Determination of Arrester Energy Handling Capability - Testing Investigation Surge Protective Devices Committee Spring 2005 Meeting

Size: px
Start display at page:

Download "Determination of Arrester Energy Handling Capability - Testing Investigation Surge Protective Devices Committee Spring 2005 Meeting"

Transcription

1 Determination of Arrester Energy Handling Capability - Testing Investigation Surge Protective Devices Committee Spring 2005 Meeting Raymond C. Hill, PE

2 Introduction Conflicting opinions exist concerning the method of rating the energy handling capability of MOV arresters. The top contenders comprise the following methods: Joule kj / kv mcov Coulomb charge transfer I-squared-t action integral

3 Introduction A project proposal was made to NEETRAC by an SPDC officer and member of the NEETRAC Technical Advisors to investigate. In the fall of 2001, NEETRAC launched Phase I of a Baseline Research Project funded by the membership in order to investigate and provide input to the IEEE SPDC.

4 Introduction Phase I involved a test program utilizing one size of a single MOV arrester block and was completed at the end of Phase II was then proposed to investigate additional MOV arrester blocks with different aspect ratios.

5 Introduction In the fall of 2003, NEETRAC launched Phase II of the investigation. Phase II was a test program utilizing several sizes of a single MOV arrester block with different aspect ratios. NEETRAC has recently completed Phase II of the investigation.

6 Purpose & Scope Phases I & II To investigate the energy handling capability of single MOV arrester blocks To determine which method(s) of energy rating will describe this parameter across the board providing an equal energy rating system for all concerned.

7 Purpose & Scope Phases I & II Various sizes of blocks with different aspect ratios were tested in order to investigate the relationship of height, width, volume, and cross-sectional area to energy handling capability. Various impulse waveforms were used to investigate the relationship between waveshape and energy handling capability of the various sizes and aspect ratios of MOV arrester blocks. A total of more than 160 MOV blocks were surged during this investigation.

8 Test Procedure New MOV arrester blocks were surged (individually) to determine the single-surge-to-failure level using various current impulse waveforms. The surge current and voltage waveforms were digitized and recorded. Calculations were then made to determine the Joule, Coulomb, and I 2 t values of the surges just prior to and after destruction.

9 Test Procedure The three methods of energy rating were then analyzed and compared utilizing the various parameters of the MOV arrester blocks. A determination was then made as to which method was the most consistent and accurate.

10 Test Procedure Waveforms, Generators, and Fixtures Standard Wave 8 / 20 µs Long Tail Wave 9 / 170 µs Triangle Wave / 410 µs / 370 µs

11 Test Procedure Waveforms, Generators, and Fixtures Impulse Current Waveshapes ( Normalized to 1kA) Current (A) Time (us) 180/410 9/170 10/350 8/20

12 Test Procedure Waveforms, Generators, and Fixtures 8 / 20 µs generator and SF 6 pressure vessel

13 Test Procedure Waveforms, Generators, and Fixtures SF 6 Pressure Vessel

14 Test Procedure Waveforms, Generators, and Fixtures Sample Fixture within SF 6 Pressure Vessel

15 Test Procedure Waveforms, Generators, and Fixtures Long Tail and Triangle Wave Generator

16 Test Procedure Waveforms, Generators, and Fixtures Sample Holder for the Long Tail and Triangle Waves

17 Sample Sets for Phases I & II Quantity Height (inches) Height (mm) Width (inches) Width (mm) Table 1 Aspect Ratio (width/height) Volume (mm3) Crosssectional Area (cm2) MCOV (kv) approx. Sample Designation A1 - A B1 - B C1 - C D1 - D E1 - E F1 - F G1 - G H1 - H A - ZZZZ MOV blocks were provided by Cooper Power Systems and Hubbell / Ohio Brass

18 Sample Sets for Phases I & II A E B F C G D H Complete Set

19 Failure Criteria Individual samples were surged only once each until the failure level was achieved for that block design. Several data sets above the failure level and below (withstand) were then acquired. The one block - one surge only protocol was maintained throughout. A failure was defined as any physical damage to the block.

20 Failure Criteria A flashover across the edge of the block was not considered a failure. Examples of failures:

21 Waveshape Triangle (180/410) Phase I Results Table 2 Current Current Duration Capacitor (I**2)*t Front Tail or Time- Charge Peak (Ampere- Block Time Time to- Voltage Current I*t squared- V*I*t Withstand / Sample (us) (us) Failure (kv) (ka) (Coulombs) seconds) (kj) Fail Comments CC w/stand Epoxy collar bubbled DD fail Very small hole and crack at edge EE w/stand Epoxy collar bubbled FF w/stand Epoxy collar bubbled GG w/stand Epoxy collar bubbled MMM w/stand NNN w/stand SSS fail Channel part way down the edge TTT w/stand UUU w/stand VVV w/stand WWW w/stand XXX w/stand YYY w/stand ZZZ w/stand AAAA w/stand BBBB w/stand CCCC 172 n/app fail Failed near edge; blew off portion of block; epoxy collar bubbled DDDD w/stand EEEE 178 n/app fail Blew off chip on the edge

22 Waveshape Long Tail (9/170) Sample Current Front Time (us) Current Tail Time (us) Duration or Time- to- Failure Phase I Results Table 3 Capacitor Charge Voltage (kv) Peak Current (ka) I*t (Coulombs) (I**2)*t (Amperesquaredseconds) V*I*t (kj) Block Withstand / Fail HH fail II fail JJ fail KK w/stand LL w/stand MM w/stand NN w/stand OO fail PP w/stand QQ w/stand PPP fail QQQ w/stand FFFF w/stand GGGG fail HHHH fail Comments Channel halfway down the edge Channel halfway down the edge Channel halfway down the edge, then blew off portion of the block Channel halfway down the edge Puncture near center; split block Puncture 5 mm from edge; blew off portion of the block Channel part way down the edge

23 Phase I Results Table 4 Waveshape Sample Standard (8/20) Current Front Time (us) Current Tail Time (us) Duration or Time- to- Failure Capacitor Charge Voltage (kv) Peak Current (ka) I*t (Coulombs) (I**2)*t (Amperesquaredseconds) V*I*t (kj) Block Withstand / Fail Comments Surged under SF6; failed during current reversal; failed near edge; blew off portion of the block; left a tree-like pattern on the side ZZ , fail XX , w/stand Surged under SF6 CCC , w/stand Surged under SF6 Surged under SF6; failed along the edge burning a tree-like EEE , fail pattern on the side FFF , w/stand Surged under SF6

24 Phase I Results A first review of the impulse data values for Coulombs, I 2 t, and Joules reveals no obvious correlation among the three different waveforms. However, when the total duration of the surge or time-to-failure is taken into account a correlation appears. This is shown graphically in the following figures.

