Extending A99 Sensor Cables

Size: px
Start display at page:

Download "Extending A99 Sensor Cables"

Transcription

1 Extending A99 Sensor ables ode No. LIT Issued June 17, 2014 IMPORTANT: The A99 temperature sensor is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the A99 temperature sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the A99 temperature sensor. When the A99x Sensor is installed more than 50 feet (15.25 meters) from the controller, the resistance of the wire in the cable can create a significant deviation to the sensor reading. Use the following procedure to compensate for the deviation. Refer to the System 450 Series Modular ontrols Product Bulletin (LIT ), the A99B Series Temperature Sensors Product/ Technical Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. Note: Use shielded wire when you install the sensor more than 50 feet (15.25 meters) from the controller. IMPORTANT: When connecting an A99 temperature sensor with shielded cable to an electronic controller, connect the cable shield drain lead to a low-voltage common terminal on the input sensor terminal block. Do not connect the shield at any other point along the cable. Isolate and insulate the shield drain at the sensor end of the cable. onnecting a cable shield at more than one point can enable transient currents to flow through the sensor cable shield, which can cause erratic control operation. 1. Use one of the following formulas to calculate the total wire resistance (error): a. Total wire resistance (ohms) = 2 x (Length of wire cable in meters) x (Resistance in ohms/meter) b. Total wire resistance (ohms) = 2 x (Length of wire cable in feet) x (Resistance in ohms/foot) Ohm Resistance of Typical Stranded opper Wire Wire Size ross Section Resistance Area American Wire Metric (mm) ircular mils Ohm/foot Ohm/meter Gauge (AWG) , , , , Determine the approximate temperature control point of the remote-mounted A99 Sensor, and then use that F or temperature in one of the following formulas to determine the ohms/degree at that temperature: Ohms/ = ( x ) Ohms/ F = ( x F) alculate the wire resistance error in F or : Error = (ohm wire resistance error)/(ohms/degree value at control point) Metric Example English Example If the A99 Sensor used for Sn-1 and Sn-2 inputs is installed 50 meters (164 feet) from the 450 control using 0.5 mm wire, the total wire resistance (error) is: 2 x 50 x.0352 = 3.52 ohms Then, if the A99 Sensor controls a process at 25, the ohms/ is: ( x 25) = 7.63 ohms/ Therefore, the error is: 3.52/7.63 = 0.46 So, the 450 control sensor inputs for Sn-1 and Sn-2 should be offset by If the A99 Sensor used for Sn-1 and Sn-2 inputs is installed 300 feet (91.44 meters) from the 450 control using 18 AWG wire, the total wire resistance (error) is: 2 x 300 x.0065 = 3.9 ohms Then, if the A99 Sensor controls a process at 70 F, the ohms/ F is: ( x 70) = 4.15 ohms/ F Therefore, the error is: 3.9/4.15 = 0.94 F So, the 450 control sensor inputs for Sn-1 and Sn-2 should be offset by -1 F. The following diagram illustrates how to enter this offset in the 450 Sensor Setup screen.

2 Extending A99 Sensor ables (ontinued) Press and hold + for 5 seconds to go to the Setup Start screens. Setting Up Sensor Temperature Offsets in the System 450 UI 2

3 ode No. LIT Issued June 17, 2014 Proportional ontrol of a Barber-olman MMR-400 Actuator IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. Note: This application example uses a temperature sensor, but you can control this application based on temperature, pressure, or humidity. Refer to the technical bulletin for more information on selecting and setting up System 450 compatible sensors for your application. In this System 450 application example, Sn-1 is a F (Sensor Type) and OUTA1 is an analog output that references the Sn-1 sensor. The Barber-olman actuators are set up for a 0 to 10 VD input signal from the control module, but the actuator can also be set up to respond to a 0 to 20 ma signal from the control module. In this example, the control module provides 100% signal strength (10 VD) at temperatures of 75 F and above, and 0% signal strength (0 VD) at temperatures of 55 F and below. You can use any System 450 compatible sensor and any Setpoint or End Point value within the selected sensor s defined range of values to control this proportional damper application. Terminal onnections Actuator 450PN-x Terminal Terminal Description TR2 ommon TR1 24V 24 VA 16 AO1 Signal VD or AO1 Signal ma A99 Temperature Sensor Sn-1 ontrol Sensor in UI Display ( F Sensor Type) 450PN-x ontrol Module OUTA1 24V OM AO1 Note: The (ommon) terminals on the input terminal blocks and the OM terminal on the analog output are connected internally in the control module. The connection between (on the control module) and TR2 on the actuator provides the common connection for the OUTA1 analog output. L1 120/240 VA L2 24 VA lass 2 or SELV Transformer TR2 AO VD Application with a ommon Transformer 16 TR FIG:sys450_0to10vdc_commtrans Note: Actuator terminal TR2 is internally connected to Terminal 9 on the actuator s printed circuit board. 1

4 Proportional ontrol of a Barber-olman MMR-400 Actuator (ontinued) Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Main, System, Status, and Setup Screens For the 0 10 VD Application with a ommon Transformer Example 2

5 ode No. LIT Issued June 17, 2014 Proportional Temperature, Pressure, or Humidity ontrol of an M9100-GGA or M9100-GG Actuator IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. This application note illustrates how to wire a 450PN-x ontrol Module to an M9100-GGA or M9100-GG Actuator. In these actuator application examples, Sn-1 is a F (Sensor Type) and OUTA1 is an analog output that references the Sn-1 sensor. The M-9100 actuators are set up for control via a 2 to 10 VD input signal from the System 450 control module. The System 450 control module provides 100% signal strength (10 VD) at temperatures of 75 F and above, and 20% signal strength (2 VD) at temperatures of 55 F and below. You can use any System 450 compatible sensor and any Setpoint or End Point values within the selected sensor s defined range of values to control your application. In the following application examples, a single temperature sensor is used to provide the input signal. You can also control these applications with a pressure, humidity, or functional sensor. Refer to the technical bulletin for complete information on selecting and setting up System 450 compatible sensors. A99B Temperature Sensor Sn-1 ontrol Sensor in UI Display ( F Sensor Type) See Sensor Note 450PN-x ontrol Module OUTA1 Power Module 450YNN-1 M9100-GGx Series Actuator OM AO1 240 VA 120 VA FIG:sys450_controlpower VA L1 24 VA 120/240 VA L2 OM 24 VA lass 2 or SELV 2-10V Transformer A 450PN-x ontrol Module Powered by a 450YNN-1 Power Module Driving an M9100-GGA or M9100-GG Actuator Powered by a Dedicated 24 VA External Transformer 1

6 Proportional Temperature, Pressure, or Humidity ontrol of an M9100- GGA or M9100-GG Actuator (ontinued) A99B Temperature Sensor Sn-1 ontrol Sensor in UI Display ( F Sensor Type) Sn1 See Sensor Note 24V 450PN-x ontrol Module OUTA1 Note: The (ommon) terminal on the input terminal and the OM terminal on the Analog Output are connected internally in the control module. M9100-GGx Series Actuator OM AO1 FIG:sys450_controltransformer L1 24 VA 120/240 VA L2 OM 24 VA lass 2 or SELV 2-10V Transformer A 450PN-x ontrol Module Driving an M9100-GGA or M9100-GG Actuator, All Powered by an External Transformer 2

7 Proportional Temperature, Pressure, or Humidity ontrol of an M9100- GGA or M9100-GG Actuator (ontinued) A99B Temperature Sensor Sn-1 ontrol Sensor in UI Display (F Sensor Type) See Sensor Note 450PN-x ontrol Module OUTA1 Power Module 450YNN-1 Note: Maintain polarity when wiring 24 VA power to the M9100 Series Actuators. M9100-GGx Series Actuator OM AO1 240 VA 120 VA FIG:sys450_control24vac M9100-GGx Series Actuator 120 VA L1 120/240 VA L2 24 VA OM M 24 VA 2 10V 24 VA lass 2 or SELV Transformer 2-10V A 450PN-x ontrol Module Powered by a 450YNN-1 Power Module Driving Up to Five M9100-GGA or M9100-GG Actuators Wired in Parallel and Powered by a Dedicated 24 VA External Transformer Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Main, System, Status, and Setup Screens for the ontrolling M9100-GGA or M9100-GG Actuators Example 3

8 ode No. LIT Issued June 17, 2014 Proportional Temperature ontrol of M9200 Series Actuators with Remote Minimum Positioning IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. You can use a System 450 ontrol Module with analog output, a temperature sensor, and a Y45AA-9 Rheostat to control air temperature at the sensor by modulating an M9200 Series Actuator driving an outside air damper. Use the rheostat to manually set the minimum air position of the damper between 0 and 50%. The temperature sensed at Sn-1 controls the damper position between the rheostat adjusted minimum position (0 to 50%) and full open. Set the minimum output on the 450PN-x ontrol Module to 0% rotation and then use the Y45AA-9 Rheostat to set the minimum position remotely. A99 Series Sensor Sn1 450PN-x ontrol Module OUTA1 5V 24V OM AO1 FIG:sys450_remoteminpos_0to50 Note: The (ommon) terminal on the input terminal and the OM terminal on the analog output are connected internally in the control module. 1 Field-Supplied 100 Volt (Minimum) Diode M9200 Series Actuator Y45AA-9 0 to 50% L1 120/240 VA L2 OM 24VA 24 VA lass V or SELV Transformer Wiring for Remote 0 to 50% Minimum Positioning Application 1

9 Proportional Temperature ontrol of M9200 Series Actuators with Remote Minimum Positioning (ontinued) Note: OUTA1 controls the actuator. FIG:proportional_scrns Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. UI Screens for Wiring for the Remote 0 to 50%Minimum Positioning Application Example 2

