Fuel cell field test demonstration of economic and environmental viability for portable generators, backup and UPS power system applications

Size: px
Start display at page:

Download "Fuel cell field test demonstration of economic and environmental viability for portable generators, backup and UPS power system applications"

Transcription

1 Fuel cell field test demonstration of economic and environmental viability for portable generators, backup and UPS power system applications Programme type: FP7 Subprogramme Area: Portable generators, backup and UPS power systems Contract type: Joint Technology Initiatives - Collaborative Project (FCH) Object of document: D 4.1 Development of test protocol Work Package Leader: EP Contributors: JRC, UNIDO-ICHET, LUASA, EPS, Future-E Date of issue: Status of the document: draft approved by Internal Quality Management Number of pages: 44

2 CONTENT LIST EXECUTIVE SUMMARY INTRODUCTION a. Overview of FITUP project b. Description of the system and state of the art TEST PROTOCOL DEVELOPMENT a. EU power grid characteristics a.1 L1 grid failures a.2 L2 and L3 grids failures a.3 Conclusions b. Test protocols adopted in previous projects TEST PROTOCOL GENERAL FEATURES a. Test purpose b. General test structure c. Test procedures BENCHMARK TESTS a. Test equipment and setup a.1 Installation instructions a.2 Climate chamber b. Long-term durability benchmark test procedure (BENCH-LTD) b.1 Base test procedure b.2 Climate chamber tests b.3 Hydrogen consumption evaluation b.4 System stability under stress conditions

3 4b.5 Grid restore during system start-up, grid failure during system shut-down c. Additional benchmark tests (BENCH-ADD) ON-FIELD TESTS a. Systems equipped with COMPRESSED H 2 CYLINDERS a.1 Test equipment and setup a.2 Non-TETRA systems test procedure (OF-CH2) a.3 TETRA systems test procedure (OF-TET) b. Systems equipped with ELECTROLYSER (OF-ELS) b.1 Test equipment and setup b.2 Test procedure LITERATURE REFERENCES ANNEX A - TEST PROCEDURE SCHEMES

4 EXECUTIVE SUMMARY The purpose of this document is to present the test protocol developed for the fuel cell powered backup systems that will be tested in the framework of FITUP project. The aim of FITUP is in fact to demonstrate the good performance and reliability of this innovative kind of UPS system, through an extensive test campaign, carried on both in laboratory and real-world applications. In the introduction the main characteristic of the project and the state-of-the-art of the employed technology are reported, underlining the benefits that the project can bring to the rising fuel cell UPS industry. Chapter 2 resumes the documents used for the development of the protocol, including studies regarding duration and frequency of the grid failures in European electric grid and the results of previous research projects carried out in the same field of FITUP project. In the following three chapters the details of the protocol are presented, starting from its general structure (chapter 3), and going to the precise description of the two main branches of the protocol, regarding laboratory tests (chapter 4) and on-field tests (chapter 5). In fact, starting from the same principles, stated in chapter 3, different procedures were defined according to the location of the test, taking into account the constraints of real-world situations and the wider possibilities offered by laboratory environment. In this way, laboratory and on-field tests will prove different features of the systems, leading to the complete satisfaction of project s targets. In summary, all tests are variants of the following base scenarios: short term grid failures (A type), duration of 15 medium and long term grid failures (B type), duration of 240 (4 hours) catastrophic grid failures (C type), duration of 4320 (72 hours). The document is completed by a list of literature references and an annex containing graphic representations of the different test procedures. 4

5 1. INTRODUCTION 1a. Overview of FITUP project A total of 19 (plus 2or 3 awaiting confirmation) market-ready fuel cell systems from two suppliers, Electro Power Systems and Future-E, will be installed as UPS (Uninterruptible Power Supply) backup power sources in selected sites across the European Union. Real-world customers from the telecommunications industry will use these fuel cell-based systems, with power levels in the 3-12 kw range, in their sites. These units will demonstrate a level of technical performance (start-up time, reliability, durability, number of cycles) that qualifies them for market entry, thereby accelerating the commercialisation of this technology in Europe and elsewhere. The demonstration project will involve the benchmarking of units from both fuel cell suppliers according to a test protocol to be developed within the project. It will employ this test protocol to conduct extensive tests in field trials in sites selected by final users in Italy, Switzerland and Turkey. The performance will be logged and analysed to draw conclusions regarding commercial viability and degree to which they meet customer requirements, as well as suggesting areas for improvement. A lifecycle analysis using data from the project will be carried out to determine economic and environmental value proposition over incumbent technologies such as batteries or diesel generators. The system producers will use the results of the tests, and obtain valuable first hand feedback from customers, optimise their systems as needed, and demonstrate commercial viability. On the other hand, final users from the telecommunications industry will experience first-hand the advantages of fuel cells for their applications under real world conditions. The optimisation potential is expected from the production process itself, from the installation of a significant amount of fuel cell systems and from the testing. The project will also develop a certification procedure valid in all countries where the fuel cells will be either produced or tested under the expert advice of TÜV Süd. The dissemination of project progress will be geared mostly towards getting the word out to final users through presentations at specialised conferences, thus improving the visibility of market-ready fuel cells and pave the way for market penetration. The consortium consists of large and small entities which are fuel cell suppliers, end users and R&D centres (for data acquisition and analysis). The partners are located throughout the EU covering a range of environmental conditions, such as those found in Italy, Switzerland and Turkey. This spread will demonstrate the viability and enable the use of fuel cell-based UPS across the EU. 1b. Description of the systems and state of the art The main components of the fuel cell UPS systems are the following: PEM fuel cell(s) fuel cell auxiliary equipments (air blower, water pump, power electronics, ) start-up batteries (or ultracapacitors) 5

6 electrolyser (only for models with autonomous hydrogen production). The systems without electrolysers produce electric power using pure hydrogen as energy source; therefore, they are connected to external hydrogen tanks. Systems equipped with the electrolyser need tri-phase electric power as an input to produce hydrogen, stored in an hydrogen reservoir. Figure 1 - General layout of a fuel cell UPS system During the last few years, backup power sources based on fuel cell technology have experienced a significant surge in interest, due to the fact that they can offer economic advantages to potential users, as well as technical and environmental benefits. These potential benefits may be briefly summarised as follows: autonomy - fuel cells are able to operate as long as there is available fuel, and therefore can have longer autonomy when compared to a battery. This is due to the inherent nature of hydrogen fuel cells, which separate the energy and power sources, as opposed to batteries remote monitoring - fuel cells can be fully monitored from one central location, alerting the operator when the system is in use and how much time it can run before refuelling is required, to ensure no downtime footprint - the space required for the same period of runtime is considerably less for fuel cells than for battery banks 6

7 fuels - the majority of these systems operate on hydrogen (in this instance the only emission is water), which can be generated from renewable sources (electrolysis) or fossil fuel reforming cost - over its lifetime these units can offer cost savings over existing technologies (taking into account maintenance, repairs, transport and disposal) reliability - in many cases, fuel cells are able to offer higher reliability and MTBF (Mean Time Between Failures), and there is low degradation of voltage over time; failures tend to be less critical and easily dealt with environmental - fuel cells using hydrogen produce only water vapour, presenting a clear advantage over diesel generators which generate pollutants and significant CO2 emissions; batteries present instead the issue of their recycling, especially with the large presence of lead, which requires special measures maintenance - fuel cells have very few moving parts which reduces the need for regular maintenance lifetime - longer lifetimes than batteries, in UPS systems requiring hours of annual use fuel cells can meet years of lifetime with present status of technology; batteries must be replaced approximately every 3-5 years due to self discharge regardless of their hours of real use. Several studies have also pointed out the economic benefits of fuel cells over these other alternatives. Lifecycle cost analyses reveal that fuel cells provide a more economic alternative over both batteries and diesel generators over their lifetime. Primarily this is due to the replacement schedule of batteries and the significant maintenance needs of diesel generators, adding up to significant OEM costs that overcome the larger initial capital investment in fuel cells. With these factors in mind, it is clear to see where the increasing interest in fuel cell-based solutions comes from. While there are several specific markets that fuel cells can enter, the telecommunications industry is perhaps one of the most attractive, due to their use patterns and overall increase in size worldwide. In a study for the U.S. Department of Energy, Battelle Memorial Institute analyzed lifecycle costs of emergency response radio towers, comparing fuel cells with a 2 kw battery-only backup (8 hours autonomy) and a 5 kw battery-diesel generator backup (52 hours, 72 hours, and 176 hours backup duration). PEM fuel cells can provide service at substantially lower total cost than current technologies (the higher cost for the fuel cell system for the 176-hour backup results from the cost of hydrogen storage tank rental) 1. Figure 2 - Net present value of total cost of backup power systems for emergency response radio towers 2 7

