1 Medium Voltage Distribution CBX CBX Vacuum Contactors CBX3-C CBX3 CBXS3-C Technical Manual Installation, Operation & General Maintenance

2 Any operator must read and respect in all case this technical manual. Installation, comissionning and maintenance should only be conducted by qualified people. Before installation, check that data in rating label match with the application. Accidental contact with energized components or wiring can cause shock, burn or electrocution: turn off power supplying this equipment and control voltage sources before any work on contactor. NTV112-5E (CPX) 2

3 1. SAFETY INSTRUCTIONS COMPLIANCE WITH INSTRUCTIONS IN THIS MANUAL INSTALLATION OPERATION & MAINTENANCE APPARATUS/TASK/SKILL LEVEL SCHEDULE FOR WORKING ON THE APPARATUS OPERATION & GENERAL INFORMATION GENERAL INFORMATION DESCRIPTION & OPERATION INSTALLATION & PRE-COMMISSIONING TESTS UNPACKING CRITICAL ITEMS DURING UNPACKING AND INSTALLATION INSTALLATION PRE-COMMISSIONING TESTS ROUTINE SITE VOLTAGE TEST MAINTENANCE MAINTENANCE MECHANICAL & ELECTRICAL LIFE VACUUM SWITCH CONTACT WEAR CHECK WIRING DIAGRAMS (EXCEPT CBXS3-C : SINGLE PHASE) AUXILIARY SWITCHES GENERAL INFORMATION AUXILIARY CONTACT BLOCKS CONTACT OPERATION CONTACT OPERATION AUXILIARY SWITCH MAINTENANCE FAULT FINDING CONTACTOR WILL NOT CLOSE AT ALL WHEN COILS ARE ENERGISED CONTACTOR CLOSES AND IMMEDIATELY REOPENS CONTACTOR CLOSES BUT MOTOR WILL NOT RUN CONTACTOR CLOSES - BUT STOPS AT TIPS TOUCH I.E. NO OVERTRAVEL CBXS3-C CONTACTORS (SINGLE PHASE) LATCH-IN DEVICE MAINTENANCE OF LATCH-IN MECHANISM LATCH-IN DEVICE AND SETTING IN THE EVENT OF A MALFUNCTION OF THE LATCH SPARE PARTS LIST ANNEX...26 NTV112-5E (CPX) 3

4 1. Safety Instructions 1.1 Compliance with Instructions in this Manual The Purchaser/User should comply with the instructions and information given in this document and ensure that all personnel to be associated with the apparatus supplied under this contract are made familiar with the information contained herein. 1.2 Installation The Purchaser/User should ensure that the apparatus supplied is correctly installed in a suitable location by technically qualified and competent persons. Apparatus supplied as loose components, devices or sub-assemblies could, when energised, constitute a safety hazard. The Purchaser/User should ensure that such apparatus is installed in a secure location and that adequate safety information is provided to all personnel to be associated with it. 1.3 Operation & Maintenance Guidance Notes for Users on the Safety of Personnel The rules for ensuring the safety of personnel can be summarised as follows: During Normal Use ensure that the plant operators: are fully conversant with all controls, particularly those for emergency shutdown. comply with safety warning notices and keep all enclosures shut are trained to recognise signs of maloperation and know what action to take in the event of trouble or difficulty. During Maintenance, Testing etc. ensure that only technically competent and authorised persons are permitted to carry out work and that they: comply with statutory requirements. are fully conversant with the apparatus and the system of which it is part, and recognise the safety hazards which could arise, e.g. back feed. isolate the apparatus completely, where possible, before opening enclosures and prove it to be dead before starting work. Precautions must be taken to ensure that the isolated apparatus cannot become live whilst any work is being carried out. comply with safe working procedures for the safety of themselves and others, including the use of temporary barriers and warning notices. are conversant with the information provided, particularly on matters relating to safety. recognise the hazards which can arise when working on live apparatus and take all the necessary precautions. functionally check the apparatus and then mechanically and/or electrically test it in accordance with this manual and good working practice before putting the apparatus back in service. take account of the possibility that the apparatus may have been modified without proper reference to the manufacturer and take extreme caution at all times before, during and after and work is carried out. If there is any doubt as to the correct and safe method of working then further assistance should be sought from Schneider Electric NTV112-5E (CPX) 4

5 1.3.2 Skills Required for Specific Tasks To ensure that the apparatus is safe for use under normal healthy plant operating conditions: it has been designed and tested in accordance with relevant European and International standards. information is provided in this manual about the conditions necessary for safety and about any hazards which are reasonably foreseeable during normal use, together with precautions to be taken to counteract them. However, the Purchaser/User should ensure that the apparatus is maintained in a safe condition, and if technically competent and authorised personnel have to gain access to apparatus which is not made completely safe as recommended, everyone under whose authority these persons act should ensure that appropriate safety procedures are generated and complied with. The apparatus covered in this manual has been allocated the Apparatus Grade stated above. Reference to the Apparatus/Task/Skill level schedule [1.4] enables the user to select personnel to carry out specific tasks requiring access to the apparatus. 1.4 Apparatus/Task/Skill Level Schedule for Working on the Apparatus The apparatus can be supplied as loose items, sub-assemblies etc., for which the purchaser/user is responsible for assembly etc. [1.2]. The skill level required to work on this equipment can be best described as the following : Authorised and competent staff (e.g. Electrician, Commissioning Engineer) with a HIGH degree of electrical expertise, trained to work on live apparatus and fully conversant with the apparatus and the system of which it is part. If additional information relating to the apparatus is required please contact : Schneider Electric NTV112-5E (CPX) 5

