Delaware Electric Cooperative Generator Interconnection Application Long Form (For Use with Generators Greater than 25 kw)
|
|
- Rosaline Gregory
- 6 years ago
- Views:
Transcription
1 Generator Interconnection Application Long Form (For Use with Generators Greater than 25 kw) An applicant (Generator Owner) makes application to Delaware Electric Cooperative to install an operate a generating facility greater than 25kW interconnecte with the Delaware Electric Cooperative utility system. Section 1, Applicant Information Name: Mailing Aress: City: State: ZipCoe: Facility Location (if ifferent from above): Telephone (Daytime): Area Coe Number (Evening) Area Coe Number Delaware Electric Cooperative Account No.: Section 2, Generator Type Rate Coe: Is Generator powere from a Renewable Energy Source: No Type of Energy Source (if applicable): Solar Win Hyro Other generator energy source: Diesel, Natural Gas Diesel, Fuel Oil Other: Will excess power be exporte to Delaware Electric Cooperative? No Site Loa: kw (Typical) Maximum Export: kw. Section 3, Generator Technical Information Type of Generator: Synchronous Inuction DC Generator or Solar with Inverter Generator (or solar collector) Manufacturer, Moel Name & Number: (A copy of Generator Nameplate an Manufacturer s Specification Sheet may be substitute) Output Power Rating in kw: Inverter Manufacturer, Moel Name & Number (if use): (A copy of Inverter Nameplate an Manufacturer s Specification Sheet may be substitute) Rating in kw: Generator Characteristic Data (for rotating machines): (Not neee if Generator Nameplate an Manufacture s Specification Sheet is provie) Direct Axis Synchronous Reactance, X : P.U. Negative Sequence Reactance: P.U. Direct Axis Transient Reactance, X : P.U. Zero Sequence Reactance: P.U. Direct Axis Subtransient Reactance, X : P.U. KVA Base: Page 1
2 Section 4, Interconnecting Equipment Technical Data Will an interposing transformer be use between the generator an the point of interconnection? Transformer Data (if applicable, for Customer Owne Transformer): (A copy of transformer Nameplate an Manufacturer s Test Report may be substitute) No Size: KVA. Transformer Primary : Volts Delta Wye Wye Groune Transformer Seconary: Volts Delta Wye Wye Groune Transformer Impeance: % on KVA Base Transformer Fuse Data (if applicable, for Customer Owne Fuse): (Attach copy of fuse manufacturer s Minimum Melt & Total Clearing Time-Current Curves) Manufacturer: Type: Size: Spee: Interconnecting Circuit Breaker (if applicable): (A copy of breaker s Nameplate an Specification Sheet may be substitute) Manufacturer: Type: Loa Rating: Interrupting Rating: Trip Spee: (Amps) (Amps) (Cycles) Circuit Breaker Protective Relays (if applicable): (Enclose copy of any propose Time-Overcurrent Coorination Curves) Manufacturer: Type: Style/Catalog No.: Propose Setting: Current Transformer Data (if applicable): (Enclose copy of Manufacturer s Excitation & Ratio Correction Curves) Manufacturer: Type: Accuracy Class: Propose Ratio Connection: /5 Manufacturer: Type: Accuracy Class: Propose Ratio Connection: /5 Generator Disconnect Switch: A lockable isconnect evice shall be installe within 3 feet of the DEC meter an accessible at all times by DEC personnel, by an at the cost of the owner. Manufacturer: Type: Catalog No.: Rate Volts: Rate Amps: Single or 3 Phase: Mounting Location: Page 2
