTIONS PT, PH, PTD, PHD Series using Options continued... ILD INSTALLD PRIMARY US KITS onvenient and versatile primary fuse kits are available to suit any nominal supply voltage. Assembled as a single pole primary fuse block, line to neutral voltage such as 120 volts, can be accommodated. As a double pole fuse block, line to line voltage can be fused, including 600, 480, 240 volts. ither the safety-rejection type or the standard midget style fuse can be used by selecting the appropriate fuse kit below. All Hammond pre-engineered primary fuse kits includes a fuse block, lead wire harness, mounting plate and clips, and all necessary mounting hardware. Single Pole use Kit (for units up to 1000VA) Double Pole use Kit (for units up to 1000VA) Triple Pole use Kit (for units up to 1000VA) Links links are separately packaged for user installation to ensure links are installed on the correct voltage combination. The links are included at no charge. ield Installed use Kits fuse kits consist of all necessary fuse clips, hardware and voltage links. use clips are easy to install in the terminal block (see diagram below). uses are then easily snapped into place. (uses not included) 71

44 actory Installed using Options PT, PH, PTD and PHD SRIS USING OPTIONS When factory installed fusing options are selected by adding the appropriate suffi x, transformers will be shipped with the corresponding primary and secondary fusing as indicated in the chart below. actory Installed used Kits Maximum Applicable VA Add Suffix to (block mounted) (clip mounted) atalog Part Number 12 V 24 V 120V & up (Min. order 10 pieces) (none) Not Installed (none) 1/4" x 1 1/4" glass (none) 13/32" x 1 1/2" midget Standard (Note 1) Dual Rejection 13/32" x 1 1/2" midget (Note 2) Dual Rejection 1/4" x 1 1/4" glass Single Rejection 1/4" x 1 1/4" glass Single Rejection 13/32" x 1 1/2" midget Dual Rejection Not included Dual Midget Not included Dual Rejection Single Midget (block mount) (Note 3) Notes: (1) fuse clips for 13/32 x 11/2" midget fuse are standard on all single secondary voltages. (2) Dual Rejection/ Midget fuse kits (-3) are stocked in the following voltage combination: Group AA (PT MQMJ) > 240/480 volts, 120 volts Group (PT QG) > 240/480 volts, 24 volts Group A (PH AJ) > 600 volts, 120 volts Group PTD-AA (PTD MQMJ) > 240/480 volts, 120 volts Group PHD-A (PHD AJ) > 600 volts, 120 volts (3) Uses one triple pole fuse block containing: two rejection clips for the primary and one single midget (13/32" X 1 1/2") fuse clip for the secondary. This will allow for the fusing of most transformers containing multiple secondary voltages. Links links are separately packaged for user installation to ensure links are installed on the correct voltage combination. The links are included at no charge. actory Installed use Kits fuse kits consist of all necessary fuse clips, hardware and voltage links. use clips are easy to install in the terminal block (see diagram below). uses are then easily snapped into place. (uses not included) 72

45 STION 91 PT, PH, PTD and PHD SRIS USING OPTIONS PT, PH, PTD, PHD Series using Options conttinued... ATORY INSTALLD PRIMARY US KITS Our pre-engineered factory installed primary fuse kits, now mounted directly onto the transformer core, includes the fuse block, lead wire harness, mounting plate and hardware. Single Pole use Kit (for units up to 1000VA) Double Pole use Kit (for units up to 1000VA) Triple Pole use Kit (for units up to 1000VA) Double Pole use Kit (for Open Style units over 1000VA) Triple Pole use Kit (for Open Style units over 1000VA) 73

46 PT, PH, PTD and PHD SRIS USING OPTIONS Recommendations or Overcurrent Protection UL AND SA (NORTH AMRIAN) STANDARDS North American standards, including UL 508, National lectric ode 450 and the anadian lectrical ode Part I, require overcurrent protection on all control circuit transformers. There are two options for overcurrent protection: Option 1 Provide an overcurrent device in the primary circuit rated to the current of the transformer. The overcurrent limits are as follows: 9 amps or more; 2 to 9 amps; less than 2 amps; no more than 125% of rated current. no more than 167% of rated current. no more than 300% of rated current for power circuits. no more than 500% of rated current for control circuits. This method is considered less desirable as start-up inrush to the transformer can frequently surpass the current rating of the device and result in nuisance interruptions. Option 2 The second option is to install overcurrent devices in both the primary and secondary circuits of the transformer. In this option, the secondary device must be rated no more than 125% of rated current of the transformer and the primary no more than 250%. permits 300% overcurrent on the primary for this option. In both options listed, it is recommended that time delay fuses be considered to avoid unnecessary interruptions. The overcurrent protection listed below, in amperes, is 125% of the rated current of the transformer. hoose the next higher fuse rating if these numbers do not correspond with standard fuse selections. Sec. VA RATING / /10 3-2/ / /10 8/10 1-1/4 1-8/10 2-1/2 3-1/2 4-1/ / /10 8/10 1-1/4 1-6/10 2-1/2 3-1/ /10 8/10 1-1/4 1-6/10 2-1/2 3-2/ / /10 3/4 1-1/8 1-1/2 2-1/ /2 4-1/ / /10 6/ / / /10 6/ / /2 3-2/ /2 6-1/ /100 3/10 1/2 3/4 1-1/8 1-1/2 1-8/10 2-1/4 2-1/2 3-1/2 5-6/ /100 3/10 1/2 6/ /10 1-8/ /2 3-1/ /100 3/10 1/2 6/ /4 1-6/ /4 3-2/