25 Phase I Results Arrester Block Single-Shot Energy Capability Kilojoule Method y = e x 100 Kilojoules Pulse Duration or Time-to-Failure

26 Phase I Results Arrester Block Single-Shot Energy Capability Action Integral (Ampere-Squared-Seconds) Method 1.0E+06 y = 45682e x 1.0E+05 Ampere-Squared-Seconds 1.0E E E Pulse Duration or Time-to-Failure (us)

27 Phase I Results Arrester Block Single-Shot Energy Capability Coulomb Method y = e x 10 Coulombs Pulse Duration or Time-to-Failure (us)

28 Phase I Results When the pass/fail data for all three waveforms is plotted versus total pulse duration or time-to-failure for each energy method, a definitive border appears among the pass/fail data. In general, any current surge with an energy content and duration which falls below this border will not cause an MOV block failure for the design tested. This border or trend line can be defined as shown in the following equation:

29 Phase I Results β e -mt β represents the y-intercept, which is the maximum energy achieved with an infinitesimally small pulse width. The coefficient m represents the slope of the line and t is time (pulse width). With this method, the borderline of failure can be described by defining these two coefficients.

30 Phase I Results This equation is waveform independent for durations less than 1000 microseconds. Each energy rating method would require a unique set of coefficients. At this point, the equation only applies to one MOV block size. This equation fits the Coulomb or charge transfer method better than the others which exhibit more of an upturn for times less than 200 microseconds. Obviously, further investigation is required.

31 Phase I Results Additional Observations Worth Noting The slope of the Coulomb equation was found to be small, such that, when considering the data scatter (and with further investigation), one might conclude that a single Coulomb value could be assigned to the MOV arrester block design utilized in this project in lieu of an equation. With the exception of Sample PPP, all of the block puncture locations were along the edge or within 5 mm of the edge.

32 Phase II Results - Tabulated Table 5 Waveshape 8/20 Sample Current Front Time (us) Current Tail Time (us) Duration or Until Failure or Flashover Capacitor Charge Voltage (kv) Peak Current (ka) I*t (Coulombs) (I**2)*t (Amperesquaredseconds) V*I*t (kj) Block Withstand / Fail / Flashover (f / o) Comments MCOV (kv) approx. Aspect Ratio (width/ height) B , f / o 20 psig SF C , w/stand 20 psig SF C , f / o 20 psig SF C , w/stand 25 psig SF C , f / o 20 psig SF D , w/stand 15 psig SF D , w/stand 15 psig SF D , w/stand 25 psig SF E , f / o 20 psig SF E , f / o 20 psig SF E , f / o 20 psig SF E , f / o 20 psig SF UU , w/stand 25 psig SF Width (mm) Height (mm)

33 Phase II Results Tabulated Table 6 Waveshape 9/170 Sample Current Front Time (us) Current Tail Time (us) Duration or Until Failure or Flashover Capacitor Charge Voltage (kv) Peak Current (ka) I*t (Coulombs) (I**2)*t (Amperesquaredseconds) V*I*t (kj) Block Withstand / Fail / Flashover (f / o) Comments MCOV (kv) approx. Aspect Ratio (width/ height) C , fail C , w/stand C , fail C , fail C , fail C , w/stand C , fail C , fail C , fail C , fail C ,497 n/av w/stand no voltage trace C , fail C , fail C , fail C , w/stand C , fail C , w/stand C , fail C , w/stand C , fail C , fail C , w/stand C , w/stand B , fail B , w/stand B ,835 n/av fail B , fail B , fail B , fail B , w/stand B , w/stand B , w/stand E , w/stand gen. can't fail E , w/stand gen. can't fail Width (mm) Height (mm)

34 Phase II Results - Tabulated Waveshape Triangle Wave Sample Current Front Time (us) Current Tail Time (us) Duration or Until Failure or Flashover Capacitor Charge Voltage (kv) Peak Current (ka) I*t (Coulombs) Table 7 (I**2)*t (Amperesquaredseconds) V*I*t (kj) Block Withstand / Fail / Flashover (f / o) Comments MCOV (kv) approx. Aspect Ratio (width/ height) B , f / o B n/av n/av n/av n/av n/av f / o can't determine when f/o ocurred C w/stand gen. can't fail C w/stand gen. can't fail C , w/stand gen. can't fail C , w/stand gen. can't fail C , w/stand gen. can't fail C , w/stand gen. can't fail C , w/stand gen. can't fail Width (mm) Height (mm)

35 Phase I & II Results with AE I Borderline Equation Arrester Block Single-Shot Energy Capability Kilojoule Method by Aspect Ratio and Pulse Duration Kilojoules w/s 1.4 AEI w/s 1.4 AEI fail 1.5 w/s 2.1 w/s 2.1a w/s 2.1b w/s 2.1a fail 2.1b fail 2.7 w/s 2.7a w/s 7.1 w/s 7.1 fail 2.1c w/s 7.1a w/s AEI Eq Pulse Duration

36 Phase I & II Results with AE I Borderline Equation Arrester Block Single-Shot Energy Capability Action Intergal Method by Aspect Ratio and Pulse Duration Ampere-squared-seconds 1.0E E E E w/s 1.4 AEI w/s 1.4 AEI fail 1.5 w/s 2.1 w/s 2.1a w/s 2.1b w/s 2.1a fail 2.1b fail 2.7 w/s 2.7a w/s 7.1 w/s 7.1 fail 2.1c w/s 7.1a w/s I sqrt t AEI 1.0E Pulse Duration