10 ode No. LIT Issued June 17, 2014 ooling Tower ontrol with Two-Speed Fan/Low Temperature Lockout IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), A99B Series Temperature Sensors Product Technical Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. A 450BN-x ontrol Module with Relay Output, used with a 450SN-x Expansion Module with Relay Output and two A99 Series Temperature sensors, monitors and controls the water temperature in the cooling tower sump. On an increase in sump temperature (Sn-2), the low speed fan winding is energized by the normally open contact on the left side relay (OUTR2) of the expansion module, which is in series with the normally closed contact on the right side relay (OUTR3) of the expansion module. As temperature at Sn-2 increases, the right side relay energizes, breaking contact to the low speed winding and energizing the high speed winding. If the outside air temperature (Sn-1) falls below the desired lockout temperature, the System 450 control module de-energizes the fan circuit by breaking the power connection to the System 450 relay outputs (OUTR1). The control module relay output (OUTR3) references Sn-1 and de-energizes power to the fans when the outside air temperature falls below the desired lockout temperature. Set up the desired setpoints for each relay. See the figures on pages 1 and 2 to wire the components and set up the screens in the UI. *able Shield Sump Temperature Sn-2 Outside Air Temperature Sn-1 Sn2 Sn1 450BN-x ontrol Module OUTR1 450YNN-1 Power Module 450SN-x Expansion Module OUTR2, OUTR3 * For sensor cable runs over 50 feet or sensor cables run in areas of high electrical noise, use shielded cable. onnect the cable shield drain wire to any of the terminals on the input terminal block. Isolate and insulate any exposed cable shield or cable shield drain. Do not connect the cable shield at any other point along the sensor cable run. L1 120 VA L1 LNO1 LN1 240 VA 120 VA L1 LNO1 LN1 L2 LNO2 FIG:clgtwr_app High Speed Fan Low Speed Fan ommon Fan Wiring Diagram for Typical ooling Tower Application Using System 450 omponents 1

11 ooling Tower ontrol with Two-Speed Fan/Low Temperature Lockout (ontinued) Status Screens: 50 o 70 o F 2 3 OFF OUT 1 OFF OUT 2 OFF OUT 3 Summary of UI Setup Screens: SENS M Sn-1 F F Sn-2 Sn OFFS 1 OFFS 2 OUTR1 Sn OFF SENS 1 ON 1 OFF 1 ONT 1 OFFT 1 SNF 1 Sn-1 SENS 1 Sn-2 SENS 2 75 ON 2 72 OFF 2 ONT OFFT 2 OFF SNF 2 Sn-2 SENS 2 OUTR3 Sn-2 SENS 3 80 ON 3 77 OFF 3 ONT OFFT 3 OFF SNF 3 Sn-2 SENS 3 FIG:ctcapp_scrns Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. UI Screens for the Typical ooling Tower Application Using System 450 omponents Example 2

12 ooling Tower ontrol with Two-Speed Fan/Low Temperature Lockout (ontinued) Relay State OFF Low Speed Fan High Speed Fan ON OUTR2 Disable Fan OFF Enable Fan ON 71 F 72 F 73 F 74 F 75 F 76 F 77 F 78 F 79 F 80 F 81 F Sn-2 Temperature ( F) OFF Lockout Fan Enable Fan ON OUTR1 53 F 54 F 55 F 56 F 57 F 58 F 59 F 60 F Sn-1 Outside Air Temperature ( F) Note: OUTR1 locks out the ooling Tower ontrol when the outside air temperature (Sn-1) is below 55 F. ooling Tower Fan ontrol 3

13 ode No. LIT Issued June 17, 2014 System 450 Differential ontrol to Replace a Standard Differential Pressure Transmitter IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. You can use System 450 to measure a pressure difference across pumps, heat exchangers, and similar devices where you want to control a device using differential pressure. ompared to a Differential Pressure Transmitter (DPT), installing System 450 is simpler, requires less hardware, and is less labor-intensive, saving time and money. System 450 parameters are easy to configure and readjust, if necessary, making it much more flexible than a DPT. A DPT requires a manifold, a bleeder valve, isolation valves, a bypass valve, and associated piping. Only the isolation valves are required for a System 450 installation. In this example, a System 450 control system with two identical pressure transducers is set up to control pump speed based on the pressure differential detected between the Sn-1 and Sn-2 transducers. When Sn-1 and Sn-2 are the same Sensor type, the Differential Sensor (Sn-d) is automatically enabled and available for selection when you set up the control system outputs. When the Differential ontrol sensor (Sn-d) is referenced, the differential sensor value is always equal to Sn-1 minus Sn-2. The sensed differential value (Sn-d) between Sn-1 and Sn-2 is displayed in the System Status screens as either a temperature differential value (dift), pressure differential value (difp), or humidity differential value (difh). For example, if Sn-1 has a value of 58 and Sn-2 has a value of 55, Sn-d has a value of 3 (58 minus 55). Low Pressure 450PN-x ontrol Module OUTA1 High Pressure Port Low Pressure Port High Pressure Valve A Valve B Valve Inputs: Any two compatible P499 Pressure Transducers of the same pressure range. OM AO1 Versus Differential Pressure Transmitter Speed ontrol for Water Pump FIG:sys450_diff_pressure Speed ontrol for Water Pump This System 450 control application eliminates the need to install the piping manifold, bypass valve, and bleeder valve used on a typical differential control application. omparison of a System 450 Differential Pressure ontrol to a Differential Pressure Transmitter Using a Variable Speed Water Pump to Regulate Differential Water Pressure 1

14 System 450 Differential ontrol to Replace a Standard Differential Pressure Transmitter (ontinued) 58.0 Main Screens Auto-Scroll FIG:sys450_ui_screens Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. UI Screen Parameters Needed to Set Up Sensors for Differential Pressure ontrol 2

15 ode No. LIT Issued June 17, 2014 Attaining Equal Runtimes on Redundant Mechanical Systems IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. The 450RN-x Reset ontrol Module enables you to keep the runtimes approximately equal on applications with redundant equipment. This example uses two similar cooling units with a space setpoint of 55 F. To attain equal runtimes on both cooling units, you must use the Reset function (res) in conjunction with the balancing function (bal). Refer to the System 450 Series Modular ontrol Systems with Reset ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. 450RN-x ontrol Module OUTR1, OUTR2 450YNN-1 Power Module Sn2 Sn1 Wire the sensor (Sn1) to Sn1 and any common (). Wire the space sensor (Sn2) to Sn2 and any common (). L1 L1 LNO1 LN1 L2 LNO2 240 VA 120 VA FIG:xys450_runtime L2 ooling 1 ooling 2 450RN-x ontrol Module Attaining Equal Runtimes on Redundant Mechanical Systems 1

16 Attaining Equal Runtimes on Redundant Mechanical Systems (ontinued) In this example, Sensor 2 (Sn-2) is the space sensor. Sensor 1 (Sn-1) must be installed, although the physical location of Sn-1 is not important in this example. The desired 55 F space temperature setpoint is attained by setting both the minimum setpoint (MNSP) and the maximum setpoint (MXSP) to 55 F. The control cycles the output relay (unit) with the fewest hours, keeping the runtime hours approximately equal SENS M Sn-1 F Sn-2 F - - Sn OFFS 1 OFFS RSET OUTR OUTR TIME SHE 55 12Hr LK - -:- - O-1 AM diff :22 5 SETT AM 0 ONT MNSP MXSP RSTR RENd SdHI SdLO SbK bal res SENS 1 res SENS diff 2 ONT 2 0 OFF SNF 1 OFF SNF 2 res SENS 1 res SENS 2 Note: The schedule setup for days 1 through 7 is not needed for this application; therefore, the SHE setup screens are not needed. 12:00 - -:- - 12:00 UN-1 AM O-7 AM UN-7 AM FIG:sys450_ui_screens 0 On Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Status and UI Setup Screens for the 450RN-x ontrol Module Attaining Equal Runtimes on Redundant Mechanical Systems Example 2

17 ode No. LIT Issued June 17, 2014 Floating ontrol System Powered by an External Transformer to ontrol an Actuator IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. You can set up a 450N-x ontrol Module using any compatible sensor to provide floating control (of an actuator motor or other device) with a deadband. The following diagrams illustrate how to set up an actuator for floating control using a 450N-x ontrol Module, an external transformer, and a temperature sensor. Note: You can control this application based on temperature, pressure, or humidity. Refer to the technical bulletin for more information on selecting and setting up System 450 compatible sensors for your application. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. Series A99 Sensor See Sensor Note Sn1 450N-x ontrol Module OUTR1, OUTR2 24V L1 LNO1 LN1 L2 LNO2 FIG:sys450_dual_relay L1 120/240 VA L2 24 VA lass 2 or SELV Transformer W OM W Actuator/Modulating Motor Wiring a 450N-x ontrol Module Using Any ompatible Temperature Sensor for Floating ontrol Applications 1

18 Floating ontrol System Powered by an External Transformer to ontrol an Actuator (ontinued) OUTR1 Deadband Drive W OFF to ON ON to OFF OFF OUTR2 Drive W ON 68 F 70 F 72 F 74 F 76 F Note: This graph represents a temperature example, but you can use a pressure or humidity sensor instead. Floating ontrol Diagram Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Main, System, Status, and Setup Screens For the Floating ontrol Application Example That ontrols Temperature 2

