1 Application of the Performance Validation Tool for the Evaluation of NSSS Control System Performance Sohn Suk-Whun

2 1 Pre-Op Dynamic Test 2 Test Results 3 Pre-PAT Dynamic Test 4 Conclusion IAEA IAEA Conference

3 1 Pre-Op Dynamic Test IAEA IAEA Conference Conference

4 OPR1 NSSS Control System Composition SBCS SG Press. Control TBV RRS T AVG Control CEA Group PPCS PZR Press. Control Spray Valve, Heaters FWCS SG Level Control DFWCV, EFWCV, MFWP Speed RPCS Rapid Rx Power Reduction CEA Group 5 or 4+5, TCV Dormant error can cause the reactor trip. Experience : YGN 5&6 Startup Period (Changed Hardware) PLCS PZR Level Control Charging Valve, Letdown Isolation Valve OPR1 : Optimized Power Reactor 1MW NSSS : Nuclear Steam Supply System SBCS : Steam Bypass Control System FWCS : Feedwater Control System RRS : Reactor Regulating System PPCS : Preaaurizer Pressure Control System PLCS : Pressurizer Level Control System 4

5 Tests during Startup NPPs under Construction We experienced a reactor trip in this stage due to an error in control system caused by programmer s oversight (YGN 5&6) Commercial Operation PAT Dynamic Test FAT : Factory Acceptance Test Pre-op : Pre-operational PAT : Power Ascension Test Pre-Op Test Static Test (Plant Site) FAT Static Test (Factory) Design/ Fabrication (V&V Methodology) 5

6 Tests (Hardware Replacement) Operating NPPs Commercial Operation Skip Power Ascension Test Potential Risk of Real Plant Testing Economical Loss : Reduction of Electricity Production Pre-op Dynamic Test Dynamic Test FAT : Factory Acceptance Test Pre-op : Pre-operational PAT : Power Ascension Test Pre-Op Test Static Test (Plant Site) FAT Static Test (Factory) Design/ Fabrication (V&V Methodology) 6

7 Synopsis of Pre-op Dynamic Test Hardware Functional Test Design Spec. New Control System Hardware Performance Validation Test PAT Simulation Computer Code () Modeling PAT Simulation Operability Test Old Control System Hardware PAT Simulation 7

8 Performance Validation Test Computer Code Modeling of Control System according to Design Spec. Compare the results After bypass its own control system, it connect with replaced H/W Sensor Signal (Control System) Component Control Signal 8

9 Synopsis of Pre-op Dynamic Test Hardware Functional Test Design Spec. New Control System Hardware Performance Validation Test PAT Simulation Computer Code () Modeling PAT Simulation Operability Test Old Control System Hardware PAT Simulation 9

10 Operability Test Sensor Signal (Control System) Component Control Signal Compare the results Sensor Signal (Control System) Component Control Signal 1

11 Configuration of Test Equipment Signal Interface Module 11

12 2 Test Results IAEA IAEA Conference Conference

13 Selection of Test Cases Load Rejection to House Load Loss of a Main Feedwater Pump Reactor Trip Turbine Power 1% Step Decrease (1 to 9%) Turbine Power 5%/min Ramp Decrease (1 to 3%) Valve Transfer (Increasing Direction, 2%) Valve Transfer (Decreasing Direction, 18%) 13

14 YGN 3&4 Test Result (1/6) Load Rejection to House Load (Performance Validation Test) SG 1 NR Level, % FW1 Flow DP, % SG 1 Steam Flow DP, % SG 1 pressure, psia

15 YGN 3&4 Test Result (2/6) Load Rejection to House Load (Operability Test) FOXBORO (Old) TRICONEX (New) 8 FOXBORO (Old) TRICONEX (New) SG 1 NR Level, % FW1 Flow DP, % SG 1 Steam Flow DP, % FOXBORO (Old) TRICONEX (New) SG 1 pressure, psia FOXBORO (Old) TRICONEX (New)

16 YGN 3&4 Test Result (3/6) Loss of a Main Feedwater Pump (Performance Validation Test) SG 1 NR Level, % FW1 Flow DP, % SG 1 Steam Flow DP, % SG 1 pressure, psia

17 YGN 3&4 Test Result (4/6) Loss of a Main Feedwater Pump (Operability Test) FOXBORO (Old) TRICONEX (New) 8 FOXBORO (Old) TRICONEX (New) SG 1 NR Level, % 6 4 FW1 Flow DP, % SG 1 Steam Flow DP, % FOXBORO (Old) TRICONEX (New) SG 1 pressure, psia FOXBORO (Old) TRICONEX (New)

18 YGN 3&4 Test Result (5/6) Reactor Trip (Fail Case) : PI Controller Option Related Error 1 7 SG 1 NR Level, % DFWCV 1 Position Demand, % FW1 Flow DP, % 6 4 FW1 Flow DP, % Enlargement 18

19 YGN 3&4 Test Result (6/6) Reactor Trip (Success Case) 1 1 SG 1 NR Level, % DFWCV 1 Position Demand, % Average Temperature, Deg.F Pressurizer Pressure, psia

20 3 Pre-PAT Dynamic Test IAEA IAEA Conference Conference

21 Suggest of Pre-PAT Dynamic Test NPPs under Construction Pre-PAT Dynamic Test Commercial Operation PAT Dynamic Test FAT : Factory Acceptance Test Pre-op : Pre-operational PAT : Power Ascension Test Pre-Op Test Static Test (Plant Site) FAT Static Test (Factory) Design/ Fabrication (V&V Methodology) 21

22 Individual Test including Component FW Flow Stm Flow SG Level Rx Power Reactor Power AFW PC Main Steam MFWPs Speed Demand FWCS 6" 8" M M 8" HO HO Chemical Injection PC Isolation 6" Steam Generator 1 8" HO HO 2" 2" 18" 16" PC 12" Feedwater Steam Generator 2 BOP PCS RCS(cold) RCS(hot) BOP : Balance of Plant PCS : Plant Computer System FWCS : Feedwater Control System 22

