ELECTRICAL INSTALLATION PROCEDURES For Custom Grid Assemblies & Power Generators

Size: px
Start display at page:

Download "ELECTRICAL INSTALLATION PROCEDURES For Custom Grid Assemblies & Power Generators"

Transcription

1 ELECTRICAL INSTALLATION PROCEDURES For Custom Grid Assemblies & Power Generators BECAUSE CLEAN AIR MATTERS Note: Factory trained or suitably qualified personnel must perform this installation. General: Figure 1 shows the general recommended arrangement of the Power Generator, Input Power and Safety Door Switch in relation to the grid assembly within the plenum. The solid state power generator produces a high-voltage (HV) direct current, which is carried to the smaller HV grid by the red wire. The generator also produces a high-frequency (HF) alternating current, which is carried to the HF screen grid by the black wire. The power generator is supplied with a red 9 (2.8m) output cable with a potted male plug. Ring terminals, supplied loose, are used for field installation for the interconnection of output power to the grids. Also provided is a black HF and green ground cable of similar length. The electrical contractor must provide input power wiring and conduit. HV Grid Figure: 1 typical installation Mounting the Power Generator: As shown in Figure: 1, 2 & 6, the power generator must be mounted as close to the grids as possible. (No further away than 9 (2.8m) wire length.) Note: Mounting the power generator more than 9 (2.8m) from the grids voids the warranty. If mounting within 9 (2.8m) of the grids creates an observation problem, an optional Remote Indicator Lamp Unit is available for observation at a suitable location. In those instances where the customer has a building management system, CosaTron can also provide an optional system that provides dry contacts, which will interface with it.

2 The power generator can be mounted on the exterior or interior plenum wall using the cabinet mounting flanges loc ted at the top and bottom of the generator enclosure. To ensure proper air circulation through the power generator louvers, a minimum 6 (15.2 cm) clearance must be maintained at the top and bottom, a 3 (7.6 cm) clearance on each side of the power generator to assure proper air fl w for cooling between solid objects or another generator. (On air units exposed to weather conditions outside of the building, the power generator must be mounted in a weatherproof, waterproof enclosure or mounted in the air stream in the air handler before the cooling coils, call CosaTron for an optional enclosure or high hat type enclosure when necessary.) The power generatort is factory set to operate on 110/120 VAC 50/60 Hz single phase, 2 amp, 3 wire input power. Input power should be brought through metal conduit to an existing knockout on the input power compartment of the generator enclosure. It must also be wired through the safety door switch(es) (see CRS-SDSA). Connection is made to the power generator by removing the cover plate labeled Connect Input Power Here, then wire input power leads to power generator leads with wire nuts (See Figure 6, 6B). Caution: This equipment must be electrically (earthed) grounded. Wiring the Power Generator to the Custom Grid Assemblies: A cable kit (2 ¼-20 X 5/8 carriage bolts, 2 ¼-20 washer nuts, 4 lock washers, 2 ring connectors, 1 #10 fork connector, 1 red heatshrink tube and 1 black heatshrink tube) is supplied for interconnection of output power of the power generator, to the grid assembly. Figure: 2

3 The power generator is equipped with a knockout and a conduit clamp on the top of the power generator for interconnection of output power to the grid assemblies through metal conduit supplied by the installing contractor. Caution: The plenum assembly should be electrically (earthed) grounded. Run metal conduit no closer than 3 (7.6 cm) from the HV grid assembly. The conduit should be burr free so that the cables are not nicked as it is pulled. Feed the three (red, black and green) wires through the conduit to the inside of the plenum. Lead wires should be cut to a length which provides sufficient service loop allowance for partial removal of the grid(s) for servicingapproximately (30.5 cm to 45.7 cm) longer than that required to reach grid(s). Excessive lead length or coiled wire may cause stray induction and adversely effect generator output. (See Figure 2 for illustration.) After cutting wires to the desired length, strip approximately ½ (1.3 cm) of insulation off the wire. Slide the ¼ (.6 cm) dia X 1¼ (3.2 cm) heatshrink tubing (provided) over the wire. Carefully and fi mly crimp the ring connectors (provided) on to the HV (red) and HF (black) wire. Carefully crimp the # 10 fork connector on the ground (green) wire. Caution: Make certain a proper mechanical as well as an electrical connection is established. Slide heatshrink tubing over crimped portion of ring connectors. Heat with a lighter, match or candle being careful not to burn insulation. Inside the plenum, connect the red HV wire to the HV braid or screen (small) grid, the black HF wire to the HF screen (large) grid and the green ground wire to the grid support framing (See Figure 2 and PUB2035). Note: Do not splice either the black HF or the red HV cable, as this will void the warranty. Caution: If the air entering the grids is above 85% relative humidity, non-hardening silicone grease should be applied to the connections to prevent corrosion. Install 2-gig ohm bleed resistor kit(s) (See Figure 2 & 6). Connect ¼ ring connector to the HV (smaller) grid with ¼-20 carriage bolt, lock washer and lock nut provided in the kit. Mount 2-gig ohm bleed resistor and grounding wire, as shown in Detail 2A of Figure 2 & Detail 6A of Figure 6, with self-drilling screws provided.

