gimagination at work GE Consumer Industrial Electrical Distribution Operation & Maintenance Manuals
|
|
- Lee Morrison
- 5 years ago
- Views:
Transcription
1 GE Consumer Industrial Electrical Distribution Operation & Maintenance Manuals Project Name: Sludge Dewatering and Odor Control at Plant 1 Project No. P1-101 Specification: Revision: 0 Medium Voltage Switchgear 02/01/2016 Volume 3 of 3 Equipment Tag(s): Shop Order SWITCHGEAR SWGR-Q-A ( 15LSWGR901 ) SWITCHGEAR SWGR-Q-B ( 15LSWGR902 ) Manufacturer: General Electric / Powell BPD Address: Kurland Drive City, State, Zip Houston, TX Website: GE Base Requisition #: 480-Z7612 Local Service Representative: GE Energ- Engineering Services Address: 3601 East LaPalma Ave. City, State, Zip Anaheim, CA Phone: 888-GE4-SERV or Website: gimagination at work
2 Sludge Dewatering and Odor Control at Plant 1 Specification: Project No. P1-101 Medium Voltage Switchgear Table of Contents Operation and Maintenance Manuals Medium Voltage Switchgear Vol. Tab Description Reference 1 * Equipment List: Medium Voltage Switchgear 480-Z LIST 1 1 Device Data Sheets: Key Components ** 1 2 Supplemental Data: Approved Submittal Documents ** 1 3 Instructions: Installation, Operation & Maintenance Maintenance: Maintenance Summary Form Operation: Supplemental Operational Information 480-Z MSF 480-Z SOI 1 3A Instruction Manuals: Medium Voltage Switchgear Instructions: Power Vac Metal -Clad Switchgear GEK Rev G Instruction Manual: Power Vac Vacuum Circuit Breakers 01.4IB.66000A Rev 11/2012 Users Guide: GE Lift Truck GEK Rev B Instructions: Test Cabinet for Power Vac Vacuum Circuit Breakers GEK Rev B Instruction Manual: GE Power Vac Manual Ground & Test Device GEK Rev B 2 3B Instruction Manuals: Communication Devices Instructions: : MultiLink ML2400 Ethernet Communications Switch GEK Rev M Instruction Manual:: MultiNet Serial to Ethernet Converter A2 Rev 0 2 3C Instruction Manuals: Protection Relays Instructions: : 350 Feeder Protection System Instruction Manual:: Undervoltage Relay BE D Spare Parts / Accessory Information Recommended Spare Parts Special Tools / Accessories GEK Rev S Rev 480-Z RSP 480-Z ACC 2 3E Warranty Information Manufacturer Terms ES-104 Special Terms Statements ** 3 4 As Built : Drawings 3 4A SWITCHGEAR SWGR-Q-A ( 15LSWGR901 ) Shop Order: B SWITCHGEAR SWGR-Q-B ( 15LSWGR902 ) Shop Order: C 12.47KV SERVICE CENTER ADDITIONS Shop Order: D Test Reports ** 3 4E Appendix : Field Settings ** Operation / Maintenance Page 1 of 1
3 Sludge Dewatering and Odor Control at Plant 1 Specification: Project No. P1-101 Medium Voltage Switchgear DWG-AB As Built Requisition: 480-Z MV Shop Order: SWITCHGEAR SWGR-Q-A ( 15LSWGR901 ) Summary, Ratings, Device & Nameplate Information Summary Set: Summary of Equipment Lineup Sheet 1 Breaker Information B-Sheet Set Device Summary (Bill of Material) D-Sheet Set Nameplate Schedules E -Sheet Set Section Rating Details EE1 List of Lineup Options L-Sheet Set Special Requirements S-Sheet Set Technical Submittal: Drawing Set: Mechanical Sheets: 1 thru 6 Elevation, Layout & Single Line Side Views Panel Layouts per Section: Electrical Sheets: 7 thru 18 Schematics Control Circuits Power Elementaries Wiring Diagrams Sheets: 19 thru FNL Connection Details - Point to Point
4 Sludge Dewatering and Odor Control at Plant 1 Specification: Project No. P1-101 Medium Voltage Switchgear Requisition: 480-Z MV Shop Order: SWITCHGEAR SWGR-Q-A ( 15LSWGR901 ) DRAWING LIST - Customer Identification Cross Reference Function Device Customer Customer Unit Mark Mark Description Mark Loop Tag 101B 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG A 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG B 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG B 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG B 52M1 001 Main Breaker Q00 15LMBK A 52A1 001 Feeder Breaker Q01 15LFBK B 52A2 001 Feeder Breaker Q02 15LFBK B 52A3 001 Feeder Breaker Q03 15LFBK911
5 General Electric Company SUMMARY OF EQUIPMENT CUSTOMER: ORANGE COUNT SANITATION DISTRICT CUSTOMER ORDER AA LOCATION: ORANGE COUNTY, CA STATION: SWGR Q-A, SLUDGE DEWATERING AND ODOR CONTROL AT P CONTRACTOR: HELIX ELECTRIC CONSULTANT: BLACK AND VEATCH DISTRIBUTOR: GEXPRO DISTRIBUTOR ORDER: AA PENALTY: NO CUSTOMER INSPECTION: NO WITNESS TEST: NO EQUIPMENT DUTY: High Seismic(IBC2006/IEEE ) CERTIFIED TEST REPORT: YES COMPLIANCE CERTIFICATE: NO LINEUP NO: 01 CONSTRUCTION: Indoor RATED: 12470V-3PH-3W-60HZ-40KA EQUIPMENT: PowerVac Switchgear MAIN BUS MATERIAL: LU A/CU NEUTRAL BUS MATERIAL: LU001 - N/A GROUND BUS MATERIAL: LU A/CU BUS BRACING: 40KA S.C. RATING: 40KA GE BKR HOIST: N/A TOTAL STACKS: LU001-3 EQUIPMENT I/B: GEK PAINTED PER: ANSI 61-STD (POWDER-COAT TYPE PER MFG- FINISHED COLOR: Light Gray REQN #: 480-Z7612-MV SO #: SHEET: 1 ENGR: Tom Ly SMY #: OF: 1 DATE: 7/23/2014 REV #: 2
6 POWER/VAC BREAKER SUMMARY CATALOG NUMBER: PVGX1A1A2A2202G1A PVG - POWER-VAC EQUIPMENT BREAKER X KV - 40KA A RATING A - RETROFIT CODE - NONE 1 - REVISION 1 A - NO CAP SWITCHING 2-5-CYCLE BKR A - 60 HZ. RATING 2-125VDC CLOSE COIL STANDARD WIRING 2-125VDC TRIP COIL - 1ST 0 - NO 2ND TRIP COIL 2-125VDC CHARGING MOTOR G - SEISMIC/UL LABEL/CERTIFIED TEST REPORTS 1 - NO FAST BUS TRANSFER A - NO DIELECTRIC ENHANCEMENTS 1 - NO SPECIALS Type VB NAMEPLATE Serial No. (GENERATED BY SHOP) RATED MAX 15 kv RATED 1200 AMPS 60 Hz IMPULSE 95kV INT 5 CYC VOLTAGE CURRENT WITHSTAND TIME RATED SHORT 40 ka SHORT TIME 40 ka CLOSE & LATCH 104 ka CIRCUIT AMPS CURRENT CAPABILITY AMP DC 35% RATED VOLTAGE COMP RANGE FACTOR 1.00 OPERATING DUTY CYCLE O-0.3s-CO-3m-CO CLOSE 0282A2009G002 VOLTS 125VDC CLOSING 6.0 VOLT COIL AMPS RANGE TRIP 0282A2009G008 VOLTS 125VDC TRIPPING 10.2 VOLT COIL-1 AMPS RANGE TRIP VOLTS TRIPPING VOLT COIL-2 AMPS RANGE CHARGING 0177C2164G001 VOLTS 125VDC MOTOR CONNECTION 07010P00WR3713 WT. 635lbs MECH ML-17 DATE DIAGRAM TYPE MFG MM/DD/YYYY CAPACITANCE CURRENT SWITCHING CABLE A CLASS C2 CHARGING ISOLATED A CLASS C2 BACK-TO-BACK CAP A CLASS C2 CAP BANK AMPS TRANSIENT INRUSH ka TRANSIENT INRUSH khz CURRENT FREQUENCY VAC.INTER.TYPE 48A REQ: PO# AS APP. SO: ORACLE PROJECT ORDERING PVGX1A1A2A2202G1A1 MANUAL: 01.4IB.66000B NO CAUTION: BEFORE INSTALLING OR OPERATING READ INST
