Anthony Glulam Advantages

Size: px
Start display at page:

Download "Anthony Glulam Advantages"

Transcription

1 GLULAM

2 Table of Contents Glulam Advantages...1 About Us...2 Anthony Power Products Family...3 Design Properties V4 1.7E IJC Framing Load Tables...-8 V4 1.7E Stock Depth Industrial Load Tables V3 1.8E Architectural Load Tables Load Table Notations and Examples Quick Beam Selection Guide...28 AFP 1.E Short Span Header Tables Power Column Connection Details...33 Shear Design Equations for Notched and Tapered Beams...34 Guidelines for Drilling Vertical and Horizontal Holes Dimensional Tolerances...37 Standard Radius or Curvature...38 Engineered Timbers...3 Storage, Protection, and Handling...40

3 Anthony Glulam Advantages n Economical Beam & Header n Architectural, Industrial & Framing Grades n No nail laminating necessary n Flexibility in design & installation n Cambered or non-cambered n 00F b and 1.8 E n 3 1/8, 3 1/2, 5 1/8, 5 1/2, 3/4, 8 3/4 and 10 3/4 width n Lighter than steel, LVL, and PSL n Certified Green Products n Individually wrapped The Anthony Glulam is a glued laminated beam and header used where reliable engineered wood applications are required. It is an economical alternative to LVL and PSL in many standard structural applications where the high strength and stiffness values are not really needed. Anthony s Glulam is available through wholesale stocking dealers and their retailers. The 3-1/2 and 5-1/2 widths, which match 2x4 and 2x wall framing are available. The Anthony Glulam uses only locally available Southern pine lumber which each piece is mechanically tested for strength and stiffness. To enhance Anthony Glulam quality further, all outer laminations have strict quality control procedures. Each beam has a specific lumber lay-up combination which optimizes Glulam performance. The highest strength lumber is placed in the tension and compression zones, efficiently and optimally using lumber resources. The Anthony Glulam can be used for window, door and garage door headers, floor edge and center girder beams, roof ridge beams, and commercial beams and purlins. Features Dimensional Stability: Glulam is a laminated composite product of highstrength lumber. This randomizes any natural defects so there is greater beam strength and a higher degree of reliability. There is also less likelihood of warping, twisting, checking, cupping, or shrinking. Moisture Control: Anthony Glulam consistently averages % moisture, which is near equilibrium moisture content. Building Code Evaluations: Adopted under all major material building codes and the National Design Specification 0/ (NDS). Anthony is a listee on APA s ICC ESR 140 code report. 1 Fire Performance: Glulam falls into the building code category of heavy timber; therefore, it has excellent fire performance. Quality Assurance: Glulam is manufactured in accordance with ANSI/ A10.1 (Structural Glued Laminated Timber). Plant implemented Total Quality Management, statistical process control procedures, and APA The Engineered Wood Association as our quality assurance program ensure consistent quality and performance in every Glulam.

4 The Anthony Forest Products Story Anthony Forest Products Company (AFP), headquartered in El Dorado, Arkansas, has made some dramatic changes to position itself for the twenty-first century. The generations of forest products experience passed down through the family have made this vision possible. When founded in 1, the company was Anthony Brothers Lumber Company. The name of the company has changed, and the 4th generation of the Anthony Family has taken the reigns. The company mission, however, stays the same To remain a leader in the forest products industry by: 1. Empowering the Anthony people in the constant pursuit of customer satisfaction; 2. Making Safety the standard of operating in our business; 3. Being active in the communities where our facilities and employees are located; 4. Maintaining its leadership role in sound management, utilizing forest resources through environmentally accepted practices, and manufacturing excellence through high efficiency; 5. Providing a reasonable return on investment to its shareholders. The company operates a southern pine lumber producing mill in Urbana, Arkansas; and wood chip mills in Plain Dealing, Louisiana, and Troup, Texas. The company also operates an engineered wood laminating plant in El Dorado, a laminating plant in Washington, Georgia, and a joint venture I-Joist plant, ANTHONY EACOM, Inc., in Sault Ste. Marie, Ontario, Canada. Anthony Forest s sawmill and the El Dorado laminating plant have undergone massive modernization phases over the years. Due to complete computer optimization, the sawmill is now producing 30% more lumber out of the same size logs milled previously. Not only has our sawmill diversified with changing markets, our laminating plants have diversified and have expanded to meet customer demands. Some of the company s fastest growth has been in the engineered wood products sector. The demand for engineered wood products like I-Joist forced a need to totally modernize the El Dorado facility and to add an I-Joist plant in Canada. The company joined forces with EACOM Timber Corporation of Montreal, Quebec, Canada to produce the Power Joist. The Power Joist is a high quality solid sawn lumber flange I-joist. Anthony Forest has contributed its superior customer service, plant management, engineered wood products knowledge, and distribution network to meet demands for an I-joist to complement the Power Beam I-joist compatible glulam. When the company grows, the surrounding communities also grow. We encourage and support our employees community involvement. Anthony Forest feels that civic mindedness will assist in the overall growth of the company and in the prosperity of the communities in which we reside. 2

5 Anthony Power Products Family What s included in this brochure... Anthony 00F b Glulam Allowable Load Tables Architectural, Industrial and Framing Appearance 00F b -1.7E IJC Depths 00F b -1.7E Stock Depths 00F b -1.8E Stock Depths AFP 1. E Short Span Header Allowable Load Tables 00F b -1.E-0F v Substitute for LSL and OSL Substitute for built-up lumber Anthony Power Column Allowable Load Tables Combination # F b -1.E Other Power Products Family Literature available... Power Joist PJI-40, 0, 80 and 0 Series Anthony Power Beam 3000F b -2.1E-300F v PSL and LVL Equivalent Power Rated Glulam (PRG ) 00F b -1.E-300F v IJC Depths Substitute for LVL at lower cost Power Preserved Glulam Beams and Columns Cop-Guard & Cop-8 treated glulam Southern Yellow Pine Lumber 2x4-2x Grades: MSR, #1, #2, #3, #4, and export Power Sizer Software Sizes all Power Products Family of engineered wood 3

6 F Design Properties ** Flexural Stress, F b, shall be modified by volume Factor, Cv, as outlined in ICC ESR-140, and AITC 7-Design where; Cv = [(5.5/b) 0.05 x (/d) 0.05 x (/L) 0.05 ] < 1.0 F - V4-1.7E - IJC Framing and Industrial Grades 3 1/8 Beam Width (F v =175) Depth 1/2 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /2 Beam Width (F v =175) Depth 1/2 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /4 Beam Width (F v =0) Depth 1/2 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /8 Beam Width (F v =0) Depth 1/2 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /2 Beam Width (F v =0) Depth 1/2 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) Design Values Combination F-V4 MOE 1.7x10 psi F b 00 psi F v psi 740 psi F c F - V4-1.7E - Industrial Stock Depth 3 1/8 Beam Width (Fv=175) Depth 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /8 Beam Width (Fv=0) Depth 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) / Shear Capacity (lbs) /4 Beam Width (Fv=0) Depth 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) Design Values Combination F-V4 MOE 1.7x10 psi F b 00 psi F v psi 740 psi F c 4

7 F Design Properties ** Flexural Stress, F b, shall be modified by volume Factor, Cv, as outlined in ICC ESR-140, and AITC 7-Design where; Cv = [(5.5/b) 0.05 x (/d) 0.05 x (/L) 0.05 ] < 1.0 F - V3-1.8E - Architectural Stock Depth 3 1/8 Beam Width (Fv=300) Depth 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /8 Beam Width (Fv=300) Depth 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /4 Beam Width (Fv=300) Depth 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /4 Beam Width (Fv=300) Depth 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) /4 Beam Width (Fv=300) Depth 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/8 Weight Cdb factor (L= ) I (in 4 ) Moment Capacity (Ft-lbs) Shear Capacity (lbs) Design Values Combination F-V3 MOE 1.8x10 psi F b 00 psi F v 300 psi 740 psi F c 5

8 F V4 1.7E IJC Framing Grade Allowable Floor Load Tables LDF=1.00 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/2 Width 5 1/2 Width 3/4 Width Span Depth (in.) Depth (in.) Depth (in.) (ft) 1/2 7/8 1/2 7/8 1/2 7/

9 F V4 1.7E IJC Framing Grade Allowable Roof Load Tables LDF=1. Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1., and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/2 Width 5 1/2 Width 3/4 Width Span Depth (in.) Depth (in.) Depth (in.) (ft) 1/2 7/8 1/2 7/8 1/2 7/

10 F V4 1.7E IJC Framing Grade Allowable Roof Load Tables LDF=1.25 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.25, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/2 Width 5 1/2 Width 3/4 Width Span Depth (in.) Depth (in.) Depth (in.) (ft) 1/2 7/8 1/2 7/8 1/2 7/

11 F V4 1.7E Industrial IJC Depth Allowable Floor Load Tables LDF=1.00 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width Single 5 1/8 Width Span Depth (in.) Span Depth (in.) (ft) 1/2 7/8 (ft) 1/2 7/

12 F V4 1.7E Industrial IJC Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1., and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Roof Load Tables LDF=1. These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width Single 5 1/8 Width Span Depth (in.) Span Depth (in.) (ft) 1/2 7/8 (ft) 1/2 7/

13 F V4 1.7E Industrial IJC Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.25, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Roof Load Tables LDF=1.25 These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width Single 5 1/8 Width Span Depth (in.) Span Depth (in.) (ft) 1/2 7/8 (ft) 1/2 7/

14 F V4 1.7E Industrial Stock Glulam Allowable Floor Load Tables LDF=1.00 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width 5 1/8 Width Span Depth (in.) Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/

15 F V4 1.7E Industrial Stock Glulam Allowable Roof Load Tables LDF=1. Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1., and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width 5 1/8 Width Span Depth (in.) Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/

16 F V4 1.7E Industrial Stock Glulam Allowable Roof Load Tables LDF=1.25 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.25, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width 5 1/8 Width Span Depth (in.) Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/

17 F V4 1.7E Industrial Stock Glulam Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Floor Load Tables LDF=1.00 These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Single Span (ft) Allowable Loads for Anthony Glulam in Pounds per Linear Foot 3/4 Width Depth (in.) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

18 F V4 1.7E Industrial Stock Glulam Allowable Roof Load Tables LDF=1. Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1., and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Single Span (ft) Allowable Loads for Anthony Glulam in Pounds per Linear Foot 3/4 Width Depth (in.) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

19 F V4 1.7E Industrial Stock Glulam Allowable Roof Load Tables LDF=1.25 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.25, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Single Span (ft) Allowable Loads for Anthony Glulam in Pounds per Linear Foot 3/4 Width Depth (in.) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

20 F V3 1.8E Architectural Stock Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Floor Load Tables LDF=1.00 These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width 5 1/8 Width Span Depth (in.) Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/

21 F V3 1.8E Architectural Stock Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1., and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Roof Load Tables LDF=1. These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width 5 1/8 Width Span Depth (in.) Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/