4 The electrical connection between grids, sideto-side and top-to-bottom, are made using the prepunched holes located 4 (10.2 cm) from the corner of the grid frames. Using the ¼-20 carriage bolts, lock nuts, and washers provided, attach as follows: Side-to-side: Aluminum electrical/mechanical connecting bars are provided for connecting adjacent grids side-to-side. Two sizes are included; the shorter bar provides electrical/mechanical connection between adjacent HF (large) screen grids at the pre-punched holes. The longer bar provides electrical/ mechanical connection between the adjacent HV braid (smaller) grids and is attached as shown in Figure 3. Top-to-bottom: For gridassemblies two or more high-connect the HV (small) braid grids with the red HV jumper wire. At the same time, connect the HF (larger) screen grids with the black HF jumper wire as shown in Figure 4. CAUTION: More than one generator will be supplied for plenums when cross section area exceeds the power generator capacity. Special instructions related to wiring will be provided with the submittal drawings and the shipping documents.

5 Mounting the Safety Door Switch: The safety door switch is an essential part of CosaTron it is designed for the safe operation of the system. One Safety Door switch is located inside each plenum access door (See Figure 5) and is wired into the line voltage circuit, using #14 or larger wire, to interrupt input power to the power generator when access doors are opened. Safety Door Switch 9/32" (7.1mm) X 3/4" (19mm) Slot typical 4 places Mounting Bracket Note 3/8" (9.5mm) holes provided for mounting switch from either end. Access Door Note: Any other plenum access within the immediate vicinity of the gridsmust be similarly equipped. A minimum 3 (7.6 cm) clearance must be maintained between the smaller HV grid and 1 (2.5 cm) from the larger HF gridand the safety door switch housing. This will help prevent any malfunction of the CosaTron system. In the USA, the switch must be an enclosed, carry-off, snap-action type, SPST, No., with minimum 2.0 amps per generator, 125-vac rating UL approved. The special support bracket provided is designed so that the switch can only PUB2020 Top of Plenum Figure:5 be activated by the properly positioned, special plunger, provided as part of the safety door switch assembly. See Safety Door Switch Data sheet (CRSSDSA) for additional information. Note: Do Not use normally closed (N/C) on safety door switch. Black Wire from Line Voltage Circuit to Normally Open Black Wire from Common to Input Power of Generator Side of Plenum access door Access Door Note: When plenum cross section area exceeds the power generator capacity, more than one power generator is required. When CosaTron systems are installed in separate plenums, one generator is required for each plenum. When more than one generator is required per gridassembly, refer to the CosaTronmultiple system-wiring diagrams in the submittal package and shipping papers for grid jumper locations and generator wiring. Note: The 2-gig ohm resistor provides a means for the capacitance voltage on the HV, braid gridto dissipate once power to the generator is removed. Generator power is typically removed when the plenum door is opened and plenum safety door switch opens or the power is turned off at the generator. The resistor should be mounted on the plenum floor or wall, not the grids. Three #8 X ¾ hex head self-drilling sheetmetal screws are supplied, 2 for mounting the 2-gig ohm resistor (See Figure 2, 2A and Figure 6, 6A) and one for attaching to a grounded surface. Note: Connect the 2-gig ohm bleed resistor to the HV grid that the power generator is connected to. NC NO COM

6 Figure: 6 For more information CosaTron 40 Odell School Rd, Suite 1 Concord, NC t sales@cosatron.com IOM.elecrical.4 Updated 08/2014 Made in the USA

MECHANICAL INSTALLATION PROCEDURES for Custom Grids and Support Framing

MECHANICAL INSTALLATION PROCEDURES for Custom Grids and Support Framing CosaTron Mechanical Installation Instructions MECHANICAL INSTALLATION PROCEDURES for Custom Grids and Support Framing BECAUSE CLEAN AIR MATTERS General The CosaTron Custom Grids are located within the