7 MK QTY DESCRIPTION RATING QTY L/U UNIT 0LF 3 ORDERING NO: 9L11XPB015S IP S LA 15KV L/G POLYMER STATION TYPE GEH-6323 OL 9L11XPBXXXS MOUNTING BASE DOWN 0NH 3 ORDERING NO: BURNDY CRIMP TERM FOR CU CABLE #4 AWG YA4C2N UL/CSA A B B 0NM 2 ORDERING NO: YA252N UL/CSA B BURNDY CRIMP TERM FOR CU CABLE 1/0 0NN 9 ORDERING NO: BURNDY CRIMP TERM FOR CU CABLE 2/0 YA262N UL/CSA A B B 0NW 6 ORDERING NO: YA312N UL/CSA B BURNDY CRIMP TERM FOR CU CABLE 350kcmil/185SQMM 0PJ 2 ORDERING NO: 0282A4158P004 NA S TERMINAL #2-250kcmil S TIN PLATED 1EM 7 ORDERING NO: LOCKOUT RELAY 125VDC/120VAC 7803D UR-IP B ELECTROSWITCH LOR W/MANUALRESET I/B LOR-1, 3 DECK 6 N.O./6 N.C. CONTACTS A B B 1P8 2 ORDERING NO: PTG FF UL A ITI VOLTAGE TRANSFORMER 12000/120, 100:1 WITH (2) 0.5E FUSES ORDERING NO: PZWZ7 UR-IP A VM AC 4.25" SWBD TYPE RATED 150V, SCALE 0-15kV, 50/60Hz TRANSFORMER RATED AB-40 METAL CASE REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/31/2015 SMY #: Issue rev. 5 WO #: CONT ON SH D2 SH D1
8 MK QTY DESCRIPTION RATING QTY L/U UNIT 30D 1 ORDERING NO: FT-1 TEST PLUG SEPARATE SOURCE TEST PLUG UL XS 30KC 1 ORDERING NO: FTC-066 UL A ITI TYPE FT TEST SWITCH 10 POLE, 10-POTENTIAL CLEAR COVER 30W 1 ORDERING NO: TP-109 UL XS ITI TYPE FT TEST PLUG USE WITH DOBS # 30K, 30S, 30T ORDERING NO: SB1 PCB CONT SW 3 STG GEH SB1B9X2 IP B A B B 5AA 12 ORDERING NO: C2000 AUX RLY 120V 50/60HZ 2NO, 2NC RL4RA022TJ UL B DIN A B B 65Q 5 71G ORDERING NO: INFRARED INSPECTION WINDOW FLK-050-CLKT UR-IP S 2" CRYSTAL WINDOW TYPE-C LENS 0.07" THICKNESS, 96% I.R. TRANSMITTION, LOW SMOKE & FUME GASKET, FOR OUTDOOR & HV USE,KWIK-TWIST(MAGNETIC COVER) S S ORDERING NO: BE1-27A3EE1JA1S3F UR-IP B UNDERVOLTAGE RLY, BASLER 1PH, SEC TD, 2N.O. TUV, 2N.O.INST CONTACTS AUX PWR: 125VDC/120VAC, PUSH TO ENGERGIZE O/P BASLER S1 CASE, SEMI-FLUSH MTG, I/B ORDERING NO: 0177C3943G001 NA XS BKR SEC EXT TEST CABLE OL 0177C X 34 ORDERING NO: SLIDING LINK TERM BLK CEZWM D UR-IP A AVO/STATES, 50A, 600V, 12-POLE, CLASS 1E, FRONT CONNECTED,EVERDUR BRONZE LINK SCREW WHITE MARKER STRIP, DOUBLE NUTS, CLEAR COVER B A B A B REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/31/2015 SMY #: Issue rev. 5 WO #: CONT ON SH D3 SH D2
9 MK QTY DESCRIPTION RATING QTY L/U UNIT ORDERING NO: JITE S/C TERMINAL BLOCK 4-POLE 30A-600V BTB M1 IP B A B B 7L2 20 ORDERING NO: CLASS CC ULTRASAFE USM FUSE HOLDER 2 POLE 30A 800VAC/1000VDC 100KAIC 800VAC/1000VDC USM2 UR-IP A B A B B 7NC 3 ORDERING NO: UR-IP S GRD SENSOR CT 50/5A S INSTR TRANSF INC, CLASS C20 ACCURACY 7.31" WINDOW ORDERING NO: COVER, BALL GRD STUD CHANCE C NA S S S 87V 1 ORDERING NO: 0282A2459G001 NA XS BKR WIPE ADJ TOOL ML-17 87W 1 ORDERING NO: 0209B5075G001 NA XS MANUAL RACKING WRENCH 88Z 1 ORDERING NO: 0144D2933G001 NA XS BKR HOIST TRUCK TWO-MAST GE HIGH LIFT TYPE 8EV 1 ORDERING NO: 0237C4219G001 NA XS BKR TEST BOX, 1 TRIP COIL OL 0237C4219, CONN 0329B8573, AC/DC CLOSE, AC/DC TRIP, AC/DC MOTOR, GEK C02S 9 ORDERING NO: SINGLE RATIO CT 200/ UR-IP A ACCURACY CLASS C20, CURVES 0329A5504, DWG 0144D2684P003, MODEL B B REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/31/2015 SMY #: Issue rev. 5 WO #: CONT ON SH D4 SH D3
10 MK QTY DESCRIPTION RATING QTY L/U UNIT C04S 6 ORDERING NO: UR-IP XS SINGLE RATIO CT 400/5 ACCURACY CLASS C50, CURVES 0329A5507, DWG 0144D2684P006, MODEL C06S 3 ORDERING NO: UR-IP B SINGLE RATIO CT 600/5 ACCURACY CLASS C100, CURVES 0329A5509 DWG 0144D2684P008, MODEL F10A 10 ORDERING NO: 10A CLF CLASS J FU OTM10 UL A FERRAZ-SHAWMUT FUSE, 10A 250VAC B A B B F30D 30 ORDERING NO: 30A CLF CLASS J FU FERRAZ-SHAWMUT FUSE 30A 600VAC/VDC ATM30 UL B A B B GND 5 ORDERING NO: INTERMEDIATE GROUND BUS 17171P ~BS NA A B A B B M049 4 ORDERING NO: COLLAR FOR 350 RELAY 07070H ~061T NA B A B B P476 1 P82C 4 ORDERING NO: VM SWITCH ELECTROSWITCH SERIES 24 2 DECK, 3PH, PH-PH, W/ OFF HANDLE: ROUND,KNURLED ORDERING NO: ITI FT-1 TEST SWITCH 10 POLE, 10-CURRENT C-C C-C C-C C-C C-C 2404C UR-IP A FTC-082 UL B A B B P881 4 ORDERING NO: 350 FEEDER PROTECTION RELAY 350-E-P5-G5-H-E-S-N-N-1E-D-N UL B 5A PH & GRD CURRENT, STD O/C PROTECTION POWER SUPPLY: VDC/ VAC, STD COMM.(FRONT USB & REAR RS485) + ETHERNET A B B REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/31/2015 SMY #: Issue rev. 5 WO #: CONT ON SH D5 SH D4
11 MK QTY DESCRIPTION RATING QTY L/U UNIT PS1 4 ORDERING NO: POSITION (TOC) SWITCH, 6A/6B ANY COMPT TYPE 07100G ~061T061TES IP B USE WITH ML-18 BKR AND ML-17-4 BKR A B B Q196 1 ORDERING NO: 07100G ~061T061TES NA XS BKR MANUAL CHARGE HDL (ML-17) Q647 4 Q649 4 Q654 7 Q685 2 ORDERING NO: PUSH TO TEST PILOT LIGHT ALLEN BRADLEY 30.5MM, LED TYPE, RED LENS V AC/DC, 1 NO-1 NC FULL VOLTAGE TYPE ORDERING NO: PUSH TO TEST PILOT LIGHT 800T-QTH2R UL B ALLEN BRADLEY 30.5MM, LED TYPE, GREEN LENS V AC/DC, 1 NO-1 NC FULL VOLTAGE TYPE ORDERING NO: PUSH TO TEST PILOT LIGHT A B B 800T-QTH2G UL B ALLEN BRADLEY 30.5 mm, LED TYPE, WHITE LENS VAC/VDC, 1 NO 1 NC FULL VOLTAGE TYPE A B B 800T-QTH2W UL B A B B ORDERING NO: XS ANSI-61 SPRAY PAINT 12 OZ. CAN Q701 4 SS1 4 ORDERING NO: PUSH TO TEST PILOT LIGHT ALLEN BRADLEY 30.5 mm, LED TYPE, AMBER LENS VAC/VDC, 1 NO 1 NC FULL VOLTAGE TYPE 800T-QTH2A UL B ORDERING NO: STATION (MOC) SWITCH, CONNECT-TEST, 6A/6B ANY COMPT TYPE USE WITH ML-18 BKR AND ML-17-4 BKR A B B 07100G ~061T061TES IP B A B B TB02STD 8 ORDERING NO: 75A 2PT TERMINAL BLOCK #4-#16 AWG 1602STD UL/IP A A A REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/31/2015 SMY #: Issue rev. 5 WO #: CONT ON SH D6 SH D5
