Instruction/Guidelines regarding rooftop solar PV Grid interactive systems and Net metering.

Size: px
Start display at page:

Download "Instruction/Guidelines regarding rooftop solar PV Grid interactive systems and Net metering."

Transcription

1 Jharkhand Bijli Vitran Nigam Limited (CIN:U40108JH2013SGC001702) Regd. Office : Engineering Building, H.E.C., Dhurwa, Ranchi , -coml.rev@rediffmail.com Telephone: & Fax: Draft Letter no. 677 Date To, All General Manager-cum-Chief Engineer, All Electric Supply Area. All Electrical Superintending Engineer All Electric Supply Circle Sub: Instruction/Guidelines regarding rooftop solar PV Grid interactive systems and Net metering. In compliance to JSERC (rooftop solar PV) regulations 2015 notified by Gazette 20 th January, 2016 for increasing solar power generation to harness vast solar potential in the State, JBVNL is pleased to formulate instructions on Net metering for Grid interactive rooftop solar photo voltaic power plants. The salient features of the policy are detailed below:- All the consumers of the JBVNL who intend to setup rooftop solar PV plants in their premises shall be eligible to do so with project capacity ranging from minimum 1 kwp upto 1MWp (AC side). Third party owned solar PV plant system where developers or intermediaries or turnkey installers who lease rooftop systems to individual owners and the owners in turn, pay them monthly lease rental shall also be eligible. In case of third party on solar PV Plant the arrangement i.e. signing of and agreement for lease of rooftop system between Rooftop owner and developer or intermediary or turnkey installer will be personal to them. For all intent and purposes, JBVNL will deal with the consumer only, in case of Net-metering. The maximum peak capacity of the grid connected rooftop solar PV system to be installed by any eligible consumer shall not exceed 100% of the sanctioned load / contract demand of the consumer and shall be more than one kilo watt peak minimum. The capacity to be allowed in the area fed from the distribution transformer or any other transformer from which power is fed to the eligible consumer shall not exceed 15% of the rated capacity of such transformer(s). 1. Procedure/salient features I. The eligible consumer or third party owner hereinafter referred to as applicant who intends to install grid interactive rooftop solar PV system in his/her premises shall apply in the application form at Annexure- I along with the application fees as specified in Annexure-II. Consumers shall submit the application to the concerned Electric Supply Sub-Division along with a copy to JREDA officer in the district.

2 II. AEE of the concerned Sub-Division will prepare the feasibility report in the form of Annexure-III, with approval from the competent authority as per table I. After checking the feasibility the concerned AEE shall issue approval letter to the feasibility cleared applicant within 30 days of receipt of application. (Annexure-IV, letter of approval). TABLE I Connected Load/Contract Demand of Eligible Consumer Connectivity Level Competent Authority to check the feasibility Upto 5 kw Single Phase at 230 V AEE/Supply 5 kw and above up to 50 3 Phase, 4 Wire at 415 V EEE/Supply kw/ 67 HP Above 50 kw and up to 1 MW 3 Phase at 6.6 kv or 11 kv ESE/Supply III. AEE of concerned sub-divn shall issue approval letter to the feasibility cleared applicant within 30 days of receipt of application (Annexure - IV). IV. The consumer shall set up the plant and submit the work completion report along with Single Line Diagram of the synchronizing and protection arrangement issued by the plant supplier/epc contractor within 180 days envisaging that the plant has been installed as per the approved standards and specifications as per Annexure- VII. In case of delay, the consumer shall have to get further extension from JBVNL within original (180 days) allowed period. Such extension shall be granted for a maximum period of 2-months only and the approval granted shall lapse automatically if the project is not set-up even in the extended 2- months period and the fee deposited by the consumer shall be forfeited. Such consumer shall have to apply afresh. V. Competent authority to approve the single line diagram, protection arrangements and site verification of the solar plant to be set up by the consumer shall be as per the table I. VI. After approval of Rooftop Solar PV System by the competent authority as above, the applicant shall apply for registration of the scheme for rooftop solar PV system by completing the registration form provided at Annexure-V of this circular, along with the registration fees as specified in Annexure-II of this circular. JBVNL shall install and seal the Bi-directional or unidirectional or both energy meter(s) as required (as per ESIM Clause 53) within 10 days of the submission of work completion report and shall be treated as commissioned for commercial operations from that date for net-metering. VII. For the applicant who has applied under the net metering scheme the inter connection agreement provided at Annexure-VI of this circular shall be executed

3 by the JBVNL within thirty (30) days of issue of Registration number to the eligible applicant. 2. Metering All the meters shall adhere to the standards and provisions specified in CEA (Installation and Operation of Meters), Regulations, 2006 and subsequent amendments thereof. The appropriate meter(s) shall be single phase or three phase as per requirement. All the meters to be installed shall be of the same or better Accuracy Class Index than the existing meter installed at the premises. The appropriate meter(s) at the premises of the consumer shall be procured, installed and maintained by the JBVNL at the cost of the eligible consumer. However if the eligible consumer wishes to procure the appropriate Meter(s), he may procure such meter(s) and present the same to the JBVNL for testing and installation. The location of appropriate meter(s) shall be in accordance with the CEA (Installation and Operation of Meters), Regulations, 2006 as amendments from time to time and the JSERC (Electricity Supply Code) Regulations, 2005 as amendments from time to time. The installation of check meters shall be mandatory for rooftop solar PV system having rated capacity more than 50 kwp. The charges for testing, installation and maintenance of the check meter shall be borne by the eligible consumer. The JBVNL shall own the check meter. For installations having rated capacity up to 50 kwp, the eligible consumer or the JBVNL who so ever if desires, may install check meter at their own cost. The JBVNL shall own the check meter. The check meter shall be installed after the inverter of the solar rooftop system. The specification and standards of the check meter shall be same as or better than the consumer meter installed at the premises of the eligible consumer. All the meters installed shall be jointly inspected and sealed on behalf of both the parties. Provided that the meter reading taken by the JBVNL shall be the basis of commercial settlement. 3. Energy Accounting and Settlement Meter readings shall be taken as per the applicable cycle as provided in the JSERC (Electricity Supply Code) Regulations 2005 and subsequent amendments thereof; The energy accounting and settlement procedure for consumers installing and operating rooftop solar PV system under net metering arrangement shall be as per the following procedure: i. For each billing period, the Licensee shall show the quantum of electricity injected by the rooftop solar PV system in the billing period, supplied