More information

TRAC-Station BT Installation Instructions

TRAC-Station BT Installation Instructions TRAC-Station BT Installation Instructions P/N 10103024P1 November 2011 2011 UTC Fire & Security. All rights reserved. Introduction This is the Supra TRAC-Station BT Installation Instructions. Read these

More information

CIRCLE SEAL CONTROLS

CIRCLE SEAL CONTROLS CIRCLE SEAL CONTROLS ATKOMATIC SOLENOID VALVES INSTALLATION, MAINTENANCE, AND OPERATION INSTRUCTIONS 13000 SERIES Stainless, Normally Closed, Direct Lift, 3-Way Valve Installation Instructions WARNING:

More information

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators MAx-305 & MAx-38 Series MAx-405 Through MAx-49 Series Two-Position Actuators General Instructions Application For two-position operation of dampers, valves, and other equipment which require the return

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to VAC, 3 HP to VAC without NEMA1 Enclosures

Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to VAC, 3 HP to VAC without NEMA1 Enclosures Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to 150 HP @ 230 VAC, 3 HP to 600 HP @ 460 VAC without NEA1 Enclosures odel Numbers 912FKxxxx and 913FKxxxx Instruction anual

More information

Start-up and Operation

Start-up and Operation Start-up and Operation NEVER FORGET THAT ANY MACHINE CAN BE VERY DANGEROUS WHEN NOT OPERATED CORRECTLY AND SAFELY. ALWAYS VISUALLY CHECK TO MAKE SURE THAT ALL PERSONS ARE CLEAR BEFORE TURNING ON ANY CONTROLS.

More information

BULLETIN NO.ELEC IM121/10A Replaces IM121/09A

BULLETIN NO.ELEC IM121/10A Replaces IM121/09A Mid-West Instrument BULLETIN NO.ELEC IM121/10A Replaces IM121/09A INSPECTION Model 121 Indicating Differential Pressure Switch / Transmitter Electrical: Installation and Operating Instructions Upon receipt

More information

E E VDC COOLEDGE TILE INTERIOR INSTALLATION INSTRUCTIONS. Caution: Observe precautions for handling electrostatic sensitive devices.

E E VDC COOLEDGE TILE INTERIOR INSTALLATION INSTRUCTIONS. Caution: Observe precautions for handling electrostatic sensitive devices. 5 YEAR WARRANTY 5 YEAR WARRANTY COOLEDGE TILE INTERIOR INSTALLATION INSTRUCTIONS E354088 LISTED AC E354088 58VDC E354088 E354088 5 5 YEAR WARRANTY 5 YEAR WARRANTY E354088 Caution: Observe precautions for

More information

Model 124 Filter Minder & Model 124

Model 124 Filter Minder & Model 124 Installation & Maintenance Instructions Model 124 Filter Minder & Model 124 Indicating Differential Pressure Switch / Transmitter Reading Office Cutbush Park, Danehill, Lower Earley, Reading, Berkshire.

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 144F TABLE OF CONTENTS GENERAL... 2 SPECIFICATIONS... 2 PACKAGE CONTENTS... 2 PACKAGE CONTENTS: ACCESSORIES... 3 REQUIRED TOOLS... 3 ADD-ON COMPONENTS... 3 CABINET MOUNTING WALL MOUNT BRACKET ATTACHMENT...

More information

ELECTRIC HEAT ACCESSORY INSTALLATION INSTRUCTION. 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL A-0102

ELECTRIC HEAT ACCESSORY INSTALLATION INSTRUCTION. 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL A-0102 INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 20, 30 & 40 kw for 15 Ton Split System Air Conditioners Models: LB180 & LL-15 CONTENTS GENERAL...2 NOTES, CAUTIONS AND WARNINGS........... 2 REFERENCE...2

More information

Patient Care Facility

Patient Care Facility ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for

More information

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control

More information

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING Matrix AP 400V 690V INSTALLATION GUIDE FORM: MAP-IG-E REL. May 2017 REV. 002 2017 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 080920 2008 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic mitigation

More information

Sentinel Field Satellite Controller

Sentinel Field Satellite Controller WARNING HIGH VOLTAGE 115V M AP Sentinel Field Satellite Controller Installation Instructions Important: For your protection and the safety of the product user, please comply with all Caution and Warning

More information

ELECTRO-MECH SCOREBOARD CO.

ELECTRO-MECH SCOREBOARD CO. ELECTRO-MECH SCOREBOARD CO. MM-338 FOOTBALL SCOREBOARD OWNER S HANDBOOK Thank you for choosing an Electro-Mech Scoreboard for your athletic complex. We are confident that your new scoreboard will give

More information

1100 Series Piston Type Differential Pressure Gauges

1100 Series Piston Type Differential Pressure Gauges 1100 Series Piston Type Differential Pressure Gauges 1. Safety Before installing, check the Series Number and verify compatibility to the process media and temperature in contact with the wetted parts.