12 MK QTY DESCRIPTION RATING QTY L/U UNIT TB04STD 1 ORDERING NO: 1604STD UL/IP A 75A 4PT TERMINAL BLOCK #4-#16 AWG REQ #: 480-Z7612-MV SMY #: WO #: ENGR: Tom Ly Issue rev. 5 DATE: 8/31/2015 CONT ON SH SH D6
13 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 64 NP VOLT METER 101A 1 64 NP VOLT SWITCH 101A 1 64 NP TS1 101A VOLT METER TEST SWITCH 1 64 NP BE1 101B UNDERVOLTAGE RELAY 1 64 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 64 NP TS1 101B SR-350 CURRENT TEST SWITCH 1 64 NP BREAKER CONTROL SWITCH 101B 52CS 1 64 NP DEVICE B LOCKOUT RELAY 2 58 NP IL1 101B BREAKER OPEN 2 58 NP IL2 101B BREAKER CLOSED 2 58 NP IL3 101B BREAKER CHARGED 2 58 NP IL4 101B 86 HEALTHY 1 64 NP LITG A FEEDER BREAKER PROTECTION RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E2 SH E1
14 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 64 NP TS1 102A SR-350 CURRENT TEST SWITCH 1 64 NP BREAKER CONTROL SWITCH 102A 52CS 1 64 NP DEVICE A LOCKOUT RELAY 1 64 NP DEVICE 86FP 102A LOCKOUT RELAY 2 58 NP IL1 102A BREAKER OPEN 2 58 NP IL2 102A BREAKER CLOSED 2 58 NP IL3 102A BREAKER CHARGED 2 58 NP IL4 102A 86 HEALTHY 2 58 NP IL5 102A 86FP HEALTHY 1 64 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 64 NP TS1 102B SR-350 CURRENT TEST SWITCH 1 64 NP DEVICE B LOCKOUT RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E3 SH E2
15 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 64 NP DEVICE 86FP 102B LOCKOUT RELAY 1 64 NP BREAKER CONTROL SWITCH 102B 52CS 2 58 NP IL1 102B BREAKER OPEN 2 58 NP IL2 102B BREAKER CLOSED 2 58 NP IL3 102B BREAKER CHARGED 2 58 NP IL4 102B 86 HEALTHY 2 58 NP IL5 102B 86FP HEALTHY 1 64 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 64 NP TS1 103B SR-350 CURRENT TEST SWITCH 1 64 NP BREAKER CONTROL SWITCH 103B 52CS 1 64 NP DEVICE B LOCKOUT RELAY 1 64 NP DEVICE 86FP 103B LOCKOUT RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E4 SH E3
16 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 2 58 NP IL1 103B BREAKER OPEN 2 58 NP IL2 103B BREAKER CLOSED 2 58 NP IL3 103B BREAKER CHARGED 2 58 NP IL4 103B 86 HEALTHY 2 58 NP IL5 103B 86FP HEALTHY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E5 SH E4
17 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT NP LSWGR A KV SWITCHGEAR SWGR Q-A 1 16 NP VOLT METER 101A 1 16 NP TS1 101A VOLT METER TEST SWITCH 1 33 NP SECTION A 1 9 NP FBLPT 101A PT SEC FUSE 10A 1 16 NP VOLT SWITCH 101A 1 33 NP LINE PT COMPARTMENT 101A 1 16 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 16 NP BE1 101B UNDERVOLTAGE RELAY 1 16 NP TS1 101B SR-350 CURRENT TEST SWITCH 1 16 NP BREAKER CONTROL SWITCH 101B 52CS 1 16 NP DEVICE B LOCKOUT RELAY 1 33 NP LMBK B Q00 52M1 MAIN BREAKER 2 9 NP IL1 101B BREAKER OPEN - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E6 SH E5
18 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 2 9 NP IL2 101B BREAKER CLOSED 2 9 NP IL3 101B BREAKER CHARGED 2 9 NP IL4 101B 86 HEALTHY 1 9 NP FBCL 101B 52 CLOSE FUSE 30A 1 9 NP FBTR 101B 52 TRIP FUSE 30A 1 9 NP FB86 101B 86 CKT FUSE 30A 1 9 NP RX 101B PLC RX AUX RELAY 1 9 NP TXA 101B PLC TXA AUX RELAY 1 9 NP CXA 101B PLC CXA AUX RELAY 1 9 NP FBPLC 101B PLC CKT FUSE 10A 1 33 NP SECTION S 1 33 NP LINE PT COMPARTMENT 101S - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E7 SH E6
19 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 33 NP LMBK S Q00 52M1 MAIN BREAKER 1 16 NP DEVICE A LOCKOUT RELAY 1 16 NP BREAKER CONTROL SWITCH 102A 52CS 1 16 NP DEVICE 86FP 102A LOCKOUT RELAY 1 33 NP LFBK A Q01 52A1 FEEDER BREAKER 1 16 NP LITG A FEEDER BREAKER PROTECTION RELAY 1 33 NP SECTION A 1 16 NP TS1 102A SR-350 CURRENT TEST SWITCH 2 9 NP IL1 102A BREAKER OPEN 2 9 NP IL2 102A BREAKER CLOSED 2 9 NP IL3 102A BREAKER CHARGED 1 9 NP FBCL 102A 52 CLOSE FUSE 30A - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E8 SH E7
20 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 2 9 NP IL4 102A 86 HEALTHY 2 9 NP IL5 102A 86FP HEALTHY 1 9 NP FBTR 102A 52 TRIP FUSE 30A 1 9 NP F86FP 102A 86FP CKT FUSE 30A 1 9 NP FB86 102A 86 CKT FUSE 30A 1 9 NP RX 102A PLC RX AUX RELAY 1 9 NP CXA 102A PLC CXA AUX RELAY 1 9 NP TXA 102A PLC TXA AUX RELAY 1 9 NP FBPLC 102A PLC CKT FUSE 10A 1 16 NP BREAKER CONTROL SWITCH 102B 52CS 1 33 NP LFBK B Q02 52A2 FEEDER BREAKER - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E9 SH E8
21 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 16 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 16 NP TS1 102B SR-350 CURRENT TEST SWITCH 1 16 NP DEVICE B LOCKOUT RELAY 1 16 NP DEVICE 86FP 102B LOCKOUT RELAY 2 9 NP IL1 102B BREAKER OPEN 2 9 NP IL2 102B BREAKER CLOSED 2 9 NP IL3 102B BREAKER CHARGED 2 9 NP IL4 102B 86 HEALTHY 2 9 NP IL5 102B 86FP HEALTHY 1 9 NP FBCL 102B 52 CLOSE FUSE 30A 1 9 NP FBTR 102B 52 TRIP FUSE 30A 1 9 NP F86FP 102B 86FP CKT FUSE 30A - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E10 SH E9
22 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 9 NP FB86 102B 86 CKT FUSE 30A 1 9 NP RX 102B PLC RX AUX RELAY 1 9 NP CXA 102B PLC CXA AUX RELAY 1 9 NP TXA 102B PLC TXA AUX RELAY 1 9 NP FBPLC 102B PLC CKT FUSE 10A 1 33 NP SECTION S 1 33 NP LFBK S Q01 52A1 FEEDER BREAKER 1 33 NP LFBK S Q02 52A2 FEEDER BREAKER 1 33 NP SECTION A 1 33 NP SPACE 103A 1 33 NP LFBK B Q03 52A3 FEEDER BREAKER 2 9 NP IL1 103B BREAKER OPEN 2 9 NP IL2 103B BREAKER CLOSED - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E11 SH E10
