1 Siemens AG 203 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23 4-pole, fixed-mounted versions /30 4-pole, withdrawable versions /37 /44 Accessories and spare parts 3WL non-automatic air circuit breakers up to 4000 A (DC) /66 3- and 4-pole, fixed-mounted versions /67 3- and 4-pole, withdrawable versions /69 Accessories and spare parts Ch. 2 3KC ATC5300 transfer control devices For further technical product information: Service&Support portal: technical-support. Product list: Technical specifications Entry list: Updates / Downloads / FAQs / Manuals / Operating instructions / Characteristic curves / Certificates Siemens LV
2 * +, - Siemens AG 203 Introduction Overview Devices Page Applications/ Individual components Standards Used in Non-residential buildings Residential buildings Industry 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /9... /36 As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations. For switching and protecting motors, capacitors, generators, transformers, busbars and cables. IEC , climate-proof according to IEC WL non-automatic air circuit breakers up to 4000 A (DC) /66... /68 As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations. For switching and protecting motors, capacitors, generators, transformers, busbars and cables. IEC , climate-proof according to IEC ! ) 5 - ' ' > Protective devices with device holder and optional measurement function (ETU) /5 Electronic Trip Unit with protection functions LI, LSI, LSING and LSIN(G), with or without measurement function Plus Rating Plugs /5 For rated currents I n from 250 A to 6300 A. The maximum rated current of the circuit breaker must not be exceeded. As for circuit breakers -- As for circuit breakers -- 5 /. ) 6 " # Ground-fault modules /5 With alarm and tripping As for circuit breakers --.. C / ) ) ) 4 ) ) 4 J C I # " 6 4 2! JC 5 -! " # Displays /5 4-line displays for ETU45B As for circuit breakers $ ' Current transformers for N conductor protection /5 Internal transformers for N conductors, external transformers for N conductors As for circuit breakers ' '. % EMC filters /5 Common-mode interference suppressor filters More accessories for Electronic Trip Units /52 Sealable and lockable covers, automatic reset of the reclosing lockout, remote reset solenoid, retrofittable internal CubicleBUS wiring, retrofittable internal wiring for connection of external N and G transformers As for circuit breakers -- As for circuit breakers ' ' ' = NSE0_00987 NSE0_00982 Locking devices /52 Interlocking set for mechanical ON/OFF, As for circuit breakers -- locking devices against unauthorized closing in operator panels/for withdrawable circuit breakers, locking devices for operating mechanism handle with padlock, locking devices to prevent movement of the withdrawable circuit breakers, interlocking systems Locking mechanisms /53 To prevent movement of the withdrawable As for circuit breakers -- circuit breakers into disconnected position, to prevent opening of the cabinet door in ON position, to prevent opening of the cabinet door, to prevent movement with the cabinet door open Interlocks /54 Mutual mechanical interlocking, couplings on the circuit breaker (with ring) for mutual interlocking, Bowden wire As for circuit breakers -- NSE0_00989 /2 Siemens LV
3 Siemens AG 203 Introduction Devices Page Applications/ Individual components Standards Used in Non-residential buildings Residential buildings Industry Test devices /54 Manual tester Release 2 for Electronic As for circuit breakers -- Trip Units, function testers Capacitor storage devices /54 For shunt releases As for circuit breakers ' ' # = 5 - $ ' Indicators, control elements /55 Ready-to-close signaling switches, As for circuit breakers -- signaling switches, tripped signaling switches, operating cycles counters, stored energy status signaling switches, position signaling switches for guide frames, electric ON buttons, motor shutdown switches, EMERGENCY-STOP buttons Auxiliary conductor connections /56 Male connectors for circuit breakers, extension for 000 V male connector versions, male connectors and extension for 000 V, auxiliary supply connectors for circuit breakers or guide frames, coding kits, sliding contacts for guide frames, blanking blocks for circuit breakers As for circuit breakers -- Auxiliary releases /57 Closing solenoids/shunt releases, As for circuit breakers -- undervoltage releases Operating mechanisms /57 Motorized operating mechanism As for circuit breakers -- Auxiliary contacts /57 Auxiliary switch blocks As for circuit breakers -- Door sealing frames, hoods, shutters /58 Door sealing frames, IP55 protective covers, shutters As for circuit breakers -- Arc chutes /58 Arc chutes, arc chute covers As for circuit breakers -- Coding for withdrawable version /58 By customer, for 36 coding variants As for circuit breakers -- Grounding connections /59 Grounding connection between the guide frame and the withdrawable circuit breaker, contacting modules for withdrawable circuit breakers Support brackets /59 For mounting fixed-mounted circuit breakers on vertical plane CubicleBUS modules /59 Digital and analog input and output modules, Zone Selective Interlocking modules Parameterization systems /59 Breaker Data Adapter (BDA), BDA Plus, Connection cables for BDA Plus, powerconfig parameterization software Accessories for communications /60 Factory-fitted cables for CubicleBUS modules, SENTRON manuals for communication solutions, voltage transformers Retrofitting and spare parts /60 PROFIBUS retrofit kits, COM5 PROFIBUS modules, COM6 MODBUS modules, MODBUS IEC retrofit kits, Breaker Status Sensor (BSS), measurement function Plus As for circuit breakers -- As for circuit breakers -- As for circuit breakers -- As for circuit breakers -- As for circuit breakers -- As for circuit breakers -- Main conductor connections, fixed-mounted Main conductor connections, withdrawable /6 /62 Front-accessible main connections with double or single hole, rear vertical main connections, rear horizontal main connections, circuit connecting flanges, supports for front and DIN connecting bars As for circuit breakers -- Siemens LV /3
