IS46/PS33 Current Power Supply System

Size: px
Start display at page:

Download "IS46/PS33 Current Power Supply System"

Transcription

1 ATTACHMENT B IS46/PS33 Current Power Supply System Page 1 of 11

2 TABLE OF CONTENTS: 1. Summary Terminology Remote elements power supply system kv power transmission line /0.2 kv Step-down transformers VAC power transmission lines / 20 V step-down transformers VAC power transmission lines VAC/12 VDC power supply units Other CRF power supply system Figures... 6 Page 2 of 11

3 1. Summary The document describes the Power Supply System (PSS) of IS46/PS33 co-located IMS arrays in Zalesovo, Russian Federation. 2. Terminology CRF Central Recording Facility; PSS Power Supply System, low-voltage part (220 VAC / 24&12 VDC); SPD Surge Protective Device; Station IS46 infrasound and PS33 seismic co-located IMS arrays; 3. Remote elements power supply system The power supply system for the remote elements consists of 10 kv AC overhead line to each array element, step-down transformers (10 kv to 220 AC and 220 AC to 20 AC), located on the last pole of the 10 kv line at each array element, rectifiers and battery chargers, back-up batteries and DC distribution boxes inside the equipment vaults. The remote elements PSS consist of: 10 kv overhead power transmission line; 10 /0.2 kv step-down transformer at each array element (except B4/H4 array elements, sharing one transformer); 220 VAC power transmission lines; 220/20 VAC step-down transformer at each array element; 20 VAC power transmission lines; 20 VAC/12 VDC power supply units, at each array element; 12 VDC distribution system, including DC filters, at each array element; Back-up batteries; The main parts of the PSS are described below. The diagrams of the PSS are shown in Figures 1 and 2. The step-down transformers, surge protective devices and manual switches are located at the last pole of the 10 kv overhead power line. The rest of the equipment is installed inside the equipment vaults kv power transmission line The line is an IT 3-phase 3-conductor line (without the neutral conductor). The part of the line going to the array elements has only 2 phase conductors out of three. The phases are split at the CRF (see Figure 1 for details). The total length of the line from the CRF sub-station is 11.5 km. Page 3 of 11

4 3.2 10/0.2 kv Step-down transformers Two types of 10/0.2 kv transformers (TR3 in the Figure 1) are used at the array elements: oil-cooled OM-0.63/10 UKhL1 and OM-1.25/10 71U1. The capacity of transformers, installed at particular array elements, is unknown, since the access to the 10 kv installation is restricted to authorized personnel of electrical company only. The main technical data of the transformers are as follows: OM-0.63/10 UKhL1 Nominal frequency 50 Hz 50 Hz OM-1.25/10 71U1 Nominal power 0.63 kva 1.25 kva Nominal voltage at primary winding 10 kv 10 kv Nominal voltage at secondary winding kv kv Nominal current at primary winding A A Nominal current at secondary winding 2.74 A 5.44 A The a 1 (N conductor) low-voltage output of the transformers has to be grounded at the transformer, but at least at two array elements this output is not connected to the ground VAC power transmission lines The 220 VAC power is transmitted from the 10kV/0.2 kv transformers to 220 V/20 V transformers via two separate 4 mm 2 aluminium wires. The length of the transmission lines vary from 6 to 100 m (at the array elements H4 and B4). There are no automatic circuit breakers or surge protection devices in the 220 VAC line. No protective ground is used; the neutral conductor is not grounded. The power can be disconnected from 220/20 V transformers by a manual switch Q1 (Fig. 1) / 20 V step-down transformers The transformers (TR4, Fig. 1) are installed on the last pole of the power transmission lines. Each installation consists of two transformers V.U. EMME, 200 VA, 220/18 V mod. 120, installed in parallel. Note, that the transformers do not have sufficient power for maximum consumption of H1 array element (470 VA) VAC power transmission lines The lines consist of 3 x 4 mm 2 copper unshielded cables, laid in steel pipes between the step-down transformers and equipment vaults. The neutral conductor is not grounded, the PE conductor is not connected at the moment to ground at the transformer side, but grounded at the equipment vault. There are no automatic circuit breakers or surge protection devices in the 220 VAC line VAC/12 VDC power supply units The power supply units consist of two separate blocks, AC/DC converter and charger. The blocks are shown in the Figure XX. The units are not available on the market anymore. Manual and specification sheets for the units are not available. Page 4 of 11