19 ode No. LIT Issued June 17, 2014 Head Pressure ontrol - Water Source Heat Pump with Analog Output Limiter ontrol IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. In this example, the 450EN-x ontrol Module controls head pressure on a water source heat pump for both heating and cooling. In this type of application, the head pressure is typically lower when the heat pump is operating in heating mode, and the pressure is higher when operating in cooling mode. AO1 is controlling the head pressure in the heating mode and AO2 is controlling the head pressure in the cooling mode. The analog output limiter function prevents the valve from excessive modulating. Refer to the System 450 Series Modular ontrol Systems with ommunications ontrol Modules (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information psi Pressure Transducer Wire to Sn1 Head Pressure Transducer Install on Liquid Line After ondenser oil Sn1 5V 450EN-x ontrol Module 450SQN-x Expansion Module OUTA1, OUTA2 L1 120/240 VA L2 24 VA lass 2 or SELV Transformer 24V OM VG1241BL+9T4GGA Valve with VA9104-GGA-2 Valve Motor. 0-10VD NSR Direct Acting (Fail in Place) om 1 +24v 2 Input 3 Position 4 Note: A wire lead from OM on the analog output terminal block is not required because all of the common terminals (OM and ) in the module assembly are connected internally. OM on the control module input terminal block is connected to OM on the actuator and serves as the analog output common connection. AO2 OM AO1 FIG:sys450_heat_pump Note: When the analog outputs are connected together, they function as a high signal select output. ontrolling Head Pressure on a Water Source Heat Pump for both Heating and ooling 1

20 Head Pressure ontrol - Water Source Heat Pump with Analog Output Limiter ontrol (ontinued) In this example, the sensor input Sn-1 is set to P500 (with a range from 0 to 500 psi). The Sn-2 and Sn-3 inputs are not used. The sensor outputs AO1 and AO2 on the 450SQN-x Expansion Module are configured as separate control feedback loops, but both use Sn1 as the input sensor and both control the valve actuator motor. OUTA1 is used for heating mode (lower head pressure operating range), and OUTA2 is used for cooling mode (higher head pressure operating range). The update rate and output deadband settings are used to minimize changes to the valve position. These parameters form the analog output limiter OMM USER AdMN Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Refer to the System 450 Series ontrol Modules with ommunications Technical Bulletin (LIT ) for more information. FIG:sys450_ui_screens Example Status and UI Setup Screens for ontrolling Head Pressure on a Water Source Heat Pump for Both Heating and ooling Heating Mode ooling Mode 100% Proportional Band OEP 100% Proportional Band OEP 0% AO2 OSP 0% OSP EP=110 psi SP=195 psi SP=300 psi EP=360 psi FIG:sys450_graphs System Output Diagrams Showing Heating and ooling Modes for the Head Pressure ontrol Example The screen captures on pages 3 and 4 show the web user interface on the 450EN-x ontrol Module. Note: This example is for illustrative purposes only. onditions may vary using different applications. 2

21 Head Pressure ontrol - Water Source Heat Pump with Analog Output Limiter ontrol (ontinued) Sensor onfiguration Screen OUTA-1 onfiguration Screen 3

22 Head Pressure ontrol - Water Source Heat Pump with Analog Output Limiter ontrol (ontinued) Note: Refer to the System 450 Series ontrol Modules with ommunications Technical Bulletin (LIT ) for information on setting up the network parameters for your Ethernet network. OUTA-2 onfiguration Screen 4

23 ode No. LIT Issued June 17, 2014 Heating and ooling ontrol with System Status Indication IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. The 450N-x ontrol Module maintains the temperature with the OUTR1 output connected to the heating equipment and the OUTR2 output connected to the cooling equipment. See the wiring diagram for an illustration of this connection. Use a 450SN-x Expansion Module to activate indicator lights or alarms in the event of out-of-range temperature conditions. When the system is in operation, one of three status lights or audible alarms indicates the operating status. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. Series A99 Sensor Note: Series A99 Sensor of choice shown wired to Sn1 and (common) Sn1 terminals. 450N-x ontrol Module OUTR1, OUTR2 450YNN-1 Power Module 450SN-x Expansion Module OUTR3, OUTR4 L1 LNO1 LN1 L2 LNO2 240 VA 120 VA L1 LNO1 LN1 L2 LNO2 FIG: sys450_lights_wiring_diagram L1 120 VA N Heating Equipment ooling Equipment Low Normal High 24, 120, or 230 VA L1 L2 Temperature Heating and ooling ontrol with System Status Lights Wiring Diagram 1

24 Heating and ooling ontrol with System Status Indication (ontinued) Deadband OUTR4 Relay State OFF High Temperature Alarm ON OUTR3 OFF Low Temperature Alarm ON OUTR2 OUTR1 OFF ON ooling Heating 70 F 71 F 72 F 73 F 74 F 75 F 76 F 77 F 78 F ON OFF FIG:sys450_app_operating_sequence_diagram Temperature Low Temperature Normal Application Operating Sequence Temperature High Sensor Setup SENS Sn-1 F Sn-2 Sn-3 Heating Equipment Sn-1 SENS OFF SNF 1 Sn-1 SENS 1 ooling Equipment Low Temperature Alarm High Temperature Alarm Sn-1 SENS 2 Sn-1 SENS 3 Sn-1 SENS 4 ON 1 76 ON 2 72 ON 3 77 ON 4 OFF 1 75 OFF 2 71 OFF 3 76 OFF 4 ONT 1 0 ONT 2 0 ONT 3 0 ONT 4 OFFT 1 0 OFFT 2 0 OFFT 3 0 OFFT 4 OFF SNF 2 On SNF 3 SNF 4 On Sn-1 SENS 2 Sn-1 SENS 3 Sn-1 SENS 4 FIG: sys450_ui_screens Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Setup Screens for the Heating and ooling ontrol Applications with System Status Indication System Example 2

25 ode No. LIT Issued June 17, 2014 ontrolling Head Pressure on a Two-ircuit ondenser with High Input Signal Select IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. Refer to the System 450 Series Modular ontrol Systems with ommunications ontrol Modules (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. When a cooling system has a two-circuit condenser with a single cooling fan, it is necessary to control the fan based on the condenser circuit with the highest pressure. The 450EN-x ontrol Module is capable of performing this function using the high input signal select feature. You must use identical sensors connected to Sn1 and Sn2 to enable the high input signal select feature (HI-2). Install two identical P499 Electronic Pressure Transducers on the high side of each circuit, and wire them as shown in the wiring diagram. The liquid line on the outlet side of the condensers is the recommended mounting location. The 450EN-x ontrol Module can perform high input signal select using up to three inputs, but this example only uses two inputs. Use the 450SPN-x Expansion Module in the place of the 450SQN-x Expansion Module if you do not need a spare output. P499 Electronic Pressure Transducer Sn2 5V 450EN-x ontrol Module 450YNN-1 Power Module 450SQN-x Expansion Module OUTA1, OUTA2 P499 Electronic Pressure Transducer Sn1 5V Ethernet onnection Ethernet Port 240 VA 120 VA OM AO1 AO2 FIG:sys450_head_pressure L1 L2 L3 VFD ondenser Fan Motor 450EN-x ontrol Module ontrolling Head Pressure on a Multi-ircuit ondenser with a Single Fan Using High Input Signal Select 1

26 ontrolling Head Pressure on a Two-ircuit ondenser with High Input Signal Select (ontinued) The High Input Signal Select 2 (HI-2) functional sensor is selected in this application example. When the sensors connected to Sn1 and Sn2 are the same sensor types, the HI-2 sensor is enabled for selection. When you select the HI-2 sensor for an output, the output is controlled by the sensor (Sn-1 or Sn-2) that is sensing the higher value of the two inputs. FIG:sys450_ui_screens SPARE - OUTA2 is not used in this application Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for a output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Status and UI Setup Screens for the 450EN-x ontrol Module ontrolling Head Pressure on a Multi-ircuit ondenser with a Single Fan Using High Output Signal Select Example The screen captures on pages 2 through 4 show the web user interface on the 450EN-x ontrol Module. Note: The System 450 web UI screens and values shown are for the application example illustrated on the previous page. The screens and values for your application may vary depending the sensors connected and the desired setpoints. System onfiguration Screen 2

27 ontrolling Head Pressure on a Two-ircuit ondenser with High Input Signal Select (ontinued) Sensor onfiguration Screen Note: Refer to the System 450 Series ontrol Modules with ommunications Technical Bulletin (LIT ) for information on setting up the network parameters for your Ethernet network. Output onfiguration Screen for OUTA1 3

28 ode No. LIT Issued June 17, 2014 Small Refrigeration Rack ontroller with Ethernet ommunication IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. Refer to the System 450 Series Modular ontrol Systems with ommunications ontrol Modules (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. System 450 can be used to control a small refrigeration rack with up to three suction groups with a total of ten stages of compression. In this example, the 450EN-x ontrol Module with Ethernet communication controls a small refrigeration rack with two suction groups: a low temperature group and a medium temperature group. The low pressure suction groups has two compressors (omp 1 and omp 2). The medium pressure suction has one compressor (omp 3). This control system also controls the condenser fan motor. Suction Pressure Group 1 (Low Temp) Sensor Sn1 P499Rxx-100 Suction Pressure Group 2 (Medium Temp) Sensor Sn2 Sn1 Sn2 450EN-x ontrol Module 450YNN-1 Power Module 450SN-x 450SN-x Expansion Module Expansion Module OUTR1, OUTR2 OUTR3, OUTR4 P499Rxx-100 ondenser Pressure Sensor Sn3 P499Rxx-105 Sn3 L VA VA L1 LNO1 LN1 L2 LNO2 L1 LNO1 LN1 L2 LNO2 FIG:sys450_small_refrig Neutral omp 1 omp 2 omp 3 ondenser Fan 450EN-x ontrol Module with Ethernet ommunication ontrolling a Small Refrigeration Rack 1