37 Phase I & II Results with AE I Borderline Equation Arrester Block Single-Shot Energy Capability Coulomb Method by Aspect Ratio and Pulse Duration Coulombs w/s 1.4 AEI w/s 1.4 AEI fail 1.5 w/s 2.1 w/s 2.1a w/s 2.1b w/s 2.1a fail 2.1b fail 2.7 w/s 2.7a w/s 7.1 w/s 7.1 fail 2.1c w/s 7.1a w/s AE1 Eq Pulse Duration

38 Phase II Results As can be seen, the borderline equation from Phase I requires adjusting in order to take into account the variance caused by the different MOV block sizes. Many different aspects of MOV block size were compared with the three energy rating methods. The correlations of predominant interest are the following:

39 Phase I & II Results Arrester Energy in Kilojoules per Unit Diameter Kilojoules / mm diameter w/s AE I fail AE I w/s AE II fail AE II AEI Eq Pulse Duration (us)

40 Phase I & II Results Arrester Energy in Kilojoules per kv of MCOV 100 kilojoules per kv of MCOV w/s 2.1 fail 7.1 w/s 7.1 fail 2.1c w/s 7.1a w/s 1.4 AE I w/s 1.4 AE I fail Duration (us)

41 Phase I & II Results Arrester Energy in Kilojoules per kv of MCOV per Unit Diameter 1.00 kj / kvmcov / mm 0.10 w/s AE I fail AE I w/s AE II fail AE II Pulse Duration

42 Phase I & II Results Arrester Energy in "I squared t" per Unit Diameter Ampere-squared seconds / mm diameter w/s AE I fail AE I w/s AE II fail AE II I sqr t AEI Pulse Duration (us)

43 Phase I & II Results Arrester Energy in "I - squared - t" per Kilovolt of MCOV Ampere-squared seconds / kv of MCOV w/s AE fail AE w/s AE fail AE Pulse Duration (us)

44 Phase I & II Results Arrester Energy in Coulombs per Kilovolt of MCOV 10.0 C / kvmcov 1.0 w/s AE I fail AE I w/s AE II fail AE II Pulse Duration (us)

45 Phase I & II Results Arreser Energy in Coulombs per Unit Diameter 1.00 Coulombs / mm diameter 0.10 w/s AE I w/s AE II fail AE I fail AE II AE I Borderline AE I & AE II Borderline Threshold Pulse Duration (us)

46 Phase I & II Results Arrester Energy in Coulombs per Unit Cross-sectional Area 1.00 Coulombs per square cm 0.10 w/s AE I fail AE I w/s AE II fail AE II AE I Borderline AE I & AE II Borderline Threshold Pulse Duration (us)

47 Phase I & II Results Arrester Block Single-Shot Energy Capability Coulomb Method by Cross-sectional Area 10.0 Coulombs 1.0 AE I Withstand AE I Fail AE II Withstand AE II Fail Cross-sectional Area (square-cm)

48 Discussion / Conclusions The kilojoule per unit diameter data exhibits the most scatter of the three methods, with the most scatter occurring at the longer durations. The I 2 t per unit diameter data exhibits less scatter than the kilojoule method. The Coulombs per unit diameter and per unit cross-sectional area data also exhibit less scatter than the kilojoule method. (Converting the diameter to cross-sectional area allows for square MOV blocks.)

49 Discussion / Conclusions When inspecting the Coulombs per unit crosssectional area graph, one could conceivably rate these arrester blocks at 0.09 or 0.1 Coulomb per square centimeter. A flat rating such as this would then be MOV recipe dependent along with any other presently unknown physical or dimensional limits. It is understood that two manufacturers provided samples, which could cause some scattering of the data due to different recipes. Any rating from this investigation is still limited to total pulse durations less than 1000 microseconds.

50 Future Work It is understood that further investigation is required before any solid conclusions can be reached. More data sets are needed. This data is presented to the IEEE Surge Protective Devices Committee as a challenge to industry leaders and other laboratories to help investigate further the possibilities presented here in order to obtain a more consistent method of rating arrester energy capability across the board for all concerned.

Environmental Management Chapter

Environmental Management Chapter Environmental Management Chapter 335-3-10 ALABAMA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT AIR DIVISION AIR POLLUTION CONTROL PROGRAM ADMINISTRATIVE CODE CHAPTER 335-3-10 STANDARDS OF PERFORMANCE FOR NEW

More information

1 Communication format Inquiry Command... 1

1 Communication format Inquiry Command... 1 1 Communication format... 1 2 Inquiry Command... 1 2.1 QPI: Device Protocol ID Inquiry... 1 2.2 QID: The device serial number inquiry... 1 2.3 QVFW: Main CPU Firmware version inquiry... 1 2.4

More information

Zinc Oxide Surge Arrester EXLIM R

Zinc Oxide Surge Arrester EXLIM R Zinc Oxide Surge Arrester EXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. For use when requirements of lightning intensity, energy

More information

Overview about research project Energy handling capability

Overview about research project Energy handling capability Cigré WG A3.25 meeting San Diego October 16, 2012 Max Tuczek, Volker Hinrichsen, TU Darmstadt Note: all information beginning from slide 21 are provisional results in the frame of Cigré WG A3.25 work,

More information

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester This report records the results of the design tests made on Type PDV 100 Optima Distribution

More information

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4)

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4) CP9817 PAGE: 1 of 16 CERTIFIED TEST REPORT VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC 60099-4 (99-4) 0711 Supersedes 0601 Cooper Industries. All Rights Reserved. CP9817 PAGE:

More information

Eskom s unique type test requirements for lightning surge arrester ground lead disconnectors

Eskom s unique type test requirements for lightning surge arrester ground lead disconnectors Eskom s unique type test requirements for lightning surge arrester ground lead disconnectors Author & Presenter: R Theron M.Eng Chief Engineer Co-author: H Geldenhuys Phd Corporate Specialist (Technology