4 Rating Plug Siemens AG 203 Introduction I Air circuit breakers 3WL air circuit breakers/non-automatic air circuit breakers up to 6300 A (AC), IEC I, II, III II Rated current I n A 630, 800, 000, 250, 600, 2000, 2500, 3200, 4000, 5000, 6300 Number of poles 3-pole, 4-pole 3-pole, 4-pole Rated operational voltage U e Rated ultimate short-circuit breaking capacity at 500 V AC Endurance Mounting position II V AC V DC ka Operating cycles /000/50 -- I 55/66/85 3WL non-automatic air circuit breakers up to 4000 A (DC) Transfer control devices 3KC ATC5300 transfer control devices 000, 2000, 4000 see chapter "Monitoring devices" II 66/80/00 III 00/50 (3-pole), 30 (4-pole) Up to III /25/20 (at 300/600/000 V DC) ATC5300 H NSS0_00535 Degree of protection With cover IP55 IP55 Without cover IP4 IP4 (with door sealing frame) Dimensions W mm 320/40 460/ /94 460/590 3-/4-pole Fixedmounted D mm H mm B T 29 Withdrawable NSE0_0006a NSE0_00062a H mm D mm NSE0_0006a NSE0_00062a Electronic Trip Units for 3WL air circuit breakers Type ETU5B ) ETU25B ETU27B ETU45B ETU76B Overload protection Short-time delayed -- short-circuit protection Instantaneous short-circuit protection Neutral conductor protection Ground-fault protection Zone Selective Interlocking LCD, 4-line LCD, graphic Communication Measurement function Plus Selectable parameter sets Parameters freely programmable CubicleBUS Standard -- Not available Optional ) ETU5B cannot be used with 3WL air circuit breakers, size III. NSE0_006a NSE0_007a NSE0_008a NSE0_009a 3WL air circuit breakers/non-automatic air circuit breakers according to UL 489 up to 5,000 A, see Catalog LV 6. 3KC ATC5300 transfer control devices, see chapter "Monitoring Devices". NSE0_0a /4 Siemens LV
5 Siemens AG 203 Introduction Breaking capacity I II III Type 3WL 3WL2 3WL3 Breaking capacity class N S H N S H H C C N S H N S H H C 3-pole 4-pole C Short-circuit breaking capacity Rated operational voltage U e up to 45 V AC I cu ka I cs ka I cm ka Rated operational voltage U e up to 500 V AC I cu ka I cs ka I cm ka Rated operational voltage U e up to 690 V AC I cu ka I cs ka I cm ka Rated operational voltage U e up to 000 V/50 V AC I cu ka ) ) 70 4) I cs ka ) ) 70 4) I cm ka ) ) 54 4) Rated short-time withstand current I cw of the circuit breakers 3) 0.5 s ka s ka s ka ) /70 2) s ka ) /65 2) Short-circuit breaking capacity I cc of the non-automatic air circuit breakers Up to 500 V AC ka Up to 690 V AC ka Up to 000 V /50 V AC ka ) ) 50 4) 70 4) 70 4) Type Breaking capacity class Short-circuit breaking capacity Up to 220 V DC I cc Up to 300 V DC I cc Up to 600 V DC I cc Up to 000 V DC I cc Rated short-time withstand current I cw 0.5 s s 2 s 3 s ka ka ka ka II 3WL2 DC DC ka -- ka 35 5) /30 6) /25 7) /20 8) ka -- ka -- N S H C DC Note: Circuit breaker with ECO breaking capacity N Circuit breaker with standard breaking capacity S Circuit breaker with high breaking capacity H Circuit breakers with very high breaking capacity C Non-automatic air circuit breakers with DC breaking capacity These breaking capacities are indicated in the corresponding tables by the symbols shown on orange backgrounds. For further technical specifications see the configuration manual "". Free download from: ) II with I n max 2500 A. 2) II with I n max = 3200 A and I n max = 4000 A. 3) At a rated voltage of 690 V the I cw value of the circuit breaker cannot be greater than the I cu or I cs value at 690 V. Abbreviations* English long text Explanation (functions) L Long Time Delay Overload protection S Short Time Delay Short-circuit protection (short-time delayed) I Instantaneous Short-circuit protection (instantaneous) N Neutral Protection Neutral conductor protection G Ground Fault Ground-fault protection * Designations according to IEC , Appendix K. 4) Rated operational voltage U e = 50 V. 5) At U e = 220 V DC. 6) At U e = 300 V DC. 7) At U e = 600 V DC. 8) At U e = 000 V DC. 9) Values also apply to 690 V + 20 % version with Z-option "A6". Siemens LV /5
6 Siemens AG 203 Introduction 3WL air circuit breakers: Superior individual products integrated into uniform power distribution systems - up to and including industry-specific industrial and infrastructure solutions NSE0_0887d $ Guide frame (pages /45 to /50) % Main circuit connection front, flange, horizontal, vertical (pages /42, /6 and /62) & Position signaling switch (pages /40 and /55) ( Grounding connection, leading (page /59) ) Shutters (pages /40 and /58) * COM5 PROFIBUS module or COM6 MODBUS module (pages /40 and /60) + External CubicleBUS modules (page /59), Closing coil, auxiliary release (pages /37, /39 and /57) - Auxiliary conductor plug-in system (pages /4 and /56). Auxiliary switch block (pages /37 and /57) / Door sealing frame (pages /39 and /58) 0 Interlocking set for mechanical ON/OFF (page /52) Transparent panel, function insert (page /52) 2 EMERGENCY-STOP pushbutton, key operated (page /55) 3 Motorized operating mechanism (pages /39 and /57) 4 Operating cycles counters (pages /39 and /55) 5 Breaker status sensor (BSS) (pages /40 and /60) 6 Protective device with device holder, Electronic Trip Unit (ETU) (page /5) 7 Remote reset solenoid (pages /39 and /52) 8 Breaker data adapter (BDA Plus) (page /59) 9 Four-line display (page /5) : Ground-fault protection module (page /5) ; Rating plug (pages /38 and /5) < Measurement function module (pages /40 and /5) = Air circuit breaker (pages /9 to /36) /6 Siemens LV
7 Siemens AG 203 Introduction Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit) 8 Ethernet 6 7 PROFIBUS from Release 2 7 CubicleBUS NSE0_005l VL molded case circuit breakers Electronic Trip Unit LCD Electronic Trip Unit COM20 Release 2 PROFIBUS module ) Including ZSS BDA Plus with Ethernet interface 3WL air circuit breakers COM5 PROFIBUS module 2) Breaker status sensor (BSS) Electronic Trip Unit Measurement function Plus Zone Selective Interlocking modules Digital output module with relay contacts Digital output module with relay contacts, configurable Analog output modules Digital input module powerconfig as of V2.3 PLC, e. g. SIMATIC S7 e. g. Powermanager or SIMATIC powerrate 7KM PAC measuring devices ) For a MODBUS-RTU connection the COM2 module is required. 2) For a MODBUS-RTU connection the COM6 module is required. Features Coordinated communication concept using the PROFIBUS DP or MODBUS, ranging from 6 A to 6300 A with 3VL molded case circuit breakers and 3WL air circuit breakers The high level of modularity of circuit breakers and accessories allows easy retrofitting of all communication components Significant additional benefits for the switchgear due to the possibility of linking up external input and output modules to the circuit breaker-internal CubicleBUS of the 3WL Innovative software products for parameterization, operation, monitoring, and diagnostics of circuit breakers, both locally or via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet Complete integration of the circuit breakers into the Totally Integrated Power and Totally Integrated Automation solutions Communication: For air circuit breakers with optional communication function (ETU45B or ETU76B Electronic Trip Unit) see pages /9 to /36. For accessories see pages /59 and /60. For more information see also chapters "Measuring Devices and Power Monitoring" and "Software". Siemens LV /7