4 electricity by JBVNL in the billing period, net billed electricity for payment by the consumer for that billing period and net carried over electricity to the next billing period separately; ii. If the electricity injected exceeds the electricity consumed during the billing period, such excess injected electricity shall be carried forward to next billing period as electricity credit and may be utilized to net electricity injected or consumed in future billing periods but within the settlement period; iii. If the electricity supplied by the JBVNL during any billing period exceeds the electricity generated by the eligible consumer s rooftop solar PV system, the JBVNL shall raise invoice for the net electricity consumption after taking into account any electricity credit balance remaining from previous billing periods; Provided, in case the eligible customer is under the ambit of time of day tariff, as determined by the Commission from time to time, the electricity consumption in any time block (e.g., peak hours, off-peak hours, etc.) shall be first compensated with the electricity generation in the same time block. Any excess generation over consumption in any time block in a billing cycle shall be carried forward to the corresponding time block in the subsequent month for adjustment purpose. iv. Provided also that the excess electricity measured in kilo-watt hour may only be utilized to offset the consumption measured in kilo-watt hour and may not be utilized to compensate any other fee and charges imposed by the JBVNL as per the instructions of Commission. v. Provided also at the end of each settlement period, any electricity credits, which remain unadjusted, shall be paid at a rate of Rs 0.50/kWh by the JBVNL or as notified by the Commission from time to time. vi. Provide further that at the beginning of each settlement period, cumulative carried over electricity credits shall be reset to zero. vii. When an eligible consumer leaves the system, that consumers unused electricity credits shall be paid at a rate of Rs 0.50/kWh by the JBVNL or as notified by the Commission from time to time. viii. Regardless of availability of electricity credits with the eligible consumer during any billing period, the consumer shall continue to pay applicable charges such as fixed/ demand charges, Government levy etc. viv. The JBVNL shall necessarily provide the following details along with the electricity bill relating to each billing period: a) Quantum of electricity generated from the rooftop solar PV system. b) Quantum of electricity injected into the distribution system by the rooftop solar PV system. c) Quantum of electricity supplied by the JBVNL to the eligible consumer. d) Quantum of net electricity that has been billed for payment by the eligible consumer.

5 e) Quantum of electricity credits available to the eligible consumer which is carried over from the previous billing period. f) Quantum of electricity injected into the distribution system in excess of the drawl by the eligible consumer (quantum of electricity credits) which shall be carried forward to the next billing period. In case of any dispute in billing it would be settled by the Consumer Grievance Redressal Forum and if issue still remains unresolved, it shall be settled by the Ombudsman following appropriate procedure. APPLICABILITY OF OTHER CHARGES In rooftop solar PV system under net metering scheme, whether self-owned or third party owned and installed on eligible consumer premises shall be exempted from wheeling and cross subsidy surcharge. All charges on net electricity consumed in case of Net metering from JBVNL shall be leviable as usual. All the instructions rules and regulations applicable to the consumers of the JBVNL for the applicable class/category including but not limited to the tariff rates, payment schedule, late payment surcharge, connected load / contracted demand, load surcharge, peak load restrictions, security Consumption Deposit etc., shall also be applicable to the Roof Top Solar plant owner as a consumer of JBVNL. This has got the approval of competent authority. Note: These instructions / guidelines shall be read with provisions of JSERC Regulation 2015 for Rooftop Solar PV Grid Interactive System and Net/ Gross Metering and in case of any inconsistency the provision of Regulation shall prevail. Sd/- Chief Engineer (Commercial & Revenue) JBVNL, Ranchi

6 Annexure-I APPLICATION FOR INTENT TO SEEK CONNECTIVITY OF ROOFTOP SOLAR PV SYSTYEM 1. Name Full Address of Consumer Applicant 2. Consumer No. (CA.NO.) (Owner of the premises) 3. Category (Domestic / Non Domestic / Commercial etc. specify) (Owner of the premises) 4. Telephone No Res: Mob: 5. address 6. Sanctioned Load 7. Capacity of Rooftop Solar PV System proposed to be connected 8. Whether the Consumer is under ToD billing system (Owner of the premises) 9. Whether the Consumer or third party owner shall avail accelerated depreciation benefits on the Rooftop Solar PV system 10. Type of Rooftop Solar PV System proposed (Net Metering) 11. Location and address of Proposed Rooftop Solar PV System (rooftop, ground, any other specify) 12. Preferred mode of Communication (Post/By Hand/Electronic etc. specify) Yes/No Yes/No Place: Signature of Eligible Consumer/Third Party owner

7 ACKNOWLEDGEMENT Application Number. Received the application for connectivity of Rooftop Solar PV System Name: Consumer No.: Date..., Time, Serial No. Application Fee Paid or Not: Rooftop Solar PV Plant Capacity:. Mode of payment (Cheque / DD / RTGS / NEFT):.. Details of Cheque / DD / RTGS / NEFT:.. Name of Officer Signature (Designation of Officer) (To be specified at the time of signing)

8 Annexure-II APPLICATION FEES Sl. No. Connected Load / Contract Demand of Eligible Consumer Amount 1. Up to 50 kw / 63 kva Rs Above 50 kw and up to 1 MW Rs. 750 The amount of application fee for eligible consumer and third party other than the owner of the premises shall be the amount mentioned above. REGISTRATION FEES Sl. No. Connected Load / Contract Demand of Eligible Consumer Amount 1. Up to 50 kw / 63 kva Rs Above 50 kw and up to 1 MW Rs The amount of registration fee for eligible consumer and third party other than the owner of the premises shall be the amount mentioned above.

9 Annexure-III TECHNICAL DATA FORM FOR FEASIBILITY CLEARANCE OF ROOF TOP SPV POWER PLAN (To be filled by JEE/AEE/Area Incharge) 1. Name of Consumer: 2. Name of Address/Location: 3. Contact No. and ID: 4. Consumer No.: 5. Application No: 6. Name of Sub-Division : 7. Name of Division: 8. Name of Circle: 9. Sanctioned load / CD of Consumer with category and supply voltage 10. Capacity of proposed SPVPP (in kw): 11. Name /Location of feeding Transformer: (i) (ii) Capacity of above Transformer: Connected Load (kva) on the Transformer: (iii) Maximum Demand in Amps: (iv) No. of LT Ckts. : 12. Length of LT Feeder: (i) Size of conductor (sq. mm) (ii) Maximum Demand in Amps 13. Name of feeder: (i) Size of Conductor / Capacity 14. Name of feeding Sub-Station: 15. SPVPPs already connected on this Distribution Transformer (in kw/kva): 16. Senior pending SPVPPs to be connected on the T/F: 17. Capacity of proposed SPVPP on this T/F (in kw/kva): (As per column no. 6.2 of PSERC Notification) 18. Total load on this T/F (in kw/kva) = Sum total of columns ( ): (It should not be more than 15% of the T/F Capacity 19. Recommendation of Field Office: (Whether capacity of SPVPP as per column 9 approved or not, if approved mention the approved capacity, if not assign the reasons) Date:

10 Signature of Authorized Officer Signature of JBVNL Official Annexure-IV Letter of Approval To Mr. / Ms. / M/s Consumer No Memo No Dated:.. Ref: Your request of Application No.. Your request for installing Rooftop PV system for kwp capacity is considered and approval is accorded with the following conditions: - 1. You shall set up the plant and submit the work completion report along with Single Line Diagram of the synchronizing and protection arrangement issued by the approved plant supplier/epc contractor that the plant has been installed as per approved standards and specifications within 180 days. In case of delay you shall have to get further extension from JBVNL. Such extension will be granted for a maximum period of 2-months only and the approval granted will lapse automatically if the project is not set-up even in the extended 2-months period. However, you will be eligible to apply in the next financial year but your application will be kept at the bottom of the list of applicants and you will be permitted to set-up the plant only if all the applicants above you are selected and there is still capacity available for allotment. 2. You will abide by the guidelines for Grid Interactive Rooftop Solar Photo Voltaic Power Plants issued by Govt. of Jharkhand/JSERC/ JBVNL/JREDA. 3. The solar plant shall comply with the relevant standards specified by the MNRE / BIS and CEA. The responsibility of operation and maintenance of the solar photo voltaic (SPV) generator including all accessories and apparatus lies with the consumer. The design and installation of the rooftop SPV should be equipped with appropriately rated protective devices to sense any abnormality in the system and carry out automatic isolation of the SPV from the grid. The inverters used should meet the necessary quality requirements and should be certified for their quality by appropriate authority; the protection logic should be tested before commissioning of the plant. 4. The automatic isolation or islanding protection of SPV should be ensured for, no grid supply and low or over voltage conditions and within the required response time. Adequate rated fuses and fast acting circuit breakers on input and output side of the inverters and disconnect/isolating switches to isolate DC and AC system for maintenance shall be provided. The consumer should provide for all internal safety and protective mechanism for earthing, surge, DC ground fault, transients etc. To prevent back feeding and possible accidents when maintenance works are carried out by JBVNL personnel, Double pole / Triple pole with neutral isolation disconnection switches which ever applicable can be locked by JBVNL personnel should be

11 provided. This is in addition to automatic sensing and isolating on grid supply failure etc and in addition to internal disconnection switches. In the event of JBVNL LT/HT supply failure, the consumer has to ensure that there will not be any solar power being fed to the LT/HT grid of JBVNL. You will be solely responsible for any accident to human beings/animals whatsoever (fatal/non) fatal/departmental/non departmental) that may occur due to back feeding from SPV plant when the grid supply is off. JBVNL have the right to disconnect the rooftop solar system at any time in the event of possible threat/damage, from such rooftop solar system to its distribution system, to prevent any accident or damage, without any notice. You shall abide by all the codes and regulations issued by the Commission to the extent applicable and in force from time to time and shall comply with JSERC/JBVNL/CEA requirements with respect safe, secure and reliable functioning of the SPV plant and the grid. The power injected into the grid shall be of the required quality in respect of wave shape, frequency, absence of DC components etc. The inverter standard shall be such that it should not allow solar power / battery power to extend to JBVNL s Grid on failure of JBVNL s Grid supply irrespective of connectivity options. You shall restrict the harmonic generation within the limit specified in IEEE 519 or as may be specified by the Central Electricity Authority. AEE/Supply Sub Division JBVNL.

12 Annexure-V APPLICATION FOR REGISTRATION OF THE SCHEME FOR ROOFTOP SOLAR SYSTEM 1. Name 2. Address for Communication 3. Consumer No., 4. Telephone No., Application No./Date 7. Letter of Approval Memo No. / Date 8. Contract Demand of Consumer 9. Capacity of Rooftop Solar PV System to be connected (Capacity not to exceed as approved by the JBVNL and as per RSPV Regulation 2015) 10. Technical specifications and other particulars of Renewable Panel, Grid Tied Inverter and Interlocking System etc. proposed to be installed whether attached (Yes/No) 11. Technical specifications and other particulars of Renewable energy meter to be installed whether attached (Yes/No) 12. Whether Consumer opts to purchase meter himself or from Distribution Licensee 13. Drawings for installing the Rooftop Solar PV System whether attached (Yes/No) 14. Date of completion of the installation Place: Signature of Eligible Consumer / Third Party Owner

13 ACKNOWLEDGEMENT Received the application for registration of the scheme for Rooftop Solar PV System Name: Date: Registration Number: Consumer Number: Solar Energy Plant Capacity: Mode of payment (Cheque / DD / RTGS / NEFT): Details of Cheque / DD / RTGS / NEFT: Name of Officer Signature Seal (Designation of Officer)

14 Annexure-VI Inter connection agreement (Net Metering Arrangement) This Agreement is made and entered into at (location)..on this (date)..day of (month)..year..between The Eligible Consumer by the name of having or leasing the premises at (address) as first party AND JBVNL (herein after called as Licensee) and represented by (Designation of office) and having its registered office at Engineering Building, H.E.C., Dhurwa, Ranchi as second party of the agreement And whereas, the Jharkhand Bijli Vitran Nigam Limited agrees to provide grid connectivity to the eligible consumer for injection of the electricity generated from his SPV plant of capacity.. kilowatts into the power system of Licensee and as per conditions of this agreement and net/gross - metering regulations/orders issued by the Jharkhand State Electricity Regulatory Commission. Both the parties hereby agree to as follows: 1. Eligibility 1.1. Eligibility for net-metering has been specified in the JSERC (Rooftop Solar PV Grid Interactive System Gross / Net Metering) Regulations, 2015 (hereinafter referred to as RSPV Regulations, 2015). Eligible consumer is required to be aware, in advance, of the standards and conditions his system has to meet for being integrated into grid/distribution system. 2. Technical and Interconnection Requirements 2.1. The eligible consumer agrees that his Rooftop Solar PV generation plant and net metering system will conform to the standards and requirements specified in these regulations and in the following Regulations and codes as amended from time to time. i. Central Electricity Authority (Technical Standards for connectivity of the Distributed Generating Resources) Regulations, 2013 and subsequent amendments thereof; ii. Central Electricity Authority (Installation and Operation of Meters) Regulation 2006 and subsequent amendments thereof; iii. Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, 2010 and subsequent amendments thereof; iv. JSERC State Grid Code, 2008 and subsequent amendments thereof to the extent specified in the JSERC RSPV Regulations 2015; v. JSERC Supply Code Regulations 2005 and subsequent amendments thereof; vi. Any other provisions applicable to the electricity consumer of the Distribution Licensee.