More information

memorandum Sasaki Associates, Inc. Coastal Carolina University Master Plan

memorandum Sasaki Associates, Inc. Coastal Carolina University Master Plan memorandum date 27 September 2010 to from project name project # 94657.00 subject Coastal Carolina University Master Plan Committee and Steering Committee Sasaki Associates, Inc. Coastal Carolina University

More information

Analog RF Proof of Performance Testing Methodology

Analog RF Proof of Performance Testing Methodology Analog RF Proof of Performance Testing Methodology System Description: Dickey Rural Networks CATV network is a fiber to the home (FTTH) system with an RF overlay. The headend is based in Oakes, ND. This

More information

Zinc-Oxide Surge Arrester TEXLIM Q-C

Zinc-Oxide Surge Arrester TEXLIM Q-C Zinc-Oxide Surge Arrester TEXLIM Q-C Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. in areas with very high lightning intensity where

More information

Managing Projects Teaching materials to accompany:

Managing Projects Teaching materials to accompany: Managing Projects Teaching materials to accompany: Product Design and Development Chapter 14 Karl T. Ulrich and Steven D. Eppinger 2nd Edition, Irwin McGraw-Hill, 2000. Product Development Process Planning

More information

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka) Surge s UltraSIL Polymer-Housed VariSTAR Surge s: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka) Electrical Apparatus 235-35 General Cooper Power Systems has set the standard

More information

OHIO BRASS AIKEN, SC, USA

OHIO BRASS AIKEN, SC, USA Section 31-1 31 Optima Distribution Class (PDV) and Riser Pole (PVR) Surge Arresters Copyright 20 Hubbell Incorporated Printed in USA 31-2 Table of Contents Page Warranty 31-2 Introduction 31-3 Distribution

More information

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL Surge Arresters UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 Electrical Apparatus I235-93 GENERAL UltraSIL Polymer-Housed VariSTAR

More information

Optima Distribution Class (PDV) and Riser Pole (PVR) Surge Arresters

Optima Distribution Class (PDV) and Riser Pole (PVR) Surge Arresters Section 1-1 1 Optima Distribution Class (PDV) and Riser Pole (PVR) Surge Arresters NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications

More information

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION HIGH VOLTAGE SURGE ARRESTER SPECIFICATION Applications: (Polymer housed MOA for 110kv) (The polymer housed MOA for 10kv) (Porcelain housed MOA for 220kv) (35kv MOA without gaps for middle phase) (110kv

More information

Eaton s Cooper Power Systems

Eaton s Cooper Power Systems Page: 1 of CERTIFIED TEST REPORT Eaton s Cooper Power Systems 600 Amp - 35 kv Class Deadbreak Bushing With Internal Ground Screen Design Qualification Tests December 17, 2013 Supersedes 10/20 2013 Eaton

More information

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge

More information

Terminal Boxes Series 8252/1

Terminal Boxes Series 8252/1 www.stahl.de > Ex d enclosure made of saltwater-resistant, copper-free aluminium cast alloy > Powder coated to RAL 7032 > Available in 3 different sizes > With DIN rail for standard terminals > Enclosure

More information

Technical specifications for 10 ka, heavy-duty class 1, 3 kv and 3.33 kv VariSTAR MOV disks

Technical specifications for 10 ka, heavy-duty class 1, 3 kv and 3.33 kv VariSTAR MOV disks Surge Arresters Technical Data TD235026EN Supersedes November 2003 (TD-228) COOPER POWER SERIES Technical specifications for 10 ka, heavy-duty class 1, 3 kv and 3.33 kv VariSTAR MOV disks Ø40.74 ±0.41

More information

Technical specifications for 10 ka, heavy-duty class 1, 4.5 kv and 5 kv VariSTAR MOV disks

Technical specifications for 10 ka, heavy-duty class 1, 4.5 kv and 5 kv VariSTAR MOV disks Surge Arresters Technical Data TD235027EN Supersedes November 2003 (TD-230) COOPER POWER SERIES Technical specifications for 10 ka, heavy-duty class 1, 4.5 kv and 5 kv VariSTAR MOV disks Ø40.74 ±0.41 0.051

More information

FUSE TECHNOLOGY Ambient temperature

FUSE TECHNOLOGY Ambient temperature This fuse technology guide will discuss basic fuse operating, application, and selection criteria concepts. The intended purpose of this section is to aid designers with the operation and characteristics

More information

Report Addendum. Terry Keller, SDDOT. Noise Study Technical Report I-29 from Tea Interchange to Skunk Creek Sioux Falls, South Dakota

Report Addendum. Terry Keller, SDDOT. Noise Study Technical Report I-29 from Tea Interchange to Skunk Creek Sioux Falls, South Dakota Report Addendum To: Terry Keller, SDDOT From: HDR Project: Noise Study Technical Report I-29 from Tea Interchange to Skunk Creek Sioux Falls, South Dakota cc: file Date: May 28, 2010; rev July 16, July

More information

Transient Voltage Suppression Diodes SMTO ka > LTKAK6 series. Description. Features. Test Current I T. Reverse Breakdown Voltage (V BR I T

Transient Voltage Suppression Diodes SMTO ka > LTKAK6 series. Description. Features. Test Current I T. Reverse Breakdown Voltage (V BR I T SMTO-218-6 ka > LTKAK6 series LTKAK6 Series RoHS Pb e3 Description The LTKAK6 series offers superior clamping characteristics over standard S.A.D. technologies by virtue of the Littelfuse Foldbak technology,

More information

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks D. M. Nobre W. L. A. Neves B. A. de Souza Departamento de Engenharia Elétrica - UFPB Av. Aprígio Veloso, 882 Bodocongó 58.109-970,

More information

Burn Characteristics of Visco Fuse

Burn Characteristics of Visco Fuse Originally appeared in Pyrotechnics Guild International Bulletin, No. 75 (1991). Burn Characteristics of Visco Fuse by K.L. and B.J. Kosanke From time to time there is speculation regarding the performance

More information

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE H U B B ELL L ABO R ATO R I E S CAPABILITY GUIDE INTRODUCTION Hubbell Power Systems, Inc. manufactures a wide variety of products for the electric utility, telecommunications, civil construction, transportation,

More information

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features Surge s Electrical Apparatus 235-99 General Cooper Power Systems set the standard for design, manufacturing and delivery of polymeric distribution arresters with the UltraSIL polymerhoused arrester family.