5 3.7 Other The DC part of the power supply system is done according to the certification documentation and is standard for seismic and infrasound installations. Back-up batteries are 2 x BAE 6V OPz 200 type, and have a capacity to maintain the equipment for at leats 3 days (2 days for H1). 4. CRF power supply system The power supply system at the CRF is a 3-phase TN-C-S system, designed and built according to Russian and international standards. The system is shown in Figure 2. The CRF building has three independent power supply lines (two from 10 kv lines, and one from emergency diesel generator). Note, that none of incoming and outgoing cables are protected by surge protective devices. Page 5 of 11

6 5. Figures Figure 1. IS46/PS33 schematic power supply system diagram Page 6 of 11

7 Figure21. IS46/PS33 CRF schematic power supply system diagram Page 7 of 11

8 Explication table for Figure 2 AQ1 KM1/KM2 AQ2 AE-2066, 150 A AQ3 AE-2066, 250 A AQ4 100 A, 3-phase AQ5 40 A, 3-phase AQ6 16 A, 3-phase AQ7 32 A, 3-phase AQ8 25 A, 3-phase AQ9 16 A, single-phase RS1 Residual switches, I n =30 ma F1 150 A Q1 Manual switch Circles 1 to 8 Distribution cabinets Page 8 of 11

9 Figure 3. First pole of 10 kv PTL Figure 4. 10/0.4 kv transformer at the CRF Page 9 of 11

10 Figure 5. Surge protective devices at 10 kv line. Figure 6. 10/0.2 kv transformer and 10 kv fuses at the last pole of 10 kv PTL Page 10 of 11

11 Figure VAC manual switch Figure /20 V transformer Page 11 of 11

LASERMET MINIATURE LED SIGN POWER AND SWITCH UNIT. Installation Instructions

LASERMET MINIATURE LED SIGN POWER AND SWITCH UNIT. Installation Instructions LASERMET MINIATURE LED SIGN POWER AND SWITCH UNIT Installation Instructions PS-LEDS-1W PS-LEDS-RG 00597-53-000 Issue 2 23 August 2010 Introduction The Miniature LED Sign Power and Switch Unit is intended

More information

1.7. Portable insulation fault location system EDS3060/EDS3360 in combination with EDS460/461 systems

1.7. Portable insulation fault location system EDS3060/EDS3360 in combination with EDS460/461 systems Portable insulation fault location system EDS3060/EDS3360 in combination with EDS460/461 systems An additional function allows measuring residual currents in earthed power supplies (TN/TT systems) too.

More information

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A Transfer switches The solution for > Genset < 90 kva > Heating systems > Climate control > Ventilation systems > Telecommunications atys-s_018_a Strong points Function products are 4 pole remotely operated

More information

Schedules 1 to 4, Lot B: Extension of the Lessos Substation

Schedules 1 to 4, Lot B: Extension of the Lessos Substation 1.0 LIGHTNING ARRESTORS 1.1 ZNO lightning arrester, 192 kv rated voltage, 10 ka nominal discharge current 2.0 CAPACITIVE VOLTAGE TRANSFORMER ea. 45 2.1 220 kv capacitive voltage transformer 220/ 3 / 0.11/

More information

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino

More information

132/11 kv, 25 MVA MOBILE SUBSTATION

132/11 kv, 25 MVA MOBILE SUBSTATION File name: Mob EN katalog1 Zagreb, 11.11.2014. Page: 1 od 9 Summary Mobile substation consists of two semitrailers. One trailer is for 132 kv equipment (HV equipment) and another trailer is for medium

More information

DPX 1600 Electronic release

DPX 1600 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

Steca Elektronik INVERTER / CHARGER WITH MPPT: SOLARIX PLI

Steca Elektronik INVERTER / CHARGER WITH MPPT: SOLARIX PLI Steca Elektronik INVERTER / CHARGER WITH MPPT: 5000-48 Inverter / Charger with MPPT charge controller All-in-one: 5 kw / 5 kva pure sine wave inverter (10 kw / 10 kva up to 5 s) 80 A MPPT charge controller

More information

designing and producing a wide range of railway power converters and devices since 1986 FOCUS ON TRANSPORT ELECTRONICA

designing and producing a wide range of railway power converters and devices since 1986 FOCUS ON TRANSPORT ELECTRONICA designing and producing a wide range of railway power converters and devices since 1986 FOCUS ON TRANSPORT ELECTRONICA TROLLEYBUS CATENARY SUPPLIED BATTERY CHARGER The trolleybus catenary supplied battery

More information

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS TABLE OF CONTENTS 1.0 - WARNINGS 2.0 - GENERAL DATA 2.1 - Technical characteristics 2.2 - Data on electrical

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series 10 20 30 40 kva 400 Vac CE Series 5 GE Consumer & Industrial SA General Electric Company CH

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work Digital Energy Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91

More information

Power Conversion Systems 2005/2006. Schaefer the Power to make it happen.