47 STION 91 PT, PH, PTD and PHD SRIS USING OPTIONS Recommendations for Overcurrent Protection continued... (UL and SA) To assist in the selection of fuses, the following chart recommends the maximum primary fuse rating in amperes. The fi rst number shown is the maximum overcurrent protection when the primary current is less than 2 amps and the overcurrent protection device is rated for 300%. The second number shown (in brackets) is recommended when the primary is less than 2 amps and the overcurrent device is to be rated at 500% of rated current. Where only one number is indicated, the primary is 2 amps or more and one rating of over current protection is shown as optimal. hoose the next higher fuse rating if these numbers do not correspond with standard fuse selections. Pri. VA RATING Volt /10 1-1/4 1-8/10 2-1/2 3-1/ (1) (2) (3-2/10) (4) (6-1/4) (8) 120 6/10 1-1/4 1-8/10 2-1/4 3-1/ (1) (2) (3) (4) (6-1/4) (8) 200 3/10 3/4 1-1/8 1-1/2 2-1/ /2 4-1/ / (6/10) (1-1/4) (1-8/10) (2-1/2) (3-1/2) 5 (6-1/4) (7-1/2) (8) 208 3/10 6/ / /10 3-1/ (6/10) (1-1/8) (1-8/10) (2-1/4) (3-1/2) (4-1/2) (6) (7) (8) 220 3/10 6/ / /2 3-2/ / (1/2) (1-1/8) (1-6/10) (2-1/4) (3-2/10) (4-1/2) (5-6/10) (6-1/4) (7-1/2) 230 3/10 6/10 8/10 1-1/4 1-8/10 2-1/2 3-2/10 3-1/2 4-1/ (1/2) (1) (1-6/10) (2) (3-2/10) (4) (5) (6-1/4) (7-1/2) 240 3/10 6/10 8/10 1-1/4 1-8/10 2-1/ / / (1/2) (1) (1-1/2) (2) (3) (4) (5) (6-1/4) (7) 277 1/4 1/2 8/ / /2 3-2/10 3-1/ (4/10) (8/10) (1-1/4) (1-8/10) (2-1/2) (3-1/2) (4-1/2) (5) (6-1/4) (9) 347 1/4 1/2 8/ / /2 3-2/10 3-1/ / / (4/10) (8/10) (1-1/4) (1-8/10) (2-1/2) (3-1/2) (4-1/2) (5) (6-1/4) (9) 380 3/16 3/10 1/2 3/4 1-1/8 1-1/2 1-8/10 2-1/4 2-1/2 3-1/2 5-6/10 4-1/2 6-1/ (3/10) (6/10) (8/10) (1-1/4) (1-8/10) (2-1/2) (3-2/10) (3-1/2) (4-1/2) (6-1/4) (9) 400 3/16 3/10 1/2 3/4 1-1/8 1-1/2 1-8/10 2-1/4 2-1/2 3-1/2 5-6/10 4-1/2 6-1/ (3/10) (6/10) (8/10) (1-1/4) (1-8/10) (2-1/2) (3) (3-1/2) (4) (6-1/4) (9) /100 3/10 1/2 6/ /10 1-8/ /2 3-1/ (3/10) (6/10) (8/10) (1-1/8) (1-8/10) (2-1/4) (3) (3-1/2) (4) (6) (9) /100 3/10 1/2 6/ /4 1-6/ /4 3-2/ (1/4) (1/2) (8/10) (1-1/8) (1-6/10) (2-1/4) (2-8/10) (3-2/10) (3-1/2) (5-6/10) (8) /100 3/10 4/10 6/10 8/10 1-1/4 1-6/10 1-8/10 2-1/4 3-2/10 4-1/2 3-1/ (1/4) (1/2) (8/10) (1) (1-6/10) (2) (2-1/2) (3-2/10) (3-1/2) (5) (8) /100 3/10 4/10 6/10 8/10 1-1/4 1-1/2 1-8/ /2 3-1/ (1/4) (1/2) (3/4) (1) (1-1/2) (2) (2-1/2) (3) (3-1/2) (5) (7-1/2) 550 1/8 1/4 4/10 1/2 8/ /4 1-6/10 1-8/10 2-1/ / (2/10) (4/10) (6/10) (8/10) (1-1/4) (1-8/10) (2-1/4) (2-1/2) (3) (4-1/2) (6-1/4) 575 1/8 1/4 3/10 1/2 3/ /4 1-1/2 1-8/10 2-1/2 3-1/ / (2/10) (4/10) (6/10) (8/10) (1-1/4) (1-6/10) (2) (2-1/2) (3) (4) (6-1/4) 600 1/8 2/10 3/10 1/2 3/4 8/10 1-1/4 1-1/2 1-6/10 2-1/4 3-1/ (2/10) (4/10) (6/10) (8/10) (1-1/4) (1-6/10) (2) (2-1/2) (2-8/10) (4) (6-1/4) References: UL 508, 32.7 UL 845, and N (c) exception #2 N (b) 1 and 2 Part I,

48 PT, PH, PTD and PHD SRIS USING OPTIONS I (UROPAN) STANDARDS I (uropean) Standards are very different from UL (North American) standards including fuses and fuse selection guidelines. As the electrical characteristics of these fuses are different, UL and I rated fuses are NOT interchangeable. Of signifi cance is the time current characteristics. uses built to North American standards DO NOT MT uropean Standards. Unlike North American standards whereby overcurrent protection is to be 125% of the rated current of the transformer (25% derated), no derating is required for I using applications. (I) Sec. MAXIMUM ROMMNDD I US RATING Volt 25VA 50VA 75VA 100VA 150VA 200VA 250VA 300VA 350VA 500VA 750VA 1000VA 12 V 2.08 A 4.17 A 6.25 A 8.33 A 9.00 A A A A A A A A 24 V 1.04 A 2.08 A 3.13 A 4.17 A 1.08 A 8.33 A A A A A A A 90 V 0.28 A 0.56 A 0.83 A 1.11 A 0.49 A 2.22 A 2.78 A 3.33 A 3.89 A 5.56 A 8.33 A A 95 V 0.26 A 0.53 A 0.79 A 1.05 A 0.23 A 2.11 A 2.63 A 3.16 A 3.68 A 5.26 A 7.89 A A 100 V 0.25 A 0.50 A 0.75 A 1.00 A 0.12 A 2.00 A 2.50 A 3.00 A 3.50 A 5.00 A 7.50 A A 110 V 0.23 A 0.45 A 0.68 A 0.91 A 0.06 A 1.82 A 2.27 A 2.73 A 3.18 A 4.55 A 6.82 A 9.09 A 115 V 0.22 A 0.43 A 0.65 A 0.87 A 0.04 A 1.74 A 2.17 A 2.61 A 3.04 A 4.35 A 6.52 A 8.70 A 120 V 0.21 A 0.42 A 0.63 A 0.83 A 0.02 A 1.67 A 2.08 A 2.50 A 2.92 A 4.17 A 6.25 A 8.33 A 220 V 0.11 A 0.23 A 0.34 A 0.45 A 0.02 A 0.91 A 1.14 A 1.36 A 1.59 A 2.27 A 3.41 A 4.55 A 230 V 0.11 A 0.22 A 0.33 A 0.43 A 0.03 A 0.87 A 1.09 A 1.30 A 1.52 A 2.17 A 3.26 A 4.35 A 240 V 0.10 A 0.21 A 0.31 A 0.42 A 0.03 A 0.83 A 1.04 A 1.25 A 1.46 A 2.08 A 3.13 A 4.17 A Note: I publication 127, Sheet III, Type M fuses are recommended. (I) Pri. MAXIMUM ROMMNDD I US RATING Volt 25VA 50VA 75VA 100VA 150VA 200VA 250VA 300VA 350VA 500VA 750VA 1000VA 230 V 0.11 A 0.22 A 0.33 A 0.43 A 0.03 A 0.87 A 1.09 A 1.30 A 1.52 A 2.17 A 3.26 A 4.35 A 240 V 0.10 A 0.21 A 0.31 A 0.42 A 0.03 A 0.83 A 1.04 A 1.25 A 1.46 A 2.08 A 3.13 A 4.17 A 115 V 0.31 A 0.57 A 0.78 A 1.10 A 1.57 A 1.98 A 2.50 A 2.92 A 3.44 A 5.01 A 7.25 A 9.44 A 120 V 0.30 A 0.55 A 0.75 A 1.05 A 1.50 A 1.90 A 2.40 A 2.80 A 3.30 A 4.80 A 6.95 A 9.05 A 200 V 0.18 A 0.33 A 0.45 A 0.63 A 0.90 A 1.14 A 1.44 A 1.68 A 1.98 A 2.88 A 4.17 A 5.43 A 208 V 0.17 A 0.32 A 0.43 A 0.61 A 0.87 A 1.10 A 1.38 A 1.62 A 1.90 A 2.77 A 4.01 A 5.22 A 220 V 0.16 A 0.30 A 0.41 A 0.57 A 0.82 A 1.04 A 1.31 A 1.53 A 1.80 A 2.62 A 3.79 A 4.94 A 230 V 0.16 A 0.29 A 0.39 A 0.55 A 0.78 A 0.99 A 1.25 A 1.46 A 1.72 A 2.50 A 3.63 A 4.72 A 240 V 0.15 A 0.28 A 0.38 A 0.53 A 0.75 A 0.95 A 1.20 A 1.40 A 1.65 A 2.40 A 3.47 A 4.53 A 277 V 0.13 A 0.24 A 0.32 A 0.45 A 0.65 A 0.82 A 1.04 A 1.21 A 1.43 A 2.08 A 3.01 A 3.92 A 347 V 0.10 A 0.19 A 0.26 A 0.36 A 0.52 A 0.66 A 0.83 A 0.97 A 1.14 A 1.66 A 2.40 A 3.13 A 380 V 0.09 A 0.17 A 0.24 A 0.33 A 0.47 A 0.60 A 0.76 A 0.88 A 1.04 A 1.52 A 2.19 A 2.86 A 400 V 0.09 A 0.17 A 0.23 A 0.32 A 0.45 A 0.57 A 0.72 A 0.84 A 0.99 A 1.44 A 2.08 A 2.71 A 416 V 0.09 A 0.16 A 0.22 A 0.30 A 0.43 A 0.55 A 0.69 A 0.81 A 0.95 A 1.38 A 2.00 A 2.61 A 440 V 0.08 A 0.15 A 0.20 A 0.29 A 0.41 A 0.52 A 0.65 A 0.76 A 0.90 A 1.31 A 1.90 A 2.47 A 460 V 0.08 A 0.14 A 0.20 A 0.27 A 0.39 A 0.50 A 0.63 A 0.73 A 0.86 A 1.25 A 1.81 A 2.36 A 480 V 0.07 A 0.14 A 0.19 A 0.26 A 0.38 A 0.47 A 0.60 A 0.70 A 0.82 A 1.20 A 1.74 A 2.26 A 550 V 0.07 A 0.12 A 0.16 A 0.23 A 0.33 A 0.41 A 0.52 A 0.61 A 0.72 A 1.05 A 1.52 A 1.97 A 575 V 0.06 A 0.11 A 0.16 A 0.22 A 0.31 A 0.40 A 0.50 A 0.58 A 0.69 A 1.00 A 1.45 A 1.89 A 600 V 0.06 A 0.11 A 0.15 A 0.21 A 0.30 A 0.38 A 0.48 A 0.56 A 0.66 A 0.96 A 1.39 A 1.81 A Note: I publication 127, Sheet I, Type T fuses are recommended. 76