23 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 2 9 NP IL3 103B BREAKER CHARGED 2 9 NP IL4 103B 86 HEALTHY 2 9 NP IL5 103B 86FP HEALTHY 1 16 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 16 NP BREAKER CONTROL SWITCH 103B 52CS 1 16 NP DEVICE B LOCKOUT RELAY 1 16 NP DEVICE 86FP 103B LOCKOUT RELAY 1 9 NP FBCL 103B 52 CLOSE FUSE 30A 1 9 NP FBTR 103B 52 TRIP FUSE 30A 1 9 NP F86FP 103B 86FP CKT FUSE 30A 1 9 NP FB86 103B 86 CKT FUSE 30A 1 9 NP RX 103B PLC RX AUX RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E12 SH E11
24 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 9 NP CXA 103B PLC CXA AUX RELAY 1 9 NP TXA 103B PLC TXA AUX RELAY 1 16 NP TS1 103B SR-350 CURRENT TEST SWITCH 1 9 NP FBPLC 103B PLC CKT FUSE 10A 1 33 NP SPACE 103S 1 33 NP LFBK S Q03 52A3 FEEDER BREAKER 1 33 NP SECTION S - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON E13 SH E12
25 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: WHITE LETTERS ON RED BACKGROUND MOUNTING: STAINLESS STEEL REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 33 NP NOTICE - WITHDRAWING 101A ROLLOUT DISCONNECTS POTENTIAL TRANSFORMERS 1 33 NP CAUTION - THIS UNIT 101A CONTAINS FOREIGN VOLTAGE SOURCES 1 33 NP CAUTION - THIS UNIT 101A CONTAINS AN EXTERNAL VOLTAGE SOURCE 1 33 NP CAUTION - THIS UNIT 101B CONTAINS FOREIGN VOLTAGE SOURCES 1 33 NP CAUTION - THIS UNIT 101B CONTAINS AN EXTERNAL VOLTAGE SOURCE 1 33 NP CAUTION - THIS UNIT 101S CONTAINS AN EXTERNAL VOLTAGE SOURCE 1 33 NP CAUTION - THIS UNIT 101S CONTAINS AN EXTERNAL VOLTAGE SOURCE 1 33 NP CAUTION - THIS UNIT 102A CONTAINS FOREIGN VOLTAGE SOURCES 1 33 NP CAUTION - THIS UNIT 102B CONTAINS FOREIGN VOLTAGE SOURCES 1 33 NP CAUTION - THIS UNIT 103A CONTAINS FOREIGN VOLTAGE SOURCES 1 33 NP CAUTION - THIS UNIT 103B CONTAINS FOREIGN VOLTAGE SOURCES - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 6 DATE: 9/1/2015 CONT ON SH E13
26 POWER-VAC SWITCHGEAR Product Type POWER-VAC Style:Indoor : Plant Code : AIR Summary Number : Lineup Cust. Mark No. Volts Phase Wire HZ Volts Max. 01 MV SWGR LOW FREQ.: 36KV IMPULSE: 95KV MOMENTARY:104 PeakKA SHORT CKT RATING STACK SECTION SUPPLY SECTION NEUTRAL RMS SYM AMPS LABEL ,000 UL ,000 UL ,000 UL REQN NO: 480-Z7612-MV SUMM NO: SO NO: ENGR: Tom Ly REV NO: 2 DATE: 7/21/14 10:06 SH EE
27 Summary of Power-Vac Switchgear Equipment Standard Options LineUp : Certifications UL/UR 1670 Label UL Label Units , 102, 103 CSA Not Required Units Corona Spec Not Required Corona Testing Not Required Regulatory Code California Code Seismic Zone High Seismic(IBC2006/IEEE ) Breaker Testing Mech Int/Operational Test Electrical Options Wire Size Wire Sleeves Origin/Destination - Heat Shrinkable Sleeve Wire Terminals Ring Insulated CT Wire Size CT Wire Terminals Ring Insulated Serialized Metering/Relaying CTs w/ Test Reports No System Phase Configuration WYE System Ground Configuration Effectively Grounded Mechanical Options Construction Indoor Arc Resistant Not Required Drip Proof Roof Not Required Stack Depth Stack Depth Ext Cable Lug Type Cable Supports Cable Boots Device Door Barriers Front Door Hinge Front Door Handle Type Front Door Flat Gasket Front Door Padlock Compression-Copper Yes Required Required LH Thumbscrew Required Required Rear Door Type Hinged Height: Split Rear Door Handle Type Rear Door Stop Rear Door Padlock Bolt Required Required Indoor Floor Plates Not Required Primary and Bus Supports Polyester Main Bus Plating Full Tin (Std) Ground Bus Plating Full Tin (Std) Mimic Bus Not Required Width : Color : Mounting : Heaters Outdoor Aisle Extension Outdoor PA/CA Ship Not Required Not Required Not Required Pull Box Not Required Pull Box Height : 0 Ventilation Insect/Rodent/Dust Screen Option: Screen and Filter Roll-In Breakers Not Required Remote Racking Required Remote Racking Type : Saddle-Mount Special PaintThickness (mils) Special Interior Paint Not Required Not Required Special Exterior Paint Not Required REQN NO: 480-Z7612-MV SUMM NO: SO NO: ENGR: Tom Ly REV NO: 2 DATE: 7/21/ :04 SH L
28 EQUIPMENT SUMMARY SPECIAL REQUIREMENTS 01. BREAKER CONTROL CIRCUIT TO BE WIRED SUCH THAT THE TRIP FUSES ARE WIRED TO PROTECT THE TRIP AND CLOSE CIRCUIT. CLOSE FUSES (FED FROM THE TRIP FUSES) TO BE PROVIDED TO PROTECT THE CLOSE CIRCUIT. THIS WILL ENSURE THAT THE BREAKER CAN'T BE CLOSED IF THERE IS NO TRIP POWER AVAILABLE. 02. ELECTRICAL DESIGNER TO PROVIDE 20% SPARE TERMINAL POINTS WHERE POSSIBLE. 03. CALIFORNIA CODE TO BE PROVIDED FOR THIS LINEUP. 04. WIRING TO PROVIDE STATES SLIDING LINK TERMINAL BLOCKS MK# 74X FOR ALL CUSTOMER CONNECTIONS (EXCLUDING SHORT CIRCUITING TERMINAL BLOCKS). 05. CLEAR COVERS ARE TO BE PROVIDED FOR ALL TERMINAL BLOCKS. OPAQUE COVERS ARE ACCEPTABLE. 06. QTY. (1) MANUAL GROUND AND TEST DEVICE TO BE PROVIDED UNDER LINE ITEM 07, CAT. NO. GEPVMGT01J1AA1A1A. 07. QTY. (01) SPARE BREAKER CAT# PVGY1J1A2A2202G1A1-1, AND QTY. (06) 400/5A ITI SINGLE RATIO CT S CAT # TO BE PROVIDED IN LINE ITEM NUMBER MECHANICAL: HAWK (MK# 65Q) REAR DOOR INFRARED SIGHT GLASS PROVISIONS ARE REQUIRED FOR STACK(S) 101, 102, TERMINAL POINTS FOR FIELD CONNECTION SHALL BE A MININUM OF 12 ABOVE THE FLOOR. 10. INSPECTION TO NOTIFY ENGINEER WHEN JOB IS RELEASED FOR SHIPMENT. PHOTOS ARE TO BE TAKEN BY ENGINEER OR BY INSPECTOR BEFORE SWITCHGEAR SHIPS. 11. SHOP TO PROVIDE THE WARNING SIGN NAME PLATES ON THE FRONT AND REAR DOORS AS FOLLOWS: SIZE: 10 L X 7 H, WHITE LETTERS ON THE RED BACKGROUND, 0.5 LETTER SIZE, CENTER JUSTIFIED. LINE1: DANGER LINE2: VOLTS LINE3: INSIDE REQN NO: 480-Z7612-MV SUMM NO: SO NO: ENGR: Tom Ly REV NO: 2 CONT ON SH FNL SHS1 DATE: 7/21/ :29
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61 Sludge Dewatering and Odor Control at Plant 1 Specification: Project No. P1-101 Medium Voltage Switchgear DWG-AB As Built Requisition: 480-Z MV Shop Order: SWITCHGEAR SWGR-Q-B ( 15LSWGR902 ) Summary, Ratings, Device & Nameplate Information Summary Set: Summary of Equipment Lineup Sheet 1 Breaker Information B-Sheet Set Device Summary (Bill of Material) D-Sheet Set Nameplate Schedules E -Sheet Set Section Rating Details EE1 List of Lineup Options L-Sheet Set Special Requirements S-Sheet Set Technical Submittal: Drawing Set: Mechanical Sheets: 1 thru 6 Elevation, Layout & Single Line Side Views Panel Layouts per Section: Electrical Sheets: 7 thru 18 Schematics Control Circuits Power Elementaries Wiring Diagrams Sheets: 19 thru FNL Connection Details - Point to Point