23 Integrated Test SG Level Stm Flow FW Flow FWCS MFWP Speed Demand DFWCV EFWCV Permissive Stm HDR Press. SBCS Quick Open Modulation TBV A/D D/A PZR Press. PPCS Spray Valve PZR Level PLCS CCV TLI Hot Leg Temp. Rx Power RRS AMI, AWP AMI, AWP CEA Direction, Rate CEDMCS Cold Leg Temp. FWCS : Feedwater Control System SBCS : Steam Bypass Control System PPCS : Pressurizer Pressure Control System PLCS : Pressurizer Level Control System RRS : Reactor Regulating System RPCS : Reactor Power Cutback System TCS : Turbine Control System DFWCV : Downcomer Feedwater Control Valve EFWCV : Economizer Feedwater Control Valve TBV : Turbine Bypass Valve AMI : Automatic Motion Inhibit AWP : Automatic Withdrawal Prohibit RPCS Arm, Drop TBN Load Increase Inhibit TBN Setback TBN Runback TCS DAQ 23

24 4 Conclusion IAEA IAEA Conference Conference

25 Conclusion We develop the new tool to validate the performance of control and monitoring system. The tool showed a greater performance than expected. (We found the lots of error during YGN 3&4 Project) We try to expand the scope of tool to the NPPs under construction. (Pre-PAT Dynamic Test) We changed the name of our engineering simulator from win-npa to N-Fast. -FAST NSSS Fast Analysis and Simulat iontool 25

26

AP Plant Operational Transient Analysis

AP Plant Operational Transient Analysis www.ijnese.org International Journal of Nuclear Energy Science and Engineering Volume 3 Issue 2, June 2013 AP1000 1 Plant Operational Transient Analysis LIU Lixin 1, ZHENG Limin 2 Shanghai Nuclear Engineering

More information

Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance MP-SEE-THRU-01 Rev. 018

Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance MP-SEE-THRU-01 Rev. 018 Student Operating Procedure Millstone Station Startup and Operation of SEE-THRU Nuclear Power Plant for Student Performance Approval Date: 01/12/2011 Effective Date: 01/12/2011 TABLE OF CONTENTS 1. PURPOSE...3

More information

AP1000 European 7. Instrumentation and Controls Design Control Document

AP1000 European 7. Instrumentation and Controls Design Control Document 7.7 Control and Instrumentation Systems The function of the AP1000 control systems is to establish and maintain the plant operating conditions within prescribed limits. The control system improves plant

More information

CONTROL SYSTEM DESIGN FOR A SMALL PRESSURIZED WATER REACTOR

CONTROL SYSTEM DESIGN FOR A SMALL PRESSURIZED WATER REACTOR CONTROL SYSTEM DESIGN FOR A SMALL PRESSURIZED WATER REACTOR Peiwei Sun and Jianmin Zhang Xi'an Jiaotong University No. 28 Xianing Road West, Xi'an, Shaanxi 710049, China sunpeiwei@mail.xjtu.edu.cn; zhangjm@mail.xjtu.edu.cn

More information

PLANT HATCH FEEDWATER SYSTEM OPERATING EXPERIENCE. Significant events from 2015

PLANT HATCH FEEDWATER SYSTEM OPERATING EXPERIENCE. Significant events from 2015 PLANT HATCH FEEDWATER SYSTEM OPERATING EXPERIENCE Significant events from 2015 ICES Report #315779 Hatch Unit 2 March 10, 2015 Startup from 2R23 refueling outage Feedwater Control System (RWL Control)

More information

AP1000 European 7. Instrumentation and Controls Design Control Document

AP1000 European 7. Instrumentation and Controls Design Control Document 7.3 Engineered Safety Features AP1000 provides instrumentation and controls to sense accident situations and initiate engineered safety features (ESF). The occurrence of a limiting fault, such as a loss

More information

S. Y. Park (*), K. I. Ahn

S. Y. Park (*), K. I. Ahn IEM on Strengthening R&D Effectiveness in the Light of the Accident at the Fukushima Daiichi NPP, Vienna, 16-0 Feb. 015 Assessment of the Mitigative Strategy using External Coolant Injection for OPR-1000

More information

The Establishment and Application of TRACE/FRAPTRAN Model for Kuosheng Nuclear Power Plant

The Establishment and Application of TRACE/FRAPTRAN Model for Kuosheng Nuclear Power Plant The Establishment and Application of /FRAPTRAN Model for Kuosheng Nuclear Power Plant S. W. Chen, W. K. Lin, J. R. Wang, C. Shih, H. T. Lin, H. C. Chang, W. Y. Li Abstract Kuosheng nuclear power plant

More information

Evaluating Generation Considering All Plant Losses and Efficiencies Duane H. Morris, P.E. Tennessee Valley Authority

Evaluating Generation Considering All Plant Losses and Efficiencies Duane H. Morris, P.E. Tennessee Valley Authority Evaluating Generation Considering All Plant Losses and Efficiencies Duane H. Morris, P.E. Tennessee Valley Authority James W. Brower Scientech a business unit of Curtiss-Wright Flow Control Company Evaluating

More information

The IAEA does not normally maintain stocks of reports in this series.