8 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC Introduction Benefits Low space requirements The 3WL air circuit breakers require very little space. I devices (up to 2000 A) fit into a 400 mm wide switchgear panel. III devices (up to 6300 A) are the smallest of their kind and with their construction width of 704 mm fit into an 800 mm wide switchgear panel. Modular design Components like auxiliary releases, motorized operating mechanisms, Electronic Trip Units, current transformers, auxiliary circuit signaling switches, automatic reset devices, interlocks and engagement operating mechanisms can all be exchanged or retrofitted at a later stage, thus allowing the circuit breaker to be adapted to new, changing requirements. The main contact elements can all be replaced in order to increase the endurance of the circuit breaker. Retrofittable modules for Electronic Trip Units Modularity is one of the main features of the new 3WL air circuit breakers. Special LCDs, ground-fault modules, rating plugs and communication modules for the Electronic Trip Units are available for fast and easy retrofitting and adaptation to changing requirements. Communication/measurement functions The use of modern communication-capable circuit breakers opens up completely new possibilities in terms of start-up, parameterization, diagnostics, maintenance and operation. This allows many different ways of reducing costs and improving productivity in industrial plants, buildings and infrastructure projects to be achieved: Conductor cross-sections Fast and reliable parameterization Timely information and response can prevent plant stoppages Effective diagnostics management Measured values are the basis for efficient load management, for drawing up power demand profiles and for allocating energy to cost centers Preventive maintenance reduces the risk of expensive plant downtimes Measurement function with a very wide range of measured values, such as current, voltage, energy, power etc. Can be used in 000 V AC and 690 V IT networks Applications As incoming-feeder, distribution, tie, and outgoing-feeder circuit breakers in electrical installations. For switching and protecting motors, capacitors, generators, transformers, busbars and cables. When connected to an electronic I&C system, the air circuit breakers offer a wide range of options for monitoring network events. The extensive, coordinated SENTRON range of devices covers applications between 6 A and 6300 A with molded case and air circuit breakers. The AC devices are available as circuit breakers and non-automatic air circuit breakers. DC devices are only available as nonautomatic air circuit breakers. Standards 3WL air circuit breakers comply with: IEC Climate-proof according to IEC Versions with UL 489 also available, see Catalog LV 6. For further standards, see Appendix. I II Type Up to 3WL 2 3WL 6 3WL 20 3WL2 08 3WL2 0 3WL2 2 3WL2 6 3WL2 20 3WL 0 Permissible load for withdrawable versions at rear horizontal main connections Main conductor minimum cross-sections Up to 55 C (Cu bare) Up to 60 C (Cu bare) ) Up to 70 C (Cu black painted) ) Copper bars, bare Copper bars, painted black A 000 A 000 A 000 Unit(s) mm Unit(s) mm ) II III Type 3WL2 25 3WL2 32 3WL2 40 3) 3WL3 40 3WL3 50 3WL3 63 3) Permissible load for withdrawable versions at rear horizontal main connections Main conductor minimum cross-sections Up to 55 C (Cu bare) Up to 60 C (Cu bare) ) Up to 70 C (Cu black painted) ) Copper bars, bare Copper bars, painted black A 2500 A 2500 A 2280 Unit(s) 2 mm Unit(s) 2 mm ) ETU76B can be used up to max. 55 C. 2) At breaking capacity H: 600 A up to 70 C 3) With rear vertical connections 4) II, 3-pole, in fixed-mounted version 5) Minimum main conductor cross-sections for 4-pole withdrawable circuit breakers: 4 20 mm 0 mm ) ) x 00 x x 00 x x 20 x /8 Siemens LV
9 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Selection and ordering data Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 55/66 ka at 500 V, I cu = I cs ECO breaking capacity N N Basic price A A ka kg Horizontal main circuit connection I WL 06-2@@32-@@@@ unit WL 08-2@@32-@@@@ unit WL 0-2@@32-@@@@ unit WL 2-2@@32-@@@@ unit WL 6-2@@32-@@@@ unit WL 20-2@@32-@@@@ unit II WL2 08-2@@32-@@@@ unit WL2 0-2@@32-@@@@ unit WL2 2-2@@32-@@@@ unit WL2 6-2@@32-@@@@ unit WL2 20-2@@32-@@@@ unit WL2 25-2@@32-@@@@ unit WL2 32-2@@32-@@@@ unit Vertical main circuit connection I WL 06-2@@3-@@@@ unit WL 08-2@@3-@@@@ unit WL 0-2@@3-@@@@ unit WL 2-2@@3-@@@@ unit WL 6-2@@3-@@@@ unit WL 20-2@@3-@@@@ unit II WL2 08-2@@3-@@@@ unit WL2 0-2@@3-@@@@ unit WL2 2-2@@3-@@@@ unit WL2 6-2@@3-@@@@ unit WL2 20-2@@3-@@@@ unit WL2 25-2@@3-@@@@ unit WL2 32-2@@3-@@@@ unit WL2 40-2@@3-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI 6) BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. 6) ETU5B cannot be used with 3WL air circuit breakers, size III. Siemens LV /9
10 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 55/66 ka at 500 V, I cu = I cs ECO breaking capacity N N Basic price A A ka kg Front main circuit connection, single hole I WL 06-2@@33-@@@@ unit WL 08-2@@33-@@@@ unit WL 0-2@@33-@@@@ unit WL 2-2@@33-@@@@ unit WL 6-2@@33-@@@@ unit II WL2 08-2@@33-@@@@ unit WL2 0-2@@33-@@@@ unit WL2 2-2@@33-@@@@ unit WL2 6-2@@33-@@@@ unit WL2 20-2@@33-@@@@ unit WL2 25-2@@33-@@@@ unit WL2 32-2@@33-@@@@ unit Front main circuit connection, double hole I WL 06-2@@34-@@@@ unit WL 08-2@@34-@@@@ unit WL 0-2@@34-@@@@ unit WL 2-2@@34-@@@@ unit WL 6-2@@34-@@@@ unit WL 20-2@@34-@@@@ unit II WL2 08-2@@34-@@@@ unit WL2 0-2@@34-@@@@ unit WL2 2-2@@34-@@@@ unit WL2 6-2@@34-@@@@ unit WL2 20-2@@34-@@@@ unit WL2 25-2@@34-@@@@ unit WL2 32-2@@34-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI 6) BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. 6) ETU5B cannot be used with 3WL air circuit breakers, size III. /0 Siemens LV