62 Sludge Dewatering and Odor Control at Plant 1 Specification: Project No. P1-101 Medium Voltage Switchgear Requisition: 480-Z MV Shop Order: SWITCHGEAR SWGR-Q-B ( 15LSWGR902 ) DRAWING LIST - Customer Identification Cross Reference Function Device Customer Customer Unit Mark Mark Description Mark Loop Tag 101B 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG A 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG B 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG B 350 Q471 Feeder Protection Relay 50/51 Relay 15LITG B 52M2 001 Main Breaker Q50 15LMBK A 52B1 001 Feeder Breaker Q51 15LFBK B 52B2 001 Feeder Breaker Q52 15LFBK B 52B3 001 Feeder Breaker Q53 15LFBK912
63 General Electric Company SUMMARY OF EQUIPMENT CUSTOMER: ORANGE COUNT SANITATION DISTRICT CUSTOMER ORDER AA LOCATION: ORANGE COUNTY, CA STATION: SWGR Q-B, SLUDGE DEWATERING AND ODOR CONTROL AT P CONTRACTOR: HELIX ELECTRIC CONSULTANT: BLACK AND VEATCH DISTRIBUTOR: GEXPRO DISTRIBUTOR ORDER: AA PENALTY: NO CUSTOMER INSPECTION: NO WITNESS TEST: NO EQUIPMENT DUTY: High Seismic(IBC2006/IEEE ) CERTIFIED TEST REPORT: YES COMPLIANCE CERTIFICATE: NO LINEUP NO: 01 CONSTRUCTION: Indoor RATED: 12470V-3PH-3W-60HZ-40KA EQUIPMENT: PowerVac Switchgear MAIN BUS MATERIAL: LU A/CU NEUTRAL BUS MATERIAL: LU001 - N/A GROUND BUS MATERIAL: LU A/CU BUS BRACING: 40KA S.C. RATING: 40KA GE BKR HOIST: N/A TOTAL STACKS: LU001-3 EQUIPMENT I/B: GEK PAINTED PER: ANSI 61-STD (POWDER-COAT TYPE PER MFG- FINISHED COLOR: Light Gray REQN #: 480-Z7612-MV SO #: SHEET: 1 ENGR: Tom Ly SMY #: OF: 1 DATE: 7/23/2014 REV #: 2
64 POWER/VAC BREAKER SUMMARY CATALOG NUMBER: PVGX1A1A2A2202G1A PVG - POWER-VAC EQUIPMENT BREAKER X KV - 40KA A RATING A - RETROFIT CODE - NONE 1 - REVISION 1 A - NO CAP SWITCHING 2-5-CYCLE BKR A - 60 HZ. RATING 2-125VDC CLOSE COIL STANDARD WIRING 2-125VDC TRIP COIL - 1ST 0 - NO 2ND TRIP COIL 2-125VDC CHARGING MOTOR G - SEISMIC/UL LABEL/CERTIFIED TEST REPORTS 1 - NO FAST BUS TRANSFER A - NO DIELECTRIC ENHANCEMENTS 1 - NO SPECIALS Type VB NAMEPLATE Serial No. (GENERATED BY SHOP) RATED MAX 15 kv RATED 1200 AMPS 60 Hz IMPULSE 95kV INT 5 CYC VOLTAGE CURRENT WITHSTAND TIME RATED SHORT 40 ka SHORT TIME 40 ka CLOSE & LATCH 104 ka CIRCUIT AMPS CURRENT CAPABILITY AMP DC 35% RATED VOLTAGE COMP RANGE FACTOR 1.00 OPERATING DUTY CYCLE O-0.3s-CO-3m-CO CLOSE 0282A2009G002 VOLTS 125VDC CLOSING 6.0 VOLT COIL AMPS RANGE TRIP 0282A2009G008 VOLTS 125VDC TRIPPING 10.2 VOLT COIL-1 AMPS RANGE TRIP VOLTS TRIPPING VOLT COIL-2 AMPS RANGE CHARGING 0177C2164G001 VOLTS 125VDC MOTOR CONNECTION 07010P00WR3713 WT. 635lbs MECH ML-17 DATE DIAGRAM TYPE MFG MM/DD/YYYY CAPACITANCE CURRENT SWITCHING CABLE A CLASS C2 CHARGING ISOLATED A CLASS C2 BACK-TO-BACK CAP A CLASS C2 CAP BANK AMPS TRANSIENT INRUSH ka TRANSIENT INRUSH khz CURRENT FREQUENCY VAC.INTER.TYPE 48A REQ: PO# AS APP. SO: ORACLE PROJECT ORDERING PVGX1A1A2A2202G1A1 MANUAL: 01.4IB.66000B NO CAUTION: BEFORE INSTALLING OR OPERATING READ INST
65 MK QTY DESCRIPTION RATING QTY L/U UNIT 0LF 3 ORDERING NO: 9L11XPB015S IP S LA 15KV L/G POLYMER STATION TYPE GEH-6323 OL 9L11XPBXXXS MOUNTING BASE DOWN 0NH 3 ORDERING NO: BURNDY CRIMP TERM FOR CU CABLE #4 AWG YA4C2N UL/CSA A B B 0NM 2 ORDERING NO: YA252N UL/CSA B BURNDY CRIMP TERM FOR CU CABLE 1/0 0NN 9 ORDERING NO: BURNDY CRIMP TERM FOR CU CABLE 2/0 YA262N UL/CSA A B B 0NW 6 ORDERING NO: YA312N UL/CSA B BURNDY CRIMP TERM FOR CU CABLE 350kcmil/185SQMM 0PJ 2 ORDERING NO: 0282A4158P004 NA S TERMINAL #2-250kcmil S TIN PLATED 1EM 7 ORDERING NO: LOCKOUT RELAY 125VDC/120VAC 7803D UR-IP B ELECTROSWITCH LOR W/MANUALRESET I/B LOR-1, 3 DECK 6 N.O./6 N.C. CONTACTS A B B 1P8 2 ORDERING NO: PTG FF UL A ITI VOLTAGE TRANSFORMER 12000/120, 100:1 WITH (2) 0.5E FUSES ORDERING NO: PZWZ7 UR-IP A VM AC 4.25" SWBD TYPE RATED 150V, SCALE 0-15kV, 50/60Hz TRANSFORMER RATED AB-40 METAL CASE REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/8/2014 SMY #: Issue rev. 5 WO #: CONT ON SH D2 SH D1
66 MK QTY DESCRIPTION RATING QTY L/U UNIT 30KC 1 ORDERING NO: FTC-066 UL A ITI TYPE FT TEST SWITCH 10 POLE, 10-POTENTIAL CLEAR COVER ORDERING NO: SB1 PCB CONT SW 3 STG GEH SB1B9X2 IP B A B B 5AA 12 ORDERING NO: C2000 AUX RLY 120V 50/60HZ 2NO, 2NC RL4RA022TJ UL B DIN A B B 65Q 5 71G 1 74X 34 ORDERING NO: INFRARED INSPECTION WINDOW FLK-050-CLKT UR-IP S 2" CRYSTAL WINDOW TYPE-C LENS 0.07" THICKNESS, 96% I.R. TRANSMITTION, LOW SMOKE & FUME GASKET, FOR OUTDOOR & HV USE,KWIK-TWIST(MAGNETIC COVER) S S ORDERING NO: BE1-27A3EE1JA1S3F UR-IP B UNDERVOLTAGE RLY, BASLER 1PH, SEC TD, 2N.O. TUV, 2N.O.INST CONTACTS AUX PWR: 125VDC/120VAC, PUSH TO ENGERGIZE O/P BASLER S1 CASE, SEMI-FLUSH MTG, I/B ORDERING NO: SLIDING LINK TERM BLK CEZWM D UR-IP A AVO/STATES, 50A, 600V, 12-POLE, CLASS 1E, FRONT CONNECTED,EVERDUR BRONZE LINK SCREW WHITE MARKER STRIP, DOUBLE NUTS, CLEAR COVER B A B A B ORDERING NO: JITE S/C TERMINAL BLOCK 4-POLE 30A-600V BTB M1 IP B A B B 7L2 20 ORDERING NO: CLASS CC ULTRASAFE USM FUSE HOLDER 2 POLE 30A 800VAC/1000VDC 100KAIC 800VAC/1000VDC USM2 UR-IP A B A B B 7NC 3 ORDERING NO: UR-IP S GRD SENSOR CT 50/5A S INSTR TRANSF INC, CLASS C20 ACCURACY 7.31" WINDOW REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/8/2014 SMY #: Issue rev. 5 WO #: CONT ON SH D3 SH D2