22 F V3 1.8E Architectural Stock Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.25, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Roof Load Tables LDF=1.25 These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3 1/8 Width 5 1/8 Width Span Depth (in.) Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/

23 F V3 1.8E Architectural Stock Depth Allowable Floor Load Tables LDF=1.00 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3/4 Width Span Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

24 F V3 1.8E Architectural Stock Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1., and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Roof Load Tables LDF=1. These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3/4 Width Span Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

25 F V3 1.8E Architectural Stock Depth Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.25, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/0 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) Allowable Roof Load Tables LDF=1.25 These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 3/4 Width Span Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

26 F V3 1.8E Architectural Stock Depth Allowable Floor Load Tables LDF=1.00 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 8 3/4 Width Span Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

27 F V3 1.8E Architectural Stock Depth Allowable Floor Load Tables LDF=1.00 Key - for each clear span there are three numbers: Row 1: Maximum Total Load with LDF of 1.0, and deflection limited to L/0 Row 2: Maximum Live Load limited by deflection of L/30 Row 3: Required Bearing Length in trimmer thickness (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.) These tables can be used to size simple span beams and headers that carry uniform loads. The PLF loads must be calculated and take into account all floor and roof framing loads coming onto the beam or header. Codes do allow live load reductions. See appropriate code sections. Allowable Loads for Anthony Glulam in Pounds per Linear Foot Single 10 3/4 Width Span Depth (in.) (ft) 8 1/4 5/8 3/8 13 3/4 1/8 1/2 17 7/8 1 1/4 5/8 23 3/8 3/4 2 1/8 27 1/2 28 7/

28 Load Table Notations and Examples Anthony Glulam Floor and Roof PLF Loading Notes 1. Values shown are the maximum uniform loads in pounds per linear foot (PLF) that can be applied to the beam. Beam weight has been subtracted from the total allowable load. Load tables are based on dry use conditions. 2. LDF = Load Duration Factor per code requirements 3. Bearing length shown is required at each end of header and is based on an allowable bearing stress of 740 psi for all tables except low stress header which is 50 psi. The beam must be sitting directly on top of 1 or more trimmers. A longer bearing length may be required depending on the material that the beam is bearing on. For example, if the beam is sitting on a SPF top plate, a longer bearing length will be required due to the lower compression perpendicular-to-grain design value for SPF. 4. The bearing lengths show the number of trimmers needed (e.g., 1.5 = 1 trimmer, 3.0 = 2 trimmers, etc.). This is based on the maximum PLF loads. Shorter bearing lengths may be used with lighter loads. 5. Tables are based on simple span conditions using the actual span as the center-to-center of bearing. Tables do not apply for continuous or multiple span conditions. The clear opening for the actual span given can be found by subtracting the listed bearing length from the actual span.. The beam is assumed to be loaded on the top edge and supported at bearing points. The beams should be laterally braced. 7. For deflection limits of L/0 and L/480, multiply The Maximum Live Load figure (Row 2) by 1.5 and 0.75, respectively. For deflection factors of L/0 and L/30, multiply the Maximum Live Load figure (row 2) by and 0.7, respectively. The result shall not exceed the total load. Procedures for Using Simple Span Beam Tables 1. To size beams from the Floor and Roof PLF Tables, it is required to have the following: a. Live load determined by the governing Building Code b. The dead load c. The beam span or clear opening d. Span carried or tributary width 2. These tables may be used to size a simple span uniformly distributed loaded beam or to determine the maximum load capacity of a specific size Glulam beam. The allowable loads shown in PLF tables include the beam weight. A simple span condition exists when the beam is supported on each end without overhangs. A continuous or cantilever loading application may require a balanced layup and an engineering or design review. Garage Door Header: Single Story Example Problem Determine the header size for the conditions below: Roof Load Conditions: Live (LL) = 30 psf Dead (DL) = 10 psf Building Width (B) = Overhang = 2 Header Actual Span (L) = 17 Formula: Total Load = (B/2+2 ) x (LL + DL) = total applied load in PLF Live Load = (B/2+2 ) x LL = total live load in PLF Example: Total Load = (/2 + 2) x ( ) = 50 PLF Live Load = (/2 + 2) x 30 = 4 PLF To size: 1. Go to allowable roof load tables on page 7 titled F V4 1.7E IJC (LDF=1.). Find the 17 actual span row. 2. Using the top row, find a total load greater than 50 PLF (3.5 x ) 3. Using the middle row, find a live load greater than 4 PLF. Beam to select: 3-1/2 x or (bearing required = 3 ) Notes: 1. Local code may require an engineered system of wall bracing for wall sections less than 4 in length adjacent to door openings. A glulam garage door header extended continuously over these shorter walls adjacent to the garage door opening is an integral part of these engineered systems. 2. If attic loading is anticipated, additional floor loading must be considered. Example: Add Floor LL=25, DL=10 Revised Total Load = 80 PLF, Live Load = 7 PLF (5 1/2 x required) 2

29 Load Table Examples Garage or Window Header: Two Story Example Problem Determine the header size for the conditions below: Roof Load Conditions: Live (LL) = 30 psf Dead (DL) = psf Total = 45 psf Floor Load Conditions: Live (LL) = 40 psf Dead (DL) = 10 psf Total = 50 psf Calculate Total Load: Roof Load = (28/2 + 2) x 45 = 7 PLF Floor Load = (/2) x 50 = 350 PLF Wall Load = 8 x 10 psf = 80 PLF Total Load = 50 PLF Calculate Live Load : Roof Load = (28/2 + 2) x 30 = 480 PLF Floor Load = (/2) x 40 = 280 PLF Live Load = 70 PLF Anthony Glulam Sizing Examples 28 2 To Size: 1. Go to F IJC Floor Load Table using LDF = 1.00 and actual span row (page ). 2. Using top row, find total load equal to or greater than 50 PLF. Pick the 3 1/2 x since (1 for 3 1/2 x ) is less than 5%. It is safer to go up one size. 3. Using middle row, find live load equal to or greater than 70 PLF. Total Load controlled, use 3 1/2 x F IJC. Beam to Select: 3-1/2 x (3 bearing required) or 5 1/2 x (3 Bearing required) F V3 Architectural Floor Girder Beam Example Problem Floor Load Conditions: Live (LL) = 40 psf Dead (DL) = psf Building Width (B) = Calculate Total Load: Total Load = (/2) x (40 + ) = plf Calculate Live Load: Live Load = (/2) x 40 = 480 plf Beam to Select (Floor Load Table): 5-1/8 x 1/8-3 or (Bearing Required 3 ) ' building width ' actual span F V3 Architectural Simple Roof Rafter Example Problem Determine the rafter size for the conditions below: Roof Load Conditions: Live (snow) = 25 psf Dead = psf Rafter Spacing: 5 on center Rafter Span: Slope: 4/ Calculate Total Load: Total Load = 5(25 + ) = 0 plf Live Load = 5(25) = 5 plf Beam to Select (Roof 1. Table, Page 1): 3-1/8 x (Bearing Required 1.5 ) 2' ' 5' Note: If roof is greater than 4/ pitch, dead load must be figured on total horizontal length of rafter. 27

30 Stick Frame Roof Stick Frame Roof Stick Frame Roof Stick Frame Roof Stick Frame Roof Stick Frame Roof Stick Frame Roof Floor Beam House Width Floor Floor Floor Floor Beam 1 Beam 2 Beam 3 Beam 4 Beam 5 Floor Only Beam Floor Only House Width Beam Length Beam 1 Beam 2 Beam 3 Beam 4 Beam 5 Beam ' 3 1/8" x " F V4 3 1/8" x " F V4 3 1/8" x 3/8" F V4 3 1/8" x 1/8" F V4 3 1/8" x " F V4 3 1/8" x 3/8" F V4 '- 3 1/8" x " F V4 3 1/8" x 13 3/4" F V4 3 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 3 1/8" x 3/8" F V4 3 1/8" x 1/8" F V4 '- 3 1/8" x 3/8" F V4 3 1/8" x 1/8" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 5 1/8" x 1/2" F V4 3 1/8" x 13 3/4" F V4 5 1/8" x 1/8" F V4 ' ' 3 1/8" x 13 3/4" F V4 3 1/8" x 1/8" F V4 3 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 3 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 ' 3 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 1/2" F V4 5 1/8" x 5/8" F V4 3 1/8" x 1/2" F V4 5 1/8" x 1/2" F V4 ' 3 1/8" x 1/8" F V4 5 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 5 1/8" x " F V4 5 1/8" x 1/8" F V4 3/4" x 1/2" F V4 2' 3 1/8" x 1/2" F V4 5 1/8" x 1/2" F V4 5 1/8" x 1 1/4" F V4 5 1/8" x 23 3/8" F V4 5 1/8" x 1/2" F V4 3/4" x 1 1/4" F V4 ' 3 1/8" x " F V4 3 1/8" x " F V4 3 1/8" x 3/8" F V4 5 1/8" x 13 3/4" F V4 3 1/8" x " F V4 3 1/8" x 13 3/4" F V4 '- 3 1/8" x " F V4 3 1/8" x 13 3/4" F V4 3 1/8" x 1/8" F V4 5 1/8" x 17 7/8" F V4 3 1/8" x 3/8" F V4 3 1/8" x 1/2" F V4 '- 3 1/8" x 3/8" F V4 3 1/8" x 1/8" F V4 28' ' 3 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 ' 3 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 ' 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 5 1/8" x 1 1/4" F V4 3 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 5 1/8" x 5/8" F V4 3 1/8" x 1/8" F V4 5 1/8" x 1/2" F V4 5 1/8" x 1/2" F V4 5 1/8" x " F V4 3 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 5 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 3/4" x 5/8" F V4 5 1/8" x 1/8" F V4 5 1/8" x 1 1/4" F V4 2' 5 1/8" x 1/8" F V4 5 1/8" x 17 7/8" F V4 5 1/8" x 1 1/4" F V4 3/4" x " F V4 5 1/8" x 1/2" F V4 5 1/8" x 5/8" F V4 ' 3 1/8" x " F V4 '- 3 1/8" x 3/8" F V4 3 1/8" x 13 3/4" F V4 '- 3 1/8" x 13 3/4" F V4 3 1/8" x 3/8" F V4 3 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 ' ' 3 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 1/8" F V4 5 1/8" x " F V4 5 1/8" x 1/2" F V4 3 1/8" x " F V4 3 1/8" x 13 3/4" F V4 5 1/8" x 1 1/4" F V4 3 1/8" x 13 3/4" F V4 5 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 3/4" x 1/2" F V4 3 1/8" x 1/8" F V4 5 1/8" x 1/2" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 5 1/8" x 1/2" F V4 ' 3 1/8" x 1/8" F V4 5 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 3/4" x 5/8" F V4 5 1/8" x 1/8" F V4 5 1/8" x 1 1/4" F V4 ' 3 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 5 1/8" x 1 1/4" F V4 3/4" x " F V4 5 1/8" x 1/2" F V4 5 1/8" x 5/8" F V4 2' 5 1/8" x 1/8" F V4 5 1/8" x 1 1/4" F V4 5 1/8" x 5/8" F V4 3/4" x 23 3/8" F V4 5 1/8" x 17 7/8" F V4 5 1/8" x " F V4 ' 3 1/8" x " F V4 3 1/8" x 3/8" F V4 3 1/8" x 13 3/4" F V4 5 1/8" x 17 7/8" F V4 3 1/8" x 3/8" F V4 3 1/8" x 1/8" F V4 '- 3 1/8" x 3/8" F V4 3 1/8" x 1/8" F V4 3 1/8" x 1/2" F V4 3/4" x 1/2" F V4 3 1/8" x 13 3/4" F V4 5 1/8" x 1/8" F V4 '- 3 1/8" x 13 3/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 5 1/8" x 1/8" F V4 3/4" x 1 1/4" F V4 3 1/8" x 1/8" F V4 5 1/8" x 1/2" F V4 3' ' 3 1/8" x 1/8" F V4 5 1/8" x 1/8" F V4 5 1/8" x 1/2" F V4 3/4" x 1 1/4" F V4 3 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 ' 3 1/8" x 1/2" F V4 5 1/8" x 13 3/4" F V4 5 1/8" x 1/2" F V4 5 1/8" x 17 7/8" F V4 3/4" x " F V4 5 1/8" x 1/8" F V4 5 1/8" x 1 1/4" F V4 ' 5 1/8" x 1/8" F V4 5 1/8" x 17 7/8" F V4 5 1/8" x 1 1/4" F V4 No Solution / bearing restriction 5 1/8" x 1/2" F V4 5 1/8" x 5/8" F V4 2' 5 1/8" x 1/2" F V4 5 1/8" x 1 1/4" F V4 5 1/8" x 5/8" F V4 No Solution / bearing restriction 5 1/8" x 17 7/8" F V4 3/4" x 5/8" F V4 Quick Beam Selection Guide General Notes for Anthony Forest Products Beam Selection Table Table is based on: Uniform loads Simple span only. Do not use table if joists are continuous span. Roof is stick framed with 1 - soffits. Load is psf. LL & 10 psf. DL Ceiling is uninhabitable attic without storage. Load is 10 psf. LL & 5 psf. DL. Floor loading is 40psf. live load & psf. dead load. Exterior wall weights of 80 plf., interior 0 plf. Deflection criteria of L/30 live load and L/0 total load. Beam Length is out to out of 2 x 4 walls, unless noted otherwise (see below). Bearing is 3 1/2 (except at - & - which is 3 ). Beams are not designed to support brick load. How to Use This Table 1. Determine House Width. 2. Locate Beam Length. 3. Determine Beam Location. 4. Select Anthony Forest Products beam width and depth.