3 Section 5, General Technical Information Enclose copy of site One-Line Diagram showing configuration an interconnection of all equipment, current an potential circuits an protection an control schemes. Is One-Line Diagram Enclose?: Enclose copy of any site ocumentation that escribes an etails the operation of the protection an control schemes. Is Any Available Documentation Enclose?: Enclose copies of schematic rawings for all protection an control circuits, relay current circuits, relay potential circuits, an alarm/monitoring circuits. Are Schematic Drawings Enclose?: Section 6, PJM Interconnection Queue The Generator Owner must submit a Generation Interconnection Request irectly to PJM if: any Generation is esignate in whole or in part as a Capacity Resource to PJM or, if generator intens to sell output to another entity at another electrical location. Generation which is operating behin the meter in isolation from the PJM bulk power transmission system an which oes not inten to participate in the PJM wholesale energy market may not nee to apply to the PJM interconnection queue. PJM has sole iscretion on interconnection queue requirements. Prior to installation sen the complete Pages 1-3 to Delaware Electric Cooperative, Attn: Dave Shapley, Manager of Engineering: Phone: (302) FAX: (302) shapley@ecoop.com or mail to P.O. Box 600 Greenwoo, DE Section 7, Preliminary Approval to Procee with Interconnection Delaware Electric Cooperative: Has Approve Has Not Approve this Preliminary Application. Name : Date: Signature: Reason of Not Approving: Page 3
4 Section 8, Installation Details Generating System will be installe by: Owner State License Electrician Installing Electrician: Firm: License No.: Mailing Aress: City: State: Zip Coe: Telephone with Area Coe: Installation Date: Interconnection Date: Supply certification that the generating system has been installe an inspecte in compliance with the local Builing/Electrical coe of the municipality of Signe (Inspector): Date: (In lieu of signature of Inspector, a copy of the final inspection certificate may be attache) Section 9, Generator/Equipment Certification Generating systems that utilize inverter technology must be compliant with IEEE 1547 an Unerwriters Lab. UL Generating systems must be compliant with Delaware Electric Cooperative s Technical Requirements for Parallel Operation of Member Owne Generation ocument. The Applicant must certify that the installe generating equipment meets the appropriate preceing requirement(s) an can supply ocumentation that confirms compliance. Generation cannot be turne on until a Delaware Electric Cooperative representative has performe a site visit, installe a warning label near the service meter, an has authorize the system for interconnection. Section 10, Applicant Signature I hereby certify that, to the best of my knowlege, all the information provie in the Interconnection Application is true an correct. Signature of Applicant: Date: Page 4
5 (For Use with Generators Greater than 25 kw) This page for use by Delaware Electric Cooperative Only Section 11, Approval or Non-Approval Delaware Electric Cooperative: Has Approve Has Not Approve this Interconnection Application. Name : Date: Signature: Reason of Not Approving: Approval to connect to the Company system inicates only that the minimum requirements for a safe proper interconnection have been satisfie. Such approval oes not imply that the Generator Owner s facility meets all feeral, state an local stanars or regulations. Section 11, Internal Checks an Notifications DEC has performe a site visit an approve the system: DEC has installe a Warning Label on or near the service meter: Notify Billing Dept. of Interconnecte Generation: Notify Mapping Dept. of Interconnecte Generation: Notify Metering Dept. of Interconnecte Generation: Notify System Protection of Interconnecte Generation: At completion sen Pages 4-5 to Delaware Electric Cooperative, Attn: Dave Shapley, Manager of Engineering:Phone: (302) FAX: (302) shapley@ecoop.com or mail to P.O. Box 600 Greenwoo, DE Page 5
Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More informationPSNH INTERCONNECTION REQUEST
PSNH INTERCONNECTION REQUEST Send the completed Interconnection Request and required attachments to: Public Service of New Hampshire Attn: Michael Motta, Senior Engineer Supplemental Energy Sources P.
More informationNORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress
NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM ATTACHMENT 2 Utility: Duke Energy Progress Designated Utility Contact: Attention: Customer Owned Generation Mail Code ST13A E-Mail Address: Customerownedgeneration@duke-energy.com
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)
Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different
More informationMunicipality Generator Interconnection Application Single Meter Application Part I
Municipality Generator Interconnection Application Single Meter Application Part I New Application Revised Application A single customer interconnecting to a single meter at a single premise makes a new
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: City: Telephone (aytime):
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: Alternative Contact Information
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)
Section 466.APPENIX C Levels 2 to 4 Application Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less) Interconnection Customer Contact Information
More informationApplication for Interconnection and Net Metering Revision: 1 Revised: November 7, 2017
Net Metering Revision: 1 Revised: November 7, 2017 Net Metering Page 1 of 5 1 Net Metering This Application and Agreement is considered complete when it provides all applicable and correct information
More informationGENERATOR INTERCONNECTION APPLICATION
GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW Also Serves as Application for Category 3 Net Metering (Note:
More informationSOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board
SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board Policy Description: In an effort to ensure fair treatment of all of its customers,
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationCATEGORY 2 GENERATOR INTERCONNECTION APPLICATION
CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering
More informationCUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)
GENERATOR INTERCONNECTION APPLICATION Category 2 (Combined) For All Projects with Aggregate Generator Output of More Than 20 kw but Less Than or Equal to 150 kw Also Serves as Application for Category
More informationTERMS AND CONDITIONS
XXV. NET METERING A. Applicability and Availability 1. The terms Net Metering Service, Demand Charge-based Time-of- Use Tariff, Net Metering Customer, Customer, Time-of-Use Customer, Time-of-Use Tier,
More informationElectric Utility Contact Information Indiana Michigan Power
CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering
More informationApplication for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _
Application for Operation of & Net Metering for Member-Owned Generation -------------- OWNER/APPLICANT INFORMATION Name: Mailing Address: City: County: State: Zip Code: _ Phone Number: Email Address:.Representative:
More informationRider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION
SAMPLE ORDINANCE 3/5/2012 Rider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION Section 1: Applicable Service Territory Net metering and electrical system interconnection is available on a first-come,
More informationEnquiry Form (Non-Registered Generator With Capacity less than 5 MW)
Connection Applicant (Embedded Generating Unit Owner/Proponent) Business name: ABN: Contact name: Address: Telephone number: E-mail address: Connection Applicant acting and working on behalf of the above
More informationDocument Requirements for Engineering Review- PV Systems v1.1 12/6/2018
Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)
More informationColumbia Water & Light Interconnection & Net Metering Agreement Electrical Facility
Processed Date Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Customer s Printed Name Installation Street Address Account Number Please note: Columbia Water & Light
More informationNet Metering Service. Customer Information Package
Net Metering Service Customer Information Package March 20, 2017 Net Metering - The means of measuring the difference between the electricity supplied by an electric utility and the electricity generated
More informationREQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw
REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used
More informationSection 6. Generation Interconnection
Table of Contents Section 6 Generation Interconnection A. Customer-Owned Generation... 6-3 B. Net Metered Generation... 6-4 C. Standby Generation Connections to the District's System... 6-6 D. Closed Transition
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationForm C Renewable Energy Micro-Generation Connection Application Distribution System
Form C Renewable Energy Micro-Generation Connection Application Distribution System (Micro-Generation Facilities 10 kw total nameplate capacity) This form is applicable to single or multiple generating
More informationDecember 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff.
JERSEY CENTRAL POWER & LIGHT UNIFORM TECHNICAL AND PROCEDURAL INTERCONNECTION REQUIREMENTS FOR NET METERING FACILITIES FOR INVERTER BASED WIND AND PHOTOVOLTAIC SYSTEMS OF 100 kw OR SMALLER for Atlantic
More informationIf any further information is required for CHELCO to fulfill its reporting requirements, please let us know.
c o January 20, 2009 l'v1a rk Futrell Public Utility Supervisor Florida Public Service Commission 2540 Shumard Oak Boulevard Tallahassee, Florida 32399-0850 Dear Mr. Futrell, The documents accompanying
More informationAPPLICATION ELECTRICITY SERVICES. APPLICATION FOR THE CONNECTION OF SMALL SCALE EMBEDDED GENERATION Page 1
APPENDIX 2B APPLICATION ELECTRICITY SERVICES APPLICATION FOR THE CONNECTION OF SMALL SCALE EMBEDDED GENERATION Page 1 This application form for the connection of small scale embedded generation is for
More informationRENEWABLE ENERGY PROGRAM Step 1, Section 1 ENROLLMENT FORM FOR LEASED RESIDENTIAL AND SMALL COMMERCIAL PHOTOVOLTAIC AND WIND TURBINE SYSTEMS
RENEWABLE ENERGY PROGRAM Step 1, Section 1 ENROLLMENT FORM FOR LEASED RESIDENTIAL AND SMALL COMMERCIAL PHOTOVOLTAIC AND WIND TURBINE SYSTEMS For residential and commercial systems, the combined generation