8 Several government facilities are already using or have tested fuel cells as backup power for communications and other systems in the US. The State of Maryland currently uses a fuel cell backup power system at a wireless communications microwave site at Elk Neck State Park near North East, Maryland. The Elk Neck tower, which consists of a single-channel microwave repeater radio tower, supports several tenants, including the State s E 911 communications system. During hurricane Isabel (2003) and its aftermath, the fuel cell system enabled critical radio communications over the microwave network for Maryland State Police and emergency medical response services until primary grid power was restored. In the US, the three major suppliers for backup power fuel cell systems, Plug Power, Reli-on and IdaTech, have installed more than a hundred fuel cell systems so far. In the EU, the manufacturers have made inroads into the marketplace, but could still greatly benefit from a project such as FITUP. So far, the level of sales in EU countries by EU suppliers appears to have been somewhat limited, although they have been increasing. The fuel cell suppliers participating in the FITUP project are ramping up production of their units. At the same time, widespread knowledge of this technology is still an objective to be achieved in order for potential users from a number of industries to consider using fuel cells, alongside batteries or diesel generators. Because the number of demonstrations of fuel cell-based backup power applications has been limited, there is a lack of data for users to access. Without references, many potential users are perhaps understandably reticent to try a new technology that provides reliability for their networks, e.g. in the case of the telecommunications industry. Furthermore, the set of criteria for commercialisation that are included in the call regarding reliability, durability, cost, cyclability and response times, have not, as a whole, been proven with a representative set of units. FITUP project s aim is to overcome these problems, carrying on an extensive test campaign that will supply data about the systems and spread technology knowledge. 8

9 2. TEST PROTOCOL DEVELOPMENT The FITUP project proposes to conduct an EU-wide set of field trials that demonstrate the technical viability and economic maturity of backup power systems based on fuel cell technology. This three year demonstration project will constitute the largest such undertaking of its kind in Europe and will place EU companies on par with those active in the US and thus at the forefront of fuel cell technology worldwide for these applications. It will increase the visibility of fuel cells as a potential alternative to conventional backup power sources (batteries and diesel generators) and prove to potential customers in different industrial sectors their advantages. In order to achieve these objectives, an appropriate test protocol for the UPS systems is needed. The purpose of this document is to describe the test protocol and explain the reasoning behind its definition. In fact, the protocol has been developed starting from project objectives, and taking into account grid failures pattern in EU s power grid and known test procedures, previously created during other projects and industrial activities. 2a. EU power grid characteristics In order to understand how to test the UPS units in a realistic way, it is necessary to investigate the characteristics of the electrical grid failures, especially in terms of duration and frequency. In principle, three levels of supply should be considered: L1 - High level voltage grid (> 110 kv) L2 - Mid level voltage grid (> 4/6 kv and < 110 kv, typically 20kV) L3 - Low level voltage grid (< 4/6 kv, typically 400 V) Adequate and rather detailed data are available for L1 and L2 grids, but not for L3. However, while the grid is designed to allow supply at various nodes to reduce the risk of lack of supply, in reality the grid capacities are often so strained that there is a hierarchical effect, i.e. a failure on the higher level affects in most cases the lower level. 2a.1 L1 grid failures In order to obtain information about frequency and duration of the electrical grid failures in European countries, data has been taken from the last full statistical yearbook published by UCTE (former Union for the Co-ordination of Transmission of Electricity, now part of ENTSO-E network) in 2009, which contains 2008 data 3. After processing it results that during 2008 there were approximately 100 L1 grid failures in the UCTE territory (24 countries, continental western EU plus Switzerland and the western Balkan countries less Albania). This correlates also with a more detailed research by M. Rosas Casals 4, who reports a total of 908 major events for the period from 2002 through

10 In the following pictures, the number of reported L1 grid interruptions and their duration is shown. Both these elements (number and duration of interruptions) have to be analyzed, as they can influence the test design. Figure 3 - Number of L1 grid failures in UCTE countries during

11 Figure 4 - Duration distribution of L1 grid failures in UCTE countries during 2008 As can be seen from the above data there is no clear distribution pattern. This is confirmed also by the average duration, which is Excluding the minimum and the maximum of the failure duration distribution (respectively 0 and 1949 ), the average is 88.8 and the new extremes are 1 and 848. The distribution of events reasons is reported below: 11

12 Figure 5 - Reason distribution of L1 grid failures in UCTE countries during 2008 Legend: R4 - overload (including planned ones) R5 - false operation R6 - failure in protection devices or other elements R7 - outside impacts (animals, trees, fire, avalanches ) R8 - very exceptional conditions (natural or artificial disasters) R9 - other reasons Table 1 - Average duration per reason of L1 grid failures in UCTE countries during 2008 From this data it appears that the more technical issues can be handled quicker, but still lead on average to approximately 1 hour of power absence. External induced problems last longer, on average almost 2.5 hours. However, also the other categories contain actual cases with restoration periods longer than 200. It is important to note that the maximum value of 1949 or 32.4 hours occurs during an R9 case, which is not related to a major catastrophe. Therefore the specification of 72 hours of power supply for a governmental emergency response network may actually be quite reasonable. 12

13 2a.2 L2 and L3 grids failures For the lower level grids the statistical data are typically reported in form of Reliability Indexes, e.g. SAIDI (System Average Interruption Duration Index) and CAIFI (Customer Average Interruption Frequency Index). In a report of the Project UNDERSTAND 5, which among others led to a White Paper on Security of Electricity Distribution, a grid failure statistic study of CREER is quoted, regarding the period between 1999 and Table 2 - SAIDI data from UNDERSTAND project 13

14 Table 3 - CAIFI data from UNDERSTAND project Using these data it is possible to calculate average event duration (disregarding Latvia and Lithuania, as the data seem inconsistent). It is possible to clearly identify two event types, characterized by an approximate length respectively of 60 (±15 ) and 130 (±25 ). Table 4 - Average grid failure duration data from UNDERSTAND project 14

15 In order to validate these data, other examples were collected from literature. Austria (2008, 2009) Regarding unplanned interruptions, E-control GmbH, the Austrian Energy Regulator, reported SAIDI of 43,69 for 2008 and 36,65 for , 7. These values represent an aggregate and weighted average. The disaggregation for 2009 leads to a more complex picture, as shown in the graph below. Figure 6 - Planned and unplanned grid failures in Austria during 2009 As can be seen there were nearly 100 interruption events, including both L1 and L2 grids. Some of them were planned (in green), but the majority of events was of unplanned nature (in blue). Maximum duration of an unplanned event was It is also worth noting that planned grid shutdowns are quite often followed by extensions of an unplanned nature. Furthermore, the 2009 E-control report contains a comparison with other countries: 15

16 Figure 7 - comparison between Austrian and other countries SAIDI values between 2007 and 2009 Italy In a newsletter of a small town in Northern Italy owning its own electricity plant and some L2 and L3 grid, a CAIFI of 2.8 failures per customer and year and a SAIDI of 78.5 are reported for In 2004, a larger electrical utility in the region (Etschwerke) was quoted to have a CAIFI of 3.3 failures per customer and year, and a SAIDI of 123, whereas Italian national average was CAIFI 2.9 failures per customer and year and SAIDI 153 (significantly contrasting to CREER data shown earlier). Switzerland Switzerland did not show up as having L1 failures in 2008 in the UCTE statistics, but it has incidents sometimes. The following events are listed in the annual report 2002/2003 of EW Höfe AG 9, a local/regional electricity provider: 20 supply interruption in January caused by an L1 grid failure in North Eastern Switzerland, and two interruptions of unknown duration, probably on a L2 grid sector. This would mean three interruptions in total, falling in-line with statistical data from the CREER study for that year. Bosnia I Hercegovina Data are available for this country from a Quality of transmission report 10, 11, and give the following SAIFI (System Average Interruption Frequency Index) and SAIDI: 16

17 Table 5 - SAIFI and SAIDI due to interruptions in the TRANSCO BIH network Table 6 - SAIFI and SAIDI including outages of MV feeders caused by interruptions in the distribution net As can be seen the interruptions are much more frequent there, but are quite often caused by planned shutdowns, probably for repair and extension of a highly damaged network. However, the average duration again roughly fits into the 60 /130 pattern. 2a.3 Conclusions Grid stability is improving in Europe, however there are still some outages. Major weather problems and unexpected consequences of repair and maintenance works can affect even generally stable and highly developed grids. Apart from very short failures (on which complete data are not available), it is possible to classify the outages in the following way: short term (less than 1 hour) 40-60% of cases on L2 and L3 networks, happen also on L1 grid. Average duration of medium term (1 hour) 20-30% of cases on all grid levels long term (2 hours) 20-30% of cases on all networks, less frequent than medium term ones catastrophic (more than 24 hours) possible once a year in all grids at least regionally. 17

18 The obtained results have been used as a basis for the development of a mix of grid failure simulations that represent the reality. However, in order to test systems long-term durability within FITUP project time limits, the frequency of the simulations in the actual test procedure will be higher than in real world. Part of the grid failure simulations will be performed with system starting at room temperature, since this is the case in large part of real world events. Anyway also start ups with warm system (i.e. with system temperature higher than ambient one) will be operated, representing events in which planned shutdowns are followed by unplanned problems. Finally, also 72 hours grid failure simulations will be performed, even if statistically very rare, because some final users involved in the project required that the UPSs demonstrate the capability to sustain the load for that amount of time. 2b. Test protocols adopted in previous projects During the development of the test protocol, existent reports concerning test procedures of this kind of systems were taken into account. These reports were produced during previous research projects and industrial tests, and some of the suggested procedures have been included in the FITUP protocol after proper modification. The Lucerne University of Applied Sciences and Arts - Lucerne School of Engineering and Architecture conducted field tests with a fuel cell UPS since January , 13. The project took place in collaboration with the industrial partners Swisscom AG and American Power Conversion Corporation, respectively as end user of UPS systems in the telecommunications sector and market leader of UPS systems. In this project, lead-acid batteries were replaced by a PEM fuel cell system, and the delayed start-up behaviour of the fuel cell was bridged with supercapacitor technology. The system was connected to an existing and working telecommunication base station, installed on the roof of the Lucerne School of Engineering and Architecture in Horw. Hydrogen was provided by two tanks. The field test was performed during a period of three years and a half, with approximately 350 system start-ups. The test protocol was developed together with the final user. Short term tests included a sequence of five grid failure simulations of 5 and a sequence of two simulations during 20, and were performed monthly; long term tests during 4 hours were instead performed 2 or 3 times a year. Excellent results confirmed the functionality, reliability and performance of the system. The environmental impact of lead-acid batteries and of the fuel cell system was also investigated: without recycling processes, the fuel cell leads to a reduction of CO 2 emissions close to 90% within a life cycle of 10 years. Considering lead-acid batteries recycling projects the reduction is anyway more than 80%. In a publication of a CRES Project 14 regarding a 5 kw PEM FC and electrolyser backup power system, designed by the project code HELPS, the authors report that a system being able to cope with a 5 hours interruption every 48 hours, would cover 99,6% of all possible grid power failures. With Vodafone as main sponsor and Electro Power Systems as product manufacturer, Environment Park performed tests of an Electro7 unit, connected to a radio access site located in an equipped van 18