More information

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT INSTALLATION AND WIRING INSTRUCTIONS MANUAL 8030 MANUAL PART NUMBER JANUARY 2011. 4304 MATTOX RD. KANSAS CITY, MO 64150 TABLE OF CONTENTS

More information

Patient Care Facility

Patient Care Facility ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for

More information

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control

More information

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT Supersedes Form145.10-IOM1 (810) Form 145.10-IOM1 (910) LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS IMPORTANT!

More information

Instructions for Field Retrofit of a Model 98 Temperature Controller in place of a Model 85 Temperature Controller

Instructions for Field Retrofit of a Model 98 Temperature Controller in place of a Model 85 Temperature Controller Introduction: Instructions for Field Retrofit of a Model 98 Temperature Controller in place of a Model 85 Temperature Controller The following is a set of instructions for retrofitting a Model 98 Digital

More information

TABLE OF CONTENTS SPECIFICATIONS 3 INSTALLATION 4. Direct Mount 4. Ducted Installations 5. Installing Plenum 5. Machine Mount Stand 5.

TABLE OF CONTENTS SPECIFICATIONS 3 INSTALLATION 4. Direct Mount 4. Ducted Installations 5. Installing Plenum 5. Machine Mount Stand 5. TABLE OF CONTENTS PAGE SPECIFICATIONS 3 INSTALLATION 4 Direct Mount 4 Ducted Installations 5 Installing Plenum 5 Machine Mount Stand 5 Ceiling Mount 6 Pedestal Stand 7 Drain Installation 7 Electrical 8

More information

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-8 Features: ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS Filtered/Regulated 24 Volts DC Up to Full 2 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit

More information

CIRCLE SEAL CONTROLS

CIRCLE SEAL CONTROLS CIRCLE SEAL CONTROLS ATKOMATIC SOLENOID VALVES INSTALLATION, MAINTENANCE, AND OPERATION INSTRUCTIONS 3000 SERIES Bronze, Normally Closed, Direct Lift Installation Instructions WARNING: These instructions

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

PDX and PX Retrofit Series

PDX and PX Retrofit Series UNIQUE LIGHTING SOLUTIONS PDX and PX Retrofit Series PDX1-1-12-XX PX1-1-12-X-X-XX-65 RETROFIT INSTALLATION GUIDE PDX and PX Series Retrofit WARNING -Retrofit installation must only be performed by a licensed

More information

I-BFV.KIT Butterfly Valve Gear Operator Replacement

I-BFV.KIT Butterfly Valve Gear Operator Replacement SERIES 5, 05,, and 0C WARNING Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products. Depressurize and drain the piping system before

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

INSTALLATION MANUAL. Melink Corporation (513) Revision

INSTALLATION MANUAL. Melink Corporation (513) Revision INSTALLATION MANUAL Revision 130711 Table of Contents Step Installation Contractor Page 1 Install System Controller Electrical 4 2 Install Variable Frequency Drive Electrical 6 3 Install Touchpad Mechanical

More information

Job Sheet 1 Installing the Net Watt-Hour Meter

Job Sheet 1 Installing the Net Watt-Hour Meter Job Sheet 1 Installing the Net Watt-Hour Meter Net kwh Meter The Grid-Tie Training System optional net meter is a 100 140 V AC, single-phase, two-wire, bidirectional triple element watt-hour (Wh) meter

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

E.S.P. Embedded Sensing Probes for Motor Brushes

E.S.P. Embedded Sensing Probes for Motor Brushes E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com

More information

HS1B R - R. Door Interlock Switches. HS1B Series. HS1B Series Full Size Interlock Switch. Part Number. HS1B features: Part Number Key.

HS1B R - R. Door Interlock Switches. HS1B Series. HS1B Series Full Size Interlock Switch. Part Number. HS1B features: Part Number Key. HSB Series HSB Series Full Size Interlock Switch HSB features: Body Rugged aluminum die-cast housing Direct Opening Action: If the door is forced open, the contacts are disconnected even if they are welded

More information

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION: 2 Please read the safety and installation instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Photo-catalytic Air Purifier. WARNING: FAILURE

More information

SPACESAVER EC-300 A ELECTRICS

SPACESAVER EC-300 A ELECTRICS INSTALLATION INSTRUCTIONS SPACESAVER EC-300 A ELECTRICS SECTION I TOP MOUNTED ELECTRICS SECTION II FACE PANEL MOUNTED ELECTRICS SECTION III ZFS INSTALLATION INSTRUCTIONS This symbol indicates a connection

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

CENTRIFLOW METER and ELECTRONICS WIRING and INSTALLATION MANUAL REV 01/16 ORIGINAL LANGUAGE Copyright 2016 Eastern Instrument Laboratories, Inc. All Rights Reserved. TABLE OF CONTENTS SAFETY Safe Operation...

