Sample Residence HVAC Load Calculations
|
|
- Bathsheba Morrison
- 5 years ago
- Views:
Transcription
1 Sample Residence HVAC Load Calculations for Prepared By: Dale 311 E. Sherman Ave. Coeur D Alene, Id Wednesday, June 15, 2016 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
2 Coeur D Alene, ID Page 2 Project Report General Project Information Project Title: Project Date: Monday, May 16, 2016 Client Name: Timbered Ridge Construction Company Name: Company Representative: Dale Company Address: 311 E. Sherman Ave. Company City: Coeur D Alene, Id Company Phone: Company Fax: Company Address: dalerainey@gmail.com Design Data Reference City: Coeur D Alene AP, Idaho Building Orientation: Front door faces North Daily Temperature Range: High Latitude: 48 Degrees Elevation: 2400 ft. Altitude Factor: Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: n/a n/a 70 n/a Summer: % 50% Check Figures Total Building Supply CFM: 1,151 CFM Per Square ft.: Square ft. of Room Area: 2,100 Square ft. Per Ton: 1,094 Volume (ft³) of Cond. Space: 20,911 Building Loads Total Heating Required Including Ventilation Air: 41,474 Btuh MBH Total sible : 23,823 Btuh 100 % Total Latent : -777 Btuh 0 % Total Cooling Required Including Ventilation Air: 23,823 Btuh 1.99 Tons (Based On sible + Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions.
3 Coeur D Alene, ID Page 3 Miscellaneous Report System 1 HVAC Input Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hum Indoor Rel.Hum Indoor Dry Bulb Grains Difference Winter: % n/a 70 n/a Summer: % 50% Duct Sizing Inputs Main Trunk Runouts Calculate: Yes No Use Schedule: Yes Yes Roughness Factor: Pressure Drop: in.wg./100 ft in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. Outside Air Data Winter Summer Infiltration Specified: AC/hr AC/hr 77 CFM 38 CFM Infiltration Actual: AC/hr AC/hr Above Grade Volume: X 20,911 Cu.ft. X 20,911 Cu.ft. 4,600 Cu.ft./hr 2,300 Cu.ft./hr X X Total Building Infiltration: 77 CFM 38 CFM Total Building Ventilation: 0 CFM 0 CFM ---System 1--- Infiltration & Ventilation sible Multiplier: = (1.10 X X Summer Temp. Difference) Infiltration & Ventilation Latent Multiplier: = (0.68 X X Grains Difference) Infiltration & Ventilation sible Loss Multiplier: = (1.10 X X Winter Temp. Difference) Winter Infiltration Specified: AC/hr (77 CFM), Construction: Semi-Tight Summer Infiltration Specified: AC/hr (38 CFM), Construction: Semi-Tight Duct Load Factor Scenarios for System 1 No. Type Description Location Attic Ceiling Duct Leakage Duct Insulation Surface Area From [T]MDD 1 Supply Attic 16B No 1 Return Attic 16B No
4 Coeur D Alene, ID Page 4 Load Preview Report Scope Net Ton ft.² /Ton Building ,094 2,100 23, ,823 41, ,151 1,151 System ,094 2,100 23, ,823 41, ,151 1,151 11x17 Supply Duct Latent Return Duct Zone 1 2,100 23, ,193 40, ,151 1,151 1-Room , ,436 4, ,6 2-Room , ,031 10, ,6,6,6 3-Room , ,260 3, ,6 4-Room , Room , ,702 4, Room , ,049 1, Room Room , ,494 2, Room , Room , ,606 6, ,6,6 Area Lat Net Loss Sys Htg CFM Sys Clg CFM Sys Act CFM Duct Size
5 Coeur D Alene, ID Page 5 Duct Size Preview Room or Duct Name System 1 Supply Runouts Zone 1 1-Room 3 (SR-620, SR-630) 2-Room 4 (SR-640, SR-650, SR-660, SR-670) 3-Room 5 (SR-680, SR-690) Source GMDD GMDD GMDD Minimum Velocity Maximum Velocity Rough. Factor Design L/ SP Loss Duct Velocity Duct Length Htg Flow Clg Flow Act. Flow Room 12 (SR-700) GMDD Room 6 (SR-710) GMDD Room 7 (SR-720) GMDD Room 8 (SR-730) GMDD Room 9 (SR-740) GMDD Room 10 (SR-750) GMDD Room 1 (SR-760, SR-770, SR-780) Other Ducts in System 1 GMDD Supply Main Trunk (SMT-230) GMDD ,149 1,149 11x17 RMT-100 GMDD ,151 1,151 1,151 12x16 ST-240 GMDD x13 ST-250 GMDD x15 ST-260 GMDD ,025 1,025 11x16 ST-270 GMDD x15 ST-280 GMDD x15 ST-290 GMDD x13 ST-300 GMDD x12 ST-310 GMDD x11 ST-320 GMDD x13 ST-330 GMDD x9 RR-100 GMDD ,151 1,151 1,151 12x16 Summary System 1 Heating Flow: 576 Design Friction Rate: TEL Return: Cooling Flow: 1151 Total Cumulative SP Loss: TEL Supply: 178 Fan ESP: Device SP Loss: 0.29 TEL Total: Fan SP Available: Return Loss Added to Supply: Duct Size
6 Coeur D Alene, ID Page 6 Total Building Summary Loads Component Description Area Quan Loss Lat Total New Material: Glazing-Double Pane - Zone 5, u-value 303 7, ,915 11, , SHGC P: Door-Metal - Polyurethane Core F-0sw: Wall-Frame, R-21 insulation in 2 x 6 stud , cavity, no board insulation, siding finish, wood studs 16A-38: Roof/Ceiling-Under Attic with Insulation on Attic , ,330 3,330 Floor (also use for Knee Walls and Partition Ceilings), Unvented Attic, No Radiant Barrier, Any Roofing Material, Any Roof Color, R-38 insulation 19A-30p: Floor-Over enclosed crawl space, No insulation on exposed walls, sealed or vented space, passive, R-30 blanket , Subtotals for structure: 24, ,776 16,776 People: Equipment: Lighting: Ductwork: 11, ,344 5,122 Infiltration: Winter CFM: 77, Summer CFM: 38 5, Ventilation: Winter CFM: 0, Summer CFM: AED Excursion: 0 0 1,277 1,277 Total Building Load Totals: 41, ,823 23,046 Check Figures Total Building Supply CFM: 1,151 CFM Per Square ft.: Square ft. of Room Area: 2,100 Square ft. Per Ton: 1,094 Volume (ft³) of Cond. Space: 20,911 Building Loads Total Heating Required Including Ventilation Air: 41,474 Btuh MBH Total sible : 23,823 Btuh 100 % Total Latent : -777 Btuh 0 % Total Cooling Required Including Ventilation Air: 23,823 Btuh 1.99 Tons (Based On sible + Latent) Notes Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions.