Power Conversion Systems 2005/2006. Schaefer the Power to make it happen. Power Conversion Systems 2005/2006 Schaefer the Power to make it happen. Company profile workforce experience customer orientation flexibility reliability Schaefer Elektronik, founded in 1969, has grown

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

Step 1: Collection of required data

Step 1: Collection of required data Step 1: Collection of required data If the relevant parameters of the interfaces are known, it is possible to dimension ASSEMBLIES 3 Installation and environmental conditions 4 Operating and servicing

More information

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications CHABOT-LAS POSITAS COMMUNITY COLLEGE DISTRICT New Panelboard for Lot H, EV Charger Energization, Las Positas College Scope of Work and Technical Specifications Chabot-Las Positas Community College District

More information

POWER SUPPLIES & RECTIFIERS

POWER SUPPLIES & RECTIFIERS POWER SUPPLIES & RECTIFIERS TRANSFORMER RECTIFIERS The simple design of a transformer rectifier makes it one of the most reliable and durable forms of power supply. Another advantage is the easy maintenance

More information

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS. SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS Róbert Riedlmajer TRNAVA 2007 Unit 14 - Fundamentals of power system protection

More information

PHOENIX CONTACT

PHOENIX CONTACT Current transformers INTERFACE Data sheet 03359_en_03 PHOENIX CONTACT 20-04-04 Description The PACT Analog current transformers form a complete range of bus-bar, plug-in and winding current transformers

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99 65-500 kva Full Two Year Warranty Three-Phase Double-Conversion On-Line Up to 98% Efficient n Lower energy costs and carbon footprint Compact & Reliable n Requires either front, top or bottom access, so

More information

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole MULTIBLOC 1.RST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC 1.RST8 comprises NH fuse switch disconnectors for 250A. Products are designed in triple

More information

ORION PLUS three-phase kVA

ORION PLUS three-phase kVA ORION PLUS three-phase 30-1250kVA Orion Plus stabilizers are available for different ranges of input voltage fluctuation. In the ±15%/ ±20% and ±25%/ ±30% types, the change of input range is obtained through

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33U Series / 10 20 30 40 50 60 kva 208 VAC UL Series 1 Date of issue: 11/05/2008 LPS33U_030-040_S1 GE_01

More information

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99 80-125 kva/kw E Three-Phase Double-Conversion On-Line Full Four Year Warranty www.stacoenergy.com Up to 99% Efficient n Lower energy costs and carbon footprint Compact & Reliable n Requires either front,

More information

ANNEX B TERMS OF REFERENCE FOR THE DESIGN OF A LOW VOLTAGE POWER NETWORK FOR IMS STATIONS IN WARRAMUNGA, AUSTRALIA

ANNEX B TERMS OF REFERENCE FOR THE DESIGN OF A LOW VOLTAGE POWER NETWORK FOR IMS STATIONS IN WARRAMUNGA, AUSTRALIA ANNEX B TERMS OF REFERENCE FOR THE DESIGN OF A LOW VOLTAGE POWER NETWORK FOR IMS STATIONS IN WARRAMUNGA, AUSTRALIA Page 1 of 9 Table of Contents 1 Introduction... 3 2 Background... 3 3 Work Tasks... 3

More information

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole MULTIBLOC 2.RST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC 2.RST8 comprises NH fuse switch disconnectors for 400A. Products are designed in triple

More information

BCI164C - Technical Data Sheet Winding 06

BCI164C - Technical Data Sheet Winding 06 - Technical Data Sheet Winding 06 SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Sheet No. Component /Detail

Sheet No. Component /Detail Sheet No. Component /Detail Description 1 Draw ing Guide MGE Galaxy 7000 200kVA 2MOD (N+1) 400V Integrated Parallel Module UPS Draw ing guide. 2-4 Solution MGE Galaxy 7000 200kVA 2MOD (N+1) 400V Integrated

More information

LCL FILTERS INSTRUCTIONS MANUAL (M A) (c) CIRCUTOR S.A.