15 2.2. Eligible consumer agrees that he has installed or will install, prior to connection of Photovoltaic system to Licensee s distribution system, an isolation device (both automatic and inbuilt within inverter and external manual relays) and agrees for the Licensee to have access to and operation of this, if required and for repair & maintenance of the distribution system Eligible consumer agrees that in case of a power outage on Licensee s system, photovoltaic system will disconnect/isolate automatically and his plant will not inject power into Licensee s distribution system All the equipment connected to distribution system shall be compliant with relevant International (IEEE/IEC) or Indian standards (BIS) and installations of electrical equipment must comply with Central Electricity Authority (Measures of Safety and Electricity Supply) Regulations, Eligible consumer agrees that Licensee will specify the interface/interconnection point and metering point Eligible consumer and Licensee agree to comply with the relevant CEA and JSERC Regulations in respect of operation and maintenance of the plant, drawing and diagrams, site responsibility schedule, harmonics, synchronization, voltage, frequency, flicker etc Due to Licensee s obligation to maintain a safe and reliable distribution system, eligible consumer agrees that if it is determined by the Licensee that eligible consumer s photovoltaic system either causes damage to and/or produces adverse effects affecting other consumers or Licensee s assets, eligible consumer will have to disconnect photovoltaic system immediately from the distribution system upon direction from the Licensee and correct the problem at his own expense prior to a reconnection. 3. Clearances and Approvals 3.1. The eligible consumer agrees to obtain all the necessary approvals and clearances (environmental and grid connection related) before connecting the photovoltaic system to the distribution system. 4. Access and Disconnection 4.1. Licensee shall have access to metering equipment and disconnecting means of the solar photovoltaic system, both automatic and manual, at all times In emergency or outage situation, where there is no access to the disconnecting means, both automatic and manual, such as a switch or breaker, Licensee may disconnect service to the premises of the eligible consumer. 5. Liabilities 5.1. Eligible consumer and Licensee will indemnify each other for damages or adverse effects from either party s negligence or intentional misconduct in the connection and operation of photovoltaic system or Licensee s distribution system Licensee and eligible consumer will not be liable to each other for any loss of profits or revenues, business interruption losses, loss of contract or loss of goodwill, or for indirect, consequential, incidental or special damages, including, but not limited to, punitive or

16 exemplary damages, whether any of the said liability, loss or damages arise in contract, or otherwise Licensee shall not be liable for delivery or realization by eligible consumer for any fiscal or other incentive provided by the Central/State Government beyond the scope specified by the Commission in its relevant Order 5.4. The Licensee may consider the quantum of electricity generation from the Rooftop Solar PV system towards RPO. 6. Commercial Settlement 6.1. All the commercial settlement under this agreement shall follow the RSPV Regulations, 2015 issued by the JSERC. 7. Connection Costs 7.1. The eligible consumer shall bear all costs related to setting up of photovoltaic system including metering and interconnection costs. The eligible consumer agrees to pay the actual cost of modifications and upgrades to the service line required to connect photovoltaic system to the grid in case it is required. 8. Termination 8.1. The eligible consumer can terminate agreement at any time by providing Licensee with 90 days prior notice Licensee has the right to terminate Agreement on 30 days prior written notice, if eligible consumer commits breach of any of the term of this Agreement and does not remedy the breach within 30 days of receiving written notice from Licensee of the breach Eligible consumer shall upon termination of this Agreement, disconnect the photovoltaic system from Licensee s distribution system in a timely manner and to Licensee s satisfaction. In witness, whereof, Mr. for and on behalf of (Eligible consumer) and Mr. for and on behalf of (Licensee) sign this agreement in two originals. Eligible Consumer JBVNL Name Name Address Designation Service connection No. Office Address

17 Annexure-VII INFORMATION RELATED TO TECHNICAL & INTERCONNECTION STANDARDS Parameter Reference Requirement Overall conditions of Service State Electricity Supply Code Reference to State Electricity Distribution Code Overall Standards Central Electricity Authority (Grid Standard) Regulations 2010 Reference to regulations Equipment BIS/IEC/IEEE Reference to standards Meters Safety and supply Central Electricity Authority (Installation & operation of meters) Regulation 2006 Central Electricity Authority (measures of safety and electricity supply) Regulations, 2010 Harmonic Current IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources) Regulations 2013 Synchronization IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Voltage IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Reference to regulations and addition conditions issued by the Commission. Reference to regulations Harmonic current injection from a generating station shall not exceed the limits specified in IEEE 519 Rooftop Solar PV System must be equipped with a grid frequency synchronization device. Every time the generating station is synchronized to the electricity system. It shall not cause voltage fluctuation greater than +/- 5% at point of connection. The voltage operation window should minimize nuisance tripping and should be under operating range of 80% to 110% of the nominal connected voltage. Beyond a clearing time of 2 second, the Rooftop Solar PV System must isolate itself from the grid.

18 Flicker IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Frequency IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 DC injection IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Power Factor IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Islanding and Overheat IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Paralleling Device IEEE 519 CEA (Technical Standards for Connectivity of the Distribution Generation Resources ) Regulations 2013 Operation of Rooftop Solar PV System should not cause voltage flicker in excess of the limits stated in ICE standards or other equivalent Indian standards, if any. When the Distribution system frequency deviates outside the specified conditions (50.5 Hz on upper side and 47.5 Hz on lower side), There should be over and under frequency trip functions with a clearing time of 0.2 seconds. Rooftop Solar PV System should not inject DC power more than 0.5% of full rated output at the interconnection point or 1% of rated inverter output current into distribution system under nay operation conditions. While the output of inverter is greater than 50%, a lagging power factor of greater than 0.9 should operate. The inverter should have the facility to automatically switch off in case of overload or overheating and should restart when normal conditions are restored. Paralleling device of Rooftop Solar PV System shall be capable of withstanding 220% of the normal voltage at the interconnection point.

19

POWER PURCHASE AGREEMENT FOR ROOFTOP SOLAR PV PLANTS WITH NET METERING ARRANGEMENT

POWER PURCHASE AGREEMENT FOR ROOFTOP SOLAR PV PLANTS WITH NET METERING ARRANGEMENT POWER PURCHASE AGREEMENT FOR ROOFTOP SOLAR PV PLANTS WITH NET METERING ARRANGEMENT This Power Purchase agreement is entered into at (place).. on this. day of between Manipur State Power Distribution Company

More information

Bihar Electricity Regulatory Commission Vidyut Bhawan, J.L.Nehru Marg, Patna

Bihar Electricity Regulatory Commission Vidyut Bhawan, J.L.Nehru Marg, Patna Bihar Electricity Regulatory Commission Vidyut Bhawan, J.L.Nehru Marg, Patna 800 021 ------------------------------------------------------------------------------------------------------------- ROOFTOP

More information

EXTRA ORDINARY 16 AASHAADHA, 1937(S) BIHAR ELECTRICITY REGULATORY COMMISSION

EXTRA ORDINARY 16 AASHAADHA, 1937(S) BIHAR ELECTRICITY REGULATORY COMMISSION REGISTERED NO. PT.-40 The B Bihar Gazett te EXTRA ORDINARY PUBLISHED BY AUTHORITY 16 AASHAADHA, 1937(S) (NO.PATNA 737) PATNA, TUESDAY, 7 TH JULY 2015 BIHAR ELECTRICITY REGULATORY COMMISSION NOTIFICATION