7 Coeur D Alene, ID Page 7 Building Pie Chart Floor 10% Infiltration 13% Roof 9% Building Loss 41,474 Btuh Wall 19% Ductwork 28% Glass 18% Door 2% Roof 14% Floor 3% AED Excursion 6% Wall 3% Ductwork 22% Building 23,046 Btuh Door 1% Glass 51%
8 Coeur D Alene, ID Page 8 Detailed Room Loads - Room 1 - Room 3 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 15.5 ft. System Number: 1 Room Width: 16.0 ft. Zone Number: 1 Area: sq.ft. Supply Air: 121 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 3.2 AC/hr Volume: 2,232.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 2 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 11 CFM Actual Summer Infil.: 5 CFM Item Area -U- Htg Clg Lat Description Quantity Value HTM Loss HTM N -Wall-12F-0sw 15.5 X E -Wall-12F-0sw 16 X E -Gls-New Material shgc %S ,169 UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 2, ,749 Infil.: Win.: 10.5, Sum.: Ductwork: 1, AED Excursion: 134 Room Totals: 4, ,436
9 Coeur D Alene, ID Page 9 Detailed Room Loads - Room 2 - Room 4 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 20.5 ft. System Number: 1 Room Width: 24.5 ft. Zone Number: 1 Area: sq.ft. Supply Air: 250 CFM Ceiling Height: 13.0 ft. Supply Air Changes: 2.3 AC/hr Volume: 6,529.3 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 4 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 14 CFM Actual Summer Infil.: 7 CFM Item Area -U- Htg Clg Lat Description Quantity Value HTM Loss HTM S -Wall-12F-0sw 20.5 X N -Wall-12F-0sw 20.5 X N -Door-11P 3 X S -Gls-New Material shgc %S S -Gls-New Material shgc %S S -Gls-New Material shgc %S N -Gls-New Material shgc %S N -Gls-New Material shgc %S N -Gls-New Material shgc %S N -Gls-New Material shgc %S UP-Ceil-16A X Floor-19A-30p 1 X , Subtotals for Structure: 6, ,655 Infil.: Win.: 13.7, Sum.: Ductwork: 2,815 1,023 AED Excursion: 277 Room Totals: 10, ,031
10 Coeur D Alene, ID Page 10 Detailed Room Loads - Room 3 - Room 5 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 13.5 ft. System Number: 1 Room Width: 10.0 ft. Zone Number: 1 Area: sq.ft. Supply Air: 162 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 8.0 AC/hr Volume: 1,215.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 2 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 8 CFM Actual Summer Infil.: 4 CFM Item Description Area Quantity -U- Value Htg HTM Loss Clg HTM Lat S -Wall-12F-0sw 13.5 X E -Wall-12F-0sw 10 X S -Gls-New Material shgc %S E -Gls-New Material shgc %S ,315 UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 2, ,374 Infil.: Win.: 7.9, Sum.: Ductwork: 1, AED Excursion: 179 Room Totals: 3, ,260
11 Coeur D Alene, ID Page 11 Detailed Room Loads - Room 4 - Room 12 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 13.5 ft. System Number: 1 Room Width: 16.0 ft. Zone Number: 1 Area: sq.ft. Supply Air: 27 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 0.8 AC/hr Volume: 1,944.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 0 CFM Actual Summer Infil.: 0 CFM Item Area -U- Htg Clg Lat Description Quantity Value HTM Loss HTM UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: Infil.: Win.: 0.0, Sum.: Ductwork: AED Excursion: 31 Room Totals: 1,
12 Coeur D Alene, ID Page 12 Detailed Room Loads - Room 5 - Room 6 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 16.0 ft. System Number: 1 Room Width: 12.5 ft. Zone Number: 1 Area: sq.ft. Supply Air: 84 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 2.8 AC/hr Volume: 1,800.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 10 CFM Actual Summer Infil.: 5 CFM Item Description Area Quantity -U- Value Htg HTM Loss Clg HTM Lat S -Wall-12F-0sw 16 X W -Wall-12F-0sw 12.5 X S -Gls-New Material shgc %S UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 2, ,209 Infil.: Win.: 9.5, Sum.: Ductwork: 1, AED Excursion: 94 Room Totals: 4, ,702
13 Coeur D Alene, ID Page 13 Detailed Room Loads - Room 6 - Room 7 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 16.0 ft. System Number: 1 Room Width: 9.5 ft. Zone Number: 1 Area: sq.ft. Supply Air: 52 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 2.3 AC/hr Volume: 1,368.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 3 CFM Actual Summer Infil.: 2 CFM Item Description Area Quantity -U- Value Htg HTM Loss Clg HTM Lat W -Wall-12F-0sw 9.5 X W -Gls-New Material shgc %S UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 1, Infil.: Win.: 3.2, Sum.: Ductwork: AED Excursion: 58 Room Totals: 1, ,049
14 Coeur D Alene, ID Page 14 Detailed Room Loads - Room 7 - Room 8 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 14.0 ft. System Number: 1 Room Width: 4.5 ft. Zone Number: 1 Area: 63.0 sq.ft. Supply Air: 8 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 0.8 AC/hr Volume: cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 0 CFM Actual Summer Infil.: 0 CFM Item Area -U- Htg Clg Lat Description Quantity Value HTM Loss HTM UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: Infil.: Win.: 0.0, Sum.: Ductwork: AED Excursion: 9 Room Totals:
15 Coeur D Alene, ID Page 15 Detailed Room Loads - Room 8 - Room 9 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 12.0 ft. System Number: 1 Room Width: 14.0 ft. Zone Number: 1 Area: sq.ft. Supply Air: 124 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 4.9 AC/hr Volume: 1,512.0 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 5 CFM Actual Summer Infil.: 2 CFM Item Description Area Quantity -U- Value Htg HTM Loss Clg HTM Lat W -Wall-12F-0sw 14 X W -Gls-New Material shgc ,462 0%S UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 1, ,824 Infil.: Win.: 4.7, Sum.: Ductwork: AED Excursion: 137 Room Totals: 2, ,494
16 Coeur D Alene, ID Page 16 Detailed Room Loads - Room 9 - Room 10 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: n/a System Number: 1 Room Width: n/a Zone Number: 1 Area: sq.ft. Supply Air: 45 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 1.6 AC/hr Volume: 1,721.3 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 1 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 12 CFM Actual Summer Infil.: 6 CFM Item Area -U- Htg Clg Lat Description Quantity Value HTM Loss HTM W -Wall-12F-0sw 4 X N -Wall-12F-0sw 23.5 X E -Wall-12F-0sw 9.5 X W -Door-11P 3 X N -Door-11P 3 X UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 2, Infil.: Win.: 12.4, Sum.: Ductwork: 1, AED Excursion: 49 Room Totals: 4,