49 STION 91 SL SRIS ONTROL TRANSORMRS SL Series ontrol Transformers Applications Hammond is pleased to introduce a line of specialty control transformers ideally suited for general purpose, industrial, light duty loads. Designed for applications where high inrush or machine tool duty are not necessary, the SL control transformer offers an effi cient and economical solution. These units are well suited for HVA applications, signal and alarm systems, small motors, lighting and circuit isolation. The SL control transformer is an open style unit with molded terminal blocks, but available with a full array of features including 10 fusing options, multiple primary and secondary voltages and optional clear plastic fi nger safe terminal covers. or an economical approach for control transformers, the SL is the transformer of choice. eatures SA ertifi ed (fi le LR3902 and LR38216), UL Listed (fi le 50394). Meets NMA and ANSI standards. Molded terminal blocks for primary and secondary connections up to 1000 VA. Open terminals over 1000 VA. 60 Hz Operation Welded core construction oils with high dielectric strength insulation. All SL Series Transformers are Vacuum Impregnated with VT (vinyl-toluene) Polyester Resin and oven cured. Mylar, Nomex and other insulating materials are used. The SL series transformers have the following insulation systems: Up to 150 VA: 55 rise, 105 temperature class (A) 200 VA to 1500 VA: 80 rise, 130 temperature class () 2000 VA to 5000 VA: 115 rise, 180 temperature class () 77

50 SL SRIS ONTROL TRANSORMRS SL Series Selection Tables PART NUMRS 25 VA 50 VA 75 VA 100 VA 150 VA 200 VA 250 VA 350 VA SL25AM SL50AM SL75AM SL100AM SL150AM SL200AM SL250AM SL350AM /240 SL25AP SL50AP SL75AP SL100AP SL150AP SL200AP SL250AP SL350AP SL25AJ SL50AJ SL75AJ SL100AJ SL150AJ SL200AJ SL250AJ SL350AJ SL25AG SL50AG SL75AG SL100AG SL150AG SL200AG SL250AG SL350AG /24 SL25AR SL50AR SL75AR SL100AR SL500AR SL200AR SL250AR SL350AR SL25A SL50A SL75A SL100A SL150A SL200A SL250A SL350A SL25M SL50M SL75M SL100M SL150M SL200M SL250M SL350M SL25J SL50J SL75J SL100J SL150J SL200J SL250J SL350J SL25G SL50G SL75G SL100G SL150G SL200G SL250G SL350G /24 SL25R SL50R SL75R SL100R SL150R SL200R SL250R SL350R /240 SL25KP SL50KP SL75KP SL100KP SL150KP SL200KP SL250KP SL350KP 240/ SL25QJ SL50QJ SL75QJ SL100QJ SL150QJ SL200QJ SL250QJ SL350QJ 240/ /240 SL25QP SL50QP SL75QP SL100QP SL150QP SL200QP SL250QP SL350QP 240/480 12/24 SL25QR SL50QR SL75QR SL100QR SL150QR SL200QR SL250QR SL350QR SL25MJ SL50MJ SL75MJ SL100MJ SL150MJ SL200MJ SL250MJ SL350MJ SL25LJ SL50LJ SL75LJ SL100LJ SL150LJ SL200LJ SL250LJ SL350LJ SL25LG SL50LG SL75LG SL100LG SL150LG SL200LG SL250LG SL350LG 120/ SL25PG SL50PG SL75PG SL100PG SL150PG SL200PG SL250PG SL350PG /24 SL25JR SL50JR SL75JR SL100JR SL150JR SL200JR SL250JR SL350JR SL25JG SL50JG SL75JG SL100JG SL150JG SL200JG SL250JG SL350JG SL25J SL50J SL75J SL100J SL150J SL200J SL250J SL350J PART NUMRS 500 VA 750 VA 1000 VA 1500 VA 2000 VA 3000 VA 5000 VA SL500AM SL750AM SL1000AM SL1500AM SL2000AM /240 SL500AP SL750AP SL1000AP SL1500AP SL2000AP SL500AJ SL750AJ SL1000AJ SL1500AJ SL2000AJ SL3000AJ SL5000AJ SL500AG /24 SL500AR SL500A SL500M SL750M SL1000M SL1500M SL2000M SL500J SL750J SL1000J SL1500J SL2000J SL3000J SL500G /24 SL500R /240 SL500KP SL750KP SL1000KP SL1500KP SL2000KP 240/ SL500QJ SL750QJ SL1000QJ SL1500QJ SL2000QJ 240/ /240 SL500QP SL750QP SL1000QP SL1500QP SL2000QP 240/480 12/24 SL500QR SL500MJ SL750MJ SL1000MJ SL1500MJ SL2000MJ SL500LJ SL750LJ SL1000LJ SL1500LJ SL2000LJ SL500LG 120/ SL500PG /24 SL500JR SL500JG SL500J 78

51 STION 91 SL SRIS ONTROL TRANSORMRS SL Series Dimensional Data VA ig. SL Dimensions Weight Size No. A D Slot G X H (Lbs.) 25 VA X VA X VA X VA X VA X VA X VA X VA X VA X VA X VA X VA / X VA / X VA / X VA / X All Dimensions In Inches Note: with a primary fuse kit installed, the depth and height dimensions will increase as follows: depth: height: with a secondary fuse kit installed, the height dimension will increase as follows: all dimensions are +/ unless otherwise noted. IGUR 1 IGUR 2 D A D A 79

52 SL SRIS USING OPTIONS SL Series using Options oth primary and secondary fuse kits are also available for the SL Series control transformers, either factory installed or fi eld installed from prepackaged kits. ILD INSTALLD USING OPTIONS ield Installed use Kits Maximum Applicable VA use Kit Minimum (block mounted) (clip mounted) atalog No. Quantity 12 V 24 V 120V & up Purchase (none) 1/4" x 1 1/4" glass K kit (of 10) (none) 13/32" x 1 1/2" midget K kit (of 10) Dual Rejection 13/32" x 1 1/2" midget K-3 1 box Dual Rejection 1/4" x 1 1/4" glass K-6 1 box Single Rejection 1/4" x 1 1/4" glass K-9 1 box Single Rejection 13/32" x 1 1/2" midget K-10 1 box Dual Rejection Not Included K-11 1 box Dual Midget Not Included K-12 1 box Dual Rejection Single Midget (block mount) K-14 (Note 1) 1 box Notes: (1) Uses one triple pole fuse block containing: two rejection clips for the primary and one single midget (13/32" X 1 1/2") fuse clip for the secondary. This will allow for the fusing of most transformers containing multiple secondary voltages. use Kits To protect the transformer from the load, secondary fuse kits are available. use clips for either 1/4 X 1 1/4 fuses or 13/32 X 1 1/2 fuses are optional. oth are suitable for single secondary SL series transformers. use Kits consist of all necessary fuse clips, mounting hardware and voltage links. use kits are easy to install on the terminal block (see diagram below). uses are then easily snapped into place. (uses not included). Links links are separately packaged for user installation to ensure links are installed on the correct voltage combination. The links are included at no charge. 80