More information

Installation, Maintenance, and Operation Manual

Installation, Maintenance, and Operation Manual GTX TM UNIT SUBSTATION Installation, Maintenance, and Operation Manual Rev.3 03-10-15 Marina Electrical Equipment, Inc. 100 Warwick Court Williamsburg, VA 23185 Toll Free: 1-855-258-3939 Fax: 1-757-258-3988

More information

ITS-50R TRANSFER SWITCH OWNER S MANUAL

ITS-50R TRANSFER SWITCH OWNER S MANUAL ITS-50R OWNER S MANUAL IOTA Engineering Transfer Switches provide automatic power switching between two or three separate 120/240 volt AC input sources, including powercords, onboard generators, onboard

More information

Lumencia. LLMPS SERIES Micro Power Systems. Multi-Unit Residential Lighting. Job Name: Type:

Lumencia. LLMPS SERIES Micro Power Systems. Multi-Unit Residential Lighting. Job Name: Type: APPLICATIONS LLMPS Series inverter systems are designed to provide sinusoidal AC emergency power to incandescent, flourescent, or LED fixtures of between 20 and 55 watts. Surface, recessed or ceiling T-Grid

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE*

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* Specifications - Installation and Operating Instructions Bulletin B-34 Series 43000 CAPSU-Photohelic Switch/Gage The CAPSU-Photohelic Switch/Gage is a most versatile,

More information

Pneumatic Isolation Module

Pneumatic Isolation Module Pneumatic Isolation Module (Cat. 2030-Pxxxxx) ATTENTION: Hazardous Voltage or other forms of energy could be present. To avoid serious injury or death: Prior to beginning the installation and wiring process,

More information

MA-5200 Series MA-5300 Series

MA-5200 Series MA-5300 Series MA-5200 Series MA-5300 Series Two-Position Actuators General Instructions Application The MA-5200 series and MA-5300 series actuators are used for two-position control of valves and dampers which require

More information

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None THC-2, THC-3, THCR-4, THCR-5 Enthalpy Control General Instructions APPLICATION For ON-OFF (two position) low voltage control of the amount of air brought into the cooling system with respect to the total

More information

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT

More information

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions WARNING HIGH VOLTAGE 115V 4 M AP Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions Important: For your protection and the safety of the

More information

HS1B Series Full Size Interlock Switch. GS-ET-15 BG standard in Germany. Part Number Key

HS1B Series Full Size Interlock Switch. GS-ET-15 BG standard in Germany. Part Number Key HSB Series Full Size Interlock Switch HSB features: Rugged aluminum die-cast housing Direct Opening Action: If the door is forced open, the contacts are disconnected even if they are welded or stuck Available

More information

TS Series TS Series

TS Series TS Series TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com TS-6700-850 Series TS-5700-850 Series Electronic Remote Temperature Sensors General Instructions APPLICATION Electronic thermistor

More information

Utility Distribution Systems Installation, Operation, and Maintenance Manual

Utility Distribution Systems Installation, Operation, and Maintenance Manual Utility Distribution Systems Installation, Operation, and Maintenance Manual RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately

More information

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1 Series Bulk Flow Monitor Specifications - Installation and Operating Instructions Bulletin FL-1-4x 3/4 CONDUIT KNOCKOUTS BFS 1A FUSE RED LED RELAY 5-9/64 [130.45] TRANSFORMER 3[76.20] GREEN LED 7 [177.80]

More information

Installation Instructions

Installation Instructions Outdoor plit Flow Center Kit FCP11BDO (1 pump) FCP21BDO (2 pumps) For plit Geothermal Heat Pump models GZ & H Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

BITZER Capacity Controller for CSH Compressors Temperature Sensor

BITZER Capacity Controller for CSH Compressors Temperature Sensor only. The Temperature Controller has been obsoleted. The below data is for informational purposes only BITZER Capacity Controller for CSH Compressors Temperature Sensor The BITZER CSH Capacity Controller