19 from the Vodafone Disaster Recovery department. Test objective was to investigate whether the fuel cell UPS could technically substitute lead acid batteries as back up for the TLC equipment. The results obtained during the trial at Environment Park showed that Electro7 can cope with the typical network scenarios that a mobile network operator has to manage, being a valid alternative to traditional UPSs 15. The definition of the test protocol was also based on existent procedures for fuel cell stacks, in particular the ones developed in the FP5 RTN FCTESTNET thematic network, currently validated in the FP6 STREP FCTESQA 16. Both projects, scientifically coordinated by JRC, produced standardized documents, used as base structure for the protocols of this project. 19

20 3. TEST PROTOCOL GENERAL FEATURES 3a. Test purpose This document describes the test protocol that will be followed by the fuel cell UPS systems during FITUP project that includes both laboratory benchmark experiments and on-field tests, in locations defined by final users. The main purpose of the tests is to demonstrate that the fuel cell UPS systems satisfy the following objectives, stated in the project: reliability higher than 95% durability higher than 1500 hours and 1000 cycles (real-time or extrapolated) response time smaller than 5ms The reliability will be statistically verified at the end of the whole test campaign, that will involve 19 to 22 systems. Final users also specified that their usual reliability requirements are higher than 99%, and they expect that the tested systems will meet them. Response time will be controlled at each system start-up. The requirements in terms of durability will be instead completely checked only for 4 systems, two for each manufacturer involved in the project. These systems will be operated for more than 1500 hours, and will carry on more than 1000 on-off cycles. The data collected from these tests will be used to predict the aging of the other systems. The long-time tests will be operated in laboratory, due to the logistic complexity of the hydrogen tanks replacement in real-world applications. In addition to the mere verification of project objectives, during the tests additional data will be collected in order to investigate system performances and obtain useful information for manufacturers and final users. The described protocol could also be used as a standard performance test for fuel cell UPSs, both in laboratory and in real world applications. 3b. General test structure As said before, the protocol should include a mix of simulated failures that represent the actual grid operation. However, in order to reach the purposes of the tests within the project period, it will be necessary to expose the systems to a failure frequency higher than normal. In fact, the time available for the benchmark activities is 24 months (from M7 to M30), while the onfield tests will last a maximum of 23 months (from M13 to M35). 20

21 The grid failure simulations will be divided in three main groups, each one characterized by a different duration and representing a statistical class of failures that actually happen in electrical grids (see paragraph 2a.3): short term grid failures (A type), duration of 15 medium and long term grid failures (B type), duration of 240 (4 hours) catastrophic grid failures (C type), duration of 4320 (72 hours). B and C type simulations have a larger duration compared to the actual grid failures of the same class. The duration of B failures has been fixed in order to create test procedures respecting the given number of on-off cycles and hours of operation. C simulations satisfy instead a particular demand coming from some end users, that would like to check if the systems can match TETRA applications requirements. However, since the above said durations are larger than real world ones, the resulting tests are more stressing for the systems than usual functioning. As a consequence, if the systems will be able to withstand the programmed tests, they will prove to be capable of working in harder conditions than normal operation in Europe. During laboratory tests, each kind of grid failure simulation will be performed at different power levels (50%, 75% and 100% of total system power). This will not be done in on-field tests: in fact, in realworld applications it is not possible to choose the load applied to the systems. Moreover, two different start-up conditions will be employed: warm start up (1 type), duration of the off time before the cycle 1 cold start up (2 type), duration of the off time before the cycle 60 (minimum) The characteristics of the simulations and their frequency are indicated in the following table. Table 7 - test cycles characteristics Cycle name A1 A2 B1 B2 C1 C2 Cycle duration Off period before cycle 1 60 min min min. It is important to note that 60 is the minimum interval between a cycle and the following A2, B2 or C2 cycle. Therefore, it is necessary to leave the system off at least for one hour before any 2-type cycle can be performed, but is also possible to increase this waiting time as desired. A graphical representation of the different cycle types can be found in Annex A, figures

22 3c. Test procedures Five test procedures were defined, taking care of different test objectives, locations and system characteristics: 1. LONG-TIME DURABILITY BENCHMARK test (BENCH-LTD) 2. ADDITIONAL BENCHMARK tests (BENCH-ADD) 3. ON-FIELD test for systems with COMPRESSED H 2 CYLINDERS (OF-CH2) 4. ON-FIELD test for TETRA systems with COMPRESSED H 2 CYLINDERS (OF-TET) 5. ON-FIELD test for systems equipped with ELECTROLYSER (OF-ELS) Every procedure has been constructed combining the cycles listed in table 7. The precise description can be found in chapters 4 and 5. In the following table, the assignment of the test procedure to each system is showed. Table 8 - list of UPS systems installations Installation Location End-user Fc provider Code Test procedure Lucerne/Horw Swisscom EPS A1 OF-CH2 Lucerne Swisscom Future-E A2 OF-CH2 Zizers Swisscom EPS A3 OF-CH2 Davos Swisscom Future-E A4 OF-CH2 Ennetbürgen BKPNW Future-E A5 OF-CH2 Dallenwil BKPNW EPS A6 OF-TET ON FIELD Alpnach BKPNW Future-E A7 OF-TET Lucerne cantonal police to be defined in 2012 A8 to be defined in 2012 Settimo Milanese WIND EPS A9 OF-ELS Milan WIND EPS A10 OF-ELS Milan WIND EPS A11 OF-ELS Istanbul Turkcell EPS A12 OF-ELS Istanbul Turkcell Future-E A13 OF-ELS 22

23 Istanbul Istanbul Vodafone (to be confirmed) Vodafone (to be confirmed) EPS A14 OF-ELS Future-E A15 OF-ELS Istanbul UNIDO-ICHET EPS B1 BENCH-LTD Istanbul UNIDO-ICHET Future-E B2 BENCH-LTD BENCHMARK Petten JRC EPS B3 BENCH-LTD Petten JRC EPS B4 BENCH-ADD Petten JRC Future-E B5 BENCH-LTD Petten JRC Future-E B6 BENCH-ADD 23

24 4. BENCHMARK TESTS These tests will be performed in a laboratory environment and have the main purpose of supplying reference data, that will be compared with the information coming from the on-field measurements. Moreover, benchmark tests will include features that cannot be performed in on-field tests. In the following table, the list of the systems that will undergo to laboratory benchmark tests is reported; only systems not equipped with electrolyser are involved in these tests. Table 9 - list of benchmark systems Locations End-users FC provider Code Test procedure Istanbul UNIDO-ICHET EPS B1 BENCH-LTD Istanbul UNIDO-ICHET Future-E B2 BENCH-LTD Petten JRC EPS B3 BENCH-LTD Petten JRC EPS B4 BENCH-ADD Petten JRC Future-E B5 BENCH-LTD Petten JRC Future-E B6 BENCH-ADD The controlled test variables (test inputs) during benchmark tests will be: external grid power availability (controlled through a controlled power switch) load applied to the UPS systems environment temperature (only during climatic chamber tests). The resulting measured variables (test outputs) will be instead: voltage and current at fuel cell system terminals voltage and current at start-up batteries (or ultracapacitors) terminals voltage and current at electronic load terminals. Table 10 - list of measured variables (test outputs) during benchmark tests Variable Symbol Max uncertainty Sample rate Voltage at fuel cell terminals V fc 100 mv 1000 S/s - 10 S/s Current at fuel cell terminals I fc 1.05 A 1000 S/s - 10 S/s Voltage at battery/ultracap terminals V bat 100 mv 1000 S/s - 10 S/s 24

25 Current at battery/ultracap terminals I bat 1.05 A 1000 S/s - 10 S/s Voltage at electronic load terminals V load 100 mv 1000 S/s - 10 S/s Current at electronic load terminals I load 1.05 A 1000 S/s - 10 S/s 4a. Test equipment and setup The benchmark test system is composed by the following parts: an industrial pc used to control the tests and collect the data through an acquisition board, equipped with necessary signal conditioning devices a temperature sensor used to monitor the environment temperature three couples of cables that carry the voltage signals to the acquisition board three shunts used to measure the currents an electronic load that absorb the power produced by the UPS an ac/dc converter used to power the load using AC power, before the grid failure simulations a controlled switch that breaks the connection between the AC/DC converter and the grid an optional hydrogen sensor, used to detect gas leakage in the test environment. 25