LCL FILTERS INSTRUCTIONS MANUAL (M A) (c) CIRCUTOR S.A. LCL FILTERS INSTRUCTIONS MANUAL (M98121701-03-09A) (c) CIRCUTOR S.A. ------ LCL filters: Instructions Manual ----- Page 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 1 CHECKS ON RECEIPT OF THE EQUIPMENT. 3 2

More information

MULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole

MULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole MULTIBLOC 1.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 1.ST8 comprises NH fuse switch disconnectors for 250A. They are designed for bottom

More information

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet - Winding 06 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international

More information

AME. Rectifier - Battery charger. Industrial applications: Key features:

AME. Rectifier - Battery charger. Industrial applications: Key features: Rectifier - Battery charger AME VRLA batteries, flooded battery or Ni/Cd with output voltage from 24, 48, 110, 220 Vdc up to 150A Industrial applications: Oil&Gas (Petrochemicals Offshore, Onshore, Pipelines);

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet - Winding 05 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

Three-Phase Ventilated

Three-Phase Ventilated Three-Phase Ventilated 2 15 to 2,500 kva Applications n For general loads, including lighting, industrial and commercial applications Specifications n Meets DOE-2016 and C802 standards for energy efficiency

More information

Problems of power supply of the infrasound and seismic stations. The ways to solve them

Problems of power supply of the infrasound and seismic stations. The ways to solve them Problems of power supply of the infrasound and seismic stations. The ways to solve them Special Monitoring Service of Ministry of Defense of Russian Federation Alexander Tarasov 1. Unavailability data

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01

More information

INTRODUCTION ZONE CHARACTERISTICS SURGES

INTRODUCTION ZONE CHARACTERISTICS SURGES Surge Arrester INTRODUCTION Surge Arresters Safe and Reliable Protection for Electrical Equipment The Enerdoor surge arrester series has been specifically designed to protect electrical equipment. Surge

More information

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz GR24A-5 / -7 GR24A-5 Rotary actuator for rotary valves GR24A-7 Rotary actuator for rotary valves Nominal torque 40Nm Nominal voltage AC/DC 24V Control Open-close echnical data Electrical data Nominal voltage

More information

Application. Battery. Public Grid GS HYBRID INVERTER

Application. Battery. Public Grid GS HYBRID INVERTER GS HYBRID SOLAR INVERTER Feed from Solar and Power, Grid backup, Build-in Transfer Switch / Solar Charger/ AC Charger, 500W~3kW, Pure Sine Wave Output GSH-15XX and GSH-30XX are the ideal solutions for

More information

MULTIBLOC 2.ST8 Size 2, 400A, 690VAC, Design for Bottom Fitting, 3-,4-pole

MULTIBLOC 2.ST8 Size 2, 400A, 690VAC, Design for Bottom Fitting, 3-,4-pole MULTIBLOC 2.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 2.ST8 comprises NH fuse switch disconnectors for 400A. They are designed for bottom

More information

Solar inverter AX-series

Solar inverter AX-series Power Supplies Inverters Solar inverter AX-series 1-5kVA Multifunctional inverter NEU / NEW PV inverter PV / Battery Charger with 3-stage charge Battery-backed power supply Sine wave inverter with charging

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 60 80 100 120 kva PurePulse 400 Vac CE Series 1 SG-CE Series 100-120 kva PurePulse SG-CE Series

More information

PI144D - Technical Data Sheet

PI144D - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI144J - Technical Data Sheet

PI144J - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

2 Unit Petrol Engine Spare parts kits for 4 WD Nissan Patrol

2 Unit Petrol Engine Spare parts kits for 4 WD Nissan Patrol 04-62-70001 4 WD NISSAN PATROL STATION WAGON SGL, 4500 cc 2 Unit Petrol Engine 04-62-70002 Spare parts kits for 4 WD Nissan Patrol 4 Set Station Wagon 04-62-70003 Belt-Fan 11720-03J00 4 Each 04-62-70004

More information

Cast resin transformers

Cast resin transformers Product catalogue Cast resin transformers according to IEC/EN 60076, VDE 0532, DIN 42523 Power range up to 8 MVA Voltage range up to 36 kv Conductor material: copper or aluminum Protection types: IP 00

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

DPX 630 Electronic release

DPX 630 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

Pow-R-Line 3E Panelboard

Pow-R-Line 3E Panelboard This is a photographic template your photograph should fit precisely within this rectangle. Pow-R-Line 3E Panelboard 2008 Eaton Corporation. All rights reserved. Pow-R-Line 3E Panelboard Design guided

More information

Connecting sets CS-FS CS-FS123-WD. Connecting space covers OD-FS00-.. OD-FS123-KP. Adapter for parallel outlet - HP-SE/K