More informationBulletin Interconnection of electric power production sources Rules 2-010, , , , , , and
Bulletin 84-1-11 Interconnection of electric power production sources Rules 2-010, 64-078, 64-110, 84-004, 84-008, 84-018, 84-022 and 84-030 Scope Issued May 2018 Supersedes Bulletin 84-1-10 1) Requirements
More informationKAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING
Third Revised Sheet 55a Cancels Second Revised Sheet 55a A. ELIGIBLE CUSTOMER-GENERATOR RULE NO. 17 NET ENERGY METERING Net energy metering is available to eligible customer-generators, defined as, permanent
More informationINTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY
INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application
More informationCHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER
RS-N SECOND REVISED SHEET NO. 8.2.1 CANCELLING FIRST SHEET NO. 8.2.1 NAME OF UTILITY CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER DEFINITION Net Metering means calculating
More informationDominion Energy Instructional Guide for Completing Virginia Form NMIN
Complete Sections 1 through 4, sign the form at the bottom, and submit to Dominion Energy either by scanning and e-mailing to net.metering@dominionenergy.com, or send by US Mail to Dominion Energy, Net
More informationInstructions for Completing Oncor s Interconnection Application For Solar PV Projects
Instructions for Completing Oncor s Interconnection Application For Solar PV Projects Program Year 2009 Take a Load Off, Texas SM is provided by Oncor Electric Delivery LLC as part of the company s commitment
More informationNew Hampshire Electric Cooperative (NHEC) Introduction to Net Metering
New Hampshire Electric Cooperative (NHEC) Introduction to Net Metering NHEC supports the development of member-sited renewable energy generation and storage facilities (referred to herein as an interconnection
More informationGENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview
Part 1 Introduction and Overview A. Applicability: This Generating Facility Interconnection Application (Application) is used to request the interconnection of a Generating Facility to Southern California
More informationAPPLICATION Net Energy Metering Interconnection For Solar And/Or Wind Electric Generating Facilities Of 30 Kilowatts Or Less
IMPORTANT NOTES: Customers may not operate their Generating Facility while interconnected to the PG&E system until they receive written permission from PG&E. For a non-exporting Generating Facility, RES-BCT
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationTo complete the process for a net metering interconnection, please follow the steps below:
We appreciate your interest in Rocky Mountain Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system
More informationAPPLICATION Net Energy Metering (NEM2) Interconnection For Solar And/Or Wind Electric Generating Facilities Of 30 Kilowatts Or Less
IMPORTANT NOTES: Customers may not operate their Generating Facility while interconnected to the PG&E system until they receive written permission from PG&E. For a non-exporting Generating Facility, RES-BCT
More informationDISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase
PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION:
More informationForm G5-1 PACIFIC GAS AND ELECTRIC COMPANY GENERATION PRE-PARALLEL INSPECTION
Form G5-1 Page 1 of 3 PACIFIC GAS AND ELECTRIC COMPANY PG&E LOG WO/GM D&C Name of Project: Location: Transmission Line No. Distance Circuit No. 1. Maintenance Data: Generation Customer s Maintenance Chief
More informationLouisville Gas and Electric Company
P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer
More informationLouisiana Net Metering Service. Customer Information Package
Louisiana Net Metering Service Customer Information Package August 1, 2013 Net Metering - The means of measuring the difference between the electricity supplied by an electric utility and the electricity
More informationGENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview
Part 1 Introduction and Overview A. Applicability: This Generating Facility Interconnection Application (Application) is used to request the interconnection of a Generating Facility to Southern California
More informationRequest for Payment Instructions form. Rule 21 Non-Exporting Generators Submittal Instructions
Grid Interconnection & Contract Development Request for Payment Instructions Rule 21 Non-Exporting Generators Submittal Instructions Prior to submitting your application and fee or deposit, please complete
More informationTILLAMOOK PEOPLE S UTILITY DISTRICT
TILLAMOOK PEOPLE S UTILITY DISTRICT DISTRIBUTION INTERCONNECTION PROCEDURE Inverter Based Generators 25 kw and Smaller This document contains the interconnection requirements for inverter based generators,
More informationOncor Application for Interconnection of Distributed Generation
Oncor Application for Interconnection of Distributed Generation Certified Systems (12/7/2017) What is a certified system? A certified system is one that meets the requirements of UL-1741 Utility Interactive
More informationLondon Hydro Connection Checklist
London Hydro Connection Checklist Applicants should be aware not to incur expenses prior to London Hydro approving the connection of the facility to the grid. Payment of Connection Fee: $1000 plus HST
More information40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power
40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect
More informationNet Metering Interconnection Requirements
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland
More informationApplication for Commission Approval to Construct a Generating Station Pursuant to Public Utilities Article Section and
Application for Commission Approval to Construct a Generating Station Pursuant to Public Utilities Article Section 7-207.1 and 7-207.2 APPLICABILITY The Public Service Commission of Maryland ( Commission
More information3. Customer shall provide space for metering equipment and meter base as per Springville City Power requirements.