26 Figure 8 - Setup for benchmark tests (BENCH-LTD and BENCH-OF) 4a.1 Installation instructions The installation procedure of the test equipment will vary from site to site, depending on the characteristics of the place, but there are some basic rules to follow in order to ensure the correct working of the system. The hydrogen sensor must be placed in the higher point of the system room in case of indoor installations (outdoor installations does not need this device). The ambient temperature sensor should be placed as close to the fuel cell as possible, in order to have a correct information about the temperature close to the UPS. The shunts, used to measure the current at fuel cell and batteries terminals, should be installed as close as possible to these devices. The shunt that measures the current going to the load should be instead placed immediately after the insertion of the backup systems on the DC bus, i.e. as far as possible from the load, in such a way that the ohmic losses on the bus are taken into account as loads. It is also necessary to place the shunts in a way that the heat produced by the shunts (around 10 W) can be dissipated. The voltage measurement points should be placed before shunts connections, excluding in this way the voltage drop on the shunts from the measurement. 26

27 The measurement cables should be shielded and as short as possible, in order to reduce electrical noise. The fuel cell system and start-up batteries (or ultracapacitors) must be installed and connected to the required supplies (air, hydrogen, ) according to manufacturer indications. 4a.2 Climate chamber An integrated environmental test system consisting of a walk-in climate chamber (ambient temperature in the range -40 C/+60 C, humidity up to 95%) is available at JRC. This chamber will be used to perform tests in extreme climate situations (tropical environment and freezing condition). During the preparation of a test inside the climate chamber, it is important to avoid any substantial modification of the tested system. Therefore, it is strongly recommended to connect the test equipment to the system in a way that it can be moved in and out from the chamber without any component disconnection. 4b. Long-term durability benchmark test procedure (BENCH-LTD) This test will completely satisfy the target of 1500 hours of system operation and 1000 on-off cycles, and will be done only in laboratory during benchmark activities, since it is very difficult to carry it on without an hydrogen line, due to the high number of hydrogen tanks needed. It will be applied to one system for each producer at each R&D centre in charge for benchmarking (4 systems in total, 2 at JRC and 2 at UNIDO-ICHET), in order to obtain data for the same procedure in different locations (and therefore different environmental conditions). Obtained data will be the basis for an extrapolation method that will be used to predict the performance of the systems that will run less hours. 4b.1 Base test procedure After system installation according to paragraph 4a, the test procedure can start with the turning on of the UPS, that will enter in stand-by mode. Each grid failure simulation will be carried on using the following sequence: setting of the grid failure simulation duration in the software turning on of the electronic load to the desired power value activation of the grid failure simulation through the software, that will automatically start the high frequency data logging (1000 S/s) and disconnect the grid from the load. After 10 seconds, the data logging frequency is reduced to 10 S/s at the end of the simulation, the software automatically connects the load to the grid. The data logging frequency is increased again to 1000 S/s for 10 seconds around this event. A total of 1548 operating hours and 1005 on-off cycles will be done. The characteristics of the simulations and their frequency are indicated in the following table. 27

28 Table 11 - BENCH-LTD procedure cycles characteristics Cycle name A1 A2 B1 B2 C1 C2 Cycle duration Off period before cycle 1 60 min min min. n cycles at 50% power n cycles at 75% power n cycles at 100% power Total number of cycles Total on hours % of total on hours The most of A and B cycles will be performed repeating 30 times the following sequence of simulation groups, named standard routine. Every group of the sequence contains less than 8 hours of total test time (sum of on and off periods, counted from the first start up to the last shut down of the day), therefore it can be contained in a standard working day. However, it is not compulsory to perform a group per day, but they can be arbitrarily arranged in time, as long as the waiting times between cycles are respected. Groups indicated by odd numbers share the same cycle sequence, but are performed at different power levels. The same holds for groups marked with even numbers. In Annex A graphical representations of odd- and even-numbered groups cycle sequences are reported in figures 17 and 18. Table 12 - BENCH-LTD standard routine Group Cycle order B2 3 A1 3 A2 B1 B2 3 A1 3 A2 B1 N of A N of A N of B N of B Total time Power level 75 % 75 % 75 % 75 % 28

29 Group Cycle order B2 3 A1 3 A2 B1 B2 3 A1 3 A2 B1 N of A N of A N of B N of B Total time Power level 50 % 50 % 100 % 100 % Every 6 times the standard routine is performed, a C cycle must be carried on. The order of C cycles is arbitrary, but all the cycles enumerated in table 11 must be done. At the end of the 30 repetitions of the standard routine, a final routine is performed as below: Table 13 - BENCH-LTD final routine Group Cycle order B2 3 A1 3 A2 B1 B2 3 A1 3 A2 B1 B2 3 A1 N of A N of A N of B N of B Total time Power level 75 % 75 % 75 % 75 % 75 % Group Cycle order 3 A2 B1 B2 3 A1 3 A2 B1 B2 3 A1 3 A2 B1 N of A N of A N of B N of B

30 Total time Power level 75 % 75 % 75 % 75 % 75 % 4b.2 Climate chamber tests Climate chamber tests in extreme environmental conditions will be performed at JRC, at the beginning (after 1 repetition of the standard routine), at mid-term (after 16 repetitions of the standard routine) and at the end (before the final routine) of the whole long-term test campaign: start-up in freezing environment (-15 C) the system will start and work for some minutes, until normal operating temperature is reached tropical environment continuous operation (40 C) the system will start and work for 1 hour at maximum power. The cycles carried on during climate chamber tests are additional to the ones enumerated in table 11. The climate chamber tests will be carried on in the following way: the UPS is placed inside the chamber the environment conditions are set when the temperature inside the chamber reaches the desired value, the test can start using the same procedure mentioned above. 4b.3 Hydrogen consumption evaluation The evaluation of the hydrogen consumption of the systems (and therefore the estimate of their efficiency) will be carried on through gravimetric measurements of the hydrogen tank used to feed the systems. In fact, this method assures the highest level of accuracy. These measurements will be operated both at JRC and UNIDO-ICHET, using a balance characterized by a range of 150 kg and an accuracy of 1 g. A special procedure was defined: 6 A2 cycles will be performed at 6 different constant power levels, starting at 100% of total system power (6 kw) and going down to 1 kw using 1 kw steps. The procedure is graphically represented in Annex A, figure 19. Each grid failure simulation is performed as indicated in paragraph 4b.1, but during the 60 of system inactivity between subsequent cycles, the hydrogen tank used to feed the system will be weighed. The tank should be placed directly on the balance, in order to weigh it without moving any part of the system. If this will not be possible, maximum care should be used during the disconnection of the tank from the system in order to avoid changes in tank weight not depending on hydrogen consumption. The whole procedure will be completed using a single hydrogen tank (50 l, 200 bar, approximately 10 Nm 3 ). The procedure will be done at the beginning (after 1 repetition of the standard routine), at mid-term (after 16 repetitions of the standard routine) and at the end (before the final routine) of the longterm benchmark test. 30

31 The cycles included in the hydrogen consumption evaluation procedure are additional to the ones enumerated in table 11. 4b.4 System stability under stress conditions Since the benchmark tests will start before the on-field ones, they will confirm that the chosen operating patterns do not damage the systems. In particular, the final users asked for a laboratory trial of the system stability under stress conditions test before on-field application. This test is composed by two sequences. The first one comprises 5 cycles composed by 5 start-ups and 5 shut-downs, alternatively repeated every 10 minutes (i.e. each cycle implies 5 repetitions of the succession composed by 10 minutes system on and 10 minutes system off). Between subsequent cycles the waiting time is one hour. 25 on-off cycles are performed in total. The second sequence is similar to the first one, but the duration of on and off times is 5 minutes instead of 10. Therefore, it is composed by 5 cycles made of 5 start-ups and 5 shut-downs, alternatively repeated every 5 minutes (i.e. each cycle implies 5 repetitions of the succession composed by 5 minutes system on and 5 minutes system off). Between subsequent cycles the waiting time is one hour. 25 on-off cycles are performed in total. In Annex A, graphs representing the cycles that form both sequences are reported (figures 20 and 21). 4b.5 Grid restore during system start-up, grid failure during system shut-down The final users asked also for a laboratory trial of the Grid restore during system start-up, grid failure during system shut-down test before on-field application. This test is composed by 5 grid restores during system start-up, followed by 5 grid outages during system shut-down (20 on-off cycles performed in total). The first part of the test (5 grid restores during system start-up) is automatically operated by the test software repeating 5 times the following sequence, starting with electronic load on and switch closed (i.e. load fully powered by the AC/DC rectifier): the switch opens the connection with the grid the start-up batteries power the load while the fuel cell starts up as soon as the current supplied by the fuel cell is equal to the 50% of the current drained by the load, the switch is closed again the system shuts down (the load powered again by the AC/DC rectifier) a 10 pause is observed before a new grid disconnection. The second part of the test (5 grid failures during system shut-down), always performed by he automatic software, is instead carried out repeating 5 times the sequence below, starting with electronic load on and switch open (i.e. fuel cell system supplying 100% of the current drained by the load): the switch is closed 31