More information

Safety, Installation and Service Manual Models 1952, 1953 & 1972

Safety, Installation and Service Manual Models 1952, 1953 & 1972 Ultraviolet Germicidal Lamps Model 1952 24 Rooftop Unit Model 1953 32 Rooftop Unit Model 1972 Rooftop Unit, Internal Mount Safety, Installation and Service Manual Models 1952, 1953 & 1972 READ AND SAVE

More information

Operation and Installation Manual

Operation and Installation Manual BOMBA PRESURIZADORA AUTOMÁTICA CONTROLADOR SOLAR AQUA SOLAR SERIE MINI SMART GL-235 MINI25-10/1115-110V Electronic Solar Control Operation and Installation Manual GL-235 Description The GL-235 is a differential

More information

STARTER SYSTEM TESTING 5.6

STARTER SYSTEM TESTING 5.6 STARTER SYSTEM TESTING 5.6 ON-MOTORCYCLE TESTS b088x5x Starter Relay Test NOTE Starter relay test also applies to ignition and key switch relays.. See Figure 5-5. Locate starter relay. The relay is attached

More information

Installation Instructions

Installation Instructions Installation Instructions 2-Post Capacity 12,000 lbs. OPERATING CONDITIONS Lift is not intended for outdoor use and has an operating ambient temperature range of 41-104 F (5-40 C) IMPORTANT Reference ANSI/ALI

More information

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS Supersedes: 160.75-PW2 (508) Form 160.75-PW2 (311) FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS WIRING DIAGRAM CONTRACTOR ORDER NO. YORK CONTRACT NO.

More information

30A SMART ENERGY MANAGEMENT SYSTEM TM

30A SMART ENERGY MANAGEMENT SYSTEM TM 30 Amp EMS Display Panel P/N 00-00903-030 (Black) 30 Amp EMS Distribution Panel P/N 00-0091-000 CAUTION The 30A SMART EMS is a centralized power switching, fusing, and distribution center. Power from the

More information

Model LA 4100 Time Delay OFF Controller

Model LA 4100 Time Delay OFF Controller ISIMET LA Series Model LA 4100 Time Delay OFF Controller Installation, Operation and Maintenance Manual Application: The Time Delay OFF Controller operates as a single output controller where the application

More information

Notdson MANUAL REFILL/MELTER RETROFIT KIT. SUPERSEDES -i I/ f3 NORDSON CORPORATION 1984 All Rights Reserved

Notdson MANUAL REFILL/MELTER RETROFIT KIT. SUPERSEDES -i I/ f3 NORDSON CORPORATION 1984 All Rights Reserved Packagmg and Assembly Division Notdson Atlanta, Georgia TECHNICAL PUB ICATION 5 9-3 - MANUAL 59-3 AUTOMATIC HOT MELT REFILL/MELTER RETROFIT KIT ELECTRONIC LEVEL CONTROL MODEL ISSUED 984 Publication No.

More information

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic

More information

SPO15, SPO18 I N S T A L L A T I O N I N S T R U C T I O N S

SPO15, SPO18 I N S T A L L A T I O N I N S T R U C T I O N S SPO15, SPO18 Sprinter SPO15 (3A0 Lifts) Capacity 11,000 lbs. Standard SPO15 (300 Series Lifts) Capacity 15,000 lbs. Standard SPO18 (300 Series Lifts) Capacity 18,000 lbs. SPO15 (31A0 Lifts) Capacity 14,300

More information

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure 592 Theory of Operation The 592 sensor is a two terminal integrated-circuit temperature sensor. The 592 provides an output current directly proportional to absolute temperature. When the temperature of

More information

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation MATRIX FILTER SERIES D 480 Volts, 60HZ USER MANUAL PART NO. INSTR 024 REL. 120628 REV. 012 2012 MTE Corporation Matrix Series D User s Manual 480VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions CP-90 CP-90 Electronic Drives General Instructions Application The CP-90 and CP-90 electronic actuator drives process a variable input signal from a controller to provide proportional control of an electric

More information

INSTALLATION INSTRUCTIONS CRL JACKSON 2085E

INSTALLATION INSTRUCTIONS CRL JACKSON 2085E INSTALLATION INSTRUCTIONS CRL JACKSON 2085E ELECTRIC LATCH RETRACTION CONCEALED VERTICAL ROD PANIC EXIT DEVICE crlaurence.com Phone: (800) 421-6144 Fax: (866) 921-0531 crlaurence.com usalum.com crl-arch.com

More information

Quick Connection Panel (QCP) Installation Guide

Quick Connection Panel (QCP) Installation Guide Quick Connection Panel (QCP) Installation Guide DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read this document first. The installer is responsible for compliance with National Electrical