A. General This Customer-Owned Generation Standards for Customer-Owned Grid Connected Electric Generating Systems sets forth the requirements and conditions for interconnected non-utility-owned electric
More informationSolar*Rewards Community Engineering Frequently Asked Questions For Garden Operators Minnesota
P a g e 1 Solar*Rewards Community Engineering Frequently Asked Questions For Garden Operators Minnesota The purpose of this document is to provide Garden Operators further documentation of engineering
More informationSmall Generator Interconnection Program Interconnection Technical Requirements
General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator
More informationTo complete the process for a net metering interconnection, please follow the steps below:
We appreciate your interest in Pacific Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system to
More informationSolar Power Installation Application
Solar Power Installation Application This Form must be filled out and submitted to Logan City Light and Power Department and given authorization to proceed PRIOR to installing a solar system. Also, please
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationNet Metering Program
Net Metering Program Chapter 1 Purpose and Scope. The purpose of this chapter is to establish rules for determining the terms and conditions governing the interconnection of electric generation facilities
More informationAPPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION
APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION Work Order No: File Reference: 16/2/1 This application form for the connection of small scale embedded generation is for small
More informationRenewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group
Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group Table of Contents 1. Introduction... 1 2. Purpose... 1 3. Customer Eligibility...
More informationNew Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities
New Ulm Public Utilities Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities INDEX Document Review and History... 2 Definitions... 3 Overview... 3 Application
More informationDistributed Generation Interconnection Policy
Distributed Generation Interconnection Policy 1 Introduction Carroll Electric Membership Corporation Distributed Generation Interconnection Policy Carroll Electric Membership Corporation (herein after
More informationNEW HAMPSHIRE ELECTRIC COOPERATIVE S (NHEC) ABOVE THE CAP NET METERING INTERCONNECTION APPLICATION INFORMATION
NEW HAMPSHIRE ELECTRIC COOPERATIVE S (NHEC) ABOVE THE CAP NET METERING INTERCONNECTION APPLICATION INFORMATION Dear NHEC Member: Thank you for inquiring about New Hampshire Electric Cooperative s Net Metering
More informationRenewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group
Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group Table of Contents 1. Introduction... 1 2. Purpose... 1 3. Customer Eligibility...
More informationNET METERING APPLICATION
NET METERING APPLICATION This form must be filled out completely and submitted to the City of Geneva Electric Division before a customer s renewable energy facility can be interconnected with City s distribution
More informationDocument Requirements for Engineering Review PV Systems v1.0 6/9/2017
Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection
More informationMicro-Generation Connection Application For Connection of Micro-Generation Facilities of 10 kw
This form is applicable to individual or multiple generating units at the Customer s facility with total nameplate rating of 10 kw or less. Your generation facility must generate electricity from a renewable
More informationBackup Generation Application
Backup Generation Application For connection of non-parallel generation between Menard Electric Cooperative s Electric system and standby generation that will operate with a manual or automatic transfer
More informationWest Virginia Net Metering Service. Customer Information Package
West Virginia Net Metering Service Customer Information Package Net Metering - The means of measuring the difference between the electricity supplied by an electric utility and the electricity generated
More informationRequest for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP
Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and
More informationSouthern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management
Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements
More informationExelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less
Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less Original: October 31, 2006 Table of Contents: INTRODUCTION and SCOPE... 3 DEFINITIONS... 3 QUALIFICATIONS FOR AN EXPEDITED
More informationNortheastern Rural Electric Membership Corporation Columbia City, Indiana
Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),
More informationINTERCONNECTION for GENERATING FACILITIES Up to 20 MW