11 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 66/80 ka at 500 V, I cu = I cs standard breaking capacity S S Basic price A A ka kg Horizontal main circuit connection I WL 06-3@@32-@@@@ unit WL 08-3@@32-@@@@ unit WL 0-3@@32-@@@@ unit WL 2-3@@32-@@@@ unit WL 6-3@@32-@@@@ unit WL 20-3@@32-@@@@ unit II WL2 08-3@@32-@@@@ unit WL2 0-3@@32-@@@@ unit WL2 2-3@@32-@@@@ unit WL2 6-3@@32-@@@@ unit WL2 20-3@@32-@@@@ unit WL2 25-3@@32-@@@@ unit WL2 32-3@@32-@@@@ unit Vertical main circuit connection I WL 06-3@@3-@@@@ unit WL 08-3@@3-@@@@ unit WL 0-3@@3-@@@@ unit WL 2-3@@3-@@@@ unit WL 6-3@@3-@@@@ unit WL 20-3@@3-@@@@ unit II WL2 08-3@@3-@@@@ unit WL2 0-3@@3-@@@@ unit WL2 2-3@@3-@@@@ unit WL2 6-3@@3-@@@@ unit WL2 20-3@@3-@@@@ unit WL2 25-3@@3-@@@@ unit WL2 32-3@@3-@@@@ unit WL2 40-3@@3-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI 6) BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. 6) ETU5B cannot be used with 3WL air circuit breakers, size III. Siemens LV /
12 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 66/80 ka at 500 V, I cu = I cs standard breaking capacity S S Basic price A A ka kg Front main circuit connection, single hole I WL 06-3@@33-@@@@ unit WL 08-3@@33-@@@@ unit WL 0-3@@33-@@@@ unit WL 2-3@@33-@@@@ unit WL 6-3@@33-@@@@ unit II WL2 08-3@@33-@@@@ unit WL2 0-3@@33-@@@@ unit WL2 2-3@@33-@@@@ unit WL2 6-3@@33-@@@@ unit WL2 20-3@@33-@@@@ unit WL2 25-3@@33-@@@@ unit WL2 32-3@@33-@@@@ unit Front main circuit connection, double hole I WL 06-3@@34-@@@@ unit WL 08-3@@34-@@@@ unit WL 0-3@@34-@@@@ unit WL 2-3@@34-@@@@ unit WL 6-3@@34-@@@@ unit WL 20-3@@34-@@@@ unit II WL2 08-3@@34-@@@@ unit WL2 0-3@@34-@@@@ unit WL2 2-3@@34-@@@@ unit WL2 6-3@@34-@@@@ unit WL2 20-3@@34-@@@@ unit WL2 25-3@@34-@@@@ unit WL2 32-3@@34-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI 6) BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. 6) ETU5B cannot be used with 3WL air circuit breakers, size III. /2 Siemens LV
13 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 85/00 ka at 500 V, I cu = I cs high breaking capacity H H Basic price A A ka kg Horizontal main circuit connection I WL 06-4@@32-@@@@ unit WL 08-4@@32-@@@@ unit WL 0-4@@32-@@@@ unit WL 2-4@@32-@@@@ unit WL 6-4@@32-@@@@ unit WL 20-4@@32-@@@@ unit II WL2 08-4@@32-@@@@ unit WL2 0-4@@32-@@@@ unit WL2 2-4@@32-@@@@ unit WL2 6-4@@32-@@@@ unit WL2 20-4@@32-@@@@ unit WL2 25-4@@32-@@@@ unit WL2 32-4@@32-@@@@ unit III WL3 40-4@@32-@@@@ unit WL3 50-4@@32-@@@@ unit Vertical main circuit connection I WL 06-4@@3-@@@@ unit WL 08-4@@3-@@@@ unit WL 0-4@@3-@@@@ unit WL 2-4@@3-@@@@ unit WL 6-4@@3-@@@@ unit WL 20-4@@3-@@@@ unit II WL2 08-4@@3-@@@@ unit WL2 0-4@@3-@@@@ unit WL2 2-4@@3-@@@@ unit WL2 6-4@@3-@@@@ unit WL2 20-4@@3-@@@@ unit WL2 25-4@@3-@@@@ unit WL2 32-4@@3-@@@@ unit WL2 40-4@@3-@@@@ unit III WL3 40-4@@3-@@@@ unit WL3 50-4@@3-@@@@ unit WL3 63-4@@3-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI 6) BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. 6) ETU5B cannot be used with 3WL air circuit breakers, size III. Siemens LV /3
14 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 85/00 ka at 500 V, I cu = I cs high breaking capacity H H Basic price A A ka kg Front main circuit connection, single hole II WL2 08-4@@33-@@@@ unit WL2 0-4@@33-@@@@ unit WL2 2-4@@33-@@@@ unit WL2 6-4@@33-@@@@ unit WL2 20-4@@33-@@@@ unit WL2 25-4@@33-@@@@ unit WL2 32-4@@33-@@@@ unit III WL3 40-4@@33-@@@@ unit Front main circuit connection, double hole I WL 06-4@@34-@@@@ unit WL 08-4@@34-@@@@ unit WL 0-4@@34-@@@@ unit WL 2-4@@34-@@@@ unit WL 6-4@@34-@@@@ unit WL 20-4@@34-@@@@ unit II WL2 08-4@@34-@@@@ unit WL2 0-4@@34-@@@@ unit WL2 2-4@@34-@@@@ unit WL2 6-4@@34-@@@@ unit WL2 20-4@@34-@@@@ unit WL2 25-4@@34-@@@@ unit WL2 32-4@@34-@@@@ unit III WL3 40-4@@34-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI 6) BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. 6) ETU5B cannot be used with 3WL air circuit breakers, size III. /4 Siemens LV
15 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, fixed-mounted versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 50 ka at 500 V, I cu = I cs very high breaking capacity C C Basic price A A ka kg Horizontal main circuit connection III WL3 40-5@@32-@@@@ unit WL3 50-5@@32-@@@@ unit Vertical main circuit connection III WL3 40-5@@3-@@@@ unit WL3 50-5@@3-@@@@ unit WL3 63-5@@3-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 2) Electronic Trip Units Versions without ground-fault protection ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 3) EB ETU45B: Protection functions LSIN 3) FB ETU76B: Protection functions LSIN 3) NB Versions with ground-fault protection ETU27B: Protection functions LSING 4) DG ETU45B: Protection functions LSING 3)5) EG ETU45B: Protection functions LSING 3)5) FG ETU76B: Protection functions LSING 3)5) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 3) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 4) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 5) ETU45B and ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. Siemens LV /5
16 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, withdrawable versions Selection and ordering data Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 55/66 ka at 500 V, I cu = I cs ECO breaking capacity N N Basic price A A ka kg Without guide frames 2) (for guide frames, see page /45 to /50) I WL 06-2@@35-@@@@ unit WL 08-2@@35-@@@@ unit WL 0-2@@35-@@@@ unit WL 2-2@@35-@@@@ unit WL 6-2@@35-@@@@ unit WL 20-2@@35-@@@@ unit II WL2 08-2@@35-@@@@ unit WL2 0-2@@35-@@@@ unit WL2 2-2@@35-@@@@ unit WL2 6-2@@35-@@@@ unit WL2 20-2@@35-@@@@ unit WL2 25-2@@35-@@@@ unit WL2 32-2@@35-@@@@ unit With guide frames, horizontal main circuit connection I WL 06-2@@36-@@@@ unit WL 08-2@@36-@@@@ unit WL 0-2@@36-@@@@ unit WL 2-2@@36-@@@@ unit WL 6-2@@36-@@@@ unit WL 20-2@@36-@@@@ unit II WL2 08-2@@36-@@@@ unit WL2 0-2@@36-@@@@ unit WL2 2-2@@36-@@@@ unit WL2 6-2@@36-@@@@ unit WL2 20-2@@36-@@@@ unit WL2 25-2@@36-@@@@ unit WL2 32-2@@36-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 3) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 4) EB ETU45B: Protection functions LSIN 4) FB ETU76B: Protection functions LSIN 4) NB Versions with ground-fault protection ETU27B: Protection functions LSING 5) DG ETU45B: Protection functions LSING 4)6) EG ETU45B: Protection functions LSING 4)6) FG ETU76B: Protection functions LSING 4)6) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) Z options which are installed on the guide frame are not available. 3) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 4) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 5) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. /6 Siemens LV