31 AFP 1.E Short Span Header (00F b - 0F v - 50F c ) Features & Advantages BUILT-UP LUMBER SUBSTITUE SURFACE SEALED FOR STABILITY FULL 3-1/2 WIDTH NO SHIMMING CONSISTENT QUALITY & UNIFORMITY LIMITED LIFETIME WARRANTY ONE PIECE INSTALLATION SAVE $$ APPEARANCE GRADE: FRAMING GRADE Design Values 1. Header Combination AFP 1. Header MOE 1. x 10 psi F b F v F c 00 psi 0 psi 50 psi Allowable Design Stresses and Properties (100% Load Duration) Standard Depths (in.) 4 1/8 5 1/ /4 1/2 1/4 7/8 Weight (lbs./lineal ft.) C db factor (L=') I (in 4 ) Moment Capacity (lbs-ft) Shear Capacity (lbs) Notes: 1. Header weight based on 3 pcf. 2. Moment Capacities are based on span up to. 3. Flexural Stress, F b, shall be modified by Volume Factor, C v, as outlined in APA Y-7 Design and in the 0/ National Design Specifications (NDS) for Wood Construction. 4. Allowable design properties and load capacities are based on dry use conditions. 2

32 Header Comparison Table AFP 1.E vs. LSL Allowable Floor Load (PLF) - LDF=1.00 Design Span = Header Material 1.E AFP 3-1/2"x5-1/2" 1.35 E LSL* 1.55 E LSL** 1.EAFP 3-1/2"x7" 1.E AFP 3-1/2"x-1/4" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x-1/2" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x-1/4" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x-7/8" 1.35 E LSL* 1.55 E LSL** Design Span = Header Material 1.E AFP 3-1/2"x5-1/2" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x7" 1.E AFP 3-1/2"x-1/4" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x-1/2" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x-1/4" 1.35 E LSL* 1.55 E LSL** 1.E AFP 3-1/2"x-7/8" 1.35 E LSL* 1.55 E LSL** TL LL TL LL TL LL TL LL TL LL TL LL TL LL L/0 L/30 L/0 L/30 L/0 L/30 L/0 L/30 L/0 L/30 L/0 L/30 L/0 L/ Allowable Roof Load (PLF) - LDF= TL LL TL LL TL LL TL LL TL LL TL LL TL LL L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/0 L/ * 1.35 LSL design values based upon 1730F b, 1.35E, and 410F v. ** 1.55 LSL design values based upon 230F b, 1.55E, and 410F v Notes: 1. Values shown are the maximum uniform loads in pounds per lineal foot (PLF) which can be applied to the header. Header weight has been subtracted from the allowable total load (TL). 2. When no live load (LL) is given, total load (TL) controls. 3. Headers are assumed to be loaded on the top edge with continuous lateral support along compression edge. 4. Bearing length shall be provided based upon F c (perp) of 50psi for AFP 1. SSH. The deeper depths at short spans will require bearings over 3.

33 Power Column FEATURES Combination #50 (#1 Dense SYP) MOE = 1.x10 psi F b = psi Fc = psi Architectural & Industrial Appearance Individually Wrapped 3 1 / 8, 3 1 / 2, 5 1 / 8, 5 1 / 2, 3 / 4, 7 & 8 3 / 4 Widths Treated Columns Available SERVICE AND SUPPORT National distribution through stocking dealers Comprehensive technical support literature and sizing software SM 33

34 Anthony Power Columns Combination #50 Allowable Axial Loads (Pounds) for Combination No. 50 Glulam Columns Side loads are not permitted. End loads are limited to a maximum eccentricity of either 1/ column width or depth, whichever is worse. Effective Lamination Net Width = 3-1/8 in. Column Net Depth = 4-1/8 in. (3 lams) Net Depth = 5-1/2 in. (4 lams) Net Depth = -7/8 in. (5 lams) Net Depth = 8-1/4 in. ( lams) Length Load Duration Factor Load Duration Factor Load Duration Factor Load Duration Factor (ft) ,450 13,780,00,50,700,740 23,0 25,870 27,170 2,30,280 34,010 8,0,5,8,0 13,300 13,0,830, 17,080,,350,70 8,0,410,550 8,40 8,780 8,50 10,10 10,80,10 13,750,, ,410 4,530 4,10,000,0, 7,510 7,710 7,8,780 10,00 10,0 3,280 3,30 3,400 4,450 4,550 4,00 5,50 5,80 5,750 7,280 7,440 7,540 Effective Lamination Net Width = 3-1/2 in. Column Net Depth = 3-1/2 in. (3 lams) Net Depth = 4-1/8 in. (3 lams) Net Depth = 5-1/2 in. (4 lams) Net Depth = 7 in. ( lams) Length Load Duration Factor Load Duration Factor Load Duration Factor Load Duration Factor (ft) ,750 13,130 13,0,410,10 17,0,740 25,0 2,50 2,700,50 34,50,130,810 10,0,330,0,10, 17,0 17,770,00 23,300,0 8,00,10 7,00 8,100 8,40 8,70,0,0,,350,000, ,830 5,000 5,00 5,880,070,10 8,040 8, 8,430,00,450,50 3,50 3,750 3,810 4,4 4,540 4,10,010,0,250 8, ,70 2,840 2,10 2,50 3,430 3,510 3,550 4,50 4,750 4,800,40,00,80 Effective Lamination Net Width = 5-1/8 in. Column Net Depth = 5-1/2 in. (4 lams) Net Depth = -7/8 in. (5 lams) Net Depth = 8-1/4 in. ( lams) Net Depth = -5/8 in. (7 lams) Length Load Duration Factor Load Duration Factor Load Duration Factor Load Duration Factor (ft) ,30 33,0 35,70 40,0 44, 4,800 4,550 54,880 58,0 57,810 4,0 7,840 8,0 2,850 27,0,250 34,500 35,70 40,40 43,710 45,40 47,4 51,000 53, ,740,830,470 25,0 2,270 27,000,0 33,740 34,740 37,30 3,370 40,5,40,270,30 1,570,340,70 25,250 2,310 2,30 2,40 30,700 31,4,480,80 13,0,00,0,400,230,40,350 23,00,430,00 10,0 10,430 10,50,80 13,030 13,0,500 17,000 17,280 1,250 1,830,0 8,30 8,50 8,710 10,480 10,740 10,80 13,0,050,250,70,30,30 7,040 7,0 7, 8,800,000,0,5,70,40 13,440 13,750 13,30 Effective Lamination Net Width = 5-1/2 in. Column Net Depth = 5-1/2 in. (4 lams) Net Depth = 7 in. ( lams) Net Depth = 8-1/4 in. ( lams) Net Depth = -5/8 in. (7 lams) Length Load Duration Factor Load Duration Factor Load Duration Factor Load Duration Factor (ft) , 3,550 38,810 45,10 51, 54,840 54,50 1,0 5,070 4,0 71,370 75, ,4 2,40 30,50 3, 42,50 44,5 4,310 50,10 52,470 54,030 58,50 1,0 10,70 23,280,030 31,80 33,50 34,50 37,330 3,50 40,840 43,50 4,0 47,40 17,550,380,850 25,300 2,470 27,0 2,8 31,10 31,0 34,70 3,30 37,0,0,70,080,430,0,0,080 25,000 25,5 28,00 2,0 2,780,70,00,,70 17,300 17,10 1,750,30,70 23,040 23,70,0,730 10,0 10,0 13,50,350,580,440,10 17,0 1,10 1,730,040 8,230 8,440 8,570,780,080,250 13,880,230,430,0,00,840 7,040 7,0 7,300 10,070 10, 10,4,80,130, 13,840,0,330 Effective Column Net Depth = -7/8 in. (5 lams) Lamination Net Width = -3/4 in. Net Depth = 8-1/4 in. ( lams) Net Depth = -5/8 in. (7 lams) Lamination Net Width = 7 in. Net Depth = 7 in. ( lams) Length Load Duration Factor Load Duration Factor Load Duration Factor Load Duration Factor (ft) ,730 53,70 5,880 3,540 70,30 75,0 74,70 82,750 87,40 53,40 5,380 3, ,70 45,0 47,080 55,30 5,40 2,00 4,,30 73,040 4,00 51,070 53,550 34,50 37,100 38,350 4,5 4,4 51,00 54,280 57,50 5,00 40,070 42,840 44,450 2,100 30,50 31,410 38,750 40,0 41,810 45,0 47,470 48,770 33,840 35,730 3,830,30 25,430 2,030,450 33,810 34,00 37,80 3,450 40,370 28,30 2, ,40,410,850 27,430 28,430 2,010,000 33,170 33,840,400 25,400 25,80 17,50,230,570 23,430,0,10 27,330 28,0 28,7,80,740,0,0,0,50,0,70,0 23,570,250,40,10,780 1,0 13,280 13,30 13,830 17,580,040,310,510,050,30,00,370,40 NOTES and Allowable Design Properties 1. The tabulated allowable loads apply only to one-piece glulam members made with all N1D laminations (Combination 50) without special tension laminations. 2. Applicable service conditions = dry 3. The tabulated allowable loads are based on simply axially loaded columns subjected to a maximum eccentricity of either 1/ column width or 1/ column depth, whichever is worse. For side loads, other eccentric end loads, or other combined axial and flexural loads, see 05 NDS 4. The column is assumed to be unbraced, except at the column ends, and the effective column length is equal to the actual column length. 5. Design properties for normal load duration and dry-use service conditions: Compression parallel to grain (Fc) = 2,300 psi for 4 or more lams, or 1,700 psi for 2 or 3 lams. Modulus of elasticity (E) = 1. x 10 psi Flexural stress when loaded parallel to wide faces of lamination (Fby) = 2,300 psi for 4 or more lams, or 2,100 psi for 3 lams. Flexural stress when loaded perpendicular to wide faces of lamination (Fbx) = 2,100 psi for 2 lams to in. deep without special tension laminations. Volume factor for Fbx is in accordance with 0/ (NDS). Size factor for Fby is (/d) 1/, where d is equal to the lamination width in inches. Effective Column Length (ft) Lamination Net Width = 8-3/4 in. Net Depth = 8-1/4 in. ( lams) Net Depth = -5/8 in. (7 lams) Load Duration Factor Load Duration Factor ,0 4,0 100, ,730 1,800 3,0 10 7,510 84,10 8,580 4, ,10 1,430 8,0 74,100 77,10 8,440 4,10 100,010 5, 3,800,0 77,0 83,0 8,480 51,80 54,0 5,440 7,5 71,50 73,40 44,70 47,030 48,330 58,0 1,0 3,4 38,30 40,50 41,40 51,0 53,440 54,70 34,00 35,400 3,0 44,840 4,10 47,40 2,80 31,00 31,80 3,5 40,40 41,750