The IAEA does not normally maintain stocks of reports in this series. IAEA-TECDOC- The IAEA does not normally maintain stocks of reports in this series. However, microfiche copies SAFETY ASPECTS OF STATION BLACKOUT AT NUCLEAR POWER PLANTS IAEA, VIENNA, 1985 IAEA-TECDOC-332

More information

The ADS-IDAC Dynamic PSA Platform with Dynamically Linked System Fault Trees

The ADS-IDAC Dynamic PSA Platform with Dynamically Linked System Fault Trees The ADS-IDAC Dynamic PSA Platform with Dynamically Linked System Fault Trees Mihai Diaconeasa Center for Reliability and Resilience Engineering The B. John Garrick Institute for the Risk Sciences University

More information

Analysis of Turbine Missile & Turbine-Generator Overspeed Protection System Failure Probability at NPPs: A case study from PSA perspective

Analysis of Turbine Missile & Turbine-Generator Overspeed Protection System Failure Probability at NPPs: A case study from PSA perspective Protection System Failure Probability at NPPs: A case study from D. Kančev, S. Heussen, J. U. Klügel, P. Drinovac, T. Kozlik NPP Goesgen-Daeniken AG, Kraftwerkstrasse CH-4658 Daeniken, Switzerland EDMS

More information

National Research Council

National Research Council National Research Council The Initial Sources of Power February 28, 2013, Washington DC, USA. M. M. Adibi IRD Corporation Potomac, Maryland, USA madibird@aol.com (c) IRD 2013 1 The impact of a blackout

More information

HRSG Operational Challenges and Siemens Solutions

HRSG Operational Challenges and Siemens Solutions Intelligent Energy Solutions HRSG Operational Challenges and Siemens Solutions Gary Gong Ph.D P.E. Siemens Energy Inc 4400 N Alafaya Trl Orlando, FL 32766 Siemens Energy, Inc. Siemens 2010. All Energy,

More information

Electro hydraulic actuating system is a complete modular unit with a wide range of actuator cylinders (type ASM) having a

Electro hydraulic actuating system is a complete modular unit with a wide range of actuator cylinders (type ASM) having a Electro Hydraulic Actuating System 7 Electro hydraulic actuating system is a complete modular unit with a wide range of actuator cylinders (type ASM) having a force of about 100 tonnes and large stroke.

More information

Transient Analysis for Simulator Validation. Jeffrey A. Borkowski 2008 US Users Group Meeting Tempe, Arizona October

Transient Analysis for Simulator Validation. Jeffrey A. Borkowski 2008 US Users Group Meeting Tempe, Arizona October Transient Analysis for Simulator Validation Jeffrey A. Borkowski 2008 US Users Group Meeting Tempe, Arizona October 22-24 2008 Advanced Training Simulator Models Engineering-grade model core model S3R

More information

Document Code: 1 (8) Issuing date: Status:

Document Code: 1 (8) Issuing date: Status: Document Code: 1 (8) Project : MULTI FUEL CFB BOILER SIMULATOR Author: Approved: Employer: JJA Document title: SYSTEM DESCRIPTION TURBINE CONTROL Submitted for: Employer reference: Other information: Document

More information

ABB PSPG-E7 MODAKOND More efficient and dynamic unit control. ABB Group May 8, 2014 Slide 1 ABB

ABB PSPG-E7 MODAKOND More efficient and dynamic unit control. ABB Group May 8, 2014 Slide 1 ABB ABB PSPG-E7 MODAKOND More efficient and unit control Group May 8, 2014 Slide 1 OPTIMAX MODAKOND Challenge Conventional solution for frequency control (or to improve control performance for flexible plant

More information

PID Tuning Case Study Fixing oscillation of desuperheating temperature controller resulting in significant increase in electricity production 1

PID Tuning Case Study Fixing oscillation of desuperheating temperature controller resulting in significant increase in electricity production 1 1 1. Introduction The pressure in a 6 barg steam network is controlled by letdown from the 60 barg steam network through either a turbine or through a direct let-down. The letdown from the 60 barg to the

More information

F-class OpFlex controls advancements

F-class OpFlex controls advancements GE Power & Water F-class OpFlex controls advancements Bob Bellis, F-class/OpFlex Controls Product Manager CTOTF FALL CONFERENCE COEUR D'ALENE, IDAHO SEPTEMBER 20-24, 2015 Imagination at work GE Power &

More information

Oconee Nuclear Station ALLOY 600 REPAIRS 1EOC23

Oconee Nuclear Station ALLOY 600 REPAIRS 1EOC23 Oconee Nuclear Station ALLOY 600 REPAIRS 1EOC23 We re requiring more inspections due to susceptibility of material to cracking Some utilities have implemented mitigative actions Stress improvement Weld

More information

OPAL : Commissioning a New Research Reactor. IAEA Conference, Sydney, November 2007

OPAL : Commissioning a New Research Reactor. IAEA Conference, Sydney, November 2007 OPAL : Commissioning a New Research Reactor IAEA Conference, Sydney, November 2007 Project Timeline Government announcement 1997 Design and licence application 2000/2001 Construction Licence April 2002

More information

AP1000 European 5. Reactor Coolant System and Connected Systems Design Control Document

AP1000 European 5. Reactor Coolant System and Connected Systems Design Control Document CHAPTER 5 REACTOR COOLANT SYSTEM AND CONNECTED SYSTEMS 5.1 Summary Description This section describes the reactor coolant system (RCS) and includes a schematic flow diagram of the reactor coolant system

More information

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER E: THE REACTOR COOLANT SYSTEM AND RELATED SYSTEMS

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER E: THE REACTOR COOLANT SYSTEM AND RELATED SYSTEMS PAGE : 1 / 13 4. PRESSURISER 4.1. DESCRIPTION The pressuriser (PZR) is a pressurised vessel forming part of the reactor coolant pressure boundary (CPP) [RCPB]. It comprises a vertical cylindrical shell,

More information

Forsmark 12. S3K Applications. Thomas Smed US User Group Meeting Arizona, October 2008

Forsmark 12. S3K Applications. Thomas Smed US User Group Meeting Arizona, October 2008 Forsmark 12 S3K Applications Thomas Smed US User Group Meeting Arizona, October 2008 Introduction It is well-known that we have vast experience in providing S3R (and RAMONA) to training simulators It may