6 2. Operation & General Information 2.1 General Information This vacuum contactor was manufactured by; Schneider Electric A contactor is primarily a three phase switching device, although single phase units are also available, used primarily in motor starting/reversing and capacitor bank switching applications. Each phase has a separate Vacuum Switch which switches at the first available current zero Contactor Front View Armature Moulding Economy resistor Pivot Point Closing coils Auxiliary switches Stop pin Opening Springs Fixing holes Steel Mounting Plate Contactor Rear view NTV112-5E (CPX) 6

7 Phase assembly & nyloc nuc Main Terminals Main Moulding Moulded Terminal Bar Main Terminals Vacuum Switches NTV112-5E (CPX) 7

8 2.2 Description & Operation As shown in [2.1.1 & 2.1.2], the Contactor comprises Main and Armature mouldings with two Pivot Points, a Steel Mounting Plate, three Vacuum Switches( one in a single phase unit), two Opening Springs, two Closing Coils, an Economy Resistor and one or two Auxiliary Contact Blocks Closing Coils Un-energised In this condition the opening springs acting against the centre limb of the armature moulding hold the vacuum switches in the normally open position (main circuit off) Closing Coils Energised Energising the closing coils attracts the armature which compresses the opening springs. The armature movement is transmitted through the pivot points, allowing the vacuum switches to close under the effect of atmospheric pressure which acts on the bellows inside the vacuum switches (main circuit on). The vacuum switches will remain closed as long as the closing coils are energised. The armature moulding moves further than necessary for switch closure providing overtravel which accommodates contact wear and, on opening, provides kinetic energy to break minor contact welds which may occur under severe operating duty. The energy required to close the contactor is considerably more than the energy required to maintain a closed position. On initially energising the closing coils a high current flows through the coils. After a short delay an economy resistor is automatically brought into the circuit by the contactor s own normally closed, extra-late opening auxiliary contact. This reduces the current in the closing coils which allows their continuous operation without over heating. The closing coil rating enables satisfactory operation of the contactor in cubicles with internal temperatures of up to 65 C. For use in temperatures higher than this, contact Schneider Electric. Contactors may be supplied fitted with closing coils and economy resistors suitable for d.c. or full wave rectified single phase a.c. supply voltages as required Closing Coils De-energised When the closing coils are de-energised the opening springs will act on the armature moulding causing the vacuum switches to open. The vacuum switches provide a sealed gas-free environment making the switching operation unaffected by external conditions. Once the vacuum switch contacts have separated arcing occurs until the first available current zero, at which time the current is commutated Auxiliary Contacts One or two type auxiliary contact blocks can be provided giving a maximum of 10 (ten) contacts available for customer use (5NO+5NC) in magnetically held type and a maximum of 12 (twelve) contacts (6NO+6NC) in mechanically latched type. NTV112-5E (CPX) 8

9 2.2.5 Main Terminals The main terminals consist of M10 bolts for attachment of cables or busbars. For advice on cable/busbar connection see [3.3]. The maximum torque applicable for these terminals is 40 Nm and must not be exceeded. Nut M10 Spring washer M10 Plain washer M10 M10 x 30 LG TOP TERMINAL M10 x30 LG Plain washer M10 Spring washer M10 Nut M10 LOWER TERMINAL The maximum width of the lead terminal connexions, bars or crimps is 35 mm. NTV112-5E (CPX) 9

10 3. Installation & Pre-commissioning Tests 3.1 Unpacking Contactors may be supplied as separate units, or mounted with other equipment. When supplied as separate units, care must be taken during unpacking. After removing the packing material, examine the contactor and packing material for broken or missing parts. The carriers and suppliers should be notified of the breakages within three days of delivery. These together with any other evidence should accompany communications with the insurance company and the suppliers. The particulars on the rating plate of the equipment must be quoted in all correspondence. 3.2 Critical Items During Unpacking and Installation Do not attempt to lift the contactor by means of the auxiliary contact blocks, or latch mechanisms shown in positions below marked X. Handling Areas Using moulding only Handling Areas Using moulding only Handling Areas Using moulding only Take care when fitting cables or busbars to the main terminals that the terminations do not damage, deform or restrict movement of the contactor. Particular care should be taken when two or more cable terminations are fitted onto a single terminal Everything surrounding the contactor (i.e. frames, enclosures, components, power and control cables) must be clear of the paths of the moving parts of the contactor. Nothing should be allowed to rest on top of the armature moulding or interfere with the normal operation of the moving parts of the contactor Ensure that nothing interferes with adequate air flow over the contactor, particularly around the coils and economy resistor It is not recommend that additional components are added to the contactor e.g. rectifiers, indicators, etc.. However, if components are added, checks must be made to ensure that they do not have any adverse effect on the operation of the contactor. NTV112-5E (CPX) 10