35 Connection Details Common types of connectors and connection details are shown. The design values for most fasteners used with the Glulam are the same as those for solid timber and LVL. It must be noted that connections designed for specific applications may vary based on design loads and local code requirements. More information on connections can be found in APA Glulam Connection Details form No. T300H on our website, Your local Glulam dealer can also provide connection detail literature and hardware. Typical Hangers Face Mount Hanger Top Mount Hanger Top Mount Hanger Typical Connections Top Mount Hanger Top Mount Hanger Wood or steel column Hanger Face Mount Hanger Beam to Beam Beam to Column Floor Beam to Joist Strap per code if top plate is not continuous over header Tie strap Trimmers Header to Frame Beam to Frame Do not cut or drill Anthony Glulams without tech note support 33

36 Shear Design Equations for Notched and Tapered Beams Compression side Compression side d d f v = 3V 2bd f v = 3V 2bd (a) Square End Bearing (b) Slope End Bearing 3d maximum 0.4d Max. 3d e or 1/3 of the span, whichever is less e d/3 Min. d e d d e > 0.d d f v = 3V 2bd e When e < d e, f v = 3V d - d 2b d- e d e e (c) Sloped End Cut for Roof Drainage When e > d e, f v = 3V 2bd e (d) Compression-side Notch d Bearing Length (f) Tension-side Notch f v = shear stress (psi) V = shear force at notch location (lb) b = width of beam (in.) d = depth of beam (in.) d e = effective depth as shown (in.) e = length of notch as shown (in.) Source: APA EWS S

37 Guidelines for Drilling Vertical and Horizontal Holes VERTICAL HOLES Whenever possible, avoid drilling vertical holes through glulam beams. As a rule of thumb, vertical holes drilled through the depth of a glulam beam cause a reduction in the capacity at the location directly proportional to the ratio of 1-1/2 times the diameter of the hole to the width of the beam. For example a one inch hole drilled in a -inch-wide beam would reduce the capacity of the beam at that section by approximately (1 x 1-1/2) =25% For this reason, when it is necessary to drill vertical holes through a glulam member, the holes should be positioned in areas of the member that are stressed to less than 50 percent of design in bending. In a simply supported, uniformaly loaded beam, this area would be located from the end of the beam inward approximately 1/8 of the beam span. In all cases, the minimum clear edge distance, as measured from either side of the member to the nearest edge of the vertical hole, should be 2-1/2 times the hole diameter. Use a drill guide to minimize wandering of the bit as it passes through knots or material of varying density, and to insure a true alignment of the hole through the depth of the beam. HORIZONTAL HOLES Like notches, holes in a glulam beam remove wood fiber, thus reducing the net area of the beam at the hole location and introducing stress concentrations. These effects cause a reduction in the capacity of the beam in the area of the penetration. For this reason, horizontal holes in glued laminated timbers are limited in size and location to maintain the structural integrity of the beam. Figure 3 shows the zones of a uniformly loaded, simply supported beam where the field drilling of holes may be considered. These non-critical zones are located in portions of the beam stressed to less than 50 percent of design bending stress and less than 50 percent of design shear stress. For beams of more complex loading or other than simple spans, similar diagrams may be developed. 1 = length of beam d = depth of beam Field-drilled holes shoud be used for access only and should not be used as attachment points for brackets or other load bearing hardware unless specifically designed as such by the engineer or designer. Examples of access holes include those used for the passage wires, electrical conduit, small diameter sprinkler pipes, fiber optic cables, and other small, lightweight materials. These field drilled horozontal holes should meet the following guidelines: 1. Hole size: The hole diameter should not exceed 1-1/2 inches or 1/10 the beam depth, whichever is smallest, with the exception of 1-inch-diameter or smaller holes as noted in Item 2 below. 2. Hole location: The hole should have a minimum clear distance, as measured from the edge of the hole to the nearest of the beam, of 4 hole diameters to the top or bottom face of the beam and 8 hole diameters from the end of the beam. Note that the horizontal hole should not be drilled in the moment-critical zone, as defined in the figure above, unless approved by an engineered or architect qualified in engineered timber design. 35

38 A 1-inch diameter or smaller hole may be cut at the middle half of the beam depth anywhere along the span, except for the area that is within inches of clear distance between the face of the support and the nearest edge of the hole, providing the following conditions are met: a. the beam is at least 7-1/4 inches in depth, b. the beam is subject to uniform loads only, c. the span-to-depth ratio ( /d) is at least 10, d. the hole spacing and maximum number of holes must meet the requirements specified in Items 1 and 2 bellow, and e. the hole must not be cut in cantilevers. If the depth-to-span ratio of the beam is less than 10, the 1-inch diameter of smaller hole may be cut in accordance with the provisions listed above except that the location of the hole must maintain a clear distance between the face of the support and the nearest edge of the hole of at least 1/ of the span. 1. Hole Spacing: The minimum clear spacing between adjacent holes, as measured between the nearest edge of the holes, should be 8 hole diameters based on the largest diameter of any adjacent hole in the beam. 2. Number of holes: The maximum number of holes should not exceed 1 hole per 5 feet of beam length. In other words, the maximum number of holes should not exceed 4 for a -foot-long beam. The hole spacing limitation, as given above, should be satisfied separately. For glulam members that have been oversized, the guidelines give above may be relaxed based on an engineering analysis. Regardless of the hole location, holes drilled horizontally through a member should be positioned and sized with the understanding that the beam will deflect over a period of time under in-service loading conditions. This deflection could cause distress to supported equipement or piping unless property considered. Beam depth, d (in.) 7-1/4 7-1/2 8-1/4-1/4-1/2-5/8 10-1/2-1/4-7/8-3/8 13-1/2-1/8-1/2 17-7/8 1-1/4 1-1/2-5/8-1/ Span when /d =

39 Dimensional Tolerances Glulam Appearance Grades 37

40 Standard Radius or Curvature (feet) Camber is the amount of bend or curvature which can be built into a Glulam to offset anticipated deflection or to compensate for dead load deflection. This is important for longer spans where other non-cambered engineered wood products may sag after loads are applied. Anthony Forest s standard radius is 00. Built-in camber will reduce ponding on flat roofs and eliminate unsightly appearance of deflection under load. Glulam is also offered non-cambered. Camber Before Installation Camber After Installation With Roof and Wall Loads Applied Without camber, a beam or header may sag after loads are applied. Find appropriate size selection table (e.g., Garage Door, Floor Girder, etc.) Double check your work to ensure you are using a table that meets or exceeds your loading conditions. Find Applied Load Conditions (e.g., Live psf, Dead psf) and stress increase (e.g., 1.0 for floor load, 1. for roof snow load, 1.25 for roof construction load). Is Camber Needed? If the header or beam is greater than -0, camber is necessary. Find clear opening or column spacing that meets your conditions. If exact opening is not listed, use the next larger opening or column spacing. Find Glulam size from Anthony Size Selection Tables or Anthony Power Sizing Software. Determine span of rafters or trusses framing into header We encourage you to compare cost with other products, such as LVL and PSL Header Span (3 ) Camber is the amount of bend or curvature which can be built into a Glulam beam to offset anticipated deflection or to compensate for dead load deflection. Example: a 00 Anthony Glulam beam at allows 1/8 camber LENGTH 10 1/8 1/8 1/8 1/4 1/4 1/4 3/8 3/ /2 5/8 5/8 3/4 7/ /8 1 1/4 Radius /8 1 1/2 1 5/8 1 3/4 1 7/ /4 1 3/ /2 2 3/4 38