17 Coeur D Alene, ID Page 17 Detailed Room Loads - Room 10 - Room 1 (Average Load Procedure) General Calculation Mode: Htg. & clg. Occurrences: 1 Room Length: 15.5 ft. System Number: 1 Room Width: 14.5 ft. Zone Number: 1 Area: sq.ft. Supply Air: 278 CFM Ceiling Height: 9.0 ft. Supply Air Changes: 8.2 AC/hr Volume: 2,022.8 cu.ft. Req. Vent. Clg: 0 CFM Number of Registers: 3 Actual Winter Vent.: 0 CFM Percent of Supply.: 0 % Actual Summer Vent.: 0 CFM Percent of Supply: 0 % Actual Winter Infil.: 15 CFM Actual Summer Infil.: 7 CFM Item Area -U- Htg Clg Lat Description Quantity Value HTM Loss HTM S -Wall-12F-0sw 15.5 X W -Wall-12F-0sw 14.5 X E -Wall-12F-0sw 14.5 X S -Gls-New Material shgc %S W -Gls-New Material shgc ,315 0%S E -Gls-New Material shgc %S E -Gls-New Material shgc %S UP-Ceil-16A X Floor-19A-30p 1 X Subtotals for Structure: 3, ,076 Infil.: Win.: 14.9, Sum.: , Ductwork: 1,803 1,140 AED Excursion: 309 Room Totals: 6, ,606
18 Coeur D Alene, ID Page 18 System 1 Room Load Summary Htg s Btuh Min Htg CFM No Room Name Area SF ---Zone Room , ,6-2, Room , ,6,6,6-5, Room , ,6-3, Room , Room , , Room , , Room Room , , Room , Room , ,6,6-5, Duct Latent -115 Return Duct System 1 total 2,100 41, , ,151 1,151 System 1 Main Trunk Size: 11x17 in. Velocity: 885 ft./min Loss per 100 ft.: in.wg Run Duct Size Run Duct Vel Clg s Btuh Duct size results above are from Manual D Ductsize. Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room. See the Manual D Ductsize report for duct velocities and other data. Cooling System Summary Cooling Tons sible/latent Split sible Btuh Latent Btuh Total Btuh Net Required: % / -3% 23, ,823 Equipment Data Heating System Cooling System Type: Natural Gas Furnace Standard Air Conditioner Model: R95PA MSA Indoor Model: Brand: RHEEM,RUUD Description: Natural Gas or Propane Furnace Efficiency: 95 AFUE 0 SEER Sound: 0 0 Capacity: 54,000 Btuh 0 Btuh sible Capacity: n/a 0 Btuh Latent Capacity: n/a 0 Btuh Clg Lat Btuh Min Clg CFM Act Sys CFM
19 Air Gas Furnaces R95P Series Rheem Classic Series Multi position Gas Furnaces R95P- Series 95% A.F.U.E. Input Rates from 40 to 115 kbtu [11.72 to kw] A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department of Energy test procedures. 95% residential gas furnace CSA certified 4 way multi-poise design PlusOne Diagnostics 7-Segment LED all units PlusOne Ignition System DSI for reliability and longevity PlusOne Water Management System with patented Blocked Drain sor Heat exchanger is removable for improved serviceability. Aluminized steel primary and stainless steel secondary construction provide maximum corrosion resistance and thermal fatigue reliability. Low profile 34 inch cabinet ideal for space constrained installations. Blower Shelf design serviceable in all furnace orientations Pre marked hoses insures proper system drainage Vent with 2" or 3" PVC Replaceable Collector box Hemmed edges on cabinet and doors Quarter turn fasteners for tool less access Integrated control boards feature dip switches for easy system set up Self priming condensate trap FORM NO. G REV. 2
20 Air Table of Contents R95P Series TABLE OF CONTENTS Standard & Optional Equipment...3 Physical Data & Specifications...4 Model Number Identification...5 Dimensional Data...6 Blower Performance Data...7 Accessories...8 Limited Warranty...9 2
21 Air Standard & Optional Equipment R95P Series REMOTE SENSOR DIRECT SPARK IGNITION & REMOTE SENSOR PRIMARY AND SECONDARY HEAT EXCHANGER GAS VALVE AND MANIFOLD IN-SHOT BURNERS DRAFT INDUCER PRESSURE SWITCHES BLOCKED DRAIN SENSOR CONTROL BOARD STANDARD EQUIPMENT Completely assembled and wired; blocked drain sensor, 7 segment LED and marked hoses; heat exchanger; primary: aluminized steel, secondary: 29-4C stainless steel; induced draft; pressure switches; redundant main gas control; blower compartment door safety switch; solid state time on/off blower control; limit controls; manual shut-off valve; 100% safety lock out; cool fan off delay; field selectable heat fan off delay; one hour automatic retry; power and self-test diagnostics; flame sense current diagnostics; electronic air cleaner connections; twinning (built-in) features; humidifier connections; humidifier on/off delay; low speed continuous fan option; single speed option for heating and cooling applications; transformer; direct drive, multi-speed blower motor. (Please note: a thermostat is not included as standard equipment.) OPTIONAL EQUIPMENT Side and bottom filter racks; return air cabinet for all sizes. NOTE: Furnace is not listed for use with fuels other than natural or L.P. (propane) gas. All models can be converted by a qualified distributor or local service dealer to use L.P. (propane) gas without changing burners. Factory approved kits must be used to convert from natural to L.P. (propane) gas and may be ordered as optional accessories from a parts distributor. For L.P. (propane) operation, refer to Conversion Kit Index Form. WARNING THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR USE IN MOBILE HOMES 3
22 Air Physical Data & Specifications R95P Series Physical Data and Specifications Upflow Models U.S. and Canadian Models MODEL NUMBERS R95PA MSA R95PA MSA R95PA MSA R95PA MSA R95PA MSA R95PA MSA HIGH FIRE INPUT BTU/HR [kw] ➀ 42,000 [12.31] 56,000 [16.41] 70,000 [20.50] 84,000 [24.61] 98,000 [38.71] 112,000 [32.82] HEATING CAPACITY BTU/HR [kw] 40,320 [11.82] 53,760 [15.75] 67,200 [19.68] 80,640 [23.63] 94,080 [37.16] 107,520 [31.51] HIGH ALTITUDE OUTPUT 10% DERATE [kw] ➁ 36,288 [10.64] 48,384 [14.18] 60,480 [17.72] 72,576 [21.28] 84,672 [24.81] 96,768 [28.36] BLOWER (D x W) [mm] MOTOR H.P. [W] TYPE 11 x 7 [279 x 178] 11 x 8 [279 x 203] 11 x 8 [279 x 203] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 11 [279 x 279] 1/4 [187]-4-PSC 1/2 [373]-4-PSC 1/2 [373]-4-PSC 3/4 [559]-4-PSC 3/4 [559]-4-PSC 3/4 [559]-4-PSC MOTOR FULL LOAD AMPS HEATING SPEED MED-HIGH MED-HIGH MED-HIGH MED-HIGH MED-HIGH MED-HIGH COOLING SPEED HIGH HIGH HIGH HIGH HIGH HIGH MINIMUM EXT. STATIC PRESSURE (IN. W.C.) [kpa].18 [.045].20 [.050].23 [.057].28 [.070].28 [.070].28 [.070] MAXIMUM EXT. STATIC PRESSURE (IN. W.C.) [kpa] 0.8 [0.19] 0.8 [0.19] 0.8 [0.19] 0.8 [0.19] 0.8 [0.19] 0.8 [0.19] HEATING [.049 kpa] W.C. E.S.P. [L/s] 1049 [494] 1139 [537] 1211 [571] 1704 [804] 1748 [825] 1750 [825] COOLING [.124 kpa] W.C. E.S.P. [L/s] 1121 [528] 1232 [581] 1318 [622] 1742 [822] 1782 [841] 1934 [912] TEMPERATURE RISE-HIGH FIRE RANGE IN DEGREES F [ C] APPROX. SHIPPING WEIGHT (LBS.) [kg] [14-31] [19-36] [22-39] [19-36] [19-36] [25-42] [56] 128 [58] 132 [60] [67] 152 [69] 165 [75] AFUE ➂ 95.00% 95.00% 95.00% 95.00% 95.00% 95.00% NOTES: All models are 115V, 60HZ, 1 phase Gas connection size for all models is 1 /2" [13 mm] N.P.T. ➀ Installation instructions for high altitude derate. ➁ Canadian installations only. ➂ In accordance with D.O.E. test procedures. *S=Standard Models NOTE: Standard model complies with California low nox requirements. [ ] Designates Metric Conversions 4