More information

3EK7 Medium Voltage Silicone Insulated Surge Arresters

3EK7 Medium Voltage Silicone Insulated Surge Arresters 3EK7 Medium Voltage Silicone Insulated Surge Arresters Power Transmission and Distribution Setting new Standards The 3EK7 s mechanical features: Glass-collared MOV, Silicone rubber housing, FRP rods and

More information

Aug07 Rev A All Paragraphs Revised

Aug07 Rev A All Paragraphs Revised Qualification Test Report Universal MATE-N-LOK* Connector 110-213 28Aug07 Rev A All Paragraphs Revised 1. INTRODUCTION 1.1. Purpose 1.2. Scope Testing was performed on Universal MATE-N-LOK* connectors

More information

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn Surge arresters UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters electrical apparatus 235-75 General Cooper Power Systems has set a new standard of excellence for polymerhoused

More information

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011-

PVP Field Calibration and Accuracy of Torque Wrenches. Proceedings of ASME PVP ASME Pressure Vessel and Piping Conference PVP2011- Proceedings of ASME PVP2011 2011 ASME Pressure Vessel and Piping Conference Proceedings of the ASME 2011 Pressure Vessels July 17-21, & Piping 2011, Division Baltimore, Conference Maryland PVP2011 July

More information

Simulated Annealing Algorithm for Customer-Centric Location Routing Problem

Simulated Annealing Algorithm for Customer-Centric Location Routing Problem Simulated Annealing Algorithm for Customer-Centric Location Routing Problem May 22, 2018 Eugene Sohn Advisor: Mohammad Moshref-Javadi, PhD 1 Agenda Why this research? What is this research? Methodology

More information

MAXIMUM LOAD. 9.1 kg / 20 lb MAXIMUM LOAD. 9.1 kg / 20 lb

MAXIMUM LOAD. 9.1 kg / 20 lb MAXIMUM LOAD. 9.1 kg / 20 lb TC54-6127 MAXIMUM LOAD 9.1 kg / 20 lb MAXIMUM LOAD 34 kg / 75 lb MAXIMUM LOAD 6.8 kg / 15 lb MAXIMUM LOAD 9.1 kg / 20 lb WARNING: For use with most LCD/Plasma televisions weighing 34 kg / 75 lb or less.

More information

Boombot: Low Friction Coefficient Stair Climbing Robot Using Rotating Boom and Weight Redistribution

Boombot: Low Friction Coefficient Stair Climbing Robot Using Rotating Boom and Weight Redistribution Boombot: Low Friction Coefficient Stair Climbing Robot Using Rotating Boom and Weight Redistribution Sartaj Singh and Ramachandra K Abstract Boombot comprising four wheels and a rotating boom in the middle

More information

Minnesota Power Systems Conference Insulation Coordination Tutorial November 6, 2014

Minnesota Power Systems Conference Insulation Coordination Tutorial November 6, 2014 Minnesota Power Systems Conference Insulation Coordination Tutorial November 6, 2014 Presented By: Steve Brewer Senior Product Manager HPS Arrester Business Unit Traveling Wave Theory/ Overvoltage Protection

More information

METAL OXIDE VARISTOR (MOV)

METAL OXIDE VARISTOR (MOV) METAL OXIDE VARISTOR (MOV) How to Order SR 241 K 10 D S 40 X Type code Tolerance Disk Size Code Disk Type Lead Type or Taping Code Lead Cutting Special Request SR: Walsin ( volt) (From 180 to 112) Two

More information

3EK7 Distribution Class Surge Arresters. Answers for energy.

3EK7 Distribution Class Surge Arresters. Answers for energy. 3EK7 Distribution Class Surge Arresters Answers for energy. Siemens at Your Service As a global leader of the electronics industries, Siemens has been active in the fields of power transmission and distribution

More information

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R High Voltage Surge Arresters Buyer s Guide Section PEXLIM R Zinc Oxide Surge Arrester PEXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching

More information

sponsoring agencies.)

sponsoring agencies.) DEPARTMENT OF HIGHWAYS AND TRANSPORTATION VIRGINIA TESTING EQUIPMENT CORRELATION RESULTS SKID 1974, 1975, and 1978 N. Runkle Stephen Analyst Research opinions, findings, and conclusions expressed in this

More information

GENERAL. CONSTRUCTION External

GENERAL. CONSTRUCTION External Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest

More information

METER INSTALLATIONS

METER INSTALLATIONS 25 00 00 01 TALE OF CONTENTS Sheet 1 of 2 SECTION INDEX 25 00 00 01 OUTDOOR POLE MOUNTED PRIAMRY METERING STRUCTURE 25 00 01 01 CUSTOMER OWNED UNMETERED D/D LIGHT INSTALLATION 25 01 05 00 PRIMARY METERING

More information

Please confirm that all parts are present before beginning the factory exhaust system removal and db Performance Exhaust system installation.

Please confirm that all parts are present before beginning the factory exhaust system removal and db Performance Exhaust system installation. Please take time to read and understand these installation instructions. We recommend that the installation of this system be performed by a qualified service center or professional muffler installer who

More information

Understanding the Performance of Parallel Temporary Protective Grounds

Understanding the Performance of Parallel Temporary Protective Grounds Understanding the Performance of Parallel Temporary Protective Grounds Thomas Lancaster, Shashi Patel, Josh Perkel, & Anil Poda NEETRAC Introduction NEETRAC Test Program Test Results Modeling De-Rating

More information

High Voltage Surge Arresters Buyer s Guide Section PEXLIM P-Y

High Voltage Surge Arresters Buyer s Guide Section PEXLIM P-Y High Voltage Surge Arresters uyer s Guide Section PEXLIM P-Y Zinc Oxide Surge Arrester PEXLIM P-Y Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric

More information

Air Commander Part No , with air Part No , without air

Air Commander Part No , with air Part No , without air EASYSTREET Air Commander Part No. 27325, with air Part No. 27332, without air www.airliftcompany.com Please read these instructions completely before proceeding with installation. The oil level in the