17 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, withdrawable versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 55/66 ka at 500 V, I cu = I cs ECO breaking capacity N N Basic price A A ka kg With guide frames, vertical main circuit connection I WL 06-2@@37-@@@@ unit WL 08-2@@37-@@@@ unit WL 0-2@@37-@@@@ unit WL 2-2@@37-@@@@ unit WL 6-2@@37-@@@@ unit WL 20-2@@37-@@@@ unit II WL2 08-2@@37-@@@@ unit WL2 0-2@@37-@@@@ unit WL2 2-2@@37-@@@@ unit WL2 6-2@@37-@@@@ unit WL2 20-2@@37-@@@@ unit WL2 25-2@@37-@@@@ unit WL2 32-2@@37-@@@@ unit WL2 40-2@@37-@@@@ unit With guide frames, connecting flanges I WL 06-2@@38-@@@@ unit WL 08-2@@38-@@@@ unit WL 0-2@@38-@@@@ unit WL 2-2@@38-@@@@ unit WL 6-2@@38-@@@@ unit WL 20-2@@38-@@@@ unit II WL2 08-2@@38-@@@@ unit WL2 0-2@@38-@@@@ unit WL2 2-2@@38-@@@@ unit WL2 6-2@@38-@@@@ unit WL2 20-2@@38-@@@@ unit WL2 25-2@@38-@@@@ unit WL2 32-2@@38-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 3) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 4) EB ETU45B: Protection functions LSIN 4) FB ETU76B: Protection functions LSIN 4) NB Versions with ground-fault protection ETU27B: Protection functions LSING 5) DG ETU45B: Protection functions LSING 4)6) EG ETU45B: Protection functions LSING 4)6) FG ETU76B: Protection functions LSING 4)6) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) Z options which are installed on the guide frame are not available. 3) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 4) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 5) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. Siemens LV /7
18 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, withdrawable versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 66/80 ka at 500 V, I cu = I cs standard breaking capacity S S Basic price A A ka kg Without guide frames 2) (for guide frames, see page /45 to /50) I WL 06-3@@35-@@@@ unit WL 08-3@@35-@@@@ unit WL 0-3@@35-@@@@ unit WL 2-3@@35-@@@@ unit WL 6-3@@35-@@@@ unit WL 20-3@@35-@@@@ unit II WL2 08-3@@35-@@@@ unit WL2 0-3@@35-@@@@ unit WL2 2-3@@35-@@@@ unit WL2 6-3@@35-@@@@ unit WL2 20-3@@35-@@@@ unit WL2 25-3@@35-@@@@ unit WL2 32-3@@35-@@@@ unit With guide frames, horizontal main circuit connection I WL 06-3@@36-@@@@ unit WL 08-3@@36-@@@@ unit WL 0-3@@36-@@@@ unit WL 2-3@@36-@@@@ unit WL 6-3@@36-@@@@ unit WL 20-3@@36-@@@@ unit II WL2 08-3@@36-@@@@ unit WL2 0-3@@36-@@@@ unit WL2 2-3@@36-@@@@ unit WL2 6-3@@36-@@@@ unit WL2 20-3@@36-@@@@ unit WL2 25-3@@36-@@@@ unit WL2 32-3@@36-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 3) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 4) EB ETU45B: Protection functions LSIN 4) FB ETU76B: Protection functions LSIN 4) NB Versions with ground-fault protection ETU27B: Protection functions LSING 5) DG ETU45B: Protection functions LSING 4)6) EG ETU45B: Protection functions LSING 4)6) FG ETU76B: Protection functions LSING 4)6) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) Z options which are installed on the guide frame are not available. 3) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 4) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 5) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. /8 Siemens LV
19 Siemens AG 203 3WL /Non-Automatic up to 6300 A (AC), IEC 3-pole, withdrawable versions Max. rated circuit breaker current Rated current ) I n Breaking capacity DT I cu 66/80 ka at 500 V, I cu = I cs standard breaking capacity S S Basic price A A ka kg With guide frames, vertical main circuit connection I WL 06-3@@37-@@@@ unit WL 08-3@@37-@@@@ unit WL 0-3@@37-@@@@ unit WL 2-3@@37-@@@@ unit WL 6-3@@37-@@@@ unit WL 20-3@@37-@@@@ unit II WL2 08-3@@37-@@@@ unit WL2 0-3@@37-@@@@ unit WL2 2-3@@37-@@@@ unit WL2 6-3@@37-@@@@ unit WL2 20-3@@37-@@@@ unit WL2 25-3@@37-@@@@ unit WL2 32-3@@37-@@@@ unit WL2 40-3@@37-@@@@ unit With guide frames, connecting flanges I WL 06-3@@38-@@@@ unit WL 08-3@@38-@@@@ unit WL 0-3@@38-@@@@ unit WL 2-3@@38-@@@@ unit WL 6-3@@38-@@@@ unit WL 20-3@@38-@@@@ unit II WL2 08-3@@38-@@@@ unit WL2 0-3@@38-@@@@ unit WL2 2-3@@38-@@@@ unit WL2 6-3@@38-@@@@ unit WL2 20-3@@38-@@@@ unit WL2 25-3@@38-@@@@ unit WL2 32-3@@38-@@@@ unit Non-automatic air circuit without Electronic Trip Units AA None breakers 3) Electronic Trip Units Versions without ground-fault protection ETU5B: Protection functions LI BB ETU25B: Protection functions LSI CB ETU45B: Protection functions LSIN 4) EB ETU45B: Protection functions LSIN 4) FB ETU76B: Protection functions LSIN 4) NB Versions with ground-fault protection ETU27B: Protection functions LSING 5) DG ETU45B: Protection functions LSING 4)6) EG ETU45B: Protection functions LSING 4)6) FG ETU76B: Protection functions LSING 4)6) NG Operating mechanism, Manual operating mechanism with AA2 None auxiliary release, auxiliary switch mechanical closing, without st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO For further supplements see page /37 Additional price ) The rated current is determined by the rating plug. For the standard version, the supplied module is equal to the maximum rated current. If a lower rated current is required, adaptation by order code on page /38. 2) Z options which are installed on the guide frame are not available. 3) For permissible rated short-time current I cc and rated short-circuit making capacity I cm for non-automatic air circuit breakers see page /5. 4) Current transformers for protection of the N conductor and current transformers for detection of the ground-fault current in the grounded neutral point of the transformer are to be ordered separately, see page /5. 5) Current transformers for protection of the N conductor are to be ordered separately, see page /5. 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm and tripping), see page /5. Siemens LV /9
Air Circuit Breakers
Siemens AG 204 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23
More informationSENTRON 3WL5 Air Circuit Breakers/ Non-Automatic Air Circuit Breakers according to UL 489/IEC
SENTRON 3WL5 Air Circuit Breakers/ Non-Automatic Air Circuit Breakers according to UL 89/IEC Catalog Technical Information SENTRON 3WL5 Air Circuit Breakers/Non-Automatic Air Circuit Breakers According
More informationSIEMENS 3WL Air Circuit Breakers
SIEMENS 3WL Air Circuit Breakers Switching, Protection, Measuring and Monitoring Devices The SENTRON 3WL circuit breaker takes into account the increased demands made on air circuit breakers in terms of
More informationSENTRON Switching and Protection Devices Air Circuit Breakers
SENTRON Switching and Protection Devices ir Circuit Breakers /2 Introduction 3WL ir Circuit Breakers 3WL ir Circuit Breakers/ Non-utomatic ir Circuit Breakers up to 6300 (C) / - Design /2 - Function /20
More informationSiemens AG WT Air Circuit Breakers up to 4000 A. Catalog LV SENTRON. Answers for infrastructure.