11 3.3 Installation It is recommended that the contactor be mounted with the axes of the vacuum switches vertical and with their moving contacts at the top. Two M10 x 1.5 fixing holes are provided on each side of the contactor in the turned up outer edges of the steel mounting plate, which must be used for the mechanical mounting of the contactor. The maximum torque applicable for these terminals is 40 Nm and must not be exceeded. When installing and cabling, ensure that an air gap of at least 64mm for 7,2kV and 77mm for 12kV systems, is maintained between live main circuit contactor parts and earth control circuits. It may, of course, be necessary to increase these dimensions if the contactor and associated equipment have to meet a particular impulse withstand voltage. General Arrangement of Contactor Mounting holes Theses dimensions are relatives to the optional mechanical latch. NTV112-5E (CPX) 11

12 3.4 Pre-commissioning tests It is good practice to subject vacuum switches or contactors to pre-commissioning tests Check for the presence of loose screws, swarf or other material in the gaps between closing coil pole pieces and the armature plate Check contactor operation at 75% of the control voltage after installation, including cables or busbars, but before applying full control voltage and power Perform routine site voltage test. [3.5] Perform auxiliary maintenance checks [5.4] It is also advisable to test vacuum switches and contactors under the following circumstances: If the contactor or switch has been standing for 5 years or more without use - either in storage or in service. In special applications where the switch is in use for long periods without breaking current and without normal voltage across the contacts when switched off. After a main circuit fuse has operated. 3.5 Routine Site Voltage Test The following test should be carried out by using an a.c. test set of limited rating e.g. 2 to 4kVA, on which the voltage is continuously variable from zero up to the maximum required for that particular switch. Return the contactor to the supplier if the test is not successful. Note :Applying very high voltages to open vacuum switches may generate harmful levels of X radiation. However emission of X radiation is negligible at the specified test voltages Connect output leads of the test set across the open gap of each vacuum switch in turn Slowly raise the voltage from zero to the specified test value taking approximately one minute to reach full voltage. During this stage any discharge or test set tripping should be ignored unless it proves impossible to reach the full specified voltage within two minutes Hold the voltage at the specified test value for one minute. Note: On reversing applications and on applications with VS3-C vacuum switches no discharge or test set tripping can be tolerated whilst the voltage is being slowly raised to, and held for one minute at the specified test voltage. NTV112-5E (CPX) 12

13 Contactor Type Vacuum Switch Type Nominal A.C. Test Voltage D.C. Test Voltage System Voltage 45/65 Hz (Test in both polarities) kv kv kv CBX3-C/CBXS3-C VS3-C CBX3 VS3 7, Note : The codings given to contactors in the above table have additional suffix letters and numbers in their references. When carrying out a.c. high voltage tests, current monitoring facilities are not usually available and in any event the leakage currents can be misleading due to the presence of currents associated with the vacuum switch capacitance. When carrying out d.c. high voltage tests, current monitoring facilities usually are available. If any doubt exists about the vacuum switch dielectric to pass the routine site test procedure given above, an additional criterion can be applied where the leakage current should not exceed 150 microamps at the relevant test voltage given in above table. However, before rejecting any vacuum switch which is apparently outside the limit, it should be ensured that the leakage current is due to faulty switch dielectric and not due to dirt etc. on the outside of the vacuum switch envelope. NTV112-5E (CPX) 13

14 4. Maintenance 4.1 Maintenance These contactors are extremely reliable and only slight maintenance is normally required. The following table outlines recommended maintenance intervals. Installation Precommissi on Every 100,000 Operatio ns * Every 250,000 Operatio ns * After Main Fuse Operatio n Infreque nt Switchin g (< 1 year) Every 5 Years [3.4.1] Contactor Operation [5.3 & 5.4] Auxiliary Contacts [4.2] Vacuum Switch Wear =< 400A ψ [3.5] Vacuum Switch Voltage Test ψ Assuming a normal starting peak of six times full load current when controlling a squirrel cage induction motor. * These totals are only for ELECTRICAL operations as the Vacuum switch assemblies will mechanically operate for the life of the contactor. 4.2 Mechanical & Electrical Life The contactor has a design life of 3,000,000 mechanical operations. Electrical life depends upon the type of vacuum switch fitted and the level of current to be switched. Provided that the vacuum switch contact wear does not exceed the maximum permissible [4.2.1] then contactor will continue to function correctly. NTV112-5E (CPX) 14

15 4.3 Vacuum Switch Contact Wear Check After isolating the main circuit of the contactor, close the armature by energising the coils and insert the wear gauge DRC provided underneath the washer on top of each phase (as indicated above). With the gauge in position, slide it from back to front to gain a feel for the movement. If the gauge is trapped or tight fitting i.e. phase assembly, washer, and Nyloc nut also move, this indicates that the switch contacts are worn and the switch is close to or at the end of its electrical life. If one or more switches indicate worn contacts, all three vacuum switches must be replaced. Important : Remember to remove the gauge after checking for wear! Note : A switch assembly is worn out when each contact has been reduced in thickness by 0.25mm i.e. a total of 0.5mm per pair of contacts in a switch. 4.4 Wiring Diagrams (except CBXS3-C : single phase) Magnetically held See Electric diagram contactor DRC (DC) and DRC (AC) in annex. With mechanical latch See Electric diagram contactor DRC (DC) and DRC (AC) in annex. NTV112-5E (CPX) 15