41 Engineered Timbers offer versatility, economy, strength, and durability Versatility Anthony glued laminated timber has a proven track record of reliability for a variety of structural applications. Exposed beams offer a dramatic design element, yet provide an unusual sense of softness, natural charm, and inviting warmth. At the same time, engineered timber construction provides an exceptionally high level of safety, durability, and cost efficiency. Kiln-dried Anthony Glulam offers a strong, workable long span performance capability unmatched by any other building material. Cost Effective/Energy Efficient Anthony Glulam is surprisingly economical as compared to the higher cost composites or steel. Glulam has a high strength to weight ratio and is sized to fit all system-type framing applications. One piece construction reduces building time and cost, and Glulam can be trimmed to fit on the job site. The energy efficiency of engineered timber can provide additional savings to the property owner. The natural thermal and insulating qualities of laminated wood can be combined with thermally efficient insulation materials to keep heat loss at a minimum. Strong, Durable, Fire Safe, and Stable Throughout history, wood has been a durable building material, assuming proper principles of design, construction, and maintenance are followed. Anthony Glulam provides an even higher degree of proven quality manufacturing. Both the 00F and 3000F Power Beam exhibit property characteristics superior to solid sawn wood. Extra precautions are taken to ensure all laminations are kilndried to a maximum % moisture content. The end product results in a beam member with an exceptional level of dimensional stability, virtually eliminating checking, twisting, warping, and shrinkage. High resilience allows Glulam to absorb shocks that could rupture alternative building materials like concrete or steel. Glulam is also ideal for use in areas subject to high winds or earthquake damage. Glulam also has excellent fire-resistive qualities. The performance of Glulam under fire conditions is markedly superior to most unprotected non-combustible materials. Readily Available Anthony Glulam is readily available through a network of stocking distributors throughout the country. Glulam is offered in specified lengths up to 0 in industrial, architectural, and framing grades. All beams are either bundled or individually wrapped with water-resistant paper. Beams are squared-end trimmed and manufactured with camber or no-camber. Beams are wax sealed for improved protection. Computer Software Anthony Forest offers a Power Sizer software for fast and accurate sizing of most beam applications. Roof Rafters Ridge Beams Ridge Beams Roof Rafters Stair Treaders and Stringers Window Header Garage Door Header Basement Beams Appearance Grade Code: Green - Architectural Red - Industrial 3

42 Power Products Storage, Protection, and Handling Instructions Glued laminated wood materials like Anthony Power Products are a specialized product manufactured to designed strength and appearance standards. As with other building products, however, wood can be affected by the care or lack of care used during storage. Proper handling is important to ensure that glued laminated wood material retains both the structural and appearance standards intended by the designer and built into the product at the plant. Following these simple precautions will help you obtain the kind of installation of which we can both be proud. Unloading If damage or loss in transit exists, do not unload until the delivering carrier has made an inspection. The carrier will not accept a damage claim unless its own inspection report accompanies the claim. Describe damage or loss in writing and file your written claim with the carrier. At the same time notify our sales office. Material sold F.O.B. railcar or truck requires unloading by you. Use sufficient manpower and proper equipment. Tally quantities against the material list. Do not drop or drag laminated materials. Use care in handling to prevent damage to finished surfaces; nylon or plastic slings are desireable. Storage The customer is responsible for protection of this material at all times after arrival. Dimensional changes occur in wood with changes in moisture content. Product Handling & Protection It is the responsibility of the buyer to request the shipper to tarp a truck. Schedule delivery and installation of glue laminated wood members to avoid extended yard or jobsite storage. Keep Power Products as dry as possible during delivery, storage, handling, and erection. If yard storage is necessary, place members on blocking away from ponding water or store under a shed. Proper yard and jobsite protection of Power Products is essential in maintaining dimensional stability. The Power Beam at I-joist compatible depths makes it ever more important to keep dry. All Power Products are manufactured with a moisture content that averages %. As a general rule, for every 4% increase or decrease in MC, the beam will increase or decrease in size by 1%. Anthony Forest Products Company cannot be held responsible for physical changes that may occur as the result of constant exposure to the elements and/or pressure preservative treatment of Power Products. These changes (severe checking, splitting, cupping, and warping) may occur if beams are not properly protected from exposure to the elements. Time of removal of factory wrapping is optional, but it must be emphasized that factory applied wrapping provides additional protection from damage in handling and in-transit only. If beams are wet and still in the wrap, it must be removed. Increases in width and depth will occur if the wrap stays on. If further utilization of the wrap is desired for protection after shipment, the members should be inspected and provided with additional protection as necessary. If it is impractical to replace wrapping, all of it should be removed. Do not leave members partially exposed due to potential sun bleaching. Do not allow moisture to accumulate inside the wrapping. When you must store Power Products at the jobsite, use the same care as with other mill work. Place products on blocks well off the ground; separate products with stripping in a vertically aligned position so air circulates around all four sides of each member; cover top and all sides with moisture-resistant paper, tarps, or black polyethylene. Erection On unbalanced and cambered beams, there is a top and bottom of a beam. The top is always the narrow face where protective paper is folded and stapled. The top face will also have TOP stamped on the beam. Always place the top towards the ceiling. If wrappings are removed temporarily at connections, replace them securely. If wrapping is to be left on after members are erected, it is recommended that the wrapping paper be slit on the bottom or soffit face in several places along the member length to prevent water from being entrapped in the paper. Error or Defect In case of fabrication error or material defects, immediately notify our nearest sales office. Anthony Forest reserves the right to investigate and correct alleged errors and defects. Please call the sales office to notify them of any problems. Finally Following these suggestions will help assure a satisfactory product and will assist us in maintaining our high standard of quality and customer product acceptance. We appreciate the opportunity to furnish Anthony Power Products to your customers. 40

43 Anthony 30F Power Beam, Anthony F Glulam, Power Header, Power Column, Power Preserved Glulam Beams and Columns, Power Joist, Power Log and Power Plank are superior glued laminated products engineered for reliable, lower cost performance in commercial, industrial and residential uses. Anthony Power Products are manufactured under strict quality control procedures. Subject to the terms of our warranty, we guarantee our family of Power Products to be free from defects in design, materials and workmanship and will reimburse you for or replace any Power Product which becomes structurally unfit due to any such defects. We guarantee prompt and courteous customer service. For any questions concerning our limited lifetime warranty, call us at Our family name is on all of our Power Products. We intend to live up to our reputation for quality and service. We appreciate your confidence and your business. Aubra Anthony Jr. President & CEO

44 DISTRIBUTED BY: Power Beam Power Column SYP Lumber Power Joist PRG 30 N. Washington El Dorado, AR Anthony Forest Products Company - August Visit us online!

LVL User s Guide. Technical Data for LVL Headers, Beams, Column Applications for Residential Floor and Roof Systems

LVL User s Guide. Technical Data for LVL Headers, Beams, Column Applications for Residential Floor and Roof Systems LVL User s Guide Technical Data for LVL Headers, Beams, Column Applications for Residential Floor and Roof Systems U N I T E D S T A T E S V E R S I O N Quality Products Committed Service O U R H I S TO

More information

TRUS JOIST BEAMS, HEADERS, AND COLUMNS

TRUS JOIST BEAMS, HEADERS, AND COLUMNS FLOOR SOLUTIONS ROOF SOLUTIONS TRUS JOIST BEAMS, HEADERS, AND COLUMNS Featuring TimberStrand LSL, Microllam LVL, and Parallam PSL Uniform and Predictable Minimal Bowing, Twisting, and Shrinking Strong

More information

BOISE GLULAM 24F-V4 IJC

BOISE GLULAM 24F-V4 IJC Engineered Wood Products 24F-V4 IJC I-Joist Compatible Glulam Guide 3½" x 7½" 3½" x 9½" 3½" x 11⅞" 3½" x 14" 3½" x 16" Sizes Available 5½" x 7½" 5½" x 9½" 5½" x 11⅞" 5½" x 14" 5½" x 16" IJG 01/2010 2 I-Joist

More information

1¾" BEAMS & HEADERS. [1¾" THICKNESS] NER F b E Design Values LAMINATED VENEER LUMBER. Finnforest USA, Engineered Wood Division

1¾ BEAMS & HEADERS. [1¾ THICKNESS] NER F b E Design Values LAMINATED VENEER LUMBER. Finnforest USA, Engineered Wood Division LAMINATED VENEER LUMBER 1¾" BEAMS & HEADERS [1¾" THICKNESS] NER-555 2900 F b - 2.0 E Design Values Finnforest USA, Engineered Wood Division 32205 Little Mack Avenue Roseville, Michigan 48066 Phone: 800/622-5850

More information

Requirements for Use of Allowable Load Tables

Requirements for Use of Allowable Load Tables Southern Pine Allowable Load Tables Requirements for Use of Allowable Load Tables 1. These tables are for gravity loads only. Consult a registered design professional for wind and seismic load analysis

More information

Rosboro TM. Next-Generation Glulam. n Architectural Appearance. n Full Framing-Width Stock. Glulam. n I-Joist and Conventional.

Rosboro TM. Next-Generation Glulam. n Architectural Appearance. n Full Framing-Width Stock. Glulam. n I-Joist and Conventional. n Architectural Appearance n Full Framing-Width Stock Glulam n I-Joist and Conventional Depths 2 X-Beam: X-Beam is the building industry s first full framing-width stock glulam in architectural appearance.

More information

BOISE GLULAM Beam and Column Specifier Guide

BOISE GLULAM Beam and Column Specifier Guide BOISE GLULAM Beam and Column Specifier Guide WEBGLUSPEC 02/28/2013 2... Just ask for BOISE GLULAM beams Glued laminated timbers from Boise Cascade Engineered Wood Products add functional beauty to any

More information

GP Lam LVL. Grade Thickness Depth , 9 1 4, 9 1 2, , , 14, 16, 18, 24 (20 and 22 by special order) 2.

GP Lam LVL. Grade Thickness Depth , 9 1 4, 9 1 2, , , 14, 16, 18, 24 (20 and 22 by special order) 2. GP Lam LVL GP Lam LVL Introduction.....................32 Bearing Details...................34 Handling and Installation..........35 Floor Beams.....................35 Window, Patio Door and Garage Door

More information

GP Lam LVL. Grade Thickness Depth , , , , , 149, 169, 189, 249 (209and 229 by special order) 2.

GP Lam LVL. Grade Thickness Depth , , , , , 149, 169, 189, 249 (209and 229 by special order) 2. GP Lam LVL Grade Thickness Depth 2.0E 1 3 49, 3 1 29 7 1 49, 9 1 49, 9 1 29, 11 1 49, 11 7 89, 149, 169, 189, 249 (209and 229 by special order) 1.5E 1 3 49 7 1 49, 9 1 49, 9 1 29, 11 1 49, 11 7 89, 149,

More information

2.0E ES LVL U.S. Design Manual

2.0E ES LVL U.S. Design Manual I N T E R N A T I O N A L B E A M S 2.0E ES LVL U.S. Design Manual August 2013 2 INTERNATIONAL BEAMS, INC. Our Company At International Beams, Inc. we take pride in providing our customers with premium

More information

Rosboro Manufactured Timber. Preferred lengths Dry stable timber Full-Framing Width

Rosboro Manufactured Timber. Preferred lengths Dry stable timber Full-Framing Width Rosboro Manufactured Timber n n n Preferred lengths Dry stable timber Full-Framing Width TABLE OF CONTENTS Available s 2 Beam, Header and Column Design Values 3 Allowable Uniform Floor Loads 4 Allowable

More information

GP Lam LVL. (20!and 22! by special order) 13 4! 31 2! 1.5E. Lengths: up to 60 feet. Referenced dimensions are nominal and used for design purposes.