53 STION 91 SL SRIS USING OPTIONS SL Series using Options continued... ield Installed use Kits onvenient and versatile primary fuse kits are available to suit any nominal supply voltage. Assembled as a single pole primary fuse block, line to neutral voltage such as 120 volts, can be accommodated. As a double pole fuse block, line to line voltage can be fused, including 600, 480, 240 volts. ither the safety-rejection type or the standard midget style fuse can be used by selecting the appropriate fuse kit below. All Hammond pre-engineered primary fuse kits includes a fuse block, lead wire harness, mounting plate and clips, and all necessary mounting hardware. Single Pole use Kit (for units up to 1000VA) Double Pole use Kit (for units up to 1000VA) Triple Pole use Kit (for units up to 1000VA) 81

54 SL SRIS USING OPTIONS ATORY INSTALLD USING OPTIONS When factory installed fusing options are selected by adding the appropriate suffi x, transformers will be shipped with the corresponding primary and secondary fusing as indicated in the chart below. actory Installed used Kits Maximum Applicable VA Add Suffix to (block mounted) (clip mounted) atalog Part Number 12 V 24 V 120V & up (Min. order 10 pieces) (none) Not Installed Standard (none) 1/4" x 1 1/4" glass (none) 13/32" x 1 1/2" midget Dual Rejection 13/32" x 1 1/2" midget Dual Rejection 1/4" x 1 1/4" glass Single Rejection 1/4" x 1 1/4" glass Single Rejection 13/32" x 1 1/2" midget Dual Rejection Not included Dual Midget Not included Dual Rejection Single Midget (block mount) (Note 1) Notes: (1) Uses one triple pole fuse block containing: two rejection clips for the primary and one single midget (13/32" X 1 1/2") fuse clip for the secondary. This will allow for the fusing of most transformers containing multiple secondary voltages. Links links are separately packaged for user installation to ensure links are installed on the correct voltage combination. The links are included at no charge. actory Installed use Kits fuse kits consist of all necessary fuse clips, hardware and voltage links. use clips are easy to install in the terminal block (see diagram below). uses are then easily snapped into place. (uses not included) 82

55 STION 91 SL SRIS USING OPTIONS SL Series using Options continued... actory Installed use Kits Our pre-engineered factory installed primary fuse kits, now mounted directly to the transformer core, includes the fuse block, lead wire harness, mounting plate and hardware. Single Pole use Kit (for units up to 1000VA) Double Pole use Kit (for units up to 1000VA) Triple Pole use Kit (for units up to 1000VA) Double Pole use Kit (for Open Style units over 1000VA) Triple Pole use Kit (for Open Style units over 1000VA) 83

56 INDUSTRIAL ONTROL TRANSORMRS Optional inger Safe Terminal overs One piece molded design for easy installation and removal. Molded from strong, yet fl exible Lexan polyester plastic, which will not break or chip. lear, see-through design allows for maximum visibility of both fuse and/or terminal connections. No extra parts like mounting brackets or screws ensure you always have the correct tools for installation or removal. Available in several styles to facilitate fusing or non-fusing options. Retrofi table with all ontrol Transformers up to 1000VA (look for the retrofi table notation on transformer box labels). ontrol Transformer c/w optional Terminal overs inger Safe Terminal overs SG2 Packaged inger Safe Terminal overs P/N (box of 20) (1) use lock over SG2 (2) Domed Terminal over SG3 (for fused secondary) (3) Terminal over SG4 (for unfused primary and/or secondary terminals) SG4 Optional Terminal overs SG3 Test Lead Access Hole Hole Terminal over SG4 Domed Terminal over SG3 Hole Terminal over SG4 Test Lead Access Hole Protrusion PT, PH, SL, PTD or PHD Transformer use lips Protrusion PT, PH, SL, PTD or PHD Transformer 84

57 STION 9 1 Q SRIS ONTROL TRANSORMRS SINGL PHAS NLOSD POTTD TRANSORMR ATURS or applications where a cost effective approach to general purpose loads indoor or outdoor is required, consider the Q series, single phase encapsulated control transformer. These units are specifi cally designed for the following applications; General purpose enclosed control applications used to adjust a supply voltage to match a load requirement Supplying machine tool circuits. Actuating relays, bells, signal and alarm systems. Operating small motors, valves and dampers. Industrial lighting and circuit isolation. Q Style nclosure 50 to 5000VA SINGL PHAS NAPSULATD ONTROL STANDARD SPIIATIONS 50 to 5000VA NITS UL Listed SA ertified requency ile: ile: LR Hertz Insulation System Up to 1kVA; lass, 80 temperature rise. Assures long life and reliable performance 1.5 to 5kVA; lass, 115 temperature rise. Standard Design Single Phase, all welded core construction Rugged one-piece assembly with low noise made with high quality, high permeability silicon provides optimum performance and reliability. steel laminations. omputer designed coils, accurately wound Provides enhanced voltage regulation and with optimum mean turns made from high excellent thermal characteristics and quality copper magnetic wire with insulation fi lm. compliments modern winding techniques. ncapsulation All units from 50VA to 5kVA are encapsulated with ompletely encloses the core and coil to seal electrical grade silica sand and resin compounds. out moisture, airborne contaminants and eliminates corrosion & insulation deterioration. nclosure Type Heavy Duty ncapsulated NMA Type 3R Meets the heavy industrial trade requirements (conduit knockouts on sides and rear) for indoor/outdoor enclosed transformers. Termination ront accessible wiring compartment with high Ample space for transformer connections. and low voltage copper lead wires or tabs. or primary and secondary terminations. Designed for vertical or horizontal mounting. acilitates any installation requirement. 85

58 Q SRIS ONTROL TRANSORMRS OPPR WOUND, SINGL PHAS, NMA 3R STYL NLOSUR 240/480 Volts 120/240 Volts 60 Hz atalog ase Approx. Dimensions Approx. Mtg Type Wiring VA Number Style (Inches) Weight Diagram (Page 263) Width Depth Height (Lbs.) W - Wall (Pages ) 50 Q6P NQ W SD QG6P NQ W SD QH6P NQ W SD QI6P NQ W SD QJ6P NQ W SD QK6P NQ W SD QL6P NQ W SD QM6P NQ W SD QN6P NQ W SD QP6P NQ W SD QQ6P NQ W SD QS6P NQ W SD QU6P NQ W SD Volts 120/240 Volts 60 Hz atalog ase Approx. Dimensions Approx. Mtg Type Wiring VA Number Style (Inches) Weight Diagram (Page 263) Width Depth Height (Lbs.) W - Wall (Pages ) 50 Q9P NQ W SD QG9P NQ W SD QH9P NQ W SD QI9P NQ W SD QJ9P NQ W SD QK9P NQ W SD QL9P NQ W SD QM9P NQ W SD QN9P NQ W SD QP9P NQ W SD QQ9P NQ W SD QS9P NQ W SD QU9P NQ W SD Volts 12/24 Volts 60 Hz atalog ase Approx. Dimensions Approx. Mtg Type Wiring VA Number Style (Inches) Weight Diagram (Page 263) Width Depth Height (Lbs.) W - Wall (Pages ) 50 Q05PR NQ W SD Q10PR NQ W SD Q15PR NQ W SD Q20PR NQ W SD Q25PR NQ W SD Q35PR NQ W SD Q50PR NQ W SD Q75PR NQ W SD Q10PR NQ W SD Q15PR NQ W SD Q002PR NQ W SD Q003PR NQ W SD Q005PR NQ W SD 5 86