16 5. Auxiliary Switches 5.1 General Information Auxiliary switches are provided as units of 4 (or 6) double - break, silver faced contacts with a moulded bar carrying the moving contacts and a fixed moulding carrying the fixed contacts. The last two contacts are used as Late Breaks for the contactor s economising circuit. These contacts will discolour in time and is not normally detrimental. However their operation is critical to the correct functioning of the contactor and periodic inspection is vital [4.1]. Contact arrangement can be readily changed, i.e. - normally open to normally closed or vica - versa. 5.2 Auxiliary Contact Blocks Magnetically held NTV112-5E (CPX) 16

17 With mechanical latch NTV112-5E (CPX) 17

18 5.3 Contact Operation The normal movement of the moving contact carrier is 6mm ± 0.5mm contact stroke plus 3mm ± 0.5mm overtravel. The extra late opening economising contact [5.2.5] should have a gap of 1.5 to 1.8mm with the contactor fully closed. A supplement explaining contact adjustment and replacement is available from your supplier upon request although in normal use this should not be necessary. 5.4 Auxiliary Switch Maintenance The silver faced contacts require little attention but should be kept free of dust and dirt; the black tarnish which may appear need not be removed as it does not impair conductivity Examine moving parts for side play, badly worn pivots etc., which indicate that the auxiliary switch should be replaced Check that the pivot securing nuts are tight Operate the contactor to check that the contacts have satisfactory wipe and break and that movement is free Contacts which are badly worn or burnt through the silver facing to the copper must be replaced If it is found necessary to replace a moving spring, the coils of the spring must be turned on edge to extract it through the slot in the side of the moving contact carrier. Where reliability of operation is particularly critical - e.g. continuous processes, mine winding installations, etc., inspection of the auxiliary switches is recommended at intervals of approximately 100,000 operations. NTV112-5E (CPX) 18

19 6. Fault Finding In cases of apparent contactor malfunction carry out the following checks after the isolation of the main circuit. Note A: As the contactor relies on atmospheric pressure acting on the switch bellows, loss of vacuum in one or more switches on the 7,2kV and 12kV contactors will possibly prevent closure depending on actual supply voltage and whether the coils are cold or hot. Note B: In cases of burnt out coils, this may be due to a failure to economise [5.3 & 5.4]. Note C: Do not adjust nyloc nuts on top of the phase assemblies, pivot point screws and nuts, stop pin locking nut or opening springs. It is unlikely that any of these will have altered to the extent of causing malfunction of a contactor which was previously satisfactory. 6.1 Contactor will not close at all when coils are energised Check power supply to closing coils Check auxiliary switch drive and pivots are not broken, badly worn or screws loose. Check extra late opening economising contact is operating satisfactorily [5.3 & 5.4]. Check that all switches have vacuum using the site voltage test [3.5]. Manually assist closure with coils energised. If not possible to close with moderate force, check that sufficient voltage (see rating label) appears across the coil terminals. Check that rectifier (if applicable) has not became half-wave, or coils faulty. 6.2 Contactor closes and immediately reopens Check extra late opening economising contact is operating satisfactorily [5.3 & 5.4]. Check for the presence of loose screws, swarf or other material in the gaps between closing coil pole pieces and the armature plate. Check that economy resistor is not open circuit. 6.3 Contactor closes but motor will not run Check fuses, if fitted, and any other protection equipment Check with vacuum switch contact wear gauge if contactor is nearing the end of its life.[4.2.1] Check that all switches have vacuum using the site voltage test [3.5]. 6.4 Contactor closes - but stops at tips touch i.e. No overtravel Check extra late opening economising contact is operating satisfactorily [5.3 & 5.4]. Check the voltage across the closing coils. Check for the presence of loose screws, swarf or other material in the gaps between closing coil pole pieces and the armature plate. NTV112-5E (CPX) 19

20 7. CBXS3-C Contactors (Single Phase) The information given elsewhere in this manual is, in general, also applicable to the single phase contactors except where reference is made to more than one phase or vacuum switch and to the use of closing coils and economising contacts. In particular the following information applies to the specific contactors listed below : Wiring Diagram for CBXS3-C Magnetically held See Electric diagrams contactor DRC (DC) and DRC (AC) in annex. Mechanically latch See Electric diagrams contactor DRC (DC) and DRC (AC) in annex. No economising resistor is fitted. Extra late opening economising contacts are not fitted (irrespective of the closing coil supply voltage). No provision is made for adjustment of the main opening springs. NTV112-5E (CPX) 20

21 8. Latch-in Device 8.1 Maintenance of Latch-in Mechanism No maintenance is required for the latch-in mechanism, beyond an occasional light application of molybdenum disulphide loaded grease to the sliding parts. 8.2 Latch-in Device and Setting Latch in Close position M4 GRUB SCREW ROLLER PROP CLEVIS NTV112-5E (CPX) 21