More information

Hope Creek Variable Frequency Drive

Hope Creek Variable Frequency Drive Hope Creek Variable Frequency Drive 2018 Power Plant Simulation Conference Houston, TX January 14-18, 2018 Hope Creek Variable Frequency Drive Simulation John Stone Senior Engineer - CORYS Presentation

More information

LESSONS LEARNED FORSMARK EVENT Presented To IEEEE

LESSONS LEARNED FORSMARK EVENT Presented To IEEEE LESSONS LEARNED FORSMARK EVENT Presented To IEEEE Thomas Koshy Member of the Task Group on Forsmark Chief of Mechanical & Electrical Engineering Office of Research, USNRC Thomas.Koshy@nrc.gov 1 Agenda

More information

The B&W mpower TM Small Modular Reactor I&C Design, Architecture and Challenges

The B&W mpower TM Small Modular Reactor I&C Design, Architecture and Challenges The B&W mpower TM Small Modular Reactor I&C Design, Architecture and Challenges IAEA Technical Meeting May 23, 2013 B.K. Arnholt 2013 Generation mpower LLC All rights reserved. Agenda Introduction to the

More information

IMPLEMENTATION OF THE RCP SHIELD MECHANICAL SEAL MODEL IN THE COMANCHE PEAK PRA

IMPLEMENTATION OF THE RCP SHIELD MECHANICAL SEAL MODEL IN THE COMANCHE PEAK PRA IMPLEMENTATION OF THE RCP SHIELD MECHANICAL SEAL MODEL IN THE COMANCHE PEAK PRA Nathan Larson Principal Engineer Daniel Tirsun Fellow Engineer Aaron Moreno Senior Engineer Glen Rose, TX SHIELD is a trademark

More information

Appendix G Examples and Recommended Methods

Appendix G Examples and Recommended Methods Reporting Outages to the Generating Availability Data System (GADS) Introduction The examples in this appendix illustrate the reporting of outages and deratings to GADS. They are based on a fictional 600

More information

DEVELOPMENT OF A 3D MODEL OF TUBE BUNDLE OF VVER REACTOR STEAM GENERATOR

DEVELOPMENT OF A 3D MODEL OF TUBE BUNDLE OF VVER REACTOR STEAM GENERATOR DEVELOPMENT OF A 3D MODEL OF TUBE BUNDLE OF VVER REACTOR STEAM GENERATOR V.F. Strizhov, M.A. Bykov, A.Ye. Kiselev A.V. Shishov, A.A. Krutikov, D.A. Posysaev, D.A. Mustafina IBRAE RAN, Moscow, Russia Abstract

More information

AE94.3A Flexibility Upgrade

AE94.3A Flexibility Upgrade AE94.3A Flexibility Upgrade In the current power generation market, economic and regulatory factors are forcing Gas Turbine operators to be more flexible in terms of faster startup times and extended operational

More information

AUTOMATED CFD-SIMULATION OF A TURBOCHARGER ON A HIGH PERFORMANCE BMW DIESEL ENGINE BY USE OF DFBI M. REICHHART

AUTOMATED CFD-SIMULATION OF A TURBOCHARGER ON A HIGH PERFORMANCE BMW DIESEL ENGINE BY USE OF DFBI M. REICHHART STAR Global Conference 2016, Prague BMW Group, March 7, 2016 AUTOMATED CFD-SIMULATION OF A TURBOCHARGER ON A HIGH PERFORMANCE BMW DIESEL ENGINE BY USE OF DFBI M. REICHHART CONTENT TURBOCHARGER FORMER WORKFLOW

More information

Siemens SGT6-5000F Gas Turbine Technology Update

Siemens SGT6-5000F Gas Turbine Technology Update Siemens SGT6-5000F Gas Turbine Technology Update POWER-GEN International Abstract This presentation will update the industry on the latest developments of Siemens SGT6-5000F gas turbine. Since its introduction

More information

INDUSTRIAL APPLICATIONS OF GAS TURBINES Fall 2010 Course

INDUSTRIAL APPLICATIONS OF GAS TURBINES Fall 2010 Course INDUSTRIAL APPLICATIONS OF GAS TURBINES Fall 2010 Course Session #7 Emission Reduction Case Study by Christian Kaufmann Innovative Steam Technologies Introduction Function of Catalysts Efficiency of the

More information

SOAPP-CT.25 WorkStation 11/1/00. Equipment List Project: Sample Outputs Conceptual Design: Cogen, 1 x 27 MW, NG, Quarterly

SOAPP-CT.25 WorkStation 11/1/00. Equipment List Project: Sample Outputs Conceptual Design: Cogen, 1 x 27 MW, NG, Quarterly GENERAL PROJECT DATA Ambient Conditions Maximum Site Ambient Dry Bulb Temp 85.00 F Maximum Site Ambient Wet Bulb Temp 74.00 F Minimum Site Ambient Dry Bulb Temp -20.00 F Site Average Annual Rainfall 31.00

More information

For Operation in the Control Cabinet 3RW Soft Starters

For Operation in the Control Cabinet 3RW Soft Starters General Data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations

More information

MCD Evaluation Board for Pump Motor Control Reference Guide

MCD Evaluation Board for Pump Motor Control Reference Guide MCD Evaluation Board for Pump Motor Control Reference Guide Overview TB6605FTG speed close loop reference module is a motor controller evaluation kit, for 10V~28V power supply motor driver. The reference

More information

AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface. September 2017

AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface. September 2017 AP1000 Nuclear Power Plant Squib Valve Design Challenges & Regulatory Interface September 2017 Randy C. Ivey Director Supplier Quality Oversight Westinghouse Electric Company AP1000 is a trademark or registered

More information

TANZANIA BUREAU OF STANDARDS

TANZANIA BUREAU OF STANDARDS EDC 5 (5235) P3 Mini-Grid Systems DRAFT TANZANIA STANDARD (Draft for comments only) Part 2: Application of Inverters TANZANIA BUREAU OF STANDARDS TBS 2017 First Edition 2017 T able of content 1 2 3 4 5