3WT Air Circuit Breakers up to 4000 A Catalog LV 35 011 SENTRON Answers for infrastructure. Related catalogs Low-Voltage Power Distribution and LV 10.1 Electrical Installation Technology Protection, Switching,
More informationSENTRON Switching and Protection Devices Molded Case Circuit Breakers
SENTRON Switching and Protection Devices Molded Case Circuit Breakers /2 Introduction 3VL Molded Case Circuit Breakers up to 00 A General data /4 - Design /12 - Function /15 - Integration / - Configuration
More information3VT Kompaktleistungsschalter bis 630A
Katalog LV 36 AT Österreich - Auszug 2012 3VT Kompaktleistungsschalter bis 630A SENTRON Schutz-, Schalt- und Messtechnik www.siemens.com/lowvoltage 3VT1 Molded Case Circuit Breakers up to 160 A 1 Technical
More informationLow-Voltage Controls and Distribution
3WT ir Circuit Breakers up to 4000 Catalog LV 35 009 Low-Voltage Controls and Distribution SIRIUS SENTRON SIVCON Order No. German/English: Catalog E86060-K100-101-8 E86060-K100-101-7-7600 Incl. PDF CD-ROM
More information3VF3 to 3VF8 Circuit-Breakers
3VF3 to 3VF8 Circuit-Breakers Accessories Operating mechanisms For other s for 3VF3 with knob Rotary drive, complete, scope of supply Cubicle door for 3VF6 Motor operating mechanism for 3VF3 Motor operating
More information3NP1 Fuse Switch Disconnectors up to 630 A
Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors
More informationWL Low Voltage Metal-Enclosed Switchgear. Selection and Application Guide.
WL Low Voltage Metal-Enclosed Switchgear Selection and Application Guide www.sea.siemens.com/switchgear 3 Table of Contents General Information...............................................................................................
More informationProtection Equipment
Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection
More informationSelection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker
Selection and Application Guide Supplement WL UL1066 4-Pole Circuit Breakers usa.siemens.com/wlbreaker WL Power Circuit Breaker Table of Contents Ratings for UL 1066 (ANSI C37) Circuit Breakers Frame size
More informationCatalog LV 1 Add-On October sentron CIRCUIT-BREAKERS. 3VL Molded Case Circuit-Breakers approved according to UL 489 up to 1600 A
Catalog LV 1 Add-On October 2006 sentron CIRCUIT-BREAKERS 3VL Molded Case Circuit-Breakers approved according to UL 489 up to 00 A Related catalogs Contents Low-Voltage Controls and Distribution SIRIUS
More informationDMX 3 -I 2500 switch disconnectors
8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40
More informationSpecification for 70mm pole pitch Air circuit breaker up to 1600 A
Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with
More informationWL Low Voltage Metal-Enclosed Switchgear
www.usa.siemens.com/switchgear WL Low Voltage Metal-Enclosed Switchgear Selection and Application Guide Answers for industry. Table of Contents General Information... 2 Construction Details... 3-5 WL
More informationSiemens AG 2017 SENTRON. 3VA Molded Case Circuit Breakers with UL and IEC Certification. Edition 10/2017. siemens.com/3va
SENTRON 3VA Molded Case Circuit Breakers with UL and IEC Certification Edition 10/2017 siemens.com/3va Related catalogs Low-Voltage Power Distribution and LV 10 Electrical Installation Technology SENTRON
More informationSIRIUS 3RU2 Thermal Overload Relays
Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to
More informationBETA Low-Voltage Circuit Protection
BETA Low-Voltage Circuit Protection /2 Introduction Miniature Circuit Breakers /4 5SP and 5SY miniature circuit breakers / 5SJ6...-.KS miniature circuit breakers with plug-in terminal /21 5SY6 0 miniature
More informationMOULDED CASE CIRCUIT BREAKERS BC160N
D MOULDED CASE CIRCUIT BREAKERS BC160N D BC160N COMMERCIAL INFORMATION Circuit breakers...d4 Switch-disconnectors...D5 Connecting sets......d6 Mounting sets......d6 Switches...D7 Shunt trips...d7 Undervoltage
More informationSENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors Fuse monitoring possible throughout Busbar supports can be
More information3VT5 Molded Case Circuit Breakers up to 1600 A
VT Molded Case Circuit Breakers up to 6 A Catalog General data Siemens AG Overview Connecting sets 4 Switching unit 6 7 8 9 6 4 Accessories 7 8 9 4 NSO_9a 4 6 7 8 9 Molded case circuit breaker Multiple
More informationOverload Relays. SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A for standard applications. 5/78 Siemens IC Overview
SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors.
More information3VU13, 3VU16 Circuit-Breakers
3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used
More informationProtection Equipment. 5/2 Introduction
Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1
More informationSwitch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV
Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads
More informationCritical Power Switchboards. Selection and Application Guide
Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation
More informationProtection Equipment. Overload Relays. Reference Manual 04/2011. Industrial Controls. Answers for industry.