23 Air Model Number Identification R95P Series Model Number Identification R 95 P A M S A Rheem Series 95% Efficient Motor - PSC Design Series A = 1st Design Input BTU/HR 040 = 42,000 [12.31 kw] 060 = 56,000 [16.41 kw] 070 = 70,000 [20.51 kw] 085 = 84,000 [24.62 kw] 100 = 98,000 [28.72 kw] 115 = 112,000 [32.82 kw] Stage - Single Airflow 3 - Up to 3 Tons 5 - Up to 5 Tons Cabinet Width 17 = 17.5" 21 =21.0" 24 =24.5" Configuration - Multi-Position S = Standard Revision - Marketing (A - First Time Release) [ ] Designates Metric Conversions 5
24 Air Dimensional Data R95P Series MODEL R95P UNIT DIMENSIONS (CLEARANCE TO COMBUSTIBLES) LEFT SIDE RIGHT SIDE MINIMUM CLEARANCE (IN.) [mm] FLANGE DIMENSIONS SHIP BACK TOP FRONT VENT WGTS. A B C [25] 2 [51] [56] 17 1 /2 [445] /64 [413] /64 [412] [25] 2 [51] [58] 17 1 /2 [445] /64 [413] /64 [412] [25] 2 [51] [60] 17 1 /2 [445] /64 [413] /64 [412] [25] 2 [51] [67] 21 [533] /64 [502] /64 [500] [25] 2 [51] [69] 21 [533] /64 [502] /64 [500] [25] 2 [51] [75] 24 1 /2 [662] /64 [591] /64 [589] *A service clearance of at least 24" is recommended in front of all furnaces [ ] Designates Metric Conversions Supply and return depicted as upflow configuration. Flange configuration will vary depending on installation orientation. 6
25 Air Blower Performance Data R95P Series MODEL R95PA R95PA R95PA R95PA R95PA R95PA BLOWER SIZE [mm] 11 x 7 [279 x 178] 11 x 8 [279 x 203] 11 x 8 [279 x 203] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 11 [279 x 279] MOTOR H.P. [W] 1/4 [187] 1/2 [373] 1/2 [373] 3/4 [559] 3/4 [559] 3/4 [559] BLOWER SPEED LOW MED-LO MED-HI* HIGH LOW MED-LO MED-HI* HIGH LOW MED-LO MED-HI* HIGH LOW MED-LO MED-HI* HIGH LOW MED-LO MED-HI* HIGH LOW MED-LO MED-HI* HIGH CFM [L/s] AIR DELIVERY EXTERNAL STATIC PRESSURE INCHES WATER COLUMN [kpa] 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] 0.8 [.19] 732 [345] 875 [413] 1073 [506] 1279 [603] 830 [392] 940 [443] 1168 [551] 1421 [670] 852 [402] 986 [465] 1238 [584] 1493 [704] 1313 [619] 1488 [702] 1732 [817] 1983 [935] 1329 [627] 1535 [724] 1796 [847] 2019 [952] 1249 [589] 1440 [679] 1770 [835] 2123 [1001] 695 [328] 845 [399] 1049 [495] 1239 [584] 793 [374] 908 [428] 1139 [537] 1385 [653] 827 [390] 955 [450] 1211 [571] 1452 [685] 1275 [601] 1452 [685] 1704 [804] 1929 [910] 1313 [619] 1498 [707] 1748 [825] 1961 [925] 1234 [582] 1429 [674] 1750 [825] 2077 [980] 669 [316] 820 [387] 1004 [474] 1213 [572] 755 [356] 875 [413] 1109 [523] 1349 [636] 802 [378] 923 [435] 1183 [558] 1410 [665] 1236 [583] 1415 [667] 1676 [791] 1874 [884] ] 1461 [689] 1700 [802] 1903 [898] 1219 [575] 1417 [668] 1730 [816] 2031 [958] 639 [301] 792 [374] 975 [460] 1174 [554] 705 [333] 821 [387] 1060 [500] 1291 [609] 752 [355] 883 [417] 1139 [537] 1364 [643] 1221 [576] 1384 [653] 1630 [769] 1810 [854] 1260 [594] 1422 [671] 1656 [781] 1843 [869] 1183 [558] 1381 [651] 1696 [800] 1983 [935] 605 [285] 766 [361] 943 [445] 1121 [529] 654 [308] 766 [361] 1010 [476] 1232 [581] 701 [331] 843 [398] 1094 [516] 1318 [622] 1184 [558] 1328 [626] 1579 [745] 1742 [822] 1224 [577] 1382 [652] 1612 [760] 1782 [841] 1146 [541] 1344 [634] 1662 [784] 1934 [912] 547 [258] 726 [342] 900 [425] 1069 [504] 599 [283] 710 [333] 942 [444] 1147 [541] 662 [312] 790 [373] 1036 [489] 1257 [593] 1141 [538] 1279 [603] 1498 [707] 1663 [784] 1171 [552] 1325 [625] 1536 [725] 1687 [796] 1112 [525] 1313 [619] 1611 [760] 1856 [875] *Factory setting for heat all grey cells are valid heating settings. Do not use speed tabs and/or static pressure which do not fall into the grey cells on this table. NOTE: Unit tested without filters. 512 [242] 659 [311] 864 [408] 1033 [487] 544 [257] 653 [308] 874 [412] 1062 [501] 623 [294] 737 [348] 978 [461] 1195 [564] 1098 [518] 1229 [580] 1417 [668] 1583 [747] 1117 [527] 1268 [598] 1460 [689] 1592 [751] 1078 [508] 1281 [604] 1559 [735] 1777 [838] 487 [230] 605 [286] 798 [376] 980 [462] 496 [234] 584 [275] 802 [378] 976 [460] 580 [274] 686 [324] 897 [423] 1084 [511] 1053 [497] 1170 [552] 1343 [633] 1477 [697] 1049 [495] 1203 [567] 1370 [646] 1489 [702] 1017 [480] 1221 [576] 1463 [690] 1665 [785] [ ] Designates Metric Conversions. 7
26 Air Accessories R95P Series VENT TERMINATION KITS: = RXGY-E02: Vertical/Horizontal Concentric Vent Termination Kit 2" Pipe (US Only) RXGY-E02A: Vertical/Horizontal Concentric Vent Termination Kit 2" Pipe (US & Canadian) RXGY-E03: Vertical/Horizontal Concentric Vent Termination Kit 3" Pipe (US Only) RXGY-E03A: Vertical/Horizontal Concentric Vent Termination Kit 3" Pipe (US & Canadian) RXGY-G02: Direct Vent Furnace Side Wall Vent 2" or 3" (US Only) RXGY-D05: Combustion Air Drain Kit 2" RXGY-D06: Combustion Air Drain Kit 3" NEUTRALIZER KIT: RXGY-A01 (Replacement Cartridge ) EXTERNAL BOTTOM FILTER (UPFLOW/HORIZONTAL) RACK: RXGF-CB EXTERNAL SIDE (UPFLOW) FILTER RACK: RXGF-CD EXTERNAL (DOWNFLOW) FILTER RACK: RXGF-CC FOR HIGH ALTITUDES: NOTE: For Canadian installations only, an optional derate (manifold gas pressure reduction) method may be used to adjust the furnace for altitude. See Installation Instructions for more information. This optional method may NOT be used for U.S. installations. See installation instructions as appropriate orifice change is required. L.P. CONVERSION KIT: RXGJ-FP33 CONDENSATE PUMP KIT: PROSTOCK & 1PCB151TUL DOWNFLOW/HORIZONTAL CONVERSION KIT: RXGY-CK DOWNFLOW/HORIZONTAL LEFT ZERO CLEARANCE CONVERSION KIT: RXGY-ZK COMBUSTIBLE FLOOR BASE: RXGC-B17 RXGC-B21 RXGC-B24 [ ] Designates Metric Conversions MODEL R95PA040 R95PA060 R95PA070 R95PA085 FILTER RACK FILTER SIZES* INCHES [mm] RXGF-CB (UPFLOW/ HORIZONTAL) 15 3 /4 x 25 [400 x 635] 15 3 /4 x 25 [400 x 635] 15 3 /4 x 25 [400 x 635] 19 1 /4 x 25 [489 x 635] RXGF-CD (UPFLOW) 15 3 /4 x 25 [400 x 635] 15 3 /4 x 25 [400 x 635] 15 3 /4 x 25 [400 x 635] 15 3 /4 x 25 [400 x 635] RXGF-CC (DOWNFLOW) 14 x 20 [356 x 508] 14 x 20 [356 x 508] 14 x 20 [356 x 508] 14 x 20 [356 x 508] 19 R95PA100 1 /4 x /4 x x 20 *Filter racks are shipped [489 without x 635] filters. [400 x 635] [356 x 508] Filters shipped with furnace 22 may be used or a suitable 1" [25.4 mm] filter. R95PA115 3 /4 x /4 x x 20 [578 x 635] [400 x 635] [356 x 508] INDOOR COIL CASINGS MODEL NUMBER RXBC-D17A1 RXBC-D21A1 RXBC-D21B1 RXBC-D24A1 8