More information

ODISHA ELECTRICITY REGULATORY COMMISSION UNIT VIII, BHUBANESWAR

ODISHA ELECTRICITY REGULATORY COMMISSION UNIT VIII, BHUBANESWAR ODISHA ELECTRICITY REGULATORY COMMISSION UNIT VIII, BHUBANESWAR 751012 ORDER No. OERC-Engg. 02/2010/(Vol-III)/1597(A) Dated : 26.11.2014 ON NET METERING/BI-DIRECTIONAL METERING & THEIR CONNECTIVITY WITH

More information

ODISHA ELECTRICITY REGULATORY COMMISSION PLOT NO.4, CHUNOKOLI, SAILASHREE VIHAR, BHUBANESWAR ********

ODISHA ELECTRICITY REGULATORY COMMISSION PLOT NO.4, CHUNOKOLI, SAILASHREE VIHAR, BHUBANESWAR ******** ODISHA ELECTRICITY REGULATORY COMMISSION PLOT NO.4, CHUNOKOLI, SAILASHREE VIHAR, BHUBANESWAR - 751021 ******** ORDER No. OERC-Engg. 02/2010/(Vol-IV)/1131 Dated :19.08.2016 ON NET METERING/BI-DIRECTIONAL

More information

CHECK LIST FOR REGISTRATION FORM

CHECK LIST FOR REGISTRATION FORM NNEXUREII CHECK LIST FOR REGISTRTION FORM S. No. DOCUMENTS REQUIRED SUMITTED 1 Registration form signed by Registered consumer on each page with stamp 2 Detailed SLD of solar plant signed by Registered

More information

UP Electricity Regulatory Commission Vidyut Niyamak Bhawan, Vibhuti Khand, Gomti Nagar, Lucknow. Public Notice

UP Electricity Regulatory Commission Vidyut Niyamak Bhawan, Vibhuti Khand, Gomti Nagar, Lucknow. Public Notice UP Electricity Regulatory Commission Vidyut Niyamak Bhawan, Vibhuti Khand, Gomti Nagar, Lucknow No.UPERC/ Secy/JD(G)/2018/ dated : 20 th August, 2018 Public Notice The Commission is in process of reviewing

More information

Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, DRAFT

Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, DRAFT Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, 2015- DRAFT 1. PREAMBLE 1.1 To harness the potential of renewable energy resources in the state, Government of Madhya Pradesh

More information

RAJASTHAN ELECTRICITY REGULATORY COMMISSION

RAJASTHAN ELECTRICITY REGULATORY COMMISSION RAJASTHAN ELECTRICITY REGULATORY COMMISSION NOTIFICATION Jaipur, 26.02.2015 No. RERC/Secy/Reg. - 110 In exercise of powers conferred under Section 181 read with Sections 61, 66 and 86(1) (e) of the Electricity

More information

Net +Plus Connection Code

Net +Plus Connection Code Net +Plus Connection Code LANKA ELECTRICITY COMPANY (PRIVATE) LIMITED 1.0 BACKGROUND The existing Net Metering Concept launched in the year 2010 noticed an exponential growth in the recent year and at

More information

London Hydro Connection Checklist

London Hydro Connection Checklist London Hydro Connection Checklist Applicants should be aware not to incur expenses prior to London Hydro approving the connection of the facility to the grid. Payment of Connection Fee: $1000 plus HST

More information

SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT

SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT This Net Metering and Interconnection Agreement ( Agreement ) is made and entered into as of this day of, 2018, by the City of Santa

More information

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Pacific Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system to

More information

SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT

SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT INTERCONNECTION AGREEMENT FOR SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION THIS AGREEMENT MUST ACCOMPANY

More information

In the MERC (Net Metering for Roof-top Solar Photo Voltaic Systems) Regulations, 2015, the Eligible Consumer has been defined as under:

In the MERC (Net Metering for Roof-top Solar Photo Voltaic Systems) Regulations, 2015, the Eligible Consumer has been defined as under: ~~ NIAHA VITARAN MaharasIltn< State Electricity Distribution Co. Ltd. (A Govt. of Maharashtra Undertaking) ~IN:U40109MH2005SGC153645 No. Comm/CP/Solar-Net metering/ 3'(\"5/ Office of the Chief Engineer

More information

Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, DRAFT

Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, DRAFT Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, 2015- DRAFT 1. PREAMBLE 1.1 To harness the potential of renewable energy resources in the state, Government of Madhya Pradesh

More information

Louisville Gas and Electric Company

Louisville Gas and Electric Company P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS XXV. NET METERING A. Applicability and Availability 1. The terms Net Metering Service, Demand Charge-based Time-of- Use Tariff, Net Metering Customer, Customer, Time-of-Use Customer, Time-of-Use Tier,

More information

City of, Kansas Electric Department. Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources

City of, Kansas Electric Department. Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources Ordinance No. Exhibit A ----------------------------------------- City of, Kansas Electric Department Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources -------------------------------------

More information

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING Third Revised Sheet 55a Cancels Second Revised Sheet 55a A. ELIGIBLE CUSTOMER-GENERATOR RULE NO. 17 NET ENERGY METERING Net energy metering is available to eligible customer-generators, defined as, permanent

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Rocky Mountain Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system

More information

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Processed Date Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Customer s Printed Name Installation Street Address Account Number Please note: Columbia Water & Light

More information

REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT

REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT INTRODUCTION Lathrop Irrigation District has created a policy to allow safe connection

More information

Consumer Guidelines for Electric Power Generator Installation and Interconnection

Consumer Guidelines for Electric Power Generator Installation and Interconnection Consumer Guidelines for Electric Power Generator Installation and Interconnection Habersham EMC seeks to provide its members and patrons with the best electric service possible, and at the lowest cost

More information

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program As part of our commitment to support renewable energy, Kissimmee Utility Authority

More information

City of Washington, Kansas Electric Department. Net Metering Policy & Procedure For Customer-Owned Renewable Energy Resources

City of Washington, Kansas Electric Department. Net Metering Policy & Procedure For Customer-Owned Renewable Energy Resources Ordinance No. 743 Exhibit A City of Washington, Kansas Electric Department Net Metering Policy & Procedure For Customer-Owned Renewable Energy Resources Page 1 of 7 1. INTRODUCTION The provisions of this

More information

REVISION NO.: 7 EFFECTIVE: 07/07/16

REVISION NO.: 7 EFFECTIVE: 07/07/16 SOLAR PROGRAM INTERCONNECTION PROCESS OVERVIEW FOR RESIDENTIAL AND SMALL GENERAL SERVICE REVISION NO.: 7 EFFECTIVE: 07/07/16 Required Steps for ED3 s Solar Program Interconnection Process for Residential

More information

Distributed Generation Interconnection Policy

Distributed Generation Interconnection Policy Distributed Generation Interconnection Policy 1 Introduction Carroll Electric Membership Corporation Distributed Generation Interconnection Policy Carroll Electric Membership Corporation (herein after