Protection Equipment Overload Relays Reference Manual 04/2011 Industrial Controls Answers for industry. Protection Equipment 2 3 7 7 8 9 14 1 16 17 18 18 19 20 2 26 27 28 29 30 32 37 38 40 42 Introduction
More information3VT5 Molded Case Circuit Breakers up to 1600 A
VT5 Molded Case Circuit Breakers up to A Catalog Technical Information VT5 Molded Case Circuit Breakers up to A General data /2 - Overview Standard circuit breakers, releases / - Selection and ordering
More informationControl Circuit Protection
Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC
More informationDPX moulded case circuit breakers
BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.
More information3VA Circuit Breaker Compact. Global. Next- Gen! Brandon Castro and Fred Myers Manufacturing in America 02/22-23/2017
3VA Circuit Breaker Compact. Global. Next- Gen! Brandon Castro and Fred Myers Manufacturing in America 02/22-23/2017 3VA UL molded case circuit breaker Focus: 65kA@480V (100kA FS250A) TMTU-based Compact
More informationSiemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage
SENTRON Configuration Manual Edition 10/2015 siemens.com/lowvoltage 2 Introduction LD main control and EMERGENCY-STOP switches up to 250 A 4 Introduction 7 Front mounting 10 Floor mounting 11 Distribution
More informationBETA Switching Switches and Light Indicators
Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET
More informationSION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG
Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.0 008 Answers for energy. R-HG11-17.tif Siemens HG 11.0 008 Contents Contents Page SION Vacuum Circuit-Breakers Description General Construction
More informationLow Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear
13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of
More informationSION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG
Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 2011 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.02 2011 Contents SION Vacuum Circuit-Breakers Medium-Voltage Equipment Catalog
More information3VT2 Molded Case Circuit Breakers up to 250 A
VT Molded Case Circuit Breakers up to 5 A Catalog VT Molded Case Circuit Breakers up to 5 A General data / - Overview Circuit breakers Switch disconnectors / - Overview / - Selection and ordering data
More informationSiemens AG Industrial Controls. SIRIUS 3R_1* in sizes S00/S0 to S12 SIRIUS. Catalog Add-On IC 10 AO. Edition Answers for industry.
Industrial Controls SIRIUS 3R_1* in sizes S00/S0 to S12 SIRIUS Catalog Add-On IC 10 AO Edition 2014 Answers for industry. Related catalogs Miscellaneous Industrial Controls IC 10 SIRIUS Products for Automation
More informationSIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates
Motor Starter Protectors/Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Overview Enclosures For stand-alone installation of 3RV20
More informationProtective Devices: Circuit-Breakers 1 )
Protective Devices: Circuit-Breakers 1 ) /2 Introduction SIRIUS circuit-breakers 1 ) up to 100 A / General data /20 For motor protection /22 For motor protection with overload relay function /23 For starter
More informationSelection and Application Guide usa.siemens.com/circuitbreakers
Low Voltage WL Circuit Breakers Selection and Application Guide usa.siemens.com/circuitbreakers Low Voltage Circuit Breaker Guidelines These instructions do not purport to cover all details or variations
More informationAdvanced retrofitting kits solutions for Megamax Megamax Emax 2
S ERVICE NOTE Advanced retrofitting kits solutions for Megamax Megamax Emax 2 With few modifications to your existing switchgear, ABB retrofitting kits are a cost effective solution to upgrade your electrical
More informationENYSTAR Load Centers up to 250 A
PASSION FOR POWER. up to 250 A according to IEC 61439-3 for commercial and industrial buildings Download at www.hensel-electric.en made in GERMANY since 1931 up to 250 A according to IEC 61439-3 for commercial
More informationVL Circuit Breaker Features & Benefits. powerful ideas RELIABLE SOLUTIONS
VL Circuit Breaker Features & Benefits powerful ideas RELIABLE SOLUTIONS A Solutions Oriented Circuit Protection Family The Tangram An ancient Chinese game in which a few simple components provide endless
More informationSitras SCS, -RCI, -FFP, -TTU
Sitras SCS, -RCI, -FFP, -TTU control system for traction power supply Remote control interface Frame fault protection Transfer trip unit siemens.com/rail-electrification The Sitras SCS station control
More informationData sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427
Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This
More information27Overload Relays. Overview Combinations of overload relays and contactors SIRIUS 3R. Thermally delayed overload relays CLASS 10
27Overload Relays Overview Combinations of overload relays and contactors SIRIUS 3R 27Overload Relays Contactors Current range A 3RT10 1 Size S00 3/4/5.5 kw 3RT10 2 Size S0 5.5/7.5/11 kw 3RT10 3 Size S2
More informationSENTRON Switching and Protection Devices Switch Disconnectors
SENTRON Switching and Protection Devices Switch Disconnectors /2 Introduction 3K, 3KE, 3LD Switch Disconnectors 3K, 3KE Switch Disconnectors up to 1000 /4 General data /8 Floor mounting 3LD Main and EMERGENCY-STOP
More information3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,
Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,
More informationSECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.
SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products
More informationFor Operation in the Control Cabinet 3RW Soft Starters
General Data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations
More informationABB s new control and protection devices
ABB s new control and protection devices One product family ABB presents a new generation of first-class specialized components: manual motor starters, contactors, overload relays and softstarters for
More informationMOULDED CASE CIRCUIT BREAKERS BH630N, BH630S
MOULDED CASE CIRCUIT BREAKERS BH6N, BH6S F BH6N, BH6S COMMERCIAL INFORMATION Switching units, withdrawable device, plug-in device...f4 Switch-disconnector unit...f6 Connecting sets...f7 Mounting sets...f9
More informationSystem Manual 02/2008
System Manual 02/2008 SIRIUS Infeed System for 3RA6 sirius COMPACT STARTER Introduction 1 Product-specific information 2 SIRIUS industrial switchgear Load feeders, motor and soft starters System Manual
More informationResidual Current Protective Devices / Arc Fault Detection Devices (AFDDs)
Introduction Overview Devices Page Application Standards Used in / Personnel, material and fire protection, as well as protection against direct contact. SIGRES with active condensation protection for
More informationTable Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.