59 STION 91 Metering Low Switchgear Operating Instruments Test equipment and labs eatures VOLTAG AND URRNT TRANSORMRS VM Series Indoor/Outdoor 600 Volt lass Transformers Applications Technical Specifications 60 Hz, 1 minute test, primary and secondary to ground; 4.0 kv 60 Hz, 1 minute test, secondary to ground; 2.5 kv low frequency test; 2500 RMS ontinuous thermal rating; 300 VA Metering accuracy; 0.3 W 0.6 X Temperature rise over 30 ambient; 55 ompact Lightweight Design Molded onstruction (epoxy encapsulated) High Thermal Rating asy visual-make onnection Terminals D...A. approval T-163 dimensions comply with MA and SA standards VM Series 60 Hz Ratio atalog Nominal Rating Number 1:1 VM6120 A 0.21/0.10 2:1 VM6240 A 0.42/ :1 VM6300 A 0.63/0.31 3:1 VM6360 A 0.83/0.42 4:1 VM6480 A 1.25/0.63 5:1 VM6600 A 1.67/0.83 Weights: Approximate shipping weight is 8.75 lb. 87

60 VOLTAG AND URRNT TRANSORMRS M6 Series (2-Wire) and M6-3 Series (3-Wire) 600 Volt lass Indoor urrent Transformers Applications Metering Protective Relay Operation Operating ontrol Devices Indoor service on either 2-wire or 3-wire circuits up to 600V Ideal for in-cabinet installations Accuracy M6, 2 wire M6-3, 3 wire 60 Hz metering 0.3O.9, O.5, 0.6O.9 60 Hz relaying 2.5L10, 10L15 2.5L15 ontinuous Rating actor AMP M6 AMP M6-3 Range 2 Wire Range 3 Wire * * Weights: Approximate shipping weight is 6.75 lb. M6 Series urrent atalog urrent atalog Rating Number Rating Number 5-5 M M M M M M M M M M M M M M M M61200 Weights: Approximate shipping weight is 6.75 lb. eatures ompact Lightweight Design Molded onstruction (epoxy encapsulated) High Thermal actor asy visual-make onnection Terminals D...A. approval T-160 dimensions comply with MA and SA standards Technical Specifications 60 Hz, 1 minute test, primary and secondary to ground; 4.0 kv 60 Hz, 1 minute test, secondary to ground; 2.5 kv Lightning impulse level (L.I.L.); 10 kv full wave hopped wave; 12 kv 1 second thermal rating; 80 times rated current Temperature rise over 30 ambient at continuous current rating ; 55 Mechanical rating; 90 times rated current for M6 series and 125 times rated current for M6-3 series 60 Hz M6-3 Series 60 Hz urrent atalog urrent atalog Rating Number Rating Number M M M M M63200 Weights: Approximate shipping weight is 6.75 lb. 88

61 STION 91 MV SRIS MDIUM VOLTAG INDUSTRIAL ONTROL TRANSORMRS MV Series Medium ontrol Transformers Applications or applications where a cost effective medium voltage control transformer is required, consider the MV series, single phase medium voltage industrial control transformer. These units are specifi cally designed for general purpose industrial control applications used to adjust a medium voltage supply to match a low voltage load requirement. Standard eatures Available from 2400 volts to 7200 volts 60 Hz. design 180 insulation, 115 temperature rise Superior quality silicon steel core Standard 24 leads (optional terminal block available) Available in six (6) standard voltage combinations Meets UL, SA and NMA standards MV Series Selection Table MV Medium ontrol Transformer PART NUMRS 500 VA 750 VA 1000 VA 2000 VA 3000 VA 5000 VA /240 MV500R MV750R MV1000R MV2000R MV3000R MV5000R /240 MV500Q MV750Q MV1000Q MV2000Q MV3000Q MV5000Q /240 MV500S MV750S MV1000S MV2000S MV3000S MV5000S /240 MV500T MV750T MV1000T MV2000T MV3000T MV5000T /240 MV500U MV750U MV1000U MV2000U MV3000U MV5000U /240 MV500V MV750V MV1000V MV2000V MV3000V MV5000V MV Series Dimensional Specification Table (2400V to 4800V ) 2 VA ig. MV Dimensions Weight Size No. A 1 D Slot X G (Lbs.) 500 VA X VA X VA X VA X VA X VA X Note 1 : Height dimension will increase by 4.13 inches with optional MVK1 fuse kit installed. All Dimensions In Inches Note 2 : Please contact sales for dimensional specifi cations on 6600V and 7200V primary units. MV Series Dimensional Drawings H1 H2 Standard 24 Leads A Standard 24 Leads H H2 A LV Terminal lock LV Terminal lock Slot (4) X G Slot (4) X G D D IGUR 1 All Dimensions in Inches IGUR 2 All Dimensions in Inches 89

HPS Imperator Series Control Transformers meet or exceed the standards established

HPS Imperator Series Control Transformers meet or exceed the standards established HPS IMPRATOR HPS Imperator Machine Tool Industrial ontrol Transformer The Perfect Solution The HPS Imperator line of machine tool industrial control transformers are specifically designed to meet the high

More information

INDUSTRIAL CONTROL AND GENERAL PURPOSE ENCLOSED TRANSFORMERS

INDUSTRIAL CONTROL AND GENERAL PURPOSE ENCLOSED TRANSFORMERS INDUSTRIAL ONTROL AND GENERAL PURPOSE ENLOSED TRANSFORMERS HPS Imperator, HPS Spartan, HPS Fusion and Q Series Transformers ontrol Transformer Quick Selection harts... 8 What Is A ontrol Transformer?...

More information

HPS Imperator Machine Tool Industrial Control Transformer

HPS Imperator Machine Tool Industrial Control Transformer HPS Imperator Machine Tool Industrial ontrol Transformer The Perfect Solution The HPS Imperator line of machine tool industrial control transformers are specifically designed to meet the high inrush industrial

More information

Control Transformers

Control Transformers ontrol Transformers HPS Imperator TM, QE, MV Series Industrial ontrol Transformers ontrol Transformer Quick Selection harts... 0 What Is A ontrol Transformer?... ontrol Transformer Selection Guide... HPS

More information

HPS Imperator Encapsulated Industrial Control Transformer

HPS Imperator Encapsulated Industrial Control Transformer HPS Imperator Innovative Design The Perfect Solution Features and enefits The HPS Imperator series is a unique innovative and compact design that provides the ideal solution for any industrial control

More information

PH250MQMJ CNTL 250VA 240X X240

PH250MQMJ CNTL 250VA 240X X240 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 PH250MQMJ CNTL 250VA 240X480-120X240 Hammond Power Solutions Catalog Number Manufacturer Description Weight per unit Product

More information

CPT Series Control Transformers

CPT Series Control Transformers CPT Series Control s 50 VA to 500 VA 480 VAC Primary 120 VAC Secondary (Inrush VA data should be obtained from the device manufacturers.) The inrush load power factor is difficult to determine without

More information

HPS Imperator. Innovative Solutions. Progressive. Encapsulated Machine Tool Industrial Control Transformers

HPS Imperator. Innovative Solutions. Progressive. Encapsulated Machine Tool Industrial Control Transformers Progressive Innovative Solutions HPS Imperator Encapsulated Machine Tool Industrial Control Transformers Lifetime Warranty Unique Terminal Block Innovative Fusing Method Patented Design HPS Imperator Control

More information

HPS Imperator. Innovative Solutions. Progressive. Encapsulated Machine Tool Industrial Control Transformers

HPS Imperator. Innovative Solutions. Progressive. Encapsulated Machine Tool Industrial Control Transformers Progressive Innovative Solutions HPS Imperator Encapsulated Machine Tool Industrial Control Transformers Lifetime Warranty Unique Terminal Block Innovative Fusing Method Patented Design HPS Imperator Control