29 Small Refrigeration Rack ontroller with Ethernet ommunication (ontinued) SENS M Press and hold + for 5 seconds to enter the following setup screens menu. P110 Sn-1 P110 Sn-2 P500 Sn OUTR OUTR OUTR OUTR4 Sn-1 SENS 1 Sn-1 SENS 2 Sn-2 SENS 3 Sn-3 SENS On Sn-1 ON 1 OFF 1 OFFd 1 OFFT 1 SNF 1 SENS On Sn-1 ON 2 OFF 2 OFFd 2 OFFT 2 SNF 2 SENS OFF Sn-2 ON 3 OFF 3 OFFd 3 OFFT 3 SNF 3 SENS On Sn-3 ON 4 OFF 4 OFFd 4 OFFT 4 SNF 4 SENS 4 1 Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. FIG:sys450_ui_screens Example Status and UI Setup Screens for the 450EN-x ontrol Module with Ethernet ommunication ontrolling a Small Refrigeration Rack The screen captures on pages 2 and 3 show the web user interface on the 450EN-x ontrol Module. This example is for illustrative purposes only. onditions may vary using different applications. System onfiguration Screen 2

30 Small Refrigeration Rack ontroller with Ethernet ommunication (ontinued) Sensor onfiguration Screen Note: Refer to the System 450 Series ontrol Modules with ommunications Technical Bulletin (LIT ) for information on setting up the network parameters for your Ethernet network. Output onfiguration Screen for OUTR-1 3

31 ode No. LIT Issued June 17, 2014 hilled Water Supply Loop Reset Using an Actuated Mixing Valve IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. Refer to the System 450 Series Modular ontrol Systems with Reset ontrol Modules (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. A chilled water reset application saves energy and provides tight temperature control by raising or lowering the loop water supply temperature based on a proportionate drop in outdoor air temperature. The following diagram illustrates how to set up the chiller, sensors, and mixing valve. Information on the following pages illustrates how to wire the System 450 control modules and how to enter the appropriate values in the Sensor Setup screens. Note: In this example, the chiller water temperature is not being reset. Only the cooling supply water loop temperature is being reset using the mixing valve. Sn-2 Loop Supply Temperature Sensor Sn-2 Sn-1 Master Temperature Sensor (Outdoor Air) Sn-3 hilled Water Supply Sensor Inlet 3-Way Mixing Valve Outlet Loop Water Supply Sn-1 Sn-3 Sensor snaps into TE hiller Inlet Pump FIG:sys450_chiller_sensor_setup Loop Water Return hiller, Sensor, and Mixing Valve Setup 1

32 hilled Water Supply Loop Reset Using an Actuated Mixing Valve (ontinued) The following diagram illustrates how to wire the control modules for a chilled water supply reset application. L1 120/240 VA L2 Loop Mixed Water Supply Sensor Sn-2 in Setup UI hilled Water Supply Sensor Sn-3 in Setup UI 24V Sn3 Sn2 450RBN-x ontrol Module OUTR1 450SPN-x Expansion Module OUTA2 24 VA lass 2 or SELV Transformer 100 VA to Drive Mixing Valve Master Sensor (Outdoor Air) Sn-1 in Setup UI (A99 Temperature Sensor) Sn1 Active/Passive Sensor Jumpers (All jumpers set to Passive) Sn-1 Sn-2 Sn-3 L1 LNO1 LN1 FIG:sys450_module_chiller_setup hiller ontrol ircuit 0 10 VD OM 24 VA 100 VA Mixing Valve Actuator hilled Water Supply Reset Wiring Using a 450RBN-x Reset ontrol Module, a 450SPN-x Expansion Module, and an External Power Supply 2

33 hilled Water Supply Loop Reset Using an Actuated Mixing Valve (ontinued) With the control modules wired, select Sn-3 for OUTR1 to control the chiller compressor. To regulate the supply loop temperature based on a reset setpoint, use a mixing valve, along with the analog output of the 450SPN-x Expansion Module, and select res as the sensor for OUTA2. The diagrams on pages 4 and 5 illustrate how the values for these inputs are calculated. Note: Refer to the System 450 Series Reset ontrol Modules with Real-Time lock and Relay Output Installation Instructions (Part No ) for information on setting the TIME and SHE functions. Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. UI Screens for the hilled Water Supply Reset Wiring Setup Example 3

34 hilled Water Supply Loop Reset Using an Actuated Mixing Valve (ontinued) The following diagram illustrates how the Reset Setpoint (RSP) is determined during occupied mode. The model is based on Outdoor Air Temperature (OAT). In this example, OAT = 85 F and RSP = 50 F. 55 F (MXSP) Sn-2, Loop Supply Water Temp 45 F (MNSP) 50 F (Occupied RSP) FIG:sys450_rsp_occupied RENd 75 F 85 F Sn-1 Outside Air Temp RSTR 95 F alculated Reset Setpoint (RSP) for Loop Supply Water Temperature during Occupied Mode The following diagram illustrates how the RSP is determined during unoccupied mode. The model is also based on OAT, but in this example, OAT = 85 F and RSP = 53 F. 55 F 53 F (Unoccupied RSP) Sn-2 Loop Supply Water Temp 50 F (Occupied RSP) 45 F FIG:sys450_rsp_unoccupied RENd 75 F 85 F Sn-1 Outside Air Temp RSTR 95 F alculated RSP for Loop Supply Water Temperature during Unoccupied Mode 4

35 hilled Water Supply Loop Reset Using an Actuated Mixing Valve (ontinued) When the loop chilled water supply temperature at Sn-2 increases above the RSP (50 F in this example), then the mixing valve, which was recirculating 20% return water, begins to mix in more chilled water. When the loop supply temperature at Sn-2 reaches RSP +2 F (52 F in this example), then the mixing valve circulates 100% chilled water. In this example, the normal control point is between 50 F and 52 F in O mode. OEP=100% Max hiller Water Example with a calculated RSP=50 F: The normal control on this analog output control ramp lies between 50 F and 52 F. During Setback (with Sbk = 3 F), the calculated RSP is increased by 3 F, and this ramp becomes 53 F to 55 F. 2 OUTA OUTPUT% OSP=20% Min hiller Water FIG:sys450_loop_control_temperature O: 50 F UNO: 53 F Pb=2 F Sn-2 Loop Supply Temperature RSP: O: 52 F UNO: 55 F ontrol of hilled Water Supply to the alculated RSP Temperature Using a Mixing Valve 5

36 Hot Water Supply Loop Reset ode No. LIT Issued June 17, 2014 IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. A hot water supply reset application saves energy and provides better space control by preventing overheating or underheating due to changes in outdoor air temperature. The following diagram illustrates how to set up the boiler, sensors, and mixing valve. Information on the following pages illustrates how to wire the control modules and how to enter the appropriate values in the sensor setup screen. Note: In this example, the boiler water temperature is not being reset. Only the heating supply water loop temperature is being reset. Refer to the System 450 Series Modular ontrol Systems with Reset ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. Sn-2 Loop Supply Temperature Sensor Sn-2 Sn-1 Master Temperature Sensor (Outdoor Air) Sn-3 Boiler Reservoir Temperature Sensor Sn-3 3-Way Mixing Valve Inlet Outlet Loop Hot Water Supply Sn-1 Inlet Sensor snaps into TE Boiler Pump Loop Hot Water Return FIG:sys450_boiler_sensor_setup Boiler, Sensor, and Mixing Valve Setup 1

37 Hot Water Supply Loop Reset (ontinued) The following diagram illustrates how to wire the control system for a hot water supply reset application. L1 120/240 VA L2 24 VA lass 2 or SELV Transformer 100 VA to Drive Mixing Valve Hot Water Loop Supply Sensor Sn-2 in Setup UI Boiler Reservoir Sn-3 in Setup UI 24 V Master Sensor (Outdoor Air) Sn-1 in Setup UI (A99 Temperature Sensor S1 S3 S2 Active/Passive Sensor Jumpers (All jumpers set to Passive) 450RN-x ontrol Module OUTR1, OUTR2 Sn-1 Sn-2 Sn-3 L1 LNO1 LN1 L2 LNO2 LN2 450SPN-x Expansion Module OUTA3 Note: The (ommon) terminal on the input terminal and the OM terminal on the analog output are connected internally in the control module. FIG:sys450_module_boiler_setup Boiler irculation Pump L1 120 VA N 0 10 VD OM 24 VA 100 VA Mixing Valve Actuator Hot Water Supply Reset Wiring Using a 450RN-x Reset ontrol Module, a 450SPN-x Expansion Module, and an External Power Supply 2

38 Hot Water Supply Loop Reset (ontinued) With the control system wired, select Sn-3 for OUTR1 to control the boiler temperature. Select Sn-1 for OUTR2 to control the water circulation pump. To control the supply loop temperature based on a reset setpoint, use a mixing valve, along with the analog output of the 450SPN-x Expansion Module. Set up the Reset Setpoint Sensor (res) and select the res sensor to control OUTA3 and the mixing valve actuator. The diagrams on pages 4 and 5 illustrate how the values for the reset setpoint values are calculated. SENS M F Sn-1 F Sn-2 Sn-3 F OFFS 1 OFFS 2 OFFS 3 RSET 110 MNSP 180 MXSP 50 RSTR 0 RENd SdHI SdLO -20 SbK OFF bal OUTR1 Sn OFF SENS 1 ON 1 OFF 1 ONT 1 OFFT 1 SbK 1 SNF 1 Sn-3 SENS 1 OUTR2 OUTR3 TIME SHE Sn SENS 2 ON 2 OFF 2 ONT 2 OFFT 2 SbK 2 res SENS 3 Pb 3 OSET 3 OSP 3 OEP 3 Note: Refer to the System 450 Series Modular ontrol Systems with Reset ontrol Modules Technical Bulletin ( LIT ) or the System 450 Series Reset ontrol Modules with Real-Time lock and Relay Output Installation Instructions ( Part No ) for information on setting the TIME and SHE functions. SNF 2 On On Sn-1 SENS 2 res I- 3 SNF 3 SENS 3 FIG: sys450_sensor_inputs Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Hot Water Supply Loop Reset Setup Example 3