22 8.2.2 Latch in open position NTV112-5E (CPX) 22

23 8.3 In the event of a malfunction of the latch The following points should be examined: Check freedom of moving parts. (It is possible that the alignment of the whole latch assembly may have been disturbed during transit) Check with a clock gauge, the set-back of the clevis holding the roller behind which the prop is located. (ie. its free movement in relation to the latch body in the horizontal direction, from the contactor coil energised condition to the latched-in, coil de-energised state). This set-back should be between 0.2mm and 0.4mm. The set-back can be adjusted by slackening the screws fixing the whole latch assembly to the contactor coil support angle, and adding (to decrease the set-back) or removing (to increase set-back) slotted shim washers between the collars and the angle. Retighten screws and recheck set-back. Coarse adjustment necessitates removal of the latch assembly and screwing the clevis further on to or off its drive rod in one full turn steps. (The E-clip on the roller pivot pin must be located against the lower slotted guide plate) Check prop engagement behind roller. Assuming the set-back is correct (see above), but the latch is reluctant to trip, it is possible that the prop is too far into engagement behind the roller. Conversely, insufficient engagement can result in failure to latch. The engagement can be reset as follows: Slacken the locknut on the M4 grubscrew in the prop and adjust this grubscrew until the contactor ust fails to latch. Unscrew the grubscrew 11/2 full turns from this position so that the prop is further into engagement behind the roller. Lock with locknut and recheck above Check solenoid tripping action and adjust as follows if necessary. Three solenoids are available, for nominal voltages of 24 Vdc, 48 Vdc and 110/240 volts ac or dc. having cold resistances of 3, 14 or 54 ohms respectively. (Coils are marked 24Vdc 5%, 25% or 100% respectively). With the contactor latched, there should be a clearance of 0.5mm to 1mm between the outer end of the prop and the 10mm diameter collar fixed to the trip rod passing through the prop. This dimension can be adjusted by addition or removal of M3 washers behind this collar. With the 10mm diameter collar loose on the trip rod, allow the solenoid plunger to retract as far as possible without forcing. Push in the plunger 1mm from this position and tightly secure the collar to the trip rod by means of the two grub screws and lock with the locknuts. The collar now acts as a stop for the lever/plunger assembly. The dimension between the outer end of the plunger and the solenoid mounting plate should be at least 24mm. Check that the solenoid plunger is not sticking at any stage in its movement. NTV112-5E (CPX) 23

24 Notes: To ensure correct operation, closing coils and tripping coil must be energised for a minimum of 300 milliseconds. Closing coils and Tripping coil must not be energised for more than 2 seconds. The supply to the tripping coil providing it is less than 220V d.c. can, if required, be wired through a normally open contact on the auxiliary contact block. The closing supply however, should not be wired directly through a normally closed contact on the auxiliary contact block, as this could cause the closing supply to be disconnected before the contactor is fully closed. The use of an auxiliary switch on the vacuum contactor or on the latch (if fitted) to interrupt the contactor coil supply during the closing action is not recommended unless an intermediate relay with a delay of at least 0.3 seconds is employed. NTV112-5E (CPX) 24

25 9. Spare parts list CBX3 CBX3-C CBXS3-C Recomanded quantity by contactor Closing coils 24 V DRC DRC Vdc 48 V DRC DRC V DRC DRC /125 V DRC DRC /250 V DRC DRC V DRC DRC V DRC DRC Vac 220/240 V DRC DRC Resistance 24 V DRC for CBX3/CBX3-C 48 V DRC for CBX3/CBX3-C Vdc 60 V DRC for CBX3/CBX3-C 110 V DRC for CBX3/CBX3-C 125 V DRC for CBX3/CBX3-C 220 DRC for CBX3/CBX3-C 250V DRC for CBX3/CBX3-C 110/120 V DRC for CBX3/CBX3-C 220/230 V DRC for CBX3/CBX3-C Vac 250 V DRC for CBX3/CBX3-C Equipped auxiliary switch 1NO + 1NC DRC set 2NO + 2NC DRC set 3NO + 3NC L* DRC DRC R* - 1 set 4NO + 4NC L* DRC DRC R* - 1 set 4NO + 4NC L* DRC DRC R* - 1 set 5NO + 5NC L* DRC DRC R* - 1 set 2NO + 2NC DRC set 3NO + 3NC DRC set 4NO + 4NC L* DRC DRC R* 1 set 5NO + 5NC L* DRC DRC R* 1 set 5NO + 5NC L* DRC DRC R* 1 set 6NO + 6NC L* DRC DRC R* 1 set Graetz Bridge ST Varistor ST Tripping coils (latch) Vdc DRC Vdc DRC Vdc DRC Vac DRC * L and R are for Left hand side and Right hand side when viewing coils Replacement of parts should be performed only by qualified personnel. Always de-energize a contactor and remove it from the equipment before performing any tests, maintenance or repair. Please contact Schneider Electric for training course.use of unauthorized parts in the repair of the equipment, altering of the design, or tampering by unqualified personnel will result in dangerous conditions : can cause death, serious personal injury or equipment damage. NTV112-5E (CPX) 25

26 10. Annex Electrical diagram contactor CBX DRC (DC): magnetically held Electrical diagram contactor CBX DRC (DC): with mechanical latch Electrical diagram contactor CBX DRC (AC): magnetically held Electrical diagram contactor CBX DRC (AC): with mechanical latch Electrical diagram contactor CBXS DRC (DC): magnetically held Electrical diagram contactor CBXS DRC (DC): with mechanical latch Electrical diagram contactor CBXS DRC (AC): magnetically held Electrical diagram contactor CBXS DRC (AC): with mechanical latch NTV112-5E (CPX) 26