32 the system starts the shut down procedure (the fuel cell does not supply power, but auxiliary equipment is still working) after 10 from the grid restore, the switch is opened again, i.e. the grid is disconnected the system starts up when the load is fully sustained by the fuel cell (100% of the current drained by the load supplied by the cell) the switch can be closed again. 4c. Additional benchmark tests (BENCH-ADD) The remaining 2 systems at JRC, one per manufacturer, will be tested after the end of the BENCH-LTD tests. The precise definition of the procedure is not included in this document, since the partners decided to leave it open for further development. In fact, the procedure will be decided taking into account the data resulting from BENCH-LTD tests, when they will be available. In this way, it will be possible to include in the procedure particular operating patterns, with the aim of investigating remarkable aspects underlined during previous tests. The BENCH-ADD procedure will be fully described in a separate document released after the end of the BENCH-LTD tests. 32

33 5. ON-FIELD TESTS The main target of these tests is the evaluation of UPSs behaviour in case of grid failure, in all the possible environmental conditions experimented in real-life applications. These tests must confirm the functionality, reliability and good performance of the system. In order to obtain this result, grid failure simulations will be performed in all the on-field installations of the project. Different test procedures were defined and assigned according to systems architecture and application. The attribution of the procedures to the systems is showed in the following table. Table 14 - list of on-field installations Locations End-users FC provider Code Suggested test Lucerne/Horw Swisscom EPS A1 OF-CH2 Lucerne Swisscom Future-E A2 OF-CH2 Zizers Swisscom EPS A3 OF-CH2 Davos Swisscom Future-E A4 OF-CH2 Ennetbürgen BKPNW Future-E A5 OF-CH2 Dallenwil BKPNW EPS A6 OF-TET Alpnach BKPNW Future-E A7 OF-TET Lucerne cantonal police to be defined in 2012 A8 to be defined in 2012 Settimo Milanese WIND EPS A9 OF-ELS Milan WIND EPS A10 OF-ELS Milan WIND EPS A11 OF-ELS Istanbul Turkcell EPS A12 OF-ELS Istanbul Turkcell Future-E A13 OF-ELS Istanbul Istanbul Vodafone (to be confirmed) Vodafone (to be confirmed) EPS A14 OF-ELS Future-E A15 OF-ELS 33

34 5a. Systems equipped with COMPRESSED H 2 CYLINDERS The controlled test variables (test inputs) during on-field tests of systems equipped with compressed hydrogen cylinders will be: external grid power availability (controlled through a controlled power switch). The resulting measured variables (test outputs) will be instead: voltage and current at fuel cell system terminals voltage and current at start-up batteries (or ultracapacitors) terminals voltage and current at electronic load terminals. Table 15 - list of measured variables (test outputs) in on-field tests of systems equipped with H 2 cylinders Variable Symbol Max uncertainty Sample rate Voltage at fuel cell terminals V fc 100 mv 1000 S/s - 10 S/s Current at fuel cell terminals I fc 1.05 A 1000 S/s - 10 S/s Voltage at battery/ultracap terminals V bat 100 mv 1000 S/s - 10 S/s Current at battery/ultracap terminals I bat 1.05 A 1000 S/s - 10 S/s Voltage at load terminals V load 100 mv 1000 S/s - 10 S/s Current at load terminals I load 1.05 A 1000 S/s - 10 S/s 5a.1 Test equipment and setup The test system is composed by the following components: an industrial pc used to control the tests and collect the data through an acquisition board, equipped with necessary signal conditioning devices a temperature sensor used to monitor the environment temperature three couples of cables that carry the voltage signals to the acquisition board three shunts used to measure the currents an ac/dc converter used to power the load using AC power, before the grid failure simulations. It is often already installed a controlled switch that breaks the connection between the AC/DC converter and the grid an optional hydrogen sensor used to detect gas leakage in the test environment. 34

Ilaria Rosso - FITUP project Coordinator Electro Power Systems SpA.

Ilaria Rosso - FITUP project Coordinator Electro Power Systems SpA. http://www.fch-ju.eu/ FITUP (Grant Agreement 256766 ) Fuel cell field test demonstration of economic and environmental viability for portable generators, backup and UPS power system applications Ilaria

More information

Deliverable 5.2 Public Report on Test Results

Deliverable 5.2 Public Report on Test Results Fuel Cell Field Test Demonstration of Economic and Environmental Viability for Portable Generators, Backup and UPS Power System Applications Deliverable 5.2 Public Report on Test Results Version 1.3 Report

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD May 1, 2017 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD June 1, 2018 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS) white paper ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS) Electricity, flowing continuously through the grid, is something that most of today s amenities rely on. For any electrical device to

More information

Fuel Cell Application in a New Configured Aircraft PUBLISHABLE REPORT

Fuel Cell Application in a New Configured Aircraft PUBLISHABLE REPORT Fuel Cell Application in a New Configured Aircraft PUBLISHABLE REPORT Document Reference CELINA Publishable Report Contract Nr. AST4-CT-2005-516126 Version/Date Version 1.3 January 2009 Issued by Airbus

More information

HYLIFT-DEMO DELIVERABLE 8.4

HYLIFT-DEMO DELIVERABLE 8.4 HYLIFT-DEMO DELIVERABLE 8.4 MIDTERM DISSEMINATION WORKSHOP FOR EUROPEAN ACTORS Work package 8 Lead Beneficiary: HyRaMP/EHA Dissemination Level: PU Date: June 2014 Acknowledgement This project is co-financed

More information

Publishable Executive Summary (M1-M48)

Publishable Executive Summary (M1-M48) Project no. 031414 Project acronym: METHAPU Project title: Validation of Renewable Methanol Based Auxiliary Power System for Commercial Vessels Instrument: Specific Targeted Research Project Thematic Priority:

More information

Monitoring the CO 2 emissions from new passenger cars in the EU: summary of data for 2010

Monitoring the CO 2 emissions from new passenger cars in the EU: summary of data for 2010 Monitoring the CO 2 emissions from new passenger cars in the EU: summary of data for 2010 EXECUTIVE SUMMARY EEA has collected data submitted by Member States on vehicle registrations in the year 2010,

More information

Battery Maintenance Solutions for Critical Facilities

Battery Maintenance Solutions for Critical Facilities Battery Maintenance Solutions for Critical Facilities Chapter Two: Meeting Regulatory Requirements and Observing Best Practices Click a section below In chapter one of Emerson Network Power s ebook entitled

More information

Fuel Cells and Hydrogen 2 Joint Undertaking (FCH 2 JU) Frequently Asked Questions

Fuel Cells and Hydrogen 2 Joint Undertaking (FCH 2 JU) Frequently Asked Questions Fuel Cells and Hydrogen 2 Joint Undertaking (FCH 2 JU) Frequently Asked Questions Background information: The Fuel Cells and Hydrogen Joint Undertaking was established in 2008-2013, as the first publicprivate

More information

Emergi-Lite EMEX central power supply solutions

Emergi-Lite EMEX central power supply solutions Emergi-Lite EMEX central power supply solutions Reliable central back up power Available for AC/AC and AC/DC power supply systems Exceptional overload performance Entire modular build for quick and simple

More information

A Comparison of Typical UPS Designs in Today s Markets

A Comparison of Typical UPS Designs in Today s Markets A Comparison of Typical UPS Designs in Today s Markets An Alpha Technologies White Paper by Kevin Binnie, Senior Product Portfolio Manager March 1, 2011 2 White Paper: A Comparison of Typical UPS Designs

More information

National comparison on verification of fuel dispensers

National comparison on verification of fuel dispensers 16 th International Congress of Metrology, 06011 (2013) DOI: 10.1051/ metrology/201306011 C Owned by the authors, published by EDP Sciences, 2013 National comparison on verification of fuel dispensers

More information

Ecodesign Directive for Batteries

Ecodesign Directive for Batteries January 2019 Ecodesign Directive for Batteries RECHARGE View on Criteria for Sustainable Batteries Introduction Over the next 15 years, a significant and constant growth is expected in battery volumes

More information

Smarter Solutions for a Clean Energy Future

Smarter Solutions for a Clean Energy Future April 8, 2013 FUEL CELL ENGINEERING SERVICES Smarter Solutions for a Clean Energy Future TJ Lawy Platform Manager, Engineering Services 2013 BALLARD POWER SYSTEMS, INC. ALL RIGHTS RESERVED. Who We Are

More information

Evaluation of Intelligent Transport Systems impact on school transport safety

Evaluation of Intelligent Transport Systems impact on school transport safety Evaluation of Intelligent Transport Systems impact on school transport safety Dagmara Jankowska-Karpa 1,*, and Justyna Wacowska-Ślęzak 1 1 Motor Transport Institute, Road Safety Centre, Warsaw, Poland

More information

Light Mobility Applications towards Public Education and Research

Light Mobility Applications towards Public Education and Research Light Mobility Applications towards Public Education and Research Y. Ceviz, M. Eroglu, T. Akfidan, S. Altinel, M. S. Yazici This document appeared in Detlef Stolten, Thomas Grube (Eds.): 18th World Hydrogen

More information

DG system integration in distribution networks. The transition from passive to active grids

DG system integration in distribution networks. The transition from passive to active grids DG system integration in distribution networks The transition from passive to active grids Agenda IEA ENARD Annex II Trends and drivers Targets for future electricity networks The current status of distribution

More information

DemoEV - Demonstration of the feasibility of electric vehicles towards climate change mitigation LIFE10 ENV/MT/000088

DemoEV - Demonstration of the feasibility of electric vehicles towards climate change mitigation LIFE10 ENV/MT/000088 DemoEV - Demonstration of the feasibility of electric vehicles towards climate change mitigation LIFE10 ENV/MT/000088 Project description Environmental issues Beneficiaries Administrative data Read more

More information

Propeller Blade Bearings for Aircraft Open Rotor Engine

Propeller Blade Bearings for Aircraft Open Rotor Engine NTN TECHNICAL REVIEW No.84(2016) [ New Product ] Guillaume LEFORT* The Propeller Blade Bearings for Open Rotor Engine SAGE2 were developed by NTN-SNR in the frame of the Clean Sky aerospace programme.