More information

2001 Conference on SCR and SNCR

2001 Conference on SCR and SNCR 2001 Conference on SCR and SNCR First Year's Operating Experience with SCR on 600MW PRB Fired Boiler May 17, 2001 New Madrid SCR Retrofit Project Overview Unit 2 Base Award (6/98); Unit 1 Option Award

More information

CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix

CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix CSP-gas hybrid plants: Cost effective and fully dispatchable integration of CSP into the electricity mix Erik Zindel Director Marketing CSP (Power Block) Energy Sector Siemens AG 2012 Copyright Siemens

More information

Possible Change of Ship Design Including Engine Room about Emissions of NOx and SOx

Possible Change of Ship Design Including Engine Room about Emissions of NOx and SOx Possible Change of Ship Design Including Engine Room about Emissions of NOx and SOx Masaki Ohtsu Mitsui Engineering & Shipbuilding Co., Ltd. February 28, 2007 Introduction of Mitsui -3 rd position in production

More information

ALBA Power Supplies Activities. R. Petrocelli D. Alloza

ALBA Power Supplies Activities. R. Petrocelli D. Alloza ALBA Power Supplies Activities Magnet Power Supply System Overview 2 Distribution of Power Supplies in Service Area 3 4 5 OVERVIEW OF STORAGE RING POWER SUPPLIES MAGNET QUANTITY Nº PS SPARE Current (A)

More information

Farhana Shirin Lina BSC.(Electrical and Electronic) Memorial University of Newfoundland & Labrador

Farhana Shirin Lina BSC.(Electrical and Electronic) Memorial University of Newfoundland & Labrador Farhana Shirin Lina BSC.(Electrical and Electronic) Memorial University of Newfoundland & Labrador Introduction Research Objectives Different Control Systems System Modeling and Control Controller Design

More information

AUTOMATED START/STOP SYSTEM FOR LOCOMOTIVES

AUTOMATED START/STOP SYSTEM FOR LOCOMOTIVES ELCON ELECTRICAL CONTROLS. AUTOMATED START/STOP SYSTEM FOR LOCOMOTIVES PAGE 1 4/2/2007 INTRODUCTION As fuel prices increase the need for systems that can reduce the fuel consumption of the locomotive fleet

More information

Local Union No International Brotherhood of Electrical Workers, AFL-CIO P. O. Box 4790 Walnut Creek, California 94596

Local Union No International Brotherhood of Electrical Workers, AFL-CIO P. O. Box 4790 Walnut Creek, California 94596 Local Union No. 1245 International Brotherhood of Electrical Workers, AFL-CIO P. O. Box 4790 Walnut Creek, California 94596 Company proposes adoption of the attached three versions of the revised Assistant

More information

By: Eugenijus Uspuras Algirdas Kaliatka Sigitas Rimkevicius ASME 2012 Verification & Validation Symposium May 2-4, 2012, Las Vegas, NV

By: Eugenijus Uspuras Algirdas Kaliatka Sigitas Rimkevicius ASME 2012 Verification & Validation Symposium May 2-4, 2012, Las Vegas, NV Computer codes validation for transient analysis at nuclear power plants with RBMK-1500 reactor By: Eugenijus Uspuras Algirdas Kaliatka Sigitas Rimkevicius ASME 2012 Verification & Validation Symposium

More information

FCC Special Valves Best Practices to Increase Performance, Reliability & Service Life

FCC Special Valves Best Practices to Increase Performance, Reliability & Service Life FCC Special Valves Best Practices to Increase Performance, Reliability & Service Life Mauro Natalini Deputy Manager - Valve Engineering Dept. REMOSA Cagliari, Italy Tel +39.070.2020237 / Mob +39.366.6891228

More information

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller Bulletin of Electrical Engineering and Informatics ISSN: 2302-9285 Vol. 5, No. 3, September 2016, pp. 271~283, DOI: 10.11591/eei.v5i3.593 271 Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM

More information

Rosatom Seminar on Russian Nuclear Energy Technologies and Solutions

Rosatom Seminar on Russian Nuclear Energy Technologies and Solutions ROSATOM STATE ATOMIC ENERGY CORPORATION ROSATOM VVER-100 Reactor Plant and Safety Systems Rosatom Seminar on Russian Nuclear Energy Technologies and Solutions N.S. Fil Chief Specialist, OKB GIDROPRESS

More information

OptiRamp Rational SCADA

OptiRamp Rational SCADA OptiRamp Rational SCD OptiRamp on the Edge The OptiRamp Rational SCD solution brings data on the edge into OptiRamp to fully light up your total value stream and improve model accuracy, simulation, optimization,

More information

Le stockage d énergie au Portugal : la flexibilité au service de la variabilité

Le stockage d énergie au Portugal : la flexibilité au service de la variabilité Le stockage d énergie au Portugal : la flexibilité au service de la variabilité Pierre-Yves Lowys Hydro 21, Grenoble 4 Novembre 2016 Power regulation need increases 12000000 10800000 9600000 8400000 7200000

More information

Week 10. Gas Power Cycles. ME 300 Thermodynamics II 1

Week 10. Gas Power Cycles. ME 300 Thermodynamics II 1 Week 10 Gas Power Cycles ME 300 Thermodynamics II 1 Today s Outline Gas power cycles Internal combustion engines Four-stroke cycle Thermodynamic cycles Ideal cycle ME 300 Thermodynamics II 2 Gas Power

More information

Meeting product specifications

Meeting product specifications Optimisation of a diesel hydrotreating unit A model based on operating data is used to meet sulphur product specifications at lower DHT reactor temperatures with longer catalyst life Jose Bird Valero Energy

More information

Shop and Service Center Motors

Shop and Service Center Motors Shop and Service Center Motors Nuclear Services / Field Services Nuclear Component Repair Center Auxiliary Motor Services Background Westinghouse s Nuclear Component Repair Center (NCRC) in Madison, Pennsylvania

More information

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION Presentation by Engr. O. C. Akamnnonu Chief Executive Officer, Ikeja Electricity Distribution Company AGENDA WORK THROUGH

More information

Is Throttle Pressure Control a Self- Regulating or an Integrating Process?