27 Notes NTV112-5E (CPX) 27

28 2011 Schneider Electric - All rights reserved Schneider Electric 35, rue Joseph Monier CS F Rueil Malmaison Cedex RCS Nanterre Capital social NTV112-4E As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Publishing: Schneider Electric Design: Schneider Electric Printing: 02/2011

Fuse contactor drawer CVX for PIX Switchgear (12kV)

Fuse contactor drawer CVX for PIX Switchgear (12kV) Medium Voltage Distribution Fuse contactor drawer CVX for PIX Switchgear (12kV) Operating Instruction NTV133 Edition 09/09 Important Note The Operating Instructions, which are exclusively valid, are always

More information

Fuse contactor drawer CVX for PIX-M Switchgear (7.2kV)

Fuse contactor drawer CVX for PIX-M Switchgear (7.2kV) PRIMARY DISTRIBUTION SWITCHGEAR >> Fuse contactor drawer CVX for PIX-M Switchgear (7.2kV) Operating Instructions NTV132 Edition 09/09 Operating Instructions T&D 1 IMPORTANT NOTE The Operating Instructions,

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions.

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions. Medium Voltage Distribution FBX Assembling a 1250A busbar Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists, and suitably adapted services...... 3 Overview...

More information

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution Medium Voltage Distribution PIX Withdrawable Voltage Transformer Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual Nr. Edition 11/2011 www.schneider-electric.com Schneider

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

EISHO TEK. Vacuum Circuit Breaker

EISHO TEK. Vacuum Circuit Breaker EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Introduction A contactor is an electrical device which is used for switching an electrical circuit on or off. It is considered to be a special type of relay. However, the basic difference between the relay

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition

More information

THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES. By M.J. Smart and B. Wadcock

THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES. By M.J. Smart and B. Wadcock 203 THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES By M.J. Smart and B. Wadcock 1.0 INTRODUCTION Capacitors are widely used for industrial power factor correction throughout the

More information

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B. Cutler-Hammer Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS BOOKLET IN ITS

More information

Galaxy Receiving and Unpacking 09/

Galaxy Receiving and Unpacking 09/ Galaxy 5500 20 120 kva 400 V Receiving and Unpacking 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy NorthStar TM brand Instruction Manual SLIM Tach SL56 1.125 Thru-Shaft Diameter Magnetoresistive Encoder Designed for GE Wind Energy Patent Pending *791-1061-00* Rev. B Page 2 Table of Contents Chapter/Paragraph/Illustration

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Vibrating Feeders Models: F-T01-A and DF-T01-A Contents Page

More information

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36 ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36 We thank you for having purchased VCB s from us. We are sure you will be very happy with the performance and service of

More information

1 THE WOLVERTON SYSTEM OF TRAIN LIGHTING.

1 THE WOLVERTON SYSTEM OF TRAIN LIGHTING. 1 THE WOLVERTON SYSTEM OF TRAIN LIGHTING. The Wolverton equipment is a single battery system utilising a plain shunt wound dynamo. The dynamo is controlled by an automatic field regulator which senses

More information

MCset kv Medium voltage equipment

MCset kv Medium voltage equipment Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide

More information

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos:

PHASE CONVERTERS OPERATING & MAINTENANCE INSTRUCTIONS. MODEL NO: PC40 and PC60. PART Nos: PHASE CONVERTERS MODEL NO: PC40 and PC60 MODEL PART No: NO: 6012805 PC20 and PC40 6012810 PC60 PART Nos: 6012800 6012805 6012810 OPERATING & MAINTENANCE INSTRUCTIONS 0107 Specifications PC20 PC40 PC60

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

HYDRAULIC QUICK HITCH

HYDRAULIC QUICK HITCH HYDRAULIC QUICK HITCH Installation & Operation Manual Important: This manual must be kept with the excavator at all times and referred to as required Harford Attachments Ltd Table of Contents Introduction

More information

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it. RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

LV Capacitor CLMD03 Power Module Instruction manual

LV Capacitor CLMD03 Power Module Instruction manual LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...

More information

SDS Enclosed Star-Delta Starter User Guide

SDS Enclosed Star-Delta Starter User Guide SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

IMPORTANT INSTRUCTIONS FOR OPERATION & MAINTENANCE OF

IMPORTANT INSTRUCTIONS FOR OPERATION & MAINTENANCE OF IMPORTANT INSTRUCTIONS FOR OPERATION & MAINTENANCE OF CONVEYORS EASIKIT 300 EASIKIT 450 EASIKIT 600, 900, 1200 & 1500 The manufacturer does not accept responsibility for any loss, damage to other equipment,

More information

The Powermatic User Guide Test Sieve Shaker

The Powermatic User Guide Test Sieve Shaker The Powermatic User Guide Test Sieve Shaker ISSUE 04-02 Contents Description Page 1 Setting Up: 2-8 Unpacking 2 Assembly 3-4 Levelling 4 Electrical Connections 5 Sieve Stacking 6-8 Operating Instructions

More information

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12 ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12 We thank you for having purchased VCB s from us. We are sure you will be very happy with the performance and service of