PROGRAM REQUIREMENTS Important Information from Your Local Non-Profit Utility INTERCONNECTION for GENERATING FACILITIES Up to 20 MW Interconnecting to the Electrical Distribution System of Public Utility
More informationNET METER REQUEST FORM
Form No. 3651 02/17 NET METER REQUEST FORM In order to receive a Net Meter, please provide the information requested below, sign and return only this coversheet by mail to the address below. NorthWestern
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationCustomer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone Number:
Please print the following information. Interconnect Customer Information Customer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone
More informationUmatilla Electric Cooperative Net Metering Rules
Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through
More informationNoble County Rural Electric Membership Corporation
Albion, Indiana Page 1 of 7 SCHEDULE LPDG-1 LARGE POWER AND COMMERCIAL MEMBER-OWNED GENERATION I. AVAILABILITY This Generation rate is available to any member in good standing of Noble REMC (Noble) who
More informationSANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT
SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT This Net Metering and Interconnection Agreement ( Agreement ) is made and entered into as of this day of, 2018, by the City of Santa
More informationTECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008
NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0
More informationRULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES
RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES Last Revised Date: October 15, 2015 Contents Chapter 1 - Purpose and Scope 2 Chapter 2 - Application of Rules 2 Chapter 3 - Definitions
More informationSummary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System
Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System This document is intended to be a general overview of PG&E s current technical
More informationINTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS
INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS TABLE OF CONTENTS Purpose and Scope...2 Authority...2 Applicability... 2 Intent.. 2 Maximum Connected Generation Allowed. 2 Definitions.
More informationInformation Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program
Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program As part of our commitment to support renewable energy, Kissimmee Utility Authority
More informationTECHNICAL REQUIREMENTS FOR PARALLEL OPERATION OF MEMBER-OWNED GENERATION
TECHNICAL REQUIREMENTS FOR PARALLEL OPERATION OF MEMBER-OWNED GENERATION EFFECTIVE JANUARY 27, 2014 TECHNICAL CONSIDERATIONS COVERING PARALLEL OPERATIONS OF CUSTOMER OWNED GENERATION INTERCONNECTED WITH
More informationACTION FORM. EXHIBIT #1 Regular Council Meeting of 11/27/2006
EHIBIT #1 Regular Council Meeting of 11/27/2006 PROCEEDING: Utility Committee ACTION FORM AGENDA ITEM NO.: 11/13/06 1A DEPARTMENT OF ORIGIN: Public Utilities - Electric DATE SUBMITTED: 10-26-06 PREPARED
More informationINTERCONNECTION REQUIREMENTS POLICY
Issue Date: January 8, 2018 Resolution No. 2097-18 INTERCONNECTION REQUIREMENTS POLICY 1. Purpose and Scope A. The purpose of these Interconnection Requirements is to establish rules for determining the
More informationOptimizing Emergency Power Systems for Health Care Applications
2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan
More informationCHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.
25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements
More informationOverview of State Distributed Generation Interconnection Rules
Overview of State Distributed Generation Interconnection Rules Presentation to EPA CHP Webinar Series June 26, 2008 Wayne Shirley Director The Regulatory Assistance Project 50 State Street, Suite 3 Montpelier,
More informationPolicy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620
Policy Bulletin No. 25 Net Metering Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Interconnection Standards For Residential Net Energy Metering With Electric
More informationTaxicab and Vehicle for Hire- New Driver Packet
Taxicab and Vehicle for Hire- New Driver Packet Lee County Board of County Commissioners, Lee County Municipalities, and the Lee County Tax Collector have worked together to revise the existing county
More informationARKANSAS PUBLIC SERVICE COMMISSION
Original 52.1 Schedule Sheet 1 of 36 TABLE OF CONTENTS Tariff Provisions... 52.1 Preliminary Interconnection Site Review Request... 52.4 Standard Information... 52.4 Terms and Conditions... 52.5 Standard
More informationTo complete the process for a net metering interconnection, please follow the steps below:
We appreciate your interest in Pacific Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system to
More informationRequest for Payment Instructions Rule 21 Non-Exporting Generators Submittal Instructions
Grid Interconnection & Contract Development Request for Payment Instructions Rule 21 Non-Exporting Generators Submittal Instructions Prior to submitting your application and fee or deposit, please complete
More information