27 Air Limited Warranty R95P Series GENERAL TERMS OF LIMITED WARRANTY* Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty. *For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate. Conditional Parts (Registration Required)...Ten (10) Years Heat Exchanger...Limited Lifetime 9
28 Air Notes R95P Series 10
29 Air Notes R95P Series 11
30 The new degree of comfort. In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice. Rheem Heating, Cooling & Water Heating P.O. Box Fort Smith, Arkansas Rheem Canada Ltd./Ltée 125 Edgeware Road, Unit 1 Brampton, Ontario L6Y 0P5 PRINTED IN U.S.A 05/16 QG FORM NO. G REV. 2
Rheem Classic Series Two-Stage Downflow/Horizontal Gas Furnace
Gas Furnaces Rheem Classic Series Two-Stage Downflow/Horizontal Gas Furnace RGTK- Series 92% A.F.U.E. or Above 60-120 kbtu with Dual Comfort Control A.F.U.E. (Annual Fuel Utilization Efficiency) calculated
More informationRheem Classic Series Upflow/Horizontal Gas Furnace
THIS MODEL Air Gas Furnaces Rheem Classic Series Upflow/Horizontal Gas Furnace R801S- (Upflow/Horizontal) Series 80% A.F.U.E. Input Rates 50-150 kbtu ENER UIDE Annual Fuel Utilization Efficiency - AFUE
More informationRheem Classic Series Downflow Gas Furnace
Gas Furnaces Rheem Classic Series Downflow Gas Furnace R801S (Downflow) Series 80% A.F.U.E. Input Rates 50-150 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department
More informationRheem Classic Series Upflow/Horizontal Gas Furnace
Gas Furnaces Rheem Classic Series Upflow/Horizontal Gas Furnace R801P- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-150 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance
More informationRuud Achiever Plus Series Upflow/Horizontal Gas Furnace
Gas Furnaces Ruud Achiever Plus Series Upflow/Horizontal Gas Furnace R802P- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-150 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance
More informationRheem Classic Plus Series Upflow/Horizontal Gas Furnace
Gas Furnaces Rheem Classic Plus Series Upflow/Horizontal Gas Furnace R801T- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-125 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance
More informationRheem Classic Plus Series Upflow/Horizontal Gas Furnace
Gas Furnaces Rheem Classic Plus Series Upflow/Horizontal Gas Furnace R801T- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-125 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance
More informationRheem Classic Plus Series Downflow Gas Furnace
Gas Furnaces Rheem Classic Plus Series Downflow Gas Furnace R801T Downflow Series 80% A.F.U.E. Input Rates 75-125 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department
More informationRheem Prestige Series Communicating Two-Stage Variable Speed Upflow/Horizontal Gas Furnace
Gas Furnaces Rheem Prestige Series Communicating Two-Stage Variable Speed Upflow/Horizontal Gas Furnace R802V- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-125 kbtu A.F.U.E. (Annual Fuel Utilization
More informationRheem Classic Plus Series Upflow/Horizontal Ultra Low NOx Gas Furnace
Gas Furnaces Rheem Classic Plus Series Upflow/Horizontal Ultra Low NOx Gas Furnace R801T- Upflow/Horizontal Series 80% A.F.U.E. Input Rates 50-100 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated
More informationDUAL COMFORT CONTROL TWO-STAGE DOWNFLOW/HORIZONTAL GAS FURNACES WITH
FORM NO. GSC-531 REV. 1 Supersedes Form No. GSC-488 Rev. 7 GF902D SERIES Models with Input Rates from 60 to 120 kbtu [17.58 to 35.17 kw] (All Models 92% A.F.U.E. or Above) TWO-STAGE DOWNFLOW/HORIZONTAL
More informationFORM NO. GTZ-542 Supersedes Form No. GTZ-503 Rev. 1
FORM NO. GTZ-542 Supersedes Form No. GTZ-503 Rev. 1 TZ80MSS (UPFLOW/ HORIZONTAL) SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] UPFLOW/ HORIZONTAL GAS FURNACES Features 80% residential
More informationTZ80MSX (UPFLOW/ HORIZONTAL) SERIES Models with Input Rates from 50 to 125 kbtu [15 to 37 kw] FORM NO. GTZ-544 Supersedes Form No. GTZ-503 Rev.
FORM NO. GTZ-544 Supersedes Form No. GTZ-503 Rev. 1 UPFLOW/ HORIZONTAL GAS FURNACES Features 80% residential Gas Furnace CSA certified 3 way multi poise design UF / HZ 7 Segment LED all units Direct Spark
More informationRuud Ultra Series Communicating Two-Stage Variable Speed Downflow Gas Furnace
Gas Furnaces Ruud Ultra Series Communicating Two-Stage Variable Speed Downflow Gas Furnace U802V Downflow Series 80% A.F.U.E. Input Rates 75-125 kbtu A.F.U.E. (Annual Fuel Utilization Efficiency) calculated
More informationW801S (Downflow) SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (80% A.F.U.E. )
FORM NO. G66-547 REV. 4 Supersedes Form No. G66-536 Rev. 3 DOWNF GAS FURNACE Features 80% residential Gas Furnace CSA certified 7 Segment LED all units Direct spark ignition for reliability and longevity
More informationW801T (UPFLOW/ HORIZONTAL) SERIES Models with Input Rates from 50 to 125 kbtu (80% A.F.U.E. )
FORM NO. G66-544 REV. 4 Supersedes Form No. G66-536 Rev. 3 W801T (UPFLOW/ HORIZONTAL) SERIES Models with Input Rates from 50 to 125 kbtu (80% A.F.U.E. ) UPFLOW/ HORIZONTAL GAS FURNACES Features 80% residential
More informationUPFLOW/ HORIZONTAL GAS FURNACE
FORM NO. GFJ-542 UPFLOW/ HORIZONTAL GAS FURNACE Features 80% residential Gas Furnace CSA certified 3 way multi poise design UF / HZ 7 Segment LED all units Direct Spark Ignition for reliability and longevity
More informationRheem Value Series Downflow Gas Furnace
THIS MODEL 80.0% 78% 82% 88% 97% Air Gas Furnaces Rheem Value Series Downflow Gas Furnace RGLS- Series 80% A.F.U.E. Input Rates 50-150 kbtu ENER UIDE Annual Fuel Utilization Efficiency - AFUE MID A.F.U.E.