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

NEOTECHA NTB-NTC BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 2 SAFETY Please also read through these notes carefully. 2.1 General potential danger due to: a. Failure to observe the instructions

More information

ELECTRIC HOIST MODEL NO: CH2500B, CH4000B OPERATION & MAINTENANCE INSTRUCTIONS PART NO: , LS1010

ELECTRIC HOIST MODEL NO: CH2500B, CH4000B OPERATION & MAINTENANCE INSTRUCTIONS PART NO: , LS1010 ELECTRIC HOIST MODEL NO: CH2500B, CH4000B PART NO: 7630386, 7630391 OPERATION & MAINTENANCE INSTRUCTIONS LS1010 INTRODUCTION Thank you for purchasing this CLARKE Electric Hoist. Before attempting to use

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

Functions provided by measuring relays in railway equipment

Functions provided by measuring relays in railway equipment Functions provided by measuring relays in railway equipment 1-Current relays -Minimum current relays (During normal operation, if the current is present these relays are in operating position and switch

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988 Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.

More information

The EFL 2000/1 & 2 User Guide Test Sieve Shaker. Contents

The EFL 2000/1 & 2 User Guide Test Sieve Shaker. Contents The EFL 2000/1 & 2 User Guide Test Sieve Shaker ISSUE 04-02 Contents Description Page 1 Setting Up: 2-8 Unpacking 2 Assembly 3 Clamping Assembly 4 Electrical Connections 5 Sieve Stacking 6 8 Operating

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Instruction Manual. Q Series 2 Motor Control Modules - OEM

Instruction Manual. Q Series 2 Motor Control Modules - OEM A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

These installation and maintenance instructions must be read in full and completely understood before the installation!

These installation and maintenance instructions must be read in full and completely understood before the installation! These installation and maintenance instructions must be read in full and completely understood before the installation! 1. General information on the installation and maintenance instructions These instructions

More information

Steve Summers Region Sales Manager

Steve Summers Region Sales Manager Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control

More information

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Galaxy 300 Battery Breaker Kit G3HTBKIT1 Installation 990 5739 001 03/2016 990 5739 001 Galaxy 300 Battery Breaker Kit G3HTBKIT1 What s in This Document Important Safety Instructions SAVE THESE INSTRUCTIONS...1 Safety Precautions...2 Specifications...4

More information

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03 INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment

More information

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE

INSTRUCTION MANUAL. HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA INSTALLATION - OPERATION - MAINTENANCE Document: VF00W103 Rev. 8 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-5HA 7.2kV, 400A-7.0kA (4.5kA@7.2kV) HCV-5HAL 7.2kV, 400A-7.0kA (4.5kA@7.2kV) Manufactured in the USA AUGUST 2013

More information

General Instructions and Inspection Instructions for Crane

General Instructions and Inspection Instructions for Crane General Instructions General Instructions and Inspection Instructions for Crane Distributed by Ergonomic Partners Sales@ErgonomicPartners.com www.ergonomicpartners.com Tel: 314-884-8884 EN R_(EN)/1 --

More information

OLYMPIAN MODEL 740 Operation and Service Manual

OLYMPIAN MODEL 740 Operation and Service Manual OLYMPIAN MODEL 740 Operation and Service Manual P/N 133911-102 FCI MANUAL P/N 133865-001 Data herein has been verified and validated and believed adequate for the intended use. If the machine or procedures

More information

24V 3A EN54 Ancillary Power Supply

24V 3A EN54 Ancillary Power Supply 24V 3A EN54 Ancillary Power Supply Normal supply - green light on Fault condition - call Engineer Control relay - activated 3A Power Supply C-TEC Manufactured in England by C-Tec EN 54-4 : 1997 INSTALLATION

More information

Wilkins Safety Group

Wilkins Safety Group H & S Guidance - Electricity INTRODUCTION Each year there are almost 1000 reportable accidents at work due to contact with electricity including a significant number of fatalities (about 20 a year). Even

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE MODEL A96 SERIES 130Vdc Switchmode Utility Rectifier / Battery Charger Used with LaMarche Power Cage CPN112138 ECN/DATE ISSUE DATE: ECN 17010-12/05 106 BRADROCK DRIVE DES PLAINES, IL. 60018-1967 (847)

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

BM kv Digital Insulation Tester USER MANUAL

BM kv Digital Insulation Tester USER MANUAL M BM5200 5 kv Digital Insulation Tester USER MANUAL CONTENTS Safety warnings...3 Symbols used on instrument...4 Cleaning...4 General description...5 Insulation resistance test modes...5 Automatic discharge...5

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. www.usa.siemens.com/sdv7 Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V2-4A00 Answers for infrastructure

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Installation and Maintenancee Manual

Installation and Maintenancee Manual Installation and Maintenancee Manual Commercial Boom Gate Operator Model: GDS BOOM 4 and 6 A.B.N. 62 059 806 405 Nov 2013 Section No: CONTENTS Page Number: 1 Safety Precautions 3 2 Specifications 4 3 Mechanical

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

Syntron EB-00 Vibratory Parts Feeder GENERAL MANUAL

Syntron EB-00 Vibratory Parts Feeder GENERAL MANUAL Syntron EB-00 Vibratory Parts Feeder GENERAL MANUAL INSTALLATION OPERATION MAINTENANCE Thank you for buying your equipment from Homer City Automation Inc. This manual will help you to understand how your