67 MK QTY DESCRIPTION RATING QTY L/U UNIT ORDERING NO: COVER, BALL GRD STUD CHANCE C NA S S S 87V 1 ORDERING NO: 0282A2459G001 NA XS BKR WIPE ADJ TOOL ML-17 87W 1 ORDERING NO: 0209B5075G001 NA XS MANUAL RACKING WRENCH C02S 9 ORDERING NO: SINGLE RATIO CT 200/ UR-IP A ACCURACY CLASS C20, CURVES 0329A5504, DWG 0144D2684P003, MODEL B B C06S 3 ORDERING NO: UR-IP B SINGLE RATIO CT 600/5 ACCURACY CLASS C100, CURVES 0329A5509 DWG 0144D2684P008, MODEL F10A 10 ORDERING NO: 10A CLF CLASS J FU OTM10 UL A FERRAZ-SHAWMUT FUSE, 10A 250VAC B A B B F30D 30 ORDERING NO: 30A CLF CLASS J FU FERRAZ-SHAWMUT FUSE 30A 600VAC/VDC ATM30 UL B A B B GND 5 ORDERING NO: INTERMEDIATE GROUND BUS 17171P ~BS NA A B A B B M049 4 ORDERING NO: COLLAR FOR 350 RELAY 07070H ~061T NA B A B B REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/8/2014 SMY #: Issue rev. 5 WO #: CONT ON SH D4 SH D3
68 MK QTY DESCRIPTION RATING QTY L/U UNIT P476 1 P82C 4 ORDERING NO: VM SWITCH ELECTROSWITCH SERIES 24 2 DECK, 3PH, PH-PH, W/ OFF HANDLE: ROUND,KNURLED ORDERING NO: ITI FT-1 TEST SWITCH 10 POLE, 10-CURRENT C-C C-C C-C C-C C-C 2404C UR-IP A FTC-082 UL B A B B P881 4 PS1 4 ORDERING NO: 350 FEEDER PROTECTION RELAY 350-E-P5-G5-H-E-S-N-N-1E-D-N UL B 5A PH & GRD CURRENT, STD O/C PROTECTION POWER SUPPLY: VDC/ VAC, STD COMM.(FRONT USB & REAR RS485) + ETHERNET ORDERING NO: POSITION (TOC) SWITCH, 6A/6B ANY COMPT TYPE USE WITH ML-18 BKR AND ML-17-4 BKR A B B 07100G ~061T061TES IP B A B B Q196 1 ORDERING NO: 07100G ~061T061TES NA XS BKR MANUAL CHARGE HDL (ML-17) Q647 4 Q649 4 Q654 7 Q701 4 ORDERING NO: PUSH TO TEST PILOT LIGHT ALLEN BRADLEY 30.5MM, LED TYPE, RED LENS V AC/DC, 1 NO-1 NC FULL VOLTAGE TYPE ORDERING NO: PUSH TO TEST PILOT LIGHT 800T-QTH2R UL B ALLEN BRADLEY 30.5MM, LED TYPE, GREEN LENS V AC/DC, 1 NO-1 NC FULL VOLTAGE TYPE ORDERING NO: PUSH TO TEST PILOT LIGHT A B B 800T-QTH2G UL B ALLEN BRADLEY 30.5 mm, LED TYPE, WHITE LENS VAC/VDC, 1 NO 1 NC FULL VOLTAGE TYPE ORDERING NO: PUSH TO TEST PILOT LIGHT A B B 800T-QTH2W UL B ALLEN BRADLEY 30.5 mm, LED TYPE, AMBER LENS VAC/VDC, 1 NO 1 NC FULL VOLTAGE TYPE A B B 800T-QTH2A UL B A B B REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/8/2014 SMY #: Issue rev. 5 WO #: CONT ON SH D5 SH D4
69 MK QTY DESCRIPTION RATING QTY L/U UNIT SS1 4 ORDERING NO: STATION (MOC) SWITCH, CONNECT-TEST, 6A/6B ANY COMPT TYPE 07100G ~061T061TES IP B USE WITH ML-18 BKR AND ML-17-4 BKR A B B TB02STD 8 ORDERING NO: 75A 2PT TERMINAL BLOCK #4-#16 AWG 1602STD UL/IP A A A TB04STD 1 ORDERING NO: 1604STD UL/IP A 75A 4PT TERMINAL BLOCK #4-#16 AWG REQ #: 480-Z7612-MV ENGR: Tom Ly DATE: 8/8/2014 SMY #: Issue rev. 5 WO #: CONT ON SH SH D5
70 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 64 NP VOLT METER 101A 1 64 NP VOLT SWITCH 101A 1 64 NP TS1 101A VOLT METER TEST SWITCH 1 64 NP BE1 101B UNDERVOLTAGE RELAY 1 64 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 64 NP TS1 101B SR-350 CURRENT TEST SWITCH 1 64 NP BREAKER CONTROL SWITCH 101B 52CS 1 64 NP DEVICE B LOCKOUT RELAY 2 58 NP IL1 101B BREAKER OPEN 2 58 NP IL2 101B BREAKER CLOSED 2 58 NP IL3 101B BREAKER CHARGED 2 58 NP IL4 101B 86 HEALTHY 1 64 NP LITG A FEEDER BREAKER PROTECTION RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 3 DATE: 9/1/2015 CONT ON E2 SH E1
71 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 64 NP TS1 102A SR-350 CURRENT TEST SWITCH 1 64 NP BREAKER CONTROL SWITCH 102A 52CS 1 64 NP DEVICE A LOCKOUT RELAY 1 64 NP DEVICE 86FP 102A LOCKOUT RELAY 2 58 NP IL1 102A BREAKER OPEN 2 58 NP IL2 102A BREAKER CLOSED 2 58 NP IL3 102A BREAKER CHARGED 2 58 NP IL4 102A 86 HEALTHY 2 58 NP IL5 102A 86FP HEALTHY 1 64 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 64 NP TS1 102B SR-350 CURRENT TEST SWITCH 1 64 NP DEVICE B LOCKOUT RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 3 DATE: 9/1/2015 CONT ON E3 SH E2
72 Name Plate Sheet (0185D7046) Note: All special nameplates will be located with the bottom / top edge 1/8" above / below the device as shown on the FV Device arramgement STYLE: BLACK LETTERS ON WHITE BACKGROUND MOUNTING: ADHESIVE REV PART ID CHAR *** ENGRAVE AS FOLLOWS *** UNIT 1 64 NP DEVICE 86FP 102B LOCKOUT RELAY 1 64 NP BREAKER CONTROL SWITCH 102B 52CS 2 58 NP IL1 102B BREAKER OPEN 2 58 NP IL2 102B BREAKER CLOSED 2 58 NP IL3 102B BREAKER CHARGED 2 58 NP IL4 102B 86 HEALTHY 2 58 NP IL5 102B 86FP HEALTHY 1 64 NP LITG B FEEDER BREAKER PROTECTION RELAY 1 64 NP TS1 103B SR-350 CURRENT TEST SWITCH 1 64 NP BREAKER CONTROL SWITCH 103B 52CS 1 64 NP DEVICE B LOCKOUT RELAY 1 64 NP DEVICE 86FP 103B LOCKOUT RELAY - REQN #: 480-Z7612-MV SMY #: SO NO: ENGR: Tom Ly REV #: 3 DATE: 9/1/2015 CONT ON E4 SH E3
SUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationBILL OF MATERIAL 2 C EA SP CURRENT TRANSDUCER BI-DIRECTIONAL, MV INPUT, MA OUTPUT, 125VDC POWER SUPPLY SMC
BILL OF MATERIAL WORK ORDER NUMBER : G6025-01 PURCHASER : TRACTION POWER SYSTEMS PO# : NTP USER : WMATA LOCATION : WASHINGTON, DC PAINT CODE: 061-T/061-T/B/S EQUIPMENT ID : FARRAGUT NORTH SUBSTATION-A02
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationContents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru
Contents Page INTRODUCTION... 10-2 Power/Vac GUIDE FORM SPECIFICATION... 10-2 thru 10-12 10-1 Power/Vac Guide Form Specifications Guide Form Specifications INTRODUCTION Upon completion of the one-line
More informationMEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES
MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications
More informationPage 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut
Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker
More informationSection 18. Medium Voltage Equipment. BuyLog Catalog 18-1
MV One Line...18-2 Motor Control Medium Voltage (Limitamp ) Introduction, Features, Types, Options, References...18-3 Specifications, Ratings, Equipment Reference Publications...18-4 Product Scope...18-5
More informationIntegrated Power Solutions