More information

Technical Series, Edition 16

Technical Series, Edition 16 Totally Integrated Power Technical Series, Edition 16 Transformer Selection according to Utilisation Profiles siemens.com/tip-cs 1. Regulations concerning efficiency requirements of dry-type transformers

More information

PUBLICATION NEW TRENDS IN ELEVATORING SOLUTIONS FOR MEDIUM TO MEDIUM-HIGH BUILDINGS TO IMPROVE FLEXIBILITY

PUBLICATION NEW TRENDS IN ELEVATORING SOLUTIONS FOR MEDIUM TO MEDIUM-HIGH BUILDINGS TO IMPROVE FLEXIBILITY PUBLICATION NEW TRENDS IN ELEVATORING SOLUTIONS FOR MEDIUM TO MEDIUM-HIGH BUILDINGS TO IMPROVE FLEXIBILITY Johannes de Jong E-mail: johannes.de.jong@kone.com Marja-Liisa Siikonen E-mail: marja-liisa.siikonen@kone.com

More information

SmartON / SmartON+ Installation and Use Manual

SmartON / SmartON+ Installation and Use Manual SmartON / SmartON+ Installation and Use Manual Rev. Date Ver. Ver. Notes document document SmartON SmartViewII 1.0 06/04/2007 3.08 2.30 Pre-release 1.01 10/04/2007 3.08 2.30 Release 1.02 04/10/2007 3.09

More information

Final Report. LED Streetlights Market Assessment Study

Final Report. LED Streetlights Market Assessment Study Final Report LED Streetlights Market Assessment Study October 16, 2015 Final Report LED Streetlights Market Assessment Study October 16, 2015 Funded By: Prepared By: Research Into Action, Inc. www.researchintoaction.com

More information

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants Breaking new ground A circuit breaker with the capacity to switch 15 large power plants Helmut Heiermeier, Reto Karrer The power networks that span the landscape and bring electrical energy to cities and

More information

Generators for the age of variable power generation

Generators for the age of variable power generation 6 ABB REVIEW SERVICE AND RELIABILITY SERVICE AND RELIABILITY Generators for the age of variable power generation Grid-support plants are subject to frequent starts and stops, and rapid load cycling. Improving

More information

==== ==== Use Solar energy to save you money. Check this Out! ==== ====

==== ==== Use Solar energy to save you money. Check this Out!   ==== ==== Use Solar energy to save you money. Check this Out! http://tinyurl.com/solarfreeenergy The Eastern Africa region comprises, among others countries like Kenya, Uganda, Tanzania, Rwanda, Burundi, Somalia

More information

Electric minibuses. Three new minibuses for Brive, France. Supply contract for 3 electric minibuses. Awarded: February 2016

Electric minibuses. Three new minibuses for Brive, France. Supply contract for 3 electric minibuses. Awarded: February 2016 SPP TENDER MODEL Electric minibuses Three new minibuses for Brive, France Purchasing body: Contract: Communauté d agglomération du Bassin de Brive (CABB) Supply contract for 3 electric minibuses Awarded:

More information

Utility and project update 2-3 Project description 4

Utility and project update 2-3 Project description 4 The concept of collaboration doesn t make for interesting headlines. But this kind of good news is definitely worth noting, even as other highlights of the project may seem much more exciting. Utility

More information

Plug-in Hybrid Vehicles Exhaust emissions and user barriers for a Plug-in Toyota Prius

Plug-in Hybrid Vehicles Exhaust emissions and user barriers for a Plug-in Toyota Prius Summary: Plug-in Hybrid Vehicles Exhaust emissions and user barriers for a Plug-in Toyota Prius TØI Report 1226/2012 Author(s): Rolf Hagman, Terje Assum Oslo 2012, 40 pages English language Plug-in Hybrid

More information

Performance of Batteries in Grid Connected Energy Storage Systems. June 2018

Performance of Batteries in Grid Connected Energy Storage Systems. June 2018 Performance of Batteries in Grid Connected Energy Storage Systems June 2018 PERFORMANCE OF BATTERIES IN GRID CONNECTED ENERGY STORAGE SYSTEMS Authors Laurie Florence, Principal Engineer, UL LLC Northbrook,

More information

European Tyre and Rim Technical Organisation RETREADED TYRES IMPACT OF CASING AND RETREADING PROCESS ON RETREADED TYRES LABELLED PERFORMANCES

European Tyre and Rim Technical Organisation RETREADED TYRES IMPACT OF CASING AND RETREADING PROCESS ON RETREADED TYRES LABELLED PERFORMANCES European Tyre and Rim Technical Organisation RETREADED TYRES IMPACT OF CASING AND RETREADING PROCESS ON RETREADED TYRES LABELLED PERFORMANCES Content 1. Executive summary... 4 2. Retreaded tyres: reminder

More information

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles The UK trade body for the caravan, motorhome, caravan holiday and park home industry. NCC Leisure Battery Verification Scheme Leisure Accommodation Vehicles Page 1 of 11 1 Scope The NCC Battery Verification

More information

ABB MEASUREMENT & ANALYTICS. Predictive Emission Monitoring Systems The new approach for monitoring emissions from industry

ABB MEASUREMENT & ANALYTICS. Predictive Emission Monitoring Systems The new approach for monitoring emissions from industry ABB MEASUREMENT & ANALYTICS Predictive Emission Monitoring Systems The new approach for monitoring emissions from industry 2 P R E D I C T I V E E M I S S I O N M O N I T O R I N G S Y S T E M S M O N

More information

Experiences in a Motor Protection Retrofit

Experiences in a Motor Protection Retrofit Special Feature by Kyle Craig, Ontario Power Generation Amy Sinclair, Schweitzer Engineering Laboratories, Inc. Experiences in a Motor Protection Retrofit Introduction The initial stage of any project

More information

Tendering Public Charging Infrastructure for Electric Vehicles

Tendering Public Charging Infrastructure for Electric Vehicles European Best Practices: Tendering Public Charging Infrastructure for Electric Vehicles Best Value Procurement in the city of Arnhem Authors: Peter Swart, Arnhem City Roos van der Ploeg, MA legal & EV

More information

INCREASING THE ELECTRIC MOTORS EFFICIENCY IN INDUSTRIAL APPLICATIONS

INCREASING THE ELECTRIC MOTORS EFFICIENCY IN INDUSTRIAL APPLICATIONS Institute for Sustainable Energy, UNIVERSITY OF MALTA SUSTAINABLE ENERGY 12: THE ISE ANNUAL CONFERENCE PROCEEDINGS Tuesday 21 February 12, Dolmen Hotel, Qawra, Malta INCREASING THE ELECTRIC MOTORS EFFICIENCY

More information

Redflow Telco Application Whitepaper

Redflow Telco Application Whitepaper Redflow Telco Application Whitepaper RedFlow Telco Application Whitepaper 2015 1. Introduction This article reports about the successful demonstration of the RedFlow Zinc Bromine Module (ZBM) integrated

More information

PRODUCT BROCHURE. ABB Ability Wireless Monitor for surge arrester Enabling reliability and availability of power supply

PRODUCT BROCHURE. ABB Ability Wireless Monitor for surge arrester Enabling reliability and availability of power supply PRODUCT BROCHURE ABB Ability Wireless Monitor for surge arrester Enabling reliability and availability of power supply ABB Ability Wireless Monitor for surge arresters is a remote condition monitoring

More information

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train K.Ogawa, T.Yamamoto, T.Hasegawa, T.Furuya, S.Nagaishi Railway Technical Research Institute (RTRI), TOKYO,

More information

Optimising battery energy storage systems operation

Optimising battery energy storage systems operation Optimising battery energy storage systems operation 02/26/2015-5.17 pm Network management Renewables Smart Grids Storage Grid-tied battery energy storage systems (BESS) are promising smart grid solutions

More information

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden

More information

SMART DIGITAL GRIDS: AT THE HEART OF THE ENERGY TRANSITION

SMART DIGITAL GRIDS: AT THE HEART OF THE ENERGY TRANSITION SMART DIGITAL GRIDS: AT THE HEART OF THE ENERGY TRANSITION SMART DIGITAL GRIDS For many years the European Union has been committed to the reduction of carbon dioxide emissions and the increase of the

More information

AIR POLLUTION AND ENERGY EFFICIENCY. Update on the proposal for "A transparent and reliable hull and propeller performance standard"

AIR POLLUTION AND ENERGY EFFICIENCY. Update on the proposal for A transparent and reliable hull and propeller performance standard E MARINE ENVIRONMENT PROTECTION COMMITTEE 64th session Agenda item 4 MEPC 64/INF.23 27 July 2012 ENGLISH ONLY AIR POLLUTION AND ENERGY EFFICIENCY Update on the proposal for "A transparent and reliable

More information

Project introduction. Document prepared by: Element Energy. A project co-funded by under the Grant Agreement n and n.