More information

Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Battery Breaker Box Installation 09/ Galaxy VM Battery Breaker Box Installation 09/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause

4 ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause 4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL BEFORE INSTALLING PUMP, BE SURE TO READ THIS OWNER S MANUAL CAREFULLY. CAUTION Fill pump with water before starting or pump will be damaged. The motor on

More information

Installation, Operation and Maintenance Instructions. SLS Series Single Phase Disconnector

Installation, Operation and Maintenance Instructions. SLS Series Single Phase Disconnector Installation, Operation and Maintenance Instructions SLS Series Single Phase Disconnector Contents Inspection, Preparation and Installation...4 Step 1. Mounting Bracket Installation...4 Step 2. Mounting

More information

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breaker (Vehicle) Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Two Channel Remote Shutdown Device

Two Channel Remote Shutdown Device Installation & Operation Standard Features: Two Channel Remote Shutdown Device I. Introduction Latched shutdown for increased safety Powerful transmitter with 300 feet range Waterproof sealed transmitter

More information

Example Maintenance Schedule 1. The attached document is an example of an acceptable maintenance schedule.

Example Maintenance Schedule 1. The attached document is an example of an acceptable maintenance schedule. IRRIGATION TRAINING & RESEARCH CENTER California Polytechnic State University San Luis Obispo, CA 93407-0730 Phone: 805.756.2434 FAX: 805.756.2433 www.itrc.org Example Maintenance Schedule 1 The attached

More information

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES BELL SYSTEM Plant Series PRACTICES SECTION 040-811-701 Issue 1, June, 1962 AT&TCo Standard RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION I I!

More information

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00 INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR469100 BR25AT REV00 I CONTENT: 1 SAFETY 1.1 Safety instructions 1 1.2 Specified applications 1 1.3 Safety notes on the equipment operation 1 2 BR 25

More information

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution Medium Voltage Distribution MCset 17.5 kv ir insulated switchboard Withdrawable switchgear SF6 or vaccum technology Civil engineering guide pril 2012 Contents General 2 Glossary 2 Dimensions and weights

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 07897543EN01 Rev.04 11/2017 SFset- Instructions for use Table of contents Presentation Presentation...

More information

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version Optimal Series Automatic Transfer Switch Installation and User Manual for the OPT2225 Automatic Transfer Switch Full Version File: OPT2225 Rev2.5.doc November, 2004 2 Thank You For Purchasing This DynaGen

More information

PHASERS. Operating and Instruction Manual. a n d A C C E S S O R I E S

PHASERS. Operating and Instruction Manual. a n d A C C E S S O R I E S VOLTMETERS PHASERS a n d A C C E S S O R I E S Operating and Instruction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E WA U K E G A N, I L L I N O I S 6 0 0 8 5 U. S. A. PHONE 847.473.4980

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS

More information

OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM6. 6 KV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 2.0

OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM6. 6 KV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 2.0 OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM6 6 KV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 2.0 TABLE OF CONTENTS Section Number DANGER PRODUCT INFORMATION 1 -SAFETY AND CAUTION NOTES -DESCRIPTION

More information

The Management of Electrical Safety in Quarries, Associated Plant and Equipment

The Management of Electrical Safety in Quarries, Associated Plant and Equipment Quarries National Joint Advisory Committee (QNJAC) Plant Information Sheet 1 (Version 1, November 2015, review date: 2020) The Management of Electrical Safety in Quarries, Associated Plant and Equipment

More information

HIGH SPEED SLIDING GATE OPENER

HIGH SPEED SLIDING GATE OPENER HIGH SPEED SLIDING GATE OPENER Model: is1200 + Elsema s Eclipse Control Card with GDS Operator USER MANUAL CONTENTS Section No: Page No: 1 Safety Precautions 3 2 Wiring Requirements 4 3 Installation details

More information

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA

HCV-5HA 7.2kV, 400A-7.0kA HCV-5HAL 7.2kV, 400A-7.0kA Document: VF00W103 Rev. 7 INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENANCE HCV-5HA 7.2kV, 400A-7.0kA (4.5kA@7.2kV) HCV-5HAL 7.2kV, 400A-7.0kA (4.5kA@7.2kV) Manufactured in the USA MAY 2008 MAY

More information

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968 Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9968 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

GP/GPA GROUND FAULT PROTECTION

GP/GPA GROUND FAULT PROTECTION GP/GPA GROUND FAULT PROTECTION GROUND FAULT PROTECTION C-220EM Instruction Manual, June 2015 ABOUT I-GARD I-Gard s commitment to electrical safety provides both industrial and commercial customers with

More information

MODVAR Low voltage reactive power compensation modules Installation manual

MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Before installation, read this manual carefully and keep at the disposal

More information

CALTRAP INSTALLATION AND OPERATIONS MANUAL

CALTRAP INSTALLATION AND OPERATIONS MANUAL INSTALLATION AND OPERATIONS MANUAL NOTE Please read this entire installation and operations manual before energizing the. Safety Considerations: Installing and servicing capacitor equipment can be hazardous.

More information

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION

More information