Connecting sets CS-FS CS-FS123-WD. Connecting space covers OD-FS00-.. OD-FS123-KP. Adapter for parallel outlet - HP-SE/K Varius SUMMARY OF MODELS OF FUSE-RAILS Type FSR00 FSR1 FSR2 FSR3 Rated operating current I e 160 A 250 A 400 A 630 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V Size 00 1 2 3 Busbar spacing

More information

ARCHITECTURAL DOOR HARDWARE POWER SUPPLIES & TRANSFORMER CATALOG

ARCHITECTURAL DOOR HARDWARE POWER SUPPLIES & TRANSFORMER CATALOG ARCHITECTURAL DOOR HARDWARE POWER SUPPLIES & TRANSFORMER CATALOG January 1, 2017 v3 West Coast Office (800) 544-4422 East Coast Office (800) 225-6737 intldoorclosers.com Index POWER SUPPLIES & TRANSFORMERS

More information

UCI224E - Winding 06. Technical Data Sheet APPROVED DOCUMENT

UCI224E - Winding 06. Technical Data Sheet APPROVED DOCUMENT - Winding 06 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as

More information

User Manual 1KVA-5KVA INVERTER / CHARGER

User Manual 1KVA-5KVA INVERTER / CHARGER User Manual 1KVA-5KVA INVERTER / CHARGER Version: 1.7 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

UCI274E - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

UCI274E - Winding 06 APPROVED DOCUMENT. Technical Data Sheet - Winding 06 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as

More information

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger User manual Solar Hybrid 1-5KVA Uninterruptible Power Supply / Charger All rights reserved. The information in this document is subject to change without notice. Thank you for purchasing this series UPS.

More information

User Manual 3KW/5KW INVERTER / CHARGER. Version: 1.0

User Manual 3KW/5KW INVERTER / CHARGER. Version: 1.0 User Manual 3KW/5KW INVERTER / CHARGER Version: 1.0 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

UCI224C - Winding 06. Technical Data Sheet APPROVED DOCUMENT

UCI224C - Winding 06. Technical Data Sheet APPROVED DOCUMENT UCI224C - Winding 06 Technical Data Sheet UCI224C SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international

More information

B BASIC HEAT TREATMENT CONSOLE

B BASIC HEAT TREATMENT CONSOLE Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91

More information

Photovoltaics. MPI Hybrid Series

Photovoltaics. MPI Hybrid Series Photovoltaics *Also support parallel feature to 3-phase feedback (3 units) MPI Hybrid Series These hybrid solar inverters combine the features of both grid-tied and off grid operations, and allow users

More information

TECHNICAL DATA SHEET KVA UPS Systemss

TECHNICAL DATA SHEET KVA UPS Systemss Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800

More information

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

DPX 630 Thermal magnetic and trip-free switches DPX-I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

Foreword

Foreword Foreword Content 1. Summary 2. Safety instruction Safety Symbol Indication Attention Static discharge sensitive Electric shock Dangerous Indicate risk of serious injury or death or seriously damage the

More information

MOULDED CASE CIRCUIT BREAKERS BH630N, BH630S

MOULDED CASE CIRCUIT BREAKERS BH630N, BH630S MOULDED CASE CIRCUIT BREAKERS BH6N, BH6S F BH6N, BH6S COMMERCIAL INFORMATION Switching units, withdrawable device, plug-in device...f4 Switch-disconnector unit...f6 Connecting sets...f7 Mounting sets...f9

More information

Power Supplies PSS Series

Power Supplies PSS Series 8 January 2009 PSS Supplies Product Description Eaton s of power supplies is designed to work in a variety of applications, including the power supply to the IT. line of power control products. They also

More information

Steca Solarix PLI. Inverter / Charger with Solar Charge Controller. Installation and operating instructions. Download manual at

Steca Solarix PLI. Inverter / Charger with Solar Charge Controller. Installation and operating instructions. Download manual at Inverter / Charger with Solar Charge Controller Steca Solarix PLI Installation and operating instructions GB Z03 18.20 Download manual at www.steca.com Table of Contents About this manual... 1 Purpose...