More information

Machine Tool Industrial Control Transformers

Machine Tool Industrial Control Transformers Hammond Power Solutions Inc. Page of Machine Tool Industrial ontrol Transformers The HPS Imperator TM series of machine tool rated industrial control transformers are specifcally designed to meet high

More information

Machine Tool Industrial Control Transformers

Machine Tool Industrial Control Transformers Hammond Power Solutions Inc. Page of Machine Tool Industrial Control Transformers The HPS Imperator TM series of machine tool rated industrial control transformers are specifcally designed to meet high

More information

ICT TRANSFORMERS. Industrial Control Transformers provide a low and safe control voltage for the operation of many electromagnetic devices

ICT TRANSFORMERS. Industrial Control Transformers provide a low and safe control voltage for the operation of many electromagnetic devices ICT TRANSFORMERS Industrial Control Transformers provide a low and safe control voltage for the operation of many electromagnetic devices TA SERIES INDUSTRIAL CONTROL TRANSFORMER Industrial control transformers

More information

Industrial Control Power Transformers Class MT

Industrial Control Power Transformers Class MT Class MT Features Epoxy-encapsulated (50 5000); Completely seals the transformer coils against moisture, dust, dirt and industrial contaminants for maximum protection in hostile and industrial environments

More information

Industrial Control Transformers

Industrial Control Transformers 6 Industrial Control Transformers Section 6 Industrial Control Transformers provide a low and safe control voltage for the operation of electromagnetic devices, such as motor starters, contactors, solenoids

More information

Industrial Control Power Transformers

Industrial Control Power Transformers 09/10/15 Class MT Features b Enclosed coils (50-5000); Completely encloses the transformer coils against moisture, dust, dirt and industrial contaminants for maximum protection in hostile and industrial

More information

9070T150D1 Industrial Control Transformer, 150VA

9070T150D1 Industrial Control Transformer, 150VA Product Data Sheet 9070T150D1 Industrial ontrol Transformer, 150 Technical haracteristics Application Approvals atalog Reference Number Depth Height Width Winding Material Temperature Rise Type Primary

More information

Type FEC Epoxy Encapsulated, Copper-Wound Industrial Control Transformers

Type FEC Epoxy Encapsulated, Copper-Wound Industrial Control Transformers Type FEC Epoxy Encapsulated, Copper-Wound Transformers ISO 900:2008 REGISTERED 0 Transformer Selector Guide Type FEC Transformers...Page 02 Primary Fusing Option...Page 07 Primary Overcurrent Selection...Page

More information

TA Ta VA CTRL-XFRMR

TA Ta VA CTRL-XFRMR 3804 South Street 7964-7263, TX Nacogdoches Phone: 936-69-7941 Fax: 936-60-468 TA2437 Ta-2-437 10VA CTRL-XFRMR Acme Electric Catalog Number TA2437 Manufacturer Acme Electric Description Control Transformer,

More information

HPS Fusion General Purpose Enclosed Transformer

HPS Fusion General Purpose Enclosed Transformer HPS Fusion General Purpose Enclosed Transformer Our Company Hammond Power Solutions (HPS) was established in 1917 in Guelph, Ontario and has grown from a small family owned business in the short wave radio

More information

D I D /240 I. D x /240 I D / x x /24 I. D x /120

D I D /240 I. D x /240 I D / x x /24 I. D x /120 ndustrial ontrol Transformers lass 9070 www.square.com or the most up-to-date information The T units are designed for the global market and are the best choice when size and cost are of concern. This

More information

HPS Spartan Industrial Open Core & Coil Control Transformer

HPS Spartan Industrial Open Core & Coil Control Transformer HPS Spartan Industrial Open Core & Coil Control Transformer Our Company Hammond Power Solutions (HPS) was established in 1917 in Guelph, Ontario and has grown from a small family owned business in the

More information

Industrial Control Transformers

Industrial Control Transformers The SBE - Encapsulated, Copper Wound Series The SolaHD SBE Encapsulated industrial control transformers are epoxy encapsulated to seal the transformer windings against moisture, dirt and industrial contaminants.

More information

HPS Spartan. Industrial Open Core & Coil Control Transformer

HPS Spartan. Industrial Open Core & Coil Control Transformer HPS Spartan Industrial Open Core & Coil Control Transformer OUR COMPANY Hammond Power Solutions (HPS) was established in 1917 in Guelph, Ontario and has grown from a small family owned business in the

More information

SECTION 3 HPS CENTURION R REACTORS AND RC DV/DT FILTERS

SECTION 3 HPS CENTURION R REACTORS AND RC DV/DT FILTERS HPS CENTURION R REACTORS AND RC DV/DT FILTERS Single and Three Phase Why Choose a Line Reactor?... 98 Construction Features... 100 HPS Centurion R Reactors Specifications... 101 Part Number Guide... 102

More information

Unit Substation Transformers 5 and 15 KV Class

Unit Substation Transformers 5 and 15 KV Class Transformers 5 and 15 KV Class 85 General Information Description Federal Pacific unit substation transformers are available in a wide variety of types and ratings to provide reliable and versatile electrical

More information

Industrial Control Transformers

Industrial Control Transformers Industrial Control Transformers 5 The SBE - Encapsulated Series The SBE Encapsulated industrial control transformers are epoxy encapsulated to seal the transformer windings against moisture, dirt and industrial

More information

Bulletin 1497A Machine Tool Transformers

Bulletin 1497A Machine Tool Transformers Bulletin A Overview/Catalog Number Explanation Bulletin A Bulletin A are designed to reduce supply voltages to control circuits. The complete line of transformers is available with optional factory-installed

More information

Kuhlman Electric Corporation Volt Instrument Transformers

Kuhlman Electric Corporation Volt Instrument Transformers Kuhlman Electric Corporation 46000 Volt Instrument Transformers 46000 Volt Table of Contents Description Model Page Wound, Dry-Type VT (High Accuracy available) U/VRU-52(H) 3-4 Wound, Oil-Filled VT (High

More information

28.1. NEMA Contactors and Starters. Contents. Contactors Non-Reversing and Reversing. Freedom Series. Product Description

28.1. NEMA Contactors and Starters. Contents. Contactors Non-Reversing and Reversing. Freedom Series. Product Description .1 NM ontactors and Starters Non- and ontactors ontactors Non- and Product escription Non- ontactors are most commonly used to switch motor loads in applications where running overcurrent protection is

More information

June 2005 CN35 Electrically Held Vol. 2, Ref. No. [0494]

June 2005 CN35 Electrically Held Vol. 2, Ref. No. [0494] 7-2 Lighting ontactors Open ontrol June 2005 N5 lectrically Held Vol. 2, Ref. No. [09] ontents eatures Instructional Leaflets 7 escription Page lectrically Held Product escription....... 7-2 pplication

More information

HPS Fusion General Purpose Enclosed Transformer

HPS Fusion General Purpose Enclosed Transformer HPS Fusion General Purpose Enclosed Transformer Our Company Hammond Power Solutions (HPS) was established in 1917 in Guelph, Ontario and has grown from a small family owned business in the short wave radio

More information

Kuhlman Electric Corporation Volt Instrument Transformers

Kuhlman Electric Corporation Volt Instrument Transformers Kuhlman Electric Corporation 34500 Volt Instrument Transformers 34500 Volt Table of Contents Description Model Page Wound, Dry-Type VT Y (High Accuracy available) PTT-200-9710(H) 3-4 Wound, Oil-Filled

More information

Planning Low Voltage Layouts

Planning Low Voltage Layouts Outdoor_ransformers_Outdoor_ransformers.qxd 11-11-10 3:40 PM Page 1 1850 Wilson Avenue, oronto, Ontario, anada, M9M 1A1 Ph: 416-741-7336 Fax: 416-741-9104 SEION H OUDOOR H1 OUDOOR Low Voltage ransformers