39 Hot Water Supply Loop Reset (ontinued) The following diagram illustrates how the reset setpoint (RSP) is determined during occupied mode. The model is based on outdoor air temperature (OAT). In this example, OAT = 23 F and RSP = 148 F. 180 F (MXSP) Sn-2, Loop Supply Water Temp 148 F (Occupied RSP) 110 F (MNSP) RENd 0 F 23 F Sn-1, Outside Air Temp alculated Reset Setpoint (RSP) for Loop Supply Water Temperature During Occupied Mode The following diagram illustrates how the RSP is determined during unoccupied mode. The model is also based on OAT, but in this example, OAT = 23 F and RSP = 128 F. RSTR 50 F Boiler OFF SdHI 65 F FIG:sys450_rsp_occupied 180 F Sn-2, Loop Supply Water Temp 148 F (Occupied RSP) 128 F (Unoccupied RSP) 110 F RENd 0 F 23 F Sn-1, Outside Air Temp RSTR 50 F FIG:sys450_rsp_unoccupied alculated RSP for Loop Supply Water Temperature During Unoccupied Mode 4

40 Hot Water Supply Loop Reset (ontinued) When the loop hot water supply temperature at Sn-2 falls below the calculated RSP (148 F in this example), then the mixing valve, which was recirculating 20% return water, begins to mix in more boiler water. When the loop supply temperature at Sn-2 reaches RSP -3 F (145 F in this example), then the mixing valve circulates 100% boiler water. In this example, the normal control point is between 145 F and 148 F in O mode. OEP=100% Max Boiler Water Example with a calculated RSP=148 F: The normal control point on this analog output control ramp lies between 145 F and 148 F. During Setback (with Sbk = -20 F), the calculated RSP is reduced by 20 F, and this ramp becomes 125 F to 128 F. Note: In this example, only the loop temperature is being reset. The boiler water temperature is not being reset. OUTA3 OUTPUT% OSP=20% Min Boiler Water O: 145 F UNO: 125 F Pb=-3 F Sn-2 Loop Supply Temp RSP: O: 148 F UNO: 128 F FIG:sys450_loop_control_temperature ontrol of Hot Water Supply to the alculated RSP Temperature Using a Mixing Valve 5

41 ode No. LIT Issued June 17, 2014 Room Temperature, Humidity, and Static Pressure ontrol System with ommunications IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. In this example, the 450EN-x ontrol Module with Ethernet ommunications controls the space temperature (heating and cooling), humidity, and the space static pressure of the application. The static pressure uses a floating control strategy, the heating and cooling employ analog control (0 to 10 VD), and the humidity is digitally controlled (on/off). Because this particular application is for a chicken hatchery, high temperature and humidity levels are required. Refer to the System 450 Series Modular ontrol Systems with ommunications ontrol Modules (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. DPT2650-R25B-AB Differential Air Pressure Sensor HE-67S3-0N00P Humidity and Temperature Sensor 24V Sn1 Sn2 24V Sn3 OM 450EN-x ontrol Module 450SQN-x Expansion Module OUTA1, OUTA2 450SN-x Expansion Module OUTR3, OUTR4 450SBN-x Expansion Module OUTR5 L1 LNO1 LN1 L2 LNO2 L1 LNO1 LN1 AO2 OM AO1 FIG:sys450_c450cen_exmpl L1 120/240 VA L2 24 VA lass 2 or SELV Transformer AO2 LNO1 LN2 Humidifier OUTR AO1 OM 24V 50/60Hz GRY 3 0(2)...10V Y U RED 2 BLK 1 ORN 4 0(2)...10V Static Pressure Damper Actuator OUTR3 and OUTR4 0(2)...10V Proportional 2 =OFF Factory Wiring 2 1 3V 3A 1 4 Heating Actuator OUTA1 24V 50/60Hz GRY 3 0(2)...10V Y U RED 2 BLK 1 ORN 4 0(2)...10V 0(2)...10V Proportional 2 =OFF Factory Wiring 2 1 3V 3A 1 4 ooling Actuator OUTA2 450EN-x ontrol Module ontrolling Room Temperature, Humidity, and Static Pressure 1

42 Room Temperature, Humidity, and Static Pressure ontrol System with ommunications (ontinued) - -- SENS F rh.25 0 M -- - OUTA1 84 SENS 1 SP 1 EP OUTA2 Sn-1 SENS 2 SP 2 P OUTR OUTR OUTR OMM Sn-1 Sn-1 Sn-3 SENS 3 Sn-3 SENS 4 Sn-2 SENS 5 Sn O N 3 Sn ON 4 OFFS OFF OSP 1 OEP 1 I- 1 UP- R 1 bnd 1 SNF OFF Sn-1 OSP 2 OEP 2 I- 2 UP-R 2 bnd 2 SNF OFF OFF 3 ONd 3 OFFd 3 OFFT 3 SNF OFF 4 ONd 4 OFFd 4 ONT 4 OFFT O OFF 5 ONd 5 OFFd 5 ONT 5 OFFT 5 N 5 OFF OFF Sn-3 SENS 3 Sn-3 SENS 4 Sn-2 Sn-1 FIG:sys450_ui_screens USER Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the output setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the output setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output AdMN Status and UI Setup Screens for a Room Temperature, Humidity, and Static Pressure ontrol System with Ethernet ommunications The screen captures on pages 3 and 4 show the web user interface on the 450EN-x ontrol Module. lick the Sensor button to set up sensors (inputs) and the tool bar next to any output to set up the output. You must be logged in to make any changes. Note: This example is for illustrative purposes only. onditions may vary using different applications. 2

43 Room Temperature, Humidity, and Static Pressure ontrol System with ommunications (ontinued) System onfiguration Screen Sensor (Input) onfiguration Screen 3

44 Room Temperature, Humidity, and Static Pressure ontrol System with ommunications (ontinued) Analog Output onfiguration Screen Note: Refer to the System 450 Series ontrol Modules with ommunications Technical Bulletin (LIT ) for information on setting up the network parameters for your Ethernet network. Relay Output onfiguration Screen 4

45 A99 and TE-6000 Temperature Sensor Averaging ode No. LIT Issued June 17, 2014 IMPORTANT: The A99 and TE-6000 temperature sensors are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the A99 and TE-6000 temperature sensors could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the A99 and TE-6000 temperature sensors. Note: Use shielded wire when you install the sensor more than 50 feet (15.25 meters) from the controller. In many applications, a single temperature sensor cannot provide an accurate temperature reading of the entire space. Sensors can be wired in a series/parallel arrangement to average the readings of all sensors in the network. When averaging sensor readings, you must always have the same type of sensor (A99 or TE-6000) and the same number of parallel-connected legs as there are series-connected sensors per leg. See the following diagrams for an illustration of how averaging can be accomplished using four or nine sensors. Note: The A99B Series Temperature Sensors and the TE-6000 Series Temperature are not compatible, and the sensors in the averaging arrays must be all A99B sensors or all TE-6000 sensors. IMPORTANT: When connecting an A99 or a TE-6000 temperature sensor with shielded cable to an electronic controller, connect the cable shield drain lead to a low-voltage common terminal on the input sensor terminal block. Do not connect the shield at any other point along the cable. Isolate and insulate the shield drain at the sensor end of the cable. onnecting a cable shield at more than one point can enable transient currents to flow through the sensor cable shield, which can cause erratic control operation. System 450 uses the A99 Series PT Silicon Temperature Sensors or TE-6000 Series 1000 Ohm Nickel Temperature Sensors. You can apply sensor averaging to System 450 applications. Refer to the A99B Series Temperature Sensors Product Technical Bulletin (LIT ) or the TE-6000 Series Temperature Sensing Elements Product Bulletin (LIT ) for sensor information. Four and Nine Temperature Sensors Wired in Series/Parallel Arrangement Schematics 1

46 A99 and TE-6000 Temperature Sensor Averaging (ontinued) able Shield Splice Shield at all other onnection Points Sn1 Sn1 onnect able Shield to at ontrol Module Sensor Terminal Block Note: One of the two leads from the Series/Parallel sensor array is connected to Sn1, Sn2, or Sn3, and the other lead is connected to any common ( ) terminal. The cable shield, if used, is connected to any common () terminal. All of the common () terminals are connected together internally in the control module. Any System 450 Standard ontrol Module Isolate and Tape Shield Isolate and Tape Shield Wiring of A99 Series or TE Ohm Nickel Series Sensors for Temperature Averaging Using a Shielded able FIG:sys450_shielded_cable 2

47 ode No. LIT Issued June 17, 2014 Solar Heating ontrol Applications with Differential Temperature ontrol IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. In this solar heating example, a solar panel circulating pump is controlled by differential temperature (dift). When the temperature of the solar panel is 10 F above the temperature of the water in the storage tank, the solar panel circulating pump begins to run. When the differential temperature (don 1 ) is met, the normally open contacts of relay output 1 close, energizing 2 and starting the circulating pump. The pump cycles off when the differential temperature (doff 1 ) falls to 5 F. The room temperature circulating pump is controlled by the room temperature sensor (Sn-3) and the storage tank sensor (Sn-2). When heating is required, the normally open contact on Relay Output 2 (OUTR2) closes, energizing 1 and starting the room temperature circulating pump. Relay Output 3 (OUTR3) locks out the room temperature circulating pump if the water in the tank drops below 70 F, allowing the pump to restart when the water temperature rises to 75 F or higher. TE High Temperature Solar Panel Sensor Sn-1 Solar ollector Sn1 450N-x ontrol Module OUTR1, OUTR2 450YNN-1 Power Module 450SBN-x Expansion Module OUTR3 TE Series Temperature Sensor Sn3 Sn2 L1 LNO1 LN1 L2 LNO VA VA L1 LNO1 LN1 FIG:sys450_solar_diffcontrol_diagram L1 A99B Series Room Sensor Sn-3 L2 2 1 Room Heating Loop TE Storage Tank Sensor Sn-2 Storage Tank 1 Room Temperature irculating Pump ontrolled by Room Temperature (Sn-3) 2 Solar Panel irculating Pump ontrolled by Differential Temperature (Sn-d) Note: If you require a wall mount sensor for the room sensor, order a TE-68NT-0N00S Wall Mount Sensor with a nickel sensing element. If a TE-68NT-0N00S sensor is used, change the Sn-3 value to HI-F. System 450 Solar Heating ontrol Application with Differential Temperature ontrol Example 1