More information

DynaVar Arresters IEC Line Discharge Classes 2, 3, 4 & 5

DynaVar Arresters IEC Line Discharge Classes 2, 3, 4 & 5 Section 204-1 204 DynaVar Arresters IEC Line Discharge Classes 2, 3, 4 & 5 Web: http://www.hubbellpowersystems.com E-mail: hpsliterature@hps.hubbell.com Printed in USA RGS 1M 204-2 Table of Contents Page

More information

High Voltage Surge Arresters Station Class

High Voltage Surge Arresters Station Class Power Transmission and Distribution High Voltage Surge Arresters Station Class Product Overview High Voltage High Protection Just as the Golden Gate Bridge has successfully defied all winds, weather and

More information

Metal Oxide Varistor (MOV) Data Sheet

Metal Oxide Varistor (MOV) Data Sheet Metal Oxide Varistor (MOV) Data Sheet Features Wide operating voltage (V 1mA ) range from 18V to 1800V Fast responding to transient over-voltage Large absorbing transient energy capability Low clamping

More information

Not all Low Voltage Switchgear is created equal

Not all Low Voltage Switchgear is created equal Not all Low Voltage Switchgear is created equal White Paper The must-have solution for power distribution systems Introduction Reliability and safety are the two most important criteria in the proper functioning

More information

3EK7 Distribution Class Surge Arresters. Answers for energy.

3EK7 Distribution Class Surge Arresters. Answers for energy. 3EK7 Distribution Class Surge Arresters Answers for energy. Siemens at Your Service As a global leader of the electronics industries, Siemens has been active in the fields of power transmission and distribution

More information

User Manual RC Electric Parts Electric Speed Controller (ESC) for Brushless Motors

User Manual RC Electric Parts Electric Speed Controller (ESC) for Brushless Motors User Manual RC Electric Parts Electric Speed Controller (ESC) for Brushless Motors Thank you for using RC Electric Parts ESC designed to meet your hobbies needs. As you'll find the ESC's settings are programmable

More information

Your Name Lab Section

Your Name Lab Section Pre-Lab Quiz / PHYS 224 Ohm s Law and Resistivity Your Name Lab Section 1. What do you investigate in this lab? 2. When 1.0-A electric current flows through a piece of cylindrical copper wire, the voltage

More information

Cost Benefit Analysis of Faster Transmission System Protection Systems

Cost Benefit Analysis of Faster Transmission System Protection Systems Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract

More information

Gas Discharge Tubes SL1002A Series

Gas Discharge Tubes SL1002A Series SL12A Series SL12A Series RoHS Agency Approvals AGENCY AGENCY FILE NUMBER E128662 2 Electrode GDT Graphical Symbol Additional Information Description The Broadband Optimized SL12A series has been especially

More information

TABLE of contents. Metal Oxide Varistor (MOV) Varistors-5D Series Varistors-7D Series Varistors-10D Series... 5

TABLE of contents. Metal Oxide Varistor (MOV) Varistors-5D Series Varistors-7D Series Varistors-10D Series... 5 TABLE of contents Subject Page Metal Oxide Varistor (MOV)..................................................... 1 Varistors-5D Series............................................................ 3 Varistors-7D

More information

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the

More information

UltraSIL polymer-housed VariSTAR station-class surge arresters

UltraSIL polymer-housed VariSTAR station-class surge arresters Surge s Catalog Data CA235013EN Supersedes August 2015 COOPER POWER SERIES UltraSIL polymer-housed VariSTAR station-class surge arresters General Eaton has set a new standard of excellence for polymer-housed

More information

Zinc Oxide Surge Arrester PEXLIM Q

Zinc Oxide Surge Arrester PEXLIM Q Zinc Oxide Surge Arrester Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. in areas with high lightning intensity and high

More information

CERTIFIED TEST REPORT

CERTIFIED TEST REPORT CP No.: CP0316 Rev. 01 Page: 1 of 22 CERTIFIED TEST REPORT COOPER POWER SYSTEMS FOUR POSITION SECTIONALIZING LOADBREAK SWITCH 12.5 ka Momentary and Making Rating REV. 01 DATE: December 3, 2004 ORIGINAL

More information

CDI15 6. Haar wavelets (1D) 1027, 1104, , 416, 428 SXD

CDI15 6. Haar wavelets (1D) 1027, 1104, , 416, 428 SXD CDI15 6. Haar wavelets (1D) 1027, 1104, 1110 414, 416, 428 SXD Notations 6.1. The Haar transforms 6.2. Haar wavelets 6.3. Multiresolution analysis 6.4. Compression/decompression James S. Walker A primer

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

Jaeshininformation Co., of Korea Distributor

Jaeshininformation Co., of Korea Distributor Earth Leakage Current Measurement and ELCB (RCD) trip analysis & Chemical Factory Inverter AC_DC_Battery_Temp Case study 2017. 09 Jaeshininformation Co., of Korea Distributor Our Goal We can follow IEEE1100

More information

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper

More information

PERFORMANCE DATA. The lightweight, durable, low-profile ROD CYLINDER SLIDES

PERFORMANCE DATA. The lightweight, durable, low-profile ROD CYLINDER SLIDES The lightweight, durable, low-profile H-Block design is the most versatile of our rod cylinder slides. It also has one of the highest ratings of load weight vs extension for its kind in the industry. The

More information

Introduction. Materials and Methods. How to Estimate Injection Percentage

Introduction. Materials and Methods. How to Estimate Injection Percentage How to Estimate Injection Percentage Introduction The Marel IN33-3 injector for pork bellies is a 5 needle, low-pressure conveyor type machine which utilizes a 3-gpm positive displacement pump and control

More information

Chapter 4. Vehicle Testing

Chapter 4. Vehicle Testing Chapter 4 Vehicle Testing The purpose of this chapter is to describe the field testing of the controllable dampers on a Volvo VN heavy truck. The first part of this chapter describes the test vehicle used

More information

W SERIES IMPULSE VOLTAGE TEST SYSTEM APPLICATION FEATURES

W SERIES IMPULSE VOLTAGE TEST SYSTEM APPLICATION FEATURES W SERIES IMPULSE VOLTAGE TEST SYSTEM Impulse Voltage Test System is used to generate impulse voltages from 100 KV to 2400 KV simulating lightning strokes and switching surges with energies up to 240 KJ.