Project introduction. Document prepared by: Element Energy. A project co-funded by under the Grant Agreement n and n. Project introduction Document prepared by: Element Energy A project co-funded by under the Grant Agreement n.671438 and n. 700350 H2ME initiative (2015 2022) Project overview HRS: Hydrogen Refuelling Station

More information

GREEN WAREHOUSE LOGISTICS

GREEN WAREHOUSE LOGISTICS GREEN WAREHOUSE LOGISTICS I believe that one day water will be used as a fuel and its constituents, hydrogen and oxygen, will separately or together become an inexhaustible source of heat and light. Quelle:

More information

OFF-GRID SOLUTIONS BASED ON RES AND ENERGY STORAGE CONFIGURATIONS

OFF-GRID SOLUTIONS BASED ON RES AND ENERGY STORAGE CONFIGURATIONS OFF-GRID SOLUTIONS BASED ON RES AND ENERGY STORAGE CONFIGURATIONS Kaldellis J.K., Kondili E. (*), Kavadias K., Zafirakis D. Lab of Soft Energy Applications & Environmental Protection (*) Optimisation of

More information

Measurement made easy. Predictive Emission Monitoring Systems The new approach for monitoring emissions from industry

Measurement made easy. Predictive Emission Monitoring Systems The new approach for monitoring emissions from industry Measurement made easy Predictive Emission Monitoring Systems The new approach for monitoring emissions from industry ABB s Predictive Emission Monitoring Systems (PEMS) Experts in emission monitoring ABB

More information

Using ABAQUS in tire development process

Using ABAQUS in tire development process Using ABAQUS in tire development process Jani K. Ojala Nokian Tyres plc., R&D/Tire Construction Abstract: Development of a new product is relatively challenging task, especially in tire business area.

More information

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

More information

Equipment Strategy for Stand By Diesel Generators Strategy

Equipment Strategy for Stand By Diesel Generators Strategy Equipment Strategy for Stand By Diesel Generators Strategy Current version: 26/06/2018 EXTERNAL USE Page 1 of 6 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 Defined terms...

More information

Design Modeling and Simulation of Supervisor Control for Hybrid Power System

Design Modeling and Simulation of Supervisor Control for Hybrid Power System 2013 First International Conference on Artificial Intelligence, Modelling & Simulation Design Modeling and Simulation of Supervisor Control for Hybrid Power System Vivek Venkobarao Bangalore Karnataka

More information

D1.3 FINAL REPORT (WORKPACKAGE SUMMARY REPORT)

D1.3 FINAL REPORT (WORKPACKAGE SUMMARY REPORT) WP 1 D1.3 FINAL REPORT (WORKPACKAGE SUMMARY REPORT) Project Acronym: Smart RRS Project Full Title: Innovative Concepts for smart road restraint systems to provide greater safety for vulnerable road users.

More information

The Motorcycle Industry in Europe. ACEM Position on the revision of directive 2009/40/EC on roadworthiness tests for motor vehicles

The Motorcycle Industry in Europe. ACEM Position on the revision of directive 2009/40/EC on roadworthiness tests for motor vehicles ACEM Position on the revision of directive 2009/40/EC on roadworthiness tests for motor vehicles September 2010 ACEM, the Motorcycle Industry in Europe, is the professional body representing the interests

More information

Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities. FCH Bikes

Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities. FCH Bikes Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities FCH Bikes Brussels, Fall 2017 This compilation of application-specific information forms part of the study

More information

HYSYS System Components for Hybridized Fuel Cell Vehicles

HYSYS System Components for Hybridized Fuel Cell Vehicles HYSYS System Components for Hybridized Fuel Cell Vehicles J. Wind, A. Corbet, R.-P. Essling, P. Prenninger, V. Ravello This document appeared in Detlef Stolten, Thomas Grube (Eds.): 18th World Hydrogen

More information

Accelerated Testing of Advanced Battery Technologies in PHEV Applications

Accelerated Testing of Advanced Battery Technologies in PHEV Applications Page 0171 Accelerated Testing of Advanced Battery Technologies in PHEV Applications Loïc Gaillac* EPRI and DaimlerChrysler developed a Plug-in Hybrid Electric Vehicle (PHEV) using the Sprinter Van to reduce

More information

ABB life cycle services Uninterruptible power supplies

ABB life cycle services Uninterruptible power supplies ABB life cycle services Uninterruptible power supplies 2 ABB Life cycle brochure UPS service portfolio Life cycle services for uninterruptible power supplies As your service partner, ABB guarantees you

More information

Results of the High V.LO-City & HyTRANSIT projects

Results of the High V.LO-City & HyTRANSIT projects Cities speeding up the integration of fuel cell electric buses Results of the High V.LO-City & HyTRANSIT projects Valentine Willmann Hydrogen, Fuel Cells and Electro-mobility in European Regions Giantleap

More information

White Paper. Direct Current Load Banks for Battery Capacity Testing

White Paper. Direct Current Load Banks for Battery Capacity Testing White Paper Direct Current Load Banks for Battery Capacity Testing Direct Current Load Banks for Battery Capacity Testing Reliable Direct Current (DC) power requires battery systems to be maintained according

More information

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Modular Standardized Electrical and Control Solutions for Fast Track Projects Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive

More information

Power Conditioning of Microgrids and Co-Generation Systems

Power Conditioning of Microgrids and Co-Generation Systems Power Conditioning of Microgrids and Co-Generation Systems Nothing protects quite like Piller piller.com Content 1 Introduction 3 2 Basic requirements of a stable isolated network 3 3 Requirements for

More information

Interruption Technology of Breakers for High-voltage Direct Current

Interruption Technology of Breakers for High-voltage Direct Current Interruption Technology of Breakers for High-voltage Direct MORIAI Hiroshi ABSTRT Applications for direct current () electric distribution have been spreading along with the increase of data centers and

More information

Consumers, Vehicles and Energy Integration (CVEI) project

Consumers, Vehicles and Energy Integration (CVEI) project Consumers, Vehicles and Energy Integration (CVEI) project Dr Stephen Skippon, Chief Technologist September 2016 Project aims To address the challenges involved in transitioning to a secure and sustainable

More information

PV inverters in a High PV Penetration scenario Challenges and opportunities for smart technologies

PV inverters in a High PV Penetration scenario Challenges and opportunities for smart technologies PV inverters in a High PV Penetration scenario Challenges and opportunities for smart technologies Roland Bründlinger Operating Agent IEA-PVPS Task 14 UFTP & IEA-PVPS Workshop, Istanbul, Turkey 16th February

More information

Research in use of fuel conversion adapters in automobiles running on bioethanol and gasoline mixtures

Research in use of fuel conversion adapters in automobiles running on bioethanol and gasoline mixtures Agronomy Research 11 (1), 205 214, 2013 Research in use of fuel conversion adapters in automobiles running on bioethanol and gasoline mixtures V. Pirs * and M. Gailis Motor Vehicle Institute, Faculty of

More information

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi

More information

D6.5 Public report on experience & results from FCEV city car demonstration in Oslo

D6.5 Public report on experience & results from FCEV city car demonstration in Oslo D6.5 Public report on experience & results from FCEV city car demonstration in Oslo Final Report Dissemination level: PU February 2013 Page 1 of 13 Introduction WP6 Deliverable D6.5 Public report on experience

More information

APPLICATION GUIDE. ACH580 Managing total cost of ownership of HVAC systems

APPLICATION GUIDE. ACH580 Managing total cost of ownership of HVAC systems APPLICATION GUIDE ACH580 Managing total cost of ownership of HVAC systems 3 Table of contents 4 Creating a climate of efficiency with the ACH580 5 A clear vision for the HVAC industry 6 The true cost

More information

White paper: Pneumatics or electrics important criteria when choosing technology

White paper: Pneumatics or electrics important criteria when choosing technology White paper: Pneumatics or electrics important criteria when choosing technology The requirements for modern production plants are becoming increasingly complex. It is therefore essential that the drive

More information

Doing business with Petrobras - Procurement Strategies and Local Content. Policy.

Doing business with Petrobras - Procurement Strategies and Local Content. Policy. Doing business with Petrobras - Procurement Strategies and Local Content Ronaldo M. L. Martins, M.Sc. Market Development, Manager Procurement Department March/2015 Policy. Disclaimer FORWARD-LOOKING STATEMENTS

More information

APPLICATION NOTE USING A MODEL 3060-MS AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract. Introduction. Dissipative Load Bank

APPLICATION NOTE USING A MODEL 3060-MS AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract. Introduction. Dissipative Load Bank USING A MODEL 3060-MS AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model 3060-MS

More information

Introduction: Supplied to 360 Test Labs... Battery packs as follows:

Introduction: Supplied to 360 Test Labs... Battery packs as follows: 2007 Introduction: 360 Test Labs has been retained to measure the lifetime of four different types of battery packs when connected to a typical LCD Point-Of-Purchase display (e.g., 5.5 with cycling LED

More information

N-03 STEERING GEAR CONTROL SYSTEMS

N-03 STEERING GEAR CONTROL SYSTEMS Guideline No.: N-03(201510) N-03 STEERING GEAR CONTROL SYSTEMS Issued date: October 20,2015 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements,

More information

MARANDA project overview

MARANDA project overview MARANDA project overview Open workshop on fuel cells and hydrogen in transportation applications, Espoo, 2017-10-09 Pohjoranta A., Ihonen J., Nissilä M., Pulkkinen V. VTT Technical Research Centre of Finland

More information

Presentation of the European Electricity Grid Initiative

Presentation of the European Electricity Grid Initiative Presentation of the European Electricity Grid Initiative Contractors Meeting Brussels 25th September 2009 1 Outline Electricity Network Scenario European Electricity Grids Initiative DSOs Smart Grids Model

More information

HOMER OPTIMIZATION BASED SOLAR WIND HYBRID SYSTEM 1 Supriya A. Barge, 2 Prof. D.B. Pawar,

HOMER OPTIMIZATION BASED SOLAR WIND HYBRID SYSTEM 1 Supriya A. Barge, 2 Prof. D.B. Pawar, 1 HOMER OPTIMIZATION BASED SOLAR WIND HYBRID SYSTEM 1 Supriya A. Barge, 2 Prof. D.B. Pawar, 1,2 E&TC Dept. TSSM s Bhivrabai Sawant College of Engg. & Research, Pune, Maharashtra, India. 1 priyaabarge1711@gmail.com,

More information

Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter. Model ESR60/ESR70. Designed and manufactured with pride in the UK.

Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter. Model ESR60/ESR70. Designed and manufactured with pride in the UK. GB60/70-9 Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter Model ESR60/ESR70 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2004/2016 In

More information

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS 2013 NDIA GROUND VEHICLE SYSTEMS ENGINEERING AND TECHNOLOGY SYMPOSIUM POWER AND MOBILITY (P&M) MINI-SYMPOSIUM AUGUST 21-22, 2013 TROY, MICHIGAN HIGH VOLTAGE vs. LOW VOLTAGE: POTENTIAL IN MILITARY SYSTEMS

More information

Mobile Renewable House

Mobile Renewable House Mobile Renewable House M.F. Serincan, M. Eroglu, M.S. Yazici This document appeared in Detlef Stolten, Thomas Grube (Eds.): 18th World Hydrogen Energy Conference 2010 - WHEC 2010 Parallel Sessions Book

More information

Wind Power Applications & Supercapacitors

Wind Power Applications & Supercapacitors Wind Power Applications & Supercapacitors Table of Contents Introduction... 3 Pitch Control... 3 Power Conditioning... 4 Conclusion... 5 More about KEMET... 6 Copyright 2013 KEMET Corporation Page 2 Introduction

More information

Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities. FCH Airport ground handling equip.

Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities. FCH Airport ground handling equip. Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities FCH Airport ground handling equip. Brussels, Fall 2017 This compilation of application-specific information

More information

Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities. Electricity grid services

Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities. Electricity grid services Development of Business Cases for Fuel Cells and Hydrogen Applications for Regions and Cities Electricity grid services Brussels, Fall 2017 This compilation of application-specific information forms part

More information

MINIPAK. Handheld fuel cell power system. Frequently Asked Questions

MINIPAK. Handheld fuel cell power system. Frequently Asked Questions MINIPAK Handheld fuel cell power system Frequently Asked Questions Q: What is the MINIPAK? A: The MINIPAK personal power center delivers 1.5W of continuous power using a standard USB port, and uses refillable

More information

Optimization of Total Operating Costs Using Electric Linear Drives

Optimization of Total Operating Costs Using Electric Linear Drives Optimization of Total Operating Costs Using Electric Linear Drives TCO analysis demonstrates high potential for savings, even for simple applications, by replacing pneumatic drives Electric linear drives

More information

PAKISTAN STANDARD LEAD ACID STARTER BATTERIES - Part-1: General Requirements and Methods of Test. (All Rights Reserved) PS: 206-1/2012 (2 nd Rev.

PAKISTAN STANDARD LEAD ACID STARTER BATTERIES - Part-1: General Requirements and Methods of Test. (All Rights Reserved) PS: 206-1/2012 (2 nd Rev. PAKISTAN STANDARD LEAD ACID STARTER BATTERIES - Part-1: General Requirements and Methods of Test (All Rights Reserved) PAKISTAN STANDARDS AND QUALITY CONTROL AUTHORITY, STANDARDS DEVELOPMENT CENTRE, PSQCA

More information

AN ELECTRICAL FUEL PUMPING AND METERING SYSTEM FOR MORE ELECTRICAL AERO-ENGINES

AN ELECTRICAL FUEL PUMPING AND METERING SYSTEM FOR MORE ELECTRICAL AERO-ENGINES 25 TH INTERNATIONAL CONGRESS OF THE AERONAUTICAL SCIENCES AN ELECTRICAL FUEL PUMPING AND METERING SYSTEM FOR MORE ELECTRICAL AERO-ENGINES Jean-Yves ROUTEX HISPANO-SUIZA, SAFRAN GROUP Keywords: Fuel, pumping,

More information

UNDERSTANDING GENERATOR SET RATINGS FOR MAXIMUM PERFORMANCE AND RELIABILITY

UNDERSTANDING GENERATOR SET RATINGS FOR MAXIMUM PERFORMANCE AND RELIABILITY TECHNICAL ARTICLE UNDERSTANDING GENERATOR SET RATINGS FOR MAXIMUM PERFORMANCE AND RELIABILITY Onsite power systems perform at maximum capability only when its generator sets are sized to the appropriate

More information

International Aluminium Institute

International Aluminium Institute THE INTERNATIONAL ALUMINIUM INSTITUTE S REPORT ON THE ALUMINIUM INDUSTRY S GLOBAL PERFLUOROCARBON GAS EMISSIONS REDUCTION PROGRAMME RESULTS OF THE 2003 ANODE EFFECT SURVEY 28 January 2005 Published by:

More information

Post Opening Project Evaluation. M6 Toll

Post Opening Project Evaluation. M6 Toll M6 Toll Five Post Years Opening After Study: Project Summary Evaluation Report Post Opening Project Evaluation M6 Toll Five Years After Study Summary Report October 2009 Document History JOB NUMBER: 5081587/905

More information

Proposed Special Condition for limited Icing Clearances Applicable to Large Rotorcraft, CS 29 or equivalent. ISSUE 1

Proposed Special Condition for limited Icing Clearances Applicable to Large Rotorcraft, CS 29 or equivalent. ISSUE 1 Proposed Special Condition for limited Icing Clearances Applicable to Large Rotorcraft, CS 29 or equivalent. ISSUE 1 Introductory note: The hereby presented Special Condition has been classified as important

More information

76th UNECE GRPE session

76th UNECE GRPE session Submitted by the IWG on PMP Informal document GRPE-74-33 76 th GRPE, 11-12 January 2018 Agenda item 7 76th UNECE GRPE session PMP IWG Progress Report Geneva, 10 th -11 th January 2018 UNITED NATIONS PMP

More information

TDG-F-113 CEC New Test Development Proposal for a New Engine Fuels Test Procedure

TDG-F-113 CEC New Test Development Proposal for a New Engine Fuels Test Procedure TDG-F-113 CEC New Test Development Proposal for a New Engine Fuels Test Procedure DISI (Direct Injection spark ignited engine) Injector fouling Test 1. Demonstrated need- The proposed test will address

More information

elektronik Designing vehicle power nets A single simulation tool from initial requirements to series production

elektronik Designing vehicle power nets A single simulation tool from initial requirements to series production www.atzonline.de elektronik 04 April 2013 Volume 8 Offprint from ATZelektronik 4/2013 Springer Automotive Media Springer Fachmedien Wiesbaden GmbH for Bosch Engineering Designing vehicle power nets A single

More information

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST BEFORE THE FLORIDA PUBLIC SERVICE COMMISSION In re: Staff's Second Data Request on OUC' s Review of Electric Utility Hurricane Preparedness and Restoration Actions Docket No. 20170215-EU Filed: January

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

EXPERIENCE FROM THE REFUELLING PLANNING TO PREPARE THE H2MS EUROPEAN HYDROGEN ROAD TOUR EXECUTIVE SUMMARY FOR USE IN EXPERT DISCUSSIONS

EXPERIENCE FROM THE REFUELLING PLANNING TO PREPARE THE H2MS EUROPEAN HYDROGEN ROAD TOUR EXECUTIVE SUMMARY FOR USE IN EXPERT DISCUSSIONS EXPERIENCE FROM THE REFUELLING PLANNING TO PREPARE THE H2MS EUROPEAN HYDROGEN ROAD TOUR EXECUTIVE SUMMARY FOR USE IN EXPERT DISCUSSIONS Final 19 December 2012 Dr. Ulrich Bünger, Jan Zerhusen Ludwig-Bölkow-Systemtechnik

More information

ENERGY STORAGE SOLUTIONS FOR IMPROVING THE ENERGY EFFICIENCY OF PUBLIC TRANSPORT VEHICLES

ENERGY STORAGE SOLUTIONS FOR IMPROVING THE ENERGY EFFICIENCY OF PUBLIC TRANSPORT VEHICLES ENERGY STORAGE SOLUTIONS FOR IMPROVING THE ENERGY EFFICIENCY OF PUBLIC TRANSPORT VEHICLES R. BARRERO (VUB) - X. TACKOEN (ULB) STIB - Brussels - 5th of February 2009 Plan of the presentation The EVEREST

More information

VOLTAGE SAGS; A LITTLE STORAGE CAN GO A LONG WAY

VOLTAGE SAGS; A LITTLE STORAGE CAN GO A LONG WAY WHITE PAPER VOLTAGE SAGS; A LITTLE STORAGE CAN GO A LONG WAY I. Utility power in the U.S. is very reliable; we count on it to be there, expect it to be there, and it usually is. Barring natural disasters

More information