48 Solar Heating ontrol Applications with Differential Temperature ontrol (ontinued) SENS M HI F HI F Sn-1 Sn-2 Sn-3 F 0 OFFS OFFS 2 OFFS 3 OUTR1 Sn-d SENS 1 don doff 1 0 ONT 1 0 OFFT 1 OFF SNF 2 Sn-d SENS 1 OUTR2 Sn-3 SENS ON 2 OFF 2 OUTR3 Sn SENS 3 ON 3 0 ONT 2 0 OFFT 2 OFF SNF 2 OFF 0 0 OFF 2 ONT 3 OFFT 3 SNF 3 Sn-3 SENS 2 Sn-2 SENS 3 FIG:sys450_ui_screens Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the output setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the output setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. System 450 UI Status and Setup Screens for Solar Heating ontrol Applications 2

49 ode No. LIT Issued June 17, 2014 Two-Speed Fan Motor ontrol Using Any ompatible Pressure, Humidity, or Temperature Sensor IMPORTANT: Use this System 450 modular control assembly only as an operating control. Where failure or malfunction of the System 450 modular control assembly could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 modular control assembly. Refer to the System 450 Series Modular ontrol Systems with Standard ontrol Modules Technical Bulletin (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. You can wire a 450N-x ontrol Module and a 450YNN-1 Power Module, along with a pressure, humidity, or temperature sensor, to control a two-speed fan motor. You can attach 450Sxx Series Expansion Modules and up to two additional sensors (pressure, humidity, or temperature) to create additional control loops, if desired. Note: You can control this application based on temperature, pressure, or humidity. This example depicts a temperature application. Refer to the technical bulletin for more information on selecting and setting up System 450 compatible sensors for your application. Series A99 Sensor Note: Series A99 Sensor of choice shown wired to Sn1 and (common) Sn1 terminals. See Sensor Note 450N-x ontrol Module OUTR1, OUTR2 450YNN-1 Power Module L1 LNO1 LN1 L2 LNO2 240 VA 120 VA FIG:sys450_twospeed_fan_motor_control L1 120 VA N Low Speed High Speed Wiring a 450N-x ontrol Module, a 450YNN-1 Power Module, and a Temperature Sensor to ontrol a Two-Speed Fan Motor 1

50 Two-Speed Fan Motor ontrol Using Any ompatible Pressure, Humidity, or Temperature Sensor (ontinued) FIG:sys450_ui_screens Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the Output Setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the Output Setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. Setup and UI Screens for the 450N-x ontrol Module, a 450YNN-1 Power Module, and a Temperature Sensor to ontrol a Two-Speed Fan Motor Example 2

51 ode No. LIT Issued June 17, 2014 Two-Stage ooling Application with Remote ommunications Featuring On Delay Time and Analog Output Limiter ontrol IMPORTANT: Use the System 450 control module only as an operating control. Where failure or malfunction of the System 450 control module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the System 450 control module. Refer to the System 450 Series Modular ontrol Systems with ommunications ontrol Modules (LIT ), the System 450 Series Modular ontrols Product Bulletin (LIT ), and the installation instructions for product specifications, detailed installation procedures, and important product safety information. The On Delay and Off Delay Timers (ONd and OFFd) delay the control response before it acts on the sensed value. You can use the delay timers to prevent the control from responding to momentary sensor value changes. ONd and OFFd, in addition to the Minimum On Timer and Minimum Off Timer (ONT and OFFT), can also be used to set up anti-short cycling control for your equipment or to stagger the start of staged equipment. In this example, a 450EN-x ontrol Module controls a two-stage cooling system that includes head pressure control and a high space temperature alarm. The space sensor senses the temperature in the refrigerated space. When the temperature rises, the liquid-line solenoid valve (connected to the OUTR1 output) is energized. As the suction pressure rises, the low-pressure suction transducer senses the rise in pressure, and the first compressor (connected to the OUTR2 output) starts after the on delay time expires. If the suction pressure continues to rise, the second compressor (connected to the OUTR3 output) starts, again after the on delay time expires. The on delay times prevent the compressors from responding immediately to changes in the sensor reading and prevent the compressors from short-cycling. When the head pressure rises, the high-pressure discharge pressure sensor (Sn-3) senses the rise. This causes the analog output signal OUTA5, which controls the variable-frequency drive (VFD), to increase, which starts the condenser fan at low speed. If the head pressure continues to rise, the control increases the signal, and the condenser fan speed is increased to meet the demand. The output limiter features (UPR and bnd) prevent the VFD from hunting (over-actuating). If the temperature of the refrigerated space exceeds the high temperature alarm value (of 5 F in this example) for a period of time equal to or greater than the time delay, the remote alarm activates. 450EN-x ontrol Module 450YNN-1 Power Module 450SN-x Expansion Module OUTR1, OUTR2 450SN-x Expansion Module OUTR3, OUTR4 450SPN-x Expansion Module OUTA5 Suction Pressure Transducer ondenser Pressure Transducer Space Temperature Sensor VFD Liquid Line Solenoid ompressor 1 ompressor 2 Alarm Wiring Diagram for a Two-Stage ooling Application with Remote ommunications Example R1 R2 R3 R4 1

52 Two-Stage ooling Application with Remote ommunications Featuring On Delay Time and Analog Output Limiter ontrol (ontinued) OMM FIG:sys450_ui_screens USER AdMN Note: The Sensor Selection screens (in gray) only appear when you first set up each output. After you have selected a sensor for an output, the Sensor Selection screen only appears at the end of the output setup screens. If you need to select a different sensor for an output, navigate to the Sensor Edit screen at the end of the output setup screens, change the selected sensor, press the right arrow key, and enter the new values for the output. UI Screens for the Two-Stage ooling Application with Remote ommunications Example The screen captures on pages 3 and 4 show the web user interface on the 450EN-x ontrol Module. Note: This example is for illustrative purposes only. onditions may vary depending on the application. 2

53 Two-Stage ooling Application with Remote ommunications Featuring On Delay Time and Analog Output Limiter ontrol (ontinued) System onfiguration Screen Input (Sensor) onfiguration Screen 3

ECON-ZIP-DETF; ZIP PACK

ECON-ZIP-DETF; ZIP PACK 71765-00001_A INSTUTION MANUAL EON-ZIP-DETF; ZIP PAK EON-ZIP-DETF; ZIP PAK Differential Enthalpy with DV apability and TF Spring eturn Actuator ontains: Application This kit offers all the components to

More information

System 350 P352AB Electronic Pressure Control Series

System 350 P352AB Electronic Pressure Control Series System 350 P352AB Electronic Pressure Control Series System 350 Product Guide 930 Basic Controls Section Product/Technical Bulletin P352AB Issue Date 0200 The P352AB controls are On/Off electronic pressure

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

ICL Three Pump Controller

ICL Three Pump Controller ICL Three Pump Controller Pump Operation The number of pumps that the program controls can be selected by enabling only the ones that are currently installed and in service. The enable/disable setting

More information

Vission 20/20 micro-controller. Operation and service manual

Vission 20/20 micro-controller. Operation and service manual Vission 20/20 micro-controller Operation and service manual Section Title Table of Contents Section Number How To Use This Manual...TOC-8 Section 1 Operational Flow Charts Requirements to Start Compressor...1-1

More information

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER

TECHNICAL PAPER 1002 FT. WORTH, TEXAS REPORT X ORDER I. REFERENCE: 1 30 [1] Snow Engineering Co. Drawing 80504 Sheet 21, Hydraulic Schematic [2] Snow Engineering Co. Drawing 60445, Sheet 21 Control Logic Flow Chart [3] Snow Engineering Co. Drawing 80577,

More information

System 350 S350P Proportional Plus Integral Temperature Stage Module

System 350 S350P Proportional Plus Integral Temperature Stage Module FANs 930, 930.5 Add-On Modules Section Product/Technical Bulletin S350P Issue Date 0997 System 350 S350P Proportional Plus Integral Temperature Stage Module The S350P is used in conjunction with the A350

More information

Remote Temperature Controllers. Quick Selection Guide

Remote Temperature Controllers. Quick Selection Guide Remote Temperature Controllers Quick Selection Guide A Complete Selection For A Wide Range Of Applications Electronic Standalone Controllers T775 Provide on/off, modulating, or reset control in applications

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

MicroTech II Applied Rooftop Unit Controller

MicroTech II Applied Rooftop Unit Controller Installation and Maintenance IM-696-2 Group: Applied Systems Part Number: IM696 Date: March 2004 MicroTech II Applied Rooftop Unit Controller Used with McQuay models: RPS, RFS, RCS, RDT, RPR, RFR, RPE,

More information

BAPI-Stat 3 Room Sensor

BAPI-Stat 3 Room Sensor Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read

More information

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series) Overview The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as a combination temperature and humidity sensor with optional LCD display, temperature setpoint adjustment and occupant