More information

Contactors & Starters Index

Contactors & Starters Index ontactors & Starters Index NEMA ontrol Description Page Number General Information - HP... A Magnetic ontactors - HP...4 A Magnetic Reversing ontactors - HP... 4 A Magnetic Starters - HP... A Magnetic

More information

Bulletin 1497A Machine Tool Transformers

Bulletin 1497A Machine Tool Transformers Bulletin A Overview/Catalog Number Explanation Bulletin A Bulletin A are designed to reduce supply voltages to control circuits. The complete line of transformers is available with optional factory-installed

More information

Control Circuit Transformers

Control Circuit Transformers Technical Data Control Circuit Transformers Bulletin Numbers 1497, 1497A, 1497B, 1497D Topic Page Summary of Changes 1 Control Circuit Transformers Product Overview 2 Bulletin 1497 Global Control Circuit

More information

SERVICE MANUAL IMPINGER COUNTERTOP OVEN MODEL 1300 SERIES

SERVICE MANUAL IMPINGER COUNTERTOP OVEN MODEL 1300 SERIES SERVICE MANUAL IMPINGER COUNTERTOP OVEN MODEL 1300 SERIES Lincoln Foodservice Products, LLC 1111 North Hadley Road Fort Wayne, Indiana 46804 United States of America Phone : (800) 374-3004 U.S. Fax: (888)

More information

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV. DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them

More information

Simply reliable. ABB Single-phase Transformers. When transformation means safety and control.

Simply reliable. ABB Single-phase Transformers. When transformation means safety and control. Simply reliable. ABB Single-phase s. When transformation means safety and control. 2CSC446005B0201 Robust and reliable. The two ranges of ABB transformers - to meet every need. The operational control

More information

Electropneumatic Timing Relays Series 7000 Industrial

Electropneumatic Timing Relays Series 7000 Industrial DESIGN FEATURES Available in On-Delay, True Off-Delay, and On/Off-Delay. Timing from 0.1 seconds to 60 minutes, fully calibrated in linear increments. Oversize time-calibrated adjustment knobs, serrated

More information

General Purpose Buck - Boost Wiring Diagrams... 86

General Purpose Buck - Boost Wiring Diagrams... 86 SECTION LOW VOLTAGE/ LIGHTING TRANSFORMERS General Purpose... 84 Buck - Boost... 85 Wiring Diagrams... 8 LOW VOLTAGE LIGHTING TRANSFORMERS & POWER SUPPLIES Low Voltage Lighting A greater selection for

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents

More information

Technical information

Technical information Technical information General Regulations WTL current transformers are special transformers which transfer the primary circuits with prescribed accuracy in smaller secondary circuits. Primary and secondary

More information

Class T 300 & 600 Volt Fuse Blocks F B 300 & 600V CLASS T FUSE BLOCKS RATINGS: FEATURES/BENEFITS: RECOMMENDED FUSE USAGE: CLIP & CONNECTOR TYPES

Class T 300 & 600 Volt Fuse Blocks F B 300 & 600V CLASS T FUSE BLOCKS RATINGS: FEATURES/BENEFITS: RECOMMENDED FUSE USAGE: CLIP & CONNECTOR TYPES Class T 300 & 600 Volt use locks USE LOCKS 300 & 600V CLASS T USE LOCKS RATINGS: Volts: 300VAC/DC, 600VAC/DC Amps: 30A, 60A, 00A, 200A, 400A, 600A SCCR: 200kA Mersen Class T fuse blocks accommodate Class

More information

ENCAPSULATED TRANSFORMERS FOR HAZARDOUS LOCATIONS

ENCAPSULATED TRANSFORMERS FOR HAZARDOUS LOCATIONS Hammond Power Solutions Inc. Page 1 of 1 ENCAPSULATED TRANSFORMERS FOR HAZARDOUS LOCATIONS HPS Titan has been designed to operate in harsh environments/hazardous locations where dangerous gases, liquids,

More information

Engineered solutions for power and the environment

Engineered solutions for power and the environment C e n t u ry S e r i e s I n d u s t r i a l C o n t r o l T r a n s f o r m e r s Engineered solutions for power and the environment s we celebrate our 100th nniversary, the Dongan Team wishes to thank

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive

More information

Volt Instrument Transformers

Volt Instrument Transformers www. kuhlman. com Kuhlman Electric Corporation Instrument Transformers 1 Table of Contents Description Model Page Wound, Oil-Filled VT (High Accuracy available) UTE-145-OH 3-4 Wound, Oil-Filled CCVT (High

More information

AC Wattmeters and VArmeters

AC Wattmeters and VArmeters AC Wattmeters and VArmeters The Crompton Instruments Switchboard series of AC Wattmeters and VArmeters incorporate a DC moving coil, pivot and jewel indicator with a micro-circuit watt transducer PCB to

More information

Type IMC Indoor current transformer

Type IMC Indoor current transformer Instrument transformers Type IMC Indoor current transformer Product features 600 volt indoor 10 kv BIL 25 through 400 Hertz amperes: 50-1000 2.5" (64 mm) round window Designed for variable applications

More information

SERVICE MANUAL (INTERNATIONAL)

SERVICE MANUAL (INTERNATIONAL) SERVICE MANUAL (INTERNATIONAL) IMPINGER CONVEYOR OVENS MODEL 1421-000-E, 1454, 1455 WITH PUSH BUTTON CONTROLS Lincoln Foodservice Products, LLC 1111 North Hadley Road Fort Wayne, Indiana 46804 United States

More information

Distribution Dry Type Transformers 600 Volts Class Single and Three Phase Selection

Distribution Dry Type Transformers 600 Volts Class Single and Three Phase Selection 7 Distribution Dry Type Transformers 600 Volts Class Single and Three Phase 600 Volts Class Single Phase 0.25 167 KVA Three Phase 3 1000 KVA Features Standard units are UL listed and are designed in accordance

More information

Kuhlman Electric Corporation. Engineered Designs Instrument Transformers

Kuhlman Electric Corporation. Engineered Designs Instrument Transformers Kuhlman Electric Corporation Engineered Instrument Transformers Engineered Table of Contents Description Model Page Slipover CT/ACCUSlip TM Single, Dual & Multi Ratio (High Accuracy Available) PS-981/PH-982

More information

MERCURY CONTACTORS & RELAYS

MERCURY CONTACTORS & RELAYS MERCURY CONTACTORS & RELAYS PHONE: 704-399-4248 FAX: 704-399-4167 WWW.SETHERMAL.COM INDEX GLOSSARYOFTERMS&EXPRESSIONS...1 GENERALINFORMATIONFEATURES&SELECTIONFACTORS...13 MERCURY TO METAL CONTACTORS AND

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Control Transformers

Control Transformers J., APRJL, 1983 SUP RSEPES1/8111TION Control Transformers FILE: Control Products Catalog Machine Tool Transformer Disconnects CONTENTS Description Class Pages General............ 97... 23 Application Data.........