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TM SG Series 200-250 - 300 PurePulse CE S3 TM SG Series 160 PurePulse CE S3 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno)

More information

PI044D - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044D - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI144G - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144G - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI044H - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044H - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI044F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI044E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI144E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144E - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

PI144F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet

PI144F - Winding 311 Single Phase APPROVED DOCUMENT. Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000, VDE

More information

UCI274H - Technical Data Sheet Winding 06

UCI274H - Technical Data Sheet Winding 06 - Technical Data Sheet Winding 06 SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

User Manual. Axpert King 3.2KW/5.2KW 48V MPPT SOLAR INVERTER. Version: 1.0

User Manual. Axpert King 3.2KW/5.2KW 48V MPPT SOLAR INVERTER. Version: 1.0 User Manual Axpert King 3.2KW/5.2KW 48V MPPT SOLAR INVERTER Version: 1.0 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic

More information

BREAK-SAFE Load Break & Pick-up Tool

BREAK-SAFE Load Break & Pick-up Tool BREAK-SAFE Load Break & Pick-up Tool USBS-15-1-PS USBS-27-1-PS USBS-46-1-PS USBS-15-2-PS USBS-27-2-PS USBS-46-2-PS Available Options: H - Hard Case S - Soft Case Second Generation Models Only. For tools

More information

Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip

Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip Project Number: PAL -10-00063805 Project Name: Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip Bill of Quantities Package # 2 LOT 2: Supply of Electrical Materials The contract

More information

LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA

LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA LIEBERT APM 3-PHASE UPS: 15-90KVA/KW, 60HZ, 208-600VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA BYPASS DISTRIBUTION CABINET (Optional; see Note 7) The UPS must be fed from a solidly grounded wye or delta

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

un I Jet ИБП ABB Conceptpower DPA 500 ( квт) - технические спецификации. Юниджет

un I Jet ИБП ABB Conceptpower DPA 500 ( квт) - технические спецификации. Юниджет --------- l -' un I Jet, ИБП ABB Conceptpower DPA 500 (100-500 квт) - технические спецификации. Юниджет Постоянная ссылка на страницу: https://www.uni-jet.com/catalog/istochnikibesperebojnogo-pitaniya/on-line-ibp-100-kva/abb-conceptpower-dpa-series.html

More information

7. SERVICES OVER 600 VOLTS

7. SERVICES OVER 600 VOLTS 7. SERVICES OVER 600 VOLTS 7.1 GENERAL The Company shall always be consulted to obtain required design criteria where service is contemplated.preliminary plans of the Customer shall be submitted for review

More information

UCI224F - Technical Data Sheet

UCI224F - Technical Data Sheet UCI224F - Technical Data Sheet UCI224F SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Max. Input Power (W) Inrush Current (A pk /µs)

Max. Input Power (W) Inrush Current (A pk /µs) Output Power (W) Output Voltage (V) Output Current (A) Tcase Max 150 60~210 0.70 80 C Wiring Diagram Input Current 1.4A@120VAC 0.6A@277VAC 0.67A@250VDC Max. Input Power (W) Inrush Current (A pk /µs) Max.

More information

UCI274C - Technical Data Sheet Winding 06

UCI274C - Technical Data Sheet Winding 06 - Technical Data Sheet Winding 06 SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Item Code Description Unit Qty Total

Item Code Description Unit Qty Total UNDP ELECTRICITY SECTOR NORTHERN GOVERNORATES Phase XI Item Code Description Unit Qty Total 04-02-00001 Service Pole - 6m, 75mm dia GS Pipe 11250 04-02-00002 9m Tubular Steel Poles complete with all Accessories

More information

UCI274D - Technical Data Sheet

UCI274D - Technical Data Sheet UCI274D - Technical Data Sheet UCI274D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out) TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power

More information

UCI274D - Technical Data Sheet

UCI274D - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

UCI274G - Technical Data Sheet

UCI274G - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company imagination at work QUITO: Elia Liut N45-26 y Edmundo Chiriboga Telf:

More information

James Graham, P.E. Standards Coordinator Transformers Committee

James Graham, P.E. Standards Coordinator Transformers Committee James Graham, P.E. Standards Coordinator Transformers Committee Standards approved PARs approved Ballot Status PARs Status Standards Status NEW Standards approved PC57.13.7 REVISIONS approved - Standard

More information

Offshore and process industry Safety and Automation Systems (SAS) Marine Communication systems onboard ships. Railway & Metro infrastructure

Offshore and process industry Safety and Automation Systems (SAS) Marine Communication systems onboard ships. Railway & Metro infrastructure POWER SUPPLY SYSTEMS FOR HIGHER PROTECTION CLASS Our power supply systems offer a protection class up to IP 55. Together with our Industrial building blocks it is suitable for a variety of applications,

More information

UCDI274K - Technical Data Sheet

UCDI274K - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS5000,

More information