More informationW801T (Downflow) Series Models with Input Rates from 75 to 125 kbtu [15 to 37 kw] (80% A.F.U.E. )
FORM NO. G66-549 REV. 3 Supersedes Form No. G66-536 Rev. 3 DOWNFLOW GAS FURNACE Features 80% residential Gas Furnace CSA certified 7 Segment LED all units Direct Spark Ignition System for reliability and
More informationW801S (UPFLOW/ HORIZONTAL) SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (80% A.F.U.E. )
FORM NO. G66-542 REV. 4 Supersedes Form No. G66-536 Rev. 3 W801S (UPFLOW/ HORIZONTAL) SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (80% A.F.U.E. ) UPFLOW/ HORIZONTAL GAS FURNACES Features
More informationGF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models)
FORM NO. GSC-515 GF802D SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] (U.S. & Canadian Models) TWO STAGE DOWNFLOW GAS FURNACES The Sure Comfort 2-Stage line of downflow gas furnaces
More informationRheem Classic Plus Super Quiet 80 Upflow/Horizontal Gas Furnace
THIS MODEL 80.0% 78% 82% 88% 97% Air Gas Furnaces Rheem Classic Plus Super Quiet 80 Upflow/Horizontal Gas Furnace RGPT- Series 80% A.F.U.E. Input Rates 50-125 kbtu ENER UIDE Annual Fuel Utilization Efficiency
More informationRheem Classic Series Two-Stage Upflow/Horizontal Gas Furnaces
THIS MODEL 78% 82% 88% 92.0% 97% Air Gas Furnaces Rheem Classic Series Two-Stage Upflow/Horizontal Gas Furnaces RGPQ- Series 80% A.F.U.E. Models with Input Rates from 45-105 kbtu (U.S. & Canadian Models)
More informationTable of Contents GF801U Series
FORM NO. GSC-520 GF801U SERIES Models with Input Rates from 50 to 150 kbtu [15 to 44 kw] 80% A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES The Sure Comfort line of upflow/horizontal gas furnaces are designed
More informationGAS FURNACES CLASSIC SERIES SUPER QUIET 80 80% A.F.U.E. DOWNFLOW GAS FURNACES
FORM NO. G11-487 REV. 1 Supersedes Form No. G11-487 Rev. 8 GAS FURNACES RGLN- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) Annual Fuel Utilization
More information80% A.F.U.E. DOWNFLOW GAS FURNACES
FORM NO. G66-496 REV. 5 Supersedes Form No. G66-496 Rev. 4 RGLS- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) 80% A.F.U.E. DOWNF GAS FURNACES The
More informationGAS FURNACES CLASSIC SERIES SUPER QUIET % A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES
FORM NO. G11-485 REV. 5 Supersedes Form No. G11-485 Rev. 4 GAS FURNACES RGPN- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) ISO 9001:2000 Annual Fuel
More information80% A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES
FORM NO. G66-495 Supersedes Form No. P66-765 Rev. 3 80PS- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] 80% A.F.U.E. UPF/ HORIZONTAL GAS FURNACES The WeatherKing line of upflow/horizontal
More informationGAS FURNACES QUIET 80 80% A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES
FORM NO. G11-486 REV. 3 Supersedes Form No. G11-486 Rev. 2 GAS FURNACES RGPP- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) ISO 9001:2000 Annual Fuel
More informationGAS FURNACES II 80.0% 81.4% A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES SILHOUETTE
FORM NO. G22-448 REV. 10 Supersedes Form No. G22-448 Rev. 9 GAS FURNACES UGPH- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) Annual Fuel Utilization
More informationRheem Value Series Upflow/Horizontal Gas Furnace
THIS MODEL Gas Furnaces Rheem Value Series Upflow/Horizontal Gas Furnace RGPS- Series 80% A.F.U.E. Input Rates 50-150 kbtu ENER UIDE Annual Fuel Utilization Efficiency - AFUE 80.0% MID HIGH 78% 82% 88%
More informationGAS FURNACES ACHIEVER SERIES SUPER QUIET % A.F.U.E. UPFLOW/ HORIZONTAL GAS FURNACES
FORM NO. G22-485 REV. 4 Supersedes Form No. G22-485 Rev. 3 GAS FURNACES UGPN- SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] (U.S. & Canadian Models) Annual Fuel Utilization
More information80 PLUS A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES
FORM NO. G66-478 REV. 5 Supersedes Form No. G66-478 Rev. 4 80PJ SERIES Models with Input Rates from 50,000 to 150,000 BTU/HR [15 to 44 kw] 80 PLUS A.F.U.E. UPF/HORIZONTAL GAS FURNACES Features The WeatherKing
More information80 PLUS A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES
FORM NO. G66-478 REV. 1 Supersedes Form No. G66-478 Rev. 0 80 PLUS A.F.U.E. UPF/HORIZONTAL GAS FURNACES Features The WeatherKing line of upflow/horizontal gas furnaces are designed for utility rooms, closets,
More informationFG7S (C and L Series)
TECHNICAL SPECIFICATIONS FG7S (C and L Series) High Efficiency/Direct Vent or Non Direct Vent Single Stage Condensing Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 92.1 AFUE Input 38,000-120,000
More informationGUH 95 Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS
TECHNICAL SPECIFICATIONS GUH 95 Series Two Stage, Variable Speed, Condensing Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 95.1 AFUE Input 60,000-120,000 Btuh The high efficiency upflow gas
More informationKG7T (E and N Series)
TECHNICAL SPECIFICATIONS KG7T (E and N Series) Two Stage, Fixed Speed ECM, Condensing Upflow and Downflow Gas Furnaces Induced Draft - 96% AFUE Input 60,000-115,000 Btuh The high efficiency upflow gas
More informationFG7T (E and N Series)
TECHNICAL SPECIFICATIONS FG7T (E and N Series), Smartlite Two Stage, Fixed Speed ECM, High Efficiency Upflow and Downflow Gas Furnaces Induced Draft - 96% AFUE Input 60,000-115,000 Btuh The high efficiency
More informationTECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY
TECHNICAL SPECIFICATIONS KG7S (C and L Series) High Efficiency / Direct Vent or Non Direct Vent Condensing Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 92. AFUE Input 38,000-20,000 Btuh
More informationVG7S (D and M Series) High Efficiency, Single Stage Condensing Upflow/Horizontal and Downflow Gas Furnace Models 95.0 AFUE 38, ,000 Btuh Input
TECHNICAL SPECIFICATIONS VG7S (D and M Series) High Efficiency, Single Stage Condensing Upflow/Horizontal and Downflow Gas Furnace Models 95.0 AFUE 38,000-120,000 Btuh Input The high efficiency upflow
More informationKG7T (C and L Series)
TECHNICAL SPECIFICATIONS KG7T (C and L Series) Two Stage, Fixed Speed ECM, Condensing Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 95.1 AFUE Input 60,000-120,000 Btuh The high efficiency
More informationKG7T (C and L Series)
TECHNICAL SPECIFICATIONS KG7T (C and L Series) Two Stage, Fixed Speed ECM, Condensing Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 95.1 AFUE Input 60,000-120,000 Btuh The high efficiency
More informationProduct Data. that this product meets the S 95% AFUE S Two -stage operation
DIRECT VENT 4 -WAY MULTIPOISE CONDENSING GAS FURNACE 95% DOWNFLOW / HORIZONTAL ORIENTATIONS 93.5% UPFLOW ORIENTATION 95% Variable Speed Two -Stage Heating Furnace FLEXIBILITY S Supports two -stage cooling
More informationCased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFN- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Ruud Indoor Coils are designed for use
More informationProduct Data. 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal. ama 58HDX COMFORT 95 DIRECT OR NON---DIRECT VENT CONDENSING GAS FURNACE
COMFORT 95 DIRECT OR NON---DIRECT VENT 4 --- WAY MULTIPOISE CONDENSING GAS FURNACE 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal FLEXIBILITY S Dual certified venting (1 or 2 pipes) Direct
More informationTECHNICAL GUIDE MODELS: P4HU 80 AFUE MULTI-POSITION GAS-FIRED FURNACES DESCRIPTION. WARRANTY 20-year limited warranty on the heat exchanger.
036-21047-001 Rev. A (4/00) DESCRIPTION These high efficiency, compact units employ induced combustion, reliable hot surface ignition and high heat transfer aluminized tubular heat exchangers. The units
More informationRheem Air Handlers. RHLP- Standard Efficiency X-13 (ECM) Motor
Air Handlers Rheem Air Handlers RHLP- Standard Efficiency X-13 (ECM) Motor RHLP features an X-13 (ECM) motor which provides enhanced SEER performance with most Rheem outdoor units. 1 1 /2 ton [.3 kw] through
More informationCased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFP- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,600 CFM [283-755 L/s] Rheem Indoor Coils are designed for use
More informationUPFLOW/DOWNFLOW/HORIZONTAL (NATURAL GAS)
C9MVX SoftSound VS90 Product Specifications 95% Variable Speed Two Stage Heating Furnace FLEXIBILITY Supports two stage cooling units Dual Certified venting (1 or 2 pipe), Direct Vent Furnace 40in (1016mm)
More informationFG7T (A and K Series)
TECHNICAL SPECIFICATIONS FG7T (A and K Series), Smartlite Two Stage, Variable Speed, High Efficiency Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 80 + AFUE Input 60,000-140,000 Btuh The
More informationKG7S (A and K Series)
TECHNICAL SPECIFICATIONS KG7S (A and K Series) High Efficiency Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 80+ AFUE Input 45,000-126,000 Btuh The high efficiency gas furnace may be installed
More informationRheem High Efficiency Air Handler
Air Handlers Rheem High Efficiency Air Handler Constant Torque Motor (ECM) Efficiencies up to 14 SEER The RH1T feature a Constant Torque motor (ECM) and a piston refrigerant control for efficient and reliable
More informationFG7T (A and K Series)
TECHNICAL SPECIFICATIONS FGT (A and K Series) Two Stage, Variable Speed, High Efficiency Upflow/Horizontal and Downflow Gas Furnaces Induced Draft - 80 + AFUE Input 60,000-140,000 Btuh The high efficiency
More informationTECHNICAL GUIDE MODELS: G8T-UP 80 AFUE UPFLOW/HORIZONTAL GAS-FIRED FURNACES DESCRIPTION WARRANTY FEATURES Rev.