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Vission 20/20 micro-controller. Operation and service manual Version 2.6

Vission 20/20 micro-controller. Operation and service manual Version 2.6 Vission 20/20 micro-controller Operation and service manual Version 2.6 Important Message READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR. The following instructions have been prepared to assist in operation

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

Dual Duct Variable Air Volume Terminal (Model TDS)

Dual Duct Variable Air Volume Terminal (Model TDS) Product Bulletin Issue Date June 21st, 2005 Dual Duct Variable Air Volume Terminal (Model TDS) Model TDS terminals provide Variable Air Volume (VAV) control beyond the typical dual duct box. They are specifically

More information

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication

More information

ZIP Economizer Fault Detection and Diagnostics (FDD) Table

ZIP Economizer Fault Detection and Diagnostics (FDD) Table Fault Detection and Diagnostics (FDD) Table Fault Detection Problem Diagnostic ction (in addition to alarm stored / transmitted) Potential Cause C Fault Code OT sensor predetermined range O damper returns

More information

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide 32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES

More information

LF Series At A Glance

LF Series At A Glance LF Series Spring Return Direct Coupled Actuator Minimum 35 in-lb Torque For damper areas up to 8 sq-ft* Applications Cost effective quality and performance for a range of applications including: Classroom

More information

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additional options include pushbutton override, fan

More information

MicroTech II Applied Rooftop Unit Controller

MicroTech II Applied Rooftop Unit Controller ( Installation and Maintenance IM-696 Group: Applied Systems Part Number: IM696 Date: April 21 MicroTech II Applied Rooftop Unit Controller Used with McQuay models: RPS, RFS, RCS, RDT, RPR, RFR, RDS, RAR

More information

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller

Liebert CSU3000 DISCONTINUED PRODUCT. CSI Mainframe Cooling Systems. CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller DISCONTINUED PRODUCT CSI 15621 - Mainframe Cooling Systems 1.1 SUMMARY Liebert CSU3000 CT(Three Module) Model 20, 30 & 37 ton Mainframe Chiller GUIDE SPECIFICATIONS 1.0 GENERAL These specifications describe

More information

BAS Construction Checklist

BAS Construction Checklist BAS Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist items

More information

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350R Electronic Temperature Reset Control (with Relay) FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date April 8, 2014 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is

More information

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE #

Distributed By: M&M Control Service, Inc PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Switches Selector Switches SW 786 155-118P25 G-3 Positioning Switch SW 141 155-117P25 G-5 Enthalpy Control Switch EE 141 155-054P25 G-7 Static Pressure

More information

Output Current Input Current Over Voltage. VDC VDC ma ma(typ.) ma(typ.) VDC μf % MKZI10-24S

Output Current Input Current Over Voltage. VDC VDC ma ma(typ.) ma(typ.) VDC μf % MKZI10-24S Doc. E-92 MKZI1 SERIES D/D ONVERTER 1W, Reinforced Insulation, Railway ertified FEATURES Industrial Standard 2" 1" Package Ultra-wide Input Range 9-36VD, 18-75VD, -1VD I/O Isolation 3VA with Reinforced

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide Factory Packaged Controls OE377-26-00058 (AAON Part No. V12090) MODGAS-X Controller Table of Contents GENERAL INFORMATION... 3 Overview...3 Features...3 INSTALLATION & WIRING... 4 Supply Air Temperature

More information

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to

More information

Control Panel. Operation and Service Manual

Control Panel. Operation and Service Manual Control Panel Operation and Service Manual 1 2 Important Note Before applying power to the control panel, all wiring to the panel should be per NEC. Specifically check for proper voltage and that the neutral

More information

Modulating Furnace Information. Warning on Meter Setting - Read First!

Modulating Furnace Information. Warning on Meter Setting - Read First! Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56

More information

Electronic Controls Proportional Valve Control Power Plugs

Electronic Controls Proportional Valve Control Power Plugs Electronic ontrols Proportional Valve ontrol Power Plugs EHH-AMP-70-D/J/K-* Series For use with valve types: EPV**-D-* EFV-**-0DE* ERV/**-D-* EPRV**-D-* Application Primary applications are in the control

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: 107065-01, Revision 1 March 03, 2017 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

VG7000 Series Bronze Control Valves

VG7000 Series Bronze Control Valves VG7000 Series Bronze Control Valves Product Bulletin VG7000 Series Code No. LIT-977140 Issued June 16, 2008 Supersedes March 2001 VG7000 Series Bronze Control Valves are designed primarily to regulate

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

Application Engineering Europe

Application Engineering Europe Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for

More information

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL Temperature Controller TC5+2V4SA Plus USER'S MANUAL NOTICE Every effort has been made to ensure that this manual is complete, accurate and up-to-date. The information contained in it is however subject

More information

VA-4233-GGx Series Electric Valve Actuators

VA-4233-GGx Series Electric Valve Actuators Installation Instructions Issue Date August 11, 2003 VA-4233-GGx Series Electric Valve Actuators Installation Refer to Figures 2 through 4 for proper actuator orientation before attempting to make the

More information

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS

CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS Date of last update: Apr-15 Ref: D7.8.4/0112-0415/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors...

More information

Continental Hydraulics Installation Manual CEM-AA-A

Continental Hydraulics Installation Manual CEM-AA-A Continental Hydraulics Installation Manual CEM-AA-A Description: This power amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to proportional

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS PCT plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS Ver. DESCRIPTION The PCT plus is a pressure controller for refrigeration plants that require control in their suction and discharge stages. With

More information

- Wiring Brochure Universal Reset Module 422

- Wiring Brochure Universal Reset Module 422 - Wiring Brochure Universal Reset Module 422 W 422 03/09 1 Information Brochure hoose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

MANUAL INSTALLATION. Tracking Controller. TC Series. v100 Issue Date: 02/25/ Price Industries Limited. All rights reserved. Firmware: 1.3.

MANUAL INSTALLATION. Tracking Controller. TC Series. v100 Issue Date: 02/25/ Price Industries Limited. All rights reserved. Firmware: 1.3. MANUAL INSTALLATION Tracking Controller TC Series v100 Issue Date: 02/25/16 2016 Price Industries Limited. All rights reserved. Firmware: 1.3.0 TABLE OF CONTENTS Product Overview General...1 Tracking Controller

More information

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control SP-32, SP-32D SP-33, SP-33D SP-34, SP-34D Single Stage Temperature Control Description The SP-3x and SP-3xD series of controls are single stage, general purpose, temperature controls with wide application

More information

TC62D Installation Instructions

TC62D Installation Instructions TC62D Installation Instructions January 2007 This TC62D has a return water low temperature limit option. Using the low limit precludes using a room sensor because both sensors plug into the same port.

More information

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital

More information

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/ GRUNDFOS INSTRUCTIONS Control HVAC Installation and operating instructions Other languages net.grundfos.com/qr/i/98800750 English (GB) English (GB) Installation and operating instructions Original installation

More information

MATRIX LLC LEVEL CONTROL PANEL

MATRIX LLC LEVEL CONTROL PANEL MATRIX LLC LEVEL CONTROL PANEL Installation Operation Maintenance Manual 1-26-09 REV-0.3 1 INDEX Introduction. 3 Product Configurations..... 4 I/O Descriptions. 8 Operation o Intercooler, Accumulator,

More information

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n 107065-01 Revision 0 May 20, 2016 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

YCCS TE-6800 Series Temperature Sensors

YCCS TE-6800 Series Temperature Sensors YCCS TE-6800 Series Temperature Sensors TE-68xx-xNN0S Installation Instructions 85-YIM-B-070 Applications The York Commercial Comfort System (YCCS) TE-68xx-xNN0S Series Temperature Sensors provide temperature

More information

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN February 2004 CNT-SVN02B-EN Tracer AH541

More information

DESCRIPTION AND OPERATION

DESCRIPTION AND OPERATION Page 1 of 10 DESCRIPTION AND OPERATION AIR DELIVERY DESCRIPTION AND OPERATION The air delivery description and operation is divided into five areas: HVAC Control Components Air Speed Air Delivery Recirculation

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

SAX Electronic Valve Actuator

SAX Electronic Valve Actuator SAX Electronic Valve Actuator Non-spring Return, 24 Vac, Proportional Control Technical Instructions Document No. 155-506 Description The SAX Non-spring Return (NSR), Electronic Valve Actuator requires

More information

MAGPOWR Spyder-Plus-S1 Tension Control

MAGPOWR Spyder-Plus-S1 Tension Control MAGPOWR TENSION CONTROL MAGPOWR Spyder-Plus-S1 Tension Control Instruction Manual Figure 1 EN MI 850A351 1 A COPYRIGHT All of the information herein is the exclusive proprietary property of Maxcess International,

More information

- Wiring Brochure Universal Reset Module 422e

- Wiring Brochure Universal Reset Module 422e - Wiring Brochure Universal Reset Module 422e W 422e 01/08 1 Information Brochure hoose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in

More information

EMERSON CLIMATE TECHNOLOGIES-EX

EMERSON CLIMATE TECHNOLOGIES-EX EMERSON CLIMATE TECHNOLOGIES-EX Valves & Controls EX4-EX8 Control Valve The EX4-EX8 are stepper motor driven valves that are optimized for the control of liquid or gaseous mass flow in refrigeration systems.