More information

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED

BANGALORE ELECTRICITY SUPPLY COMPANY LIMITED GUIDELINES FOR EMPANELMENT OF GRID TIED INVERTER MANUFACTURERS FOR IMPLEMENTATION OF SRTPV PROGRAM IN BESCOM. I. NEW EMPANELMENT 1. The grid tied inverter manufacturer shall register their application

More information

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655) - (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility

More information

Compendium of Regulations & Tariff Orders Issued by Regulatory Commissions for Renewable Energy Sources in India

Compendium of Regulations & Tariff Orders Issued by Regulatory Commissions for Renewable Energy Sources in India 457 JOINT ELECTRICITY REGULATORY COMMISSION Joint Electricity Regulatory Commission for State of Goa & Union Territories Grid Connected Solar Power Regulations 2015 Dated 8 th May 2015 Sl. No Description

More information

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities New Ulm Public Utilities Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities INDEX Document Review and History... 2 Definitions... 3 Overview... 3 Application

More information

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5 Columbia City, Indiana Page 1 of 5 SCHEDULE DG-2 LARGE POWER DISTRIBUTED GENERATION I. AVAILABILITY This Distributed Generation Rate is available to any member in good standing of Northeastern REMC (Northeastern)

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates

More information

Roof Top Solar Power Net Metering Solution. Guidelines for implementation of Net Metering for Roof Top Solar Power System

Roof Top Solar Power Net Metering Solution. Guidelines for implementation of Net Metering for Roof Top Solar Power System Roof Top Solar Power Net Metering Solution Guidelines for implementation of Net Metering for Roof Top Solar Power System 1. Net Metering arrangement is permitted for 3 Phase connections only. The interconnection

More information

SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board

SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board Policy Description: In an effort to ensure fair treatment of all of its customers,

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Pacific Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system to

More information

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program. Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative

More information

NET METER REQUEST FORM

NET METER REQUEST FORM Form No. 3651 02/17 NET METER REQUEST FORM In order to receive a Net Meter, please provide the information requested below, sign and return only this coversheet by mail to the address below. NorthWestern

More information

Montana-Dakota Utilities Co. A Division of MDU Resources Group, Inc. 400 N 4 th Street Bismarck, ND 58501

Montana-Dakota Utilities Co. A Division of MDU Resources Group, Inc. 400 N 4 th Street Bismarck, ND 58501 Original Sheet No. 72 Page 1 of 7 AVAILABILITY: Available to any customer that owns and operates a solar, wind or hydroelectric generating facility with a capacity of not more than 25 Kw that is located

More information

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Northeastern Rural Electric Membership Corporation Columbia City, Indiana Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),

More information

KERALA STATE ELECTRICITY REGULATORY COMMISSION. NOTIFICATION Dated, Thiruvananthapuram 6 th August,2007

KERALA STATE ELECTRICITY REGULATORY COMMISSION. NOTIFICATION Dated, Thiruvananthapuram 6 th August,2007 KERALA STATE ELECTRICITY REGULATORY COMMISSION NOTIFICATION No.1/1/KSERC-2006/ Dated, Thiruvananthapuram 6 th August,2007 KSERC (Supply of Power from Captive Generating Plants to Distribution Licensees)

More information

Net Metering Program

Net Metering Program Net Metering Program Chapter 1 Purpose and Scope. The purpose of this chapter is to establish rules for determining the terms and conditions governing the interconnection of electric generation facilities

More information

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY Outline 1. Introduction 2. Legal Basis 3. Scope, Applicability & Qualification 4. Interconnection Set-Up 5. Pricing Methodology 6. Net-Metering

More information

The following are the clarifications to the queries raised by various participants during the pre- bid meeting held on at CTC Complex.

The following are the clarifications to the queries raised by various participants during the pre- bid meeting held on at CTC Complex. Sub : TNTPO- Supply, installation, testing, commissioning & 5 years comprehensive maintenance of roof top 500 kwp grid connected Building Integrated Photovoltaic Power plant (BIPV) combined with load isolated

More information

Umatilla Electric Cooperative Net Metering Rules

Umatilla Electric Cooperative Net Metering Rules Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through

More information

Application for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _

Application for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _ Application for Operation of & Net Metering for Member-Owned Generation -------------- OWNER/APPLICANT INFORMATION Name: Mailing Address: City: County: State: Zip Code: _ Phone Number: Email Address:.Representative:

More information

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY DRAFT Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY 2018 1. INTRODUCTION Solar energy has become the most popular renewable energy source

More information

Wheeling charges, Banking charges & Cross Subsidy Surcharge for Solar Power Generators

Wheeling charges, Banking charges & Cross Subsidy Surcharge for Solar Power Generators KARNATAKA ELECTRICITY REGULATORY COMMISSION No.9/2, 6 th & 7 th Floor, Mahalaxmi Chambers, M.G.Road, Bangalore-560 001 Present: Shri M.R. Sreenivasa Murthy Chairman Shri H. D. Arun Kumar Shri D.B. Manival

More information

Application to Amend Net Metering Service under RS Appendix B. Revised RS 1289 Clean and Black-lined

Application to Amend Net Metering Service under RS Appendix B. Revised RS 1289 Clean and Black-lined Application to Amend Net Metering Service under RS 1289 Revised RS 1289 Clean and Black-lined Rate Schedule 1289 Revision 1 Effective: April 20, 2018 Page 6-1 Clean 6. OTHER RATE SCHEDULE 1289 NET METERING

More information

MANIPUR GAZETTE E X T R A O R D I N A R Y PUBLISHED BY AUTHORITY. No. 301 Imphal, Wednesday, January 7, 2015 (Pausa 17, 1936)

MANIPUR GAZETTE E X T R A O R D I N A R Y PUBLISHED BY AUTHORITY. No. 301 Imphal, Wednesday, January 7, 2015 (Pausa 17, 1936) MANIPUR GAZETTE E X T R A O R D I N A R Y PUBLISHED BY AUTHORITY 1 No. 301 Imphal, Wednesday, January 7, 2015 (Pausa 17, 1936) GOVERNMENT OF MANIPUR SECRETARIAT: SCIENCE & TECHNOLOGY DEPARTMENT N O T I

More information

Rider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION

Rider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION SAMPLE ORDINANCE 3/5/2012 Rider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION Section 1: Applicable Service Territory Net metering and electrical system interconnection is available on a first-come,

More information

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW) City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 7 SCHEDULE LPDG-1 LARGE POWER AND COMMERCIAL MEMBER-OWNED GENERATION I. AVAILABILITY This Generation rate is available to any member in good standing of Noble REMC (Noble) who

More information

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS. 25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements

More information

WOLFEBORO MUNICIPAL ELECTRIC DEPARTMENT NET METERING PILOT PROGRAM. Customer-Owned Renewable Energy Generation Resources (25 Kilowatts or Less)