Is Throttle Pressure Control a Self- Regulating or an Integrating Process? Output Is Control a Self- Regulating or an Integrating Process? By Jacques F. Smuts, Ph.D., P.E. Self-regulating and integrating processes respond differently and require the use of different tuning methods.

More information

ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES

ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES ANALYSIS OF BREST-OD-300 SAFETY DURING ANTICIPATED OPERATIONAL OCCURRENCES D.V. Didorin, V.A. Kogut, A.G. Muratov, V.V. Tyukov, A.V. Moiseev (NIKIET, Moscow, Russia) 1. Brief description of the aim and

More information

GE Oil & Gas. Masoneilan * Engineered Products. Valve Solutions and Services for the World s Toughest Applications. Experience Knowledge Technology

GE Oil & Gas. Masoneilan * Engineered Products. Valve Solutions and Services for the World s Toughest Applications. Experience Knowledge Technology GE Oil & Gas Masoneilan * Engineered Products Valve Solutions and Services for the World s Toughest Applications Experience Knowledge Technology INTEGRATED SMART ENGINEERED BEST FIT SOLUTIONS 2 2 GE Dresser

More information

PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR

PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR PARKING LOT CONTROLLER WITH LOGIC & MAIN CONTACTOR VPC-AA The VPC-AA Parking Lot Controller is an easily installed device designed for mid-sized parking lot installations. The weather proof design is ideal

More information

STEAM TURBINE BY-PASS AND STEAM CONDITIONING VALVE

STEAM TURBINE BY-PASS AND STEAM CONDITIONING VALVE STEAM TURBINE BY-PASS AND STEAM CONDITIONING VALVE Benefits Savings of up to US$ 200.000 per year in maintenance costs Production gains due to superior stability of the temperature control Operational

More information

Increasing competitiveness of CCGT plants in a dynamic market: An owner s approach

Increasing competitiveness of CCGT plants in a dynamic market: An owner s approach Increasing competitiveness of CCGT plants in a dynamic market: An owner s approach Dr. Artur Ulbrich, Andy Jones, Christian Schäferkordt, Stuart Simpson 8th International Gas Turbine Conference, Brussels

More information

AP1000 Plant Overview

AP1000 Plant Overview AP1000 Plant Overview Westinghouse IEEE Subcommittee on Qualification Tom Hayes Passive Plant Projects hayestp@westinghouse.com 1-412-374-4420 Slide 1 Westinghouse Passive Plants Meet Power Company Needs

More information

Harris IRT Enterprises Digital Resistance Tester Model XP

Harris IRT Enterprises Digital Resistance Tester Model XP Harris IRT Enterprises Digital Resistance Tester Model 5012-06XP Specifications & Dimensions 2 Theory of Operation 3 Operator Controls & Connectors 4 Test Connections 5 Calibration Procedure 6-7 Options

More information

Ignition Reliability in SGT-750 for Gas Blends at Arctic Conditions. Magnus Persson Combustion Expert / Distributed Generation / Sweden

Ignition Reliability in SGT-750 for Gas Blends at Arctic Conditions. Magnus Persson Combustion Expert / Distributed Generation / Sweden Ignition Reliability in SGT-750 for Gas Blends at Arctic Conditions Magnus Persson Combustion Expert / Distributed Generation / Sweden siemens.com/power-gas Table of content Objectives of the Project SGT-750

More information

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer (a) Purpose - This report

More information

ST Motor Profiler (STM32 PMSM FOC SDK) Tips and Tricks

ST Motor Profiler (STM32 PMSM FOC SDK) Tips and Tricks ST Motor Profiler (STM32 PMSM FOC SDK) Tips and Tricks ST Motor Profiler 2 What is the Motor Profiler tool? The Motor Profiler tool is a new algorithm able to automatically measure the electrical characteristics

More information

Beyond 60% - Pioneering H-class Efficiency with World Class Flexibility

Beyond 60% - Pioneering H-class Efficiency with World Class Flexibility SCC5-8000H / Irsching 4 Beyond 60% - Pioneering H-class Efficiency with World Class Flexibility Irsching General Manager for GT Power Plant Solutions Europe, Africa, Asia and Australia Siemens AG 2011.

More information

Re evaluation of Maximum Fuel Temperature

Re evaluation of Maximum Fuel Temperature IAEA Technical Meeting on on Re evaluation of Maximum Operating Temperatures and Accident Conditions for High Temperature Reactor Fuel and Structural Materials, 10 12 July 2012, Vienna, Austria Re evaluation

More information

(3) 2-Loop B&W PWR s Unit 1- Commissioned 7/5/1973 Unit 2- Commissioned 9/9/1974 Unit 3- Commissioned 12/16/ MW per unit for a total of 2880 MW

(3) 2-Loop B&W PWR s Unit 1- Commissioned 7/5/1973 Unit 2- Commissioned 9/9/1974 Unit 3- Commissioned 12/16/ MW per unit for a total of 2880 MW C. Edmond Allen - Steam Generator Project Mgr June 2017 (3) 2-Loop B&W PWR s Unit 1- Commissioned 7/5/1973 Unit 2- Commissioned 9/9/1974 Unit 3- Commissioned 12/16/74 960 MW per unit for a total of 2880

More information

Combustion and Boiler Performance Assessment of Kardia Power Plant

Combustion and Boiler Performance Assessment of Kardia Power Plant Combustion and Boiler Performance Assessment of Kardia Power Plant Dr. M. Michel, I. Tsolakidis DEBCO Final Conference Brussels, December 10, 2012 Thermal Calculation of the Boiler Boiler design 100%-Load