More information

BOOK 4 ELECTRICAL RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 4:

BOOK 4 ELECTRICAL RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 4: 0 Helgesen Drive, Madison, WI, 0.., 00.., Fax: 0.. support@renewaire.com www.renewaire.com RDXRT INSTALLATION AND OPERATION MANUAL BOOK ELETRIAL ABOUT BOOK : This book covers the basic electrical installation

More information

Product Instructions. Mixing Station. Features. Specifications. Materials

Product Instructions. Mixing Station. Features. Specifications. Materials Mixing Station The Viega Mixing Station provides supply water temperature modulation when connected to a variety of heat sources such as conventional or condensing boilers, water heaters, or geothermal

More information

R1000 Series Relays. Features and Benefits. Enclosed Relay Contacts Delivers maximum durability and extends life; inhibits corrosion and dust build-up

R1000 Series Relays. Features and Benefits. Enclosed Relay Contacts Delivers maximum durability and extends life; inhibits corrosion and dust build-up Master atalog 125 s and ontactors Section R Product Bulletin R1000 Issue Date 0493 R1000 Series s The R1000 Series s switch line voltage devices from low voltage controllers. Plug-in DPDT relays and snap-in

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only GENERAL These split-system condensing units are designed to

More information

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2100/2200 FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER MODEL 2100: Constant face velocity, variable volume MODEL 2200: Constant face velocity, variable volume

More information

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules Technical Specification Sheet Document No. 149-855 November 04, 2015 BACnet Lab and Pressurized Room Controllers with Off-board Air Modules NOTE: The 570-8xxPA BACnet laboratory controllers have new 67xx

More information

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Engineering Bulletin IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51) Issued By: Clarksville Marketing and Sales Support Order No. UN-PRB001-EN

More information

MF /MS Series

MF /MS Series MF41-6153/MS41-6153 Series 24 Vac, Three-position/Modulating Non-spring Return Rotary Electronic Damper SmartX Actuators General Instructions Description The direct-coupled, 24 Vac, non-spring return electronic

More information

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST

More information

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

POWERS CONTROL RC 195 Multiple Input Receiver- Controller POWERS CONTROL RC 195 Multiple Input Receiver- Controller Document No. 155-036P25 RC 195-1 Description Features Application The RC 195 Multiple lnput Receiver-Controller is a pneumatic instrument which

More information

Digital Room Thermostats with Touch Screen LCD

Digital Room Thermostats with Touch Screen LCD TC40 Touch Series Digital Room Thermostats with Touch Screen LCD Revision Date February 22, 2013 Features Wall-mount Display Control to match any decor Extra large easy-to-read Liquid Crystal Display (LCD),

More information

MINI-MASTERZONE ZONING SYSTEM. MMP2 For Plug-In Damper Motors. Installation and Operating Instructions. 2 Zones. Controlling Your Comfort Room by Room

MINI-MASTERZONE ZONING SYSTEM. MMP2 For Plug-In Damper Motors. Installation and Operating Instructions. 2 Zones. Controlling Your Comfort Room by Room MINI-MASTEZONE ZONING SYSTEM MMP2 For Plug-In Damper Motors 2 Zones Installation and Operating Instructions ontrolling Your omfort oom by oom MINI-MASTEZONE ZONING SYSTEM MMP2 Features System Mode Indicator

More information

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO: YMC 2 - MOD A STARTUP CHECKLIST Supersedes 160.78-CL2 (512) Form 160.78-CL2 (615) STARTUP CHECKLIST CUSTOMER: JOB NAME: ADDRESS: LOCATION: PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information

Figure 1: WPR2 Dimensions and Hardware

Figure 1: WPR2 Dimensions and Hardware Installation and Operation Instructions WPR2 Series (Max. Line Pressure < 300 PSI) Wet to Wet Differential Pressure Ø0.200" 2.60" 4.47" 5.47" 5.28" 3.00" Precautions Figure 1: WPR2 Dimensions and Hardware

More information

LF24-ECON-R03(-R10) US Operation, Installation and Wiring

LF24-ECON-R03(-R10) US Operation, Installation and Wiring LF24-ECON-R03(-R0) US Operation, Installation and Wiring Operation LF24-ECON-R03(-R0) US The LF24-ECON-R03(-R0) US provides a direct coupling solution for RoofTop Unit(RTU) economizer dampers. Control

More information

Appendix A: Inputs, Outputs, and Parameters

Appendix A: Inputs, Outputs, and Parameters Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Appendix A: Inputs, Outputs, and Parameters Introduction This appendix describes the inputs, outputs, and parameters used with the Metasys Zoning

More information

M9216 Series Electric Spring Return Actuators

M9216 Series Electric Spring Return Actuators *34636461G* 34-636-461, Rev. J Installation Instructions M9216 Issue Date October 217 M9216 Series Electric Spring Return Actuators Installation IMPORTANT: The M9216 Series actuator is intended to control

More information

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE CLEAN MODE Temperature Controller User s manual CURRENT CONDITIONS ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME / DATE SETTINGS SET POINT / CURVE MINIMUM

More information

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas Installation Manual IOM-MBC-00 08-30-04 Mixing Box Control Systems Installation,, and Maintenance Manual Contents Page Introduction...1 General...1 Safety...1 Inspection...1 Mixing Box Control Systems...2

More information

MS Application. Features. Proportional Valve Actuator General Instructions

MS Application. Features. Proportional Valve Actuator General Instructions Proportional Valve Actuator Application The Proportional Valve Actuator is a non-spring return actuator used with proportional to 10 Vdc or 4 to 0 ma controllers and standard 1/" to 1-1/4" two-way and

More information

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No. Application Guide 575-012 Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1 Carlyle Controller Part No. 2BSB000928 1 General Description The PCM is part of Paragon Compressor

More information

RSMD Technical Guide

RSMD Technical Guide RSMD Technical Guide TABLE OF CONTENTS OVERVIEW... 4 Features and Applications... 4 Module Dimensions... 5 INSTALLATION & WIRING... 6 Input Wiring... 6 Suction Pressure Sensor... 6 Head Pressure Sensor...

More information

NSM. R134a HIGH EFFICIENCY ALSO AT PARTIAL LOADS ENERGY SAVING MICRO-CHANNEL COIL QUICK AND EASY INSTALLATION NIGHT MODE.

NSM. R134a HIGH EFFICIENCY ALSO AT PARTIAL LOADS ENERGY SAVING MICRO-CHANNEL COIL QUICK AND EASY INSTALLATION NIGHT MODE. NSM ir/water chillers for outdoor installation with free cooling glycol free Screw compressors, shell and tube heat exchangers and axial fans from 306 2028kW 1402/9603 glycol free R134a HIGH EFFIIENY LSO

More information

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor Product Identification and Overview Power and Communication on Just Two Wires Available with Temperature Sensing, Temperature Setpoint, Optional Occupant Override, Optional Display and Optional %RH Sensing

More information

Co m f o r t Li n k N A V I G A T O R F F

Co m f o r t Li n k N A V I G A T O R F F TIME EWT LWT SETP Co m f o r t Li n k N A V I G A T O R 1 2.58 5 4. 6 F 4 4. 1 F 4 4. 0 F M O D E Alarm Status Run Status Service Test Temperatures Pressures Setpoints Inputs Outputs Configuration Time

More information

Variable speed drives

Variable speed drives 5 192 Variable speed drives SED2 Variable speed drives for speed control of three-phase a.c. motors actuating fans or pumps. Range: 0.75 kw to 90 kw for IP20/21 version, 1.1 kw to 90 kw for IP54 version.

More information

Discharge Air Control

Discharge Air Control Issue Date June 17, 2002 APPLICATION NOTE Discharge Air Control Discharge Air Control...2 Introduction... 2 Key Concepts... 3 Discharge Air Control Overview... 3 Design Considerations... 6 2002 Johnson

More information

Laboratory Room Controller

Laboratory Room Controller Technical Specification Sheet Rev. 5, April, 2001 Laboratory Room Controller Description The APOGEE Automation System Laboratory Room Controller (LRC) provides Direct Control (DDC) for laboratory space

More information

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis.

CENTRIFUGAL CHILLER. Lubrication System Pull oil sample for spectroscopic analysis. CENTRIFUGAL CHILLER Annual Inspection Refrigerant Circuit Check and record refrigerant level Inspect for leak results Calculate refrigerant lass and report to the customer. Repair minor leaks as required

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER UHC 300 22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER OVERVIEW The HVAC building automation controls market requires a DDC controller that provides scalable, consolidated control in a fully programmable,

More information

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi 1 TABLE OF CONTENTS TABLE OF CONTENTS... 2 IMPORTANT NOTE... 3 FAULT FINDING AND DIAGNOSTICS... 3 ABBREVIATIONS... 3 PCB S... 4 OUTDOOR MAIN PCB... 4 INDOOR PCB...

More information

Multi-Path RTU-TYPE 9 (RTU-1) CES-MPU-025-RE-VAV9

Multi-Path RTU-TYPE 9 (RTU-1) CES-MPU-025-RE-VAV9 ALDI # CITY, STATE SUPERMARKET MultiPath RTUTYPE 9 (RTU1) CESMPU025REVAV9 Date: December 1, 2014 2013 Consolidated Energy Solutions, Inc. UNIT FEATURES CES TYPE VAV9 Unit features include: 25 ton MultiPath

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to

More information

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions Product Identification Fig 1. BAPI-Com Communication Output Module Fig 2. BAPI-Com Room Sensor, BA/BS4SCOM Operations Overview The BAPI-Com sensor is designed to be used in retrofit applications on just

More information

BSPDDRIVE ITT. Goulds Pumps. Aquavar SPD (Single Pump Drive) Simplex Variable Speed Pump Controller

BSPDDRIVE ITT. Goulds Pumps. Aquavar SPD (Single Pump Drive) Simplex Variable Speed Pump Controller ITT BSPDDRIVE Goulds Pumps Aquavar SPD (Single Pump Drive) C U L US Do you want to Simplify your Commercial Pumping System? Goulds Pumps SPD variable speed, constant pressure pump controller is designed

More information