WOLFEBORO MUNICIPAL ELECTRIC DEPARTMENT NET METERING PILOT PROGRAM. Customer-Owned Renewable Energy Generation Resources (25 Kilowatts or Less) WOLFEBORO MUNICIPAL ELECTRIC DEPARTMENT NET METERING PILOT PROGRAM Customer-Owned Renewable Energy Generation Resources (25 Kilowatts or Less) Issued and Effective: April 3, 2008 Agreement Between And

More information

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM Page 1 of 19 Table of Contents 1.0 SCOPE...4 2.0 PURPOSE...4 3.0 LIMITATIONS...5 4.0 GENERAL INTERCONNECTION

More information

CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER

CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER RS-N SECOND REVISED SHEET NO. 8.2.1 CANCELLING FIRST SHEET NO. 8.2.1 NAME OF UTILITY CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER DEFINITION Net Metering means calculating

More information

White River Electric Association, Inc. Net Metering Information & Service Requirements

White River Electric Association, Inc. Net Metering Information & Service Requirements White River Electric Association, Inc. Net Metering Information & Service Requirements What is Net Metering? Net Metering is an electric policy and service for consumers who own and utilize renewable energy

More information

24. SOLAR INCENTIVE PROGRAM II

24. SOLAR INCENTIVE PROGRAM II 24. SOLAR INCENTIVE PROGRAM II A. General California Senate Bill 1 requires publicly owned utilities that sell electricity at the retail level, to adopt, implement, and fund a solar incentive program for

More information

BC Hydro Rate Schedule 1289 Revision 1 Effective: April 20, 2018 Page 6-1

BC Hydro Rate Schedule 1289 Revision 1 Effective: April 20, 2018 Page 6-1 Page 6-1 6. OTHER RATE SCHEDULE 1289 NET METERING SERVICE Availability For any Residential Service Customer and for any General Service Customer who: 1. installs a Generating Facility to generate electricity

More information

SOLAR PV INTEGRATION: ISSUES & CHALLENGES with NET METERING

SOLAR PV INTEGRATION: ISSUES & CHALLENGES with NET METERING SOLAR PV INTEGRATION: ISSUES & CHALLENGES with NET METERING A.K. Bohra Chief Executive Officer NESCO, WESCO & SOUTHCO Central Service Office, Bhubaneswar DISTRIBUTED RENEWABLE ENERGY GENERATION With the

More information

INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS

INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS TABLE OF CONTENTS Purpose and Scope...2 Authority...2 Applicability... 2 Intent.. 2 Maximum Connected Generation Allowed. 2 Definitions.

More information

Madhya Pradesh Policy for Net-Metered Renewable Energy Applications, 2016

Madhya Pradesh Policy for Net-Metered Renewable Energy Applications, 2016 Madhya Pradesh Policy for Net-Metered Renewable Energy Applications, 2016 1. PREAMBLE 1.1 To harness the potential of renewable energy resources in the state, Government of Madhya Pradesh wishes to encourage

More information

Application for release of capital subsidy on installation of Grid Connected Solar Power Plant

Application for release of capital subsidy on installation of Grid Connected Solar Power Plant Chandigarh Renewal Energy, Science & Technology Promotion Society (CREST) Under the Aegis of Department of Science & Technology, Chandigarh Administration), Paryavaran Bhawan, First Floor, Sec-19B, Madhya

More information

MEMBER RELATIONS POLICY NO SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES

MEMBER RELATIONS POLICY NO SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES Beartooth Electric Cooperative, Inc. MEMBER RELATIONS POLICY NO. 416 1. SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES 2. OBJECTIVE: Beartooth Electric Cooperative, Inc. (BEC) recognizes that

More information

ELECTRIC DIVISION CUSTOMER-OWNED RENEWABLE GENERATION INFORMATION PACKAGE

ELECTRIC DIVISION CUSTOMER-OWNED RENEWABLE GENERATION INFORMATION PACKAGE Public Works and Utilities 1250 N. Highland St. Mount Dora, FL 32757 352-735-7151 ext. 1805 Fax: 352-735-1539 E-mail: publicworks@cityofmountdora.com ELECTRIC DIVISION CUSTOMER-OWNED RENEWABLE GENERATION

More information

Uttar Pradesh Electricity Regulatory Commission, Lucknow

Uttar Pradesh Electricity Regulatory Commission, Lucknow Uttar Pradesh Electricity Regulatory Commission, Lucknow In the matter of Uttar Pradesh Electricity Regulatory Commission (Rooftop Solar PV Grid Interactive Systems Gross / Net Metering) Regulations, 2019

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Louisiana Net Metering Service. Customer Information Package

Louisiana Net Metering Service. Customer Information Package Louisiana Net Metering Service Customer Information Package August 1, 2013 Net Metering - The means of measuring the difference between the electricity supplied by an electric utility and the electricity

More information

Enquiry Form (Non-Registered Generator With Capacity less than 5 MW)

Enquiry Form (Non-Registered Generator With Capacity less than 5 MW) Connection Applicant (Embedded Generating Unit Owner/Proponent) Business name: ABN: Contact name: Address: Telephone number: E-mail address: Connection Applicant acting and working on behalf of the above

More information

THE EMPIRE DISTRICT ELECTRIC COMPANY P.S.C. Mo. No. 5 Sec. 4 1st Revised Sheet No. 23

THE EMPIRE DISTRICT ELECTRIC COMPANY P.S.C. Mo. No. 5 Sec. 4 1st Revised Sheet No. 23 P.S.C. Mo. No. 5 Sec. 4 1st Revised Sheet No. 23 Canceling P.S.C. Mo. No. 5 Sec. 4 Original Sheet No. 23 PURPOSE: The purpose of this Rider SR is to implement the solar rebate established through 393.1030

More information

BC Hydro Rate Schedules Effective: August 1, 2015 Fourth Revision of Page 30

BC Hydro Rate Schedules Effective: August 1, 2015 Fourth Revision of Page 30 BC Hydro Effective: August 1, 2015 Fourth Revision of Page 30 SCHEDULE 1289- NET METERING SERVICE Availability: For any Residential Service Customer and for any General Service Customer who install a Generating

More information

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW PROGRAM REQUIREMENTS Important Information from Your Local Non-Profit Utility INTERCONNECTION for GENERATING FACILITIES Up to 20 MW Interconnecting to the Electrical Distribution System of Public Utility

More information

NEWFOUNDLAND AND LABRADOR BOARD OF COMMISSIONERS OF PUBLIC UTILITIES AN ORDER OF THE BOARD NO. P.U. 17(2017)

NEWFOUNDLAND AND LABRADOR BOARD OF COMMISSIONERS OF PUBLIC UTILITIES AN ORDER OF THE BOARD NO. P.U. 17(2017) NEWFOUNDLAND AND LABRADOR BOARD OF COMMISSIONERS OF PUBLIC UTILITIES AN ORDER OF THE BOARD NO. P.U. (0) 0 0 IN THE MATTER OF the Electrical Power Control Act,, SNL, Chapter E-. (the EPCA ) and the Public