More information

Fabrication and Automation of Solvent less Packaging Machine

Fabrication and Automation of Solvent less Packaging Machine Fabrication and Automation of Solvent less Packaging Machine Masood Nazir*, Prof Rashmi Ranjan Das# * M.tech Student at School of Electrical Engineering, VIT University Vellore, Tamilnadu-632014 India

More information

Case Studies in Non-Nuclear Multiphase Flow Meters Well-Testing Applications in Alberta s Oil Sands, Niobrara, Bakken and Eagle Ford Basins

Case Studies in Non-Nuclear Multiphase Flow Meters Well-Testing Applications in Alberta s Oil Sands, Niobrara, Bakken and Eagle Ford Basins Case Studies in Non-Nuclear Multiphase Flow Meters Well-Testing Applications in Alberta s Oil Sands, Niobrara, Bakken and Eagle Ford Basins Ben Shani Agar Corporation Prepared for the Cost-Effective Well

More information

Asia Pacific Research Initiative for Sustainable Energy Systems 2011 (APRISES11)

Asia Pacific Research Initiative for Sustainable Energy Systems 2011 (APRISES11) Asia Pacific Research Initiative for Sustainable Energy Systems 2011 (APRISES11) Office of Naval Research Grant Award Number N0014-12-1-0496 Hydrogen Energy System Simulation Model for Grid Management

More information

ELECTRIC POWER RESEARCH INSITUTE (EPRI) 2011 CONDENSER TECHNOLOGY CONFERENCE AUGUST 3-4, 2011, CHICAGO, ILLINOIS

ELECTRIC POWER RESEARCH INSITUTE (EPRI) 2011 CONDENSER TECHNOLOGY CONFERENCE AUGUST 3-4, 2011, CHICAGO, ILLINOIS ELECTRIC POWER RESEARCH INSITUTE (EPRI) 2011 CONDENSER TECHNOLOGY CONFERENCE AUGUST 3-4, 2011, CHICAGO, ILLINOIS IMPORTANCE OF TEMPERATURE OF BYPASS STEAM ADMITTED INTO A STEAM SURFACE CONDENSER IN A COMBINED

More information

FLUID DYNAMICS TRANSIENT RESPONSE SIMULATION OF A VEHICLE EQUIPPED WITH A TURBOCHARGED DIESEL ENGINE USING GT-POWER

FLUID DYNAMICS TRANSIENT RESPONSE SIMULATION OF A VEHICLE EQUIPPED WITH A TURBOCHARGED DIESEL ENGINE USING GT-POWER GT-SUITE USERS CONFERENCE FRANKFURT, OCTOBER 20 TH 2003 FLUID DYNAMICS TRANSIENT RESPONSE SIMULATION OF A VEHICLE EQUIPPED WITH A TURBOCHARGED DIESEL ENGINE USING GT-POWER TEAM OF WORK: A. GALLONE, C.

More information

Main Steam Isolation Valves (MSIV) in Nuclear Power Plants with PWR

Main Steam Isolation Valves (MSIV) in Nuclear Power Plants with PWR Main Steam Isolation Valves (MSIV) in Nuclear Power Plants with PWR FD2 1 E 02/2000 1 Introduction As isolating valve in the main steam line of nuclear power stations different designs are known. Beside

More information

MSD: Case Studies D R. T A R E K A. T U T U N J I P H I L A D E L P H I A U N I V E R S I T Y, J O R D A N

MSD: Case Studies D R. T A R E K A. T U T U N J I P H I L A D E L P H I A U N I V E R S I T Y, J O R D A N MSD: Case Studies D R. T A R E K A. T U T U N J I P H I L A D E L P H I A U N I V E R S I T Y, J O R D A N 2 0 1 4 Outline Elements and design of mechatronic systems have been described in previous sections

More information

Control. Fuel Consumption and Emission Predictions Applications to a DP-FPSO Concept

Control. Fuel Consumption and Emission Predictions Applications to a DP-FPSO Concept Control Fuel Consumption and Emission Predictions Applications to a DP-FPSO Concept Albert Aalbers Marin October 17-18, 2006 Return to Session Directory MTS DP Conference 17/18 October 2006 Fuel consumption

More information

Top Mount Installation for DP Flowmeters in Steam Service

Top Mount Installation for DP Flowmeters in Steam Service 00870-0200-4809 July 2009 Page 1 Top Mount Installation for DP Flowmeters in Steam Service This paper discusses installation of Rosemount Annubar and Compact Primary Element products above the pipe in

More information

Qualification Testing of High Rate of Fire Gun Systems

Qualification Testing of High Rate of Fire Gun Systems Qualification Testing of High Rate of Fire Gun Systems Presented by: Dave Maher/Jim Talley Project Engineer Joint Strike Fighter Gun Systems General Dynamics Armament & Technical Products Burlington, Vermont

More information

Wyoming EORI 2nd Annual Wyoming CO2 Conference 5/29/08

Wyoming EORI 2nd Annual Wyoming CO2 Conference 5/29/08 Wyoming EORI 2nd Annual Wyoming CO2 Conference 5/29/08 The Beaver Creek Madison CO2 Project Spring 2008 Chuck Peterson Sr. Reservoir Engineering Advisor Beaver Creek Madison CO 2 Flood Project Overview

More information

3RW Soft Starters. General data. 6/4 Siemens LV

3RW Soft Starters. General data. 6/4 Siemens LV General data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of peaks Avoidance of mains voltage fluctuations during starting

More information

In-situ Testing Technique for On-Going Cable Aging Assessments at Oyster Creek

In-situ Testing Technique for On-Going Cable Aging Assessments at Oyster Creek In-situ Testing Technique for On-Going Cable Aging Assessments at Oyster Creek Presented by: Chad Kiger EMC Engineering Manager AMS Corporation ckiger@ams-corp.com Background Information Oyster Creek had