Integrated Power Solutions Low & Medium Voltage Distribution Power Distribution Centers Skid-Mounted Substations Custom Control & Automation ESS Metron Proposal 64000V1 DATE: PAGES (including cover): 7
More informationCITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008
CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION
More information1VAL2401-SG Rev D. Spare parts list for Outdoor Products Reclosers, breakers, & padmount switches
1VAL2401-SG Rev D Spare parts list for Outdoor Products Reclosers, breakers, & padmount switches Reclosers GridShield recloser 12A00736H05 Actuator assist capacitor Single-phase upgrade 15 KV, 800 A, 12.5
More informationLow Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear
13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationAmerican Electric Supply, Inc.
American Electric Supply, Inc. 6 S. Maple Street Date: 0/8/204 Corona, CA 92880 Telephone: 95-80-4665 Email: bmcdonald@amelect.com Fax: 95-552-626 Speedi Version: V 0.6 Valued Customer, Bill of Material
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationATLV MaxSG. Low Voltage Metal Enclosed Switchgear
ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,
More information1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.
More informationDesign Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak
Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Powergrid Solution s Metal Enclosed Switchgear has many different customizable options and configurations. Customers
More informationMedium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1
Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear
More informationPower/Vac OEM Express Switchgear
g Power/Vac OEM Express Switchgear Metalclad Switchgear 4.16kV-250 MVA through 13.8kV-1500 MVA DEA-275 FULLY ASSEMBLED MECHANICALLY COMPLETE SWITCHGEAR WITHOUT DEVICES AND WIRE. POWER/VAC OEM EXPRESS SWITCHGEAR
More informationVacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components
Supersedes July 2002 Contents Page Procedure for identifying parts... 2 Customer ordering instructions.... 2 Distributor ordering instructions.... 2 Front panel components.... 3 Breaker pan assembly....
More informationAdvance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing
Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing Introduction A modular system of switchgear building blocks and cassettes provide untouchable
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationS200 UL 1077 Series S200. Supplementary protective devices. UL 1077 Series. Miniature. circuit breakers. S200 Supplementary protective devices
UL 077 Series Supplementary protective devices The UL 077 Series miniature supplementary protector offers a compact solution for protection requirements. The devices are DIN rail mounted. The is available
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More information16.13 Unit Substation to 15kV Construction Standards Page 1 of 7
Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected
More informationEvolution * Series E9000 Motor Control Center
GE Industrial Solutions Evolution * Series E9000 Motor Control Center Renewal Parts Bulletin Table of Contents Introduction The E9000-Line motor control center, a quality product of the General Electric
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationInstruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035
Instruction Bulletin 4402-997-0 February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker
More informationMedium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General
13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear
More informationGE 8000-Line Motor Control Centers
GE 8000-Line -1 ENCLOSURE TYPES TYPE 1 General Purpose, Indoor Intended for use indoors, primarily to prevent accidental contact of personnel with the enclosed equipment, in areas where unusual service
More informationProtection Equipment. 5/2 Introduction
Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1
More informationControl Circuit Protection
Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC
More informationPanelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description
.5 Types PRL1a, 2a, a, E, 4 and Column Modifications s Types PRL1a, 2a, a, E, 4, Column Modifications Selection Guide Modifications Alphabetical Index Modification Item Contents Types PRL1a, 2a, a, E,
More informationTechnical Specification for Pole Mounted Capacitor Rack
Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to
More informationPower Break II Switchboard
Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A
More informationProduct Information Packet IDDRPM406004R1 600HP,1780/2665RPM,460V,3PH,DPGFV,RL4046
Product Information Packet IDDRPM406004R1 600HP,1780/2665RPM,460V,3PH,DPGFV,RL4046 Copyright All product information within this document is subject to ABB Motors and Mechanical Inc. copyright protection,
More informationSwitchgear Skid, C1192
CUSTOM SOLUTIONS 15kV Modular Stairs stored on floor in front of battery bay Ground grid stored on front tongue of trailer Stairs deployed for unit access Storage box for fencing materials and other parts
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationDescriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv
Descriptive Bulletin R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG TM is truly the next generation in medium voltage vacuum circuit breaker
More informationProtection Equipment
Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More informationDescriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv
Descriptive Bulletin R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG is truly the next generation in medium voltage vacuum circuit breaker technology.