-174 Series C Molded Case Circuit s July 7 Molded Case Switches Refer to Eaton for UL listed, series tested Molded Case Switch application data. Table -278. Molded Case Switches Cont. Amp Rating at 40
More informationPage. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases
Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar
More informationContents. We build a better future! MCC HCB
H8PU Low Voltage We build a better future! HYUNDAI s low voltage motor control center H8PU series with a withdrawable unit are of multi-tier, factory assembled and for rated voltage of up to 660V AC. Contents
More informationOverview of Low voltage equipment - Moulded-case & Air circuit-breakers
Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Moulded-case circuit-breakers for distribution (1) R16 and R20 Icu = 16 ka @ 220/230 V (2) All the versions with Icu = 35 ka are
More informationCENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies
Selection Checklist CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies Use this checklist to help you configure your CENTERLINE 2500 Motor Control Center. You can type in the fields
More informationMotor Applications Automation. Command and Signalling Power Management Product Overview for Machinery
Motor Applications Automation Command and Signalling Power Management Product Overview for Machinery Motor-Protective Circuit-Breakers PKZ and PKE Flexible Solutions: Simple, Intelligent, Pluggable, Versatile
More information3RW Soft Starters. General data. 6/4 Siemens LV
General data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of peaks Avoidance of mains voltage fluctuations during starting
More information3VT1 Molded Case Circuit Breakers up to 160 A
Siemens AG 4 VT Molded Case Circuit Breakers up to 6 A Catalog Technical Information VT Molded Case Circuit Breakers up to 6 A / General data / Circuit breakers Switch disconnectors Accessories and Components
More informationCPG.0 Single busbar gas-insulated cubicles
MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation
More informationOvercurrent releases - description, specifications, characteristics specifications specifications description...
BA5*37 COMMERCIAL INFORMATION Type designation specification for ordering...68 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting
More informationGV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features
Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator
More informationSENTRON VL Series Product Specifications
SENTRON VL Series Product Specifications VL 400 Frame 400 s Electronic Releases ETU TRIP RELEASE 315 12-315 3VL4731 - A 3-0AA0 400-400 3VL4740 - A 3-0AA0 3 = 3 poles All VL400 circuit-breakers are shipped
More informationGeneral data 5/37. Overview
General data Overview Benefits High short-circuit breaking capacity in the feeder Optimum usability in motor feeders for the special voltages 440 V, 480 V, 0 V and 690 V Compact design The are available
More informationATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions
to 00 A Accessories Enclosed Characteristics M e atysm_007_a cat M s atysm_0_a cat products are and 4pole switches remotely controlled by volt free contacts ( ) or automatic transfer switches ( ). They
More information3/2 Introduction. Unequipped Distribution Boards (Flat Pack) 3/6 8GK1 surface-mounting distribution boards
ALPHA 400 - DIN Wall-Mounted Distribution Boards /2 Introduction Unequipped Distribution Boards (Flat Pack) /6 8GK1 surface-mounting distribution boards Pre-Assembled Unequipped Distribution Boards /7
More informationInterchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI
. Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,
More informationMULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers
IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when
More informationManual. Industrial Controls. Protection Devices. SIRIUS 3RV Motor Starter Protectors. Edition 12/2017. siemens.com
Manual Industrial Controls Protection Devices Edition 12/2017 siemens.com Introduction 1 Standards 2 Industrial Controls Protection devices SIRIUS 3RV Motor Starter Protectors Manual Product description
More informationCOMMERCIAL INFORMATION TECHNICAL INFORMATION BA511*33
BA511*33 COMMERCIAL INFORMATION Type designation specification for ordering...146 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting
More informationSelection Guide Motor Control Device Solutions
Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements
More information3RW Soft Starters. General data. 6/2 Siemens LV 1 N SIRIUS Soft Starters 01/2008. Siemens AG 2008
Siemens AG 2008 General data The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations
More informationBETA Fuses and Fuse Systems
Introduction Overview Application LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in the switchboards of power supply companies. Fuses
More informationCircuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases
Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters
More informationDATA SHEET 3VT3 MCCB ACCESSORIES
Issued June 7 DATA SHEET VT MCCB ACCESSORIES Based on Siemens Catalog LV 8 VT Molded Case Circuit Breakers up to A 7 Accessies and Components es Overview Type designation accding to contact arrangement
More informationMotor Circuit Breakers C3
Motor Circuit Breakers C3 Motor protection rating up to 100 Amps Short circuit breaking capacity up to 100kA Phase failure protection DIN rail mounting Wide range of accessories Options and ordering codes
More informationPower Supplies. 11/2 Introduction
Siemens AG 2009 Power Supplies 11 11/2 Introduction 4AV Non-Stabilized Power Supplies Filtered for Supply of Electronic Controls 11/4 General data 11/5 4AV2, 4AV4 power supplies, filtered, single-phase
More informationMotor Circuit Breakers C4
Motor protection rating up to 100 Amps Short circuit breaking capacity up to 100kA Phase failure protection DIN rail mounting Wide range of accessories Options and ordering codes Model C4/32T Setting Short
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:
More information3 - Protection components Motor circuit-breakers
Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page
More informationcor Long Run Experience
Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30
More informationMagnum IEC Low Voltage Air Circuit Breakers
Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 Vac 42 ka to 100 ka Icu 800 to 6300 Amperes EN 60947-2 A Global Source for Innovative Electrical Power Distribution Solutions Proven
More informationAir-insulated switchgear UniGear type ZS1
Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5
More informationCustomized for maximum demands. SIVACON Technology Partner. SIVACON S8 low-voltage power distribution board: safe, flexible, efficient
SIVACON Technology Partner Customized for maximum demands SIVACON S8 low-voltage power distribution board: safe, flexible, efficient siemens.com/sivacon-partner Contents Conforming to standards: systematic
More informationPower Break II Switchboard
Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A
More informationOriginal Manual 2CCC444010M0201 Rev. 1.0, Date of Release: 02/2016. Remote Power Panel Assembly instructions
Original Manual 2CCC444010M0201 Rev. 1.0, Date of Release: 02/2016 Remote Power Panel Assembly instructions Table of contents Unpacking and checking the cabinet Visual control of the packaging 3 Unpacking
More informationMolded-Plastic Distribution Systems
Molded-Plastic Distribution Systems / Introduction ALPHA 8HP molded-plastic distribution systems /8 Empty enclosures / Modular installation devices /4 DIAZED/NEOZED fuse systems /7 NP fuse switch disconnectors
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationATyS range ATyS r, ATyS d, ATyS t, ATyS g, ATyS p from 125 to 3200 A
Transfer switches Accessories Terminal shrouds IPX protection against direct contact with terminals or connecting parts. Advantages Perforations allow remote thermographic inspection without the need to
More informationATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A
ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat
More informationSIRIUS SENTRON SIVACON
The Integrated Portfolio for Low-Voltage Controls and Distribution SIRIUS SENTRON SIVACON Answers for industry. More than Just Technology For many decades, Siemens has been one of the leading manufacturers
More informationDEVICE STATE/BYPASSED FAILURE OVERLOAD
Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated
More informationUBW Family UL489 Molded Case Circuit Breakers
UBW Family UL489 Molded Case Circuit Breakers The UBW line offers the quality, realiablity and uncompromising protection that you have come to expect from WEG Molded Case Circuit Breakers UBW Series Product
More informationShort form catalogue. Motor protection & control
Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59
More information