More information

2520- EC Motor Speed Controller

2520- EC Motor Speed Controller 2520- EC Motor Speed Controller T1 AC Line Voltage From Contactor T2 or Neutral 760-ECM ECM Motor BLACK ORANGE BLACK RED (+) Signal 24VAC (-) GND Features Motor Types: ECM (dc brushless) Motors Motor Speed:

More information

FSAF24(-S) US, FSAF120(-S) US

FSAF24(-S) US, FSAF120(-S) US FSAF4(-S) US, FSAF10(-S) US On/Off, Spring Return, Meets 50 F [11 C] for Half Hour, 75 Seconds Torque min. 133 in-lb, for control of air dampers Technical Data FSAF4(-S) US, FSAF10(-S) US Power supply

More information

IMPORTANT INSTRUCTIONS INSTALLATION AND STARTUP MODEL GDCP-A CONTROL PANEL

IMPORTANT INSTRUCTIONS INSTALLATION AND STARTUP MODEL GDCP-A CONTROL PANEL IMPORTANT INSTRUCTIONS INSTALLATION AND STARTUP MODEL GDCP-A CONTROL PANEL WARNING USE OF HOUSING FOR FIELD WIRING WILL VOID THE FACTORY WARRANTY. Transmitter is considered water resistant only when the

More information

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by

More information

TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)

TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A) TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT-29499-1A) Contractor: Please read these instructions before starting installation. After installation, please forward this guide to the user

More information

Installation Instructions Capacity 10,000 lbs. (100 Series Lift)

Installation Instructions Capacity 10,000 lbs. (100 Series Lift) Installation Instructions Capacity 10,000 lbs. (100 Series Lift) IMPORTANT Reference ANSI/ALI ALIS, Safety Requirements for Installation and Service of Automotive Lifts before installing lift. OPERATING

More information

CSA CERTIFIED Conforms to UL 507

CSA CERTIFIED Conforms to UL 507 Installation tion Instructions Please read and save these instructions! TURBO/MAXX12 Volt All Weather RV Ventilator Fans P/N 00-965001 Deluxe Model 1200T WITH THERMOSTAT P/N 00-965007 Standard Model 3550

More information

Control Panel Interface Upgrade Installation Guide For Model 200i and 250i Motorcycle Dynamometers Serial Number 202xxxx.

Control Panel Interface Upgrade Installation Guide For Model 200i and 250i Motorcycle Dynamometers Serial Number 202xxxx. 2004 Dynojet Research, Inc. All Rights Reserved. Control Panel Interface Upgrade Installation Guide For Model 200i and 250i Motorcycle Dynamometers Serial Number 202xxxx. This manual is copyrighted by

More information

BULLETIN NO.ELEC IM240/11A Supersedes IM240/10A

BULLETIN NO.ELEC IM240/11A Supersedes IM240/10A Mid-West Instrument ELECTRICAL Upon receipt of your order, please review the ratings plate to verify that the model number and the electrical ratings match the product that you ordered. Figure 1 is the

More information

Transformer Installation, Operation, and Maintenance Manual

Transformer Installation, Operation, and Maintenance Manual Transformer Installation, Operation, and Maintenance Manual CONTENTS INTRODUCTION......................................... 2 INSPECTION UPON RECEIVING... 2 STORAGE...............................................

More information

Operations and Service Manual. X30208 Load Bank

Operations and Service Manual. X30208 Load Bank Operations and Service Manual Read all instructions before using the load bank Contents 1. Components... 3 Total Assembly... 3 2) Specifications... 4 a)... 4 3) Receiving... 5 4) Safety... 5 a) Ground

More information

Hinged Safety Door Switch

Hinged Safety Door Switch Hinged Safety Door Switch Polymer housing, IP65, and slow-action contacts with positive opening. Two actuator types are available: Shaft Arm lever Arm lever type can be adjusted to allow a right (180 ),

More information

Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL

Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL POWER CONVERSION/DISTRIBUTION Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL 3 Phase 15 kva - 225 kva 50 & 60 Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1

More information

HS2B N B - R. Door Interlock Switches. HS2B Series. Full Size Interlock Switch. Part Number. HS2B features: Part Number Key.