GP Lam LVL. (20!and 22! by special order) 13 4! 31 2! 1.5E. Lengths: up to 60 feet. Referenced dimensions are nominal and used for design purposes. GP Lam LVL Grade 2.0E 1.5E Thickness Depth 13 4!, 31 2! 7 4!, 9 4!, 9 2!, 11 4!, 117 8!, 14!, 16!, 18!, 24! (20!and 22! by special order) 13 4! 7 1 4!, 9 1 4!, 9 1 2!, 111 4!, 117 8!, 14!, 16! 31 2! 45

More information

Premium Structural Engineered Wood Products. Technical Data for. LVL Flange and MSR Flange I-Joists

Premium Structural Engineered Wood Products. Technical Data for. LVL Flange and MSR Flange I-Joists Premium Structural Engineered Wood Products Premium Structural Engineered Wood Products I- USER S guide Technical Data for LVL Flange and MSR Flange I-s THE structural Wood Supplier Wood A renewable building

More information

WESTERN SPECIFIER. Technical Data for PWI Joists, PWLVL Headers, Beams, Rim Board, Stud, and Dimension

WESTERN SPECIFIER. Technical Data for PWI Joists, PWLVL Headers, Beams, Rim Board, Stud, and Dimension E N G I N E E R E D W O O D WESTERN SPECIFIER Technical Data for PWI Joists, PWLVL Headers, Beams, Rim Board, Stud, and Dimension P R O D U C T S JOIST DIMENSIONS 9½ LVL FLANGE PWI JOIST SERIES JOIST DIMENSIONS

More information

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation

Trusted ICC ES. Conformity! Look. Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 3445 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 06 00

More information

western for products manufactured in White City, Oregon

western for products manufactured in White City, Oregon western VERSA-LAM SPECIFIER Guide for products manufactured in White City, Oregon Western VERSA-LAM Guide 11/29/2012 2 VERSA-LAM Products An Introduction to VERSA-LAM Products When you specify VERSA-LAM

More information

MINI. Technical Data for. PWI Joists, PWLVL Headers, Beams, and Dimension

MINI. Technical Data for. PWI Joists, PWLVL Headers, Beams, and Dimension E N G I N E E R E D W O O D MINI Technical Data for PWI s, PWLVL Headers, Beams, and Dimension P R O D U C T S S A F E T Y, H A N D L I N G & P E R F O R M A N C E 2 SAFETY & CONSTRUCTION PRECAUTIONS INSTALLATION

More information

DESIGN CHART # 1: Lamit Basic S.I.P Properties

DESIGN CHART # 1: Lamit Basic S.I.P Properties DESIGN CHART # 1: Lamit Basic S.I.P Properties LAMIT S.I.P. PROPERTIES - WEAK AXIS ORIENTED PARALLEL TO SPAN Panel Weight Core Facing Moment Section Elastic Shear Shear Radius Allowable Allowable Allowable

More information

Allowable Holes in VERSA-LAM Beams

Allowable Holes in VERSA-LAM Beams VERSA-LAM Products 23 An Introduction to VERSA-LAM Products When you specify VERSA-LAM laminated veneer headers/beams, you are building quality into your design. They are excel lent as floor and roof framing

More information

Maximum Span Tables. for Joists and Rafters. MSR Lumber. for Performance. Figure provided courtesy of the American Forest & Paper Association

Maximum Span Tables. for Joists and Rafters. MSR Lumber. for Performance. Figure provided courtesy of the American Forest & Paper Association Maximum Span Tables for Joists and Rafters MSR Lumber for Performance Figure provided courtesy of the American Forest & Paper Association 2 MSRLumber Producers Council Span Tables Purpose and Introduction

More information

JD3 rated for greater connection strength. makes it easy to spot in the warehouse or on site

JD3 rated for greater connection strength. makes it easy to spot in the warehouse or on site JD3 rated for greater connection strength H2S termite treated Distinctive blue colour makes it easy to spot in the warehouse or on site Made in Australia Wesbeam Span Tables Roof Members Rafters 4 Roof

More information

STRUCTURAL EDGE ENGINEERING, PLLC

STRUCTURAL EDGE ENGINEERING, PLLC STRUCTURAL EDGE ENGINEERING, PLLC STRUCTURAL CALCULATIONS HINES BLD 3 BOISE, ID SE PROJECT NO: SE16-181 PREPARED FOR: CODE: DATE: NEUDESIGN ARCHITECTURE & LAWSON DESIGN INC 2012 IBC APRIL 23, 2017 683

More information

01 CONTENTS. e-beam. e-beam. Technical Information 03

01 CONTENTS. e-beam. e-beam. Technical Information 03 B 1 01 CONTENTS 02 e-beam Technical Information 03 11 e-beam Strutting Beams 12 Strutting Counter Beams 14 Strutting Hanging Beams 16 Counter Beams 18 Roof Beams 20 ENGINEERED TO LOAD ENGINEERED TO LENGTH

More information

PLANK-AND-BEAM FRAMING FOR RESIDENTIAL BUILDINGS

PLANK-AND-BEAM FRAMING FOR RESIDENTIAL BUILDINGS PLANK-AND-BAM FRAMING FOR RSIDNTIAL BUILDINGS American Wood Council 4 Wood Construction Data American Forest & Paper Association The American Wood Council (AWC) is the wood products division of the American

More information

Structurlam Mass Timber Corporation Revised October 11, 2018

Structurlam Mass Timber Corporation Revised October 11, 2018 Structurlam CrossLam PR-L314C Structurlam Mass Timber Corporation Revised October 11, 2018 Products: Structurlam CrossLam Cross-Laminated Timber Structurlam Mass Timber Corporation 2176 Government Street

More information

LP SolidStart Engineered Wood Products

LP SolidStart Engineered Wood Products LP SolidStart Engineered Wood Products Technical Guide for Residential Floors and Roofs Featuring LP SolidStart IJoists LP SolidStart LVL LP SolidStart LSL LP SolidStart Rim Board Please verify availability

More information

Bending strength, density and modulus of elasticity of BauBuche laminated veneer lumber in comparison with other materials.

Bending strength, density and modulus of elasticity of BauBuche laminated veneer lumber in comparison with other materials. BauBuche Efficiency 07-14 - EN Sheet 4 / 19 Bending strength, density and modulus of elasticity of BauBuche laminated veneer lumber in comparison with other materials. N/mm 2 kg/m 3 N/mm 2 70 48 28 120

More information

American Institute of Timber Construction 7012 South Revere Parkway, Suite 140, Centennial, CO

American Institute of Timber Construction 7012 South Revere Parkway, Suite 140, Centennial, CO American Institute of Timber Construction 7012 South Revere Parkway, Suite 140, Centennial, CO 80112-5092 303-792-9559 AITC 117-2004 STANDARD SPECIFICATIONS FOR STRUCTURAL GLUED LAMINATED TIMBER OF SOFTWOOD

More information

Bridge Overhang Brackets

Bridge Overhang Brackets Bridge C49, C49D, C49S and C49JR Bridge Dayton Superior offers the bridge contractor four different Horizontal Length versions of the C49 Bridge Bracket, which allows for maximum adjustability to meet

More information

GENERAL INFORMATION FEATURES.

GENERAL INFORMATION FEATURES. TECHNICAL GUIDE GENERAL INFORMATION SUPERIOR ENGINEERED JOIST SYSTEMS JoistRite is a specially designed, patented, cold-formed steel section that has one of the highest strength-to-mass ratios of any structural

More information

Span guide for residential framing. September Fully supported by

Span guide for residential framing. September Fully supported by Span guide for residential framing September 2011 Fully supported by Engineered to perform Structural LVL is engineered for reliable performance and is available in two complementary ranges. and + are

More information

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket Report No: Report Date: 10/31/12 130 Derry Court York, PA 17406-8405 phone:

More information

Strutting Beams Supporting Underpurlins Only

Strutting Beams Supporting Underpurlins Only Strutting Beams Supporting Underpurlins Only fan struts strutting beam roof area supported by strutting beam = L/2 x B/2 block underpurlin strutting beam strut L = total rafter span strutting beam span

More information

INDEX OF W.T.I. BEAMS

INDEX OF W.T.I. BEAMS INDEX OF W.T.I. BEAMS Contents Beam Type Page General Specification 3-7 Roof Construction Mass 8-9 Engineers Certification 10 Rafters Roof Load of Light Sheet (10kg/m2) 13 Single & Continuous Span Roof

More information

Product grading of all members is compliant with AS1720: Timber Structures.

Product grading of all members is compliant with AS1720: Timber Structures. Finger Jointed Treated Pine Span Tables SPAN TABLES These span tables have been developed in accordance with the relevant Australian Standards, however please check for state and local government variations.

More information

Formwork Solutions Guide

Formwork Solutions Guide Formwork Solutions Guide truform Trust truform truform is structural Laminated Veneer Lumber (LVL) specially manufactured for use in structural concrete formwork applications. It is manufactured in a controlled

More information

European Technical Assessment ETA-13/0900 of 10/04/2014

European Technical Assessment ETA-13/0900 of 10/04/2014 ETA-Danmark A/S Kollegievej 6 DK-2920 Charlottenlund Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet ww.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011

More information

CALCULATING THE FIRE RESISTANCE OF EXPOSED WOOD MEMBERS

CALCULATING THE FIRE RESISTANCE OF EXPOSED WOOD MEMBERS CALCULATING THE FIRE RESISTANCE OF EXPOSED WOOD MEMBERS TECHNICAL REPORT 10 American Wood Council American Forest & Paper Association The American Wood Council (AWC) is the wood products division of the

More information

Purlins and Girts. A division of Canam Group

Purlins and Girts. A division of Canam Group Purlins and Girts A division of Canam Group TABLE OF CONTENTS OUR SOLUTIONS AND SERVICES............................................................ 5 Cautionary statement..................................................................