More information

MIRI Cooler System Design Update

MIRI Cooler System Design Update 1 MIRI Cooler System Design Update M. Petach, D. Durand, M. Michaelian, J. Raab, and E. Tward Northrop Grumman Aerospace Systems Redondo Beach, CA 90278 ABSTRACT The Mid InfraRed Instrument (MIRI) for

More information

Symbol Input rating Symbol 2 Three-phase, 200 ~ 230V N 4 Three-phase, 380 ~ 480V. None. Loader. Graphic. Loader

Symbol Input rating Symbol 2 Three-phase, 200 ~ 230V N 4 Three-phase, 380 ~ 480V. None. Loader. Graphic. Loader is7 Variable Frequency Drive / Inverter High Torque Performance and Precise VFD 3 phase 0.75~22kW(1~30HP), 200~230V 3 phase 0.75~160kW(1~250HP), 380~480V Constant torque / Variable torque dual rating Selectable

More information

Grid-Friendly Utility-Scale PV Plants

Grid-Friendly Utility-Scale PV Plants White Paper Grid-Friendly Utility-Scale PV Plants Mahesh Morjaria & Dmitriy Anichkov, First Solar, Tempe, Arizona, USA 13 August 2013 Table of Contents Introduction.... 3 Power Plant Controller Architecture...

More information

Integrated Vector-Type Pump Drive Product Group D and W

Integrated Vector-Type Pump Drive Product Group D and W Integrated Vector-Type Pump Drive Product Group D and W Integrated Vector-Type Pump Drive seepex has released a new integrated drive for its popular lines of MD and BW progressive cavity pumps. The drive

More information

CCHMP Comments on ConocoPhillips Incident Report For 10/22/10 Flaring Event

CCHMP Comments on ConocoPhillips Incident Report For 10/22/10 Flaring Event CCHMP Comments on ConocoPhillips Incident Report For 10/22/10 Flaring Event The following comments relate to reviewing ConocoPhillip s RCA report received on 12/21/10. 1. The report identified that operators

More information

Liquid Filtration Experience and Capabilities

Liquid Filtration Experience and Capabilities Liquid Filtration Experience and Capabilities Donaldson understands the need for new and unique liquid filtration technologies and solutions. We have a global infrastructure and technical expertise to

More information

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers

Summary of Revision, IEEE C , Guide for Breaker Failure Protection of Power Circuit Breakers Summary of Revision, IEEE C37.119-2016, Guide for Breaker Failure Protection of Power Circuit Breakers Kevin Donahoe GE Grid Solutions 2018 Texas A&M Protective Relaying Conference Agenda Introduction

More information

INTELLIGENT ENERGY MANAGEMENT IN A TWO POWER-BUS VEHICLE SYSTEM. DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited.

INTELLIGENT ENERGY MANAGEMENT IN A TWO POWER-BUS VEHICLE SYSTEM. DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. INTELLIGENT ENERGY MANAGEMENT IN A TWO POWER-BUS VEHICLE SYSTEM 1 Report Documentation Page Form Approved OMB No. 0704-0188 Public reporting burden for the collection of information is estimated to average

More information

*TATSUYA KUNISHI, HITOSHI MUTA, KEN MURAMATSU AND YUKI KAMEKO TOKYO CITY UNIVERSITY GRADUATE SCHOOL

*TATSUYA KUNISHI, HITOSHI MUTA, KEN MURAMATSU AND YUKI KAMEKO TOKYO CITY UNIVERSITY GRADUATE SCHOOL Methodology of Treatment of Multiple Failure Initiating Events for Seismic PRA (2)Success Criteria Analysis for Multiple Pipe Break Accidents of a PWR *TATSUYA KUNISHI, HITOSHI MUTA, KEN MURAMATSU AND

More information

Steam Generator Tube Inspection and Foreign Object Retrieval in Wolsong NPP

Steam Generator Tube Inspection and Foreign Object Retrieval in Wolsong NPP Steam Generator Tube Inspection and Foreign Object Retrieval in Wolsong NPP Lee, Jeong Uk ( jwlee357@khnp.co.kr ) Wolsong NPP1 Chemistry Dep t KOREA HYDRO & NUCLEAR POWER CO., LTD. South Korea Wolsong

More information

Contents 1) Vibration situation for CGC Large Steam Turbine 2) Root cause analysis and evaluation method 3) Countermeasure with result

Contents 1) Vibration situation for CGC Large Steam Turbine 2) Root cause analysis and evaluation method 3) Countermeasure with result Preface A Large Steam Turbine had been in operation for several years and this turbine experienced the wear damage of governor linkage. Then, measured the vibration velocity profile on Governor side pedestal

More information

Example application for an supply air control with recirculated air addition. HVAC Application Note 3

Example application for an supply air control with recirculated air addition. HVAC Application Note 3 Example application for an supply air control with recirculated air addition HVAC Application Note 3 Version 14.03.2007 2 General Copyright 2007 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved.

More information

Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve

Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve Aeroflow SCV Steam Control Steam Conditioning Turbine Bypass Valve High Performance in a Competitive Package ZERO Leak Technology Non-Binding Trim Design Quick, Easy Maintenance 5/1 Version 3 Product Information

More information

Whole Engine Integration

Whole Engine Integration Sub Project 1 Whole Engine Integration Andrew Rolt, Rolls-Royce plc. European Engine Technology Workshop Warsaw, SP1 Whole Engine Integration Introduction and Objectives Development of the four advanced

More information

The Practical Uses of Computational Fluid Dynamics Not Just a Pretty Picture

The Practical Uses of Computational Fluid Dynamics Not Just a Pretty Picture The Practical Uses of Computational Fluid Dynamics Not Just a Pretty Picture Presenter: William Osley Company: CALGAVIN Ltd Email: william.osley@calgavin.com Page 1 Contents: Introduction Case Study 1:

More information