TECHNICAL GUIDE MODELS: G8T-UP 80 AFUE UPFLOW/HORIZONTAL GAS-FIRED FURNACES 40-130 MBH INPUT HIGH-EFFICIENCY INDUCED COMBUSTION EFFICIENCY RATING CERTIFIED This product was manufactured in a plant whose
More informationOperating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16
SOUND REFRIGERANT ENVIRONMENTALLY Product Specifications UP to 16 SEER, UP to 12.5 EER, PACKAGE GAS / ELECTRIC, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT
More informationTSTAT0101SC Recommended (sold separately)
Up to 96% AFUE, Communicating, Two Stage Gas Furnace EASIER TO SELL Up to 96% AFUE, all models, all positions California NOx approved All Models have earned the ENERGY STAR Two stage heating operation
More information96G1E PRODUCT SPECIFICATIONS SINGLE STAGE CONSTANT TORQUE MOTOR VENTING INSTALLATION FEATURES WARRANTY CONFIGURATIONS HEAT EXCHANGER DESIGN BURNER
96G1E PRODUCT SPECIFICATIONS SINGLE STAGE CONSTANT TORQUE MOTOR FORM NO. 96G1E-100 (04/2018) VENTING Designed certified for direct (2-pipe) and non direct (1-pipe) applications Easily vented with PVC pipe
More informationN9MPD Product Specifications
Single Stage Furnace Multiposition FLEXIBILITY Dual certified venting (1 or 2 pipes) Direct Vent furnace 40 (1016mm) high with wider cabinets, for ease of installation Factory shipped as natural gas, with
More informationCased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Ruud Indoor Coils are designed for use
More informationG8MVL. Product Specifications
80% Variable Speed, Two Stage Heating Furnace EASIER TO SELL 80% AFUE Supports two stage cooling units Flame roll out sensors standard Category I venting Blocked vent switch Dehumidification feature in
More informationUp to 96% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL
N9MSE Product Specifications Up to 96% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL Up to 96% AFUE in upflow and horizontal positions, Up to 96% AFUE in downflow positions California NOx approved
More information95G1-E. Aluminized steel primary heat exchanger with crimped non-welded construction AL 29-4C Stainless steel secondary heat exchanger
Single Stage - High Efficiency (Constant Torque) Motor 95% Gas Furnaces Features and Benefits CONFIGURATIONS Upflow / Horizontal Downflow 95G1-E Form No. D95G1-E-100 (10/2011) HEAT EXCHANGER DESIGN Aluminized
More information95G1E PRODUCT SPECIFICATIONS SINGLE STAGE CONSTANT TORQUE MOTOR VENTING INSTALLATION FEATURES WARRANTY CONFIGURATIONS HEAT EXCHANGER DESIGN BURNER
95G1E PRODUCT SPECIFICATIONS SINGLE STAGE CONSTANT TORQUE MOTOR FORM NO. 95G1E-100 (04/2016) VENTING Designed certified for direct (2-pipe) and non direct (1-pipe) applications Easily vented with PVC pipe
More informationMulti-Position, Multi-Speed Gas Furnaces
Heating Input: 40,000 140,000 BTU/h / Multi-Position, Multi-Speed Gas Furnaces 80% AFUE Standard Features Dual-diameter tubular heat exchanger Two-stage gas valve control technology allows installer to
More information95G2E PRODUCT SPECIFICATIONS 95% TWO-STAGE CONSTANT TORQUE GAS FURNACES CONTROLS VENTING CONFIGURATIONS HEAT EXCHANGER DESIGN INSTALLATION FEATURES
95G2E PRODUCT SPECIFICATIONS 95% TWO-STAGE CONSTANT TORQUE GAS FURNACES FORM NO. 95G2E-100 (04/2016) CONTROLS Two stage gas valve Integrated ignition and fan control Control board retains last ten (10)
More information95% Gas Furnaces. Single Stage - High Efficiency (Constant Torque) Motor. Features and Benefits 95G1-E CONFIGURATIONS HEAT EXCHANGER DESIGN BURNER
95G1-E Features and Benefits CONFIGURATIONS 95% Gas Furnaces Single Stage - High Efficiency (Constant Torque) Motor Upflow / Horizontal Downflow Form No. R95G1-E-100 (01/2012) HEAT EXCHANGER DESIGN Aluminized
More informationN9MSB. PS 92 Product Specifications. 92.1% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL /2/17
92.1% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 92.1% AFUE all models in all positions California NOx approved Certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized
More informationTECHNICAL GUIDE MODELS: P4DN 80 AFUE DOWNFLOW GAS-FIRED FURNACES DESCRIPTION. WARRANTY 20-year limited warranty on the heat exchanger.
036-21053-001 Rev. A (4/00) DESCRIPTION These high efficiency, dedicated downflow compact units employ induced combustion, reliable hot surface ignition and high heat transfer tubular heat exchangers.