More information

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier Performance of DC Motor Supplied From Single Phase AC-DC Rectifier Dr Othman A. Alnatheer Energy Research Institute-ENRI King Abdulaziz City for Science and Technology- KACST P O Box 6086, Riyadh 11442,

More information

Comments on sub clause of IEEE draft 802.3bt/D2.4 Presenter: Arkadiy Peker Co-author : Yair Darshan May 15, 2017

Comments on sub clause of IEEE draft 802.3bt/D2.4 Presenter: Arkadiy Peker Co-author : Yair Darshan May 15, 2017 Power Matters. TM Comments on sub clause 145.4.1 of IEEE draft 802.3bt/D2.4 Presenter: Arkadiy Peker Co-author : Yair Darshan May 15, 2017 1 Comments #121,122 Comment In the text Accessible external conductors

More information

BRAKE WINCHES B1200B B1200G B2500 B2500G B3500 B1500 B1500G B1500

BRAKE WINCHES B1200B B1200G B2500 B2500G B3500 B1500 B1500G B1500 BRAKE WINCHES B1500 B1200B B1200G B1500 B1500G B2500 B2500G B3500 B1200B, B1200G B1500, B1500G B2500, B2500G B3500 X 6 650 lb/295 kg 1 1200 lb/545 kg 6 728 lb/330 kg 1 1500 lb/680 kg 3 1554 lb/705 kg 1

More information

Medium-voltage surge arresters. Product guide. Version Catalogue HG siemens.com/energy/arrester

Medium-voltage surge arresters. Product guide. Version Catalogue HG siemens.com/energy/arrester Medium- surge arresters Product guide Catalogue HG 31.1 Version 2017 siemens.com/energy/arrester Medium- surge arresters Product guide Definition of surge arresters Surge arresters are used to protect

More information

Design Test Report Report No. EU1529-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 25 kv Veri*Lite Line Post 80S025

Design Test Report Report No. EU1529-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 25 kv Veri*Lite Line Post 80S025 Design Test Report Report No. EU1529-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 25 kv Veri*Lite Line Post 80S025 This test report records the results of laboratory tests made

More information

varistor plus catalog

varistor plus catalog varistor plus catalog Single Layer Varistor Technology Surface Mount & Leaded Products SEI electronics inc. P.O.Box 58789 Raleigh,NC 27658-8789 Tel. 1-888-sei-sei-sei Fax. 919-850-9504 www.seielect.com

More information

On the Applicability of Convex Relaxations for Matching Symmetric Shapes

On the Applicability of Convex Relaxations for Matching Symmetric Shapes On the Applicability of Convex Relaxations for Matching Symmetric Shapes Nadav Dym Weizmann Institute of Science In collaboration with Haggai Maron and Yaron Lipman Shape matching Finding isometries Shape

More information

KILOVOLT POWER SUPPLY

KILOVOLT POWER SUPPLY Instruction Sheet for the PASCO Model SF-9586 KILOVOLT POWER SUPPLY 012-02815D 1/95 $1.00 SF-9586 KILOVOLT POWER SUPPLY ON kv HIGH VOLTAGE ADJUST OFF 6 KV 6.3 VAC CAUTION! HIGH VOLTAGE 3 KV 3 KV Introduction

More information

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv 3EP1 Surge Arrester Metal-oxide surge arrester without series gaps for high-voltage systems up to U m = 170 kv Rated voltage up to 180 kv Nominal discharge current 10 ka, 8/20 µs Line discharge class LD1,

More information

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number: 15kV 200A Loadbreak Fuse Elbow Design Test Report Report Number: Date: RN-R2601 9/3/2015 Table of Contents 1. Partial Discharge Test Fuse Elbow... 2 2. AC Withstand Voltage Test - Fuse Elbow... 3 3. DC

More information

TABLE OF CONTENTS Page

TABLE OF CONTENTS Page TABLE OF CONTENTS Page Objective 3 Summary 3 Conclusion 3 Sample Preparation 4 Testing 4 Test Results 5 Summary of Test Results (Table 1) 6 Appendix I 7 Addendum 1 8 2 I. OBJECTIVE To evaluate the performance

More information

600 Amp Surge Arrester

600 Amp Surge Arrester R&D Center 497 Schooley s Mountain Road Hackettstown, NJ 07840-3906 Tele: 908-852-1122 Fax: 908-813-2091 TEST REPORT NUMBER: 379-17-12164 DATE: 4-3-2012 REPORT OF TEST ON 600 Amp Surge Arrester Statements

More information

Please read these instructions completely before proceeding with installation. Read all maintenance guidelines on page 7 before operating the vehicle.

Please read these instructions completely before proceeding with installation. Read all maintenance guidelines on page 7 before operating the vehicle. MN-643 (02511) ECR 5461 Kit No. 39205 Please read these instructions completely before proceeding with installation Item P/N Description Quantity A 26391 Driver-Side Beam Assembly 1 B 26414 Passenger-Side

More information

BOWTHORPE EMP MEH SURGE ARRESTERS (IEC) ENERGY /// MEH SURGE ARRESTERS IEC

BOWTHORPE EMP MEH SURGE ARRESTERS (IEC) ENERGY /// MEH SURGE ARRESTERS IEC BOWTHORPE EMP MEH SURGE ARRESTERS (IEC) GENERIC TECHNICAL DATA Maximum system voltage U m 800 System voltage U s 750 Nominal discharge current ka 20 High current impulse (4/10 µs) ka 100 Arrester class

More information

Reputable in Quality Smallwares

Reputable in Quality Smallwares Reputable in Quality Smallwares Traex is an innovator who continually looks for products that would ease users in operation. Traex products are designed for improved efficiency and value. Rack Max and