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

B BASIC HEAT TREATMENT CONSOLE

B BASIC HEAT TREATMENT CONSOLE Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL

More information

7000 series. Industrial Electropneumatic Timing Relay AGASTAT. Design Features. On-delay model 7012 (delay on pickup) Design & Construction

7000 series. Industrial Electropneumatic Timing Relay AGASTAT. Design Features. On-delay model 7012 (delay on pickup) Design & Construction 7000 series Industrial Electropneumatic Timing Relay File E15631 File LR29186 Note:7032 types and certain models with accessories are not agency approved. Users should thoroughly review the technical data

More information

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor ulletin Page 1 2015 Cross-kinked roof prevents standing moisture Metering Transformer compartment label is visible with doors closed Heavy duty 11-gauge steel enclosure is all-welded construction for long

More information

Bulletin A 1497B 1497D Type Control Circuit Transformer Machine Tool Transformer Control Power Transformer General Purpose Transformer

Bulletin A 1497B 1497D Type Control Circuit Transformer Machine Tool Transformer Control Power Transformer General Purpose Transformer Bulletin, A, B, D Transformers Product Overview Transformers Bulletin A B D Type Control Circuit Transformer Machine Tool Transformer Control Power Transformer General Purpose Transformer Features Single,

More information

QO and QOU Miniature Circuit Breakers QOU Miniature Circuit Breakers

QO and QOU Miniature Circuit Breakers QOU Miniature Circuit Breakers QO and Miniature ircuit reakers Miniature ircuit reakers lass 720 / Refer to atalog 0730T9801 Low mpere Miniature ircuit reakers unit mount miniature circuit breakers (cable-in/cable-out) are ideal for

More information

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor Page 1 2016 EPM-PCS-35-320P-R2/ESW-GCM6-2S-SA Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton's CPS LRTPs 35 kv Elliott Air-Insulated SuperWell Bushings 21.1/36.6 kv Grounded Wye Max Design, 150

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Non-Ventilated Automation Transformers 6

Non-Ventilated Automation Transformers 6 Non-Ventilated Automation Transformers 6 Automation Transformers - Non-Ventilated 50 VA to 45 SolaHD encapsulated transformers are rated for Hazardous Locations (Class 1, Division 2, Group A-D) as well

More information

FORM NO. HSC-543 AIR HANDLERS

FORM NO. HSC-543 AIR HANDLERS FORM NO. HSC- AIR HANDLERS AH10X1 High Efficiency featuring New Industry Standard R-10A Refrigerant Features AH10X1 features the new X-1 (ECM) motor which provides enhanced SEER performance with most Sure

More information

Constant wattage for high intensity discharge (HID) lamps

Constant wattage for high intensity discharge (HID) lamps onstant wattage for high intensity discharge (HID) lamps Index page Introduction 143 onstant wattage control equipment 144 onstant wattage application 145 onstant wattage mercury vapour and metal halide

More information

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls 11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the

More information

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor Page 1 2015 Heavy-duty 11-gauge steel enclosure is all-welded construction for long life Clear polycarbonate removable safety barrier separates upper and lower compartment (supplied only with internally

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products Hi-Tech SX Full-Range Current-Limiting Fuses Provides both overload and fault current protection for distribution equipment in a single fuse body. Trans-Guard SX Full-Range Current-Limiting Fuse As a full-range

More information

REFERENCE GUIDE INSTRUMENT TRANSFORMERS INDOOR / OUTDOOR CAST RESIN CONSTRUCTION

REFERENCE GUIDE INSTRUMENT TRANSFORMERS INDOOR / OUTDOOR CAST RESIN CONSTRUCTION REFERENCE GUIDE INSTRUMENT TRANSFORMERS INDOOR / OUTDOOR CAST RESIN CONSTRUCTION CONTENTS The instrument transformers listed in this guide are the most common for the electrical utilities and industries.

More information

Ventilated Distribution Transformers

Ventilated Distribution Transformers Ventilated Distribution Transformers The Energy Policy Act of 2005 (H.R. 6) requires Distribution Transformers manufactured after January 1, 2007 to meet specifi c energy effi ciency requirements. EPAct

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Industrial Control Transformers

Industrial Control Transformers Industrial Control Types MTE and MTK.1 Standards and Certifications................................. Catalog Selection.................................. Type MTE...............................................

More information

High barriers Recognized by UL and cul Self-extinguishing materials Nonferrous material Corrosion-resistant nickel finish Safety-grip handle A complete line of switches is available for meter, relay, instrument,

More information

AC Line / Load Reactors

AC Line / Load Reactors AC Line / Load Reactors Table of Contents Delivery / Lead Time.PB03-1100 -2 Selection & Pricing PB03-1100 -4 Replacement Parts..PB03-1100-8 Product Modifications / Options..PB03-1100 -9 Product Specifications..PB03-1100

More information

B CW POWER RELAY

B CW POWER RELAY 41-241.31B CW POWER RELAY nected in such a way that current, (I A ), leads voltage, (V BA ), by 150 degrees when the motor is operating at unity power factor. Loss of excitation to the motor causes a large

More information

AIR COOLED RECTIFIER SPECIFICATION S-50-A

AIR COOLED RECTIFIER SPECIFICATION S-50-A SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Introduction. What is Powercore? Powercore Welding Rod is an " Electro-fusion System" used for joining all types of thermoplastic parts together.

Introduction. What is Powercore? Powercore Welding Rod is an  Electro-fusion System used for joining all types of thermoplastic parts together. Introduction What is Powercore? Powercore Welding Rod is an " Electro-fusion System" used for joining all types of thermoplastic parts together. Powercore Welding Rod, is a flexible thermoplastic rod approximately

More information

Transformers 6. Gross Automation (877)

Transformers 6. Gross Automation (877) Transformers 6 Hevi-Duty Family of Transformers Sola/Hevi-Duty offers a broad range of transformers to meet many applications. These dry-type transformers are offered encapsulated, ventilated or non-ventilated,

More information

Cast resin transformers

Cast resin transformers Product catalogue Cast resin transformers according to IEC/EN 60076, VDE 0532, DIN 42523 Power range up to 8 MVA Voltage range up to 36 kv Conductor material: copper or aluminum Protection types: IP 00

More information

EDB-EPD, EGB-EPD and EJB-EPD (Equipment Protection Device) Circuit Breakers for Ground Fault Protection in NF Panelboards

EDB-EPD, EGB-EPD and EJB-EPD (Equipment Protection Device) Circuit Breakers for Ground Fault Protection in NF Panelboards -P, -P and J-P (quipment Protection evice) ircuit reakers for round ault Protection in N Panelboards Square -P, -P and J-P (quipment Protection evice) ircuit reakers are 1-pole thermal-magnetic circuit

More information

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents. PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the

More information

To discover the factors affecting the direction of rotation and speed of three-phase motors.

To discover the factors affecting the direction of rotation and speed of three-phase motors. EXPERIMENT 12 Direction of Rotation of Three-Phase Motor PURPOSE: To discover the factors affecting the direction of rotation and speed of three-phase motors. BRIEFING: The stators of three-phase motors

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

NX indoor current-limiting fuses

NX indoor current-limiting fuses Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground

More information

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q 14/03/08 A136 Relay - General Purpose 90-293Q Enclosed fan relays used for switching single or two speed fan motors, solenoids, relays, resistive loads, heating and cooling applications and general purpose

More information

Advance 27 ANSI 27 kv switchgear

Advance 27 ANSI 27 kv switchgear Advance 27 ANSI 27 kv switchgear Table of contents Advance 27...3 AMVAC breaker...4 Instrument transformers...5 Current transformers...5 27 kv voltage transformers...6 Distribution protection and control...7

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Three Phase Transformers

Three Phase Transformers Three Phase Transformers ontents Three Phase - General Purpose... 26 Three Phase - General Purpose Scott ed... 30 Three Phase - dditional ombinations vailable... 31 Three Phase - ion Diagrams... 32 Series

More information

Rheem Air Handlers. RHLP- Standard Efficiency X-13 (ECM) Motor

Rheem Air Handlers. RHLP- Standard Efficiency X-13 (ECM) Motor Air Handlers Rheem Air Handlers RHLP- Standard Efficiency X-13 (ECM) Motor RHLP features an X-13 (ECM) motor which provides enhanced SEER performance with most Rheem outdoor units. 1 1 /2 ton [.3 kw] through

More information

Rheem High Efficiency Air Handler

Rheem High Efficiency Air Handler Air Handlers Rheem High Efficiency Air Handler Constant Torque Motor (ECM) Efficiencies up to 14 SEER The RH1T feature a Constant Torque motor (ECM) and a piston refrigerant control for efficient and reliable

More information