More informationTECHNICAL GUIDE 80 AFUE DOWNFLOW GAS-FIRED FURNACES MODELS: G8T-DN DESCRIPTION WARRANTY FEATURES Rev. B (0303)
TECHNICAL GUIDE 80 AFUE DOWNFLOW GAS-FIRED FURNACES MODELS: G8T-DN 40-130 MBH INPUT HIGH-EFFICIENCY INDUCED COMBUSTION DESCRIPTION These high efficiency, dedicated downflow compact units employ induced
More informationA962E PRODUCT SPECIFICATIONS TWO STAGE HIGH EFFICIENCY CONSTANT TORQUE GAS FURNACE CONTROLS VENTING CONFIGURATIONS HEAT EXCHANGER DESIGN
A962E PRODUCT SPECIFICATIONS TWO STAGE HIGH EFFICIENCY CONSTANT TORQUE GAS FURNACE FORM NO. A962E-100 (04/2018) CONTROLS Two stage gas valve Integrated ignition and fan control System Sentry control retains
More informationCooling Capacity CFM in. w.c. (125 Pa)
95.5% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 95.5% AFUE, all models all positions, California NOx approved Certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized
More informationCooling Capacity CFM in. w.c. (125 Pa)
92.1% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 92.1% AFUE, all models all positions, California NOx approved Certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized
More informationGMS9/GCS9 SERIES 93% AFUE
/ SERIES 93% AFUE MULTI-POSITION, SINGLE-STAGE/MULTI-SPEED GAS FURNACE HEATING CAPACITY: 46,000 115,000 BTU/H Standard Features Corrosion-resistant, aluminized-steel tubular heat exchanger and stainless-steel
More information95% Gas Furnaces A95-1E. Single Stage - High Efficiency (Constant Torque) Motor. Features and Benefits CONFIGURATIONS
A95-1E 95% Gas Furnaces Single Stage - High Efficiency (Constant Torque) Motor Features and Benefits CONFIGURATIONS Upflow / Horizontal Downflow Form No. JA95-1E-100 (10/2011) HEAT EXCHANGER DESIGN Stainless
More informationTECHNICAL GUIDE. Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES
TECHNICAL GUIDE Echelon MODELS: FC8S GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE NATURAL GAS 40-130 MBH INPUT EFFICIENCY RATING CERTIFIED DESCRIPTION These high efficiency, dedicated
More informationCooling Capacity CFM in. w.c. (125 Pa)
95.5% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 95.5% AFUE, all models all positions, California NOx approved Certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized
More informationCooling Capacity CFM in. w.c. (125 Pa)
92.1% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 92.1% AFUE, all models all positions, California NOx approved Certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized
More informationCooling Capacity CFM in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
More informationRuud High Efficiency Air Handler
Air Handlers Ruud High Efficiency Air Handler RHLL- Series X-1 (ECM) Efficiencies up to 16 SEER RHLL feature an X-1 (ECM) motor which provides enhanced SEER performance with most Ruud outdoor units. Versatile
More informationTECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE DESCRIPTION WARRANTY FEATURES
TECHNICAL GUIDE AFFINITY MODELS: PS8 GAS-FIRED HIGH EFFICIENCY SINGLE STAGE DOWNFLOW FURNACES 80% AFUE NATURAL GAS 40-130 MBH INPUT EFFICIENCY RATING CERTIFIED DESCRIPTION These high efficiency, dedicated
More informationWFAR. Product Specifications 92.1 AFUE GAS FURNACE MULTIPOISE DESIGN
92.1 AFUE GAS FURNACE MULTIPOISE DESIGN WFAR Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification for individual products, go to
More informationDM80SS / DD80SS. Single-Stage, Multi-Speed Gas Furnaces 80% AFUE Heating Input: 40, ,000 BTU/h
/ Single-Stage, Multi-Speed Gas Furnaces 80% AFUE Heating Input: 40,000 140,000 BTU/h Contents Nomenclature...2 Product Specifications...3 Dimensions...5 Airflow Data...8 Wiring Diagram...10 Accessories...11
More informationCooling Capacity CFM in. w.c. (125 Pa)
92.1% AFUE, Single Stage, PSC Gas Furnace EASIER TO SELL 92.1% AFUE, all models all positions, California NOx approved Certified to leak 2% or less of nominal air conditioning CFM delivered when pressurized
More informationWFAR. Product Specifications 92.1 AFUE GAS FURNACE MULTIPOISE DESIGN UPFLOW/DOWNFLOW/HORIZONTAL (NATURAL GAS) Heat Exchangers Warranty
92.1 AFUE GAS FURNACE MULTIPOISE DESIGN WFAR Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification for individual products, go to
More informationGMH95/GCH9 PRODUCT SPECIFICATIONS 95%/93% AFUE HEAT REPLACEMENT MULTI-POSITION, TWO-STAGE (CONVERTIBLE), MULTI-SPEED GAS FURNACE
/ 95%/93% AFUE MULTI-POSITION, TWO-STAGE (CONVERTIBLE), MULTI-SPEED GAS FURNACE HEATING INPUT: 46,000 115,000 BTU/H LIFETIME HEAT EXCHANGER LIMITED WARRANTY 10 YEAR HEAT REPLACEMENT CXCHANGER WARRANTY
More informationA95-2V. 95% Gas Furnaces Two-Stage Variable Speed HEAT EXCHANGER DESIGN CONFIGURATIONS
Two- Variable Speed HEAT EXCHANGER DESIGN 409 Stainless steel primary heat exchanger material AL29-4C Stainless steel secondary heat exchanger Non-welded crimped S-curve primary heat exchanger design for
More informationWFSR. Product Specifications 95.5 AFUE GAS FURNACE MULTIPOISE DESIGN UPFLOW/DOWNFLOW/HORIZONTAL (NATURAL GAS) Heat Exchangers Warranty
95.5 AFUE GAS FURNACE MULTIPOISE DESIGN WFSR Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification for individual products, go to
More informationG9MXE. Product Specifications
Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)
More information93% Gas Furnaces Single Stage
Features and Benefits CONFIGURATIONS Upflow / Horizontal Downflow 93% Gas Furnaces Single Stage Form No. AA931A-100 (05/2012) HEAT EXCHANGER DESIGN Aluminized steel primary heat exchanger with crimped
More informationGMS8/GDS8/GHS8. Single-Stage, Multi-Speed, Multi-Position Gas Furnace 80% AFUE. Heating Input : 40, ,000 BTU/h
// Heating Input : 40,000 140,000 BTU/h Single-Stage, Multi-Speed, Multi-Position Gas Furnace 80% AFUE Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 5 Airflow Data... 8 Wiring Diagrams...
More informationProduct Data. S Variable-speed ECM blower motor. S Two heating stages. S Humidity control when using a humidity sensing thermostat
PG8MVA PG8JVA 4 --- WAY MULTIPOISE INDUCED---COMBUSTION GAS FURNACE INPUT CAPACITIES: 70,000 thru 135,000 Btuh SERIES A Product Data multipoise design, through -the-furnace downflow venting, 13 different
More informationGKS9 Series. up to 92.1% AFUE. Upflow Multi- Position, Multi-Speed Gas Furnace. Heating Input: 46, ,000 BTU/h
Series up to 92.1% AFUE Heating Input: 46,000 115,000 BTU/h Upflow Multi- Position, Multi-Speed Gas Furnace Standard Features Dual-diameter tubular heat exchanger Single-stage combination redundant gas
More informationG9MXE. Product Specifications
Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)
More information92G1 PRODUCT SPECIFICATIONS SINGLE STAGE GAS FURNACE CONFIGURATIONS HEAT EXCHANGER DESIGN BURNER CABINET DESIGN AIR DELIVERY SYSTEM CONTROLS VENTING
92G1 PRODUCT SPECIFICATIONS SINGLE STAGE GAS FURNACE FORM NO. 92G1-100 (10/2018) CONFIGURATIONS Upflow/Horizontal Downflow HEAT EXCHANGER DESIGN Aluminized steel design primary heat exchanger with crimped
More informationWFEL. Product Specifications. 80% AFUE GAS FURNACE Multipoise Design
80% AFUE GAS FURNACE Multipoise Design WFEL Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
More informationGMH8/GDH8. Two-Stage Convertible Multi-Speed Gas Furnaces 80% AFUE
/ Two-Stage Convertible Multi-Speed Gas Furnaces 80% AFUE Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 5 Airflow Data... 7 Wiring Diagram... 10 Accessories... 11 Minimum Filter
More informationF8MTL. Product Specifications
80% Two Stage Heating Furnace EASIER TO SELL 80% AFUE Suppts two stage cooling units Flame roll out senss standard Categy I venting Blocked vent switch Dehumidification feature in cooling 24 VAC and 115
More informationWFEL. Product Specifications. 80% AFUE GAS FURNACE Multipoise Design
80% AFUE GAS FURNACE Multipoise Design WFEL Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
More information14 SEER R -410A PACKAGE GAS / ELECTRIC UNIT 2 to 5 TON
14 SEER R -410A PACKAGE GAS / ELECTRIC UNIT 2 to 5 TON Two -Stage Gas Heating/Two -Stage Electric Cooling REFRIGERATION CIRCUIT All models are equipped with high efficiency two--stage Copeland UltraTech
More informationDD80HS. Two-Stage, Convertible Multi-Speed Gas Furnace 80% AFUE. Heating Input: 40, ,000 BTU/h
Two-Stage, Convertible Multi-Speed Gas Furnace 80% AFUE Heating Input: 40,000 100,000 BTU/h Contents Nomenclature...2 Product Specifications...3 Dimensions...4 Airflow Data...5 Wiring Diagram...7 Accessories...8
More information