More informationProduct Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationSelection and application guide
Selection and application guide 30A 400A fusible panelboards Coordination Panelboard www.usa.siemens.com/fusiblepanel Coordination panelboards Table of contents Subject Page Specifications 2-3 Enclosure
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationAir Circuit Breakers
Siemens AG 203 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23
More informationSwitches Unlimited Phone: * Fax:
For Info: sales@switchesunlimited.com www.switchesunlimited.com Phone: 800-1-0487 Fax: 718-67-6370 Page -4 Page -8 THREE-POLE CONTACTORS IEC Ith ratings in AC1 duty at 40 C: 16 to 1600A IEC Ie ratings
More informationches UL File No. E101598
Instrument Transformers, Inc. Series Series 95 95 Swit Switches ches UL File No. E101598 INSTRUMENT AND CONTRC ONTROL OL s Instrument and Control Switch is a heavy-duty rotary switch that satisfies the
More informationPage 2-4 Page 2-8. Page Page 2-13
Page -4 Page -8 THREE-POLE CONTACTORS IEC Ith ratings in AC1 duty at 40 C: 16 to 1600A IEC Ie ratings in AC3 440V duty: 6 to 630A IEC Power ratings in AC3 400V duty:. to 335kW UL/CSA ratings: 3 to 500HP
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More informationMULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers
IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when
More informationDuraGard Waterproof Connections
In this section... DuraGard Waterproof Connections DuraGard Overview...54 57 20 Amp...58 59 30 Amp...60 61 50 Amp...62 63 60 Amp...64 Accessories...65 66 Safety Interlocks...67 Dimensions...68 Engineering
More informationMedium Voltage Equipment. Section 15.
MV One Line...15-2 Motor Control Medium Voltage (Limitamp ) Introduction, Features, Types, Options, References...15-3 Specifications, Ratings, Equipment Reference Publications...15-4 Product Scope...15-5
More informationDetail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order
Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationNo-barrier design Self-extinguishing materials Front-connected, back-connected and flush-mounted styles Blades operate independently or can be ganged together Recognized by UL and cul STATES Type have
More informationAir Circuit Breakers
Siemens AG 204 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23
More informationDuraGard Waterproof Connections
In this section... DuraGard Waterproof Connections DuraGard Overview...54 57 20 Amp...58 59 30 Amp...60 61 50 Amp...62 63 60 Amp...64 Accessories...65 66 Safety Interlocks...67 Dimensions...68 Engineering
More informationCENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies
Selection Checklist CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies Use this checklist to help you configure your CENTERLINE 2500 Motor Control Center. You can type in the fields
More informationQuik-Spec Coordination Panelboard Specifications
Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY
More informationand legacy Motor Control Center Aftermarket Renewal Parts Catalog
tiastar TM and legacy Motor Control Center Aftermarket Renewal Parts Catalog Game Changing Innovation www.usa.siemens.com/mcc Answers for industry. Table of Contents Ordering Processes 1-2 Section Parts
More informationCONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS
LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low
More informationPower/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers
Section Contents 9 Section 9 Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers Page INTRODUCTION... 9- APPLICATION... 9- TESTING... 9- LONGER LIFE... 9- QUALITY... 9- INSTALLATION...
More informationGE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc
GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4
More informationIN2 Enclosed Switches and Circuit Breakers
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers
More informationBasics of Medium Voltage Motor Control Starter Power Components & Starter Types
Basics of Medium Voltage Motor Control Starter Power Components & Starter Types Larry Dalton Lead Operation Specialist Jude Hernandez - Application Engineer GE Industrial Solutions Slide # 1, Rev 3, 11/8/16
More informationAF40... AF96 3-pole contactors Technical data
Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional
More informationPublication No.: PSG
TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06
More information3/2 Introduction. Unequipped Distribution Boards (Flat Pack) 3/6 8GK1 surface-mounting distribution boards
ALPHA 400 - DIN Wall-Mounted Distribution Boards /2 Introduction Unequipped Distribution Boards (Flat Pack) /6 8GK1 surface-mounting distribution boards Pre-Assembled Unequipped Distribution Boards /7
More informationMK IV HORIZONTAL SLIDING DOOR REPLACEMENT PARTS BOOK
MK IV HORIZONTAL SLIDING DOOR REPLACEMENT PARTS BOOK BI-PARTING DOOR SHOWN-SINGLE DOOR SIMILAR JAMISON DOOR COMPANY P.O. BOX 70 HAGERSTOWN, MARYLAND 21740 1-800-532-3667 301-733-3100 INTERNET: http://www.jamisondoor.com
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationMCBs and accessories are certified under CSA C22.2 No. 235 per File LR Tripping characteristics
Miniature circuit breakers General information General information Miniature circuit breakers (MCBs) are used throughout the world in all types of electrical installations. ABB MCBs are recognized for
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationBulletin 1489 Circuit Breakers. Selection Guide
Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable
More informationSecoVac * R Retrofill
GE Energy Connections DEA-614 Brochure SecoVac * R Retrofill 5kV-15kV Replacement Vacuum Circuit Breakers: The Next Generation of Reliability, Performance and Sustainability GE GE is a diversified organization
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationGE Energy Connections Industrial Solutions. DET-882 Application and Technical Guide. SecoGear
GE Energy Connections Industrial Solutions DET-882 Application and Technical Guide SecoGear Me - Switchgear HAZARD CLASSIFICATIONS The following important highlighted information appears throughout this
More informationSECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE PROJECT ENGINEER STANDARDS...
SECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE... 1 2. PROJECT ENGINEER... 1 3. STANDARDS... 1 4. RATINGS... 1 5. MATERIAL AND WORKMANSHIP... 2 6. BUSHINGS...
More informationAdd-on blocks and accessories For BG series mini-contactors For BF series contactors For B series contactors...
Three-pole versions up to 630A in IEC AC3 duty Four-pole versions up to 1600A in IEC AC1 duty Versions for power factor correction up to 100kvar at 400VAC Four-pole versions with NO+NC or 4NC main poles
More informationGE CONSUMER & INDUSTRIAL
GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B
More informationFMotor Circuit Controllers
Technical Information Motor Circuit Controller IEC Performance Data Catalog Number KTA7-25S...32S 0.16A 0.25A 0.4A 0.63A 1A 1.6A 2.5A 4A 6.3A 10A 16A 20A 25A 29A 32A Rated Operational Current, I e [A]
More informationProduct Information Packet IDDRPM404006R1 400HP,1175/2000RPM,460V,3PH,DPGFV,RL4034
Product Information Packet IDDRPM404006R1 400HP,1175/2000RPM,460V,3PH,DPGFV,RL4034 Copyright All product information within this document is subject to ABB Motors and Mechanical Inc. copyright protection,
More informationShort form catalogue. Motor protection & control
Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59
More informationProtectors. 35mm DIN rail snap-on mounting. Wide range of accessories
Manual motor protectors Manual motor protectors Manual motor Protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL Listed and CSA certified
More informationIntroduction. Features. Intelligent Technologies Motor Control Center Structures
Intelligent Technologies Technical Data New Information Description Page Intelligent Technologies General............................................. 2 s.......................................................
More informationBETA Switching Switches and Light Indicators
Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationPRICING. Multi 9, Compact, Masterpact, Interpact, and Vigirex Circuit Protection Products. Class 600. October 2004
PRICING October 2004 Multi 9, Compact, Masterpact, Interpact, and Vigirex Circuit Protection Products Class 600 CONTENTS Description Page Multi 9 Supplementary Protectors and Miniature Circuit Breakers.............3
More informationExtensible Unit - VCE2a
ELECTRICAL INDUSTRIAL COMPANY (EICo) LUCY SWITCHGEAR Extensible Unit - VCE2a (Sabre) Electrical Industrial Company (EICo) Lucy Switchgear Extensible Unit VCE2a Front Panel: ELECTRICAL INDUSTRIAL COMPANY
More informationAF09... AF30 3-pole Contactors up to 25 HP / 600 VAC
AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24
More informationKuhlman Electric Corporation Volt Instrument Transformers
Kuhlman Electric Corporation 34500 Volt Instrument Transformers 34500 Volt Table of Contents Description Model Page Wound, Dry-Type VT Y (High Accuracy available) PTT-200-9710(H) 3-4 Wound, Oil-Filled
More informationMEDIUM VOLTAGE AIS ANSI SWITCHGEAR Advance and Advance 27. Non-arc-resistant MV ANSI switchgear
2018 MEDIUM VOLTAGE AIS ANSI SWITCHGEAR Non-arc-resistant MV ANSI switchgear Agenda Ratings, dimensions and qualifications MV ANSI circuit breakers for Design features Auxiliary compartments Enclosures
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationDescriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications
Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter
More information