More information

COMMUNITY SOLAR PROGRAM

COMMUNITY SOLAR PROGRAM Original Sheet No. D-22.00 COMMUNITY SOLAR PROGRAM The Cooperative's generation and transmission Cooperative ("G&T") has created a standing offer for 10 MW ofrenewable energy, produced by solar and wind

More information

Ministry of New and Renewable Energy (Jawaharlal Nehru National Solar Mission) Form B for Project Proposals for

Ministry of New and Renewable Energy (Jawaharlal Nehru National Solar Mission) Form B for Project Proposals for Form B Ministry of New and Renewable Energy (Jawaharlal Nehru National Solar Mission) Form B for Project Proposals for Grid Connected Rooftop and Small SPV Power Plants (For the project above 5 kwp & upto

More information

MCCOOK PUBLIC POWER DISTRICT McCook, Nebraska BOARD POLICY NUMBER 488

MCCOOK PUBLIC POWER DISTRICT McCook, Nebraska BOARD POLICY NUMBER 488 MCCOOK PUBLIC POWER DISTRICT McCook, Nebraska BOARD POLICY NUMBER 488 SUBJECT Renewable Generator Net Metering Interconnect Policy OBJECTIVE To set forth a policy for the interconnection and net metering

More information

INTERCONNECTION REQUIREMENTS POLICY

INTERCONNECTION REQUIREMENTS POLICY Issue Date: January 8, 2018 Resolution No. 2097-18 INTERCONNECTION REQUIREMENTS POLICY 1. Purpose and Scope A. The purpose of these Interconnection Requirements is to establish rules for determining the

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,

More information

GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS

GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS 1. INTRODUCTION... 3 1.1 POLICY ON CUSTOMER GENERATION.... 3 1.2 GENERATION SOURCES AND

More information

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,

More information

NESCO UTILITY. Januganj, Balasore TARIFF NOTIFICATION The 23 rd March, 2015 RETAIL SUPPLY TARIFF EFFECTIVE FROM 1 st APRIL, 2015

NESCO UTILITY. Januganj, Balasore TARIFF NOTIFICATION The 23 rd March, 2015 RETAIL SUPPLY TARIFF EFFECTIVE FROM 1 st APRIL, 2015 NESCO UTILITY Januganj, Balasore-756019 TARIFF NOTIFICATION The 23 rd March, 2015 RETAIL SUPPLY TARIFF EFFECTIVE FROM 1 st APRIL, 2015 In exercise of the powers conferred under section 64(3) and other

More information

INDUSTRIAL HAUL AGREEMENT

INDUSTRIAL HAUL AGREEMENT INDUSTRIAL HAUL AGREEMENT PUBLIC WORKS MEMORANDUM OF AGREEMENT entered into this day of, A.D., 20(yr). BETWEEN: PARKLAND COUNTY a County incorporated under the laws of the Province of Alberta, (hereinafter

More information

December 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff.

December 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff. JERSEY CENTRAL POWER & LIGHT UNIFORM TECHNICAL AND PROCEDURAL INTERCONNECTION REQUIREMENTS FOR NET METERING FACILITIES FOR INVERTER BASED WIND AND PHOTOVOLTAIC SYSTEMS OF 100 kw OR SMALLER for Atlantic

More information

JEA Distributed Generation Policy Effective April 1, 2018

JEA Distributed Generation Policy Effective April 1, 2018 Summary This JEA Distributed Generation Policy is intended to facilitate generation from customer-owned renewable and non-renewable energy generation systems interconnecting to the JEA electric grid. The

More information

Madhya Pradesh Policy for Rooftop Renewable Energy Projects, 2016

Madhya Pradesh Policy for Rooftop Renewable Energy Projects, 2016 Madhya Pradesh Policy for Rooftop Renewable Energy Projects, 2016 1. PREAMBLE 1.1 To harness the abundantly available renewable energy potential in the state, the Government of Madhya Pradesh wishes to

More information

Marina Bay Sands Guidelines for Electrical and Wiring Service

Marina Bay Sands Guidelines for Electrical and Wiring Service Marina Bay Sands Guidelines for Electrical and Wiring Service 1) The supply of electrical mains in the licensed area of the event is an exclusive service offered by Marina Bay Sands (MBS). In the event

More information

M.P.S.C. No. 2 Electric Third Revised Sheet No. 65 (Rate Case) Cancels Second Revised Sheet No. 65

M.P.S.C. No. 2 Electric Third Revised Sheet No. 65 (Rate Case) Cancels Second Revised Sheet No. 65 M.P.S.C. No. 2 Electric Third Revised Sheet No. 65 (Rate Case) Cancels Second Revised Sheet No. 65 CLASS OF SERVICE: CUSTOMER GENERATING SYSTEMS OVER 20 KW RATE CGS 1 AVAILABILITY To customers owning generating

More information

RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES

RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES Last Revised Date: October 15, 2015 Contents Chapter 1 - Purpose and Scope 2 Chapter 2 - Application of Rules 2 Chapter 3 - Definitions

More information

New Hampshire Electric Cooperative (NHEC) Introduction to Net Metering

New Hampshire Electric Cooperative (NHEC) Introduction to Net Metering New Hampshire Electric Cooperative (NHEC) Introduction to Net Metering NHEC supports the development of member-sited renewable energy generation and storage facilities (referred to herein as an interconnection

More information

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used

More information

40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power

40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power 40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect

More information

TILLAMOOK PEOPLE S UTILITY DISTRICT

TILLAMOOK PEOPLE S UTILITY DISTRICT TILLAMOOK PEOPLE S UTILITY DISTRICT DISTRIBUTION INTERCONNECTION PROCEDURE Inverter Based Generators 25 kw and Smaller This document contains the interconnection requirements for inverter based generators,

More information

Name and address of DISCOM with Logo. TARIFF NOTIFICATION The 22 rd March, 2018 RETAIL SUPPLY TARIFF EFFECTIVE FROM 1 st APRIL, 2018

Name and address of DISCOM with Logo. TARIFF NOTIFICATION The 22 rd March, 2018 RETAIL SUPPLY TARIFF EFFECTIVE FROM 1 st APRIL, 2018 Name and address of DISCOM with Logo TARIFF NOTIFICATION The 22 rd March, 2018 RETAIL SUPPLY TARIFF EFFECTIVE FROM 1 st APRIL, 2018 In exercise of the powers conferred under section 64(3) and other related

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Pacific Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system to

More information

BOOT/OPEX/Pay As You Use Model for Rooftop Solar Projects Workshop on Getting Started on Energy Management & Solar

BOOT/OPEX/Pay As You Use Model for Rooftop Solar Projects Workshop on Getting Started on Energy Management & Solar BOOT/OPEX/Pay As You Use Model for Rooftop Solar Projects Workshop on Getting Started on Energy Management & Solar Photonergy Solutions Private Limited Key Drivers Rooftop Solar-Business Case Rising Grid

More information