More information

Plate Girder and Stiffener

Plate Girder and Stiffener Plate Girder and Stiffener (Gelagar Pelat dan Pengaku) Dr. AZ Department of Civil Engineering Brawijaya University Introduction These girders are usually fabricated from welded plates and thus are called

More information

SHAPING THE FUTURE OF FORMWORK SHAPING THE FUTURE OF FORMWORK

SHAPING THE FUTURE OF FORMWORK SHAPING THE FUTURE OF FORMWORK SHAPING THE FUTURE OF FORMWORK SHAPING THE FUTURE OF FORMWORK Truform - Description and purpose 1 Truform is structural laminated veneer lumber (LVL) intended for use as concrete formwork beams bearers,

More information

Behavior & Design. Curved Girder. Curved Steel Girder Bridges. PDF Created with deskpdf PDF Writer - Trial ::

Behavior & Design. Curved Girder. Curved Steel Girder Bridges. PDF Created with deskpdf PDF Writer - Trial :: Curved Steel Girder Bridges Curved Girder Behavior & Design Curved Steel Girder Design L1 L2 OUTSIDE GIRDER CROSS FRAME d C L PIER C L ABUT CL ABUT RADIUS INSIDE GIRDER CURVED BRIDGE - PLAN VIEW Crossframe

More information

Revision and Errata List AISC Steel Construction Manual, 13 th Edition, Third Printing (Revision 2 June 2010)

Revision and Errata List AISC Steel Construction Manual, 13 th Edition, Third Printing (Revision 2 June 2010) Revision and Errata List AISC Steel Construction Manual, 13 th Edition, Third Printing (Revision 2 June 2010) The following list represents corrections that have been made in the Fourth Printing of the

More information

NEW ZEALAND GLULAM SPAN TABLES

NEW ZEALAND GLULAM SPAN TABLES NEW ZEALAND GLULAM SPAN TABLES The Glulam Span Tables have been developed primarily for domestic applications in accordance with NZS3603 Timber Structures Standard and with the joint AS/NZS 1328:1998 standard

More information

U.S. PATENT NO.: US 7,765,771 TECHNICAL GUIDE SUPERIOR ENGINEERED FLOOR FRAMING SYSTEM

U.S. PATENT NO.: US 7,765,771 TECHNICAL GUIDE SUPERIOR ENGINEERED FLOOR FRAMING SYSTEM U.S. PATENT NO.: US 7,765,771 TECHNICAL GUIDE SUPERIOR ENGINEERED FLOOR FRAMING SYSTEM SUPERIOR ENGINEERED JOIST SYSTEMS JoistRite is a specially designed, patented, cold-formed steel section that has

More information

SmartLVL 18 Design Guide

SmartLVL 18 Design Guide SmartLVL 18 LVL 18 Design Guide TREATABLE SUSTAINABLE STRONGER UP TO 6M LENGTHS CONSISTENCY F27 COMPATIBLE Edition 1 2011 SCOPE OF THIS PUBLICATION This Design Guide and Load Tables assist in the selection

More information

European Technical Assessment ETA-09/0355 of

European Technical Assessment ETA-09/0355 of ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet ww.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011 of

More information

This product is no longer manufactured.

This product is no longer manufactured. s t e e l R O O F d e c k L E G A C Y P R O D U C T This product is no longer manufactured. This product information has been made available to support the retrofit of existing buildings by providing the

More information

WARRANTY AND LIMITATIONS

WARRANTY AND LIMITATIONS 2 GENERAL INFORMATION QUALITY AND SERVICE COUNT Marino\Ware is proud to present this catalog that details our Lightweight Steel Framing Products. For over 70 years, Marino\Ware has been providing their

More information

SmartFrame Product Warranty*

SmartFrame Product Warranty* SCOPE OF THIS PUBLICATION This Design Guide and load Tables assist in the selection of SmartLam GL17 beams for most of the common structural arrangements met in sheet construction. Methods of developing

More information

SPAN TABLES SPAN TABLES

SPAN TABLES SPAN TABLES SPAN TABLES SPAN TABLES - These span tables have been developed in good faith, with the assistance of Mr.Peter Falvey B.E., M.I.E.Aust., C.P.Eng., R.P.E.Q.(579) in accordance with the relevant Australian

More information

December 1, Table of Contents. TABLE TOPIC PAGE General TABLE TOPIC PAGE. Roof Decks (continued) (Diaphragm Shear Values)

December 1, Table of Contents. TABLE TOPIC PAGE General TABLE TOPIC PAGE. Roof Decks (continued) (Diaphragm Shear Values) Page 1 of 57 Table of Contents Report ER-78P December 1, 02 TABLE TOPIC PAGE General 1 Allowable Shear Values - Spot or Seam Welds 2 2 Allowable Tension Loads - Hilti Fasteners... 2 3 Allowable Shear and

More information

WESTERN SPECIFIER GUIDE. for products manufactured in White City, Oregon

WESTERN SPECIFIER GUIDE. for products manufactured in White City, Oregon WESTERN SPECIFIER GUIDE for products manufactured in White City, Oregon WSG 03//2013 2 The SIMPLE FRAMING SYSTEM Makes Designing Homes Easier Architects, engineers, and designers trust Boise Cascade's

More information

Prolam LVL 15 Design Guide. Register Free for our Beam Calculator

Prolam LVL 15 Design Guide. Register Free for our Beam Calculator Prolam LVL 15 Design Guide Register Free for our Beam Calculator www.prolamnz.com/specifiers 2 Contents 03 Scope of Publication 04 Prolam LVL 15 05 Design/Effective Span 06 Continuous Spans 06 Rip Sawing

More information

G SERIES 3 ROUGH-TERRAIN FORKLIFTS

G SERIES 3 ROUGH-TERRAIN FORKLIFTS G SERIES 3 ROUGH-TERRAIN FORKLIFTS 586G 588G G SERIES 3 ROUGH-TERRAIN FORKLIFTS 586G 588G The toughest off-road material handling and lift-and-carry applications require a reliable, durable and comfortable

More information

Accessories Catalogue

Accessories Catalogue Accessories Catalogue GEKA ACCESSORIES Since 1919, GEKA Group has been manufacturing Ironworkers for angle work, flats and profiles - for black iron, metal workshops, metal constructions, telecommunication

More information

Parametric study on behaviour of box girder bridges using CSi Bridge

Parametric study on behaviour of box girder bridges using CSi Bridge Parametric study on behaviour of box girder bridges using CSi Bridge Kiran Kumar Bhagwat 1, Dr. D. K. Kulkarni 2, Prateek Cholappanavar 3 1Post Graduate student, Dept. of Civil Engineering, SDMCET Dharwad,

More information

HINDUSTAN BEARING TECHNOLOGIES. Manufacturer and Exporter of Ball & Roller Bearings. Company Profile. ISO Certified Company

HINDUSTAN BEARING TECHNOLOGIES. Manufacturer and Exporter of Ball & Roller Bearings. Company Profile. ISO Certified Company Manufacturer and Exporter of Ball & Roller Bearings Company Profile ISO 9001-2015 Certified Company Website : www.hbtbearings.com Our Vision Be globally recognized as high quality bearing manufacturer

More information

SmartLam GL18 Design Guide

SmartLam GL18 Design Guide SmartLam GL18 Design Guide A BOND ADHESIVE STRAIGHT AND TRUE 18 GlueLam STRONG ENGINEERED MECHANICALLY GRADED LAMINATES SCOPE OF THIS PUBLICATION This Design Guide and Load Tables assist in the selection

More information

UT Lift 1.2. Users Guide. Developed at: The University of Texas at Austin. Funded by the Texas Department of Transportation Project (0-5574)

UT Lift 1.2. Users Guide. Developed at: The University of Texas at Austin. Funded by the Texas Department of Transportation Project (0-5574) UT Lift 1.2 Users Guide Developed at: The University of Texas at Austin Funded by the Texas Department of Transportation Project (0-5574) Spreadsheet Developed by: Jason C. Stith, PhD Project Advisors:

More information

TRANSLATION (OR LINEAR)

TRANSLATION (OR LINEAR) 5) Load Bearing Mechanisms Load bearing mechanisms are the structural backbone of any linear / rotary motion system, and are a critical consideration. This section will introduce most of the more common

More information

STANDARD SPECIFICATIONS

STANDARD SPECIFICATIONS American National Standard SJI-K 1.1 STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-SERIES SECTION 1. SCOPE Adopted by the Steel Joist Institute November 4, 1985 Revised to November 10, 2003 - Effective

More information

Welcome! Safety first.

Welcome! Safety first. Welcome! Safety first. Please take the time to read the safety instructions given to you Keep your visitor badge visible Stay with your host and follow instructions Mind the steps, hold onto the railings

More information

SPAN TABLES FOR RESIDENTIAL BUILDING NOW AVAILABLE H2-S TREATED TO PROTECT AGAINST TERMITES

SPAN TABLES FOR RESIDENTIAL BUILDING NOW AVAILABLE H2-S TREATED TO PROTECT AGAINST TERMITES SPAN TABLES FOR RESIDENTIAL BUILDING NOW AVAILABLE H2-S TREATED TO PROTECT AGAINST TERMITES contents Contents Introduction Page Nº Application 3 Some information about Hyspan and its use _ 3 Terminology

More information

Partnership and Investment Opportunities in the Canadian Forest Products Industry. Paul Lansbergen BIO World Congress May 13, 2014

Partnership and Investment Opportunities in the Canadian Forest Products Industry. Paul Lansbergen BIO World Congress May 13, 2014 Partnership and Investment Opportunities in the Canadian Forest Products Industry Paul Lansbergen BIO World Congress May 13, 2014 Outline Key Take Aways Transformation of the Forest Industry Partnership

More information

Supreme. Supreme Framing System. Product Catalog IAPMO UNIFORM ER #0313

Supreme. Supreme Framing System. Product Catalog IAPMO UNIFORM ER #0313 Supreme Supreme Framing System Product Catalog IAPMO UNIFORM ER #0313 2507 Table of Contents Certification of Materials 5 LEED Credits 5 Independent Product Certification 5 Code Approvals, Performance

More information

TYPICAL SPECIFICATIONS: Specific: Mechanical connections shall be Taper-Lock taper threaded couplers as manufactured by Dayton Superior Corp.

TYPICAL SPECIFICATIONS: Specific: Mechanical connections shall be Taper-Lock taper threaded couplers as manufactured by Dayton Superior Corp. Why Taper-Lock is etter u ICC Evaluation Report ESR-2481 u Portable design allows you to take the system wherever you need it. u Sharpen cutters up to three times for previously unheard of efficiency!

More information

REVEAL SERIES ARCHITECTURAL DECK PRODUCTS

REVEAL SERIES ARCHITECTURAL DECK PRODUCTS REVEAL SERIES ARCHITECTURAL DECK PRODUCTS ROOF AND FLOOR DECK CEILING SYSTEMS Reveal Series is a suite of metal deck systems that utilizes the inherent strength of structural deck and the aesthetic appeal

More information

Analysis Methods for Skewed Structures. Analysis Types: Line girder model Crossframe Effects Ignored

Analysis Methods for Skewed Structures. Analysis Types: Line girder model Crossframe Effects Ignored Analysis Methods for Skewed Structures D Finite Element Model Analysis Types: Line girder model Crossframe Effects Ignored MDX Merlin Dash BSDI StlBridge PC-BARS Others Refined model Crossframe Effects

More information

Our Retail Development

Our Retail Development Our Retail Development Jiffy Lube, North America's choice for oil change and routine vehicle maintenance services Jiffy Lube Our Retail Development ince 1979 Jiffy Lube has been part of neighbourhoods.

More information

Expanding Your Solutions. Steel Framing and Accessories. ICC ESR and 2015 IBC, IRC

Expanding Your Solutions. Steel Framing and Accessories. ICC ESR and 2015 IBC, IRC Expanding Your Solutions Steel Framing and Accessories ICC ESR-30 20 and 2015 IBC, IRC Effective 1/4/2017 Table of Contents Introduction to CEMCO... 1 Product Identification... 2 3 LEED Certification...