HS2B N B - R. Door Interlock Switches. HS2B Series. Full Size Interlock Switch. Part Number. HS2B features: Part Number Key. HSB Series HSB Series Full Size Interlock Switch HSB features: Body Direct Opening Action: If the door is forced open, the contacts are disconnected even if they are welded or stuck Available with or without

More information

Inde-Pendants Family. 32L Cylinder with Ring Chicago Plenum Ceiling Types. Document No

Inde-Pendants Family. 32L Cylinder with Ring Chicago Plenum Ceiling Types. Document No Inde-Pendants Family 32L with Ring Chicago Plenum Ceiling Types Installation instructions for: 32L-CRxx-P-ID-CCEA 32L-CRxx-P-D-CCEA Document No. 32L Inde-Pendants: with Ring (Plaster Trim, Grid and Drywall

More information

Materials. Contact Ratings. Conduit Entrances

Materials. Contact Ratings. Conduit Entrances Features NEMA 1, 3, 4, 4X, 6, 6P, 9 & 13 IP66 and 67 Water tight, dust tight and corrosion resistant for outdoor use For use in hazardous locations: Class I, Div. 1 & 2, Groups C, D Class II, Div. 1 &

More information

CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR

CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR WIRING DIAGRAMS CONTRACTOR ORDER NO. JCI CONTRACT NO. JCI ORDER NO. Supersedes: 160.80-PW4 (1099) Form: 160.80-PW4 (215) FIELD CONNECTIONS ROTARY SCREW CHILLER WITH GRAPHIC CONTROL CENTER AND YORK MOD

More information

MEDIA LED. Pendant Standard Mount Installation ou de montage WARNING:

MEDIA LED. Pendant Standard Mount Installation ou de montage WARNING: MEDIA LED Pendant Standard Mount WARNING: Disconnect main power at the source prior to installation! Thread gripper base onto 1 /4 20 stud, or with #8 screw. Depress gripper nozzle to insert aircraft cable.

More information

METROLOGIC INSTRUMENTS, INC. MX001 Industrial Control Interface Installation and User s Guide

METROLOGIC INSTRUMENTS, INC. MX001 Industrial Control Interface Installation and User s Guide METROLOGIC INSTRUMENTS, INC. MX001 Industrial Control Interface Installation and User s Guide Copyright 2007 by Metrologic Instruments, Inc. All rights reserved. No part of this work may be reproduced,

More information

Electric Range installation manual

Electric Range installation manual Electric Range installation manual This manual is made with 100% recycled paper. imagine the possibilities ENGLISH Thank you for purchasing this Samsung product. To receive more complete service, please

More information

Model LA 4400 Time Delay OFF Controller

Model LA 4400 Time Delay OFF Controller ISIMET LA Series Model LA 4400 Time Delay OFF Controller Installation, Operation and Maintenance Manual Application: The Time Delay OFF Controller with integral 24-hr. programmable time clock operates

More information

IP65 COOLEDGE TILE EXTERIOR R2 INSTALLATION MANUAL. Exterior TILE Jumper Cable. Exterior Cutout TILE. Cable Clamp. T-Cable.

IP65 COOLEDGE TILE EXTERIOR R2 INSTALLATION MANUAL. Exterior TILE Jumper Cable. Exterior Cutout TILE. Cable Clamp. T-Cable. 5 YEAR SYSTEM WARRANTY 5 YEAR SYSTEM WARRANTY COOLEDGE TILE EXTERIOR R2 INSTALLATION MANUAL Exterior Cutout TILE Exterior TILE Jumper Cable T-Cable End Cap Cable Clamp Power Supply Control Module Waterproof

More information

20 amps 220 amps, 60 Hz VDC VAC G3PA-420B-VD-2 DC amps 440 amps, 60 Hz G3PA-450B-VD-2 DC12-24

20 amps 220 amps, 60 Hz VDC VAC G3PA-420B-VD-2 DC amps 440 amps, 60 Hz G3PA-450B-VD-2 DC12-24 Solid State Relays (SSRs) G3PA/G3PB Long Service Life for Circuits that Cycle Frequently D D D D D Built-in heat sink increases life and reliability Voltage turn-on at zero crossing reduces initial inrush

More information

Model LA 4300 Time Delay OFF Controller

Model LA 4300 Time Delay OFF Controller ISIMET LA Series Model LA 4300 Time Delay OFF Controller Installation, Operation and Maintenance Manual Application: The Time Delay OFF Controller operates as a single output controller where the application

More information

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS

AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS AUXILIARY BATTERY BOX INSTALLATION INSTRUCTIONS The original TOMMY GATE hydraulic lift Assembling the Auxiliary Battery Box 1. Remove the cover from the auxiliary battery box by removing the two nuts and

More information

Cam-Lok Single Pole Connectors

Cam-Lok Single Pole Connectors Cam-Lok Single Pole Connectors Cooper Interconnect Cam-Lok Single Pole Connectors are specially designed to provide the ultimate in reliable service, even under the most severe operating conditions. These

More information