More information

Property Testing and Affine Invariance Part II Madhu Sudan Harvard University

Property Testing and Affine Invariance Part II Madhu Sudan Harvard University Property Testing and Affine Invariance Part II Madhu Sudan Harvard University December 29-30, 2015 IITB: Property Testing & Affine Invariance 1 of 29 Review of last lecture Property testing: Test global

More information

Unit WorkBook 4 Level 4 ENG U13 Fundamentals of Thermodynamics and Heat Engines UniCourse Ltd. All Rights Reserved. Sample

Unit WorkBook 4 Level 4 ENG U13 Fundamentals of Thermodynamics and Heat Engines UniCourse Ltd. All Rights Reserved. Sample Pearson BTEC Levels 4 Higher Nationals in Engineering (RQF) Unit 13: Fundamentals of Thermodynamics and Heat Engines Unit Workbook 4 in a series of 4 for this unit Learning Outcome 4 Internal Combustion

More information

A Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun

A Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun A Theoretical, Computational, and Experimental Analysis of an Interdigital Armature in a High Velocity Railgun Robert MacGregor and Sikhanda Satapathy August, 2002 Institute for Advanced Technology The

More information

Bimba Extruded Linear Thrusters 2X FF X EE DP 2X DD 2X Ø DD X EE DP U V W X Y Z R S Dimensions - ET T B 4X TAP AA THRU Ø BB C BORE X CC DP (OPP.SIDE)

Bimba Extruded Linear Thrusters 2X FF X EE DP 2X DD 2X Ø DD X EE DP U V W X Y Z R S Dimensions - ET T B 4X TAP AA THRU Ø BB C BORE X CC DP (OPP.SIDE) Bimba Extruded Linear Thrusters Engineering Specifications Maximum Operating Pressure 140 psi (10 bar) Temperature Range 15 to 160 degrees F (-10 to 70 degrees C) Expected Service Life 1,500 miles (with

More information

Application of NVH Techniques to Engine Production Line Test

Application of NVH Techniques to Engine Production Line Test 05NVC49 Application of NVH Techniques to Engine Production Line Test Copyright 2004 SAE International Alex Alvey Tecumseh Products Company Gabriella Cerrato Jay MTS Systems Corp. ABSTRACT A major manufacturer

More information

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE. RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE. Alfonso Avila Ramírez. Corporativo Arian, S.A. de C.V., Hidalgo 6 Santa Ana Tlacotenco,

More information

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage 1500 kva Padmount Transformer 12470 delta Primary Voltage 208Y/120 Secondary Voltage Cooper Power Systems Proposal Number: BED1096719 Date: January 4, 2010 Revision 00 Item Number: 00001 Item Details Customer

More information

ANNEX D APPENDIX D M915A5, LINE HAUL TRACTOR TRUCK KIT SPECIFIC REQUIREMENTS. Revision Date Pages Description Draft April 2012 ALL Ron Swanson

ANNEX D APPENDIX D M915A5, LINE HAUL TRACTOR TRUCK KIT SPECIFIC REQUIREMENTS. Revision Date Pages Description Draft April 2012 ALL Ron Swanson ANNEX D APPENDIX D M915A5, LINE HAUL TRACTOR TRUCK KIT SPECIFIC REQUIREMENTS Revision Date Pages Description Draft 1.0 9 April 2012 ALL Ron Swanson Formating, insert revision table and acronyms. Verified

More information

TOYOTA SIENNA TRAILER WIRE HARNESS Preparation

TOYOTA SIENNA TRAILER WIRE HARNESS Preparation Preparation Part Number: PT791-08150 (non-se) PT791-08102 (SE only) Kit Contents Item # Quantity Reqd. Description 1 1 Trailer Module Harness 2 1 4-Flat Harness 3 1 Battery Power Wire Harness 4 1 Mounting

More information

Impulse Voltage Test System, Q Structure, kV

Impulse Voltage Test System, Q Structure, kV TCDYQ Series Impulse Voltage Test System, Q Structure, 200-3600kV Applications: Shunt reactors Power transformers Distribution transformer Instrument transformers Cables (type tests) Bushings Arresters

More information

K-Limiter high ampere Companion II fuse

K-Limiter high ampere Companion II fuse Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently

More information

Common Rail Injection System On-Line Parameter Calibration for Precise Injection Quantity Control

Common Rail Injection System On-Line Parameter Calibration for Precise Injection Quantity Control 2010 American Control Conference Marriott Waterfront Baltimore MD USA June 30-July 02 2010 WeC19.6 Common Rail Injection System On-Line Parameter Calibration for Precise Injection Quantity Control Fengjun

More information

TRANSIENT MAGNETIC FLUX DENSITY MEASUREMENT RESULTS ON A FUSELAGE-LIKE TEST SETUP AND INVESTIGATION OF THE EFFECTS OF APERTURES

TRANSIENT MAGNETIC FLUX DENSITY MEASUREMENT RESULTS ON A FUSELAGE-LIKE TEST SETUP AND INVESTIGATION OF THE EFFECTS OF APERTURES TRANSIENT MAGNETIC FLUX DENSITY MEASUREMENT RESULTS ON A FUSELAGE-LIKE TEST SETUP AND INVESTIGATION OF THE EFFECTS OF APERTURES S. A. Sebo, R. Caldecott, Ö. Altay, L. Schweickart,* J. C. Horwath,* L. C.

More information

Distribution of Electric Field Analysis in 36 kv Roof Top Bushing by using FEM Techniques

Distribution of Electric Field Analysis in 36 kv Roof Top Bushing by using FEM Techniques Journal for Research Volume 02 Issue 06 August 2016 ISSN: 2395-7549 Distribution of Electric Field Analysis in 36 kv Roof Top Bushing by using FEM Techniques Krunal J. Amodwala PG Student Department of

More information

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring ABB is a leader in power and automation technologies that enable utility and industry customers to

More information

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard A manufacturer s view of bushing reliability, testing and analysis By Lars Jonsson Håkan Rudegard 1 A manufacturer s view of bushing reliability, testing and analysis Lars Jonsson Håkan Rudegard ABB Sweden

More information

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number: 25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.

More information