More information

Submittal Data. Fiberglass Bondstrand 2000 Pipe pe

Submittal Data. Fiberglass Bondstrand 2000 Pipe pe Submittal Data Fiberglass Bondstrand 2000 Pipe pe Uses and Applications Chilled Water Chilled Hot Water Domestic Hot Water Condensate (Hot Water) return General service piping Jet fuel piping Mild chemicals

More information

REVEAL SERIES ARCHITECTURAL DECK PRODUCTS CANADA

REVEAL SERIES ARCHITECTURAL DECK PRODUCTS CANADA REVEAL SERIES ARCHITECTURAL DECK PRODUCTS CANADA ROOF AND FLOOR DECK CEILING SYSTEMS Reveal Series is a suite of metal deck systems that utilizes the inherent strength of structural deck and the aesthetic

More information

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: CONSOLIDATED SYSTEMS, INC. (CSi )

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: CONSOLIDATED SYSTEMS, INC. (CSi ) 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2839 Reissued 05/2015 This report is subject to renewal 05/2016. DIVISION: 05 00 00 METALS SECTION:

More information

National Evaluation Service, Inc.

National Evaluation Service, Inc. National Evaluation Service, Inc. 5203 Leesburg Pike, Suite 600, Falls Church, Virginia 22041-3401 Phone: 703/931-2187 www.nateval.org Fax: 703/931-6505 NATIONAL EVALUATION REPORT Report No. NER-478 Re-Issued

More information

ROOFING SOLUTIONS DESIGN GUIDE PURLINS AND GIRTS DESIGN GUIDE PURLINS AND GIRTS S&T029N

ROOFING SOLUTIONS DESIGN GUIDE PURLINS AND GIRTS DESIGN GUIDE PURLINS AND GIRTS S&T029N DESIGN GUIDE PURLINS AND GIRTS ROOFING SOLUTIONS DESIGN GUIDE PURLINS AND GIRTS S&T029N JUL 2015 CONTENTS INTRODUCTION 2 Acknowledgements 2 Disclaimer 2 Product Technical Statement 3 Producer Statement

More information

DRUM BRAKE RIMS Periodic inspection of drum brake rims is necessary to determine indications of uneven or excessive wear. In general, brake rim failures other that regular wear are caused by brake linings

More information

REVEAL SERIES ARCHITECTURAL DECK PRODUCTS UNITED STATES

REVEAL SERIES ARCHITECTURAL DECK PRODUCTS UNITED STATES REVEAL SERIES ARCHITECTURAL DECK PRODUCTS UNITED STATES ROOF AND FLOOR DECK CEILING SYSTEMS Reveal Series is a suite of metal deck systems that utilizes the inherent strength of structural deck and the

More information

7 Series Forklifts. Electric 2.2 to 3.5 ton capacity. Lifting Your Dreams

7 Series Forklifts. Electric 2.2 to 3.5 ton capacity. Lifting Your Dreams 7 Series Forklifts Electric 2.2 to 3.5 ton capacity Lifting Your Dreams About Doosan Doosan Industrial Vehicle Values that drive our future growth Major global player in the infrastructure support business

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: ITW BUILDEX

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: ITW BUILDEX 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3270 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 05 00

More information

Bondstrand 5000/5000C Product Data (Severely Corrosive Industrial Service and Oxidizing Acids)

Bondstrand 5000/5000C Product Data (Severely Corrosive Industrial Service and Oxidizing Acids) Bondstrand 5000/5000C Product Data (Severely Corrosive Industrial Service and Oxidizing Acids) Uses and Applications Acid drains Bleach processing Chemical process piping Chlorinated water Chlorine Corrosive

More information

PRODUCT EVALUATION Effective Date: July 1, 2014 RC-20

PRODUCT EVALUATION Effective Date: July 1, 2014 RC-20 TEXAS DEPARTMENT OF INSURANCE Engineering Services Program / M03-3A 333 Guadalupe Street P.O. Box 149104 Austin, Texas 78714-9104 Phone No. (512) 322-2212 Fax No. (512) 463-6693 PRODUCT EVALUATION Effective

More information

Union Pacific. Brand Guide

Union Pacific. Brand Guide Union Pacific W Brand Guide 2013 Table Of Content Logo Rationale... 4 Signature Elements... 5 Typeface... 6 Color Study... 7 Clear Space... 8 Acceptable Styles with Logo... 10 Unacceptable Styles with

More information

Strategic Plan

Strategic Plan 2005-2015 Strategic Plan SUMMARY OF THE REVISED PLAN IN 2011 A decade focused on developing mass transit in the Outaouais A updated vision of mass transit in the region The STO is embracing the future

More information

Scope : Steel Beam Design. Pinned-Pinned Bm Wt. Added to Loads LL & ST Act Together # 1 # 2 # 3 # 4 # 5 # 6 # Start Location End Location

Scope : Steel Beam Design. Pinned-Pinned Bm Wt. Added to Loads LL & ST Act Together # 1 # 2 # 3 # 4 # 5 # 6 # Start Location End Location Dsgnr: Date: 9:01AM, 12 MAR 10 (c)1983-2009 ENERCALC Engeerg Soware B2 check @ wdnw "6" General Information Code Ref: AISC 9th ASD, 1997 UBC, 2003 IBC, 2003 NFPA 5000 Steel Section : W6X15 Fy ksi Center

More information

Rural Electrification. A Brief History GEORGIA S ELECTRIC MEMBERSHIP CORPORATION

Rural Electrification. A Brief History GEORGIA S ELECTRIC MEMBERSHIP CORPORATION Rural Electrification A Brief History GEORGIA S ELECTRIC MEMBERSHIP CORPORATION Rural Electrification A BRIEF HISTORY OF RURAL ELECTRIFICATION IN AMERICA Most folks think the history of rural electrification

More information

Applied Biorefinery Sciences, LLC

Applied Biorefinery Sciences, LLC , LLC 4736 Onondaga Blvd, #451. Syracuse, NY 13219. (315) 317-9166 jrhoward@abs-llc.us Experts in: Biorefinery design & engineering Feedstock supply Hot water extraction Chemical separation & recovery

More information

Certified Sustainable Palm Oil Introduction, definitions & drivers. Ryan Welton Global Agri-trade / Natu oil Services

Certified Sustainable Palm Oil Introduction, definitions & drivers. Ryan Welton Global Agri-trade / Natu oil Services Certified Sustainable Palm Oil Introduction, definitions & drivers Ryan Welton Global Agri-trade / Natu oil Services Sustainability Defined Why Palm Oil has an intrinsic sustainable advantage Certified

More information

Expanding Your Solutions. ViperStud Product Catalog. Interior Non-Load Bearing Studs and Track

Expanding Your Solutions. ViperStud Product Catalog. Interior Non-Load Bearing Studs and Track Expanding Your Solutions ViperStud Product Catalog Interior Non-Load Bearing Studs and Track Effective 5/11/18 #VSB5-5/15 By providing a lighter, stronger, more efficient framing system, ViperStud has

More information

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT:

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1464 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 05 00

More information

Schneider Electric Powering the U.S. Department of Energy Solar Decathlon 2011

Schneider Electric Powering the U.S. Department of Energy Solar Decathlon 2011 Schneider Electric Powering the U.S. Department of Energy Solar Decathlon 2011 Washington D.C., U.S.A. Make the most of your energy sm Schneider Electric: Proud sustaining sponsor of the U.S. Department

More information

Structural Sections. Page 15

Structural Sections. Page 15 Page 15 MILD STEEL CHANNELS Product Shortname: CH AS 3679-300 AS 3679-350 (on indent only) BS4360-43A Mass per Metre = area of section x 0.00785 = kg/m Metres per Tonne = 1000 = metres kg/m Size (A x B)

More information

US 191 Load Rating Past and Present. By Ron Pierce, P.E.,S.E., CBI David Evans & Associates Bridge Operations Services Practice Leader

US 191 Load Rating Past and Present. By Ron Pierce, P.E.,S.E., CBI David Evans & Associates Bridge Operations Services Practice Leader US 191 Load Rating Past and Present By Ron Pierce, P.E.,S.E., CBI David Evans & Associates Bridge Operations Services Practice Leader Inspection Experience Bridge Inspection with Idaho Transportation Department

More information

Our mission is to be the best public service transporter for passengers in the city of Kigali using modern, clean and safe urban city buses.

Our mission is to be the best public service transporter for passengers in the city of Kigali using modern, clean and safe urban city buses. Kigali Bus Services Ltd. was incorporated in January 2006 in Kigali Rwanda. The Company started operations in March 2007 with just a few buses! We now operate a fleet of 50 Buses throughout Kigali City

More information

Nusantara-Teak Kyle Barnett. facebook.com/nusantara-teak

Nusantara-Teak Kyle Barnett. facebook.com/nusantara-teak Nusantara-Teak Kyle Barnett info@nusantara-teak.com facebook.com/nusantara-teak Canada: +1 905 449 9669 Indo : +62 818 0551 3877 Indo : +62 812 2988 6778 PROVISIONS Our mission is to be the global leader

More information

Ohio Transportation Engineering Conference 2012

Ohio Transportation Engineering Conference 2012 Ohio Transportation Engineering Conference 2012 October 31, 2012 Mitch Hardert Chief Engineer CBC Engineers Jim Noll Director Engineering Services CONTECH Joe Dennis Director Business Development CBC Engineers

More information

Glass Sanding Solution

Glass Sanding Solution Glass Sanding Solution About Mirka Mirka s Glass Sanding Solution KWH MIRKA LTD is a family-owned Finnish company and a world leader in abrasives technology innovation. We are offering a complete range

More information

Timber-Concrete Composite Floor

Timber-Concrete Composite Floor Timber-Concrete Composite Floor Technology Research, Design and Implementation Presented by: Dr. Peggi Clouston, Peng, MASc, PhD Associate Professor clouston@umass.edu Disclaimer: This presentation was

More information

BUILDING PRODUCTS LCP PURLINS & GIRTS. Purlin and Girt Structural System. BC 1:2012 FPC Cert. No. ABS-BCI-SG-0001

BUILDING PRODUCTS LCP PURLINS & GIRTS. Purlin and Girt Structural System. BC 1:2012 FPC Cert. No. ABS-BCI-SG-0001 BUILDING PRODUCTS LCP PURLINS & GIRTS Purlin and Girt Structural System BC 1:2012 FPC Cert. No. ABS-BCI-SG-0001 CERT NO. FM 59595 BS EN ISO 9001 : 2008 FEATURES Cold formed purlins and girts are recognised

More information

NYISO Market Initiatives

NYISO Market Initiatives NYISO Market Initiatives Robb Pike Director Market Design New York Independent System Operator Ventyx Market Leadership Council Santa Clara, CA April 23, 2012 Topics Roles of the NYISO Smart Grid Integrating

More information